Reduced Voltage Motor Starters
Solid-State Controllers
1.1
Technical Data and Specifications
DS6 Soft Start Controllers
Description Unit DS6-34DSX041N0-N DS6-34DSX055N0-N DS6-34DSX068N0-N DS6-34DSX081N0-N
General
Standards IEC/EN 60947-4-2 IEC/EN 60947-4-2 IEC/EN 60947-4-2 IEC/EN 60947-4-2
Certifications UL/CE/C-Tick/CSA UL/CE/C-Tick/CSA UL/CE/C-Tick/CSA UL/CE/C-Tick/CSA
Ambient temperature
(operation)
Ambient temperature
(storage)
Altitude 0–1000m, above 1000m de-rate
Installation Vertical Vertical Vertical Vertical
Protection degree IP 20 IP 20 IP 20 IP 20
Protection against contact Back of hand and finger-proof
Overvoltage category/
pollution degree
Shock resistance 8g/11 ms 8g/11 ms 8g/11 ms 8g/11 ms
Vibration resistance
according to EN 60721-3-2
Dimensions in inches (mm)
(W x H x D)
Weight in lbs (kg) 4.00 (1.8) 4.00 (1.8) 4.00 (1.8) 4.00 (1.8)
Main Circuit
Rated operation voltage V 200–460 Vac 200–460 Vac 200–460 Vac 200–460 Vac
Mains frequency Hz 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz
Rated impulse
withstand voltage
Rated operation current I
Motor Power Ratings
200V hp 10 15 20 25
230V hp 10 20 25 30
460V hp 30 40 50 60
230V kW 11 15 15 22
400V kW 22 30 37 45
Overload cycle according
to EN 60947-4-2
°C 0 to 40°C, above 40°C de-rate
°C –25 to +55°C –25 to +55°C –25 to +55°C –25 to +55°C
U
imp
50 μs
e
linearly by 1% of rated current per
Celsius to 60°C
linearly by 1% of rated current per
100m to a maximum of 2000m
(from front face)
II/2 II/2 II/2 II/2
2M2 2M2 2M2 2M2
3.66 x 6.89 x 5.47
(93.0 x 175.0 x 138.9)
1.2/
4 kV 4 kV 4 kV 4 kV
40 52 65 77
40A: AC53a; 3–5; 75–10 52A: AC53a; 3–5; 75–10 65A: AC53a; 3–5; 75–10 77A: AC53a; 3–5; 75–10
0 to 40°C, above 40°C de-rate
linearly by 1% of rated current per
Celsius to 60°C
0–1000m, above 1000m de-rate
linearly by 1% of rated current per
100m to a maximum of 2000m
Back of hand and finger-proof
(from front face)
3.66 x 6.89 x 5.47
(93.0 x 175.0 x 138.9)
0 to 40°C, above 40°C de-rate
linearly by 1% of rated current per
Celsius to 60°C
0–1000m, above 1000m de-rate
linearly by 1% of rated current per
100m to a maximum of 2000m
Back of hand and finger-proof
(from front face)
3.66 x 6.89 x 5.47
(93.0 x 175.0 x 138.9)
0 to 40°C, above 40°C de-rate
linearly by 1% of rated current per
Celsius to 60°C
0–1000m, above 1000m de-rate
linearly by 1% of rated current per
100m to a maximum of 2000m
Back of hand and finger-proof
(from front face)
3.66 x 6.89 x 5.47
(93.0 x 175.0 x 138.9)
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Reduced Voltage Motor Starters
1.1
DS6 Soft Start Controllers, continued
1
Description Unit DS6-34DSX041N0-N DS6-34DSX055N0-N DS6-34DSX068N0-N DS6-34DSX081N0-N
Wire Specifications
1
Power terminals (box terminals)
Single conductor AWG 12–2/0 12–2/0 12–2/0 12–2/0
1
Terminal torque lb-in 53–80 53–80 53–80 53–80
1
Control-signals
Single conductor AWG 16 min. 16 min. 16 min. 16 min.
1
Terminal torque lb-in 3.5 3.5 3.5 3.5
Powerpart
1
Rated impulse
withstand voltage
1
Control Commands
Supply voltage control board U
1
Nominal voltage Vdc +24 Vdc +10%/–15% +24 Vdc +10%/–15% +24 Vdc +10%/–15% +24 Vdc +10%/–15%
Nominal current ramp, TOR mA 65 65 65 65
1
Current peak
(closing shorting
1
contactors)
Voltage to the control terminals (rated control voltage)
1
DC driven +24 Vdc +10%/–15% +24 Vdc +10%/–15% +24 Vdc +10%/–15% +24 Vdc +10%/–15%
Input current at 24 VdcmA14141414
1
Relay Outputs
Number of relays 2 (TOR, ready) 2 (TOR, ready) 2 (TOR, ready) 2 (TOR, ready)
1
Maximum voltage V 250 Vac, 60 Vdc 250 Vac, 60 Vdc 250 Vac, 60 Vdc 250 Vac, 60 Vdc
1
Maximum current A 3 amps, resistive 3 amps, resistive 3 amps, resistive 3 amps, resistive
Soft Start Functions
1
Ramp times
Start ramp s 1–30 1–30 1–30 1–30
1
Stop ramp s 0–30 0–30 0–30 0–30
Initial voltage % line voltage 30–92% 30–92% 30–92% 30–92%
1
Solid-State Controllers
1.2/
U
imp
50 μs
s
4 kV 4 kV 4 kV 4 kV
600 mA/50 ms 600 mA/50 ms 600 mA/50 ms 600 mA/50 ms
1