IEC Contactors and Starters
1.2
Combination Motor Controllers Short-Circuit Ratings for UL 508 Type F Application
1
XTFC and XTFR Combination Motor Controllers (CMC), UL 508 Type F
1
Assembled Controller
1
Non-Reversing Reversing 240V 480/277V 600/347V
1
XTFC and XTFR Frame B MMP + Frame B Contactor
XTFCP16BB_ XTFRP16BB_ 0.1–0.16 2.2 65 65 50 Not required Not required
1
XTFCP25BB_ XTFRP25BB_ 0.16–0.25 3.5 65 65 50 Not required Not required
XTFCP40BB_ XTFRP40BB_ 0.25–0.4 5.6 65 65 50 Not required Not required
1
XTFCP63BB_ XTFRP63BB_ 0.4–0.63 8.82 65 65 50 Not required Not required
XTFC001BB_ XTFR001BB_ 0.63–1 14 65 65 50 Not required Not required
1
XTFC1P6BB_ XTFR1P6BB_ 1–1.6 22.4 65 65 50 Not required Not required
1
XTFC2P5BB_ XTFR2P5BB_ 1.6–2.5 35 65 65 50 Not required Not required
XTFC004BB_ XTFR004BB_ 2.5–4 56 65 65 50 Not required Not required
1
XTFC6P3BB_ XTFR6P3BB_ 4–6.3 88.2 65 65 50 Not required Not required
XTFC010BB_ XTFR010BB_ 6.3–10 140 65 65 50 Not required Not required
1
XTFC012BB_ XTFR012BB_ 8–12 168 65 65 50 Not required Not required
XTFC016BB_ — 10–16 224 50 50 — Not required Not required
1
XTFC and XTFR Frame B MMP + Frame C Contactor
1
XTFC016BC_ XTFR016BC_ 10–16 224 18 18 — Not required Not required
XTFC020BC_ XTFR020BC_ 16–20 280 18 18 — Not required Not required
1
XTFC025BC_ XTFR025BC_ 20–25 350 18 18 — Not required Not required
XTFC032BC_ XTFR032BC_ 25–32 448 18 18 — Not required Not required
1
XTFC and XTFR Frame D MMP + Frame C Contactor
1
XTFC016DC_ XTFR016DC_ 10–16 224 50 50 50 Not required Not required
XTFC025DC_ XTFR025DC_ 16–25 350 50 50 50 Not required Not required
1
XTFC032DC_ XTFR032DC_ 25–32 448 65 65 50 Not required Not required
XTFC and XTFR Frame D MMP + Frame D Contactor
1
XTFC040DD_ XTFR040DD_ 32–40 560 65 65 50 Not required Not required
XTFC050DD_ XTFR050DD_ 40–50 700 65 65 50 Not required Not required
1
XTFC058DD_ XTFR058DD_ 50–58 812 65 65 50 Not required Not required
1
XTFC063DD_ XTFR063DD_ 55–65 882 65 65 50 Not required Not required
Notes
1
1
Underscore (_) indicates magnetic coil suffix required. See Page V5-T1-204.
2
1
For UL 508 Type F applications, the combination motor controller assembly does not require a dedicated upstream protective device in the panel, thus a maximum rating is not required.
XT IEC Power Control
1
FLA Adjustment
Range/Overload
Release—
(Amps)
I
r
Short-Circuit
Release—
(Amps)
I
rm
UL 508 Type F Application
Max. rms Symmetrical Short-Circuit
Ratings (kA)
Maximum Upstream
Protective Device (A)
Maximum Fuse
600V
2
Maximum Circuit
Breaker 600V
1
1
1
1
1
1
1
1
1