F= Frame only (400 A only)
K= High-magnetic molded-case switch
V= 50 ° calibration (thermal-magnetic trip units only)
W= Without terminals
X= Load terminals only
Y= Line side terminals only
Blank= Standard load and line side terminals
Number
of Poles
2 = Two-pole
3 = Three-pole
4 = Four-pole
Circuit Breaker/
Frame Ampere
Rating
100
125
150
175
200
225
250
300
350
400
KT 3 400 F
Trip Unit Type
KT = Thermal-magnetic
Suffix
T = Trip unit only
2.4
Catalog Number Selection
This information is presented only as an aid to understanding catalog numbers.
It is not to be used to build catalog numbers for circuit breakers or trip units.
2
K-Frame with Thermal-Magnetic Trip Unit Technology
Series C
Thermal-Magnetic Breakers and Frames
Thermal-Magnetic Trip Unit
1
1
Notes
1
Frames are the same for thermal-magnetic or 310+ electronic trip units, e.g., KD3400F or HKD3400F.
Ampere rating available with electronic trip unit only.
For AC use only.
Required for four-wire systems if neutral protection is desired.
Included with LSG and LSIG trip units.
Trip unit includes protected neutral pole. Use corresponding three-pole trip unit if protected neutral pole is not required.
Fully rated neutral pole protection is standard. For 50% rated protection on neutral pole, add Suffix E to four-pole trip unit catalog number.
High
Interrupting
Capacity
600 Vac
Rated
65 kAIC at
480 Vac
Interrupting
Capacity
Current
Limiting
600 Vac
Rated
100 kAIC
at 480 Vac
StandardOptions
LSLSILSGLSIG
Adjustable
Short Time
Pickup with
2
t Short
I
Delay Ramp
Independently
Adjustable
Short Time
Pickup and
Delay
1
Adjustable
Short Time
Pickup with
2
t Short
I
Delay and
Ground Fault
Protection
Independently
Adjustable
Short Time
Pickup and
Delay and
Ground Fault
Protection
Factory Assembled Circuit Breaker Consisting of Frame and Trip Unit Less Terminals
Standard
LS
Adjustable Short Time
Pickup with I
Delay Ramp
Catalog NumberCatalog Number
Factory Assembled Circuit Breaker Consisting of Frame and Trip Unit Less Terminals
Standard
LS
Adjustable Short Time
Pickup with I
Delay Ramp
Catalog NumberCatalog Number
2
t Short
2
t Short
Optional
LSILSGLSIG
Independently Adjustable
Short Time Pickup and
Delay
Optional
LSILSGLSIG
Independently Adjustable
Short Time Pickup and
Delay
Adjustable Short Time
Pickup with I
Delay and Ground Fault
Protection
Adjustable Short Time
Pickup with I
Delay and Ground Fault
Protection
2
t Short
2
t Short
1
Independently Adjustable
Short Time Pickup and
Ground Fault Protection
1
Independently Adjustable
Short Time Pickup and
Ground Fault Protection
Neutral CT for
LSG and LSIG
Neutral CT for
LSG and LSIG
23
23
Ter mi na l
Information
V4-T2-310
Ter mi na l
Information
V4-T2-310
100% Rated Types CKD and CHKD Electronic Circuit Breakers
The NEC allows the breaker to be rated at 100% of its frame size in an assembly, provided that 90 °C wire is applied at the 75 °C
ampacity. All 100% rated circuit breakers have electronic trip units.
100% Rated Types CKD and CHKD Electronic Circuit Breakers—Three-Pole
See 310+ adjustability specifications on Page V4-T2-312.
Circuit Breaker Frame OnlyDigitrip RMS 310+ Trip Unit Only
compact switches in
applications requiring high
current switching capabilities.
Molded case switches are
constructed of circuit breaker
Molded Case Switches
Maximum
Continuous
Ampere
Rating
at 40 °C
Tw o - P o l e
400DK2400KKD2400KKDB2400K
Three-Pole
400DK3400KKD3400KKDB3400K
Four-Pole
400—KD4400KKDB4400K
Note
Molded case switches may open above 4000 amperes.
Series C
components and are of the
high instantaneous automatic
type. Molded case switches
are listed in accordance with
Underwriters Laboratories
Standard UL 489.
Digitrip OPTIM 550 Electronic Circuit Breakers with Interchangeable Rating Plug
Order as individual components: breaker frame (which includes trip unit), rating plug, terminals.
