PowerXL series
DG1 general-purpose drives
Next-generation drives for today’s demands
The DG1 general-purpose drives are part of the Eaton
next-generation PowerXLE series of variable frequency
drives specifically engineered for today’s more demanding
commercial and industrial applications. With an industryleading energy efficiency algorithm, high short-circuit
current rating and robust design, the DG1 offers customers
increased efficiency, safety and reliability.
Features
•
Graphic LCD keypad display
•
Active energy control algorithm
•
On-board communications:
• EtherNet/IP, ModbusT/TCP
• RS-485: Modbus RTU,
BACnetT MS/TP
•
Onboard I/O:
• 8DI, 1DO
• 2AI, 2AO
• 2 FC relays and 1 FA relay
•
Real-time clock with
battery backup
•
5% DC link choke
•
Standard applications:
• Standard
• Multi-pump and fan control
• Multi-PID
• Multi-purpose
•
Advanced configuration
PC tool
Benets
•
Dual VT and CT ratings
•
Easy menu navigation
•
Two configurable
keypad soft keys
•
Conformal coated
boards standard
•
EMC filter standard
•
Brake chopper standard
(FR0–FR3)
Product range
•
230 V to 125 hp, 312 A, 90 kW
•
480 V to 1000 hp, 1180 A,
630 kW
•
575 V to 800 hp, 820 A,
597 kW
•
Open Type/IP00 or IP20 or
Type 1/IP21 or Type 12/IP54
packaging
Catalog numbering system
D G1 – 3 4 4D3 F B – C 21 C
Basic naming
D = Drive
Series
G1 = General purpose
Phase reference
3 = 3~ input /3~output
Input/output voltage
2 = 230 V (208–240 V, –15%, +10%)
4 = 400 V (380–500 V, –15%, +10%)
5 = 600 V (252–600 V, –15%, +10%)
DG1—output current rating (CT)
208–240 V 380–500 V 525–600 V
3D7 = 3.7 A, 0.55 kW, 0.75 hp
4D8 = 4.8 A, 0.75 kW, 1 hp
6D6 = 6.6 A, 1.1 kW, 1.5 hp
7D8 = 7.8 A, 1.5 kW, 2 hp
011 = 11 A, 2.2 kW, 3 hp
012 =12.5 A, 3 kW, 4 hp
017 = 17.5 A, 3.7 kW, 5 hp
025 = 25 A, 5.5 kW, 7.5 hp
031 = 31 A, 7.5 kW, 10 hp
048 = 48 A, 11 kW, 15 hp
061 = 61 A, 15 kW, 20 hp
075 = 75 A, 18.5 kW, 25 hp
088 = 88 A, 22 kW, 30 hp
114 = 114 A , 30 kW, 40 hp
143 = 143 A, 37 kW, 50 hp
170 = 170 A, 45 kW, 60 hp
211 = 211 A, 55 kW, 75 hp
248 = 248 A, 75 kW, 100 hp
2D2 = 2.2 A, 0.75 kW, 1 hp
3D3 = 3.3 A, 1.1 kW, 1.5 hp
4D3 = 4.3 A, 1.5 kW, 2 hp
5D6 = 5.6 A, 2.2 kW, 3 hp
7D6 = 7.6 A, 3 kW, 5 hp
9D0 = 9 A, 4 kW, 7.5 hp (VT)
012 = 12 A, 5.5 kW, 7.5 hp
016 = 16 A, 7.5 kW, 10 hp
023 = 23 A, 11 kW, 15 hp
031 = 31 A, 15 kW, 20 hp
038 = 38 A, 18.5 kW, 25 hp
046 = 46 A, 22 kW, 30 hp
061 = 61 A, 30 kW, 40 hp
072 = 72 A, 37 kW, 50 hp
087 = 87 A, 45 kW, 60 hp
105 = 105 A, 55 kW, 75 hp
140 = 140 A, 75 kW, 100 hp
170 = 170 A, 90 kW, 125 hp
205 = 205 A, 110 kW, 150 hp
245 = 245 A, 132 kW, 200 hp
310 = 310 A, 160 kW, 250 hp
385 = 385 A, 200 kW, 300 hp
460 = 460 A, 250 kW, 350 hp
520 = 520 A, 250 kW, 450 hp
590 = 590 A, 315 kW, 500 hp
650 = 650 A, 355 kW, 500 hp
730 = 730 A, 400 kW, 600 hp
820 = 820 A, 450 kW, 700 hp
920 = 920 A, 500 kW, 800 hp
1K0 = 1180 A, 630 kW, 1000 hp (VT)
3D3 = 3.3 A, 1.5 kW, 2 hp
4D5 = 4.5 A, 2.2 kW, 3 hp
7D5 = 7.5 A, 3.7 kW, 5 hp
010 = 10 A, 5.5 kW, 7.5 hp
013 = 13.5 A, 7.5 kW, 10 hp
