Cutler Hammer, Div of Eaton Corp EVR010208D208YAS Data Sheet

Electronic voltage regulator
Microprocessor-controlled tap changer (10–500 kVA, three-phase)
Eaton’s electronic voltage regulator (EVR) reduces equipment downtime through constant voltage regulation. It is the ideal solution for equipment or facilities experiencing brownouts and voltage regulation problems. The EVR’s patented design offers a high in-rush current, rapid response and operating advantages over other manufacturers.
Overview
Seven taps per phase are used for optimal voltage regulation. Also, the EVR is a low output impedance, shielded isolation transformer. As a result of the low impedance, load changes do not affect other equipment connecting the system.
The EVR’s patented design ensures high efficiency at 97% and 1000% in-rush capability. It is equipped with a thermal­magnetic breaker that allows for proper system coordination to prevent nuisance trips.
The EVR provides the triple function of isolation, noise attenu­ation and voltage regulation. The power transformer supplies the first two functions. The third function, voltage regulation, is supplied by the SCRs connected to taps on the power transformer. This sequential tap-changing design eliminates voltage “over­shoot” from typical electronic voltage regulators, providing a seamless transition between the required power transformer taps.
EVR features
•
±3% voltage output for a +10/–23% voltage input
•
Power factor—the EVR is not affected by load power factor
•
Total harmonic distortion (THD)—the EVR adds less than 1% THD
•
High Efficiency—97%
•
Wide input frequency range —the EVR operates within a broad input frequency range from 57–63 Hz
•
Seven taps per phase used to provide optimal voltage regulation
•
Fail-safe bypass circuit, triple­shielded isolation transformer and overtemperature protection
•
Two-year parts and labor warranty with no startup required
EVR Specifications
Technology Electronic tap changer Input voltages 208–600V, three-phase (three-wire) Input voltage range +10% to –23% of nominal rated input Output voltage ±3% of nominal Response time 1/2 cycle Frequency 60 Hz, ±3% Efficiency 97% typical Line regulation Output is ±3% of nominal for input variations of +10% to –23% of nominal Load regulation Output is maintained within 3% from no load to full load Correction time Output will be corrected in one step to within ±3% of nominal in 1.5 cycles or less Harmonic distortion Less than 1.0% THD Noise attenuation
Common mode Normal mode
140 dB
3 dB down at 1000 Hz, 40 dB/decade to below 50 Hz with resistive load Turn-on characteristics When energized, voltage overshoot will be less than 5% of nominal for 1 cycle or less Overload rating 1000% for 1 cycle and 200% for 10 seconds Ambient rating –10º to 40ºC Monitoring Three green LEDs (phase power on indication), one red LED (alert indication) Surge protection (optional) CVL 100 kA SPD device Input breaker MCCB rated 125% of full rated current Bypass switch Normal and bypass selector Metering (optional) Standard metering—voltage and current
Premium metering—voltage, current, frequency, power, energy,
communications capabilities Warranty 2-year parts and labor
For custom design, call the support number below.
Application support
If you are having trouble under­standing a problem related to power quality, reliability or energy management, call an application engineer at 800-809-2772 (Option 1).
EVR ordering guidelines
EVR XXXX XXXX XXXX X X XX
kVA Ratings and Dimensions
kVA Weight BTUs/ Dimensions W x D x H in inches (mm) (lbs) hr
0010 440 1705 21.00 x 29.00 x 30.00 (533.4 x 736.6 x 762.0) 0015 520 2557 21.00 x 29.00 x 30.00 (533.4 x 736.6 x 762.0) 0025 700 2560 21.00 x 29.00 x 44.00 (533.4 x 736.6 x 1117.6) 0030 720 3090 21.00 x 29.00 x 44.00 (533.4 x 736.6 x 1117.6) 0045 950 4600 45.00 x 29.00 x 44.00 (1143.0 x 736.6 x 1117.6) 0050 950 5525 45.00 x 29.00 x 44.00 (1143.0 x 736.6 x 1117.6) 0075 1100 12,787 45.00 x 29.00 x 44.00 (1143.0 x 736.6 x 1117.6) 0100 1660 17,050 45.00 x 29.00 x 44.00 (1143.0 x 736.6 x 1117.6) 0125 1980 21,312 45.00 x 29.00 x 44.00 (1143.0 x 736.6 x 1117.6) 0150 2200 25,575 45.00 x 29.00 x 44.00 (1143.0 x 736.6 x 1117.6) 0225 3300 23,000 56.00 x 41.50 x 77.00 (1422.4 x 1054.1 x 1955.8) 0300 4000 30,750 56.00 x 41.50 x 77.00 (1422.4 x 1054.1 x 1955.8) 0500 5500 51,250 72.00 x 48.50 x 77.00 (1828.8 x 1231.9 x 1955.8)
Nominal Input Voltage
Delta Input: L, L, L, G
240D = 240 400D = 400 480D = 480 600D = 600
Nominal Output Voltage
Wye Output: L, L, L, N, G
208Y = 120/208 400Y = 230/400 480Y = 277/480 600Y = 347/600
Metering
M1 = Standard metering (IQ 110) M2 = Premium metering (IQ 220) Blank = No metering option
Surge Protection
X = No S = Yes
Frequency
A = 60 Hz B = 50 Hz
Eaton Corporation
Electrical Sector 1111 Superior Ave. Cleveland, OH 44114 United States 877-ETN-CARE (877-386-2273) Eaton.com
© 2010 Eaton Corporation All Rights Reserved Printed in USA Publication No. PA01002001E / Z10470 December 2010