Cutler Hammer, Div of Eaton Corp DH1 Application Information

PowerXL DH1 Series VFD
Application manual
Effective May 2018
Supports Firmware Version Bundle: DH1-V0003-ETN
PowerXL DH1 series variable frequency drives
Table of contents
SAFETY
Before commencing the installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...xii
Definitions and symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..xiii
Hazardous high voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..xiii
Warnings and cautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..xiii
Important safety information ...........................................xiv
CHAPTER 1—PowerXL DH1 series overview
How to use this manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ....1
Receiving and inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...1
Real time clock battery activation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .....1
Rating label . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ....2
Carton labels (U.S. and Europe) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ....2
Catalog number system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ....3
Power ratings and product selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .....4
Chapter 2—Keypad overview
Keypad buttons .......................................................9
LED lights ..........................................................11
LCD display .........................................................11
Chapter 3—Menu overview
Main menu page .....................................................14
Menu navigation .....................................................14
Menu structure ......................................................15
M—Monitor .........................................................16
F—Fault ............................................................17
Pop-up fault .........................................................18
Fault history .........................................................19
Fault Log ...........................................................20
P—Parameter .......................................................20
Value edit ...........................................................25
T—Favorite .........................................................26
Chapter 4—Startup
Startup wizard page ...................................................27
Startup wizard .......................................................27
PID Mini-wizard ......................................................28
Chapter 5—Basic application
Introduction .........................................................29
I/O Controls .........................................................29
Force open/force close selection ........................................30
DIGIN Selection .....................................................30
Option board digIN selection ............................................30
Timer channel selection ................................................30
iv
PowerXL DH1 series variable frequency drives
Table of contents, continued
Basic Application Control I/O configuration .................................31
Control I/O configuration ...............................................33
Basic application—parameters list .......................................33
Monitor ............................................................33
Parameters .........................................................36
Inputs ..............................................................37
Outputs ............................................................40
Drive Control ........................................................43
Motor Control .......................................................44
Protections .........................................................44
Bypass .............................................................47
Communication ......................................................48
RS485 Bus ..........................................................49
EtherNet Bus ........................................................50
System. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .51
Chapter 6 — PID Application
Introduction ........................................................54
I/O Controls ........................................................54
Force open/force close selection ........................................55
DIGIN selection ......................................................55
Option board DigIN selection ...........................................55
Timer channel selection ................................................55
Control I/O Configuration ...............................................56
PID application—parameters list .........................................57
Parameters .........................................................62
Inputs ..............................................................62
Outputs ............................................................66
Drive Control ........................................................69
Motor Control .......................................................71
Protections .........................................................71
PID Controller 1 ......................................................74
PID Controller 2 ......................................................78
Bypass .............................................................82
Real Time Clock ......................................................83
Communication ......................................................84
RS485 Bus ..........................................................86
EtherNet Bus ........................................................87
System. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .88
v
PowerXL DH1 series variable frequency drives
Table of contents, continued
Chapter 7—Advanced application parameter
Introduction .........................................................92
I/O Controls .........................................................92
Force open/force close selection ........................................93
Force open/force close selection ........................................93
DIGIN selection ......................................................93
Option board digIN selection ............................................93
Timer channel selection ................................................93
Control I/O configuration ...............................................94
Advanced application—Parameters List ...................................96
Monitor ............................................................96
Parameters .........................................................99
Outputs ...........................................................104
Drive Control .......................................................10 8
Motor Control ......................................................109
Protections ........................................................110
PID Controller 1 .....................................................113
PID Controller 2 .....................................................117
Bypass ............................................................121
Real Time Clock .....................................................121
Communication .....................................................123
RS485 Bus .........................................................124
EtherNet Bus .......................................................125
System. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .126
Appendix A – Description of parameters
Application level .....................................................129
Appendix B – Fault Log
Fault codes and descriptions ...........................................208
Appendix C – PowerXL Recommended Secure Hardening Guidelines
PowerXL - Secure Configuration Guidelines ...............................213
vi
PowerXL DH1 series variable frequency drives
List of figures
Figure 1. RTC battery connection ............................................1
Figure 2. Rating label......................................................2
Figure 3. Carton labels.....................................................2
Figure 4. Catalog numbering system .........................................3
Figure 5. Keypad and display ................................................8
Figure 6. General view of LCD .............................................11
Figure 7. Welcome page...................................................11
Figure 8. Upgrade page ...................................................12
Figure 9. Auto backup page................................................12
Figure 10. Main menu ....................................................12
Figure 11. Parent node page ...............................................13
Figure 12. Parameter page ................................................13
Figure 13. Parameter page from favorite menu.................................13
Figure 14. Fault page .....................................................13
Figure 15. Main Menu Page ...............................................14
Figure 16. Main menu navigation ...........................................14
Figure 17. M—Monitor....................................................16
Figure 18. Active Faults ...................................................17
Figure 19. Pop-up active faults..............................................18
Figure 20. Fault history ...................................................19
Figure 21. Parameter menu overview ........................................20
Figure 22. Parameter sets ................................................21
Figure 23. Down from keypad ..............................................22
Figure 24. Parameters comparison ..........................................23
Figure 25. Password .....................................................24
Figure 26. Edit parameter value.............................................25
Figure 27. Parameter locked................................................26
Figure 28. Acceleration and deceleration time.................................129
Figure 29. Motor parameters from ratings plate ...............................130
Figure 30. With and without reference scaling ................................133
Figure 31. Start forward/start reverse .......................................133
Figure 32. Start, stop and reverse ..........................................134
Figure 33. Start pulse/stop pulse ...........................................135
Figure 34. Start forward/start reverse .......................................136
Figure 35. Start pulse/stop pulse ...........................................137
Figure 36. Activation of fixed frequencies ....................................141
Figure 37. AI1 2wire-current ...............................................145
Figure 38. AI1 3wire-current...............................................145
Figure 39. AI1 4wire-current...............................................146
vii
PowerXL DH1 series variable frequency drives
List of figures, continued
Figure 40. AI1 reference potentiometer 10V ..................................146
Figure 41. Analog input AI scaling ..........................................146
Figure 42. AI1 signal filtering ..............................................147
Figure 43. AI1 No signal inversion ..........................................147
Figure 44. AI1 Signal Inversion.............................................147
Figure 45. Example of joystick hysteresis ....................................148
Figure 46. Example of sleep limit function....................................148
Figure 47. AI2 2wire-current ...............................................149
Figure 48. AI2 3wire-current...............................................149
Figure 49. AI2 4wire-current...............................................149
Figure 50. AI2 differential voltage...........................................149
Figure 51. AI2 pot ref ....................................................150
Figure 52. Supervision function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .158
Figure 53. Analog output filtering...........................................162
Figure 54. Analog output scaling ...........................................162
Figure 55. Analog output invert ............................................163
Figure 56. Acceleration/Deceleration (S-shaped) ...............................165
Figure 57. DC-Braking time when stop mode = coasting ........................167
Figure 58. DC-Braking time when stop mode = ramp...........................167
