Page 1
Technical Data TD01203013E
Effective March 2011
Supersedes February 2010
F-Frame circuit breaker
10–225 amperes
Product description
•
AllofEaton’sF-Framecircuitbreakersare
HACRrated
•
AllF-Framethermal-magneticcircuitbreakers
10–50AaresuitableforHID(highintensity
discharge)use
•
AllF-Framecircuitbreakersaresuitablefor
reversefeeduse
Table 1. Frame Trip Ratings
Frame Ampere Rating
EDB, EDS, EDH, EDC 100–225
EHD 10–100
FDB 10–150
ED, HFD, FDC, HFDDC 15–225
FD 15–225
FDE, HFDE, FDCE
The 80A FDE, HFDE, FDCE is adjustable from 15–80A.
The 160A FDE, HFDE, FDCE is adjustable from 60–160A.
The 225A FDE, HFDE, FDCE is adjustable from 100–225A.
80, 160, 225
Page 2
TechnicalData TD01203013E
F-Frame circuit breaker
Effective March 2011
Table 2. ULT 489 Interrupting Capacity Ratings
Interrupting Capacity (Symmetrical Amperes)
Circuit
Breaker Type
EDB
EDS
ED
EDH
d
EDC
EHD 1
Number
of Poles Trip Type
2, 3
T/M N.I.T. 22,000
2, 3
2, 3
T/M N.I.T. 65,000
2, 3
2, 3
T/M N.I.T. —
2, 3
Volts AC (50/60 Hz) Volts DC
240 277 480 600 125 250
42,000
100,000
200,000
18,000
—
—
—
—
—
14,000
—
—
—
—
—
—
—
14,000
—
—
—
—
—
—
—
10,000
10,000
10,000
10,000
10,000
10,000
—
—
—
—
—
—
—
10,000
FDB 2, 3, 4 T/M N.I.T. 18,000 — 14,000 14,000 — 10,000
FD 1
2, 3, 4
HFD 1
2, 3, 4
d
FDC
e
HFDDC
FDE
HFDE
d
FDCE
N.I.T. is non-interchangeable trip unit. T/M is thermal-magnetic. For DC applications, magnetics are approximately 40% higher.
b
Two-pole circuit breaker, or two poles of three-pole circuit breaker.
c
Time constant is 3 milliseconds minimum at 10 kA and 8 milliseconds minimum at 22 kA.
d
Current limiting.
e
HFDDC is UL only and is not tested to other standards.
f
Interrupting rating is 42,000A at 600 Vdc with three-poles in series.
2, 3, 4 T/M N.I.T. 200,000 — 100,000 35,000 — 22,000
3 T/M N.I.T. — — — — — 50,000
3
3
3
T/M N.I.T. —
T/M N.I.T. —
Electronic N.I.T.
Electronic N.I.T.
Electronic N.I.T.
65,000
100,000
65,000
100,000
200,000
35,000
—
65,000
—
—
—
—
—
35,000
—
65,000
35,000
65,000
100,000
—
18,000
—
25,000
18,000
25,000
25,000
10,000
—
10,000
—
—
—
—
—
10,000
—
22,000
—
—
—
bc
f
Table 3. Line and Load Terminals
Maximum Breaker
Amperes
Terminal Body
Material
Wire
Type
Standard Pressure Type Terminals
20 (EHD)
100
150
225
Steel
Steel
Aluminum
Aluminum
Cu/Al
Cu/Al
Cu/Al
Cu/Al
Optional Pressure Terminals
50
100
225
UL listed for use with copper or aluminum conductors as noted.
b
Use only on 175–225A. Includes terminal shield and increases height.
