Cutler Hammer, Div of Eaton Corp DK, KDB, KD, HKD, KDC Installation Guide

...
Instruction Leaflet IL 29C104E
Supersedes IL 29C104D Dated 02/12
Installation Instruc tions for DK, KDB, KD, HKD, KDC, KW, HKW, KWC, CKD, CHKD Circuit Breakers and Molded Case Switches
Contents
Introduction . . . .. . . . .. . . .. . . .. . . . . . .. . . .. . . . .2
Installation . . . . .. . . . .. . . .. . . .. . . .. . . . . . .. . . . 3
Replacement of Existing Eaton Circuit Breakers
Types DA, JA, KA, HKA, LB, LBB, HLB . . 6 Manual Operation and Thermal Magnetic Trip
Unit Adjustment . . . . . .. . . . . . . . . .. .7
Inspection and Field Testing .. . . .. . . .. . . .. . . .. 8
Page noitpircseD
Installation Instructions for DK, KDB, KD, HKD, KDC, KW, HKW,
KWC, CKD, CHKD Circuit Breakers and Molded Case Switches
WARNING
DO NOT ATTEMPT TO INSTALL OR PERFORM MAINTENANCE ON EQUIPMENT WHILE IT IS ENER­GIZED. DEATH, SEVERE PERSONAL INJURY, OR SUBSTANTIAL PROPERTY DAMAGE CAN RESULT FROM CONTACT WITH ENERGIZED EQUIPMENT. ALWAYS VERIFY THAT NO VOLTAGE IS PRESENT BEFORE PROCEEDING WITH THE TASK, AND ALWAYS FOLLOW GENERALLY ACCEPTED SAFE­TY PROCEDURES.
EATON IS NOT LIABLE FOR THE MISAPPLICATION OR MISINSTALLATION OF ITS PRODUCTS.
The user is cautioned to observe all recommendations, warnings, and cautions relating to the safety of person­nel and equipment as well as all general and local health and safety laws, codes, and procedures.
The recommendations and information contained herein are based on Eaton experience and judgment, but should not be considered to be all-inclusive or covering every application or circumstance which may arise. If any questions arise, contact Eaton for further informa- tion or instructions.
1. INTRODUCTION
General Information
The K-frame Series C circuit breaker (Figure 1-1) types KD, HKD, and KDC are 600 Vac maximum rated devices with interchangeable thermal-magnetic or elec­tronic (Seltronic) trip units rated 400A maximum continu­ous current. Circuit breaker types KW, HKW, and KWC are 660 Vac maximum rated devices using interchange­able adjustable thermal/adjustable magnetic or electron­ic trip units rated up to 400A continu type KDB noninterchangeable trip circuit breaker is rated 600 Vac maximum with a maximum continuous current rating of 400A. The type DK 240 Vac maximum circuit breaker is also a noninterchangeable trip device with trip unit ratings from 250A to 400A. Refer to Table 4-1 on page 9 for all av breakers are listed in accordance with Underwriters Laboratories, Inc. Standard UL489 and satisfy the (P1) requirements of the International Electrotechnical Commission Recommendations No. IEC 157-1. Model W circuit breakers satisfy the requirements of IEC C947-
2. Molded case switches are listed in accordance with UL 489.
ailable trip unit ratings. Model D circuit
o
us current. The
100 Percent Rated K-Frame Circuit Breakers
CKD and CHKD circuit breakers are suitable for contin­uous operation at 100 percent of the frame rating if used with an 90°C insulated wire and AL9CU terminals in an enclosure which measures at least 24” high x 15” wide x 6” deep. Ventilation is not required in an enclo­sure having these minimum dimensions. CKD and CHKD 100 percent rated circuit breakers use electronic trip units only.
Figure 1-1 K-Frame Model D Series C Circuit Breaker Frame with KT Trip Unit Installed
2
EATON CORPORATION
ers. Instructions are also provided for replacement of existing Eaton circuit breaker types DA, LB, LBB, HLB, JA, KA, and HKA. For this publication, the term circuit breaker shall also include the molded case switch.
Installation Instructions for DK, KDB, KD, HKD, KDC, KW, HKW, KWC, CKD, CHKD Circuit Breaker and Molded Case Switches
Pan Head Screws
3 - Pole 4 - Pole No. 8 x 1.63 in, Flat - Head 6 3 .190 - 32 x 3.125 in, Pan - Head 2 7
Flat Head, Thread Forming Screws
Figure 2-1 Cover Mounting Hardware
Terminal Cover
e installation procedure consists of
Figure 2-3 Terminal Cover Installation
,
Dovetails
Mounting Slots
1
3P
4P
2
2
1
3
1
3P
2
4P
Screw, No. 8x 1.63 Inch, Flat Head, Cross-Recessed,
1
Thread Forming. Screw .190-32 x 3.125 Inch Pan Head, Cross-Recessed.
2
Note: Hatched lines show additional pole and screw for
4-pole circuit breaker.
Figure 2-2 Cover Screw Installation Positions
2. INSTALLATION
1
3P
2
The installation procedure consist of inspecting the cir-
4P
cuit breaker and, as applicable, installing the trip unit and rating plug, accessories, interphase barriers, and termi­nals; mounting the circuit breaker; connecting the line
2
and load conductors; torquing terminals; and attaching terminal shields. Circuit breaker frames, trip units, rating plugs, accesories, mounting hardware, and unmounted
1
terminals may be supplied in separate packages. To install the circuit breaker, perform the following steps.
NOTICE
If circuit breaker is replacing a DA, JA, KA, HKA, LB, LBB, or HLB circuit breaker, refer to section 3 of
2
DK and KDB circuit breakers are factory sealed for reverse feed applications under UL489. UL requires that internal accessories be installed at the factory in these types of circuit breakers.
1
3P
NOTICE
If required, internal accessory installation in any type of circuit breaker should be done before the
EATONON CORPORATION
3
Loading...
+ 7 hidden pages