Technical Data TD01203013E
Effective March 2011 Supersedes February 2010
F-Frame circuit breaker 10–225 amperes
Product description
•
AllofEaton’sF-Framecircuitbreakersare HACRrated
•
AllF-Framethermal-magneticcircuitbreakers 10–50AaresuitableforHID(highintensity discharge)use
•
AllF-Framecircuitbreakersaresuitablefor reversefeeduse
Table 1. Frame Trip Ratings
Frame Ampere Rating
EDB, EDS, EDH, EDC 100–225 EHD 10–100 FDB 10–150 ED, HFD, FDC, HFDDC 15–225 FD 15–225 FDE, HFDE, FDCE
The 80A FDE, HFDE, FDCE is adjustable from 15–80A. The 160A FDE, HFDE, FDCE is adjustable from 60–160A. The 225A FDE, HFDE, FDCE is adjustable from 100–225A.
80, 160, 225
Page 2
TechnicalDataTD01203013E
F-Frame circuit breaker
Effective March 2011
Table 2. ULT 489 Interrupting Capacity Ratings
Interrupting Capacity (Symmetrical Amperes)
Circuit Breaker Type
EDB EDS
ED EDH
d
EDC EHD 1
Number of Poles Trip Type
2, 3
T/M N.I.T. 22,000
2, 3 2, 3
T/M N.I.T. 65,000 2, 3 2, 3
T/M N.I.T. — 2, 3
Volts AC (50/60 Hz) Volts DC
240 277 480 600 125 250
42,000
100,000 200,000
18,000
— —
— — —
14,000 —
— —
— — —
— 14,000
— —
— — —
— —
10,000 10,000
10,000 10,000 10,000
10,000 —
— —
— — —
— 10,000
FDB 2, 3, 4 T/M N.I.T. 18,000 14,000 14,000 10,000
FD 1
2, 3, 4
HFD 1
2, 3, 4
d
FDC
e
HFDDC
FDE HFDE
d
FDCE
N.I.T. is non-interchangeable trip unit. T/M is thermal-magnetic. For DC applications, magnetics are approximately 40% higher.
b
Two-pole circuit breaker, or two poles of three-pole circuit breaker.
c
Time constant is 3 milliseconds minimum at 10 kA and 8 milliseconds minimum at 22 kA.
d
Current limiting.
e
HFDDC is UL only and is not tested to other standards.
f
Interrupting rating is 42,000A at 600 Vdc with three-poles in series.
2, 3, 4 T/M N.I.T. 200,000 100,000 35,000 22,000 3 T/M N.I.T. 50,000 3
3 3
T/M N.I.T.
T/M N.I.T.
Electronic N.I.T.
Electronic N.I.T.
Electronic N.I.T.
65,000
100,000
65,000 100,000 200,000
35,000 —
65,000 —
— — —
— 35,000
— 65,000
35,000 65,000 100,000
— 18,000
— 25,000
18,000 25,000 25,000
10,000 —
10,000 —
— — —
— 10,000
— 22,000
— — —
bc
f
Table 3. Line and Load Terminals
Maximum Breaker Amperes
Terminal Body Material
Wire Type
Standard Pressure Type Terminals
20 (EHD) 100 150 225
Steel Steel Aluminum Aluminum
Cu/Al Cu/Al Cu/Al Cu/Al
Optional Pressure Terminals
50 100 225
UL listed for use with copper or aluminum conductors as noted.
b
Use only on 175–225A. Includes terminal shield and increases height.