Aluminum
Aluminum
Aluminum
Cu/Al
Cu/Al
Cu/Al
Table 4. Approximate Shipping Weight in Lbs (kg)
Circuit
Breaker Type
Number of Poles
1 2 3 4
ED, EDB, EDS, EDH, EDC — 3 (1.4) 4.5 (2.0) —
EHD, FDB, FD, HFD, HFDDC, FDC 2 (0.9) 3 (1.4) 4.5 (2.0) 6 (2.7)
FDE, HFDE, FDCE — — 4.2 (1.9) —
AWG Wire
Range
(1) #14–#10
(1) #14–1/0
(1) #4–4/0
(1) #4–4/0
(1) #14–#4
(1) #14–1/0
(1) #6–300 kcmil
Metric Wire
Range (mm
2.5–4
2.5–50
25–95
25–95
2.5–16
2.5–50
16–150
2
)
Catalog Number
(Package of 3 Terminals)
3T20FB
3T100FB
3TA150FB
3TA225FD
3TA50FB
3TA100FD
3TA225FDK
b
Table 5. Dimensions in Inches (mm)
Number of Poles
Dimensions
1 2 3 4
Height 6.00 (152.4) 6.00 (152.4) 6.00 (152.4) 6.00 (152.4)
Width 1.38 (34.8) 2.75 (69.9) 4.13 (104.8) 5.50 (139.7)
Depth 3.38 (85.7) 3.38 (85.7) 3.38 (85.7) 3.38 (85.7)
2
EATON CORPORATION www.eaton.com
Page 3
F-Frame circuit breaker
Dimensions in inches (mm)
4.12
(104.7)
TechnicalData TD01203013E
Effective March 2011
6.00
(152.4)
1.38
(34.8)
6.00
(152.4)
Figure 1. Single-Pole F-Frame Breaker
4.12
(104.7)
3.38
(85.7)
3.38
(85.7)
Figure 3. Three-Pole F-Frame Breaker
4.13
(104.8)
4.12
(104.7)
6.00
(152.4)
2.75
(69.9)
6.00
(152.4)
Figure 2. Two-Pole F-Frame Breaker
ote: N Forcurvesandadditionaltechnicalinformation,pleasevisitourWebsiteatwww.eaton.com.
3.38
(85.7)
(85.7)
Figure 4. Four-Pole F-Frame Breaker
3.38
5.50
(139.7)
EATON CORPORATION www.eaton.com
4.12
(104.7)
3
Page 4
TechnicalData TD01203013E
Effective March 2011
F-Frame circuit breaker
Front View
1.56
(39.7)
0.38
1.41
(35.7)
2.72
(69.1)
0.09(2.3) R
(Typ.)
4-PLC’S.
0.17
(4.4)
0.02 (.4)
0.69
(17.5)
0.50
(12.7)
1.56
(39.7)
(9.5)
Push to trip
Line End
0.19 R
0.75
(4.8 R)
(19.1)
4.50
(114.3)
0.75
(19.1)
Load End
Reproduced from drawings 1490D61 and 1490D65
1.38
(34.9)
On
Off
0.74
(18.8)
0.45 (11.4) diameter 2 holes
1.03
(26.2)
0.82
(20.8)
0.16 R
(4.1 R)
4.00
(101.6)
0.34
(8.7)
0.02 (.4)
1.00
(25.4)
0.74
(18.8)
0.11 (2.8) diameter x 0.31 (7.9)
deep, 1 hole accept #6 (M3.5)
thread cutting screws
Breaker
status
Dimensions
AB
On 3.07 (78.0) 2.92 (74.2) 3.96 (100.6) 3.40 (86.4) 3.33 (84.6) 8
Tripped 2.65 (67.3) 2.57 (65.3) 4.06 (103.1) 2.99 (75.9) 2.98 (75.7) 3
Off 2.08 (52.8) 2.14 (54.4) 4.12 (104.7) 2.42 (61.5) 2.56 (65.0) 9
Reset 1.98 (50.3) 2.05 (52.1) 4.11 (104.4) 2.30 (58.4) 2.48 (63.1) 10
Measured 0.125 (3.175) above Escutcheon.
Applied by breaker handle to external handle mechanism.
Dimensions in parentheses in millimeters
Side View
Handle: 0.34 (8.7) wide
x 0.38 (9.5) thick
0˚ taper, load end
7˚ taper, line end
2.35 (59.7) R
EDBA
To top of clip
0.50 (12.7) wide
conductor with
0.22 (5.6) diameter
hole
0.09 R
(2.4) R
0.08
(19.8)
2.22 (56.4)
2.94 (74.6)
3.19 (81.0)
3.38 (85.7)
3.50 (88.9)
C
CD
1.77
(44.8)
0.75
(19.1)
0.08
(2.0)
0.22 (5.6)
0.19 (4.8)
1.25
(31.8)
E
0.50 (12.7) wide conductor
with 0.22 (5.6) diameter hole
0.47
0.63
(11.9)
0.27
(15.9)
(6.8)
1.13
(28.6)
53˚
2.38
0.31
(60.3)
(8.0)
0.27 (6.8)
0.25 (6.4)
0.75 (19.1)
0.06 (1.6)
Handle
force, lbs.
