Cutler Hammer, Div of Eaton Corp DG1 Operation Manual

PowerXL DG1 Series VFD
Application manual
Effective April 2018 Supersedes June 2017
Supports Firmware Version Bundle: DG1-V0034-ETN
Disclaimer of warranties and limitation of liability
The information, recommendations, descriptions, and safety notations in this document are based on Eaton’s experience and judgment and may not cover all contingencies. If further information is required, an Eaton sales office should be consulted. Sale of the product shown in this literature is subject to the terms and conditions outlined in appropriate Eaton selling policies or other contractual agreement between Eaton and the purchaser.
THERE ARE NO UNDERSTANDINGS, AGREEMENTS, WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY, OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES. ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON. THE CONTENTS OF THIS DOCUMENT SHALL NOT BECOME PART OF OR MODIFY ANY CONTRACT BETWEEN THE PARTIES.
In no event will Eaton be responsible to the purchaser or user in contract, in tort (including negligence), strict liability, or otherwise for any special, indirect, incidental, or consequential damage or loss whatsoever, including but not limited to damage or loss of use of equipment, plant or power system, cost of capital, loss of power, additional expenses in the use of existing power facilities, or claims against the purchaser or user by its customers resulting from the use of the information, recommendations, and descriptions contained herein. The information contained in this manual is subject to change withoutnotice.
Cover Photo: Eaton PowerXL
®
Series Drives
ii
Support services
Support services
The goal of Eaton is to ensure your greatest possible satisfaction with the operation of our products. We are dedicated to providing fast, friendly, and accurate assistance. That is why we offer you so many ways to get the support you need. Whether it is by phone, fax, or email, you can access Eaton’s support information 24 hours a day, seven days a week.
Our wide range of services is listed below. You should contact your local distributor for product pricing,
availability, ordering, expediting, and repairs.
Website
Use the Eaton Website to find product information. You can also find information on local distributors or Eaton’s sales offices.
Website address
www.eaton.com/drives
EatonCare customer support center
Call the EatonCare Support Center if you need assistance with placing an order, stock availability or proof of shipment, expediting an existing order, emergency shipments, product price information, returns other than warranty returns, and information on local distributors or sales offices.
Voice: 877-ETN-CARE (386-2273) (8:00 a.m.–6:00 p.m. EST) After-Hours Emergency: 800-543-7038 (6:00 p.m.–8:00 a.m. EST)
Drives technical resource center
Voice: 877-ETN-CARE (386-2273) option 2, option 6 (8:00 a.m.–5:00 p.m. Central Time U.S. [UTC –6]) email: TRCDrives@Eaton.com
For customers in europe, contact
Phone: +49 (0) 228 6 02-3640 Hotline: +49 (0) 180 5 223822 email: AfterSalesEGBonn@Eaton.com www.eaton.com/moeller/aftersales
iii
Table of contents
SAFETY
Before commencing the installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..xiii
Definitions and symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..xiv
Hazardous high voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..xiv
Warnings and cautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..xiv
Important safety information ............................................xv
CHAPTER 1—powerXL DG1 series overview
How to use this manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...23
Receiving and inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..23
Real time clock battery activation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ....23
Rating label . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...24
Carton labels (U.S. and Europe) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...24
Catalog number system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...25
Power ratings and product selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ....26
Chapter 2—Keypad overview
Keypad buttons ......................................................32
LED lights ..........................................................34
LCD display .........................................................34
Chapter 3—Menu overview
Main menu page .....................................................37
Menu navigation .....................................................37
Menu structure ......................................................38
T—Favorite .........................................................49
Chapter 4—Startup
Startup wizard page ...................................................50
Startup wizard .......................................................51
Application macro mini-wizard ...........................................52
PID Mini-wizard ......................................................52
Chapter 5—Standard application
Introduction .........................................................53
I/O Controls .........................................................53
Force open/force close selection ........................................54
DIGIN Selection .....................................................54
Option board digIN selection ............................................54
Timer channel selection ................................................54
Force open/force close selection ........................................54
Control I/O configuration ...............................................55
Standard application—parameters list .....................................57
iv
Table of Contents, continued
Chapter 6 — Multi-Pump and fan control application
Introduction ........................................................80
I/O Controls ........................................................80
Control examples ....................................................82
Control I/O Configuration ...............................................91
Pump and fan application—Parameters list .................................93
Chapter 7—Multi-pid application
Introduction ........................................................123
I/O Controls ........................................................123
Multi-PID application—Parameters list ...................................127
Chapter 8 – Multi-Purpose application
Introduction .......................................................161
Multi-Purpose application—parameters list ................................165
Appendix A – Description of parameters
Application level .....................................................202
Appendix B – Fault Log
Fault codes and descriptions ...........................................302
Appendix C – Recommend Cyber security information
Recommended Secure Hardening Guidelines .............................307
v
List of gures
Figure 1. RTC battery connection ...........................................23
Figure 2. Rating label.....................................................24
Figure 3. Catalog numbering system ........................................25
Figure 4. Keypad and display ...............................................31
Figure 5. General view of LCD .............................................34
Figure 6. Welcome page ..................................................34
Figure 7. Upgrade page ...................................................35
Figure 8. Auto backup page................................................35
Figure 9. Main menu .....................................................35
Figure 10. Parent node page ...............................................35
Figure 11. Parameter page.................................................36
Figure 12. Parameter page from favorite menu.................................36
Figure 13. Fault page .....................................................36
Figure 14. Main Menu Page ...............................................37
Figure 15. Main menu navigation ...........................................37
Figure 16. M—Monitor ...................................................39
Figure 17. Active Faults ...................................................40
Figure 18. Pop-up active faults..............................................41
Figure 19. Fault history ...................................................42
Figure 20. Parameter menu overview .......................................43