Aluminum Aluminum Aluminum
Cu/Al Cu/Al Cu/Al
Table 4. Approximate Shipping Weight in Lbs (kg)
Circuit Breaker Type
Number of Poles
1 2 3 4
ED, EDB, EDS, EDH, EDC 3 (1.4) 4.5 (2.0) — EHD, FDB, FD, HFD, HFDDC, FDC 2 (0.9) 3 (1.4) 4.5 (2.0) 6 (2.7) FDE, HFDE, FDCE 4.2 (1.9)
AWG Wire Range
(1) #14–#10 (1) #14–1/0 (1) #4–4/0 (1) #4–4/0
(1) #14–#4 (1) #14–1/0 (1) #6–300 kcmil
Metric Wire Range (mm
2.5–4
2.5–50 25–95 25–95
2.5–16
2.5–50 16–150
2
)
Catalog Number (Package of 3 Terminals)
3T20FB 3T100FB 3TA150FB 3TA225FD
3TA50FB 3TA100FD 3TA225FDK
b
Table 5. Dimensions in Inches (mm)
Number of Poles
Dimensions
1 2 3 4
Height 6.00 (152.4) 6.00 (152.4) 6.00 (152.4) 6.00 (152.4) Width 1.38 (34.8) 2.75 (69.9) 4.13 (104.8) 5.50 (139.7) Depth 3.38 (85.7) 3.38 (85.7) 3.38 (85.7) 3.38 (85.7)
2
EATON CORPORATION www.eaton.com
Page 3
F-Frame circuit breaker
Dimensions in inches (mm)
4.12
(104.7)
TechnicalDataTD01203013E
Effective March 2011
6.00
(152.4)
1.38
(34.8)
6.00
(152.4)
Figure 1. Single-Pole F-Frame Breaker
4.12
(104.7)
3.38
(85.7)
3.38
(85.7)
Figure 3. Three-Pole F-Frame Breaker
4.13
(104.8)
4.12
(104.7)
6.00
(152.4)
2.75
(69.9)
6.00
(152.4)
Figure 2. Two-Pole F-Frame Breaker
ote:N Forcurvesandadditionaltechnicalinformation,pleasevisitourWebsiteatwww.eaton.com.
3.38
(85.7)
(85.7)
Figure 4. Four-Pole F-Frame Breaker
3.38
5.50
(139.7)
EATON CORPORATION www.eaton.com
4.12
(104.7)
3
Page 4
TechnicalDataTD01203013E
Effective March 2011
F-Frame circuit breaker
Front View
1.56
(39.7)
0.38
1.41
(35.7)
2.72
(69.1)
0.09(2.3) R (Typ.) 4-PLC’S.
0.17 (4.4)
0.02 (.4)
0.69
(17.5)
0.50
(12.7)
1.56
(39.7)
(9.5)
Push to trip
Line End
0.19 R
0.75
(4.8 R)
(19.1)
4.50
(114.3)
0.75
(19.1)
Load End
Reproduced from drawings 1490D61 and 1490D65
1.38
(34.9)
On Off
0.74
(18.8)
0.45 (11.4) diameter 2 holes
1.03
(26.2)
0.82
(20.8)
0.16 R (4.1 R)
4.00
(101.6)
0.34 (8.7)
0.02 (.4)
1.00
(25.4)
0.74
(18.8)
0.11 (2.8) diameter x 0.31 (7.9) deep, 1 hole accept #6 (M3.5) thread cutting screws
Breaker status
Dimensions
AB
On 3.07 (78.0) 2.92 (74.2) 3.96 (100.6) 3.40 (86.4) 3.33 (84.6) 8 Tripped 2.65 (67.3) 2.57 (65.3) 4.06 (103.1) 2.99 (75.9) 2.98 (75.7) 3 Off 2.08 (52.8) 2.14 (54.4) 4.12 (104.7) 2.42 (61.5) 2.56 (65.0) 9 Reset 1.98 (50.3) 2.05 (52.1) 4.11 (104.4) 2.30 (58.4) 2.48 (63.1) 10
Measured 0.125 (3.175) above Escutcheon.
Applied by breaker handle to external handle mechanism.
Dimensions in parentheses in millimeters
Side View
Handle: 0.34 (8.7) wide x 0.38 (9.5) thick 0˚ taper, load end 7˚ taper, line end
2.35 (59.7) R
EDBA
To top of clip
0.50 (12.7) wide conductor with
0.22 (5.6) diameter hole
0.09 R (2.4) R
0.08
(19.8)
2.22 (56.4)
2.94 (74.6)
3.19 (81.0)
3.38 (85.7)
3.50 (88.9)
C
CD
1.77
(44.8)
0.75
(19.1)
0.08 (2.0)
0.22 (5.6)
0.19 (4.8)
1.25
(31.8)
E
0.50 (12.7) wide conductor with 0.22 (5.6) diameter hole
0.47
0.63 (11.9)
0.27 (15.9)
(6.8)
1.13
(28.6)
53˚
2.38
0.31
(60.3)
(8.0)
0.27 (6.8)
0.25 (6.4)
0.75 (19.1)
0.06 (1.6)
Handle force, lbs.