Figure 59. Example of skip frequency area setting .............................169
Figure 60. Linear and squared change of motor voltage .........................170
Figure 61. Programmable V/Hz curve ........................................171
Figure 62. Motor thermal current it curve ....................................173
Figure 63. Motor temperature calculation ....................................174
Figure 64. Stall characteristics settings ......................................175
Figure 65. Stall time count ................................................175
Figure 66. Setting of minimum load.........................................176
Figure 67. Underload time counter function ...................................176
Figure 68. Auto restart fail (try number >2.) ..................................180
Figure 69. Setting up PID application........................................182
Figure 70. Setting up PID application........................................187
viii
PowerXL DH1 series variable frequency drives
List of tables
Table 1. Common abbreviations .............................................1
Table 2. Open Type /IP20 ...................................................4
Table 3. Type 1/IP21 ......................................................4
Table 4. Type 12/IP54 .....................................................4
Table 5. Open Type /IP20 ..................................................5
Table 6. Type 1/IP21 ......................................................5
Table 7. Type 12/IP54 ......................................................5
Table 8. Type 1/IP21 ......................................................6
Table 9. Type 12/IP54 .....................................................7
Table 10. Keypad buttons ..................................................9
Table 11. LED state indicators ............................................. 11
Table 12. Soft keys ......................................................12
Table 13. Keypad menus ..................................................15
Table 14. Startup wizard instructions ........................................27
Table 15. PID Mini-wizard values ...........................................28
Table 16. I/O Connection .................................................31
Table 17. Drive communication ports ........................................32
Table 18. Basic—M1 ..................................................... 33
Table 19. IO Status—M2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Table 20. Optional Boards — M3 ...........................................34
Table 21. Energy Savings — M4 ............................................34
Table 22. FB Monitor Menu — M5 ..........................................34
Table 23. User Defined Output — M8 .......................................35
Table 24. MWH Monitor — M9 ............................................ 35
Table 25. Multi-Monitoring — M10 .......................................... 36
Table 26. Basic Parameters — P1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Table 27. Basic Setting — P2.1 .............................................37
Table 28. Digital Input — P2.2 .............................................37
Table 29 Preset Speed — P2.3 .............................................39
Table 30 AI1 Settings — P2.4 .............................................. 39
Table 31 AI2 Settings — P2.5 .............................................. 39
Table 32 Digital Output — P3.1 ............................................40
Table 33 Supervisions — P3.2 .............................................41
Table 34 Analog Output 1 — P3.3 ..........................................42
Table 35 Analog Output 2 — P3.4 ..........................................42
Table 36 Basic Setting — P4.1 .............................................43
Table 37 Brake — P4.2 ...................................................43
Table 38 Skip Frequency — P4.3 ...........................................43
Table 39 Energy Savings Calc — P4.4 .......................................44
ix
PowerXL DH1 series variable frequency drives
List of tables, continued
Table 40 Basic Setting — P5.1 .............................................44
Table 41. Motor — P6.1 ..................................................44
Table 42. Drive — P6.2 ...................................................46
Table 43. Communication — P6.3 ..........................................46
Table 44. Auto Restart — P6.4 .............................................47
Table 45. Fire Mode — P9 ................................................ 47
Table 46. Basic Setting — P10.1 ............................................47
Table 47. FB Process Data Input Sel — P12.1 .................................48
Table 48. FB Process Data Output Sel — P12.2 ...............................48
Table 49. Basic Setting — P12.3.1 ..........................................49
Table 50. Modbus RTU — P12.3.2 ..........................................49
Table 51. BACnet MS/TP — P12.3.3 .........................................50
Table 52. Basic Setting — P12.4.1 ..........................................50
Table 53. Modbus TCP — P12.4.2 ..........................................50
Table 54. BACnet IP — P12.4.3 ............................................51
Table 55. Basic Setting — P13.1 ............................................51
Table 56. Version Info -- P13.2 .............................................53
Table 57. Application Info -- P13.3 ...........................................53
Table 58. User Info -- P13.4 ...............................................53
Table 59. Operate Mode - O ...............................................53
Table 60. PID application default I/O connection ...............................56
Table 61 Drive communication ports ........................................57
Table 62. Basic - M1 .....................................................58
Table 63. IO Status — M2 ................................................58
Table 64. Optional Boards — M3 ...........................................58
Table 65. Energy Savings — M4 ............................................58
Table 66. FB Monitor Menu — M5 ..........................................59
Table 67. PID Monitor — M6 ..............................................60
Table 68. Timer/Interval Control — M7 .......................................61
Table 69. User Defined Output — M8 .......................................61
Table 70. MWH Monitor — M9 ............................................ 61
Table 71. Multi-Monitoring — M10 ..........................................61
Table 72. Basic Parameters — P1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Table 73. Basic Setting — P2.1 .............................................62
Table 74. Digital Input — P2.2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Table 75. Preset Speed — P2.3 ............................................65
Table 76. AI1 Settings — P2.4 .............................................65
Table 77. AI2 Settings — P2.5 ..............................................65
Table 78. Digital Output — P3.1 ............................................66
Table 79. Supervisions — P3.2 ............................................. 67
x
PowerXL DH1 series variable frequency drives
List of tables, continued
Table 80. Analog Output 1 — P3.3 .......................................... 68
Table 81. Analog Output 2 — P3.4 ..........................................69
Table 82. Basic Setting — P4.1 .............................................69
Table 83. Brake — P4.2 ..................................................70
Table 84. Skip Frequency — P4.3 ...........................................70
Table 85. Energy Savings Calc — P4.4 .......................................70
Table 86. Basic Setting — P5.1 .............................................71
Table 87. Second Motor Parameter — P5.2 ...................................71
Table 88. Motor — P6.1 ..................................................71
Table 89. Drive — P6.2 ...................................................73
Table 90. Communication — P6.3 ..........................................73
Table 91. Auto Restart — P6.4 .............................................73
Table 92. Basic Setting — P7.1 ............................................. 74
Table 93. Monitor — P7.2 ................................................. 75
Table 94. Basic — P7.3.1 .................................................. 75
Table 95. Setpoint 1 — P7.3.2 .............................................. 75
Table 96. Setpoint 2 — P7.3.3 .............................................. 76
Table 97. Basic — P7.4.1 .................................................. 76
Table 98. Feedback 1 — P7.4.2 ............................................. 77
Table 99. Feedback 2 — P7.4.3 ............................................. 77
Table 100. Basic — P7.5.1 ................................................. 77
Table 101. Feedforward 1 — P7.5.2 .......................................... 78
Table 102. Feedforward 2 — P7.5.3 ......................................... 78
Table 103. Basic Setting — P8.1 ............................................ 78
Table 104. Monitor — P8.2 ................................................ 79
Table 105. Basic — P8.3.1 ................................................ 79
Table 106. Setpoint 1 — P8.3.2 ............................................ 79
Table 107. Setpoint 2 — P8.3.3 ............................................. 80
Table 108. Basic — P8.4.1 ................................................ 80
Table 109. Feedback 1 — P8.4.2 ........................................... 80
Table 110. Feedback 2 — P8.4.3 ............................................ 81
Table 111. Basic — P8.5.1 ................................................. 81
Table 112. Feedforward 1 — P8.5.2 ......................................... 81
Table 113. Feedforward 2 — P8.5.3 ......................................... 81
Table 114. Fire Mode — P9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Table 115. Basic Setting — P10.1 ........................................... 82
Table 116. Redundant Drive — P10.2 ........................................ 83
Table 117. Interval 1 — P11.1 ............................................... 83
Table 118. Interval 2 — P11.2 .............................................. 83
xi
PowerXL DH1 series variable frequency drives
List of tables, continued
Table 119. Interval 3 — P11.3 .............................................. 83
Table 120. Interval 4 — P11.4 .............................................. 84
Table 121. Interval 5 — P11.5 .............................................. 84
Table 122. Timer — P11.6 ................................................. 84
Table 123. FB Process Data Input Sel — P12.1 ................................ 84
Table 124. FB Process Data Output Sel — P12.2 ............................... 85
Table 125. Basic Setting — P12.3.1 ......................................... 86
Table 126. Modbus RTU — P12.3.2 ......................................... 86
Table 127. BACnet MS/TP — P12.3.3 ........................................ 87
Table 128. Basic Setting — P12.4.1 ......................................... 87
Table 129. Modbus TCP — P12.4.2 ......................................... 87
Table 130. BACnet IP — P12.4.3 ........................................... 88
Table 131. Basic Setting — P13.1 ........................................... 88
Table 132. Version Info — P13.2 ............................................ 90
Table 133. Application Info — P13.3 ......................................... 91
Table 134. User Info — P13.4 .............................................. 91
Table 135. Operate Mode — O ............................................ 91
Table 136. Advanced Application Default I/O Configuration ....................... 94
Table 137. Drive Communication Ports ....................................... 95
Table 138. Basic — M1 ................................................... 96
Table 139. IO Status — M2 ............................................... 96
Table 140. Optional Boards — M3 .......................................... 97
Table 141. Energy Savings — M4 ........................................... 97
Table 142. FB Monitor Menu — M5 ......................................... 97
Table 143. PID Monitor — M6 ............................................. 98
Table 144. Timer/Interval Control — M7 ...................................... 99
Table 145. User Defined Output — M8 ...................................... 99
Table 146. MWH Monitor — M9 ........................................... 99