Digitrip OPTIM 550 Electronic Circuit Breakers with Interchangeable Rating Plug
Circuit Breaker Frame OnlyDigitrip OPTIM Rating Plug Only
L – Adjustable Long Delay Pickup (I
S – Adjustable Short Delay Pickup with Adjustable Short Delay Time (I2t or Flat Response)
I – Adjustable Instantaneous Pickup
G – Adjustable Ground Fault Pickup with Adjustable Ground Fault Time (I
Maximum
Continuous
Ampere
Rating
at 40 °C
Three-Pole Standard Interrupting Capacity 600 Vac Rated 35 kAIC at 480 Vac
125KD3125T52WKD3125T56WKD3125T57W70ORPK125A70
250KD3250T52WKD3250T56WKD3250T57W125ORPK025A125
400KD3400T52WKD3400T56WKD3400T57W200ORPK40A200
Notes
1
Long delay I4t response selection limits short delay time to flat response.
2
Zone interlocking, PowerNet, or both features can be added at the factory by adding suffixes ZG, PN or ZGP respectively to above catalog number.
A – Adjustable Ground Fault Alarm with Adjustable Ground Fault Time (I
OPTIM 550
LSILSIGLSIA
Catalog
Number
2
) with Adjustable Long Delay Time (I2t or I4t Response)
Long delay I4t response selection limits short delay time to flat response.
2
Zone interlocking, PowerNet, or both features can be added at the factory by adding suffixes ZG, PN or ZGP respectively to above catalog number.
Series C
Circuit Breaker Frame OnlyDigitrip OPTIM Rating Plug Only
L – Adjustable Long Delay Pickup (I
S – Adjustable Short Delay Pickup with Adjustable Short Delay Time (I2t or Flat Response)
I – Adjustable Instantaneous Pickup
G – Adjustable Ground Fault Pickup with Adjustable Ground Fault Time (I
A – Adjustable Ground Fault Alarm with Adjustable Ground Fault Time (I
OPTIM 550
LSILSIGLSIA
Catalog
Number
2
) with Adjustable Long Delay Time (I2t or I4t Response)
Digitrip OPTIM 550 Electronic Circuit Breakers with Interchangeable Rating Plug, continued
Circuit Breaker Frame OnlyDigitrip OPTIM Rating Plug Only
L – Adjustable Long Delay Pickup (I
S – Adjustable Short Delay Pickup with Adjustable Short Delay Time (I2t or Flat Response)
I – Adjustable Instantaneous Pickup
G – Adjustable Ground Fault Pickup with Adjustable Ground Fault Time (I
Maximum
Continuous
Ampere
Rating
at 40 °C
Three-Pole Ultra High Interrupting Capacity Current Limiting 600 Vac Rated 100 kAIC at 480 Vac
Digitrip OPTIM 1050 Electronic Circuit Breakers with Interchangeable Rating Plug
Order as individual components: breaker frame (which includes trip unit), rating plug, terminals.
2
Digitrip OPTIM 1050 Electronic Circuit Breakers with Interchangeable Rating Plug
Maximum
Continuous
Ampere
Rating
at 40 °C
Three-Pole Standard Interrupting Capacity 600 Vac Rated 35 kAIC at 480 Vac
125KD3125T106WKD3125T107W70ORPK125A70
250KD3250T106WKD3250T107W125ORPK025A125
400KD3400T106WKD3400T107W200ORPK40A200
Notes
1
Long delay I4t response selection limits short delay time to flat response.
2
Factory sealed.
Series C
Circuit Breaker Frame OnlyDigitrip OPTIM Rating Plug Only
L – Adjustable Long Delay Pickup (I
S – Adjustable Short Delay Pickup with Adjustable Short Delay Time (I2t or Flat Response)
I – Adjustable Instantaneous Pickup
G – Adjustable Ground Fault Pickup with Adjustable Ground Fault Time (I
A – Adjustable Ground Fault Alarm with Adjustable Ground Fault Time (I
OPTIM 1050
LSIGLSIA
Catalog
Number
2
) with Adjustable Long Delay Time (I2t or I4t Response)
Digitrip OPTIM 1050 Electronic Circuit Breakers with Interchangeable Rating Plug, continued
Circuit Breaker Frame OnlyDigitrip OPTIM Rating Plug Only
L – Adjustable Long Delay Pickup (I
S – Adjustable Short Delay Pickup with Adjustable Short Delay Time (I2t or Flat Response)
I – Adjustable Instantaneous Pickup
G – Adjustable Ground Fault Pickup with Adjustable Ground Fault Time (I
Maximum
Continuous
Ampere
Rating
at 40 °C
Three-Pole High Interrupting Capacity 600 Vac Rated 65 kAIC at 480 Vac
125HKD3125T106WHKD3125T107W70ORPK125A70
250HKD3250T106WHKD3250T107W125ORPK025A125
400HKD3400T106WHKD3400T107W200ORPK40A200
Notes
1
Long delay I4t response selection limits short delay time to flat response.
