Cutler Hammer, Div of Eaton Corp DG1 Product Flyer

PowerXL series
DG1 general-purpose drives
Next-generation drives for today’s demands
The DG1 general-purpose drives are part of the Eaton next-generation PowerXLE series of variable frequency drives specifically engineered for today’s more demanding commercial and industrial applications. With an industry­leading energy efficiency algorithm, high short-circuit current rating and robust design, the DG1 offers customers increased efficiency, safety and reliability.
Graphic LCD keypad display
Active energy control algorithm
On-board communications:
EtherNet/IP, ModbusT/TCP
RS-485: Modbus RTU,
BACnetT MS/TP
Onboard I/O:
8DI, 1DO
2AI, 2AO
2 FC relays and 1 FA relay
Real-time clock with battery backup
5% DC link choke
Standard applications:
Standard
Multi-pump and fan control
Multi-PID
Multi-purpose
Advanced configuration PC tool
Benets
Dual VT and CT ratings
Easy menu navigation
Two configurable keypad soft keys
Conformal coated boards standard
EMC filter standard
Brake chopper standard (FR0–FR3)
Product range
230 V to 125 hp, 312 A, 90 kW
480 V to 1000 hp, 1180 A, 630 kW
575 V to 800 hp, 820 A, 597 kW
Open Type/IP00 or IP20 or Type 1/IP21 or Type 12/IP54 packaging
Catalog numbering system
D G1 – 3 4 4D3 F B – C 21 C
Basic naming
D = Drive
Series
G1 = General purpose
Phase reference
3 = 3~ input /3~output
Input/output voltage
2 = 230 V (208–240 V, –15%, +10%) 4 = 400 V (380–500 V, –15%, +10%) 5 = 600 V (252–600 V, –15%, +10%)
DG1—output current rating (CT)
208–240 V 380–500 V 525–600 V
3D7 = 3.7 A, 0.55 kW, 0.75 hp 4D8 = 4.8 A, 0.75 kW, 1 hp 6D6 = 6.6 A, 1.1 kW, 1.5 hp 7D8 = 7.8 A, 1.5 kW, 2 hp 011 = 11 A, 2.2 kW, 3 hp 012 =12.5 A, 3 kW, 4 hp 017 = 17.5 A, 3.7 kW, 5 hp 025 = 25 A, 5.5 kW, 7.5 hp 031 = 31 A, 7.5 kW, 10 hp 048 = 48 A, 11 kW, 15 hp 061 = 61 A, 15 kW, 20 hp 075 = 75 A, 18.5 kW, 25 hp 088 = 88 A, 22 kW, 30 hp 114 = 114 A , 30 kW, 40 hp 143 = 143 A, 37 kW, 50 hp 170 = 170 A, 45 kW, 60 hp 211 = 211 A, 55 kW, 75 hp 248 = 248 A, 75 kW, 100 hp
2D2 = 2.2 A, 0.75 kW, 1 hp 3D3 = 3.3 A, 1.1 kW, 1.5 hp 4D3 = 4.3 A, 1.5 kW, 2 hp 5D6 = 5.6 A, 2.2 kW, 3 hp 7D6 = 7.6 A, 3 kW, 5 hp 9D0 = 9 A, 4 kW, 7.5 hp (VT) 012 = 12 A, 5.5 kW, 7.5 hp 016 = 16 A, 7.5 kW, 10 hp 023 = 23 A, 11 kW, 15 hp 031 = 31 A, 15 kW, 20 hp 038 = 38 A, 18.5 kW, 25 hp 046 = 46 A, 22 kW, 30 hp 061 = 61 A, 30 kW, 40 hp 072 = 72 A, 37 kW, 50 hp 087 = 87 A, 45 kW, 60 hp 105 = 105 A, 55 kW, 75 hp 140 = 140 A, 75 kW, 100 hp 170 = 170 A, 90 kW, 125 hp 205 = 205 A, 110 kW, 150 hp 245 = 245 A, 132 kW, 200 hp 310 = 310 A, 160 kW, 250 hp 385 = 385 A, 200 kW, 300 hp 460 = 460 A, 250 kW, 350 hp 520 = 520 A, 250 kW, 450 hp 590 = 590 A, 315 kW, 500 hp 650 = 650 A, 355 kW, 500 hp 730 = 730 A, 400 kW, 600 hp 820 = 820 A, 450 kW, 700 hp 920 = 920 A, 500 kW, 800 hp 1K0 = 1180 A, 630 kW, 1000 hp (VT)