Table 147. Multi-Monitoring — M10 ......................................... 99
Table 148. Basic Parameters — P1 .......................................... 99
Table 149. Basic Setting — P2.1 ........................................... 10 0
Table 150. Digital Input — P2.2 ........................................... 101
Table 151. Preset Speed — P2.3 .......................................... 103
Table 152. AI1 Settings - P2.4 ............................................. 10 3
Table 153. AI2 Settings - P2.5 ............................................. 10 3
Table 154. Digital Output — P3.1 .......................................... 104
Table 155. Supervisions — P3.2 ........................................... 105
Table 156. Analog Output 1 - P3.3 ......................................... 106
xii
PowerXL DH1 series variable frequency drives
List of tables, continued
Table 157. Analog Output 2 — P3.4 ........................................ 107
Table 158. Logic Function — P3.5 ......................................... 107
Table 159. Basic Setting — P4.1 ........................................... 10 8
Table 160. Brake — P4.2 ................................................ 10 9
Table 161. Skip Frequency — P4.3 ......................................... 109
Table 162. Energy Savings Calc — P4.4 ..................................... 109
Table 163. Basic Setting — P5.1 ........................................... 10 9
Table 164. Second Motor Parameter — P5.2 ................................. 110
Table 165. Motor — P6.1 ................................................ 110
Table 166. Drive — P6.2 ................................................. 11 2
Table 167. Communication — P6.3 ......................................... 11 2
Table 168. Auto Restart — P6.4 ........................................... 112
Table 169. Basic Setting — P7.1 ........................................... 11 3
Table 170. Monitor — P7.2 ............................................... 11 4
Table 171. Basic — P7.3.1 ................................................ 114
Table 172. Setpoint 1 — P7.3.2 ............................................ 115
Table 173. Setpoint 2 — P7.3.3 ............................................ 116
Table 174. Basic — P7.4.1 ................................................ 11 6
Table 175. Feedback 1 — P7.4.2 ........................................... 116
Table 176. Feedback 2 — P7.4.3 ........................................... 11 6
Table 177. Basic — P7.5.1 ................................................ 116
Table 178. Feedforward 1 — P7.5.2 ........................................ 117
Table 179. Feedforward 2 — P7.5.3 ........................................ 117
Table 180. Basic Setting — P8.1 ........................................... 117
Table 181. Monitor — P8.2 ............................................... 118
Table 182. Basic — P8.3.1 ............................................... 118
Table 183. Setpoint 1 — P8.3.2 ........................................... 118
Table 184. Setpoint 2 — P8.3.3 ........................................... 119
Table 185. Basic — P8.4.1 ............................................... 119
Table 186. Feedback 1 — P8.4.2 .......................................... 119
Table 187. Feedback 2 — P8.4.3 ........................................... 11 9
Table 188. Basic — P8.5.1 ............................................... 120
Table 189. Feedforward 1 — P8.5.2 ........................................ 120
Table 190. Feedforward 2 − P8.5.3 ........................................ 120
Table 191. Fire Mode − P9 ............................................... 120
Table 192. Basic Setting — P10.1 .......................................... 121
Table 193. Redundant Drive — P10.2 ....................................... 121
Table 194. Interval 1 — P11.1 ............................................. 121
Table 195. Interval 2 — P11.2 ............................................. 122
xiii
PowerXL DH1 series variable frequency drives
List of tables, continued
Table 196. Interval 3 — P11.3 ............................................. 122
Table 197. Interval 4 — P11.4 ............................................. 122
Table 198. Interval 5 — P11.5 ............................................. 122
Table 199. Timer — P11.6 ................................................ 123
Table 200. FB Process Data Input Sel — P12.1 ............................... 123
Table 201. FB Process Data Output Sel — P12.2 .............................. 123
Table 202. Basic Setting — P12.3.1 ........................................ 124
Table 203. Modbus RTU — P12.3.2 ........................................ 124
Table 204. BACnet MS/TP — P12.3.3 ....................................... 125
Table 205. Basic Setting — P12.4.1 ........................................ 125
Table 206. Modbus TCP — P12.4.2 ........................................ 125
Table 207. BACnet IP — P12.4.3 ........................................... 126
Table 208. Basic Setting — P13.1 .......................................... 126
Table 209. Version Info — P13.2 ........................................... 128
Table 210. Application Info — P13.3 ........................................ 128
Table 211. User Info — P13.4 ............................................. 128
Table 212. Operate Mode - O ............................................. 128
Table 213. Active Faults .................................................208
Table 214. History faults ................................................208
xiv
PowerXL DH1 series variable frequency drives
Safety
WARNING! DANGEROUS ELECTRICAL VOLTAGE!
Before commencing the installation
Disconnect the power supply of the device
Ensure that devices cannot be accidentally restarted
Verify isolation from the supply
Earth and short circuit the device
Cover or enclose any adjacent live components
Only suitably qualified personnel in accordance with EN 50110-1/-2 (VDE 0105 Part 100) may work on this device/system
Before installation and before touching the device ensure that you are free of electrostatic charge
The functional earth (FE, PES) must be connected to the protective earth (PE) or the potential equalization. The system installer is responsible for implementing this connection
Connecting cables and signal lines should be installed so that inductive or capacitive interference does not impair the automation functions
Install automation devices and related operating elements in such a way that they are well protected against unintentional operation
Suitable safety hardware and software measures should be implemented for the I/O interface so that an open circuit on the signal side does not result in undefined states in the automation devices
Ensure a reliable electrical isolation of the extra-low voltage of the 24 V supply. Only use power supply units complying with IEC 60364-4-41 (VDE 0100 Part 410) or HD384.4.41 S2
Deviations of the input voltage from the rated value must not exceed the tolerance limits given in the specifications, otherwise this may cause malfunction and dangerous operation
Emergency stop devices complying with IEC/EN 60204-1 must be effective in all operating modes of the automation devices. Unlatching the emergency-stop devices must not cause a restart
Devices that are designed for mounting in housings or control cabinets must only be operated and controlled after they have been installed and with the housing closed. Desktop or portable units must only be operated and controlled in enclosed housings
Measures should be taken to ensure the proper restart of programs interrupted after a voltage dip or failure. Thisshould not cause dangerous operating states even for
a short time. If necessary, emergency-stop devices should be implemented
Wherever faults in the automation system may cause injury or material damage, external measures must be implemented to ensure a safe operating state in the event of a fault or malfunction (for example, by means of separate limit switches, mechanical interlocks, and so on)
Depending on their degree of protection, adjustable frequency drives may contain live bright metal parts, moving or rotating components, or hot surfaces during and immediately after operation
Removal of the required covers, improper installation, or incorrect operation of motor or adjustable frequency drive may cause the failure of the device and may lead to serious injury or damage
The applicable national accident prevention and safety regulations apply to all work carried out on live adjustable frequency drives
The electrical installation must be carried out in accordance with the relevant regulations (for example, with regard to cable cross sections, fuses, PE)
Transport, installation, commissioning, and maintenance work must be carried out only by qualified personnel (IEC 60364, HD 384 and national occupational safetyregulations)
Installations containing adjustable frequency drives must be provided with additional monitoring and protective devices in accordance with the applicable safety regulations. Modifications to the adjustable frequency drives using the operating software are permitted
All covers and doors must be kept closed during operation
To reduce hazards for people or equipment, the user must include in the machine design measures that restrict the consequences of a malfunction or failure of the drive (increased motor speed or sudden standstill of motor). These measures include:
Other independent devices for monitoring safety-related
variables (speed, travel, end positions, and so on)
Electrical or non-electrical system-wide measures
(electrical or mechanical interlocks)
Never touch live parts or cable connections of
the adjustable frequency drive after it has been disconnected from the power supply. Due to the charge in the capacitors, these parts may still be live after disconnection. Fit appropriate warning signs
xv
PowerXL DH1 series variable frequency drives
Definitions and symbols
WARNING
This symbol indicates high voltage. It calls your attention to items or operations that could be dangerous to you and other persons operating this equipment. Read the message and follow the instructions carefully. This symbol is the “Safety Alert Symbol”. It occurs with either of two signal words: CAUTION or WARNING, as described below.
WARNING
Indicates a potentially hazardous situation which, if not avoided, can result in serious injury or death.
CAUTION
Indicates a potentially hazardous situation which, if not avoided, can result in minor to moderate injury, or serious damage to the product. The situation described in the CAUTION may, if not avoided, lead to serious results. Important safety measures are described in CAUTION (as well as WARNING).
Hazardous high voltage
WARNING
Motor control equipment and electronic controllers are connected to hazardous line voltages. When servicing drives and electronic controllers, there may be exposed components with housings or protrusions at or above line potential. Extreme care should be taken to protect against shock.
Warnings and cautions
This manual contains clearly marked cautions and warnings which are intended for your personal safety and to avoid any unintentional damage to the product or connected appliances. Please read the information included in cautions and warnings carefully.
WARNING
The relay outputs and other I/O-terminals may have a dangerous control voltage present even when PowerXL Series is disconnected from mains.
WARNING
Be sure not to plug the Ethernet/BACnet/IP cable to the terminal under the keypad! This might harm your personal computer.
WARNING
Be sure not to plug the Modbus TCP cable to the terminal under the keypad! This might harm your personal computer.
CAUTION
Remove external control signal before resetting the fault to prevent unintentional restart of the drive.
Stand on an insulating pad and make it a habit to use only one hand when checking components. Always work with another person in case an emergency occurs. Disconnect power before checking controllers or performing maintenance. Be sure equipment is properly grounded. Wear safety glasses whenever working on electronic controllers or rotating machinery.
xvi
PowerXL DH1 series variable frequency drives
Important safety information
Hazardous high voltage
WARNING
The components of the power unit of PowerXL Series are live when the AC drive is connected to mains potential. Coming into contact with this voltage is extremely dangerous and may cause death or severe injury.
WARNING
The motor terminals U, V, W and the brake resistor terminals are live when PowerXL Series is connected to mains, even if the motor is not running.