Figure 21. Parameter sets .................................................44
Figure 22. Down from keypad ..............................................45
Figure 23. Parameters comparison ..........................................46
Figure 24. Password .....................................................47
Figure 25. Edit parameter value.............................................48
Figure 26. Parameter locked ...............................................49
Figure 27. Example of Two-Pump Autochange, Main Diagram .....................82
Figure 28. Two-Pump Autochange System Principal Control Diagram................83
Figure 29. Example of Three-Pump Autochange, Main Diagram ....................84
Figure 30. Three-Pump Autochange System Principal Control Diagram ..............84
Figure 31. Example of the Function of the PFC Application
Figure 32. Multi Pump Control Curve ........................................86
Figure 33. Multi-Drive/Multi-Pump Layout.....................................86
Figure 34. PowerXL Drives with 10 V Supply with a 0–10 V Transducer ..............87
Figure 35. PowerXL Drives with 10 V Supply with a 4–20 mA Transducer ............88
Figure 36. PowerXL Drives with Ext Supply with a 4–20 mA Transducer .............89
Figure 37. Bandwidth Feedback.............................................90
Figure 38. PID Controller Flowchart.........................................124
Figure 39. Acceleration and deceleration time ................................202
Figure 40. Motor parameters from ratings plate...............................203
Figure 41. With and without reference scaling.................................206
Figure 42. AI1 2wire-current ..............................................207
with Three Auxiliary Drives ................................... . . . . 85
vi
List of gures, continued
Figure 43. AI1 3wire-current ..............................................207
Figure 44. AI1 4wire-current ..............................................207
Figure 45. AI1 reference potentiometer 10V ..................................207
Figure 46. Analog input AI scaling ..........................................208
Figure 47. AI1 signal filtering ..............................................208
Figure 48. AI1 No signal inversion..........................................209
Figure 49. AI1 Signal Inversion ............................................209
Figure 50. Example of joystick hysteresis ...................................2 10
Figure 51. Example of sleep limit function ...................................211
Figure 52. A/2 2wire-current ..............................................212
Figure 53. AI2 3wire-current ..............................................212
Figure 54. AI2 4wire-current ..............................................212
Figure 55. AI2 pot ref....................................................212
Figure 56. AI2 differential voltage ..........................................213
Figure 57. AI2 Filter time .................................................213
Figure 58. AI2 No signal inversion .........................................214
Figure 59. AI2 Signal inversion ............................................214
Figure 60. Example of joystick hysteresis ...................................215
Figure 61. Example of sleep limit function ...................................215
Figure 62. Start forward/start reverse ......................................216
Figure 63. Start, stop and reverse .........................................217
Figure 64. Start pulse/stop pulse . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .218
Figure 65. Activation of fixed frequencies ...................................221
Figure 66. Start forward/start reverse ......................................227
Figure 67. Start, stop and reverse ..........................................227
Figure 68. Start pulse/stop pulse . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .228
Figure 69. Analog output filtering...........................................232
Figure 70. Analog output scaling ...........................................232
Figure 71. Analog output invert.............................................233
Figure 72. AO2 Filter Time ................................................234
Figure 73. Analog output scalling...........................................234
Figure 74. Analog output invert ............................................235
Figure 75. Supervision function ...........................................237
Figure 76. Supervision function ............................................238
Figure 77. External brake control ...........................................238
Figure 78. Acceleration/Deceleration (S-shaped) ...............................244
Figure 79. Acceleration/Deceleration (S-shaped) ...............................245
Figure 80. Example of skip frequency area setting .............................246
Figure 81. Ramp speed scaling between skip frequencies .......................246
Figure 82. Linear and squared change of motor voltage ........................248
Figure 83. Programmable V/Hz curve........................................249
Figure 84. Speed control F1 ..............................................251
Figure 85. Motor thermal current it curve ....................................255
vii
List of gures, continued
Figure 86. Motor temperature calculation ....................................256
Figure 87. Stall characteristics settings.......................................256
Figure 88. Stall time count ................................................257
Figure 89. Setting of minimum load.........................................257
Figure 90. Underload time counter function ..................................258
Figure 91. Auto restart fail (try number >2.)...................................259
Figure 92. Setting up PID application........................................267
Figure 93. DC-Braking time when stop mode = coasting ........................275
Figure 94. DC-Braking time when stop mode = ramp...........................275
List of tables
Table 1. Common abbreviations ............................................23
Table 2. Type/IP20 .......................................................26
Table 3. Type 1/IP21 .....................................................26
Table 4. Type 12/IP54 ....................................................26
Table 5. Type/IP20 .......................................................27
Table 6. Type 1/IP21 .....................................................27
Table 7. Type 12/IP54 ..................................................... 28
Table 8. Type 0/IP00 ..................................................... 28
Table 9. Type 1/IP21 .....................................................29
Table 10. Type 12/IP54 .................................................... 29
Table 11. Type 0/IP00 .....................................................30
Table 12. Keypad buttons .................................................32
Table 13. LED state indicators .............................................34
Table 14. Soft keys ......................................................35
Table 15. Keypad menus .................................................. 38
Table 16. Startup Wizard Instructions ........................................51
Table 17. Multi-Pump and fan control ........................................52
Table 18. PID Mini-Wizard values ...........................................52
Table 19. I/O connection .................................................. 55
Table 20. Drive communication ports ........................................56
Table 21. Monitor—M ....................................................57
Table 22. Operate mode—O ...............................................59
Table 23. Basic parameters—P1 ............................................60
Table 24. Analog input—P2 ................................................61
Table 25. Digital input—P3 ................................................62
Table 26. Analog output—P4 ..............................................64
Table 27. Digital output—P5 ...............................................66
Table 28. Drive control—P7 ...............................................68
Table 29. Motor control—P8 ..............................................70
viii
List of tables, continued
Table 30. Protections—P9 ................................................71
Table 31. Preset speed—P12 .............................................. 74
Table 32. Brake—P14 .................................................... 74
