Specications
Description Ratings
Surge current capacity per phase 50, 80, 100, 120, 160, 200, 250, 300 and 400 kA ratings available Nominal discharge current (In) 20 kA Short-circuit current rating (SCCR) 200 kA SPD type Basic Feature Package = Type 1 (can also be used in Type 2 applications)
Standard and Standard with Surge Counter Feature Packages = Type 2
System voltages available (Vac)
Single split-phase (three-wire plus ground) 120/240
Three-phase wye (four-wire plus ground) 120/208, 127/220, 230/400, 277/480, 347/600 Three-phase delta (three-wire plus ground) 240, 480, 600 Three-phase high leg delta (four-wire plus ground) 120/240 Input power frequency 50/60 Hz
Protection modes
Single split-phase L-N, L-G, L-L, N-G Three-phase wye L-N, L-G, L-L, N-G Three-phase delta L-G, L-L
Three-phase high leg delta L-N, L-G, L-L, N-G Operating temperature –40°C through 50°C (–40°F through 122°F) Operating humidity 5% through 95%, noncondensing Agency certifications and approvals UL 1449 3rd Edition listed device; CSA listed; UL 1283 (Type 2 SPDs only) Warranty 10 years (15 years when registered on www.eaton.com/spd)
SPD Series catalog number conguration for units mounted external to electrical distribution equipment
SPD 250 480D 2 K
Series
SPD = Surge
protective device
Example: SPD250480D2K = SPD Series, 250 kA per phase, 480D voltage, standard feature package, housed in NEMA 1 enclosure
A
Please consult the factory for 240 delta high leg (4W + G) applications with high leg on ‘C’ phase.
B
NEMA 1 flushmount units are available in 50–200 kA ratings only.
kA Rating
050 = 50 kA per phase 080 = 80 kA per phase 100 = 100 kA per phase 120 = 120 kA per phase 160 = 160 kA per phase 200 = 200 kA per phase 250 = 250 kA per phase 300 = 300 kA per phase 400 = 400 kA per phase
Voltage Code
240S = 120/240 single split-phase 208Y = 120/208 wye (4W + G) 220Y = 127/220 wye (4W + G) 400Y = 230/400 wye (4W + G) 480Y = 277/480 wye (4W + G) 600Y = 347/600 wye (4W + G) 240D = 240 delta (3W + G) 480D = 480 delta (3W + G) 600D = 600 delta (3W + G) 240H = 240 delta high leg (4W + G)
on 'B' phase
1
Feature Package
1 = Basic 2 = Standard 3 = Standard with
surge counter
Application—Sidemount Units
K = NEMA 1 enclosure L = NEMA 1 flushmount enclosure
2
M = NEMA 1 enclosure with internal disconnect N = NEMA 4 enclosure O = NEMA 4 enclosure with internal disconnect P = NEMA 4X enclosure (stainless steel) Q = NEMA 4X enclosure with internal disconnect
(stainless steel)
Eaton
1000 Eaton Boulevard Cleveland, OH 44122 USA Eaton.com
Eaton is a registered trademark of Eaton Corporation.
All other trademarks are property of their respective owners.