Cutler Hammer, Div of Eaton Corp WMZ General Product Line Information

UL 489 DIN Rail Miniature Circuit Breakers WMZ Circuit Breakers Product Overview
UL 489 DIN Rail Miniature Circuit Breakers
WMZ Circuit Breakers
PRODUCT OVERVIEW
Optimum and Efficient Protection for Every Application
Product Overview
Optimum product quality, tested reliability and safety stand for best protection of personnel, installations and plant. Eaton’s WMZ DIN rail mountable circuit breaker is designed for use in branch service applications.
Powerful Offering for Machine and System Builders
The WMZ is available with C and D characteristics in accordance with ULT 489, CSAT C22.2 No.5; UL 1077, CSA C22.2 No.235 and IEC 60947-2.
Typical Applications
Feeder and Branch Circuit Protection
Convenience receptacle circuits (internal / external)
Motor control circuits
Load circuits leaving the equipment (external)
HACR equipment (heating, air conditioning, refrigeration)
(internal / external)
PLC I/O points
Computers
Power supplies
Control instrumentation
Relays
UPS
Power conditioners
Features
Complete range of UL 489 listed DIN rail mounted miniature
circuit breakers up to 40 ampere current rating
Standard ratings of 10 kAIC at 277/480 Vac
Select amperages available at 14 kAIC at 277/480 Vac and
10 kAIC at125 Vdc
Current limiting design provides fast short-circuit interruption
that reduces the let-through energy, which can damage the circuit
Suitable for branch circuit device protection
Thermal-magnetic overcurrent protection
Two levels of short-circuit protection, categorized by
C and D curves
Trip-free design — breaker can not be defeated by holding the
handle in the ON position
Captive screws cannot be lost
SWD (switching duty) — suitable for switching fluorescent
lighting loads (I
Fulfill UL 489, CSA C22.2 No.5 and also IEC 60947-2 Standard
For use in applications for which UL 1077 or
20A)
n
CSA C22.2 No.235 are also allowed
Field installable shunt trip and auxiliary switch subsequent
mounting
Separate version for ring-tongue connection (Type WMZT….T),
terminal screws can be removed (on both sides)
Module width of only 17.7 mm (per pole)
Contact Position Indicator (red / green)
Easy installation on DIN rail
Possibility for sealing the toggle in ON or OFF position
WMZ Complies with the Latest National and International Standards
Standards — Feeder and Branch Circuit Protection
UL 489
Standard for molded case circuit breakers (MCCB) for feeder and branch circuit protection.
Products meet the requirements of the National Electrical Code
®
(NEC®).
CSA C22.2 No.5
Standard for molded case circuit breakers (MCCB) for feeder and branch circuit protection (corresponds closely to UL 489 Standard).
Products meet the requirements of the Canadian Electrical Code (CEC).