Cutler Hammer, Div of Eaton Corp Series C Molded Case Circuit Breakers Catalog Page

Molded Case Circuit Breakers
Typical K-Frame Circuit Breaker
Series C
Contents
Product Overview . . . . . . . . . . . . . . . . . . . . . . . . . . V4-T2-246
Standards and Certifications . . . . . . . . . . . . . . . . . . V4-T2-247
Quick Reference . . . . . . . . . . . . . . . . . . . . . . . . . . . V4-T2-248
G-Frame (15–100 Amperes) . . . . . . . . . . . . . . . . . . V4-T2-251
F-Frame (10–225 Amperes) . . . . . . . . . . . . . . . . . . V4-T2-265
J-Frame (70–250 Amperes). . . . . . . . . . . . . . . . . . . V4-T2-283
K-Frame (70–400 Amperes)
Catalog Number Selection. . . . . . . . . . . . . . . . .
Product Selection. . . . . . . . . . . . . . . . . . . . . . . . V4-T2-294
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . V4-T2-310
Technical Data and Specifications . . . . . . . . . . . V4-T2-311
Dimensions and Weights. . . . . . . . . . . . . . . . . . V4-T2-314
L-Frame (125–600 Amperes) . . . . . . . . . . . . . . . . . V4-T2-315
M-Frame (300–800 Amperes) . . . . . . . . . . . . . . . . . V4-T2-341
N-Frame (400–1200 Amperes) . . . . . . . . . . . . . . . . V4-T2-352
R-Frame (800–2500 Amperes) . . . . . . . . . . . . . . . . V4-T2-367
Motor Circuit Protectors (MCP) . . . . . . . . . . . . . . . V4-T2-386
Motor Protection Circuit Breakers (MPCB). . . . . . . V4-T2-397
Type ELC Current Limiter Attachment (Size 0–4) Current Limiting Circuit Breaker Module
Internal Accessories . . . . . . . . . . . . . . . . . . . . . . . . V4-T2-403
External Accessories. . . . . . . . . . . . . . . . . . . . . . . . V4-T2-436
. . . . V4-T2-399
. . . . . . . . . . V4-T2-400
2.4
2
V4-T2-292
K-Frame (70–400 Amperes)
Product Description
l
All Eaton K-Frame circuit breakers are HACR rated
l
K-Frame circuit breakers are available as individual components (frame, trip unit, terminals), or factory assembled complete breakers
l
K-Frame circuit breakers with non-interchangeable trip units are suitable for reverse feed use
Volume 4—Circuit Protection CA08100005E—March 2020 V4-T2-291
Molded Case Circuit Breakers
Number of Poles
2 = Two-pole 3 = Three-pole 4 = Four-pole
Circuit Breaker/
Frame Ampere
Rating
100 125 150 175 200 225 250 300 350 400
KD 3 400 F
Circuit Breaker/
Frame Type
DK KD KDB HKD KDC
Suffix
C= Copper terminals E= 50% protected neutral pole (four-pole electronic trip
unit circuit breaker only)
F= Frame only (400 A only) K= High-magnetic molded-case switch V= 50 ° calibration (thermal-magnetic trip units only) W= Without terminals X= Load terminals only Y= Line side terminals only Blank= Standard load and line side terminals
Number of Poles
2 = Two-pole 3 = Three-pole 4 = Four-pole
Circuit Breaker/
Frame Ampere
Rating
100 125 150 175 200 225 250 300 350 400
KT 3 400 F
Trip Unit Type
KT = Thermal-magnetic
Suffix
T = Trip unit only
2.4
Catalog Number Selection
This information is presented only as an aid to understanding catalog numbers. It is not to be used to build catalog numbers for circuit breakers or trip units.
2
K-Frame with Thermal-Magnetic Trip Unit Technology
Series C
Thermal-Magnetic Breakers and Frames
Thermal-Magnetic Trip Unit
1
1
Notes
1
Frames are the same for thermal-magnetic or 310+ electronic trip units, e.g., KD3400F or HKD3400F.
Ampere rating available with electronic trip unit only.