3.00
(76.2)
0.44
(11.1)
(11.9)
0.47
6.00
(152.4)
Trough for attachment leads
Figure 5. Type FD Single-Pole Outline
4
EATON CORPORATION www.eaton.com
Page 5
F-Frame circuit breaker
TechnicalDataTD01203013E
Effective March 2011
Front Cover Cutout
Line End
2.31
(58.8)
Breaker handle
1.91
(48.4)
0.19 (4.8) Diameter
Load End
Location of 0.50 (12.7) diameter megger holes, if required
1.19 (30.2)
0.59
(15.1)
0.25 (6.4) R
2.91
(73.8)
0.58
14.8)
Drilling Plans
Front Connected Rear Connected
0.75
Line End
Load End
Breaker handle
1.38
(34.9)
0.164-32 (M4 x 0.7) tap, 2 holes
0.69
(17.5)
2.88
(73.0)
(19.1)
(114.3)
4.50
Line End
Load End
0.44 (11.1) diameter holes for 15 to 100A
0.56 (14.3) diameter holes for 125 to 150A
Breaker handle
0.47
(11.9)
3.16
(73.0)
5.06
(114.3)
Figure 6. Type FD Single-Pole Outline Drilling Plans
EATON CORPORATION www.eaton.com
5
Page 6
TechnicalDataTD01203013E
AE
Effective March 2011
F-Frame circuit breaker
Front View
Line End
0.75
0.19 R
(19.1)
(4.8 R)
4.50
(114.3)
0.75
(19.1)
1.56
(39.7)
1.41
(35.7)
2.72
(69.1)
0.17 (4.4)
0.38 (9.5)
Push to trip
1.38
(34.9)
On Off
1.33 (33.7)
0.38 (9.5)
0.16
(4.0) R
0.74
(18.8)
(11.4) diameter
0.45 4 holes
0.11
(2.8) diameter x .31 (7.9) deep, 2 holes accept #6 (M3.5) thread cutting screws
0.82
(20.8)
1.03
(26.2)
0.13
0.48
1.72
3 holes accept #8 (M4)
(43.7)
thread cutting screws
0.34 (8.7)
4.00
(101.6)
0.38 (9.5)
(3.2) diameter x (12.3) deep,
Side View
0.13 (3.2) x 0.75 (19.1) slots for attachment leads
2.35 (59.7) R
E D B A
0.75
(19.1)
0.08 (2.0)
0.09 R (2.4) R
1.77
(44.8)
(31.8)
0.19 (4.8)
1.25
0.50 (12.7) wide conductor with 0.22 (5.6) diameter hole [0.26 (6.6) diameter hole 175A]
0.63
(15.9)
0.27
(6.8)
0.47
1.13
(28.6)
(11.9)
53˚
0.22 (5.6)
0.47
0.19
(11.9)
0.31 (8.0)
2.38
(60.3)
(4.8)
3.00
(76.2)
0.50
(12.7)
3.38
(85.7)
Trough for attachment leads
6.00
(152.4)
2.75
(69.9)
(25.4)
0.74
(18.8)
0.69
(17.5)
1.00
(2.3) R
0.02 (0.4)
0.69
(17.5)
0.09 (Typ.) 4-PLC’S.
Load End
Reproduced from drawings 1490D62 and 1490D66
0.50
(12.7)
1.56
(39.7)
1.38
(34.9)
Figure 7. Type FD Two-Pole Outline
0.02
(0.4)
0.20
(5.0) diameter hole
0.33
(8.3) diameter c‘bore
1.94
(49.2) deep from top
0.34
(8.7) diameter c‘bore
0.66
(16.7) deep from bottom
2 mounting holes for
0.164-32 [#8] (M4 x 0.7) x
1.50
(38.1)
mounting screws
Breaker status
On 3.07 (78.0) 2.92 (74.2) 3.96 (100.6) 3.40 (86.4) 3.33 (84.6) 12 Tripped 2.65 (67.3) 2.57 (65.3) 4.06 (103.1) 2.99 (75.9) 2.98 (75.7) 4 Off 2.08 (52.8) 2.14 (54.4) 4.12 (104.7) 2.42 (61.5) 2.56 (65.0) 15 Reset 1.98 (50.3) 2.05 (52.1) 4.11 (104.4) 2.30 (58.4) 2.48 (63.1)
Measured 0.13 (3.18) above Escutcheon.