Table 33. FB Process Data Input Sel—P20.1 .................................74
Table 34. FB Process Data Output Sel—P20.2 ................................75
Table 35. Basic Setting— P20.3.1 ..........................................75
Table 36. Modbus RTU— P20.3.2 ..........................................75
Table 37. BACnet MS/TP— P20.3.3 .........................................53
Table 38. Ethernet IP—P20.4 .............................................76
Table 39. Modbus TCP—P20.5 ............................................. 76
Table 40. Basic setting—P21.1 .............................................77
Table 41. Version Info—P21.2 ..............................................79
Table 42. Application Info—P21.3 ...........................................79
Table 43. User Info—P21.4 ................................................79
Table 44. Multi-Pump and fan application default I/O connection ..................91
Table 45. Drive communication ports ........................................92
Table 46. Monito r—M ...................................................93
Table 47. Operate mode—O ...............................................95
Table 48. Basic paramete rs—P1 ...........................................96
Table 49. Analog input—P2 ................................................97
Table 50. Digital input—P3 ................................................98
Table 51. Analog output—P4 .............................................. 10 0
Table 52. Digital output—P5 .............................................. 101
Table 53. Drive control—P7 .............................................. 103
Table 54. Moto r control—P8 .............................................104
Table 55. Prote ctions—P9 ...............................................104
Table 56. PID controller 1—P10 ...........................................107
Table 57. Preset speed—P12 ............................................. 110
Table 58. Brake—P14 ................................................... 110
Table 59. Fire mode—P15 ............................................... 111
Table 60. Second moto r paramete r—P16 .................................. 111
Table 61. Bypass—P17 .................................................. 111
Table 62. Basic sett ings—P18.1 ..........................................11 2
Table 63. Operation mode P18.2.1 ......................................... 112
Table 64. Multi Pump status P18.2.2 ....................................... 113
Table 65. Network status P18.2.3 .......................................... 113
Table 66. Last fault code P18.3.1 .......................................... 114
Table 67. Output frequency P18.3.2 ........................................ 114
Table 68. Moto r voltage P18.3.3 ..........................................11 4
Table 69. Moto r current P18.3.4 .......................................... 114
Table 70. Moto r to rque P18.3.5 .......................................... 11 4
Table 71. Moto r power P18.3.6 ........................................... 11 4
ix
List of tables, continued
Table 72. Moto r speed P18.3.7 ...........................................115
Table 73. Moto r run time P18.3.8 ......................................... 115
Table 74. Multi-Pump single drive - P18.4 .................................... 11 5
Table 75. Multi-Pump multi drive - P18.5 .................................... 11 5
Table 76. Prote ctions - P18.6 ............................................ 116
Table 77. Real time clock—P19 ............................................ 116
Table 78. FB Process Data Input Sel—P20.1 ................................. 117
Table 79. FB Process Data Output Sel—P20.2 ............................... 117
Table 80. Basic Sett ing— P20.3.1 ......................................... 118
Table 81. Modbus RTU—P20.3.2 .......................................... 118
Table 82. BACnet MS/TP—P20.3.3 ......................................... 118
Table 83. Ethernet IP—P20.4 ............................................. 11 9
Table 84. Modbus TCP—P20.5 ............................................ 119
Table 85. Basic sett ing—P21.1 ............................................120
Table 86. Version info—P21.2 .............................................121
Table 87. Application info—P21.3 ..........................................122
Table 88. User info—P21.4 ...............................................122
Table 89. Multi-PID Application Default I/O Configuration .......................125
Table 90. Drive Communication Ports ......................................126
Table 91. Monitor—M ...................................................127
Table 92. Operate Mode—O. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129
Table 93. Basic Parameters—P1 ........................................... 130
Table 94. Analog Input—P2 ..............................................131
Table 95. Digital Input—P3 ...............................................132
Table 96. Analog Output—P4 .............................................135
Table 97. Digital Output—P5 ..............................................136
Table 98. Drive Control—P7 ..............................................138
Table 99. Motor Control—P8 .............................................139
Table 100. Protections—P9 ...............................................140
Table 101. PID Controller 1—P10 ..........................................142
Table 102. PID Controller 2—P11 ..........................................145
Table 103. Preset Speed—P12 ............................................147
Table 104. Brake—P14 ..................................................148
Table 105. Fire Mode—P15 ...............................................148
Table 106. Second Motor Parameter—P16 ...................................148
Table 107. Bypass—P17 .................................................149
Table 108. Basic Settings - P18.1 ..........................................149
Table 109. Operation Mode P18.2.1 ........................................150
Table 110. Multi Pump Status P18.2.2 ......................................150
Table 111. Network Status P18.2.3 .........................................151
Table 112. Last Fault Code P18.3.1 ......................................... 151
Table 113. Output Frequency P18.3.2 .......................................151
x
List of tables, continued
Table 114. Motor Voltage P18.3.3 ..........................................151
Table 115. Motor Current P18.3.4 ..........................................152
Table 116. Motor Torque P18.3.5 ...........................................152
Table 117. Motor Power P18.3.6 ...........................................152
Table 118. Motor Speed P18.3.7 ...........................................152
Table 119. Motor Run Time P18.3.8 ........................................152
Table 120. Multi-Pump Single Drive - P18.4 ..................................153
Table 121. Multi-Pump Multi Drive - P18.5 ...................................153
Table 122. Protections—P18.6 ............................................ 153
Table 123. Real Time Clock—P19 ..........................................154
Table 124. FB Process Data Input Sel—P20.1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 155
Table 125. FB Process Data Output Sel—P20.2 ...............................155
Table 126. Basic Setting— P20.3.1 .........................................156
Table 127. Modbus RTU— P20.3.2 ........................................156
Table 128. BACnet MS/TP— P20.3.3 .......................................157
Table 129. Table 118. Ethernet IP—P20.4 .................................... 157
Table 130. Modbus TCP—P20.5 ..........................................157
Table 131. Basic Setting—P21.1 ...........................................158
Table 132. Version Info—P21.2 ............................................159
Table 133. Application Info—P21.3 .........................................159
Table 134. User Info—P21.4 .............................................. 160
Table 135. Multi-Purpose application default I/O configuration ...................163
Table 136. Drive communication ports ......................................164
Table 137. Monitor—M ..................................................165
Table 138. Operate mode—O ............................................. 167
Table 139. Basic parameters—P1 .......................................... 168
Table 140. Analog input—P2 .............................................. 169
