Cutler Hammer, Div of Eaton Corp Series C Moulded Case Circuit Breakers Catalog Page

Page 1
Series C Moulded Case Circuit Breakers
70-600 Amperes L-Frame
Typical L-Frame Circuit Breaker
Product Description
All L-frame circuit breakers are HACR rated.
L-frame circuit breakers are available as individual components (Frame, Trip Unit, Terminals), or factory assembled complete breakers. OPTIM circuit breakers are available as factory assembled only.
L-frame circuit breakers are suitable for reverse feed use.
Technical Data and Specifications
CSA C22.2 No. 5 and UL489 Interrupting Capacity Ratings
Interrupting Capacity (RMS Symmetrical Amperes) (kA)
Circuit Breaker Type
LD CLD
HLD CHLD
LDC
CLDC
IEC 947-2 Interrupting Capacity Ratings
Circuit Breaker Type
LD 2, 3, 4 I
CLD
HLD 2, 3, 4 I
CHLD
LDC 2, 3, 4 I
CLDC
Number of Poles
2, 3, 4 2, 3, 4 2, 3, 4 2, 3, 4
2, 3, 4 2, 3, 4
Number of Poles
2, 3, 4 I
2, 3, 4 I
2, 3, 4 I
Volts Ac (50/60 Hz) Volts Dc
240 277 480 600 125 250
65 65 100 100
200 200
cu
I
cs
cu
I
cs
cu
I
cs
cu
I
cs
cu
I
cs
cu
I
cs
– – – –
– –
35 35 65 65
100 100
Interrupting Capacity (Symmetrical Amperes) (kA)
Volts Ac (50/60 Hz) Volts Dc
240 415 690 250
85 85
85 85
100 100
100 100
200 100
200 100
25 25 35 35
50 50
45 45
45 45
70 70
70 70
100 75
100 75
49
49
Section Page
➁➂
Number
– – – –
– –
22 – 25 –
30 –
L-4,5,7 L-5,9 L-4,5,7 L-5,9
L-4,5,8 L-5,10
49
49
49
49
49
49
Section
➁➂
20 10
20 10
25 13
25 13
35 18
35 18
20 10
– –
20 10
– –
20 10
– –
Page Number
L-4,5,7
L-5,9
L-4,5,7
L-5,9
L-4,5,8
L-5,10
49
49
49
49
49
49
49
Utilization category A circuit breakers.
L/R = 8 milliseconds minimum.
2-pole circuit breaker or two poles of 3-pole circuit breaker. Incorporating Thermal-Magnetic trip unit only.
100% rated breakers.
Current limiting.
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
Series C and Special Application Moulded Case Circuit Breakers
PG01200001K—October 2011
41
Page 2
Series C Moulded Case Circuit Breakers
70-600 Amperes L-Frame
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
L-Frame Digitrip Specifications
Trip Unit Type Digitrip RMS 310 Digitrip OPTIM 550 Digitrip OPTIM 1050
RMS Sensing Yes Yes Yes
Breaker Type
Frame L L L
Ampere Range 300-600A 200-600A 70-600A
Interrupting Rating @ 600V 25, 35, 50 (kA) 25, 35, 50 (kA) 25, 35, 50 (kA)
Protection
Ordering Options LS, LSG LSI, LSIG LSI, LSI(A), LSIG LSI(A), LSIG
Fixed Rated Plug (In) Yes Yes Yes Yes
Overtemperature Trip Yes Yes Yes Yes
Long Delay Protection (L)
Adjustable Rating Plug (I
Long Delay Pickup 0.5-1.0 (In)
Long Delay Time I
Long Delay Time I4t No No 1-5 Seconds 1-5 Seconds
Long Delay Thermal Memory Yes Yes Yes Yes
High Load Alarm No No 0.5-1.0 x I
Short Delay Protection (S)
Short Delay Pickup 200-800% x (In) 200-800% x (In) 150-800% x (Ir) 150-800% x (Ir)
Short Delay Time I2t 100 ms No 100-500 ms 100-500 ms
Short Delay Time Flat No Inst-300 ms 100-500 ms 100-500 ms
Short Delay Time Zone Selective Interlocking No No Yes
Instantaneous Protection (I)
Instantaneous Pickup No 200-800% x (In) 200-800% x (In) 200-800% x (In)
Discriminator No No Yes Yes
Instantaneous Override Yes Yes Yes Yes
Ground Fault Protection (G)
Ground Fault Alarm No No 20-100% x (Is) 20-100% x (Is)
Ground Fault Pickup 1-5 x 1g (120A) 1-5 x 1g (120A) 20-100% x (Is) 20-100% x (Is)
Ground Fault Delay I2t No No 100-500 ms 100-500 ms
Ground Fault Delay Flat Inst-500 ms Inst-500 ms 100-500 ms 100-500 ms
Ground Fault Zone Selective Interlocking No No Yes
Ground Fault Thermal Memory Yes Yes Yes Yes
System Diagnostics
Status LEDs Yes Yes Yes Yes
Cause of Trip LEDs No No Yes Yes
Magnitude of Trip Information No No Yes Yes
Remote Signal Contact – Ground Alarm Yes
Local Auxiliary and Bell Alarm Contact Optional Optional Optional Included
System Monitoring
Digital Display No No Yes
Current No No Yes Yes
Power and Energy No No No Yes
Power Quality-Harmonics No No No Yes
Power Factor No No No Yes
Communications
Eaton PowerNet No No Yes
Testing
Testing Method Test Set OPTIMizer, BIM, Eaton PowerNet
Adjust by rating plug.
