Cutler Hammer, Div of Eaton Corp Solid-State Controllers Features and Benefits

1.1
Features and Benefits
1
Run bypass mode greatly
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
reduces internal heating created by the power dissipation across the SCRs. The bypass contactor directly connects the motor to the line and improves system efficiency by reducing internal power losses
Less heat minimizes enclosure size and cooling requirements, and maximizes the life of all devices in the enclosure
LED displays device status and provides fault indication
Variable ramp times and voltage control (torque control) settings provide unlimited starting configurations, allowing for maximum application flexibility
Reduced Voltage Motor Starters
Solid-State Controllers
Soft stop control suits applications where an abrupt stop of the load is not acceptable. Soft acceleration and deceleration reduces wear on belts, gears, chains, clutches, shafts, and bearings
Minimizes the peak inrush current’s stress on the power system
Manages peak starting torque to diminish mechanical system wear and damage
24 Vdc control module enhances personnel and equipment safety
Protective Features
There are two auxiliary relays—
Mains connection— The mains connection is monitored for an open condition and/or undervoltage
Motor connection— The motor connection is monitored for an open condition
SCR faults—SCR performance is monitored during the ramp cycle for proper operation
First relay is a TOR relay which closes when the TOR is achieved (internal bypass relays close)
The second relay is a RUN relay which closes when the RUN signal is initiated and opens when RUN signal is removed. It remains closed during stop ramp time, if set to a value greater than 0. The RUN relay will also open if a fault occurs
Heat sink over/under temperature—High ambient temperatures, extended ramp times, and high duty cycle conditions may cause the DS6 to exceed its thermal rating. When temperature goes under –5°C, unit will trip as well. The DS6 is equipped with sensors that monitor the temperature of the device. The soft starter will trip in over/under temperature conditions, preventing device failure
Bypass relay—The DS6 can detect if the bypass relay fails to close after the ramp start or opens while the motor is running. The DS6 will trip on a bypass dropout fault if either of these conditions occur. The device does not start when bypass relay is closed and start signal is applied
24 Vdc low voltage— If the control voltage falls below 20 Vdc at any time during operation, the unit will fault
1
Standards and Certifications
1
1
1
IEC 60947-4-2
EN 60947-4-2
UL listed (E251034)
CSA certified
CE marked
C-Tick
1
1
1
Instructional Leaflets
1
Instruction Leaflet IL03901001E
1
1
1
1
1
1
Loading...