Table 141. Digital input—P3 .............................................. 170
Table 142. Analog output—P4 ............................................173
Table 143. Digital output—P5 ............................................. 174
Table 144. Logic function—P6 ............................................177
Table 145. Drive control—P7 .............................................178
Table 146. Motor control—P8 ............................................. 179
Table 147. Protections—P9 ...............................................181
Table 148. PID Controller 1—P10 ..........................................184
Table 149. PID Controller 2—P11 ..........................................187
Table 150. Preset speed—P12 ............................................189
Table 151. Torque control—P13 ............................................ 190
Table 152. Brake—P14 .................................................. 190
Table 153. Fire Mode—P15 ..............................................191
Table 154. Second motor parameter—P16 ................................... 191
Table 155. Bypass—P17 .................................................191
xi
List of tables, continued
Table 156. Basic settings—P18.1 ..........................................192
Table 157. Operation mode—P18.2.1 .......................................192
Table 158. Multi pump status—P18.2.2 .....................................193
Table 159. Network status—P18.2.3 .......................................193
Table 160. Last fault code—P18.3.1 ........................................193
Table 161. Output frequency—P18.3.2 ...................................... 194
Table 162. Motor voltage—P18.3.3 ........................................194
Table 163. Motor current—P18.3.4 ......................................... 194
Table 164. Motor torque—P18.3.5 .........................................194
Table 165. Motor power—P18.3.6 .........................................194
Table 166. Motor Speed—P18.3.7 .........................................194
Table 167. Motor run Time—P18.3.8 ........................................ 195
Table 168. Multi-pump single drive—P18.4 ..................................195
Table 169. Multi-Pump multi drive—P18.5 ...................................195
Table 170. Protections—P18.6 ............................................195
Table 171. Real time clock—P19 ...........................................196
Table 172. FB Process Data Input Sel—P20.1 ................................197
Table 173. FB Process Data Output Sel—P20.2 ............................... 197
Table 174. Basic Setting— P20.3.1 .........................................198
Table 175. Modbus RTU— P20.3.2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 198
Table 176. BACnet MS/TP— P20.3.3 .......................................198
Table 177. Ethernet IP—P20.4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 199
Table 178. Modbus TCP—P20.5 ........................................... 199
Table 179. Basic setting—P21.1 ........................................... 199
Table 180. Version info—P21.2 ............................................201
Table 181. Application info—P21.3 .........................................201
Table 182. User info—P21.4 .............................................. 201
Table 183. Active Faults ................................................. 302
Table 184. History faults .................................................302
xii
Safety
WARNING! DANGEROUS ELECTRICAL VOLTAGE!
Before commencing the installation
Disconnect the power supply of the device
Ensure that devices cannot be accidentally restarted
Verify isolation from the supply
Earth and short circuit the device
Cover or enclose any adjacent live components
Only suitably qualified personnel in accordance with EN 50110-1/-2 (VDE 0105 Part 100) may work on this device/system
Before installation and before touching the device ensure that you are free of electrostatic charge
The functional earth (FE, PES) must be connected to the protective earth (PE) or the potential equalization. The system installer is responsible for implementing this connection
Connecting cables and signal lines should be installed so that inductive or capacitive interference does not impair the automation functions
Install automation devices and related operating elements in such a way that they are well protected against unintentional operation
Suitable safety hardware and software measures should be implemented for the I/O interface so that an open circuit on the signal side does not result in undefined states in the automation devices
Ensure a reliable electrical isolation of the extra-low voltage of the 24 V supply. Only use power supply units complying with IEC 60364-4-41 (VDE 0100 Part 410) or HD384.4.41 S2
Deviations of the input voltage from the rated value must not exceed the tolerance limits given in the specifications, otherwise this may cause malfunction and dangerous operation
Emergency stop devices complying with IEC/EN 60204-1 must be effective in all operating modes of the automation devices. Unlatching the emergency-stop devices must not cause a restart
Devices that are designed for mounting in housings or control cabinets must only be operated and controlled after they have been installed and with the housing closed. Desktop or portable units must only be operated and controlled in enclosed housings
Measures should be taken to ensure the proper restart of programs interrupted after a voltage dip or failure. This should not cause dangerous operating states even for a short time. If necessary, emergency-stop devices should be implemented
Wherever faults in the automation system may cause injury or material damage, external measures must be implemented to ensure a safe operating state in the event of a fault or malfunction (for example, by means of separate limit switches, mechanical interlocks, and so on)
Depending on their degree of protection, adjustable frequency drives may contain live bright metal parts, moving or rotating components, or hot surfaces during and immediately after operation
Removal of the required covers, improper installation, or incorrect operation of motor or adjustable frequency drive may cause the failure of the device and may lead to serious injury or damage
The applicable national accident prevention and safety regulations apply to all work carried out on live adjustable frequency drives
The electrical installation must be carried out in accordance with the relevant regulations (for example, with regard to cable cross sections, fuses, PE)
Transport, installation, commissioning, and maintenance work must be carried out only by qualified personnel (IEC 60364, HD 384 and national occupational safetyregulations)
Installations containing adjustable frequency drives must be provided with additional monitoring and protective devices in accordance with the applicable safety regulations. Modifications to the adjustable frequency drives using the operating software are permitted
All covers and doors must be kept closed during operation
To reduce hazards for people or equipment, the user must include in the machine design measures that restrict the consequences of a malfunction or failure of the drive (increased motor speed or sudden standstill of motor). These measures include:
Other independent devices for monitoring safety-related
variables (speed, travel, end positions, and so on)
Electrical or non-electrical system-wide measures
(electrical or mechanical interlocks)
Never touch live parts or cable connections of
the adjustable frequency drive after it has been disconnected from the power supply. Due to the charge in the capacitors, these parts may still be live after disconnection. Fit appropriate warning signs
xiii
Denitions and symbols
WARNING
This symbol indicates high voltage. It calls your attention to items or operations that could be dangerous to you and other persons operating this equipment. Read the message and follow the instructions carefully. This symbol is the “Safety Alert Symbol”. It occurs with either of two signal words: CAUTION or WARNING, as described below.
WARNING
Indicates a potentially hazardous situation which, if not avoided, can result in serious injury or death.
CAUTION
Indicates a potentially hazardous situation which, if not avoided, can result in minor to moderate injury, or serious damage to the product. The situation described in the CAUTION may, if not avoided, lead to serious results. Important safety measures are described in CAUTION (as well as WARNING).