3.00
(76.2)
0.44
(11.1)
(11.9)
0.47
6.00
(152.4)
Trough for
attachment
leads
Figure 5. Type FD Single-Pole Outline
4
EATON CORPORATION www.eaton.com
Page 5
F-Frame circuit breaker
TechnicalData TD01203013E
Effective March 2011
Front Cover Cutout
Line End
2.31
(58.8)
Breaker
handle
1.91
(48.4)
0.19 (4.8)
Diameter
Load End
Location of 0.50 (12.7) diameter
megger holes, if required
1.19 (30.2)
0.59
(15.1)
0.25 (6.4) R
2.91
(73.8)
0.58
14.8)
Drilling Plans
Front Connected Rear Connected
0.75
Line End
Load End
Breaker
handle
1.38
(34.9)
0.164-32 (M4 x 0.7) tap, 2 holes
0.69
(17.5)
2.88
(73.0)
(19.1)
(114.3)
4.50
Line End
Load End
0.44 (11.1) diameter holes for 15 to 100A
0.56 (14.3) diameter holes for 125 to 150A
Breaker
handle
0.47
(11.9)
3.16
(73.0)
5.06
(114.3)
Figure 6. Type FD Single-Pole Outline Drilling Plans
EATON CORPORATION www.eaton.com
5
Page 6
TechnicalDataTD01203013E
Effective March 2011
F-Frame circuit breaker
Front View
Line End
0.75
0.19 R
(19.1)
(4.8 R)
4.50
(114.3)
0.75
(19.1)
1.56
(39.7)
1.41
(35.7)
2.72
(69.1)
0.17
(4.4)
0.38
(9.5)
Push to trip
1.38
(34.9)
On
Off
1.33 (33.7)
0.38
(9.5)
0.16
(4.0) R
0.74
(18.8)
(11.4) diameter
0.45
4 holes
0.11
(2.8) diameter x .31 (7.9)
deep, 2 holes accept #6 (M3.5)
thread cutting screws
0.82
(20.8)
1.03
(26.2)
0.13
0.48
1.72
3 holes accept #8 (M4)
(43.7)
thread cutting screws
0.34
(8.7)
4.00
(101.6)
0.38
(9.5)
(3.2) diameter x
(12.3) deep,
Side View
0.13 (3.2) x 0.75 (19.1) slots
for attachment leads
2.35 (59.7) R
E D B A
0.75
(19.1)
0.08
(2.0)
0.09 R
(2.4) R
1.77
(44.8)
(31.8)
0.19
(4.8)
1.25
0.50 (12.7) wide conductor
with 0.22 (5.6) diameter hole
[0.26 (6.6) diameter hole
≥ 175A]
0.63
(15.9)
0.27
(6.8)
0.47
1.13
(28.6)
(11.9)
53˚
0.22 (5.6)
0.47
0.19
(11.9)
0.31
(8.0)
2.38
(60.3)
(4.8)
3.00
(76.2)
0.50
(12.7)
3.38
(85.7)
Trough for
attachment
leads
6.00
(152.4)
2.75
(69.9)
(25.4)
0.74
(18.8)
0.69
(17.5)
1.00
(2.3) R
0.02
(0.4)
0.69
(17.5)
0.09
(Typ.)
4-PLC’S.
Load End
Reproduced from drawings 1490D62 and 1490D66
0.50
(12.7)
1.56
(39.7)
1.38
(34.9)
Figure 7. Type FD Two-Pole Outline
0.02
(0.4)
0.20
(5.0) diameter hole
0.33
(8.3) diameter c‘bore
1.94
(49.2) deep from top
0.34
(8.7) diameter c‘bore
0.66
(16.7) deep from bottom
2 mounting holes for
0.164-32 [#8] (M4 x 0.7) x
1.50
(38.1)
mounting screws
Breaker
status
On 3.07 (78.0) 2.92 (74.2) 3.96 (100.6) 3.40 (86.4) 3.33 (84.6) 12
Tripped 2.65 (67.3) 2.57 (65.3) 4.06 (103.1) 2.99 (75.9) 2.98 (75.7) 4
Off 2.08 (52.8) 2.14 (54.4) 4.12 (104.7) 2.42 (61.5) 2.56 (65.0) 15
Reset 1.98 (50.3) 2.05 (52.1) 4.11 (104.4) 2.30 (58.4) 2.48 (63.1)
Measured 0.13 (3.18) above Escutcheon.
