Cutler Hammer, Div of Eaton Corp DK, KDB, KD, HKD, KDC Installation Instructions

...
I.L. 29C104C
File 29-000
Effective June 1998 Supersedes I.L. 29C104-B dated August 1997.
Cutler-Hammer
Installation Instructions for DK, KDB, KD, HKD, KDC, KW, HKW, KWC, CKD, CHKD Circuit Breakers and Molded Case Switches
The recommendations and information contained herein are based on Cutler-Hammer experience and judgment, but should not be considered to be all-inclusive or cover­ing every application or circumstance which may arise. If any questions arise, contact Cutler-Hammer for further information or instructions.
1. INTRODUCTION
General Information
The K-frame Series C circuit breaker (Figure 1-1) types KD, HKD, and KDC are 600 Vac maximum rated devices with interchangeable thermal-magnetic or elec­tronic (Seltronic) trip units rated 400A maximum continu­ous current. Circuit breaker types KW, HKW, and KWC are 660 Vac maximum rated devices using interchange­able adjustable thermal/adjustable magnetic or electron­ic trip units rated up to 400A continuous current. The type KDB noninterchangeable trip circuit breaker is rated 600 Vac maximum with a maximum continuous current rating of 400A. The type DK 240 Vac maximum circuit breaker is also a noninterchangeable trip device with trip unit ratings from 250A to 400A. Refer to Table 4-1 on page 8 for all available trip unit ratings. Model D circuit breakers are listed in accordance with Underwriters Laboratories, Inc. Standard UL489 and satisfy the (P1) requirements of the International Electrotechnical Commission Recommendations No. IEC 157-1. Model W circuit breakers satisfy the requirements of IEC C947-
2. Molded case switches are listed in accordance with UL1087. For more information, see Frame Book 29-103.
100 Percent Rated K-Frame Circuit Breakers
CKD and CHKD circuit breakers are suitable for contin­uous operation at 100 percent of the frame rating if used with an 90°C insulated wire and AL9CU terminals in an enclosure which measures at least 24” high x 15” wide x 6” deep. Ventilation is not required in an enclo­sure having these minimum dimensions. CKD and CHKD 100 percent rated circuit breakers use electronic trip units only.
This instruction leaflet (IL) gives procedures for installa­tion and field testing of K-frame Series C circuit break­ers. Instructions are also provided for replacement of existing Cutler-Hammer circuit breaker types DA, LB, LBB, HLB, JA, KA, and HKA. For this publication, the term circuit breaker shall also include the molded case switch.
DO NOT ATTEMPT TO INSTALL OR PERFORM MAINTENANCE ON EQUIPMENT WHILE IT IS ENER­GIZED. DEATH, SEVERE PERSONAL INJURY, OR SUBSTANTIAL PROPERTY DAMAGE CAN RESULT FROM CONTACT WITH ENERGIZED EQUIPMENT. ALWAYS VERIFY THAT NO VOLTAGE IS PRESENT BEFORE PROCEEDING WITH THE TASK, AND ALWAYS FOLLOW GENERALLY ACCEPTED SAFE­TY PROCEDURES.
CUTLER-HAMMER IS NOT LIABLE FOR THE MISAP­PLICATION OR MISINSTALLATION OF ITS PROD­UCTS.
The user is cautioned to observe all recommendations, warnings, and cautions relating to the safety of person­nel and equipment as well as all general and local health and safety laws, codes, and procedures.
Figure 1-1 K-Frame Model D Series C Circuit Breaker Frame with KT Trip Unit Installed
WARNING
I.L. 29C104C
Page 2
Effective 6/98
2. INSTALLATION
The installation procedure consists of inspecting the cir­cuit breaker and, as applicable, installing the trip unit and rating plug, accessories, interphase barriers, and termi­nals; mounting the circuit breaker; connecting the line and load conductors; torquing terminals; and attaching terminal shields. Circuit breaker frames, trip units, rating plugs, accessories, mounting hardware, and unmounted terminals may be supplied in separate packages. To install the circuit breaker, perform the following steps.