Hazardous high voltage
WARNING
Motor control equipment and electronic controllers are connected to hazardous line voltages. When servicing drives and electronic controllers, there may be exposed components with housings or protrusions at or above line potential. Extreme care should be taken to protect against shock.
Warnings and cautions
This manual contains clearly marked cautions and warnings which are intended for your personal safety and to avoid any unintentional damage to the product or connected appliances. Please read the information included in cautions and warnings carefully.
WARNING
The relay outputs and other I/O-terminals may have a dangerous control voltage present even when PowerXL DG1 is disconnected from mains.
WARNING
Be sure not to plug the Ethernet IP cable to the terminal under the keypad! This might harm your personal computer.
WARNING
Be sure not to plug the Modbus TCP cable to the terminal under the keypad! This might harm your personal computer.
CAUTION
Remove external control signal before resetting the fault to prevent unintentional restart of the drive.
Stand on an insulating pad and make it a habit to use only one hand when checking components. Always work with another person in case an emergency occurs. Disconnect power before checking controllers or performing maintenance. Be sure equipment is properly grounded. Wear safety glasses whenever working on electronic controllers or rotating machinery.
xiv
Important safety information
Hazardous high voltage
WARNING
The components of the power unit of PowerXL Series are live when the AC drive is connected to mains potential. Coming into contact with this voltage is extremely dangerous and may cause death or severe injury.
WARNING
The motor terminals U, V, W and the brake resistor terminals are live when PowerXL Series is connected to mains, even if the motor is not running.
WARNING
After disconnecting the AC drive from the mains, wait until the indicators on the keypad go out (if no keypad is attached see the indicators on the cover). Wait 5 more minutes before doing any work on the connections of PowerXL Series. Do not open the cover before this time has expired. After expiration of this time, use a measuring equipment to absolutely ensure that no voltage is present. Always ensure absence of voltage before starting any electrical work!
WARNING
The control I/O-terminals are isolated from the mains potential. However, the relay outputs and other I/O­terminals may have a dangerous control voltage present even when PowerXL DG1 is disconnected from mains.
WARNING
Before connecting the AC drive to mains, confirm that the front and cable covers of PowerXL DG1 are closed.
WARNING
During a ramp stop (see the Application Manual), the motor is still generating voltage to the drive. Therefore, do not touch the components of the AC drive before the motor has completely stopped. Wait until the indicators on the keypad go out (if no keypad is attached see the indicators on the cover). Wait additional 5 minutes before starting any work on the drive.
Important warnings
WARNING
PowerXL Series AC drive is meant for fixed installations only.
WARNING
Do not perform any measurements when the AC drive is connected to the mains.
WARNING
The ground leakage current of PowerXL Series AC drives exceeds 3.5 mA AC. According to standard EN61800-5-1, a reinforced protective ground connection must be ensured.
WARNING
If the AC drive is used as a part of a machine, the machine manufacturer is responsible for providing the machine with a supply disconnecting device (EN 60204-1).
WARNING
Only spare parts delivered by Eaton can be used.
WARNING
At power-up, power brake or fault reset the motor will start immediately if the start signal is active, unless the pulse control for Start/Stop logic has been selected. Furthermore, the I/O functionalistic (including start inputs) may change if parameters, applications or software are changed. Disconnect, therefore, the motor if an unexpected start can cause danger.
WARNING
The motor starts automatically after automatic fault reset if the auto restart function is activated. See the Application Manual for more detailed information.
WARNING
Prior to measurements on the motor or the motor cable, disconnect the motor cable from the AC drive.
WARNING
Do not touch the components on the circuit boards. Static voltage discharge may damage the components.
WARNING
Check that the EMC level of the AC drive corresponds to the requirements of your supply network.
xv
Additional cautions
CAUTION
The PowerXL DG1 AC drive must always be grounded with an grounding conductor connected to the grounding terminal marked with. The ground leakage current of PowerXL DG1 exceeds 3.5 mA AC. According to EN61800-5-1, one or more of the following conditions for the associated protective circuit shall be satisfied:
a) The protective conductor shall have a cross-sectional
area of at least 10 mm
2
Cu or 16 mm2 Al, through its
total run
b) Where the protective conductor has a cross-sectional
area of less than 10 mm2 Cu or 16 mm2 Al, a second protective conductor of at least the same cross-sectional area shall be provided up to a point where the protective conductor has a cross-sectional area not less than 10 mm
2
Cu or 16 mm2 Al
c) Automatic disconnection of the supply in case of loss
of continuity of the protective conductor. The cross-sectional area of every protective grounding conductor that does not form part of the supply cable or cable enclosure shall, in any case, be not less than:
2.5mm2 if mechanical protection is provided or
4 mm2 if mechanical protection is not provided.
The ground fault protection inside the AC drive
protects only the drive itself against ground faults in the motor or the motor cable. It is not intended for personal safety. The ground fault protection inside the AC drive protects only the drive itself against ground faults in the motor or the motor cable. It is not intended for personal safety. Due to the high capacitive currents present in the AC drive, fault current protective switches may not function properly.
Do not perform any voltage withstand tests on
any part of PowerXL Series. There is a certain procedure according to which the tests shall be performed. Ignoring this procedure may result in damagedproduct.
xvi
Sécurité
AVERTISSEMENT ! TENSION ÉLECTRIQUE DANGEREUSE !