Applied by breaker handle to external handle mechanism.
Dimensions in parentheses in millimeters
Handle:
0.34 (8.7) wide x
0.38 (9.5) thick 0˚ taper, load end 7˚ taper, line end
To top of clip
0.50 (12.7) wide conductor with
0.22 (5.6) diameter hole [0.25 (6.4) diameter hole 175A]
Dimensions
B
0.27 (6.8)
0.08
(19.8)
2.22 (56.4)
2.94 (74.6)
3.19 (81.0)
3.38 (85.7)
3.50 (88.9)
C
C
D
0.25 (6.4)
0.75 (19.1)
0.06 (1.6)
Handle force, lbs.
0.47
(11.9)
20
6
EATON CORPORATION www.eaton.com
Page 7
F-Frame circuit breaker
TechnicalDataTD01203013E
Effective March 2011
Front Cover Cutout
Line End
2.31
(58.8)
Breaker handle
1.91
(48.4)
1.19
(30.2)
0.19 (4.8) diameter
Location of 0.50 (12.7) diameter megger holes, if required
1.38
(34.9)
0.25 (6.4) R
2.91
(73.8)
0.59
(15.1)
0.58
(14.8)
Drilling Plans
Front Connected
Line End
Load End
Figure 8. Type FD Two-Pole Outline Drilling Plans
Breaker handle
0.69
(17.5)
0.75
(19.1)
2.88
(73.0)
4.50
(114.3)
0.164-3 2 (M4 x 0.7) tap, 2 holes
Rear Connected
Line End
Load EndLoad End
0.44 (11.1) diameter holes for 15 to 100A
0.56 (14.3) diameter holes for 125 to 150A
Breaker handle
1.38
(34.9)
0.47
(11.9)
3.16
(80.2)
5.06
(128.6)
EATON CORPORATION www.eaton.com
7
Page 8
TechnicalDataTD01203013E
AE
Effective March 2011
F-Frame circuit breaker
Front View
1.56
(39.7)
0.20 (5.0) diameter hole
0.33 (8.3) diameter c'bore
1.94 (49.2) deep from top.
0.34 (8.7) diameter c'bore
0.66 (16.7) deep from bottom. 4 munting holes for .164-32 (No. 8) x 1.50 (M4 x 0.7 x 38.1) mounting screws.
Line End
0.75
(19.1)
(19.1)
Load End
Reproduced from drawings 1490D63 and 1490D67
(114.3)
0.75
0.19 (4.8)R
1.41
(35.7)
4.50
0.09 (2.3) R (Typ.) 4-PLC’S.
0.13 (3.2) x
0.48 (12.3) deep 6 holes accept #8 (M4) thread cutting screws
1.72
(43.7)
0.17 (4.4)
0.38 (9.5)
0.02
(0.4)
1.56
(39.7)
0.38 (9.5)
(33.7)
2.06
(52.4)
0.50
(12.7)
0.38 (9.5)
(34.9)
1.33
1.38
Push to trip
(34.9)
(104.8)
1.38
4.13
On Off
0.74
(18.8)
0.45 (11.4) diameter 6 holes
0.11 (2.8) dia. x 0.31 (7.9) deep, 2 holes accept #6 (M3.5)
1.38
(34.9)
1.33
(33.7)
1.00
(25.4)
0.16 R (4.0) R
0.69
(17.5)
thread cutting screws
0.82
1.03
(20.8)
(26.2)
4.00
(101.6)
0.34
(8.7)
0.02 (0.4)
Breaker status
On 3.07 (78.0) 2.92 (74.2) 3.96 (100.6) 3.40 (86.4) 3.33 (84.6) 14 Tripped 2.65 (67.3) 2.57 (65.3) 4.06 (103.1) 2.99 (75.9) 2.98 (75.7) 4 Off 2.08 (52.8) 2.14 (54.4) 4.12 (104.7) 2.42 (61.5) 2.56 (65.0) 16
0.74
(18.8)
Dimensions in parentheses in millimeters
Reset 1.98 (50.3) 2.05 (52.1) 4.11 (104.4) 2.30 (58.4) 2.48 (63.1) 21
Measured 0.13 (3.18) above Escutcheon.
