Cutler Hammer, Div of Eaton Corp JDB, JD, HJD, JDC, JW Instruction Sheet

...
I.L. 29C103G
JWC Circuit Breakers and Molded Case Switches
nel and equipment as well as all general and local health and safety laws, codes, and procedures.
The recommendations and information contained herein are based on Cutler-Hammer experience and judgment, but should not be considered to be all-inclusive or cov­ering every application or circumstance which may arise. If any questions arise, contact Cutler-Hammer for further information or instructions.
1. INTRODUCTION
General Information
The J-frame Series C circuit breaker (Figure 1-1) types JD, JDB, HJD, and JDC are 600 Vac maximum rated devices with inter changeable thermal-magnetic trip units rated 250A maximum continuous current. Circuit breaker types JW, HJW, and JWC are 660 Vac maxi­mum rated devices using interchangeable adjustable thermal/adjustable magnetic or electronic trip units rated up to 250A continuous current. The type JDB noninter­changeable trip circuit breaker is rated 600 Vac maxi­mum with a maximum continuous current rating of 250A. Refer to Table 1-1 for all available trip unit rat-
DO NOT ATTEMPT TO INSTALL OR PERFORM MAINTENANCE ON EQUIPMENT WHILE IT IS ENER­GIZED. DEATH, SEVERE PERSONAL INJURY, OR SUBSTANTIAL PROPERTY DAMAGE CAN RESULT FROM CONTACT WITH ENERGIZED EQUIPMENT. ALWAYS VERIFY THAT NO VOLTAGE IS PRESENT BEFORE PROCEEDING WITH THE TASK, AND ALWAYS FOLLOW GENERALLY ACCEPTED SAFE­TY PROCEDURES.
CUTLER-HAMMER IS NOT LIABLE FOR THE MISAP­PLICATION OR MISINSTALLATION OF ITS PROD­UCTS.
The user is cautioned to observe all recommendations, warnings, and cautions relating to the safety of person-
Figure 1-1 J-Frame Model D Series C Circuit Breaker with JT Trip Unit Installed
WARNING
Circuit Breaker Trip Unit Types Types Thermal-Magnetic Amperes I
n
Fixed Adjustable Adjustable Thermal Thermal Magnetic
of I
n
JDB 70 5 to 10 JD 90 HJD 100 JDC JW 125 100-125
HJW 150 125-160 JWC
175 200 160-200 225 250 200-250
Not UL listed. For adjustable thermal trip units, the magnetic setting is a multiple of the maximum thermal setting.
Table 1-1 Available Trip Unit Ratings
Installation Instructions for JDB, JD, HJD, JDC, JW HJW,
!
1
2
1 2
I.L. 29C103G
Page 2
Effective 1/10
ings. Model D circuit breakers are listed in accordance with Underwriters’ Laboratories, Inc. Standard UL489 and satisfy the (P1) requirements of the International Electrotechnical Commission Recommendations No. IEC 157-1 Model W circuit breakers satisfy the require­ments of IEC 947-2. Molded case switches are listed in accordance with UL 489.
2. INSTALLATION
The installation procedure consists of inspecting the cir­cuit breaker and, as applicable, installing the trip unit, accessories, interphase barriers and terminals; mount­ing the circuit breaker; connecting the line and load con­ductors; torquing terminals; and attaching terminal shields. Circuit breaker frames, trip units, accessories, mounting hardware, and unmounted terminals may be supplied in separate packages. To install the circuit breaker, perform the following steps.
JDB circuit breakers are factory sealed for reverse feed applications under UL489. UL requires that internal accessories be installed at the factory in this type of circuit breaker.
For hardware conversion kits and handle mechanisms required to replace existing Cutler-Hammer circuit breakers.
If required, internal accessory installation in any type of circuit breaker should be done before the circuit breaker is mounted and connected. Refer to individual accesso­ry instruction leaflets.
Circuit breaker mounting hardware is supplied separate­ly.