018 = 18 A, 11 kW, 15 hp
022 = 22 A, 15 kW, 20 hp
027 = 27 A, 18.5 kW, 25 hp
034 = 34 A, 22 kW, 30 hp
041 = 41 A, 30 kW, 40 hp
052 = 52 A, 37 kW, 50 hp
062 = 62 A, 45 kW, 60 hp
080 = 80 A, 55 kW, 75 hp
100 = 100 A, 75 kW, 100 hp
125 = 125 A, 90 kW, 125 hp
144 = 144 A, 110 kW, 150 hp
208 = 208 A, 132 kW, 200 hp
261 = 261 A, 187 kW, 250 hp
325 = 325 A, 224 kW, 300 hp
385 = 385 A, 224 kW, 300 hp
416 = 416 A, 298 kW, 400 hp
460 = 460 A, 336 kW, 450 hp
520 = 520 A, 373 kW, 500 hp
590 = 590 A, 448 kW, 600 hp
650 = 650 A, 485 kW, 650 hp
820 = 820 A, 597 kW, 800 hp (VT)
Coating of boards
C = Coated
Enclosure (IP rating)
00 = IP00/Open type
20 = IP20
21 = IP21/Type 1
54 = IP54/Type 12
Display option
C = LCD (graphical)
W = No display
Internal brake chopper
N = No brake chopper
B = Brake chopper
Internal EMC filter
D = DC choke only
E = EMC filter only
F = Internal EMC filter and DC choke
N = No EMC filter, no DC choke
Input ratings
Description Specification
Input voltage (Bin) 208–240 V, 380–500 V, 525–600 V, –15 to 10%
Input frequency (fin) 50–60 Hz (variation up to 45–66 Hz)
Connection to power Up to one connection every 60 seconds
Short-circuit withstand rating 100 kAIC (with fuses and circuit breakers)
Output ratings
Description Specification
Output voltage 0 to Vin
VT/IL overload Overload 1.1 x IL (1 min./10 min.)
CT/IH overload Overload 1.5 x IH (1 min./10 min.)
Initial output current 200% (2 sec./20 sec.)
Output frequency 0–400 Hz (standard)
Frequency resolution 0.01 Hz
Ambient conditions
Description Specification
Operating temperature –10 °C (no frost) to +50 °C, up to +60 °C withderating
Storage temperature –40 °C to +70 °C
Relative humidity 0–95% RH, noncondensing, non-corrosive
Altitude 100% load capacity (no derating) up to
3280 ft (1000 m); 1% derating for each
328 ft (100 m) above 3280 ft (1000 m)
9843 ft (3000 m) maximum
Frames and power ranges
Frame size Voltage hp (CT/ IH) kW
Amperes (C T/IH)
FR0 230 Vac 0.75–1.5 0.55–1.1 3.7–6.6
480 Vac 1–3 0.75–2.2 2.2–5.6
FR1 230 Vac 0.75–3 0.55–2.2 3.7–11
480 Vac 1–5 0.75–3.7 2.2–7.6
575 Vac 2–5 1.5–3.7 3.3–7.5
FR2 230 Vac 4–7.5 3–5.5 12.5–25
480 Vac 7.5–15 5.5–11 12–23
575 Vac 7.5–15 5.5–11 10–18
FR3 230 Vac 10–15 7.5–11 31–48
480 Vac 20–30 15–22 31–46
575 Vac 20–30 15–22 22–34
FR4 230 Vac 20–30 15–22 61–88
480 Vac 40–60 30–45 61–87
575 Vac 40–60 30–45 41–62
FR5 230 Vac 40–60 30–45 114–170
480 Vac 75–125 55–90 105–170
575 Vac 75–125 55–90 80–125
FR6 230 Vac 75–100 55–75 211–248
480 Vac 150–200 110–132 205–245
575 Vac 150–200 110–132 144–208
FR7 480 Vac 250–450 160–250 311–520
575 Vac 250–400 187–298 261–416
FR8 480 Vac 500–800 315–500 590–920
575 Vac 450–650 336–485 460–650
kW ratings are at 400 V / 50 Hz. The above guidelines apply unless testing has been completed
to validate a design outside of these recommendations.
Eaton is a registered trademark.
All other trademarks are property
of their respective owners.
Follow us on social media to get the
latest product and support information.