By OPTIMizer/BIM.
Require Eaton PowerNet kit.
Require Zone interlock kit.
With separate ground fault alarm unit (GFAU).
) Yes Yes No No
n
2
t 12 Seconds 12 Seconds 2-24 Seconds 2-24 Seconds
Legend: BIM = Breaker Interface Module (A) = GF Alarm
0.5-1.0 (In)
Yes
0.4-1.0 x (In) 0.4-1.0 x (In)
r
Yes
➃➄
= Sensor Rating
I
s
= Rating Plug
I
n
Ir = Long Delay Pickup Setting
0.5-1.0 x I
Yes
Yes
Yes
Yes
Yes
r
42 Series C and Special Application Moulded Case Circuit Breakers
PG01200001K—October 2011
Page 3
Series C Moulded Case Circuit Breakers
70-600 Amperes L-Frame
Catalogue Numbering System
This information is presented only as an aid to understanding Catalogue numbers. It is not to be used to build Catalogue numbers for circuit breakers or trip units.
Thermal-Magnetic Trip Unit Catalogue NumberCircuit Breaker/Frame Catalogue Number
LD
3 600 F LT 3 400 T
Circuit
Breaker/
Frame Type
LD
HLD
LDC
CLD
CHLD
CLDC
“VISA option is available. CSA listed only.
Number
of Poles
2: 2 Poles 3: 3 Poles 4: 4 Poles
Circuit Breaker/Frame Ampere Rating
300 350 400 450 500 600
F: Frame Only WK: High Magnetic Moulded
V: 50°C (Thermal-Magnetic
FS: VISA - Frame only. SKW: VISA - High Magnetic
Suffix
Case Switch without terminals
Trip Units Only)
Moulded Case Switch without terminals
Trip Unit Type
LT:Thermal-
Magnetic
Number of Poles
2: 2 Poles 3: 3 Poles 4: 4 Poles
OPTIM Circuit Breaker/Frame Catalogue Number Digitrip RMS 310 Trip Unit Catalogue Number
Circuit
Breaker/
Frame
Type
LD HLD LDC CLD CHLD CLDC
Number of Poles
3: 3 Poles
LD
3 125 T5 7 W
Circuit
Breaker/
Frame
Ampere
Rating
125 (Available on Model 1050 only)
250 (Available on Model 1050 only)
400
600
Trip Model
T5 – Model 550
T10 – Model 1050
Trip Type
2 – LSI (550 only) 6 – LSIG 7 – LSIA
Suffix
W:Without Terminals
Trip Unit Type
LES:Electronic
LES
Number of
Poles
3: 3 Poles 4: 4 Poles
Trip Unit/
Rating Plug
Ampere
Rating
300 350 400 450 500 600
T: Trip Unit Thermal-Magnetic
TV: 50°C Calibration (Thermal-
3 600 LS P
Trip Unit
Ampere
Rating
600
Suffix
LS LSI LSG LSIG
Suffix
Fixed Thermal Adjustable Magnetic
Magnetic Trip Units Only)
Suffix
P: 100% Protected
Neutral on 4-Pole Trip Unit
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
Dimensions/Weights
Dimensions, Inches (mm)
Number of Poles Width Height Depth
2, 3 8.25
4 11
Approximate Shipping Weight, Lbs. (kg)
Complete Breaker Frame Only Trip Unit
Breaker Type
LD, HLD, LDC
Series C and Special Application Moulded Case Circuit Breakers
Number of Poles
234234234
18 (8.172)20(9.080)25(11.340)14(6.356)15(6.810)20(9.072)3(1.361)4(1.814)5(2.268)
(210)
(279)
10.75 (274)
10.75 (274)
PG01200001K—October 2011
4.062 (103)
4.062 (103)
49
49
49
49
49
49
49
49
49
43
Page 4
Series C Moulded Case Circuit Breakers
70-600 Amperes L-Frame
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
Product Selection
Types LD, HLD, and LDC Thermal-Magnetic Circuit Breakers with Interchangeable Trip Units
Standard Interrupting Capacity 600 Vac Rated 25 kAIC @600 Vac
Factory Assembled Circuit Breaker
Maximum Continuous Ampere Rating @ 40°C
2-Pole
300 350 400 450 500 600
3-Pole
300 350 400 450 500 600
4-Pole
300 350 400 450 500 600
Instruction Leaflet Number 29C105 for Breaker; 29C607 for Thermal Magnetic Trip Unit
Consisting of Frame, Trip Unit, and Terminals
Catalogue Number
LD2300 LD2350 LD2400 LD2450 LD2500 LD2600
LD3300 LD3350 LD3400 LD3450 LD3500 LD3600
LD4300 LD4350 LD4400 LD4450 LD4500 LD4600
Frame
Only
LD2600F HLD2300
LD3600F HLD3300
LD4600F HLD4300
High Interrupting Capacity 600 Vac Rated 35 kAIC @ 600 Vac
Factory Assembled Circuit Breaker Consisting of Frame, Trip Unit, and Terminals
HLD2350 HLD2400 HLD2450 HLD2500 HLD2600
HLD3350 HLD3400 HLD3450 HLD3500 HLD3600
