Cutler Hammer, Div of Eaton Corp ECS7 Series Current Switches Catalog

CurrentWatch™ Current Sensors
1
CA05311007E
August 2007
ECS7 Series Current Switch CurrentWatch Current Sensors
Contents
Overview . . . . . . . . . . . . . . . . . . . . . 1
Model Selection,
Switches . . . . . . . . . . . . . . . . . . . . 2
Model Selection,
Accessories . . . . . . . . . . . . . . . . . . 3
Wiring Diagram . . . . . . . . . . . . . . . 3
Specifications . . . . . . . . . . . . . . . . . 3
Dimensions . . . . . . . . . . . . . . . . . . . 4
The CurrentWatch ECS7 Series load monitoring switches from Eaton’s electrical business are designed for overload, underload or operating window applications. Upon sensing an average operating current, the ECS7 Series self-learns and estab­lishes a limit-alarm trip point based on ± 15% of the average expected current draw. The ECS7 Series is available in solid- or split-core hous­ing styles.
For typical applications of the Current­Watch ECS7 Series, see listing to the right.
Approvals
UL Listed
C-UL Listed
Self-Calibrating AC Current Switch with Solid-State Outputs
Smart, Self-Calibrating Sensors
Solid- and Split-Core
with Limit Alarm Trip Points
Models, All Self-Powered
Built-In Mounting Tabs for Quick Installation
Product Features
Self-Powered and Self-Calibrating — Reduces installation costs
Status Monitoring, Overload and Operating Window Options — Choose
the operating style that matches your application
Universal Output — AC or DC compatibility with any automation system
UL, C-UL and CE Approved — Accepted worldwide
Typical Applications
Conveyors — Use current overload models to detect conveyor jams
Unless otherwise noted, the products contained in this document are not designed or intended for use in human safety applications.
caused by scenarios such as
Electronic Proof of Flow — More reliable than electro-mechanical pressure
or flow switches, with no need for pipe or duct penetrations
Pump Protection — Provides overload (jams) and underload (suction loss)
indication
For more information visit: www.eaton.com
side-by-sides
For Customer Service in the U.S. call 1-877-ETN CARE (386-2273) ,
in Canada call 1-800-268-3578 .
For Application Assistance in the U.S. and Canada
call 1-800-426-9184 .
CA05311007E
August 2007
Model Selection — CurrentWatch ECS7 Series
Power Supply Output Type Aperture Size Intelligent Logic Catalog Number
Front and Top Terminal Switches
Solid-Core Housing
Split-Core Housing
Self-Powered (No External Power Needed)
CurrentWatch™ Current Sensors ECS7 Series Current Switches
Normally Open 0.74 in. (19 mm) Over/Underload, 1.5 – 150A
Self-Calibrating
Overload Only, 1.5 – 150A Self-Calibrating
Underload Only, 1.5 – 150A Self-Calibrating
0.85 in. (21.6 mm) Over/UnderLoad, 2.8 – 150A Self-Calibrating
Overload Only, 2.8 – 150A Self-Calibrating
Underload Only, 2.8 – 150A Self-Calibrating
ECS701SC
ECS700SC
ECS702SC
ECS711SP
ECS710SP
ECS712SP
2
Output is closed when current is within ± 15% window.
Stocked product, typical order quantities guaranteed in stock.
Current Switch Operation
Model Output Diagram
Underload Only Models
Output Tripped
LOAD
Amps
Output in
“Normal” State
Overload Only Models
Output Tripped
LOAD
Amps
Output in
“Normal” State
Over/Underload Models
Output is closed when current is within ±15% window.
Output in
“Normal” State
LOAD
Amps
Output in
“Normal” State
Setpoint
Setpoint
Overload Setpoint Output Tripped Underload Setpoint
CA05311007E For more information visit: www.eaton.com