Cutler Hammer, Div of Eaton Corp EDC Series Current Sensor Catalog

Page 1
Top Screw Terminals
Three Jumper­Selectable Ranges
Split-Core Housing
Internal Power Regulation
September 2009
EDC Series Current Sensor CurrentWatch Current Sensors
Contents
Overview . . . . . . . . . . . . . . . . . . . . 1
Model Selection,
Switches . . . . . . . . . . . . . . . . . . . . 2
Model Selection,
Accessories . . . . . . . . . . . . . . . . . 3
Wiring Diagram . . . . . . . . . . . . . . . 3
Specifications . . . . . . . . . . . . . . . . 3
Dimensions . . . . . . . . . . . . . . . . . . 4
The CurrentWatch EDC Series from Eaton’s electrical business combines a hall effect sensor and signal conditioner into a single package for use in DC current applications up to 300A. The EDC Series has jumper­selected current input ranges and industry standard outputs: 4 – 20 mA, 0 – 5V DC or 0 – 10V DC. Available in split-core models for quick and easy installation.
For typical applications of the CurrentWatch™ EDC Series, see listing to the right.
Approvals
UL Listed (Pending)
Unless otherwise noted, the products contained in this document are not designed or intended for use in human safety applications.
CurrentWatch™ Current Sensors EDC Series Current Sensor
CA05311009E
Current Sensing for DC Loads up to 300A with Analog Outputs
Product Features
Jumper-Selectable Ranges — Reduces inventory and eliminates zero or
span pots
Isolation — Output is magnetically isolated from the input for safety, also
eliminating insertion loss (voltage drop)
Internal Power Regulation — Cuts installation costs and works well, even
with unregulated power
Split Core Design and Built-In Mounting Brackets — Makes installation
quick and easy
UL and CE Approved
Typical Applications
1
Battery Banks — Monitors load current, monitors charging current and
verifies operation
Transportation — Measures traction power or auxiliary loads
Electric Heating Elements — Monitors heater loads with a faster response
time than temperature sensors
For Customer Service in the U.S. call 1-877-ETN CARE (386-2273) ,
CA05311009E For more information visit: www.eaton.com
in Canada call 1-800-268-3578 .
For Application Assistance in the U.S. and Canada
call 1-800-426-9184 .
Page 2
CurrentWatch™ Current Sensors
2
EDC Series Current Sensor
September 2009
Example Application — CurrentWatch EDC Series
Battery Charging System
Charging
System
Load
Model Selection — CurrentWatch EDC Series
Power Supply Aperture Size Output Graph Output Signal Current Range Catalog Number
Top Terminal Current Sensors
Split-Core Housings
Split-Core Housings
24V AC/DC 0.85 in. (21.6 mm) 0 – 5V DC 50, 75 or 100A EDC205SP
0.85 in. (21.6 mm) -10 – 10V DC 0 – 100A
100%
50%
0%
(Magnitude Only)
- Amps
+10V DC
Unipolar
0+ Amps
100%
50%
0%
- Amps
0
0+ Amps
100, 150 or 200A EDC305SP
150, 225 or 300A EDC405SP
0 – 10V DC 50, 75 or 100A EDC210SP
100, 150 or 200A EDC310SP
150, 225 or 300A EDC410SP
4 – 20 mA 50, 75 or 100A EDC2420SP
100, 150 or 200A EDC3420SP
150, 225 or 300A EDC4420SP
EDCB100SP
0 – 200A
0 – 300A
EDCB200SP
EDCB300SP
Solid-Core Housings
Stocked product, typical order quantities guaranteed in stock.
0.75 in. (19 mm) 4 – 20 mA 5, 10 or 20A
-10V DC
100%
50%
0%
- Max.
Amps
- Amps
0+ Max.
0+ Amps
For more information visit: www.eaton.com
Amps
EDC1420SC
CA05311009E
Page 3
September 2009
Accessories — CurrentWatch EDC Series
Description Catalog Number
DIN Rail Mounting Kit (Sensor pictured for reference and not included in kit)
Stocked product, typical order quantities guaranteed in stock.
Wiring Diagram — CurrentWatch EDC Series
24V AC/DC
CurrentWatch™ Current Sensors EDC Series Current Sensor
EDINKIT
Output is powered by EDC Sensor.
3
Range
Jumper
1(-) 2(+) 3(-) 4(+)
Power Output
Specifications — CurrentWatch EDC Series
Description Models with 0 – 5V DC Output Models with 0 – 10V DC Output Models with 4 – 20 mA Output
Power Supply 24V AC/DC (22 – 38V AC/DC) 2 VA Max.
Output Signal 0 – 5V DC 0 – 10V DC 4 – 20 mA
Output Limit 5.75V DC 11.5V DC 23 mA
Accuracy Solid-Core Models: 1% FS
Response Time Solid-Core Models: 20 mS (to 90% of step change)
Frequency Range DC
Loading 25 k
Isolation Voltage 3 kV (monitored line to output)
Linearity 0.75% FS
Current Ranges Field selectable ranges from 0 – 300A
Sensing Aperture Solid-Core Housings: 0.75 in. (19 mm) dia.
Environmental Operating Temperature: -4 to 122°F (-20 to 50°C)
Approvals UL 508 Industrial Control Equipment (Pending, USA and Canada), CE Certified
min. 50 k min. 650 max.
Split-Core Models: 100 mS (to 90% of step change)
Split-Core Models: 2% FS
300A Models: 1.5% FS
Split-Core Housings: 0.85 in. (21.6 mm) sq.
Humidity: 0 – 95% RH, Non-condensing
CA05311009E For more information visit: www.eaton.com
Page 4
CurrentWatch™ Current Sensors
4
EDC Series Current Sensor
Approximate Dimensions — CurrentWatch EDC Series
Description Approximate Dimensions in Inches (mm)
Solid-Core Housings
1.50
(38.1)
3.38
(85.9)
September 2009
3.87
(98.3)
2.90
(73.7)
0.80
(20.3)
Split-Core Housings
1.18 (30)
0.45
(11.4)
0.85
(21.6)
3.53
(89.7)
(77.2)
2.40 (61)
0.75 Dia. (19.1)
0.19 (4.8) Dia.
3.04
0.45
(11.4)
0.85
(21.7)
2.25
(57.2)
For more information visit: www.eaton.com
CA05311009E
Loading...