Applied by breaker handle to external handle mechanism.
Side View
0.13 (3.2) x .75 (19.1) slots for attachment leads
2.35 (59.7) R
E D B A
Handle:
0.34 (8.7) wide x
0.38 (9.5) thick 0˚ taper, load end 7˚ taper, line end
To top of clip
0.50 (12.7) wide conductor with
0.22 (5.6) diameter hole [0.25 (6.4) diameter hole 175A]
Dimensions
B
1.77
(44.8)
0.75
(19.1)
0.08 (2.0)
0.09 R (2.4) R
0.19 (4.8)
1.25
(31.8)
0.08
(19.8)
2.22 (56.4)
2.94 (74.6)
3.19 (81.0)
3.38 (85.7)
3.50 (88.9)
C
CD
0.50 (12.7) wide conductor with 0.22 (5.6) diameter hole [0.26 (6.6) diameter hole 175A]
0.63
0.27
(15.9)
(6.8)
0.47 (28.6)
(11.9)
53˚
0.22 (5.6)
0.47
0.31 (11.9)
(8.0)
0.27 (6.8)
0.25 (6.4)
0.75 (19.1)
0.06 (1.6)
2.38
(60.3)
(85.7)
1.13
3.00
(76.2)
0.50
(12.7)
0.19 (4.8)
Handle force, lbs.
3.38
0.47
(11.9)
Trough for attachment leads
6.00
(152.4)
Figure 9. Type FD Three-Pole Outline
8
EATON CORPORATION www.eaton.com
Page 9
F-Frame circuit breaker
TechnicalDataTD01203013E
Effective March 2011
Front Cover Cutout
Line End
2.31
(58.8)
Breaker handle
1.91
(48.4)
1.19
(30.2)
1.38
(34.9)
Load End
Location of 0.50 (12.7) diameter megger holes, if required
1.38
(34.9)
0.25
2.91
(73.8)
0.59
(15.1)
0.58
(14.8)
0.19 (4.8) Diameter
Drilling Plans
Front Connected
Line End
Breaker handle
0.69
(17.5)
Load End
1.38
(34.9)
0.75
(19.1)
2.88
(73.0)
4.50
(114.3)
0.164-32 (M4 x 0.7) tap, 4 holes
Rear Connected
Line End
0.44 (11.1) diameter holes for 15 to 100A
0.56 (14.3) diameter holes for 125 to 150A
Load End
Breaker handle
2.75
(69.9)
1.38
(34.9)
0.47
(11.9)
3.16
(80.2)
5.06
(128.6)
Optional Ring Terminal Dimensions
0.73
(18.5)
Dia. 0.22 (<=160A)
0.27
(6.8)
(5.6)
0.25 (>160A) (6.4)
Figure 10. Type FD Three-Pole Outline Drilling Plans
EATON CORPORATION www.eaton.com
9
Page 10
TechnicalDataTD01203013E
AE
Effective March 2011
Front View
1.56
(39.7)
0.38
On Off
Push to trip
1.38
(34.9)
(9.5)
1.38
(34.9)
1.33
(33.7)
5.50
(139.7)
1.00
(25.4)
0.74
(18.8)
0.69 (17.4)
1.38
(34.9)
Line End
0.75
(19.1)
(114.3)
0.75 (19.1)
Load End
Reproduced from drawings 1490D64 and 1490D68
1.41
(35.7)
2.72
(69.1)
4.50
0.09 (2.3)R (Typ.) 4-PLCs
0.17
(4.4)
1.56
(39.7)
1.72
(43.7)
0.19 R (4.8) R
0.38 (9.5)
(34.9)
0.38
(9.5)
1.33
(33.7)
0.02 (0.4)
2.06 (52.4)
0.50
(12.7)
1.38
(18.8)
1.38
(34.9)
0.16 (4.0) R
0.74
0.45 (11.4) diameter 8 holes
0.11 (2.8) diameter x
0.31 (7.9) deep, 4 holes accept #6 (M3.5) thread cutting screws
1.03
(26.2)
0.82
(20.8)
0.13 (.32) diameter x
0.49 (12.3) deep, 6 holes accept #8 (M4) thread cutting screws
4.00
(101.6)
0.34 (8.7)
0.02 (0.4)
0.20 (5.0) dia hole
0.33 (8.3) dia c‘bore
1.94 (49.2) deep from top
0.34 (8.7) dia c‘bore
0.66 (16.7) deep from bottom 2 mounting holes for
0.164-32 [#8] (M4 x 0.7) x 1.50 (38.1) mounting screws
Breaker status
On 3.07 (78.0) 2.92 (74.2) 3.96 (100.6) 3.40 (86.4) 3.33 (84.6) 14 Tripped 2.65 (67.3) 2.57 (65.3) 4.06 (103.1) 2.99 (75.9) 2.98 (75.7) 4 Off 2.08 (52.8) 2.14 (54.4) 4.12 (104.7) 2.42 (61.5) 2.56 (65.0) 16 Reset 1.98 (50.3) 2.05 (52.1) 4.11 (104.4) 2.30 (58.4) 2.48 (63.1) 21
Measured 0.13 (3.18) above Escutcheon.