Applied by breaker handle to external handle mechanism.
Dimensions in parentheses in millimeters
Handle:
0.34 (8.7) wide x
0.38 (9.5) thick
0˚ taper, load end
7˚ taper, line end
To top of clip
0.50 (12.7) wide
conductor with
0.22 (5.6)
diameter hole
[0.25 (6.4) diameter hole ≥ 175A]
Dimensions
B
0.27 (6.8)
0.08
(19.8)
2.22 (56.4)
2.94 (74.6)
3.19 (81.0)
3.38 (85.7)
3.50 (88.9)
C
C
D
0.25 (6.4)
0.75 (19.1)
0.06 (1.6)
Handle
force, lbs.
0.47
(11.9)
20
6
EATON CORPORATION www.eaton.com
Page 7
F-Frame circuit breaker
TechnicalData TD01203013E
Effective March 2011
Front Cover Cutout
Line End
2.31
(58.8)
Breaker
handle
1.91
(48.4)
1.19
(30.2)
0.19 (4.8)
diameter
Location of 0.50 (12.7)
diameter megger holes,
if required
1.38
(34.9)
0.25 (6.4) R
2.91
(73.8)
0.59
(15.1)
0.58
(14.8)
Drilling Plans
Front Connected
Line End
Load End
Figure 8. Type FD Two-Pole Outline Drilling Plans
Breaker
handle
0.69
(17.5)
0.75
(19.1)
2.88
(73.0)
4.50
(114.3)
0.164-3 2 (M4 x 0.7) tap,
2 holes
Rear Connected
Line End
Load End Load End
0.44 (11.1) diameter holes for 15 to 100A
0.56 (14.3) diameter holes for 125 to 150A
Breaker
handle
1.38
(34.9)
0.47
(11.9)
3.16
(80.2)
5.06
(128.6)
EATON CORPORATION www.eaton.com
7
Page 8
TechnicalDataTD01203013E
Effective March 2011
F-Frame circuit breaker
Front View
1.56
(39.7)
0.20 (5.0) diameter hole
0.33 (8.3) diameter c'bore
1.94 (49.2) deep from top.
0.34 (8.7) diameter c'bore
0.66 (16.7) deep from bottom.
4 munting holes for .164-32
(No. 8) x 1.50 (M4 x 0.7 x 38.1)
mounting screws.
Line End
0.75
(19.1)
(19.1)
Load End
Reproduced from drawings 1490D63 and 1490D67
(114.3)
0.75
0.19 (4.8)R
1.41
(35.7)
4.50
0.09 (2.3) R
(Typ.)
4-PLC’S.
0.13 (3.2) x
0.48 (12.3) deep
6 holes
accept #8 (M4)
thread cutting
screws
1.72
(43.7)
0.17
(4.4)
0.38
(9.5)
0.02
(0.4)
1.56
(39.7)
0.38
(9.5)
(33.7)
2.06
(52.4)
0.50
(12.7)
0.38
(9.5)
(34.9)
1.33
1.38
Push to trip
(34.9)
(104.8)
1.38
4.13
On
Off
0.74
(18.8)
0.45 (11.4)
diameter
6 holes
0.11 (2.8) dia.
x 0.31 (7.9) deep,
2 holes accept
#6 (M3.5)
1.38
(34.9)
1.33
(33.7)
1.00
(25.4)
0.16 R
(4.0) R
0.69
(17.5)
thread cutting
screws
0.82
1.03
(20.8)
(26.2)
4.00
(101.6)
0.34
(8.7)
0.02
(0.4)
Breaker
status
On 3.07 (78.0) 2.92 (74.2) 3.96 (100.6) 3.40 (86.4) 3.33 (84.6) 14
Tripped 2.65 (67.3) 2.57 (65.3) 4.06 (103.1) 2.99 (75.9) 2.98 (75.7) 4
Off 2.08 (52.8) 2.14 (54.4) 4.12 (104.7) 2.42 (61.5) 2.56 (65.0) 16
0.74
(18.8)
Dimensions in parentheses in millimeters
Reset 1.98 (50.3) 2.05 (52.1) 4.11 (104.4) 2.30 (58.4) 2.48 (63.1) 21
Measured 0.13 (3.18) above Escutcheon.