Avant de commencer l’installation
Débrancher l’alimentation de l’appareil
S’assurer que les dispositifs ne peuvent pas être accidentellement redémarrés
Vérifier l’isolement de l’alimentation
Mettre l’appareil à la terre et le protéger contre les courts-circuits
Couvrir ou enfermer tout composant sous tension adjacent
Seul le personnel qualifié conformément à la norme EN 50110-1/-2 (VDE 0105 Partie 100) peut travailler sur cet appareil/ce système
Avant l’installation et avant de toucher l’appareil, s’assurer de ne porter aucune charge électrostatique
La terre fonctionnelle (FE, PSE) doit être raccordée à la terre de protection (PE) ou la compensation de potentiel. L’installateur du système a la responsabilité d’assurer cette connexion
Les câbles de connexion et les lignes de signal doivent être installés de façon à ce que les interférences capacitives ou inductives ne compromettent pas les fonctions d’automatisation
Installer les appareils d’automatisation et les éléments de fonctionnement associés de manière à ce qu’ils soient bien protégés contre tout fonctionnement accidentel
Des dispositifs de sécurité matériels et logiciels appropriés doivent être utilisés en rapport avec l’interface des E/S afin qu’un circuit ouvert sur le côté signal ne résulte pas en états indéfinis dans les dispositifs d’automatisation
Assurer une isolation électrique fiable sur le côté tension extra basse de l’alimentation 24 V. Utiliser uniquement des blocs d’alimentation conformes à la norme CEI 60364-4-41 (VDE 0100, partie 410) ou HD384.4.41 S2
Les écarts entre la tension d’entrée et la tension nominale ne doivent pas dépasser les limites de tolérance indiquées dans les spécifications, au risque de provoquer un mauvais fonctionnement et une utilisation dangereuse du système
Les dispositifs d’arrêt d’urgence conformes à la norme CEI/EN 60204-1 doivent être efficace dans tous les modes de fonctionnement des dispositifs d’automatisation. Le déverrouillage des dispositifs d’arrêt d’urgence ne doit pas entraîner un redémarrage
Les dispositifs conçus pour un montage dans des boîtiers ou armoires de commande ne doivent être utilisés et contrôlés qu’après avoir été installés et avec le boîtier fermé. Les unités de bureau ou portatives ne doivent être utilisées et contrôlées que dans leurs boîtiers fermés
Des mesures doivent être prises pour assurer un bon redémarrage des programmes interrompus après une chute ou une panne de tension. Ceci ne doit pas causer des états de fonctionnement dangereux, même pour un court laps de temps. Si nécessaire, des dispositifs d’arrêt d’urgence doivent être utilisés
Quand des défaillances du système d’automatisation peuvent entraîner des blessures ou des dommages matériels, des mesures externes doivent être appliquées pour assurer un état de fonctionnement sans danger en cas de panne ou de mauvais fonctionnement (par exemple au moyen de disjoncteurs séparés, de verrouillages mécaniques, etc.)
En fonction de leur degré de protection, les entraînements à fréquence variable peuvent contenir des pièces métalliques sous tension, des composants rotatifs ou en mouvement et des surfaces brûlantes, pendant le fonctionnement et immédiatement après l’arrêt
Le retrait des protections requises, une installation incorrecte ou un mauvais fonctionnement du moteur ou de l’entraînement à fréquence variable peuvent causer la défaillance de l’appareil et entraîner des blessures graves et des dommages importants
La réglementation nationale applicable en matière de sécurité et de prévention des accidents s’applique à tous les travaux effectués sur les entraînements à fréquence variable sous tension
L’installation électrique doit être effectuée conformément aux réglementations applicables (par exemple, en ce qui concerne les sections transversales des câbles, les fusibles, la mise à la terre de protection)
Le transport, l’installation, la mise en service et les travaux de maintenance doivent être effectués uniquement par un personnel qualifié (IEC 60364, HD384 et règles de sécurité du travail)
Les installations contenant des entraînements à fréquence variable doivent être équipées de dispositifs de surveillance et de protection, conformément aux réglementations applicables en matière de sécurité. Les modifications des entraînements à fréquence variable réalisées à l’aide du logiciel d’exploitation sont autorisées
Toutes les protections et les portes doivent être maintenues fermées pendant le fonctionnement
xvii
Pour réduire les risques d’accidents et de dommages matériels, l’utilisateur doit inclure dans la conception de la machine des mesures limitant les conséquences de panne ou de mauvais fonctionnement de l’entraînement (augmentation de la vitesse ou arrêt soudain du moteur). Ces mesures comprennent :
Autres dispositifs indépendants de surveillance des
variables en rapport avec la sécurité (vitesse, voyages, positions d’extrémité, etc.)
Mesures électriques ou non électriques appliquées à
l’ensemble du système (verrouillages électriques ou mécaniques)
Ne jamais toucher les pièces sous tension ni les
connexions des câbles de l’entraînement à fréquence variable après leur déconnexion de l’alimentation. En raison de la charge dans les condensateurs, ces pièces peuvent être encore sous tension après la déconnexion. Installer les panneaux d’avertissement appropriés
Lire ce manuel en entier et s’assurer de bien comprendre les procédures avant de tenter d’installer, de configurer, d’utiliser et d’effectuer tout travail d’entretien sur cet entraînement à fréquence variable DG1.
Haute tension dangereuse
AVERTISSEMENT
L’équipement de contrôle du moteur et les contrôleurs électroniques sont branchés sur des tensions secteur dangereuses. Lors de l’entretien des entraînements et des contrôleurs électroniques, il peut y avoir des composants exposés avec des boîtiers ou des protubérances au niveau du potentiel du réseau ou au-dessus. Toutes les précautions doivent être prises pour se protéger contre les chocs électriques.
Se tenir sur un tapis isolant et prendre l’habitude de n’utiliser qu’une seule main pour vérifier lescomposants
Toujours travailler avec une autre personne lorsqu’une situation d’urgence se produit
Débrancher l’alimentation avant de vérifier les contrôleurs ou d’effectuer des travaux d’entretien
S’assurer que l’équipement est correctement relié à la terre
Porter des lunettes de sécurité lors des travaux sur les contrôleurs électroniques ou les machines rotatives
Dénitions et symboles
AVERTISSEMENT
Ce symbole indique une haute tension. Il attire l’attention sur les éléments ou les opérations qui pourraient être dangereux pour les personnes utilisant cet équipement. Lire attentivement le message et suivre attentivement les instructions.
Ce symbole est le « symbole d’alerte de sécurité ». Il accompagne les deux termes d’avertissement suivants: MISE EN GARDE ou AVERTISSEMENT, comme décrit ci-dessous.
AVERTISSEMENT
Indique une situation potentiellement dangereuse qui, si elle n’est pas évitée, peut entraîner des blessures graves ou la mort.