2
Factory sealed.
A – Adjustable Ground Fault Alarm with Adjustable Ground Fault Time (I
OPTIM 1050
LSIGLSIA
Catalog
Number
2
) with Adjustable Long Delay Time (I2t or I4t Response)
Digitrip OPTIM 1050 Electronic Circuit Breakers with Interchangeable Rating Plug, continued
2
Maximum
Continuous
Ampere
Rating
at 40 °C
Three-Pole Ultra High Interrupting Capacity Current Limiting 600 Vac Rated 100 kAIC at 480 Vac
125KDC3125T106WKDC3125T107W70ORPK125A70
250KDC3250T106WKDC3250T107W125ORPK025A125
400KDC3400T106WKDC3400T107W200ORPK40A200
Notes
1
Long delay I4t response selection limits short delay time to flat response.
2
Factory sealed.
Series C
Circuit Breaker Frame OnlyDigitrip OPTIM Rating Plug Only
L – Adjustable Long Delay Pickup (I
S – Adjustable Short Delay Pickup with Adjustable Short Delay Time (I2t or Flat Response)
I – Adjustable Instantaneous Pickup
G – Adjustable Ground Fault Pickup with Adjustable Ground Fault Time (I
A – Adjustable Ground Fault Alarm with Adjustable Ground Fault Time (I
OPTIM 1050
LSIGLSIA
Catalog
Number
2
) with Adjustable Long Delay Time (I2t or I4t Response)
Circuit Breaker Frame OnlyDigitrip OPTIM Rating Plug Only
L – Adjustable Long Delay Pickup (I
S – Adjustable Short Delay Pickup with Adjustable Short Delay Time (I2t or Flat Response)
I – Adjustable Instantaneous Pickup
G – Adjustable Ground Fault Pickup with Adjustable Ground Fault Time (I
Maximum
Continuous
Ampere
Rating
at 40 °C
Three-Pole Standard Interrupting Capacity 600 Vac Rated 35 kAIC at 480 Vac
Long delay I4t response selection limits short delay time to flat response.
2
Zone interlocking, PowerNet, or both features can be added at the factory by adding suffixes ZG, PN or ZGP respectively to above catalog number
(refer to Page V4-T2-423).
A – Adjustable Ground Fault Alarm with Adjustable Ground Fault Time (I
OPTIM 550
LSILSIGLSIA
Catalog
Number
2
) with Adjustable Long Delay Time (I2t or I4t Response)
Long delay I4t response selection limits short delay time to flat response.
2
Zone interlocking, PowerNet, or both features can be added at the factory by adding suffixes ZG, PN or ZGP respectively to above catalog number.
Series C
Circuit Breaker Frame OnlyDigitrip OPTIM Rating Plug Only
L – Adjustable Long Delay Pickup (I
S – Adjustable Short Delay Pickup with Adjustable Short Delay Time (I2t or Flat Response)
I – Adjustable Instantaneous Pickup
G – Adjustable Ground Fault Pickup with Adjustable Ground Fault Time (I
A – Adjustable Ground Fault Alarm with Adjustable Ground Fault Time (I
OPTIM 550
LSILSIGLSIA
Catalog
Number
2
) with Adjustable Long Delay Time (I2t or I4t Response)
Circuit Breaker Frame OnlyDigitrip OPTIM Rating Plug Only
L – Adjustable Long Delay Pickup (I
S – Adjustable Short Delay Pickup with Adjustable Short Delay Time (I2t or Flat Response)
I – Adjustable Instantaneous Pickup
G – Adjustable Ground Fault Pickup with Adjustable Ground Fault Time (I
Maximum
Continuous
Ampere
Rating
at 40 °C
Three-Pole Standard Interrupting Capacity 600 Vac Rated 35 kAIC at 480 Vac
125CKD3125T106WCKD3125T107W70ORPK125A70
250CKD3250T106WCKD3250T107W125ORPK025A125
400CKD3400T106WCKD3400T107W200ORPK40A200
Notes
1
Long delay I4t response selection limits short delay time to flat response.
2
Factory sealed.