Applied by breaker handle to external handle mechanism.
Side View
0.13 (3.2) x .75 (19.1) slots
for attachment leads
2.35 (59.7) R
E D B A
Handle:
0.34 (8.7) wide x
0.38 (9.5) thick
0˚ taper, load end
7˚ taper, line end
To top of clip
0.50 (12.7) wide
conductor with
0.22 (5.6)
diameter hole
[0.25 (6.4) diameter hole ≥ 175A]
Dimensions
B
1.77
(44.8)
0.75
(19.1)
0.08
(2.0)
0.09 R
(2.4) R
0.19
(4.8)
1.25
(31.8)
0.08
(19.8)
2.22 (56.4)
2.94 (74.6)
3.19 (81.0)
3.38 (85.7)
3.50 (88.9)
C
CD
0.50 (12.7) wide conductor
with 0.22 (5.6) diameter hole
[0.26 (6.6) diameter hole
≥ 175A]
0.63
0.27
(15.9)
(6.8)
0.47
(28.6)
(11.9)
53˚
0.22 (5.6)
0.47
0.31
(11.9)
(8.0)
0.27 (6.8)
0.25 (6.4)
0.75 (19.1)
0.06 (1.6)
2.38
(60.3)
(85.7)
1.13
3.00
(76.2)
0.50
(12.7)
0.19
(4.8)
Handle
force, lbs.
3.38
0.47
(11.9)
Trough for
attachment
leads
6.00
(152.4)
Figure 9. Type FD Three-Pole Outline
8
EATON CORPORATION www.eaton.com
Page 9
F-Frame circuit breaker
TechnicalData TD01203013E
Effective March 2011
Front Cover Cutout
Line End
2.31
(58.8)
Breaker
handle
1.91
(48.4)
1.19
(30.2)
1.38
(34.9)
Load End
Location of 0.50 (12.7) diameter
megger holes, if required
1.38
(34.9)
0.25
2.91
(73.8)
0.59
(15.1)
0.58
(14.8)
0.19 (4.8)
Diameter
Drilling Plans
Front Connected
Line End
Breaker
handle
0.69
(17.5)
Load End
1.38
(34.9)
0.75
(19.1)
2.88
(73.0)
4.50
(114.3)
0.164-32 (M4 x 0.7) tap,
4 holes
Rear Connected
Line End
0.44 (11.1) diameter holes for 15 to 100A
0.56 (14.3) diameter holes for 125 to 150A
Load End
Breaker
handle
2.75
(69.9)
1.38
(34.9)
0.47
(11.9)
3.16
(80.2)
5.06
(128.6)
Optional Ring Terminal Dimensions
0.73
(18.5)
Dia. 0.22 (<=160A)
0.27
(6.8)
(5.6)
0.25 (>160A)
(6.4)
Figure 10. Type FD Three-Pole Outline Drilling Plans
EATON CORPORATION www.eaton.com
9
Page 10
TechnicalDataTD01203013E
Effective March 2011
Front View
1.56
(39.7)
0.38
On
Off
Push to trip
1.38
(34.9)
(9.5)
1.38
(34.9)
1.33
(33.7)
5.50
(139.7)
1.00
(25.4)
0.74
(18.8)
0.69 (17.4)
1.38
(34.9)
Line End
0.75
(19.1)
(114.3)
0.75 (19.1)
Load End
Reproduced from drawings 1490D64 and 1490D68
1.41
(35.7)
2.72
(69.1)
4.50
0.09 (2.3)R
(Typ.)
