Cutler Hammer, Div of Eaton Corp Series G Technical Data

Application Paper AP01200007E
Effective December 2009
Application of tap rules to
molded case breaker terminals
Table 4. Breaker SCCR Ratings—Series G
UL Listed Interrupting Ratings (rms Symmetrical Amperes)
Continuous Ampere Rating at 40°C
Number of Poles Type of Trip
AC (kV) DC (kV)
240 480 600
125/250
EG-Frame
EGB 15–125 1 FT-FM, AT-FM 25 10
EGB 15–125 2, 3, 4 FT-FM, AT-FM 25 18 10
EGE 15–125 2, 3, 4 FT-FM, AT-FM 35 25 18 10
EGS 15–125 1 FT-FM, AT-FM 85 35
EGS 15–125 2, 3, 4 FT-FM, AT-FM 85 35 22 35
EGH 15–125 1 FT-FM, AT-FM 100 42
EGH 15–126 2, 3, 4 FT-FM, AT-FM 100 65 25 42
EGC 15–125 3, 4 FT-FM, AT-FM 200 100 35 42
JG-Frame
JGE 20–250 2, 3, 4 FT-AM, AT-AM, electronic 65 25 18 10
JGS 20–250 2, 3, 4 FT-AM, AT-AM, electronic 85 35 18 22
JGH 20–250 2, 3, 4 FT-AM, AT-AM, electronic 100 65 25 22
JGC 20–250 3, 4 FT-AM, AT-AM, electronic 200 100 35 42
JGU 20–250 3, 4 FT-AM, AT-AM, electronic 200 150 50 50
JGX 20–250 3, 4 FT-AM, AT-AM, electronic 200 200 50 50
LG-Frame
LGE 100–600 3, 4 FT-AM, AT-AM, electronic 65 35 18 22
LGS 100–600 3, 4 FT-AM, AT-AM, electronic 85 50 25 22
LGH 100–600 3, 4 FT-AM, AT-AM, electronic 100 65 35 42
LGC 100–600 3, 4 FT-AM, AT-AM, electronic 200 100 50 42
LGU 100–600 3, 4 FT-AM, AT-AM, electronic 200 150 65 50
LGX 100–600 3, 4 FT-AM, AT-AM, electronic 200 200 65 50
NG-Frame
NGS 400–1200 2, 3, 4 Electronic 65 50 25
NGH 400–1200 2, 3, 4 Electronic 100 65 35
NGC 400–1200 2, 3, 4 Electronic 200 100 50
NGS 400–1200 3 Electronic ————
NGU 400–800 3 Electronic 300 150 75
RG-Frame
RGH 800–2500 3, 4 Electronic 125 65 50
RGC 800–2500 3, 4 Electronic 200 100 65
EG breaker rated 600/347 Vac.
Two poles in series.
125 Vdc only for single-pole breakers.