HLD4350 HLD4400 HLD4450 HLD4500 HLD4600
Frame
Only
HLD2600F LDC2300
HLD3600F LDC3300
HLD4600F LDC4300
Ultra High Interrupting Capacity Current Limiting 600 Vac Rated 50 kAIC @ 600 Vac
Factory Assembled Circuit Breaker Consisting of Frame, Trip Unit, and Terminals
LDC2350 LDC2400 LDC2450 LDC2500 LDC2600
LDC3350 LDC3400 LDC3450 LDC3500 LDC3600
LDC4350 LDC4400 LDC4450 LDC4500 LDC4600
Frame Only
LDC2600F LT2300T
LDC3600F LT3300T
LDC4600F LT4300T
Thermal Magnetic Trip Unit Only
For Use With: Standard or High or Ultra High Interrupting Frames
Magnetic Trip Range is 5-10 x Continuous Ampere Rating
LT2350T LT2400T LT2450T LT2500T LT2600T
LT3350T LT3400T LT3450T LT3500T LT3600T
LT4350T LT4400T LT4450T LT4500T LT4600T
Standard Terminals Only
See Section Page Number L-11 for Optional Terminals
TA602LD TA602LD
TA602LD
TA602LD
TA602LD
2TA603LDK
TA602LD TA602LD TA602LD TA602LD TA602LD 3TA603LDK
TA602LD TA602LD TA602LD TA602LD TA602LD 4TA603LDK
➃ ➃ ➃ ➃ ➃
➃ ➃ ➃ ➃ ➃
49
49
49
49
49
49
49
49
49
49
49
49
49
When a “VISA” frame is required, add suffix “S” to circuit breaker frame catalogue number. LD and HLD only.
2-pole circuit breaker supplied in 3-pole frame.
Neutral is in right pole.
Individually packed.
Terminal kits contain one terminal for each pole and one terminal cover.
44 Series C and Special Application Moulded Case Circuit Breakers
PG01200001K—October 2011
Page 5
Series C Moulded Case Circuit Breakers
70-600 Amperes L-Frame
Types LD, HLD, and LDC Electronic Circuit Breakers with Interchangeable Trip Units
Order as individual components: Breaker Frame, Trip Unit, Rating Plug, Terminals.
Circuit Breaker Frame Only Digitrip RMS 310 Trip Unit Only Digitrip RMS 310 Rating Plug Only
L– Adjustable Long Delay Pickup (By Adjustable Rating Plug) S–Adjustable Short Delay Pickup with Fixed Short Delay
2
t Response) or Adjustable Short Delay Time (Flat
Time (I Response)
I– Adjustable Instantaneous Pickup by Setting Short Delay
Time to Instantaneous
G–Adjustable Ground Fault Pickup with Adjustable Ground
Fault Delay (Flat Response)
Ultra High
Standard Interrupting Capacity
Maximum Continuous Ampere Rating @ 40°C
3-Pole
600 LD3600F HLD3600F LDC3600F LES3600LS LES3600LSI LES3600LSG LES3600LSIG 300
4-Pole
600 LD4600F HLD4600F LDC4600F LES4600LS LES4600LSI 300
Instruction Leaflet Number 29C105 for Breaker; 29C615 for LES Trip Unit
600 Vac Rated 25 kAIC @ 600 Vac
Catalogue Number
High Interrupting Capacity 600 Vac Rated 35 kAIC @ 600 Vac
Interrupting Capacity Current Limiting 600 Vac Rated 50 kAIC @ 600 Vac
Standard Options
Independently Adjustable Short Delay Pickup with Fixed Short Delay Time
2
t Response)
(I
Adjustable
Short Delay
Pickup and
Short Delay
Time (Flat
Response)
Adjustable Short Delay Pickup with Fixed Short Delay Time (I Response) and Ground Fault Protection
2
Independently Adjustable Short Delay Pickup and
t
Short Delay Time (Flat Response) and Ground Fault Protection
Ampere Rating
350 400 450 500 600
350 400 450 500 600
Fixed Rating Plug
6LES300T 6LES350T 6LES400T 6LES450T 6LES500T 6LES600T
6LES300T 6LES350T 6LES400T 6LES450T 6LES500T 6LES600T
Adjustable Rating Plug
Ampere Rating Catalogue Number
300/400/500/600
A6LES600T1
420/440/460/480
A6LES400T5
520/540/560/580
A6LES500T5
300/400/500/600
A6LES600T1
420/440/460/480
A6LES400T5
520/540/560/580
A6LES500T5
100% Rated Types CLD, CHLD, and CLDC Electronic Circuit Breakers with Interchangeable Trip Units
The CEC allows the breaker to be rated at 100% of its frame size in an assembly, provided that 90°C wire is applied at the 75°C ampacity. All 100% rated circuit breakers have electronic trip units. Order as individual components: Breaker Frame, Trip Unit, Rating Plug and Terminals.