2-1. Make sure that the circuit breaker frame is suitable for the intended installation by comparing nameplate data with existing ratings and system requirements. Inspect the circuit breaker for completeness, and check for damage before mounting. Uninstalled cover mount­ing hardware is supplied in a plastic bag with the circuit breaker frame. (See Figure 2-1)
2-2. Remove installed cover screws and cover.
Figure 2-1 Cover Mounting Hardware
Pan Head Screws
Thread-Forming Screws
Figure 2-2 Cover Screw Installation Positions
NOTICE
On/
Off/
Screw, .190-32 x 3.13 Inch, Pan Head, Cross-Recessed.
Screw, No. 8 x 1.88 Inch, Pan Head, Cross-Recessed, Thread Forming.
Screw, No. 6 x 1.50 Inch, Pan Head, Cross-Recessed, Thread Forming (used with 4 Pole Only)
Note: Hatched lines show additional pole and screws for 4-pole circuit breaker.
I.L. 29C103G
Effective 1/10
The circuit breaker handle must be in the tripped or OFF position to remove the cover. Instructions for installing the trip unit accessories are supplied with the devices.
2-3. If not already installed, mount trip unit and acces­sories (if required) in circuit breaker frame.
WHEN REMOVED AND REINSTALLED, THREAD­FORMING SCREWS WILL TRY TO REFORM THE THREADS IN THE BASE. CARE SHOULD BE TAKEN EVERY TIME A THREAD-FORMING SCREW IS USED TO ENSURE THE SCREW STARTS IN THE ORIGINAL THREADS. DAMAGED THREADS CAN RESULT IN IMPROPER CIRCUIT BREAKER COVER RETENTION.
2-4. Install cover, and secure with pan-head screws fol­lowed by threadforming screws, as shown in Figure 2-2.
2-5. If not already installed, mount terminals as shown in Figure 2-3. When using terminal (Catalog No. TA250KB), secure the terminal to the circuit breaker using a 1/8-inch socket wrench and torque to 6-8 lb.-ft (8-11 N.m). After mounting the circuit breaker and
before installation of the conductors, the terminal mount­ing screw can be checked or retightened through the terminal when the conductor screw is removed. When using terminal (Catalog No. T250KB), secure the termi­nal to the circuit breaker using screw and nut. Torque to 7-9 lb.-in (0.8-1.0 N.m).
THE VOLTAGES IN ENERGIZED EQUIPMENT CAN CAUSE DEATH OR SEVERE PERSONAL INJURY. BEFORE MOUNTING THE CIRCUIT BREAKER IN AN ELECTRICAL SYSTEM, MAKE SURE THERE IS NO VOLTAGE PRESENT WHERE WORK IS TO BE PER­FORMED. SPECIAL ATTENTION SHOULD BE PAID TO REVERSE FEED APPLICATIONS TO ENSURE NO VOLTAGE IS PRESENT.
Depending on the equipment configuration, the cir­cuit breaker can be mounted using different styles of hardware. The following steps describe how to mount the circuit breaker using standard hardware. When special hardware is needed (for example, with the electrical operator), the instruction leaflet describing the accessory also describes the special mounting arrangements.
2-6. To mount the circuit breaker, perform the following steps:
a. For individual surface mounting, drill mounting panel
using the drilling plan shown in Figure 2-4. For panel­board mounting, only load end support mounting holes are required. For deadfront cover applications, cut out cover to correct escutcheon dimensions. (See Figure 2-5)
b. If circuit breaker includes factory- or field-installed
internal accessories, make sure that accessory wiring can be reached when the circuit breaker is mounted.
Labels with accessory connection schematic dia­grams are provided on the side of the circuit breaker. A note should be made of the diagrams if the labels cannot be seen when the circuit breaker is mounted.
Figure 2-3 Terminal Installation
NOTICE
NOTICE
!
CAUTION
!
