Cutler Hammer, Div of Eaton Corp SP1 Catalog Page

Eaton SP1
Surge Protective Device (SPD)
Reliable, Cost-Effective Surge Protection
Introduction
Eaton‘sT SP1 is a ULT 1449 3rd Edition-listed surge protective device that provides reliable, cost-effective surge protection. This Type 1 SPD is capable of being installed on either the line or load side of the service entrance disconnect and can be used as a replacement for devices formerly known as secondary surge arrestors or lightning arrestors, which could not be manufactured after UL 1449 3rd Edition went into effect on September 29, 2009. The unit is available in many common voltages and configurations. Multiple mounting options coupled with a compact footprint enables installation of the SP1 in a wide range of applications, including panel­boards, loadcenters, pump panels, control cabinets, and other electrical assemblies and applications.
Installation and Operation
Installation and operation of the SP1 is simple. The unit comes pre-wired with 24 inches of 10-gauge wire and is mounted via the ½" nipple that is molded into its enclosure. Wall or DIN­rail mounting can also be accom­plished with the addition of an optional kit. When powered, the unit‘s light-emitting diode (LED) indicator reports the status of the protection elements and is active when all of them are intact and providing protection. Any loss of protection is signaled when the LED extinguishes.
Features
Type 1 SPD capable of installation on either the line or load side of the service entrance disconnect
20 kA nominal discharge current rating (In) on most models
50 kA per phase surge current capacity
Compact footprint—
4.8"L x 2.9"W x 2.5"D
Pre-wired with 24 inches of 10-gauge wire
½" nipple molded into enclosure enables quick and easy mounting
Optional kit enables wall or DIN-rail mounting
2-year warranty
Standards and Certications
UL 1449 3rd Edition­listed device
Specifications
Description Ratings
Surge current capacity per phase 50 kA
Nominal discharge current (I
) 20 kA for SP1-240S, 208Y, 480Y,
n
240D and 480D
10 kA for SP1-600Y and 600D
Short-circuit current rating (SCCR) 200 kA
SPD type Type 1 (can also be used in Type 2 applications)
System voltages available (Vac)
Single split-phase 120/240
Three-phase wye 120/208, 277/480, 347/600
Three-phase delta 240, 480, 600
Protection modes
Single split-phase and three-phase wye L-N, L-L
Three-phase delta L-G, L-L
Maximum continuous operating voltage (MCOV)
SP1-240S and SP1-208Y 150 L-N, 300 L-L
SP1-480Y 320 L-N, 640 L-G
SP1-600Y 420 L-N, 840 L-G
SP1-240D 300 L-G, 300 L-L
SP1-480D 640 L-G, 640 L-L
SP1-600D 840 L-G, 840 L-L
Input power frequency 50/60 Hz
Enclosure rating NEMA 4
Operating temperature -20°C to 50°C (-4°F to 122°F)
Operating humidity 5–95%, noncondensing
Operating altitude Up to 16,000 ft (5000m) Agency certification and approvals UL 1449 3rd Edition listed device Warranty 2 years
ANSI/UL 1449 3rd Edition Voltage Protection Ratings
Protection Mode
Catalog Number
L-N L-G L-L
SP1-240S 600 N/A 1000
SP1-208Y 600 N/A 1000
SP1-480Y 1200 N/A 2000
SP1-600Y 1500 N/A 2500
SP1-240D N/A 1000 1000
SP1-480D N/A 2000 2000
SP1-600D N/A 2500 2500
SP1 Dimensions—inches (millimeters)
1/2" (12.7) Straight Pipe Thread
.79 (20.1)
3.95
(100.3)
2.89
(73.4)
SP1 Catalog Number Configuration
1.35
(34.3)
2.46
(62.5)
SP1 XXXX
Series
SP1-
SP1MNTGKIT = optional wall or DIN-rail mounting kit
(order separately—not included with SP1 unit)
240S = 120/240V single split-phase 208Y = 120/208 wye 480Y = 277/480 wye 600Y = 347/600Y wye 240D = 240 delta 480D = 480 delta 600D = 600 delta
Voltage Code
Technical Support Information
If you have any questions or need additional information, please contact the Eaton Technical Resource Center at 800-809-2772,
option 4, option 2. You may also submit inquiries via e-mail:
surgeprotection@eaton.com.