Circuit Breaker Frame Only Digitrip RMS 310 Trip Unit Only Digitrip RMS 310 Rating Plug Only
L– Adjustable Long Delay Pickup (By Adjustable Rating Plug) S– Adjustable Short Delay Pickup with Fixed Short Delay
2
Time (I I– Adjustable Instantaneous Pickup by Setting Short Delay
G– Adjustable Ground Fault Pickup with Adjustable Ground
Ultra High
Standard Interrupting Capacity
Maximum Continuous Ampere Rating @ 40°C
3-Pole
600 CLD3600F CHLD3600F CLDC3600F LES3600LS LES3600LSI LES3600LSG LES3600LSIG 300
Instruction Leaflet Number 29C105 for Breaker; 29C615 for LES Trip Unit
600 Vac Rated 25 kAIC @ 600 Vac
Catalogue Number
When a “VISA” frame is required, add suffix “S” to circuit breaker frame catalogue number. CLD & CHLD only.
For AC use only. Ampere rating is established by rating plug.
High Interrupting Capacity 600 Vac Rated 35 kAIC @ 600 Vac
Series C and Special Application Moulded Case Circuit Breakers
Interrupting Capacity Current Limiting 600 Vac Rated 50 kAIC @ 600 Vac
Standard Options
Adjustable Short Delay Pickup with Fixed Short Delay Time (I Response)
t Response) or Adjustable Short Delay Time (Flat Response)
Time to Instantaneous
Fault Delay (Flat Response)
Independently Adjustable Short Delay Pickup and
2
t
Short Delay Time (Flat Response)
Adjustable Short Delay Pickup with Fixed Short Delay Time (I Response) and Ground Fault Protection
2
t
3-pole LES Trip Units are for use in 3-pole frame only. Trip unit includes unprotected right neutral pole. For 100% protected right pole neutral, add “P” to
catalogue number. ie. LES4600LSP Individually packed. Terminal kits contain one terminal for each pole and one terminal cover.
PG01200001K—October 2011
Independently Adjustable Short Delay Pickup and Short Delay Time (Flat Response) and Ground Fault Protection
Ampere Rating
350 400 450 500 600
Fixed Rating Plug
6LES300T 6LES350T 6LES400T 6LES450T 6LES500T 6LES600T
Adjustable Rating Plug
Ampere Rating Catalogue Number
300/400/500/600
A6LES600T1
420/440/460/480
A6LES400T5
520/540/560/580
A6LES500T5
Standard Terminals Only
See Section Page Number L-11 for Optional Terminals
TA602LD TA602LD TA602LD TA602LD TA602LD 3TA603LDK
TA602LD TA602LD TA602LD TA602LD TA602LD 4TA603LDK
Standard Terminals Only
See Section Page Number L-11 for Optional Terminals
TA602LD TA602LD TA602LD TA602LD TA602LD 3TA603LDK
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
45
Page 6
Series C Moulded Case Circuit Breakers
70-600 Amperes L-Frame
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
Moulded Case Switches
Moulded case switches are used as compact switches in applications requiring high current switching capabilities. Moulded case switches are constructed of circuit breaker components and are of the high instantaneous automatic type. Moulded case switches are listed in accordance with CSA C22.2 No. 5 and UL 489, suitable for reverse feed use, and as 100% rated devices.
600 Vac Maximum, 250 Vdc Standard Terminals Only
Maximum Continuous Ampere Rating @ 40°C
2-Pole
600 LD2600WK HLD2600WK 2TA603LDK
3-Pole
600 LD3600WK HLD3600WK 3TA603LDK
4-Pole
600 LD4600WK HLD4600WK 4TA603LDK
Note: Note: Moulded Case Switch may trip above 6000 amperes.
Instruction Leaflet Number 29C105 for Moulded Case Switch
Moulded Case Switch Type
LD 2,3,4 65 35 25 22
HLD 2,3,4 100 65 35 25
MCS Only Without Line and Load Terminals
Catalogue Number
Number of Poles
Unfused Short Circuit Withstand Rating (Symmetrical Amperes) (kA)
Volts Ac (50/60 Hz) Volts DC
240 480 600 250
See Section Page Number L-11 for Optional Terminals
49
49
49
49
49
49
49
49
49
49
49
49
49
49
When a “VISA” type Moulded Case Switch is required, change the suffix of the MCS catalogue number from “WK” to “SKW”. ie. LD3600SKW
Terminal kits contain one terminal for each pole and one terminal cover.