A – Adjustable Ground Fault Alarm with Adjustable Ground Fault Time (I
OPTIM 1050
LSIGLSIA
Catalog
Number
2
) with Adjustable Long Delay Time (I2t or I4t Response)
100% Rated Digitrip OPTIM 1050 Electronic Circuit Breakers with Interchangeable Rating Plug, continued
2
Maximum
Continuous
Ampere
Rating
at 40 °C
Three-Pole High Interrupting Capacity 600 Vac Rated 65 kAIC at 480 Vac
125CHKD3125T106WCHKD3125T107W70ORPK125A70
250CHKD3250T106WCHKD3250T107W125ORPK025A125
400CHKD3400T106WCHKD3400T107W200ORPK40A200
Notes
1
Long delay I4t response selection limits short delay time to flat response.
2
Factory sealed.
Series C
Circuit Breaker Frame OnlyDigitrip OPTIM Rating Plug Only
L – Adjustable Long Delay Pickup (I
S – Adjustable Short Delay Pickup with Adjustable Short Delay Time (I2t or Flat Response)
I – Adjustable Instantaneous Pickup
G – Adjustable Ground Fault Pickup with Adjustable Ground Fault Time (I
A – Adjustable Ground Fault Alarm with Adjustable Ground Fault Time (I
OPTIM 1050
LSIGLSIA
Catalog
Number
2
) with Adjustable Long Delay Time (I2t or I4t Response)
Eaton’s line and load
terminals provide wire
connecting capabilities for
specific ranges of continuous
current ratings and wire
types. All terminals comply
with Underwriters
UL 486A and UL 486B and
CSA Standard C22.2 No. 65,
or Electrical Bulletin 1165.
Unless otherwise specified,
K-Frame circuit breaker line
and load terminals are
shipped separately for field
installation.
Ordering Information
K-Frame circuit breakers use
Cu/AI terminals as standard.
When optional copper or Cu/
AI terminals are required,
order by catalog number.
Specify if factory installation
is required.
Different combinations of accessories can be supplied, depending on the types of accessories
2
and the number of poles in the circuit breaker.
KD Frame Accessories
Description
Internal Accessories (Only One Internal Accessory Per Pole)
Alarm lockout (Make/Break)
Alarm lockout (2Make/2Break)
Auxiliary switch (1A, 1B)
Auxiliary switch (2A, 2B)
Auxiliary switch (3A, 3B)
Auxiliary switch and alarm switch combination
Shunt trip—standard
Shunt trip—low energy
Undervoltage release mechanism
PowerNet or zone interlock kit (OPTIM 550)
External Accessories
End cap kitV4-T2-440
Keeper nutV4-T2-440
Control wire terminal kitV4-T2-441
Terminal adapterV4-T2-441
Multiwire connectorsV4-T2-442
Rea
r fed te
Base mounting hardwareV4-T2-443
Terminal shieldsV4-T2-445
Interphase barriersV4-T2-445
Non-padlockable handle blockV4-T2-446
P
adloc
kable handle blockV4-T2-446
Padlockable handle lock haspV4-T2-447
Cylinder lockV4-T2-447
Key Interlock kitV4-T2-448
Sliding bar interlock—requires two breakersV4-T2-449
Walking beam interlock—requires two breakersV4-T2-449
Electrical (solenoid) operatorV4-T2-450
Plug-in adaptersV4-T2-451
Re
ar con
necting studsV4-T2-453
Panelboard connecting strapsV4-T2-454
Handle mechanismsV4-T2-534
Handle extensionV4-T2-546
IQ Energy SentinelV4-T2-456
Solid
-state
OPTIM System Components Three Poles
Breaker interface module (BIM)
Digitrip OPTIMizer
Auxiliary power module
Modifications (Refer to Eaton)
Special calibration—
Moisture fungus treatmentV4-T2-246
Freeze-tested circuit breakers—
Marine/naval application—
Legend
n Applicable in indicated pole position
o May be mounted on left or right pole—not both
l Accessory available/modification available
Notes
1
Two-pole breaker supplied in three-pole frame. Current carrying parts omitted from center pole.
2
Shunt trip and UVR cannot be mounted in right poles on KES or OPTIM trip units. Standard internal accessories cannot be mounted in right pole on any K-Frame OPTIM trip unites. Special OPTIM
ground fault and zone interlock accessories are available for field installation in the right pole of K-Frame 550 OPTIM trip units. Factory installed 2a/2b and bell/aux are available for factory
installation. K-Frame breakers equipped with OPTIM 1050 trip units include aux-bell alarm in the right pole.