WARNING
NOTICE
Terminal Connectors
TA250KB Terminal
Collar
Page 3
Collar
Socket Screw
Flat-Head Screw
T250KB Terminal
Nut
Torque cover screws to 18-23 lb-in (2-2.6 N.m.).
I.L. 29C103G
Page 4
Effective 1/10
c. Position circuit breaker on mounting surface.
d. Install circuit breaker mounting screws and washers.
Tighten screws firmly, but do not exceed 28 pound­inches (3 N.m.).
WHEN ALUMINUM CONDUCTORS ARE USED, THE APPLICATION OF A SUITABLE JOINT COMPOUND IS RECOMMENDED TO REDUCE THE POSSIBILITY OF TERMINAL OVERHEATING. OVERHEATING CAN CAUSE NUISANCE TRIPPING AND DAMAGE TO THE CIRCUIT BREAKER.
2-7. Connect line and load conductors and accessory leads.
2-8. If required, install terminal shield on circuit breaker cover with mounting screws provided.
2-9. After the circuit breaker is installed, check all mounting hardware and terminal connecting hardware for correct torque loading. Torque values for line/load terminals are given in Table 2-1 and on the circuit breaker nameplate.
3. MANUAL OPERATION, AND THERMAL­MAGNETIC ADJUSTMENT
Manual Operation
Manual operation of the circuit breaker is controlled by the circuit breaker handle and the PUSH-TO-TRIP but­ton in the trip unit. The circuit breaker handle has three positions, two of which are shown on the cover with raised lettering to indicate ON and OFF. On the sliding handle barrier, ON, OFF, and trip are also shown by a color-coded strip for each circuit breaker handle posi­tion: red for ON, white for tripped, and green for OFF. ON/OFF is also shown with the international symbols 1/0. (See Figure 3-1)
Circuit Breaker Reset
After an automatic or accessory initiated trip, or a manu­al Push-to-Trip operation, the circuit breaker is reset by moving the circuit breaker handle to the extreme OFF position.
In the event of a thermal trip in a thermal magnetic type trip unit, the circuit breaker cannot be reset until the thermal element in the trip unit cools.
Figure 2-5 Circuit Breaker Escutcheon Dimensions
CAUTION
NOTICE
Figure 2-4 Circuit Breaker Mounting Bolt Drilling Plans
2, 3 Pole Breakers
1.375
(34.37)
4.078
(103.58)
7.250
(184.15)
C
L
.688
(14.47)
.250-20
(M6-1.0)
Tap
(6 Holes)
C
Circuit Breaker Handle
L
.250-20
(M6-1.0)
Tap
(4 Holes)
Circuit Breaker
Handle
4-Pole Breakers
2.750
(69.85)
C
L
1.375
(34.37)
!
1.562
.344R (8.74)
3.938
(100.02)
.781
.188R (4.77)
(39.67)
(19.84)
2.922
(74.22)
3.50
(88.90)
Circuit Breaker Handle
C
L
.781
Circuit Breaker Handle
C
L
.875
(22.22)
I.L. 29C103G
Eective 1/10
No circuit breaker should be reclosed until the cause of trip is known and the situation rectified.
PUSH-TO-TRIP Button
The PUSH-TO-TRIP button checks the circuit breaker tripping function and is used to periodically exercise the operating mechanism in thermal-magnetic trip units. The button is designed to be operated by a small screwdriver.
Thermal-Magnetic Trip Unit Adjustment
The magnetic element of each pole of the trip unit can be adjusted by rotating the adjustment buttons on the front face of the trip unit with a screwdriver. The buttons have several settings, as indicated on the nameplate, with values in multiples of the trip unit ampere rating (In). (See Figure 3-2) To adjust the setting, rotate each but­ton clockwise until arrow on button points to desired set­ting.
4. INSPECTION AND FIELD TESTING
Series C molded case circuit breakers are designed to provide years of almost maintenance-free operation.
The following procedure describes how to inspect and test a circuit breaker in service.