If circuit breaker is replacing a DA, JA, KA, HKA, LB, LBB, or HLB circuit breaker, refer to section 3 of this instruction leaflet.
DK and KDB circuit breakers are factory sealed for reverse feed applications under UL489. UL requires that internal accessories be installed at the factory in these types of circuit breakers.
If required, internal accessory installation in any type of circuit breaker should be done before the
Figure 2-1 Cover Mounting Hardware
Flat Head, Thread
Forming Screws
Pan Head
Screws
Figure 2-2 Cover Screw Installation Positions
On
Off
Screw, .190-32 x 3.125 Inch Pan Head, Cross-Recessed.
Screw, No. 8 x 1.63 Inch, Flat Head, Cross-Recessed, Thread Forming.
Note: Hatched lines show additional pole and screws for 4-pole circuit breaker.
Figure 2-3 Terminal Cover Installation
Terminal Cover
Dovetails
Mounting Slots
NOTICE
NOTICE
I.L. 29C104C
Page 3
Effective 6/98
circuit breaker is mounted and connected. Refer to individual accessory instruction leaflets.
2-1. Make sure that the circuit breaker is suitable for the intended installation by comparing nameplate data with existing equipment ratings and system requirements. Inspect the circuit breaker for completeness, and check for damage before mounting. Uninstalled cover mount­ing hardware is supplied in a plastic bag with the circuit breaker frame. (See Figure 2-1.)
2-2. Remove installed cover screws and cover.
The circuit breaker handle must be in the tripped or OFF position to remove the cover. Instructions for installing the trip unit and accessories are supplied with the devices.
2-3. If not already installed, mount trip unit and acces­sories (if required) in circuit breaker frame. Rating plug must be installed in Seltronic trip units.
WHEN REMOVED AND REINSTALLED, THREAD­FORMING SCREWS WILL TRY TO REFORM THE THREADS IN THE BASE. CARE SHOULD BE TAKEN EVERY TIME A THREAD-FORMING SCREW IS USED TO ENSURE THE SCREW STARTS IN THE ORIGINAL THREADS. DAMAGED THREADS CAN RESULT IN IMPROPER CIRCUIT BREAKER COVER RETENTION.
2-4. Replace cover and install pan-head screws fol­lowed by thread-forming screws as shown in Figure 2-2.
2-5. If not already installed, mount terminals as shown in Figure 2-4. Secure the terminals to the circuit breaker using a 7/32-inch socket wrench, and torque to 6-8 lb-ft (8-11 N.m). After mounting the circuit breaker and before installation of the conductors, the terminal mount­ing screw can be checked or retightened through the terminal when the conductor screw is removed. If Warning label is supplied with terminal, place on upper portion of circuit breaker cover.
THE VOLTAGE IN ENERGIZED EQUIPMENT CAN
CAUSE DEATH OR SEVERE PERSONAL INJURY. BEFORE MOUNTING THE CIRCUIT BREAKER IN AN ELECTRICAL SYSTEM, MAKE SURE THERE IS NO VOLTAGE PRESENT WHERE WORK IS TO BE PER­FORMED. SPECIAL ATTENTION SHOULD BE PAID TO REVERSE FEED APPLICATIONS TO ENSURE NO VOLTAGE IS PRESENT.
Depending on the equipment configuration, the cir­cuit breaker can be mounted using different styles of hardware. The following steps describe how to mount the circuit breaker using standard hardware. When special hardware is needed (for example, with the electrical operator), the instruction leaflet describing the accessory also describes the special mounting arrangements.
2-6. To mount the circuit breaker, perform the following steps:
a. For individual surface mounting, drill mounting panel
using the drilling plan shown in Figure 2-5. For panel­board mounting, only load end support mounting
NOTICE
CAUTION
WARNING
Figure 2-4 Terminal Installation
TA300K/TA350K T300K/T350K Terminals
Circuit Breaker Terminal Conductors
Conductor Screws
Terminal Mounting Screw
TA400K, TA401K, TA402K, T400K Terminals
Terminal Mounting Screw
NOTICE
Loading...
+ 5 hidden pages