3D3 = 3.3 A, 1.5 kW, 2 hp 4D5 = 4.5 A, 2.2 kW, 3 hp 7D5 = 7.5 A, 3.7 kW, 5 hp 010 = 10 A, 5.5 kW, 7.5 hp 013 = 13.5 A, 7.5 kW, 10 hp 018 = 18 A, 11 kW, 15 hp 022 = 22 A, 15 kW, 20 hp 027 = 27 A, 18.5 kW, 25 hp 034 = 34 A, 22 kW, 30 hp 041 = 41 A, 30 kW, 40 hp 052 = 52 A, 37 kW, 50 hp 062 = 62 A, 45 kW, 60 hp 080 = 80 A, 55 kW, 75 hp 100 = 100 A, 75 kW, 100 hp 125 = 125 A, 90 kW, 125 hp 144 = 144 A, 110 kW, 150 hp 208 = 208 A, 132 kW, 200 hp 261 = 261 A, 187 kW, 250 hp 325 = 325 A, 224 kW, 300 hp 385 = 385 A, 224 kW, 300 hp 416 = 416 A, 298 kW, 400 hp 460 = 460 A, 336 kW, 450 hp 520 = 520 A, 373 kW, 500 hp 590 = 590 A, 448 kW, 600 hp 650 = 650 A, 485 kW, 650 hp 820 = 820 A, 597 kW, 800 hp (VT)
Coating of boards
C = Coated
Enclosure (IP rating)
00 = IP00/Open type 20 = IP20 21 = IP21/Type 1 54 = IP54/Type 12
Display option
C = LCD (graphical) W = No display
Internal brake chopper
N = No brake chopper B = Brake chopper
Internal EMC filter
D = DC choke only E = EMC filter only F = Internal EMC filter and DC choke N = No EMC filter, no DC choke
Input ratings
Description Specification
Input voltage (Bin) 208–240 V, 380–500 V, 525–600 V, –15 to 10% Input frequency (fin) 50–60 Hz (variation up to 45–66 Hz) Connection to power Up to one connection every 60 seconds
Short-circuit withstand rating 100 kAIC (with fuses and circuit breakers)
Output ratings
Description Specification
Output voltage 0 to Vin VT/IL overload Overload 1.1 x IL (1 min./10 min.) CT/IH overload Overload 1.5 x IH (1 min./10 min.) Initial output current 200% (2 sec./20 sec.) Output frequency 0–400 Hz (standard) Frequency resolution 0.01 Hz
Ambient conditions
Description Specification
Operating temperature –10 °C (no frost) to +50 °C, up to +60 °C withderating Storage temperature –40 °C to +70 °C Relative humidity 0–95% RH, noncondensing, non-corrosive Altitude 100% load capacity (no derating) up to
3280 ft (1000 m); 1% derating for each 328 ft (100 m) above 3280 ft (1000 m) 9843 ft (3000 m) maximum
Frames and power ranges
Frame size Voltage hp (CT/ IH) kW
Amperes (C T/IH)
FR0 230 Vac 0.75–1.5 0.55–1.1 3.7–6.6
480 Vac 1–3 0.75–2.2 2.2–5.6
FR1 230 Vac 0.75–3 0.55–2.2 3.7–11
480 Vac 1–5 0.75–3.7 2.2–7.6 575 Vac 2–5 1.5–3.7 3.3–7.5
FR2 230 Vac 4–7.5 3–5.5 12.5–25
480 Vac 7.5–15 5.5–11 12–23 575 Vac 7.5–15 5.5–11 10–18
FR3 230 Vac 10–15 7.5–11 31–48
480 Vac 20–30 15–22 31–46 575 Vac 20–30 15–22 22–34
FR4 230 Vac 20–30 15–22 61–88
480 Vac 40–60 30–45 61–87 575 Vac 40–60 30–45 41–62
FR5 230 Vac 40–60 30–45 114–170
480 Vac 75–125 55–90 105–170 575 Vac 75–125 55–90 80–125
FR6 230 Vac 75–100 55–75 211–248
480 Vac 150–200 110–132 205–245 575 Vac 150–200 110–132 144–208
FR7 480 Vac 250–450 160–250 311–520
575 Vac 250–400 187–298 261–416
FR8 480 Vac 500–800 315–500 590–920
575 Vac 450–650 336–485 460–650
kW ratings are at 400 V / 50 Hz. The above guidelines apply unless testing has been completed to validate a design outside of these recommendations.
Eaton is a registered trademark.
All other trademarks are property of their respective owners.
Follow us on social media to get the latest product and support information.
Loading...