V4-T2-292 Volume 4—Circuit Protection CA08100005E—March 2020
Molded Case Circuit Breakers
Performance at
480 Vac
KDB= 35 kAIC HKDB= 65 kAIC CKDB= 35 kAIC
100% rated
CHKDB= 65 kAIC
100% rated
Number of Poles
3 = Three-pole
Ampere Rating
125 250 400
Trip Unit
T33=310+ Electronic LS T32=310+ Electronic LSI T35=310+ Electronic LSG T36=310+ Electronic LSIG T38=310+ Electronic ALSI with Maintenance Mode T39=310+ Electronic ALSIG with Maintenance Mode
Feature
Blank= No feature B20 = High load alarm B21 = Ground fault alarm, with trip B22 = Ground fault alarm, no trip ZG = Zone selective interlocking
Terminals
W = No terminals L = Line and load
Frame Designation F
KDB 3 400 F T36 ZG W
Trip Unit Type
KES
Number of Poles
3 = Three-pole 4 = Four-pole
Ampere Rating
125 250 400
Trip Unit
LS= 310+ Electronic LS LSI=310+ Electronic LSI LSG=310+ Electronic LSG
2
LSIG=310+ Electronic LSIG
2
ALSI=310+ Electronic LSI with Maintenance Mode ALSIG=310+ Electronic LSIG with Maintenance Mode
2
Feature
Blank= No feature B20 = High load alarm B21 = Ground fault alarm, with trip
2
B22 = Ground fault alarm, no trip
2
ZG = Zone selective interlocking
KES 3 400 LSIG ZG
Circuit Breaker/Frame
Ampere Rating
125 250 400
Trip Model
T5= Model 550 T10= Model 1050
KD 3 125 T5 7 W
Trip Type
2 = LSI 6 = LSIG 7 = LSIA
Suffix
W = Without terminals
Circuit Breaker/
Frame Type
KD HKD KDC CKD CHKD
Number of Poles
3 = Three-pole
Series C
2.4
K-Frame with 310+ Electronic Trip Unit Technology
310+ Circuit Breakers
310+ Electronic Trip Units
2
3
1
2
K-Frame with OPTIM Trip Unit Technology
OPTIM Circuit Breakers
Notes
1
Cannot combine ‘B2X’ suffixes with ‘B2X’ suffixes.
2
Not available in four-pole configurations.
3
Frames are the same for thermal-magnetic or 310+ electronic trip units, e.g., KD3400F, HKD3400F, etc.
Volume 4—Circuit Protection CA08100005E—March 2020 V4-T2-293
Molded Case Circuit Breakers
2.4
Product Selection
2
Types KD, HKD and KDC Thermal-Magnetic Circuit Breakers with Interchangeable Trip Units
Maximum Continuous Ampere Rating at 40 °C
Tw o - P o l e
100 KD2100 HKD2100 KDC2100 KT2100T TA300K
125 KD2125 HKD2125 KDC2125 KT2125T TA300K
150 KD2150 HKD2150 KDC2150 KT2150T TA300K
175 KD2175 HKD2175 KDC2175 KT2175T TA300K
200 KD2200 HKD2200 KDC2200 KT2200T TA300K
225 KD2225 HKD2225 KDC2225 KT2225T TA300K
250 KD2250 HKD2250 KDC2250 KT2250T TA350K
300 KD2300 HKD2300 KDC2300 KT2300T TA350K
350 KD2350 HKD2350 KDC2350 KT2350T TA350K
400 KD2400 HKD2400 KDC2400 KT2400T 2TA400K
Three-Pole
100 KD3100 HKD3100 KDC3100 KT3100T TA300K
125 KD3125 HKD3125 KDC3125 KT3125T TA300K
150 KD3150 HKD3150 KDC3150 KT3150T TA300K
175 KD3175 HKD3175 KDC3175 KT3175T TA300K
200 KD3200 HKD3200 KDC3200 KT3200T TA300K
225 KD3225 HKD3225 KDC3225 KT3225T TA300K
250 KD3250 HKD3250 KDC3250 KT3250T TA350K
300 KD3300 HKD3300 KDC3300 KT3300T TA350K
350 KD3350 HKD3350 KDC3350 KT3350T TA350K
400 KD3400 HKD3400 KDC3400 KT3400T 3TA400K
Four-Pole
100 KD4100 HKD4100 KDC4100 KT3100T TA300K
125 KD4125 HKD4125 KDC4125 KT3125T TA300K
175 KD4175 HKD4175 KDC4175 KT3175T TA300K
200 KD4200 HKD4200 KDC4200 KT3200T TA300K
225 KD4225 HKD4225 KDC4225 KT3225T TA300K
250 KD4250 HKD4250 KDC4250 KT3250T TA350K
300 KD4300 HKD4300 KDC4300 KT3300T TA350K
350 KD4350 HKD4350 KDC4350 KT3350T TA350K
400 KD4400 HKD4400 KDC4400 KT3400T 4TA400K
Notes
1
Magnetic trip adjustable 5–10 times continuous ampere rating.