4-PLCs
0.17
(4.4)
1.56
(39.7)
1.72
(43.7)
0.19 R
(4.8) R
0.38
(9.5)
(34.9)
0.38
(9.5)
1.33
(33.7)
0.02
(0.4)
2.06 (52.4)
0.50
(12.7)
1.38
(18.8)
1.38
(34.9)
0.16 (4.0) R
0.74
0.45 (11.4) diameter
8 holes
0.11 (2.8) diameter x
0.31 (7.9) deep, 4 holes
accept #6 (M3.5)
thread cutting screws
1.03
(26.2)
0.82
(20.8)
0.13 (.32) diameter x
0.49 (12.3) deep,
6 holes accept #8 (M4)
thread cutting screws
4.00
(101.6)
0.34
(8.7)
0.02
(0.4)
0.20 (5.0) dia hole
0.33 (8.3) dia c‘bore
1.94 (49.2) deep
from top
0.34 (8.7) dia c‘bore
0.66 (16.7) deep
from bottom
2 mounting holes for
0.164-32 [#8] (M4 x 0.7)
x 1.50 (38.1)
mounting screws
Breaker
status
On 3.07 (78.0) 2.92 (74.2) 3.96 (100.6) 3.40 (86.4) 3.33 (84.6) 14
Tripped 2.65 (67.3) 2.57 (65.3) 4.06 (103.1) 2.99 (75.9) 2.98 (75.7) 4
Off 2.08 (52.8) 2.14 (54.4) 4.12 (104.7) 2.42 (61.5) 2.56 (65.0) 16
Reset 1.98 (50.3) 2.05 (52.1) 4.11 (104.4) 2.30 (58.4) 2.48 (63.1) 21
Measured 0.13 (3.18) above Escutcheon.
Applied by breaker handle to external handle mechanism.
Dimensions in parentheses in millimeters
Side View
0.125 (3.18) x 0.750 (19.05) slots
for attachment leads
2.35 (59.7) R
E D B A
Handle:
0.34 (8.7) wide x
0.38 (9.5) thick
0˚ taper, load end
7˚ taper, line end
To top of clip
0.500 (12.70) wide
conductor with
0.219 (5.56)
diameter hole
[
0.250 (6.35) diameter hole ≥ 175A]
Dimensions
B C
0.08
(2.0)
0.08
(19.8)
2.22 (56.4)
2.94 (74.6)
3.19 (81.0)
3.38 (85.7)
3.50 (88.9)
C
D
1.77
(44.8)
0.75
(19.1)
0.09 R
(2.4) R
F-Frame circuit breaker
0.50 (12.7) wide conductor
with 0.22 (5.6) diameter hole
[
0.26 (6.6) diameter hole
≥ 175A]
0.63
0.27
(15.9)
(6.8)
0.47
1.13
(28.6)
0.19
(4.8)
1.25
(31.8)
53˚
0.22 (5.6)
0.47
0.31
(11.9)
(8.0)
0.27 (6.8)
0.25 (6.4)
0.75 (19.1)
0.06 (1.6)
(11.9)
0.19
(4.8)
2.38
(60.3)
Handle
force, lbs.
3.00
(76.2)
3.38
(85.7)
0.50
(12.7)
0.47
(11.9)
(152.4)
Trough for
attachment
leads
6.00
Figure 11. Type FD Four-Pole Outline
10
EATON CORPORATION www.eaton.com
Page 11
F-Frame circuit breaker
TechnicalData TD01203013E
Effective March 2011
Front Cover Cutout
Line End
2.31
(58.8)
Breaker
handle
0.59
1.91
(48.4)
Load End
(15.1)
1.19
(30.2)
1.38
(35.0)
Location of 0.50 (12.7)
diameter megger holes,
if required
1.38
(35.0)
0.25 (6.4) R
2.91
(73.8)
(35.0)
1.38
0.19 (4.8)
diameter
Drilling Plans
Front Connected Rear Connected
Line End
Breaker
handle
0.58
(14.8)
Load End
Figure 12. Type FD Four-Pole Outline Drilling Plans
1.38
(34.9)
2.75
(69.9)
0.164-32 (M4 x 0.7) tap,
6 holes
0.69
(17.5)
2.88
(73.0)
0.75
(19.1)
(114.3)
Line End
4.50
Load End
Breaker
handle
1.38
(34.9)
2.75
(69.9)
4.13
(104.8)
(11.1) diameter holes for 15 to 100A
0.44
0.56
(14.3) diameter holes for 125 to 150A
3.16
(80.2)
0.47
(11.9)
5.06
(128.6)
EATON CORPORATION www.eaton.com
11
Page 12
TechnicalData TD01203013E
Effective March 2011
F-Frame circuit breaker
Eaton Corporation
ElectricalSector
1111SuperiorAve.
Cleveland,OH44114
UnitedStates
877-ETN-CARE(877-386-2273)
Eaton.com
©2011EatonCorporation
AllRightsReserved
PrintedinUSA
PublicationNo.TD01203013E/Z10989
March2011
Eatonisaregisteredtrademark
ofEatonCorporation.
Allothertrademarksareproperty
oftheirrespectiveowners.