46 Series C and Special Application Moulded Case Circuit Breakers PG01200001K—October 2011
Page 7
Series C Moulded Case Circuit Breakers
70-600 Amperes L-Frame
Digitrip OPTIM Electronic Circuit Breaker with Interchangeable Rating Plug
Order as individual components: Breaker Frame (which includes Trip Unit), Rating Plug, Terminals.
Circuit Breaker Frame Only
L – Adjustable Long Delay Pickup (I S – Adjustable Short Delay Pickup with Adjustable Short Delay Time (I2t or Flat Response) I – Adjustable Instantaneous Pickup G – Adjustable Ground Fault Pickup with Adjustable Ground Fault Time (I
Maximum Continuous Ampere Rating @ 40°C
3-Pole Standard Interrupting Capacity 600 Volt Ac Rated 25 kAIC @ 600 Vac
125 LD3125T52W LD3125T56W LD3125T57W LD3125T106W LD3125T107W 70
250 LD3250T52W LD3250T56W LD3250T57W LD3250T106W LD3250T107W 125
400 LD3400T52W LD3400T56W LD3400T57W LD3400T106W LD3400T107W 200
600 LD3600T52W LD3600T56W LD3600T57W LD3600T106W LD3600T107W 300
3-Pole High Interrupting Capacity 600 Volt Ac Rated 35 kAIC @ 600 Vac
125 HLD3125T52W HLD3125T56W HLD3125T57W HLD3125T106W HLD3125T107W 70
250 HLD3250T52W HLD3250T56W HLD3250T57W HLD3250T106W HLD3250T107W 125
400 HLD3400T52W HLD3400T56W HLD3400T57W HLD3400T106W HLD3400T107W 200
600 HLD3600T52W HLD3600T56W HLD3600T57W HLD3600T106W HLD3600T107W 300
Instruction Leaflet Number 29C105 for Breaker; 29C891 for OPTIM Trip Unit
A – Adjustable Ground Fault Alarm with Adjustable Ground Fault Time (I
OPTIM 550
LSI LSIG LSIA LSIG LSIA
Catalogue Number
OPTIM 1050 ➂➃
) with Adjustable Long Delay Time (I2t or I4t Response)
r
2
t or Flat Response)
2
t or Flat Response)
Digitrip OPTIM Rating Plug Only
Ampere Rating Fixed Rating Plug
ORPL125A070
90
ORPL125A090
100
ORPL125A100
110
ORPL125A110
125
ORPL125A125
ORPL025A125
150
ORPL025A150
175
ORPL025A175
200
ORPL025A200
225
ORPL025A225
250
ORPL025A250
ORPL40A200
225
ORPL40A225
250
ORPL40A250
300
ORPL40A300
350
ORPL40A350
400
ORPL40A400
ORPL60A300
350
ORPL60A350
400
ORPL60A400
500
ORPL60A500
600
ORPL60A600
ORPL125A070
90
ORPL125A090
100
ORPL125A100
110
ORPL125A110
125
ORPL125A125
ORPL025A125
150
ORPL025A150
175
ORPL025A175
200
ORPL025A200
225
ORPL025A225
250
ORPL025A250
ORPL40A200
225
ORPL40A225
250
ORPL40A250
300
ORPL40A300
350
ORPL40A350
400
ORPL40A400
ORPL60A300
350
ORPL60A350
400
ORPL60A400
500
ORPL60A500
600
ORPL60A600
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
Long delay I4t response selection limits short delay time to flat response.
Zone Interlocking, PowerNet, or both features can be added at the factory by adding Suffixes ZG, PN or ZGP respectively to above Catalogue Number. (A factory assembly charge will be applied, please refer to the Breaker Accessories/Modifications section in the MCCB Price List for details)
One Form C auxiliary switch and one Form C bell alarm switch supplied with breaker as standard on model 1050.
Factory sealed.
Series C and Special Application Moulded Case Circuit Breakers PG01200001K—October 2011 47
49
49
49
49
Page 8
Series C Moulded Case Circuit Breakers
70-600 Amperes L-Frame
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
Digitrip OPTIM Electronic Circuit Breaker with Interchangeable Rating Plug
Order as individual components: Breaker Frame (which includes Trip Unit), Rating Plug, Terminals.