2
Individually packed.
3
2TA400K, 3TA400K and 4TA400K terminal kits contain one terminal for each pole and one terminal cover.
Series C
Standard Interrupting Capacity 600 Vac Rated 35 kAIC at 480 Vac
Factory Assembled Circuit Consisting of Frame, Trip Unit and Terminals
Catalog Number
1
High Interrupting Capacity 600 Vac Rated 65 kAIC at 480 Vac
Factory Assembled Circuit Consisting of Frame, Trip Unit and Terminals
1
Catalog Number
Ultra High Interrupting Capacity Current Limiting 600 Vac Rated 100 kAIC at 480 Vac
Factory Assembled Circuit Consisting of Frame, Trip Unit and Terminals
1
Catalog Number
Thermal-Magnetic Trip Unit Only
For Use with Standard or High or Ultra High Interrupting Frames
1
Catalog Number
Standard Terminals Only
See Page V4-T2-309 for Optional Terminals
Catalog Number
2
2
2
2
2
2
2
2
2
3
2
2
2
2
2
2
2
2
2
3
2
2
2
2
2
2
2
2
3
V4-T2-294 Volume 4—Circuit Protection CA08100005E—March 2020
Molded Case Circuit Breakers
23
2.4
Terminal Information
V4-T2-309
Series C
Types KD, HKD and KDC Thermal-Magnetic Circuit Breakers—Frame Only
Standard Interrupting Capacity 600 Vac Rated 35 kAIC at 480 Vac
Catalog Number
Tw o - P o l e
KD2400F HKD2400F KDC2400F
Three-Pole
KD3400F HKD3400F KDC3400F
Four-Pole
KD4400F HKD4400F KDC4400F
High Interrupting Capacity 600 Vac Rated 65 kAIC at 480 Vac
Catalog Number
Types KD, HKD and KDC Electronic Circuit Breakers with Interchangeable 310+ Trip Units
Order as individual components: breaker frame, trip unit and terminals. See 310+ adjustability specifications on Page V4-T2-312.
Types KD, HKD and KDC Electronic Circuit Breakers with Interchangeable 310+ Trip Units—Three-Pole
Circuit Breaker Frame Only Digitrip RMS 310+ Trip Unit Only
Ultra High
Standard Interrupting Capacity
Max. Cont. Ampere Rating at 40 °C
125 KD3400F HKD3400F KDC3400F KES3125LS KES3125LSI KES3125LSG KES3125LSIG LGFCT125 See Page
250 KD3400F HKD3400F KDC3400F KES3250LS KES3250LSI KES3250LSG KES3250LSIG LGFCT250
400 KD3400F HKD3400F KDC3400F KES3400LS KES3400LSI KES3400LSG KES3400LSIG LGFCT400
600 Vac Rated 35 kAIC at 480 Vac
Catalog Number Catalog Number
High Interrupting Capacity 600 Vac Rated 65 kAIC at 480 Vac
Interrupting Capacity Current Limiting 600 Vac Rated 100 kAIC at 480 Vac
Standard Options LS LSI LSG LSIG
Adjustable Short Time Pickup with
2
t Short
I Delay Ramp
Ultra High Interrupting Capacity Current Limiting 600 Vac Rated 100 kAIC at 480 Vac
Catalog Number
1
Independently Adjustable Short Time Pickup and Delay
Adjustable Short Time Pickup with
2
t Short
I Delay and Ground Fault Protection
Independently Adjustable Short Time Pickup and Delay and Ground Fault Protection
Neutral CT for LSG and LSIG
2
Types KD, HKD and KDC Electronic Circuit Breakers with Interchangeable 310+ Trip Units—Four-Pole
Circuit Breaker Frame Only Digitrip RMS 310+ Trip Unit Only
Ultra High
Standard Interrupting Capacity
Max. Cont. Ampere Rating at 40 °C
125 KD4400F HKD4400F KDC4400F KES4125LS KES4125LSI See Page
250 KD4400F HKD4400F KDC4400F KES4250LS KES4250LSI
400 KD4400F HKD4400F KDC4400F KES4400LS KES4400LSI
Notes
1
2
3
4
5
600 Vac Rated 35 kAIC at 480 Vac
Catalog Number Catalog Number
For AC use only. Required for four-wire systems if neutral protection is desired. Included with LSG and LSIG trip units. Trip unit includes protected neutral pole. Use corresponding three-pole trip unit if protected neutral pole is not required. Fully rated neutral pole protection is standard. For 50% rated protection on neutral pole, add Suffix E to four-pole trip unit catalog number.