MISE EN GARDE
Indique une situation potentiellement dangereuse qui, si elle n’est pas évitée, peut entraîner des blessures légères à modérées et d’importants dégâts matériels. La situation décrite dans la MISE EN GARDE peut, si elle n’est pas évitée, entraîner des conséquences graves. Des mesures de sécurité importantes sont décrites dans les MISES EN GARDE (ainsi que dans les AVERTISSEMENTS).
AVERTISSEMENT
Les composants de la section d’alimentation de l’entraînement restent sous tension après la coupure de la tension d’alimentation. Après la déconnexion de l’alimentation, attendre au moins cinq minutes avant de retirer le couvercle pour permettre la décharge des condensateurs du circuit intermédiaire.
Prêter attention aux avertissements signalant desdangers !
DANGER 5 MIN
AVERTISSEMENT
Risque de choc électrique – risque de blessures ! Effectuer le câblage uniquement si l’unité n’est plus sous tension.
AVERTISSEMENT
Ne pas effectuer de modifications sur l’entraînement CA lorsqu’il est connecté à l’alimentation secteur.
xviii
Avertissements et mises en garde
AVERTISSEMENT
S’assurer de mettre l’appareil à la terre en suivant les instructions de ce manuel. Les unités non mises à la terre peuvent causer des chocs électriques et desincendies.
AVERTISSEMENT
Cet équipement ne doit être installé, réglé et entretenu que par un personnel d’entretien électrique qualifié connaissant la construction et le fonctionnement de ce type d’équipement, ainsi que les risques encourus. Le non-respect de cette précaution peut entraîner la mort ou des blessures graves.
AVERTISSEMENT
Les composants à l’intérieur de l’entraînement sont sous tension lorsque l’entraînement est branché à l’alimentation. Le contact avec cette tension est extrêmement dangereux et peut causer la mort ou des blessures graves.
AVERTISSEMENT
Les bornes de phase (L1, L2, L3), les bornes du moteur (U, V, W) et les bornes de résistance de liaison CC/ frein (DC-, DC+/R+, R-) sont sous tension lorsque l’entraînement est branché à l’alimentation, même si le moteur ne tourne pas. Le contact avec cette tension est extrêmement dangereux et peut causer la mort ou des blessures graves.
AVERTISSEMENT
Même si les bornes E/S de commande sont isolées de la tension secteur, les sorties de relais et les autres bornes E/S peuvent présenter une tension dangereuse même lorsque l’entraînement est débranché. Le contact avec cette tension est extrêmement dangereux et peut causer la mort ou des blessures graves.
AVERTISSEMENT
Cet équipement a un grand courant de fuite capacitif pendant le fonctionnement, ce qui peut mettre les pièces du boîtier à un niveau supérieur au potentiel de terre. Une mise à la terre appropriée, telle que décrite dans ce manuel, est nécessaire. Le non-respect de cette précaution peut entraîner la mort ou des blessuresgraves.
AVERTISSEMENT
Un dispositif de protection/déconnexion en amont doit être fourni, tel que requis par le code électrique national (NEC entraîner la mort ou des blessures graves.
®
). Le non-respect de cette précaution peut
AVERTISSEMENT
Cet entraînement peut causer un courant CC dans le conducteur de mise à la terre de protection. Lorsqu’un dispositif de protection ou de surveillance à courant résiduel est utilisé pour la protection en cas de contact direct ou indirect, seul un dispositif de type B est autorisé sur le côté alimentation de ce produit.
AVERTISSEMENT
Ne travailler sur le câblage qu’après que l’entraînement a été correctement monté et attaché.
AVERTISSEMENT
Avant d’ouvrir les couvercles de l’entraînement :
Débrancher toute l’alimentation allant à l’entraînement, y compris l’alimentation de commande externe pouvant être présente
Attendre un minimum de cinq minutes après l’extinction de tous les voyants du clavier. Cela permet aux condensateurs de bus CC de se décharger
Une tension dangereuse peut rester dans les condensateurs de bus CC même si l’alimentation a été coupée. Confirmer que les condensateurs sont entièrement déchargés en mesurant la tension à l’aide d’un multimètre réglé pour mesurer la tension CC
Le non-respect de cette précaution peut entraîner la mort ou des blessures graves.
AVERTISSEMENT
L’ouverture du dispositif de protection du circuit de dérivation peut indiquer que le courant de défaut a été interrompu. Pour réduire le risque d’incendie ou de choc électrique, les pièces porteuses de courant et les autres composants du contrôleur doivent être examinés et remplacés s’ils sont endommagés. Si l’élément de courant d’un relais de surcharge a grillé, le relais de surcharge doit être intégralement remplacé.
AVERTISSEMENT
Avant de mettre l’entraînement sous tension, s’assurer que les protections avant et des câbles sont fermées et attachées pour empêcher l’exposition à d’éventuelles défaillances électriques. Le non-respect de cette précaution peut entraîner la mort ou des blessures graves.
xix
AVERTISSEMENT
Le fonctionnement de cet équipement nécessite le respect des instructions d’installation et de fonctionnement détaillées fournies dans le manuel d’installation/de fonctionnement destiné à être utilisé avec ce produit. Ces informations sont fournies sur le CD-ROM, la disquette ou tout autre périphérique de stockage inclus dans l’emballage contenant ce dispositif. Ce support doit être conservé avec cet appareil à tout moment. Une copie papier de ces informations peut être commandée auprès du service de documentation Eaton.
AVERTISSEMENT
Avant de procéder à l’entretien de l’entraînement :
Débrancher toute l’alimentation allant à l’entraînement, y compris l’alimentation de commande externe pouvant être présente
Placer une étiquette « NE PAS UTILISER » sur le dispositif de déconnexion
Verrouiller le dispositif de déconnexion en positionouverte
Le non-respect de ces instructions peut entraîner la mort ou des blessures graves.
AVERTISSEMENT
Les sorties de l’entraînement (U, V, W) ne doivent pas être connectées à la tension d’entrée ni à l’alimentation secteur, car ceci pourrait gravement endommager l’appareil et causer un incendie.