Applied by breaker handle to external handle mechanism.
Dimensions in parentheses in millimeters
Side View
0.125 (3.18) x 0.750 (19.05) slots for attachment leads
2.35 (59.7) R
E D B A
Handle:
0.34 (8.7) wide x
0.38 (9.5) thick 0˚ taper, load end 7˚ taper, line end
To top of clip
0.500 (12.70) wide conductor with
0.219 (5.56) diameter hole [
0.250 (6.35) diameter hole 175A]
Dimensions
B C
0.08 (2.0)
0.08
(19.8)
2.22 (56.4)
2.94 (74.6)
3.19 (81.0)
3.38 (85.7)
3.50 (88.9)
C
D
1.77
(44.8)
0.75
(19.1)
0.09 R (2.4) R
F-Frame circuit breaker
0.50 (12.7) wide conductor with 0.22 (5.6) diameter hole [
0.26 (6.6) diameter hole
175A]
0.63
0.27 (15.9)
(6.8)
0.47
1.13
(28.6)
0.19 (4.8)
1.25
(31.8)
53˚
0.22 (5.6)
0.47
0.31 (11.9)
(8.0)
0.27 (6.8)
0.25 (6.4)
0.75 (19.1)
0.06 (1.6)
(11.9)
0.19 (4.8)
2.38
(60.3)
Handle force, lbs.
3.00
(76.2)
3.38
(85.7)
0.50
(12.7)
0.47
(11.9)
(152.4)
Trough for attachment leads
6.00
Figure 11. Type FD Four-Pole Outline
10
EATON CORPORATION www.eaton.com
Page 11
F-Frame circuit breaker
TechnicalDataTD01203013E
Effective March 2011
Front Cover Cutout
Line End
2.31
(58.8)
Breaker handle
0.59
1.91
(48.4)
Load End
(15.1)
1.19
(30.2)
1.38
(35.0)
Location of 0.50 (12.7) diameter megger holes, if required
1.38
(35.0)
0.25 (6.4) R
2.91
(73.8)
(35.0)
1.38
0.19 (4.8) diameter
Drilling Plans
Front Connected Rear Connected
Line End
Breaker handle
0.58
(14.8)
Load End
Figure 12. Type FD Four-Pole Outline Drilling Plans
1.38
(34.9)
2.75
(69.9)
0.164-32 (M4 x 0.7) tap, 6 holes
0.69
(17.5)
2.88
(73.0)
0.75
(19.1)
(114.3)
Line End
4.50
Load End
Breaker handle
1.38
(34.9)
2.75
(69.9)
4.13
(104.8)
(11.1) diameter holes for 15 to 100A
0.44
0.56
(14.3) diameter holes for 125 to 150A
3.16
(80.2)
0.47
(11.9)
5.06
(128.6)
EATON CORPORATION www.eaton.com
11
Page 12
TechnicalDataTD01203013E
Effective March 2011
F-Frame circuit breaker
Eaton Corporation
ElectricalSector 1111SuperiorAve. Cleveland,OH44114 UnitedStates 877-ETN-CARE(877-386-2273) Eaton.com
©2011EatonCorporation AllRightsReserved PrintedinUSA PublicationNo.TD01203013E/Z10989 March2011
Eatonisaregisteredtrademark ofEatonCorporation.