High Interrupting Capacity 600 Vac Rated 65 kAIC at 480 Vac
Interrupting Capacity Current Limiting 600 Vac Rated 100 kAIC at 480 Vac
Standard Options LS LSI LSG LSIG
Adjustable Short Time Pickup with
2
t Short
I Delay Ramp
Independently Adjustable Short Time Pickup and Delay
1
Adjustable Short Time Pickup with
2
t Short
I Delay and Ground Fault Protection
Independently Adjustable Short Time Pickup and Delay and Ground Fault Protection
45
Neutral CT for LSG and LSIG
23
Terminal Information
V4-T2-309
Volume 4—Circuit Protection CA08100005E—March 2020 V4-T2-295
Molded Case Circuit Breakers
2.4
Type KDB with Digitrip 310+ Non-Interchangeable Trip Unit Suitable for Reverse Feed
See 310+ adjustability specifications on Page V4-T2-312.
2
Maximum Continuous Ampere Rating at 40 °C
125 3 KDB3125FT33W KDB3125FT32W KDB3125FT35W KDB3125FT36W LGFCT125 See Page
250 3 KDB3250FT33W KDB3250FT32W KDB3250FT35W KDB3250FT36W LGFCT250
400 3 KDB3400FT33W KDB3400FT32W KDB3400FT35W KDB3400FT36W LGFCT400
Type HKDB with Digitrip 310+ Non-Interchangeable Trip Unit Suitable for Reverse Feed
See 310+ adjustability specifications on Page V4-T2-312.
Maximum Continuous Ampere Rating at 40 °C
125 3 HKDB3125FT33W HKDB3125FT32W HKDB3125FT35W HKDB3125FT36W LGFCT125 See Page
250 3 HKDB3250FT33W HKDB3250FT32W HKDB3250FT35W HKDB3250FT36W LGFCT250
400 3 HKDB3400FT33W HKDB3400FT32W HKDB3400FT35W HKDB3400FT36W LGFCT400
Number of Poles
Number of Poles
Series C
Factory Assembled Circuit Breaker Consisting of Frame and Trip Unit Less Terminals Standard
LS
Adjustable Short Time Pickup with I Delay Ramp
Catalog Number Catalog Number
Factory Assembled Circuit Breaker Consisting of Frame and Trip Unit Less Terminals Standard
LS
Adjustable Short Time Pickup with I Delay Ramp
Catalog Number Catalog Number
2
t Short
2
t Short
Optional LSI LSG LSIG
Independently Adjustable Short Time Pickup and Delay
Optional LSI LSG LSIG
Independently Adjustable Short Time Pickup and Delay
Adjustable Short Time Pickup with I Delay and Ground Fault Protection
Adjustable Short Time Pickup with I Delay and Ground Fault Protection
2
t Short
2
t Short
1
Independently Adjustable Short Time Pickup and Ground Fault Protection
1
Independently Adjustable Short Time Pickup and Ground Fault Protection
Neutral CT for LSG and LSIG
Neutral CT for LSG and LSIG
23
23
Ter mi na l Information
V4-T2-310
Ter mi na l Information
V4-T2-310
100% Rated Types CKD and CHKD Electronic Circuit Breakers
The NEC allows the breaker to be rated at 100% of its frame size in an assembly, provided that 90 °C wire is applied at the 75 °C ampacity. All 100% rated circuit breakers have electronic trip units.
100% Rated Types CKD and CHKD Electronic Circuit Breakers—Three-Pole
See 310+ adjustability specifications on Page V4-T2-312.