WARNING
After disconnecting the AC drive from the mains, wait until the indicators on the keypad go out (if no keypad is attached see the indicators on the cover). Wait 5 more minutes before doing any work on the connections of PowerXL Series Drive. Do not open the cover before this time has expired. After expiration of this time, use a measuring equipment to absolutely ensure that no voltage is present. Always ensure absence of voltage before starting any electrical work!
WARNING
The control I/O-terminals are isolated from the mains potential. However, the relay outputs and other I/O­terminals may have a dangerous control voltage present even when PowerXL Series is disconnected from mains.
WARNING
Before connecting the AC drive to mains, confirm that the front and cable covers of PowerXL Series Drive are closed.
WARNING
During a ramp stop (see the Application Manual), the motor is still generating voltage to the drive. Therefore, do not touch the components of the AC drive before the motor has completely stopped. Wait until the indicators on the keypad go out (if no keypad is attached see the indicators on the cover). Wait additional 5 minutes before starting any work on the drive.
Important warnings
WARNING
PowerXL Series AC drive is meant for fixed installations only.
WARNING
Do not perform any measurements when the AC drive is connected to the mains.
WARNING
The ground leakage current of PowerXL Series AC drives exceeds 3.5 mA AC. According to standard EN61800-5-1, a reinforced protective ground connection must be ensured.
WARNING
If the AC drive is used as a part of a machine, the machine manufacturer is responsible for providing the machine with a supply disconnecting device (EN 60204-1).
WARNING
Only spare parts delivered by Eaton can be used.
WARNING
At power-up, power brake or fault reset the motor will start immediately if the start signal is active, unless the pulse control for Start/Stop logic has been selected. Furthermore, the I/O functionalistic (including start inputs) may change if parameters, applications or software are changed. Disconnect, therefore, the motor if an unexpected start can cause danger.
WARNING
The motor starts automatically after automatic fault reset if the auto restart function is activated. See the Application Manual for more detailed information.
WARNING
Prior to measurements on the motor or the motor cable, disconnect the motor cable from the AC drive.
WARNING
Do not touch the components on the circuit boards. Static voltage discharge may damage the components.
WARNING
Check that the EMC level of the AC drive corresponds to the requirements of your supply network.
xvii
PowerXL DH1 series variable frequency drives
Additional cautions
CAUTION
The PowerXL Series AC drive must always be grounded with an grounding conductor connected to the grounding terminal marked with. The ground leakage current of PowerXL Series exceeds 3.5 mA AC. According to EN61800-5-1, one or more of the following conditions for the associated protective circuit shall be satisfied:
a) The protective conductor shall have a cross-sectional
area of at least 10 mm2 Cu or 16 mm2 Al, through its total run
b) Where the protective conductor has a cross-sectional
area of less than 10 mm2 Cu or 16 mm2 Al, a second protective conductor of at least the same cross-sectional area shall be provided up to a point where the protective conductor has a cross-sectional area not less than 10 mm2 Cu or 16 mm2 Al
c) Automatic disconnection of the supply in case of loss
of continuity of the protective conductor. The cross-sectional area of every protective grounding conductor that does not form part of the supply cable or cable enclosure shall, in any case, be not less than:
2.5mm2 if mechanical protection is provided or
4 mm2 if mechanical protection is not provided.
The ground fault protection inside the AC drive
protects only the drive itself against ground faults in the motor or the motor cable. It is not intended for personal safety. The ground fault protection inside the AC drive protects only the drive itself against ground faults in the motor or the motor cable. It is not intended for personal safety. Due to the high capacitive currents present in the AC drive, fault current protective switches may not function properly.
Do not perform any voltage withstand tests on any
part of PowerXL Series Drive. There is a certain procedure according to which the tests shall be performed. Ignoring this procedure may result in damagedproduct.
xviii
PowerXL DH1 series variable frequency drives
Sécurité
AVERTISSEMENT ! TENSION ÉLECTRIQUE DANGEREUSE !
Avant de commencer l’installation
Débrancher l’alimentation de l’appareil
S’assurer que les dispositifs ne peuvent pas être accidentellement redémarrés
Vérifier l’isolement de l’alimentation
Mettre l’appareil à la terre et le protéger contre les courts-circuits
Couvrir ou enfermer tout composant sous tension adjacent
Seul le personnel qualifié conformément à la norme EN 50110-1/-2 (VDE 0105 Partie 100) peut travailler sur cet appareil/ce système
Avant l’installation et avant de toucher l’appareil, s’assurer de ne porter aucune charge électrostatique
La terre fonctionnelle (FE, PSE) doit être raccordée à la terre de protection (PE) ou la compensation de potentiel. L’installateur du système a la responsabilité d’assurer cette connexion
Les câbles de connexion et les lignes de signal doivent être installés de façon à ce que les interférences capacitives ou inductives ne compromettent pas les fonctions d’automatisation
Installer les appareils d’automatisation et les éléments de fonctionnement associés de manière à ce qu’ils soient bien protégés contre tout fonctionnement accidentel
Des dispositifs de sécurité matériels et logiciels appropriés doivent être utilisés en rapport avec l’interface des E/S afin qu’un circuit ouvert sur le côté signal ne résulte pas en états indéfinis dans les dispositifs d’automatisation
Assurer une isolation électrique fiable sur le côté tension extra basse de l’alimentation 24 V. Utiliser uniquement des blocs d’alimentation conformes à la norme CEI 60364-4-41 (VDE 0100, partie 410) ou HD384.4.41 S2
Les écarts entre la tension d’entrée et la tension nominale ne doivent pas dépasser les limites de tolérance indiquées dans les spécifications, au risque de provoquer un mauvais fonctionnement et une utilisation dangereuse du système
Les dispositifs d’arrêt d’urgence conformes à la norme CEI/EN 60204-1 doivent être efficace dans tous les modes de fonctionnement des dispositifs d’automatisation. Le déverrouillage des dispositifs d’arrêt d’urgence ne doit pas entraîner un redémarrage
Les dispositifs conçus pour un montage dans des boîtiers ou armoires de commande ne doivent être utilisés et contrôlés qu’après avoir été installés et avec le boîtier fermé. Les unités de bureau ou portatives ne doivent être utilisées et contrôlées que dans leurs boîtiers fermés
Des mesures doivent être prises pour assurer un bon redémarrage des programmes interrompus après une chute ou une panne de tension. Ceci ne doit pas causer des états de fonctionnement dangereux, même pour un court laps de temps. Si nécessaire, des dispositifs d’arrêt d’urgence doivent être utilisés
Quand des défaillances du système d’automatisation peuvent entraîner des blessures ou des dommages matériels, des mesures externes doivent être appliquées pour assurer un état de fonctionnement sans danger en cas de panne ou de mauvais fonctionnement (par exemple au moyen de disjoncteurs séparés, de verrouillages mécaniques, etc.)
En fonction de leur degré de protection, les entraînements à fréquence variable peuvent contenir des pièces métalliques sous tension, des composants rotatifs ou en mouvement et des surfaces brûlantes, pendant le fonctionnement et immédiatement après l’arrêt
Le retrait des protections requises, une installation incorrecte ou un mauvais fonctionnement du moteur ou de l’entraînement à fréquence variable peuvent causer la défaillance de l’appareil et entraîner des blessures graves et des dommages importants
La réglementation nationale applicable en matière de sécurité et de prévention des accidents s’applique à tous les travaux effectués sur les entraînements à fréquence variable sous tension
L’installation électrique doit être effectuée conformément aux réglementations applicables (par exemple, en ce qui concerne les sections transversales des câbles, les fusibles, la mise à la terre de protection)
Le transport, l’installation, la mise en service et les travaux de maintenance doivent être effectués uniquement par un personnel qualifié (IEC 60364, HD384 et règles de sécurité du travail)
Les installations contenant des entraînements à fréquence variable doivent être équipées de dispositifs de surveillance et de protection, conformément aux réglementations applicables en matière de sécurité. Les modifications des entraînements à fréquence variable réalisées à l’aide du logiciel d’exploitation sont autorisées
Toutes les protections et les portes doivent être maintenues fermées pendant le fonctionnement
xix
PowerXL DH1 series variable frequency drives
Pour réduire les risques d’accidents et de dommages matériels, l’utilisateur doit inclure dans la conception de la machine des mesures limitant les conséquences de panne ou de mauvais fonctionnement de l’entraînement (augmentation de la vitesse ou arrêt soudain du moteur). Ces mesures comprennent :
Autres dispositifs indépendants de surveillance des
variables en rapport avec la sécurité (vitesse, voyages, positions d’extrémité, etc.)