Circuit Breaker Frame Only
L – Adjustable Long Delay Pickup (I S – Adjustable Short Delay Pickup with Adjustable Short Delay Time (I2t or Flat Response) I – Adjustable Instantaneous Pickup G – Adjustable Ground Fault Pickup with Adjustable Ground Fault Time (I
Maximum Continuous Ampere Rating @ 40°C
3-Pole Ultra High Interrupting Capacity Current Limiting 600 Volt Ac Rated 50 kAIC @ 600 Vac
125 LDC3125T52W LDC3125T56W LDC3125T57W LDC3125T106W LDC3125T107W 70
250 LDC3250T52W LDC3250T56W LDC3250T57W LDC3250T106W LDC3250T107W 125
400 LDC3400T52W LDC3400T56W LDC3400T57W LDC3400T106W LDC3400T107W 200
600 LDC3600T52W LDC3600T56W LDC3600T57W LDC3600T106W LDC3600T107W 300
Instruction Leaflet Number 29C105 for Breaker; 29C891 for OPTIM Trip Unit
A – Adjustable Ground Fault Alarm with Adjustable Ground Fault Time (I
OPTIM 550
LSI LSIG LSIA LSIG LSIA
Catalogue Number
OPTIM 1050 ➂➃
) with Adjustable Long Delay Time (I2t or I4t Response)
r
2
t or Flat Response)
2
t or Flat Response)
Digitrip OPTIM Rating Plug Only
Ampere Rating Fixed Rating Plug
ORPL125A070
90
ORPL125A090
100
ORPL125A100
110
ORPL125A110
125
ORPL125A125
ORPL025A125
150
ORPL025A150
175
ORPL025A175
200
ORPL025A200
225
ORPL025A225
250
ORPL025A250
ORPL40A200
225
ORPL40A225
250
ORPL40A250
300
ORPL40A300
350
ORPL40A350
400
ORPL40A400
ORPL60A300
350
ORPL60A350
400
ORPL60A400
500
ORPL60A500
600
ORPL60A600
49
49
49
49
49
49
49
49
49
49
49
49
49
Long delay I4t response selection limits short delay time to flat response.
Zone Interlocking, PowerNet, or both features can be added at the factory by adding Suffixes ZG, PN or ZGP respectively to above Catalogue Number.
One Form C auxiliary switch and one Form C bell alarm switch supplied with breaker as standard on model 1050.
Factory sealed.
48 Series C and Special Application Moulded Case Circuit Breakers PG01200001K—October 2011
Page 9
Series C Moulded Case Circuit Breakers
70-600 Amperes L-Frame
100% Rated Digitrip OPTIM Circuit Breakers with Interchangeable Rating Plug
Order as individual components: Breaker Frame (which includes Trip Unit), Rating Plug, Terminals.
Circuit Breaker Frame Only
L – Adjustable Long Delay Pickup (I S – Adjustable Short Delay Pickup with Adjustable Short Delay Time (I2t or Flat Response) I – Adjustable Instantaneous Pickup G – Adjustable Ground Fault Pickup with Adjustable Ground Fault Time (I
Maximum Continuous Ampere Rating @ 40°C
3-Pole Standard Interrupting Capacity 600 Volt Ac Rated 25 kAIC @ 600 Vac
125 CLD3125T52W CLD3125T56W CLD3125T57W CLD3125T106W CLD3125T107W 70
250 CLD3250T52W CLD3250T56W CLD3250T57W CLD3250T106W CLD3250T107W 125
400 CLD3400T52W CLD3400T56W CLD3400T57W CLD3400T106W CLD3400T107W 200
600 CLD3600T52W CLD3600T56W CLD3600T57W CLD3600T106W CLD3600T107W 300
3-Pole High Interrupting Capacity 600 Volt Ac Rated 35 kAIC @ 600 Vac
125 CHLD3125T52W CHLD3125T56W CHLD3125T57W CHLD3125T106W CHLD3125T107W 70
250 CHLD3250T52W CHLD3250T56W CHLD3250T57W CHLD3250T106W CHLD3250T107W 125
400 CHLD3400T52W CHLD3400T56W CHLD3400T57W CHLD3400T106W CHLD3400T107W 200
600 CHLD3600T52W CHLD3600T56W CHLD3600T57W CHLD3600T106W CHLD3600T107W 300
Instruction Leaflet Number 29C105 for Breaker; 29C891 for OPTIM Trip Unit
A – Adjustable Ground Fault Alarm with Adjustable Ground Fault Time (I
OPTIM 550
LSI LSIG LSIA LSIG LSIA
Catalogue Number
OPTIM 1050 ➂➃
) with Adjustable Long Delay Time (I2t or I4t Response)
r
2
t or Flat Response)
2
t or Flat Response)
Digitrip OPTIM Rating Plug Only
Ampere Rating Fixed Rating Plug
90 100 110 125
150 175 200 225 250
225 250 300 350 400
350 400 500 600
90 100 110 125
150 175 200 225 250
225 250 300 350 400
350 400 500 600
ORPL125A070 ORPL125A090 ORPL125A100 ORPL125A110 ORPL125A125
ORPL025A125 ORPL025A150 ORPL025A175 ORPL025A200 ORPL025A225 ORPL025A250
ORPL40A200 ORPL40A225 ORPL40A250 ORPL40A300 ORPL40A350 ORPL40A400
ORPL60A300 ORPL60A350 ORPL60A400 ORPL60A500 ORPL60A600
ORPL125A070 ORPL125A090 ORPL125A100 ORPL125A110 ORPL125A125
ORPL025A125 ORPL025A150 ORPL025A175 ORPL025A200 ORPL025A225 ORPL025A250
ORPL40A200 ORPL40A225 ORPL40A250 ORPL40A300 ORPL40A350 ORPL40A400
ORPL60A300 ORPL60A350 ORPL60A400 ORPL60A500 ORPL60A600
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
Long delay I4t response selection limits short delay time to flat response.