Inspection
Circuit breakers in service should be inspected periodi­cally. The inspection should include the following checks (4-1 through 4-8):
THE VOLTAGES IN ENERGIZED EQUIPMENT CAN CAUSE DEATH OR SEVERE PERSONAL INJURY. BEFORE INSPECTING THE CIRCUIT BREAKER IN AN ELECTRICAL SYSTEM, MAKE SURE THERE IS NO VOLTAGE PRESENT WHERE WORK IS TO BE PERFORMED. SPECIAL ATTENTION SHOULD BE PAID TO REVERSE FEED APPLICATIONS TO ENSURE NO VOLTAGE IS PRESENT.
!
WARNING
Table 2-1 Terminal Types
Terminal Terminal Screw AWG Metric Wire Torque Cat. No. Material Head Wire Wire Type Value
Body Type Range Range lb-in
(N.m.)
T250KB Stainless Socket 4-350 MCM 25-185 Cu Only 180 (20)
Steel
TA250KB Aluminum Socket 4-350 MCM 25-185 Cu/AI 275 (31)
Figure 3-1 Circuit Breaker Manual Controls
Figure 3-2 Trip Unit Magnetic Trip Adjustment Buttons
Page 5
Handle Position Indicator Color
ON
TRIP
OFF (Reset)
International Symbols
ON OFF
Thermal-Magnetic Trip Unit Adjustment Button (3 Places)
Red – ON White – TRIP Green – OFF (Reset)
On/
Off/
Push-To-Trip Button
Adjustment Buttons
I.L. 29C103G
Page 6
Effective 1/10
MAKE SURE THAT CLEANING AGENTS OR SOL­VENTS USED TO CLEAN THE CIRCUIT BREAKER ARE SUITABLE FOR THE JOB. SOME COMMER­CIAL CLEANING AGENTS WILL DAMAGE THE NAMEPLATES OR MOLDED PARTS.
4-1. Remove dust, dirt, soot, grease, or moisture from the surface of the circuit breaker using a lint-free dry cloth, brush, or vacuum cleaner. Do not blow debris into circuit breaker. If contamination is found, look for the source and eliminate the problem.
4-2. Switch circuit breaker to ON and OFF several times to be sure that the mechanical linkages are free and do not bind. If mechanical linkages are not free, replace circuit breaker.
4-3. With the circuit breaker in the ON position, press the PUSH TO-TRIP button to mechanically trip the cir­cuit breaker. Trip, reset, and switch circuit breaker ON several times. If mechanism does not reset each time the circuit breaker is tripped, replace the circuit breaker.
4-4. Check base, cover, and operating handle for cracks, chipping, and discoloration. Circuit breakers should be replaced if cracks or severe discoloration is found.
4-5. Check terminals and connectors for looseness or signs of overheating. Overheating will show as discol­oration, melting, or blistering of conductor insulation, or as pitting or melting of conductor surfaces due to arcing. If there is no evidence of overheating or looseness, do not disturb or tighten the connections. If there is evi­dence of overheating, terminations should be cleaned or replaced. Before reenergizing the circuit breaker, all ter­minations and cable should be refurbished to the condi­tion when originally installed.
4-6. Check circuit breaker mounting hardware, Tighten if necessary.
4-7. Check area where circuit breaker is installed for any safety hazards, including personal safety and fire hazards. Exposure to certain types of chemicals can cause deterioration of electrical connections.
4-8. The operation of circuit breakers with electronic trip units can be field-tested periodically using the Seltronic test kit.
Field Testing
Any field testing should be done in accordance with applicable NEMA Standard.
!
CAUTION
I.L. 29C103G
Effective 1/10
Page 7
Style 6632C43H08 Printed in U.S.A.
/TQC
I.L. 29C103G
Page 8
Eaton Electrical, Inc.
1000 Cherrington parkway
Moon Township, PA 15108-4312 USA Tel: 1-800-525-2000
www.EatonElectrical.com
©2010 Eaton corporation All Rights Reserved
Printed USA/TQC
Eective January 2010
Loading...