PowerXL series
DH1 HVAC/R drives
Next-generation drives for today’s demands
The DH1 HVAC/R drives are part of the Eaton next
generation PowerXLE series of variable frequency
drives specifically engineered to exceed the demands
of the HVAC/R market. With an industry-leading energy
efficiency algorithm, high short-circuit current rating
and robust design, the DH1 offers customers increased
efficiency, safety and reliability.
Features
•
Graphic LCD keypad display
•
Active Energy ControlT
algorithm
•
On-board communications:
• ModbusT/TCP
• Modbus RTU
• BACnetT MS/TP
• BACnet/IP
•
Onboard I/O:
• 8DI, 1DO
• 2AI, 2AO
• 2 FC relays and 1 FA relay
•
Real-time clock with
battery backup
•
5% DC link choke
•
Standard applications:
• Basic
• Multi-PID
• Multi-purpose
•
Advanced configuration
PC tool
Benets
•
Variable torque rated for
HVAC/R applications
•
Easy menu navigation
•
Two configurable
keypad soft keys
•
Conformal coated
boards standard
Product range
•
208–240 V, 1–125 hp,
312 A, 90 kW
•
380–500 V, 1.5–250 hp,
310 A, 160 kW
•
525–600 V, 3–250 hp,
250 A, 160 kW
•
Type 1/IP21 or
Type 12/IP54 packaging
Catalog numbering system
Series Power part Options
D H1 – 3 4 011 D N – C 21 C
Basic naming
D = Drive
Series
H1 = HVAC
Phase reference
3 = 3~ input /3~output
Input/output voltage
2 = 230 V (208–240 V, –15%, +10%)
4 = 400 V (380–500 V, –15%, +10%)
5 = 600 V (252–600 V, –15%, +10%)
208–240 V 380–500 V 525–600 V
4D8 = 4.8 A, 1.0 hp, 0.75 kW
6D6 = 6.6 A, 1.5 hp, 1.1 kW
7D8 = 7.8 A, 2.0 hp, 1.5 kW
011 = 11 A, 3.0 hp, 2.2 kW
012 =12.5 A, 4.0 hp, 3.0 kW
017 = 17.5 A, 5.0 hp, 3.7 kW
025 = 25 A, 7.5 hp, 5.5 kW
031 = 31 A, 10 hp, 7.5 kW
048 = 48 A, 15 hp, 11 kW
061 = 61 A, 20 hp, 15 kW
075 = 75 A, 25 hp, 18.5 kW
088 = 88 A, 30 hp, 22 kW
114 = 114 A , 40 hp, 30 kW
143 = 143 A, 50 hp, 37 kW
170 = 170 A, 60 hp, 45 kW
211 = 211 A, 75 hp, 55 kW
261 = 261 A, 100 hp, 75 kW
312 = 312 A, 125 hp, 90 kW
Output current rating (VT)
3D3 = 3.3 A, 1.5 hp, 1.1 kW
4D3 = 4.3 A, 2.0 hp, 1.5 kW
5D6 = 5.6, 3.0 hp, 2.2 kW
7D6 = 7.6 A, 4.0 hp, 3 kW
9D0 = 9 A, 5.0 hp, 4 kW
012 = 12 A, 7.5 hp, 5.5 kW
016 = 16 A, 10 hp, 7.5 kW
023 = 23 A, 15 hp, 11 kW
031 = 31 A, 20 hp, 15 kW
038 = 38 A, 25 hp, 18.5 kW
046 = 46 A, 30 hp, 22 kW
061 = 61 A, 40 hp, 30 kW
072 = 72 A, 50 hp, 37 kW
087 = 87 A, 60 hp, 45 kW
105 = 105 A, 75 hp, 55 kW
140 = 140 A, 100 hp, 75 kW
170 = 170 A, 125 hp, 90 kW
205 = 205 A, 150 hp, 110 kW
261 = 261 A, 200 hp, 132 kW
310 = 310 A, 250 hp, 160 kW
Frames and power ranges
Frame size Voltage hp (V T/IL) kW Amperes (VT/IL)
FR0 230 Vac 1–2 0.75–1.5 4.8–7.8