Zone Interlocking, PowerNet, or both features can be added at the factory by adding Suffixes ZG, PN or ZGP respectively to above Catalogue Number.
One Form C auxiliary switch and one Form C bell alarm switch supplied with breaker as standard on model 1050.
Factory sealed.
Series C and Special Application Moulded Case Circuit Breakers PG01200001K—October 2011 49
49
49
49
49
Page 10
L-10
Series C Moulded Case Circuit Breakers
70-600 Amperes L-Frame
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
100% Rated Digitrip OPTIM Electronic Circuit Breaker with Interchangeable Rating Plug
Order as individual components: Breaker Frame (which includes Trip Unit), Rating Plug, Terminals.
Circuit Breaker Frame Only
L – Adjustable Long Delay Pickup (I S – Adjustable Short Delay Pickup with Adjustable Short Delay Time (I2t or Flat Response) I – Adjustable Instantaneous Pickup G – Adjustable Ground Fault Pickup with Adjustable Ground Fault Time (I
Maximum Continuous Ampere Rating @ 40°C
3-Pole Ultra High Interrupting Capacity Current Limiting 600 Volt Ac Rated 50 kAIC @ 600 Vac
125 CLDC3125T52W CLDC3125T56W CLDC3125T57W CLDC3125T106W CLDC3125T107W 70
250 CLDC3250T52W CLDC3250T56W CLDC3250T57W CLDC3250T106W CLDC3250T107W 125
400 CLDC3400T52W CLDC3400T56W CLDC3400T57W CLDC3400T106W CLDC3400T107W 200
600 CLDC3600T52W CLDC3600T56W CLDC3600T57W CLDC3600T106W CLDC3600T107W 300
Instruction Leaflet Number 29C105 for Breaker; 29C891 for OPTIM Trip Unit
A – Adjustable Ground Fault Alarm with Adjustable Ground Fault Time (I
OPTIM 550
LSI LSIG LSIA LSIG LSIA
Catalogue Number
OPTIM 1050 ➂➃
) with Adjustable Long Delay Time (I2t or I4t Response)
r
2
t or Flat Response)
2
t or Flat Response)
Digitrip OPTIM Rating Plug Only
Ampere Rating Fixed Rating Plug
ORPL125A070
90
ORPL125A090
100
ORPL125A100
110
ORPL125A110
125
ORPL125A125
ORPL025A125
150
ORPL025A150
175
ORPL025A175
200
ORPL025A200
225
ORPL025A225
250
ORPL025A250
ORPL40A200
225
ORPL40A225
250
ORPL40A250
300
ORPL40A300
350
ORPL40A350
400
ORPL40A400
ORPL60A300
350
ORPL60A350
400
ORPL60A400
500
ORPL60A500
600
ORPL60A600
49
49
49
49
49
49
49
49
49
49
49
49
49
Long delay I4t response selection limits short delay time to flat response.
Zone Interlocking, PowerNet, or both features can be added at the factory by adding Suffixes ZG, PN or ZGP respectively to above Catalogue Number.
One Form C auxiliary switch and one Form C bell alarm switch supplied with breaker as standard on model 1050.
Factory sealed.
50 Series C and Special Application Moulded Case Circuit Breakers PG01200001K—October 2011
Page 11
Series C Moulded Case Circuit Breakers
70-600 Amperes L-Frame
L-11
Line and Load Terminals
Line and load terminals provide wire connecting capabilities for specific ranges of continuous current ratings and wire types. All terminals comply with Underwriters Laboratories, Inc., Standards UL486A and UL486B and CSA Standard C22.2 No. 65. Unless otherwise specified, L-frame circuit breaker line and load terminals are shipped separately for field installation.
Line and Load Terminals
Maximum Breaker Amperes
Standard Cu/AI Pressure Terminals
400
450 500 600
Optional Copper and Cu/AI Pressure Type Terminals
600 Copper Cu 250-350 (2) 120-150 T602LD
Terminal Body Material Wire Type
Aluminum
Aluminum Aluminum Aluminum
Cu/AI
Cu/AI Cu/AI Cu/AI
The wire connecting terminal is secured with two pan-head, slotted screws and lock washers which can be checked for the correct torque loading or retightened from the front of the circuit breaker before installation of the conductors. (Applies to all styles.) The circuit breaker line/load terminal conductors are positioned in the conducting holes in the wire connecting terminal and are secured
AWG Wire Range/ Number of Conductors
4/0-600 (1)
4-4/0 (2) 3/0-350 (2) 400-500 (2)
Metric Wire Range mm
120-300
25-95 95-150 185-240
2
Terminal Catalogue Number
2TA401LDK– 2-Pole Kit 3TA401LDK– 3-Pole Kit 4TA401LDK– 4-Pole Kit TA450LD TA602LD 2TA603LDK– 2-Pole Kit 3TA603LDK– 3-Pole Kit 4TA603LDK– 4-Pole Kit
with recessed socket screws which are tightened to the correct torque loading from the front of the circuit breaker.