Mesures électriques ou non électriques appliquées à
l’ensemble du système (verrouillages électriques ou mécaniques)
Ne jamais toucher les pièces sous tension ni les
connexions des câbles de l’entraînement à fréquence variable après leur déconnexion de l’alimentation. En raison de la charge dans les condensateurs, ces pièces peuvent être encore sous tension après la déconnexion. Installer les panneaux d’avertissement appropriés
Lire ce manuel en entier et s’assurer de bien comprendre les procédures avant de tenter d’installer, de configurer, d’utiliser et d’effectuer tout travail d’entretien sur cet entraînement à fréquence variable manejar.
Haute tension dangereuse
AVERTISSEMENT
L’équipement de contrôle du moteur et les contrôleurs électroniques sont branchés sur des tensions secteur dangereuses. Lors de l’entretien des entraînements et des contrôleurs électroniques, il peut y avoir des composants exposés avec des boîtiers ou des protubérances au niveau du potentiel du réseau ou au-dessus. Toutes les précautions doivent être prises pour se protéger contre les chocs électriques.
Se tenir sur un tapis isolant et prendre l’habitude de n’utiliser qu’une seule main pour vérifier lescomposants
Toujours travailler avec une autre personne lorsqu’une situation d’urgence se produit
Débrancher l’alimentation avant de vérifier les contrôleurs ou d’effectuer des travaux d’entretien
S’assurer que l’équipement est correctement relié à la terre
Porter des lunettes de sécurité lors des travaux sur les contrôleurs électroniques ou les machines rotatives
Définitions et symboles
AVERTISSEMENT
Ce symbole indique une haute tension. Il attire l’attention sur les éléments ou les opérations qui pourraient être dangereux pour les personnes utilisant cet équipement. Lire attentivement le message et suivre attentivement les instructions.
Ce symbole est le « symbole d’alerte de sécurité ». Il accompagne les deux termes d’avertissement suivants: MISE EN GARDE ou AVERTISSEMENT, comme décrit ci-dessous.
AVERTISSEMENT
Indique une situation potentiellement dangereuse qui, si elle n’est pas évitée, peut entraîner des blessures graves ou la mort.
MISE EN GARDE
Indique une situation potentiellement dangereuse qui, si elle n’est pas évitée, peut entraîner des blessures légères à modérées et d’importants dégâts matériels. La situation décrite dans la MISE EN GARDE peut, si elle n’est pas évitée, entraîner des conséquences graves. Des mesures de sécurité importantes sont décrites dans les MISES EN GARDE (ainsi que dans les AVERTISSEMENTS).
AVERTISSEMENT
Les composants de la section d’alimentation de l’entraînement restent sous tension après la coupure de la tension d’alimentation. Après la déconnexion de l’alimentation, attendre au moins cinq minutes avant de retirer le couvercle pour permettre la décharge des condensateurs du circuit intermédiaire.
Prêter attention aux avertissements signalant desdangers !
DANGER 5 MIN
AVERTISSEMENT
Risque de choc électrique – risque de blessures ! Effectuer le câblage uniquement si l’unité n’est plus sous tension.
AVERTISSEMENT
Ne pas effectuer de modifications sur l’entraînement CA lorsqu’il est connecté à l’alimentation secteur.
xx
PowerXL DH1 series variable frequency drives
Avertissements et mises en garde
AVERTISSEMENT
S’assurer de mettre l’appareil à la terre en suivant les instructions de ce manuel. Les unités non mises à la terre peuvent causer des chocs électriques et desincendies.
AVERTISSEMENT
Cet équipement ne doit être installé, réglé et entretenu que par un personnel d’entretien électrique qualifié connaissant la construction et le fonctionnement de ce type d’équipement, ainsi que les risques encourus. Le non-respect de cette précaution peut entraîner la mort ou des blessures graves.
AVERTISSEMENT
Les composants à l’intérieur de l’entraînement sont sous tension lorsque l’entraînement est branché à l’alimentation. Le contact avec cette tension est extrêmement dangereux et peut causer la mort ou des blessures graves.
AVERTISSEMENT
Les bornes de phase (L1, L2, L3), les bornes du moteur (U, V, W) et les bornes de résistance de liaison CC/ frein (DC-, DC+/R+, R-) sont sous tension lorsque l’entraînement est branché à l’alimentation, même si le moteur ne tourne pas. Le contact avec cette tension est extrêmement dangereux et peut causer la mort ou des blessures graves.
AVERTISSEMENT
Même si les bornes E/S de commande sont isolées de la tension secteur, les sorties de relais et les autres bornes E/S peuvent présenter une tension dangereuse même lorsque l’entraînement est débranché. Le contact avec cette tension est extrêmement dangereux et peut causer la mort ou des blessures graves.
AVERTISSEMENT
Cet équipement a un grand courant de fuite capacitif pendant le fonctionnement, ce qui peut mettre les pièces du boîtier à un niveau supérieur au potentiel de terre. Une mise à la terre appropriée, telle que décrite dans ce manuel, est nécessaire. Le non-respect de cette précaution peut entraîner la mort ou des blessuresgraves.
AVERTISSEMENT
Un dispositif de protection/déconnexion en amont doit être fourni, tel que requis par le code électrique national (NEC®). Le non-respect de cette précaution peut entraîner la mort ou des blessures graves.
AVERTISSEMENT
Cet entraînement peut causer un courant CC dans le conducteur de mise à la terre de protection. Lorsqu’un dispositif de protection ou de surveillance à courant résiduel est utilisé pour la protection en cas de contact direct ou indirect, seul un dispositif de type B est autorisé sur le côté alimentation de ce produit.
AVERTISSEMENT
Ne travailler sur le câblage qu’après que l’entraînement a été correctement monté et attaché.
AVERTISSEMENT
Avant d’ouvrir les couvercles de l’entraînement :
Débrancher toute l’alimentation allant à l’entraînement, y compris l’alimentation de commande externe pouvant être présente
Attendre un minimum de cinq minutes après l’extinction de tous les voyants du clavier. Cela permet aux condensateurs de bus CC de se décharger
Une tension dangereuse peut rester dans les condensateurs de bus CC même si l’alimentation a été coupée. Confirmer que les condensateurs sont entièrement déchargés en mesurant la tension à l’aide d’un multimètre réglé pour mesurer la tension CC
Le non-respect de cette précaution peut entraîner la mort ou des blessures graves.
AVERTISSEMENT
L’ouverture du dispositif de protection du circuit de dérivation peut indiquer que le courant de défaut a été interrompu. Pour réduire le risque d’incendie ou de choc électrique, les pièces porteuses de courant et les autres composants du contrôleur doivent être examinés et remplacés s’ils sont endommagés. Si l’élément de courant d’un relais de surcharge a grillé, le relais de surcharge doit être intégralement remplacé.
AVERTISSEMENT
Avant de mettre l’entraînement sous tension, s’assurer que les protections avant et des câbles sont fermées et attachées pour empêcher l’exposition à d’éventuelles défaillances électriques. Le non-respect de cette précaution peut entraîner la mort ou des blessures graves.
xxi
PowerXL DH1 series variable frequency drives
AVERTISSEMENT
Le fonctionnement de cet équipement nécessite le respect des instructions d’installation et de fonctionnement détaillées fournies dans le manuel d’installation/de fonctionnement destiné à être utilisé avec ce produit. Ces informations sont fournies sur le CD-ROM, la disquette ou tout autre périphérique de stockage inclus dans l’emballage contenant ce dispositif. Ce support doit être conservé avec cet appareil à tout moment. Une copie papier de ces informations peut être commandée auprès du service de documentation Eaton.
AVERTISSEMENT
Avant de procéder à l’entretien de l’entraînement :
Débrancher toute l’alimentation allant à l’entraînement, y compris l’alimentation de commande externe pouvant être présente
Placer une étiquette « NE PAS UTILISER » sur le dispositif de déconnexion
Verrouiller le dispositif de déconnexion en positionouverte
Le non-respect de ces instructions peut entraîner la mort ou des blessures graves.
AVERTISSEMENT
Les sorties de l’entraînement (U, V, W) ne doivent pas être connectées à la tension d’entrée ni à l’alimentation secteur, car ceci pourrait gravement endommager l’appareil et causer un incendie.
AVERTISSEMENT
Le dissipateur de chaleur et/ou le boîtier externe peuvent atteindre une température élevée.
Prêter attention aux avertissements signalant des dangers !
MISE EN GARDE
Installer cet entraînement sur une surface perpendiculaire capable de supporter le poids de l’entraînement et non soumise à des vibrations afin de diminuer les risques de chute et de dommage de l’entraînement, ainsi que les risques de blessures.
MISE EN GARDE
Empêcher la pénétration de corps étrangers, tels que morceaux de fils et copeaux métalliques, dans le boîtier de l’entraînement, car ceci pourrait provoquer la formation d’un arc électrique et un incendie.
MISE EN GARDE
Installer cet entraînement dans une pièce bien aérée non soumise à des températures extrêmes, à une forte humidité ou à la condensation. Éviter les endroits directement exposés au soleil ou présentant de fortes concentrations de poussières, des gaz corrosifs, des gaz explosifs, des gaz inflammables, ou des vapeurs de liquide de meulage, etc. Une installation inadéquate peut entraîner un risqued’incendie.