Circuit Breaker Frame Only Digitrip RMS 310+ Trip Unit Only
Standard Options
Standard Interrupting
Maximum Continuous Ampere Rating at 40 °C
125 CKD3400F CHKD3400F KES3125LS KES3125LSI KES3125LSG KES3125LSIG LGFCT125 See Page
250 CKD3400F CHKD3400F KES3250LS KES3250LSI KES3250LSG KES3250LSIG LGFCT250
400 CKD3400F CHKD3400F KES3400LS KES3400LSI KES3400LSG KES3400LSIG LGFCT400
Notes
1
For AC use only.
2
Required for four-wire systems if neutral protection is desired.
3
Included with LSG and LSIG trip units.
Capacity
35 kAIC at 480 Vac
Catalog Number Catalog Number
High Interrupting Capacity
65 kAIC at 480 Vac
Adjustable Short Time Pickup with
2
t Short
I Delay Ramp
Independently Adjustable Short Time Pickup and Delay
Adjustable Short Time Pickup with
2
t Short
I Delay and Ground Fault Protection
Independently Adjustable Short Time Pickup and Delay and Ground Fault Protection
Neutral CT for LSG and LSIG
23
Terminal Information
V4-T2-309
V4-T2-296 Volume 4—Circuit Protection CA08100005E—March 2020
Molded Case Circuit Breakers
Series C
Types DK and KDB Thermal-Magnetic Circuit Breakers with Non-Interchangeable Trip Units
Suitable for reverse feed application.
Types DK and KDB Thermal-Magnetic Circuit Breakers with Non-Interchangeable Trip Units
240 Vac Rated, 250 Vdc 600 Vac Rated, 250 Vdc
Maximum Continuous Ampere Rating at 40 °C
Tw o - P o l e
100 KDB2100W KDB2100
125 KDB2125W KDB2125
150 KDB2150W KDB2150
175 KDB2175W KDB2175
200 KDB2200W KDB2200
225 KDB2225W KDB2225
250 DK2250W DK2250Y DK2250 KDB2250W KDB2250
300 DK2300W DK2300Y DK2300 KDB2300W KDB2300
350 DK2350W DK2350Y DK2350 KDB2350W KDB2350
400 DK2400W DK2400Y DK2400 KDB2400W KDB2400
Three-Pole
100 KDB3100W KDB3100
125 KDB3125W KDB3125
150 KDB3150W KDB3150
175 KDB3175W KDB3175
200 KDB3200W KDB3200
225 KDB3225W KDB3225
250 DK3250W DK3250Y DK3250 KDB3250W KDB3250
300 DK3300W DK3300Y DK3300 KDB3300W KDB3300
350 DK3350W DK3350Y DK3350 KDB3350W KDB3350
400 DK3400W DK3400Y DK3400 KDB3400W KDB3400
Complete Circuit Breaker Complete Circuit Breaker Without Line and
Load Terminals Catalog
Number
With Line Terminals Only
Catalog Number
With Standard Line and Load Terminals Only
Catalog Number
Without Line and Load Terminals
Catalog Number
With Standard Line and Load Terminals
Catalog Number
2.4
2
Volume 4—Circuit Protection CA08100005E—March 2020 V4-T2-297
Molded Case Circuit Breakers
2.4
Molded Case Switches
Eaton’s molded case switches are used as
2
compact switches in applications requiring high current switching capabilities. Molded case switches are constructed of circuit breaker
Molded Case Switches
Maximum Continuous Ampere Rating at 40 °C
Tw o - P o l e
400 DK2400K KD2400K KDB2400K
Three-Pole
400 DK3400K KD3400K KDB3400K
Four-Pole
400 KD4400K KDB4400K
Note
Molded case switches may open above 4000 amperes.
Series C
components and are of the high instantaneous automatic type. Molded case switches are listed in accordance with Underwriters Laboratories Standard UL 489.
240 Vac Maximum, 250 Vdc 600 Vac Maximum, 250 Vdc 600 Vac Maximum, 250 Vdc
Complete Circuit Breaker with Standard Line and Load Terminals
Catalog Number
HKD2400K HKDB2400K
HKD3400K HKDB3400K
HKD4400K HKDB4400K
Complete Circuit Breaker with Standard Line and Load Terminals
Catalog Number
Complete Circuit Breaker with Standard Line and Load Terminals. Suitable for Reverse Feed Use
Catalog Number
V4-T2-298 Volume 4—Circuit Protection CA08100005E—March 2020