480 Vac 1.5–5 1.1–3 3.3–7.6
FR1 230 Vac 1–4 0.75–3 4.8-12.5
480 Vac 1.5–7.5 1.1–5.5 3.3–12
575 Vac 3–7.5 2.2–5.5 4.5–10
FR2 230 Vac 5–10 3.7–7.5 17.5–31
480 Vac 10–20 7.5–15 16–31
575 Vac 10–20 7.5–15 13.5–22
FR3 230 Vac 15–20 11–15 48–61
480 Vac 25–40 18.5–30 38–61
575 Vac 25–40 18.5–30 27–41
FR4 230 Vac 25–40 18.5–30 75–114
480 Vac 50–75 37–55 72–105
575 Vac 50–75 37–55 52–80
FR5 230 Vac 50–75 37–55 143–211
480 Vac 100–150 75–110 140–205
575 Vac 100–150 75–110 100–144
FR6 230 Vac 100–125 75–90 261–312
480 Vac 200–250 132–160 261–310
575 Vac 200–250 150–187 208–250
Coating of boards
C = Coated
Enclosure (IP rating)
20 = IP20 (FR0 only)
4D5 = 4.5 A, 3 hp, 2.2 kW
7D5 = 7.5 A, 5.0 hp, 3.7 kW
010 = 10 A, 7.5 hp, 5.5 kW
013 = 13.5 A, 10 hp, 7.5 kW
018 = 18 A, 15 hp, 11 kW
022 = 22 A, 20 hp, 15 kW
21 = IP21/Type 1
54 = IP54/Type 12
Display option
C = LCD (graphical)
W = No display
027 = 27 A, 25 hp, 18.5 kW
034 = 34 A, 30 hp, 22 kW
041 = 41 A, 40 hp, 30 kW
052 = 52 A, 50 hp, 37 kW
062 = 62 A, 60 hp, 45 kW
080 = 80 A, 75 hp, 55 kW
100 = 100 A, 100 hp, 75 kW
125 = 125 A, 125 hp, 90 kW
144 = 144 A, 150 hp, 110 kW
208 = 208 A, 200 hp, 150 kW
250 = 250 A, 250 hp, 187 kW
Internal brake chopper
N = No brake chopper
B = Brake chopper
Internal EMC filter
D = DC choke only
E = EMC filter only
F = Internal EMC filter and DC choke
N = No EMC filter, no DC choke
Input ratings
Description Specification
Input voltage (Bin) 208–240 V, 380–500 V, 525–600 V, –15 to 10%
Input frequency (fin) 50–60 Hz (variation up to 45–66 Hz)
Connection to power Up to one connection every 60 seconds
Short-circuit withstand rating 100 kAIC (with fuses and circuit breakers)
Output ratings
Description Specification
Output voltage 0 to Vin
VT/IL overload Overload 1.1 x IL (1 min./10 min.)
Initial output current 200% (2 sec./20 sec.)
Output frequency 0–400 Hz (standard)
Frequency resolution 0.01 Hz
Ambient conditions
Description Specification
Operating temperature –10 ° C (no frost) to +50 ° C, up to +60 ° C
withderating
Storage temperature –40 °C to +70 ° C
Relative humidity 0–95% RH, noncondensing, non-corrosive
Altitude 100% load capacity (no derating) up to
3280 ft (1000 m); 1% derating for each
328 ft (100 m) above 3280 ft (1000 m)
9843 ft (3000 m) maximum
Eaton
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Eaton.com
© 2018 Eaton
All Rights Reserved
Printed in USA
Publication No. PA040023EN / Z20482
February 2018
Eaton is a registered trademark.
All other trademarks are property
of their respective owners.
Follow us on social media to get the
latest product and support information.