MISE EN GARDE
Lors de la sélection de la section transversale des câbles, prendre en compte la chute de tension dans des conditions de charge. La prise en compte d’autres paramètres relève de la responsabilité de l’utilisateur.
Il relève de la responsabilité de l’utilisateur de respecter toutes les normes électriques nationales et internationales en vigueur concernant la mise à la terre de protection de l’ensemble de l’équipement.
MISE EN GARDE
Les spécifications minimum relatives aux sections transversales des conducteurs de terre de protection indiquées dans ce manuel doivent être respectées.
Le courant de fuite de cet équipement dépasse 3,5 mA(CA). La taille minimum du conducteur de la mise à la terre de protection doit être conforme aux exigences de la norme EN 61800-5-1 et/ou aux réglementations de sécurité locales.
Surface brûlante – Risque de brûlure. NE PAS TOUCHER !
MISE EN GARDE
Toute modification électrique ou mécanique de cet entraînement sans consentement écrit préalable d’Eaton annule toutes les garanties, peut entraîner un danger pour la sécurité et annuler l’homologation UL®.
MISE EN GARDE
Installer cet entraînement sur une matière résistante aux flammes, telle qu’une plaque d’acier, pour réduire les risques d’incendie.
xxii
MISE EN GARDE
Les courants de fuite de ce convertisseur de fréquence sont supérieures à 3,5 mA (CA). Conformément à la norme CEI/EN 61800-5-1, un conducteur de mise à la terre de l’équipement supplémentaire possédant la même superficie de coupe transversale que le conducteur de mise à la terre de protection d’origine doit être branché, ou la section transversale du conducteur de mise à la terre de l’équipement doit être d’au moins 10 mm2 Cu. Seul un conducteur en cuivre doit être utilisé avec cet entraînement.
PowerXL DH1 series variable frequency drives
MISE EN GARDE
Les entrées anti-rebond ne sont pas permises dans le schéma du circuit de sécurité. Des disjoncteurs de courant résiduel (RCD) ne peuvent être installés qu’entre le réseau de courant alternatif et l’entraînement.
Ne pas tenter d’installer ou de retirer les vis des VOM et CEM lorsque l’alimentation est appliquée aux bornes d’entrée de l’entraînement
Sécurité du moteur et de l’équipement
MISE EN GARDE
Les entrées anti-rebond ne sont pas permises dans le schéma du circuit de sécurité. Si plusieurs moteurs sont connectés à un entraînement, des contacteurs doivent être conçus pour les moteurs individuels conformément à la catégorie d’utilisation AC-3.
Sélectionner du contacteur du moteur en fonction du courant de fonctionnement nominal du moteur à connecter.
MISE EN GARDE
Les entrées anti-rebond ne sont pas permises dans le schéma du circuit de sécurité. Une commutation entre l’entraînement et l’alimentation d’entrée doit avoir lieu dans un état sans tension.
MISE EN GARDE
Les entrées anti-rebond ne sont pas permises dans le schéma du circuit de sécurité. Risque d’incendie !
Utiliser uniquement des câbles, des interrupteurs de protection et des contacteurs indiquant le courant nominal permis.
MISE EN GARDE
Avant de connecter l’entraînement à l’alimentation secteur CA, s’assurer que les réglages de la classe de protection CEM sont correctement effectués selon les instructions de ce manuel.
Si l’entraînement doit être utilisé dans un réseau de distribution flottant, retirer les vis au niveau des VOM et CEM. Voir « Installation dans un réseau à une phase connectée à la terre (corner-grounded) » et « Installation dans un réseau IT»
Débrancher le filtre CEM interne lors de l’installation de l’entraînement sur un réseau IT (système d’alimentation non mis à la terre ou système d’alimentation électrique mis à la terre haute résistance [plus de 30 ohms]) pour ne pas que le système soit connecté au potentiel de terre via les condensateurs du filtre CEM. Ceci peut être une cause de dangers ou endommager l’entraînement
Débrancher le filtre CEM interne lors de l’installation de l’entraînement sur un système TN à une phase connectée à la terre pour ne pas endommager l’entraînement
ote:N Lorsque le filtre CEM interne est débranché,
l’entraînement peut ne pas être conforme aux normes de compatibilité électromagnétique.
MISE EN GARDE
n’effectuer aucun test de résistance de tension ou au mégohmmètre sur toute partie de l’entraînement ou de ses composants. Un test inadéquat peut entraîner desdommages.
MISE EN GARDE
Avant tout test ou mesure du moteur ou du câble du moteur, débrancher le câble du moteur au niveau des bornes de sortie de l’entraînement (U, V, W) pour éviter d’endommager ce dernier lors des tests.
MISE EN GARDE
Ne toucher aucun composant sur les cartes de circuit. Les décharges d’électricité statique peuvent endommager les composants.
MISE EN GARDE
Avant de mettre le moteur en marche, vérifier qu’il est correctement monté et aligné avec l’équipement entraîné. S’assurer que le démarrage du moteur ne risque pas de provoquer des blessures ou d’endommager l’équipement connecté au moteur.
MISE EN GARDE
Régler la vitesse maximale du moteur (fréquence) dans l’entraînement conformément aux exigences du moteur et de l’équipement qui lui est connecté. Des réglages de fréquence maximum incorrects peuvent endommager le moteur ou l’équipement et causer des blessures.
MISE EN GARDE
Avant d’inverser le sens de rotation du moteur, veiller à ce que cela ne risque pas de provoquer des blessures ou des dommages matériels.
MISE EN GARDE
S’assurer qu’aucun condensateur de correction de puissance n’est connecté à la sortie de l’entraînement ou aux bornes du moteur pour éviter un mauvais fonctionnement de l’entraînement et des dommages potentiels.
xxiii
PowerXL DH1 series variable frequency drives
MISE EN GARDE
S’assurer que les bornes de sortie de l’entraînement (U, V, W) ne sont pas connectées à l’alimentation secteur, ce qui pourrait causer de graves dommages à l’entraînement.
MISE EN GARDE
Lorsque les bornes de commande de deux ou plusieurs unités d’entraînement sont raccordées en parallèle, la tension auxiliaire de ces connexions de commande doit être fournie par une source unique, qui peut être soit l’une des unités, soit une alimentation externe.
MISE EN GARDE
L’entraînement démarre automatiquement après une interruption de la tension d’entrée si la commande de démarrage externe est active.
MISE EN GARDE
Ne pas commander le moteur avec le dispositif de déconnexion ; à la place, utiliser les touches de marche et d’arrêt du tableau de contrôle ou les commandes du tableau des E/S de l’entraînement. Le nombre de cycles de charge maximum permis des condensateurs CC (c’est-à-dire les mises sous tension par application de puissance) est de cinq en dix minutes.
MISE EN GARDE
Fonctionnement incorrect de l’entraînement :
Si l’entraînement n’est pas mis en marche pendant une longue période, la performance de ses condensateurs électrolytiques sera réduite
S’il est arrêté pour une période prolongée, le mettre en marche au moins tous les six mois pendant au moins 5heures pour restaurer la performance des condensateurs, puis vérifier son fonctionnement. Il est recommandé de ne pas brancher l’entraînement directement sur la tension secteur. La tension doit être augmentée progressivement en utilisant une source CAréglable
Le non-respect de ces instructions peut entraîner des blessures ou des dégâts matériels.
Pour plus d’informations techniques, contacter l’usine ou le représentant commercial Eaton local.
xxiv
Chapter 1—PowerXL series overview
This chapter describes the purpose and contents of this manual, the receiving inspection recommendations and the PowerXL Series Open Drive catalog numbering system.
How to use this manual
The purpose of this manual is to provide you with information necessary to install, set and customize parameters, start up, troubleshoot and maintain the Eaton PowerXL Series variable frequency drive (VFD). To provide for safe installation and operation of the equipment, read the safety guidelines at the beginning of this manual and follow the procedures outlined in the following chapters before connecting power to the PowerXL Series VFD. Keep this operating manual handy and distribute to all users, technicians and maintenance personnel for reference.
Receiving and inspection
The PowerXL Series VFD has met a stringent series of factory quality requirements before shipment. It is possible that packaging or equipment damage may have occurred during shipment. After receiving your PowerXL Series VFD, please check for the following:
Check to make sure that the package includes the Instruction Leaflet, Quick Start Guide, and accessory packet. The accessory packet includes:
Rubber grommets
Control cable grounding clamps
Additional grounding screw
Inspect the unit to ensure it was not damaged duringshipment.
Make sure that the part number indicated on the nameplate corresponds with the catalog number on your order.
If shipping damage has occurred, please contact and file a claim with the carrier involved immediately.