Ordering Information
L-frame circuit breakers use Cu/AI terminals as standard. When optional copper terminals are required, order by Catalogue number. Specify if factory installation is required.
Terminals with Control Wire Termination Catalogue Numbers
 
T602LDCW
 
  
– – – – TA602LDCW 2TA603LDCW 3TA603LDCW 4TA603LDCW
  
49
49
49
49
49
49
49
49
49
49
49
49
49
49
TA401LD or TA603LD Terminal (Step-Type Terminal Requires Terminal Cover and Warning Label. See Inset.)
Pan-Head Screws and Lockwashers
TA450LD or TA602LD or T602LD Terminal
Circuit Breaker Line Terminal Cover
Pan-Head Screws and Lockwashers (Installed before Cable Clamping Screws)
Terminal Cover
Warning Label
Retainer
Screws
49
49
49
49
49
49
49
49
49
49
49
49
49
49
Terminal kits contain one terminal for each pole and one terminal cover.
Individually packed.
Terminal is marked with AL9CU to indicate the 90ºC temperature rating.
Series C and Special Application Moulded Case Circuit Breakers PG01200001K—October 2011 51
49
49
Page 12
L-12
Series C Moulded Case Circuit Breakers
70-600 Amperes
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
Allowable Accessory Combinations
Different combinations of accessories can be supplied, depending on the types of accessories and the number of poles in the circuit breaker.
2-Pole
Description
Internal Accessories (Only One Internal Accessory Per Pole)
Alarm Lockout (Make/Break) INTA-3
Alarm Lockout (2Make/2Break) INTA-3
Auxiliary Switch (1A, 1B) INTA-7
Auxiliary Switch (2A, 2B) INTA-7
Auxiliary Switch (3A, 3B) INTA-7
Auxiliary Switch (1A, 1B) and Alarm Switch Combination INTA-9
Auxiliary Switch (2A, 2B) and Alarm Switch Combination INTA-9
Shunt Trip – Standard INTA-12
Shunt Trip – Low Energy INTA-15
Undervoltage Release Mechanism INTA-20
Eaton PowerNet and Zone Interlock Kit (OPTIM 550) INTA-23
External Accessories
End Cap Kit EXTA-2
Control Wire Terminal Kit EXTA-3
Base Mounting Hardware EXTA-5
Terminal Shields EXTA-7
Interphase Barriers EXTA-8
Non-Padlockable Handle Block EXTA-10
Padlockable Handle Lock Hasp EXTA-11
Key Interlock Kit EXTA-12
Sliding Bar Interlock – Requires Two Breakers EXTA-13
Walking Beam Interlock – Requires Two Breakers EXTA-13
Electrical (Motor) Operator EXTA-15
Plug-in Adapters EXTA-16
Rear Connecting Studs EXTA-19
Panelboard Connecting Straps EXTA-20
Handle Mechanisms EXTA-21
Handle Extension EXTA-27
Solid-State (Electronic) Portable Test Kit EXTA-28
Ground Fault Alarm Unit EXTA-28
OPTIM System Components 3-Poles
Breaker Interface Module (BIM) EXTA-29
Digitrip OPTIMizer EXTA-29
Auxiliary Power Module EXTA-29
Potential Transformer Module EXTA-30
Modifications (Refer to Eaton)
Special Calibration 1.2
Moisture Fungus Treatment 1.2
Freeze-Tested Circuit Breakers 1.2
Marine Application 1.2
Applicable in indicated pole position May be mounted on left or right pole –
Reference Page
not both
, 3-Pole 4-Pole
Left Centre Right Left Centre Right Neu.
■■■■
■■■■
■■■■
■■■■
■■■■
■■■■
■■■■
■■■■
■■■■
■■■■
●●● ●●●●
●●● ●●●●
●●● ●●●●
●●● ●●●●
●●● ●●●●
■■
❏❏❏❏
❏❏❏❏
●●●
●●● ●●●●
●●● ●●●●
●●● ●●●●
●●● ●●●●
●●● ●●●●
●●● ●●●●
●●● ●●●●
●●● ●●●●
●●● ●●●●
●●● ●●●●
●●● ●●●●
●●● ●●●●
●●● ●●●●
Accessory available/Modification available
49
49
49
2-pole breaker supplied in 3-pole frame. Current carrying parts omitted from centre pole.
Refer to Eaton for appropriate neutral pole accessory combinations.
OPTIM model 1050 is factory sealed and does not have the right pole space available for accessories.
Shunt trip and UVR cannot be mounted in right poles on LES trip units or OPTIM trip units.
52 Series C and Special Application Moulded Case Circuit Breakers PG01200001K—October 2011