Can be switched in parallelfor redundancy, with O ring diode (PSG480R24RM/PSG960R24RM)
General characteristics
HousingAluminium
Status indicationgreen LED for "DC OK"
MTBF (mean time between failures)> 300,000 h
Heightmm121
Widthmm70
Depthmm117.3
Weightkg0.89
TerminationsScrew connection
Stripping lengthmm7
Terminal capacity
flexible with ferrules/solid
Tightening torqueNmPrimary side: 0.9
Ambient air temperature range°C
Operation°C-25 - +80
Storage, transportϑ°C
Storageϑ°C-25 - +85
damp heat< 95 % relative humidity at +25 °C, no condensation
Vibrations (IEC/EN 60068-2-6)10 - 500 Hz at 30 m/s² (3 G max ) for 60 min. in X-axis, Y-axis, Z-axis directions
Mechanical shock resistance (IEC 60068-2-27)30 g (300 m/s²) in all directions
Pollution degree2
Climatic class (IEC)3K3 according to EN 60721
2
Primary side: 0.82 - 3.3 mm² (18 - 12 AWG)
mm
Secondary side: 1.3 - 3.3 mm² (16 - 12 AWG)
Secondary side: 0.6
Safety and safety features
Transient overvoltage protectionVaristor
Current limitation at short-circuitI
Overvoltage protectionYes, against internal overvoltage
Insulation voltage
Input/Output4 kV AC
Input/PE2 kV AC
Output/PE1.5 kV AC
Degree of ProtectionIP20
Protection classClass I with PE connection
= 150 % der max. Ausgangsleistung
Überstrom
Standards
Electrical equipment of machines: IEC60204-1 (Overvoltage category III)
Equipping power installations with electronic apparatus: EN 50178/IEC 62103
Safety extra-low voltage: PELV (EN 60204), SELV (EN 60950)
Protection against electric shock: DIN 57100-410
CE: according to EMC Directive 2014/30/EU and Low Voltage Directive 2014/35/EU
RoHS-compliant: RoHS Directive 2011/65/EU
ITE: EN 55022, EN 61000-3-2, EN 61000-3-3, EN 55024
Industrial: EN 55011
Mains harmonics limitation: EN 601000-3-2
Electrical Safety (of IT equipment) : SIQ to EN60950-1, UL/c-UL recognized to UL
60950-1, CSA C22.2 No. 60950-1, CB scheme to IEC 60950-1
UL508
Class2: UL/c-UL recognized to UL1310 and CSA C22.2 No. 223 |
Component power supply unit for general use: EN61204-3
ApprovalsEAC
Design verification as per IEC/EN 61439
Technical data for design verification
Rated operational current for specified heat dissipationI
Heat dissipation per pole, current-dependentP
Equipment heat dissipation, current-dependentP
Static heat dissipation, non-current-dependentP
Heat dissipation capacityP
Operating ambient temperature min.°C-25
08/30/2019Eaton 172884 ED2019 V58.0 EN2 / 4
n
vid
vid
vs
diss
A0
W0
W0
W26.7
W0
Operating ambient temperature max.°C80
IEC/EN 61439 design verification
10.2 Strength of materials and parts
10.2.2 Corrosion resistanceMeets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosuresMeets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heatMeets the product standard's requirements.
10.2.3.3 Verification of resistance of insulating materials to abnormal heat
and fire due to internal electric effects
10.2.4 Resistance to ultra-violet (UV) radiationMeets the product standard's requirements.
10.2.5 LiftingDoes not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impactDoes not apply, since the entire switchgear needs to be evaluated.
10.2.7 InscriptionsMeets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIESMeets the product standard's requirements.
10.4 Clearances and creepage distancesMeets the product standard's requirements.
10.5 Protection against electric shockDoes not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and componentsDoes not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connectionsIs the panel builder's responsibility.
10.8 Connections for external conductorsIs the panel builder's responsibility.
10.9 Insulation properties
10.9.2 Power-frequency electric strengthIs the panel builder's responsibility.
10.9.3 Impulse withstand voltageIs the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating materialIs the panel builder's responsibility.
10.10 Temperature riseThe panel builder is responsible for the temperature rise calculation. Eaton will
10.11 Short-circuit ratingIs the panel builder's responsibility.
10.12 Electromagnetic compatibilityIs the panel builder's responsibility.
10.13 Mechanical functionThe device meets the requirements, provided the information in the instruction
Electric engineering, automation, process control engineering / Power supply devices / Power supply device / Continuous current supply (ecl@ss10.0.1-27-04-07-01 [AFX040003])
Voltage type of supply voltageAC
1st secondary output voltageV24 - 28
2nd secondary output voltageV0 - 0
3rd secondary output voltageV0 - 0
Max. output current 1A10
Max. output current 2A0
Max. output current 3A0
Secondary voltage adjustableYes
Nominal value output voltage 1V24
Nominal value output voltage 2V0
Nominal value output voltage 3V0
Nominal value output current 1A10
Nominal value output current 2A0
Nominal value output current 3A0
Short-circuit-proofYes
Rated supply voltage at AC 50 HzV320 - 600
Rated supply voltage at AC 60 HzV320 - 600
Rated supply voltage at DCV0 - 0
Output voltage stabilizedYes
Power consumptionVA300
Power outputW240
StabilizedYes
Type of electric connectionScrew connection
Rail mounting possibleYes
08/30/2019Eaton 172884 ED2019 V58.0 EN3 / 4
Wall mounting possibleNo
Modular versionYes
Width in number of modular spacings0
Built-in widthmm70
Built-in heightmm121
Direct mounting possibleNo
Widthmm70
Heightmm121
Depthmm117.3
Suitable for safety functionsNo
SIL according to IEC 61508None
Performance level acc. EN ISO 13849-1None
Degree of protection (IP)IP20
Degree of protection (NEMA)1
Dimensions
08/30/20194 / 4