If the delivery does not correspond to your order, please contact your Eaton Electrical representative.
ote:N Do not destroy the packing. The template printed on
the protective cardboard can be used for marking the mounting points of the PowerXL Series VFD on the wall or in a cabinet.
Chapter 1—PowerXL series overview
Real time clock battery activation
To activate the real time clock (RTC) functionality in the PowerXL Series VFD, the RTC battery (already mounted in the drive) must be connected to the controlboard.
Simply remove the primary drive cover, locate the RTC battery directly below the keypad, and connect the white 2-wire connector to the receptacle on the control board.
Figure 1. RTC battery connection
Table 1. Common abbreviations
Abbreviation Definition
CT Constant torque with high overload rating (150%) VT Variable torque with low overload rating (110%) IH High overload current (150%) I
L
VFD Variable Frequency Drive RTC Real Time Clock
Low overload current (110%)
1
Chapter 1—PowerXL series overview
Rating label
Figure 2. Rating label
Carton labels (U.S. and Europe)
Same as rating label shown above.
Figure 3. Rating label
2
Catalog number system
Figure 4. Catalog numbering system
Chapter 1—PowerXL series overview
D H1 – 3 4 012 D N – C 21 C
Basic Naming
D = Drive
Series
G1 = General Purpose H1 = HVAC
208-240V 380-500V 525-600V
4D8 = 4.8A, 1.0HP, 0.75KW 3D3 = 3.3A, 1.5HP, 1.1KW 4D5 = 4.5A, 3HP, 2.2KW
6D6 = 6.6A, 1.5HP, 1.1KW 4D3 = 4.3A, 2.0HP, 1.5KW 7D5 = 7.5A, 5.0HP, 3.7KW
7D8 = 7.8A, 2.0HP, 1.5KW 5D6 = 5.6, 3.0HP, 2.2KW 010 = 10A, 7.5HP, 5.5KW
011 = 11A, 3.0HP, 2.2KW 7D6 = 7.6A, 5.0HP, 3KW 013 = 13.5A, 10HP, 7.5KW
012 = 12.5A, - HP, 3.0KW 9D0 = 9A, - HP, 4KW 018 = 18A, 15HP, 11KW
017 = 17.5A, 5.0HP, 3.7KW 012 = 12A, 7.5HP, 5.5KW 022 = 22A, 20HP, 15KW
025 = 25A, 7.5HP, 5.5KW 016 = 16A, 10HP, 7.5KW 027 = 27A, 25HP, 18.5KW
031 = 31A, 10HP, 7.5KW 023 = 23A, 15HP, 11KW 034 = 34A, 30HP, 22KW
048 = 48A, 15HP, 11KW 031 = 31A, 20HP, 15KW 041 = 41A, 40HP, 30KW
061 = 61A, 20HP, 15KW 038 = 38A, 25HP, 18.5KW 052 = 52A, 50HP, 37KW
075 = 75A, 25HP, 18.5KW 046 = 46A, 30HP, 22KW 062 = 62A, 60HP, 45KW
088 = 88A, 30HP, 22KW 061 = 61A, 40HP, 30KW 080 = 80A, 75HP, 55KW
114 = 114A, 40HP, 30KW 072 = 72A, 50HP, 37KW 100 = 100A, 100HP, 75KW
143 = 143A, 50HP, 37KW 087 = 87A, 60HP, 45KW 125 = 125A, 125HP, 90KW
170 = 170A, 60HP, 45KW 105 = 105A, 75HP, 55KW 144 = 144A, 150HP, 110KW
211 = 211A, 75HP, 55KW 140 = 140A, 100HP, 75KW 208 = 208A, 200HP, 132KW
261 = 261A, 100HP, 75KW 170 = 170A, 125HP, 90KW 250 = 250A, 250HP, 160KW
312 = 312A, 125HP, 90KW 205 = 205A, 150HP, 110KW
Phase Reference
3 = 3~ INPUT /3~OUTPUT
Input / Output Voltage
2 = 230V (208-240V, -15%, +10%) 4 = 400V (380-500V, - 15%, +10%) 5 = 600V (525-600V, -15%, +10%)
DH1 - Output Current Rating (VT)
261 = 261A, 200HP, 132KW
310 = 310A, 250HP, 160KW
Internal Brake Chopper
N = No brake chopper B = Brake chopper
Internal EMC Filter
D = DC choke only E = EMC filter only F = Internal EMC filter and DC choke N = No EMC filter, no DC choke
C = Coated
Enclosure (IP Rating)
a
00 = IP00
b
20 = IP20 21 = IP21/Type 1 54 = IP54/Type 12
Display Option
C = LCD (graphical) N = No display
Coating of Boards
a
IP00 FR7 and FR8 is not avaliable for 230V input product or with the PowerXL DH1 Product
b
IP20 FR0 will be avalible in June 2018
3
Chapter 1—PowerXL series overview
Power ratings and product selection
DH1 series drives—FRO, 230 Volt
Table 2. Open Type /IP20
Constant tor que (CT) /high overload (IH) Variable torque (VT)/low overload (IL)
Frame size
230 V, 50 Hz kW rating
FR0 0.55 0.75 3.7 0.75 1 4.8 DH1-324D8EB-C20C
0.75 1 4.8 1.1 1.5 6.6 DH1-326D6EB-C20C
1.1 1.5 6.6 1.5 2 7.8 DH1-327D8EB-C20C
Note: a IP20 FR0 will be available in June 2018.
DH1 series drives—FR1 - FR6, 230 Volt
Table 3. Type 1/IP21
Constant tor que (CT) /high overload (IH) Variable torque (VT)/low overload (IL)
Frame size
FR1 0.55 0.75 3.7 0.75 1 4.8 DH1-324D8DN-C21C
FR2 3 12.5 3.7 5 17. 5 DH1-32017DN-C21C
FR3 7. 5 10 31 11 15 48 DH1-32048DN-C21C
FR4 15 20 61 18.5 25 75 DH1-32075DN-C21C
FR5 30 40 114 37 50 143 DH1-32143DN-C21C
FR6 55 75 211 75 100 261 DH1-32261DN-C21C
230 V, 50 Hz kW rating
0.75 1 4.8 1.1 1.5 6.6 DH1-326D6DN-C21C
1.1 1.5 6.6 1.5 2 7.8 DH1-327D8DN-C21C
1.5 2 7.8 2.2 3 11 DH1-32011DN-C21C
2.2 3 11 3 12.5 DH1-32012DN-C21C
3.7 5 17. 5 5.5 7.5 25 DH1-32025DN-C21C
5.5 7.5 25 7. 5 10 31 DH1-32031DN-C21C
11 15 48 15 20 61 DH1-32061DN-C21C
18.5 25 75 22 30 88 DH1-32088DN-C21C 22 30 88 30 40 114 DH1-32114DN-C21C
37 50 143 45 60 170 DH1-32170DN-C21C 45 60 170 55 75 211 DH1-32211DN-C21C
75 100 248 90 125 312 DH1-32312DN-C21C
230 V, 60 Hz hpCurrent
230 V, 60 Hz hpCurrent
A
A
230 V, 50 Hz kW rating
230 V, 50 Hz kW rating
230 V, 60 HzhpCurrent
230 V, 60 HzhpCurrent
A
A
DH1 Catalog number
DH1 Catalog number
a
a
a
Table 4. Type 12/IP54
Constant tor que (CT) /high overload (IH) Variable torque (VT)/low overload (IL)
Frame size
230 V, 50 Hz kW rating
FR1 0.55 0.75 3.7 0.75 1 4.8 DH1-324D8DN-C54C
0.75 1 4.8 1.1 1.5 6.6 DH1-326D6DN-C54C
1.1 1.5 6.6 1.5 2 7.8 DH1-327D8DN-C54C
1.5 2 7.8 2.2 3 11 DH1-32011DN-C54C
2.2 3 11 3 12.5 DH1-32012DN-C54C
FR2 3 12.5 3.7 5 17.5 DH1-32017DN-C54C
3.7 5 17. 5 5.5 7. 5 25 DH1-32025DN-C54C
5.5 7.5 25 7. 5 10 31 DH1-32031DN-C54C
FR3 7. 5 10 31 11 15 48 DH1-32048DN-C54C
11 15 48 15 20 61 DH1-32061DN-C54C
FR4 15 20 61 18.5 25 75 DH1-32075DN-C54C
18.5 25 75 22 30 88 DH1-32088DN-C54C 22 30 88 30 40 114 DH1-32114DN-C54C
4
230 V, 60 Hz hpCurrent
A
230 V, 50 Hz kW rating
230 V, 60 HzhpCurrent
A
DH1 Catalog number
Chapter 1—PowerXL series overview
Table 4. Type 12/IP54
Constant tor que (CT) /high overload (IH) Variable torque (VT)/low overload (IL)
Frame size
230 V, 50 Hz kW rating
FR5 30 40 114 37 50 143 DH1-32143DN-C54C
37 50 143 45 60 170 DH1-32170DN-C54C 45 60 170 55 75 2 11 DH1-32211DN-C54C
FR6 55 75 211 75 100 261 DH1-32261DN-C54C
75 100 248 90 125 312 DH1-32312DN-C54C
DH1 series drives—FRO, 380-500 Volt
Table 5. Open Type /IP20
Constant tor que (CT) /high overload (IH) Variable torque (VT)/low overload (IL)
Frame size
FR0 0.75 1 2.2 1.1 1.5 3.3 DH1-343D3EB-C20C
400 V, 50 Hz kW rating
1.1 1.5 3.3 1.5 2 4.3 DH1-344D3EB-C20C
1.5 2 4.3 2.2 3 5.6 DH1-345D6EB-C20C
2.2 3 5.6 3 5 7. 6 DH1-347D6EB-C20C
230 V, 60 Hz hpCurrent
460 V, 60 Hz hpCurrent
A
A
230 V, 50 Hz kW rating
400 V, 50 Hz kW rating
230 V, 60 HzhpCurrent
460 V, 60 HzhpCurrent
A
A
DH1 Catalog number
DH1 Catalog number
a
a
a
a
Note: a IP20 FR0 will be available in June 2018.
DH1 series drives—380–500 volt
Table 6. Type 1/IP21
Constant tor que (CT) /high overload (IH) Variable torque (VT)/low overload (IL)
Frame size
400 V, 50 Hz kW rating
FR1 0.75 1 2.2 1.1 1.5 3.3 DH1-343D3DN-C21C
1.1 1.5 3.3 1.5 2 4.3 DH1-344D3DN-C21C
1.5 2 4.3 2.2 3 5.6 DH1-345D6DN-C21C
2.2 3 5.6 3 5 7. 6 DH1-347D6DN-C21C 3 5 7. 6 4 9 DH1-349D0DN-C21C 4 9 5.5 7. 5 12 DH1-34012DN-C21C
FR2 5.5 7. 5 12 7.5 10 16 DH1-34016DN-C21C
7.5 10 16 11 15 23 DH1-34023DN-C21C 11 15 23 15 20 31 DH1-34031DN-C21C
FR3 15 20 31 18.5 25 38 DH1-34038DN-C21C
18.5 25 38 22 30 46 DH1-34046DN-C21C 22 30 46 30 40 61 DH1-34061DN-C21C
FR4 30 40 61 37 50 72 DH1-34072DN-C21C
37 50 72 45 60 87 DH1-34087DN-C21C 45 60 87 55 75 105 DH1-34105DN-C21C
FR5 55 75 105 75 10 0 140 DH1-34140DN-C21C
75 100 140 90 125 170 DH1-34170DN-C21C 90 125 170 110 150 205 DH1-34205DN-C21C
FR6 110 150 205 132 200 261 DH1-34261DN-C21C
150 200 245 160 250 310 DH1-34310DN-C21C
460 V, 60 Hz hpCurrent
A
400 V, 50 Hz kW rating
460 V, 60 HzhpCurrent
A
DH1 Catalog number
5
Chapter 1—PowerXL series overview
Table 7. Type 12/IP54
Constant tor que (CT) /high overload (IH) Variable torque (VT)/low overload (IL)
Frame size
400 V, 50 Hz kW rating
FR1 0.75 1 2.2 1.1 1.5 3.3 DH1-343D3DN-C54C
1.1 1.5 3.3 1.5 2 4.3 DH1-344D3DN-C54C
1.5 2 4.3 2.2 3 5.6 DH1-345D6DN-C54C
2.2 3 5.6 3 5 7. 6 DH1-347D6DN-C54C 3 5 7. 6 4 9 DH1-349D0DN-C54C 4 9 5.5 7. 5 12 DH1-34012DN-C54C
FR2 5.5 7. 5 12 7.5 10 16 DH1-34016DN-C54C
7.5 10 16 11 15 23 DH1-34023DN-C54C 11 15 23 15 20 31 DH1-34031DN-C54C
FR3 15 20 31 18.5 25 38 DH1-34038DN-C54C
18.5 25 38 22 30 46 DH1-34046DN-C54C 22 30 46 30 40 61 DH1-34061DN-C54C
FR4 30 40 61 37 50 72 DH1-34072DN-C54C
37 50 72 45 60 87 DH1-34087DN-C54C 45 60 87 55 75 105 DH1-34105DN-C54C
FR5 55 75 105 75 10 0 140 DH1-34140DN-C54C
75 100 140 90 125 170 DH1-34170DN-C54C 90 125 170 110 150 205 DH1-34205DN-C54C
FR6 110 150 205 132 200 261 DH1-34261DN-C54C
150 200 245 160 250 310 DH1-34310DN-C54C
460 V, 60 Hz hpCurrent
A
400 V, 50 Hz kW rating
460 V, 60 HzhpCurrent
A Catalog number
DH1 series drives—600 volt
Table 8. Type 1/IP21
Constant tor que (CT) /high overload (IH) Variable torque (VT)/low overload (IL)
Frame size
600 V, 60 Hz kW rating
FR1 1.5 2 3.3 2.2 3 4.5 DH1-354D5DN-C21C
2.2 3 4.5 3.7 5 7.5 DH1-357D5DN-C21C
3.7 5 7.5 5.5 7.5 10 DH1-35010DN-C21C
FR2 5.5 7. 5 10 7.5 10 13.5 DH1-35013DN-C21C
7.5 10 13.5 11 15 18 DH1-35018DN-C21C 11 15 18 15 20 22 DH1-35022DN-C21C
FR3 15 20 22 18.5 25 27 DH1-35027DN-C21C
18.5 25 27 22 30 34 DH1-35034DN-C21C 22 30 34 30 40 41 DH1-35041DN-C21C
FR4 30 40 41 37 50 52 DH1-35052DN-C21C
37 50 52 45 60 62 DH1-35062DN-C21C 45 60 62 55 75 80 DH1-35080DN-C21C
FR5 55 75 80 75 100 100 DH1-35100DN-C21C
75 100 100 90 125 125 DH1-35125DN-C21C 90 125 125 110 150 144 DH1-35144DN-C21C
FR6 110 150 144 150 200 208 DH1-35208DN-C21C
150 200 208 187 250 250 DH1-35250DN-C21C
600 V, 60 Hz hpCurrent
A
600 V, 60 Hz kW rating
600 V, 60 HzhpCurrent
A Catalog number
6
Chapter 1—PowerXL series overview
Table 9. Type 12/IP54
Constant tor que (CT) /high overload (IH) Variable torque (VT)/low overload (IL)
Frame size
600 V, 60 Hz kW rating
FR1 1.5 2 3.3 2.2 3 4.5 DH1-354D5DN-C54C
2.2 3 4.5 3.7 5 7.5 DH1-357D5DN-C54C
3.7 5 7.5 5.5 7.5 10 DH1-35010DN-C54C
FR2 5.5 7. 5 10 7.5 10 13.5 DH1-35013DN-C54C
7.5 10 13.5 11 15 18 DH1-35018DN-C54C 11 15 18 15 20 22 DH1-35022DN-C54C
FR3 15 20 22 18.5 25 27 DH1-35027DN-C54C
18.5 25 27 22 30 34 DH1-35034DN-C54C 22 30 34 30 40 41 DH1-35041DN-C54C
FR4 30 40 41 37 50 52 DH1-35052DN-C54C
37 50 52 45 60 62 DH1-35062DN-C54C 45 60 62 55 75 80 DH1-35080DN-C54C
FR5 55 75 80 75 100 100 DH1-35100DN-C54C
75 100 100 90 125 125 DH1-35125DN-C54C 90 125 125 110 150 144 DH1-35144DN-C54C
FR6 110 150 144 150 200 208 DH1-35208DN-C54C
150 200 208 187 250 250 DH1-35250DN-C54C
600 V, 60 Hz hpCurrent
A
600 V, 60 Hz kW rating
600 V, 60 HzhpCurrent
A Catalog number
7
Chapter 2—Keypad overview
2
Programmable Soft Key
Chapter 2—Keypad overview
The keypad is the interface between the drive and the user. It features an LCD display, 3 LED lights and 11 buttons. With the control keypad, it is possible to control the speed of a motor, to supervise the state of the equipment and to set the frequency converter’s parameters. See Figure 5.
Figure 5. Keypad and display
Increase Value
Scroll Menu Up
Back/Reset Button
Stop/Off Button
1
Move Cursor Left
Enter Menu Confirm Selection
Decrease Value Scroll Menu Down
Programmable Soft Key
Auto Control Place Select
Move Cursor Right
Start /Hand Button
8 POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—May 2018 www.eaton.com