AVERTISSEMENT
Le dissipateur de chaleur et/ou le boîtier externe peuvent atteindre une température élevée.
Prêter attention aux avertissements signalant des dangers !
MISE EN GARDE
Installer cet entraînement sur une surface perpendiculaire capable de supporter le poids de l’entraînement et non soumise à des vibrations afin de diminuer les risques de chute et de dommage de l’entraînement, ainsi que les risques de blessures.
MISE EN GARDE
Empêcher la pénétration de corps étrangers, tels que morceaux de fils et copeaux métalliques, dans le boîtier de l’entraînement, car ceci pourrait provoquer la formation d’un arc électrique et un incendie.
MISE EN GARDE
Installer cet entraînement dans une pièce bien aérée non soumise à des températures extrêmes, à une forte humidité ou à la condensation. Éviter les endroits directement exposés au soleil ou présentant de fortes concentrations de poussières, des gaz corrosifs, des gaz explosifs, des gaz inflammables, ou des vapeurs de liquide de meulage, etc. Une installation inadéquate peut entraîner un risqued’incendie.
MISE EN GARDE
Lors de la sélection de la section transversale des câbles, prendre en compte la chute de tension dans des conditions de charge. La prise en compte d’autres paramètres relève de la responsabilité de l’utilisateur.
Il relève de la responsabilité de l’utilisateur de respecter toutes les normes électriques nationales et internationales en vigueur concernant la mise à la terre de protection de l’ensemble de l’équipement.
MISE EN GARDE
Les spécifications minimum relatives aux sections transversales des conducteurs de terre de protection indiquées dans ce manuel doivent être respectées.
Le courant de fuite de cet équipement dépasse 3,5 mA(CA). La taille minimum du conducteur de la mise à la terre de protection doit être conforme aux exigences de la norme EN 61800-5-1 et/ou aux réglementations de sécurité locales.
Surface brûlante – Risque de brûlure. NE PAS TOUCHER !
MISE EN GARDE
Toute modification électrique ou mécanique de cet entraînement sans consentement écrit préalable d’Eaton annule toutes les garanties, peut entraîner un danger pour la sécurité et annuler l’homologation UL
®
.
MISE EN GARDE
Installer cet entraînement sur une matière résistante aux flammes, telle qu’une plaque d’acier, pour réduire les risques d’incendie.
xx
MISE EN GARDE
Les courants de fuite de ce convertisseur de fréquence sont supérieures à 3,5 mA (CA). Conformément à la norme CEI/EN 61800-5-1, un conducteur de mise à la terre de l’équipement supplémentaire possédant la même superficie de coupe transversale que le conducteur de mise à la terre de protection d’origine doit être branché, ou la section transversale du conducteur de mise à la terre de l’équipement doit être d’au moins 10 mm conducteur en cuivre doit être utilisé avec cet entraînement.
2
Cu. Seul un
MISE EN GARDE
Les entrées anti-rebond ne sont pas permises dans le schéma du circuit de sécurité. Des disjoncteurs de courant résiduel (RCD) ne peuvent être installés qu’entre le réseau de courant alternatif et l’entraînement.
Ne pas tenter d’installer ou de retirer les vis des VOM et CEM lorsque l’alimentation est appliquée aux bornes d’entrée de l’entraînement
Sécurité du moteur et de l’équipement
MISE EN GARDE
Les entrées anti-rebond ne sont pas permises dans le schéma du circuit de sécurité. Si plusieurs moteurs sont connectés à un entraînement, des contacteurs doivent être conçus pour les moteurs individuels conformément à la catégorie d’utilisation AC-3.
Sélectionner du contacteur du moteur en fonction du courant de fonctionnement nominal du moteur à connecter.
MISE EN GARDE
Les entrées anti-rebond ne sont pas permises dans le schéma du circuit de sécurité. Une commutation entre l’entraînement et l’alimentation d’entrée doit avoir lieu dans un état sans tension.
MISE EN GARDE
Les entrées anti-rebond ne sont pas permises dans le schéma du circuit de sécurité. Risque d’incendie !
Utiliser uniquement des câbles, des interrupteurs de protection et des contacteurs indiquant le courant nominal permis.
MISE EN GARDE
Avant de connecter l’entraînement à l’alimentation secteur CA, s’assurer que les réglages de la classe de protection CEM sont correctement effectués selon les instructions de ce manuel.
Si l’entraînement doit être utilisé dans un réseau de distribution flottant, retirer les vis au niveau des VOM et CEM. Voir « Installation dans un réseau à une phase connectée à la terre (corner-grounded) » et « Installation dans un réseau IT»
Débrancher le filtre CEM interne lors de l’installation de l’entraînement sur un réseau IT (système d’alimentation non mis à la terre ou système d’alimentation électrique mis à la terre haute résistance [plus de 30 ohms]) pour ne pas que le système soit connecté au potentiel de terre via les condensateurs du filtre CEM. Ceci peut être une cause de dangers ou endommager l’entraînement
Débrancher le filtre CEM interne lors de l’installation de l’entraînement sur un système TN à une phase connectée à la terre pour ne pas endommager l’entraînement
ote:N Lorsque le filtre CEM interne est débranché,
l’entraînement peut ne pas être conforme aux normes de compatibilité électromagnétique.
MISE EN GARDE
n’effectuer aucun test de résistance de tension ou au mégohmmètre sur toute partie de l’entraînement ou de ses composants. Un test inadéquat peut entraîner desdommages.
MISE EN GARDE
Avant tout test ou mesure du moteur ou du câble du moteur, débrancher le câble du moteur au niveau des bornes de sortie de l’entraînement (U, V, W) pour éviter d’endommager ce dernier lors des tests.
MISE EN GARDE
Ne toucher aucun composant sur les cartes de circuit. Les décharges d’électricité statique peuvent endommager les composants.
MISE EN GARDE
Avant de mettre le moteur en marche, vérifier qu’il est correctement monté et aligné avec l’équipement entraîné. S’assurer que le démarrage du moteur ne risque pas de provoquer des blessures ou d’endommager l’équipement connecté au moteur.
MISE EN GARDE
Régler la vitesse maximale du moteur (fréquence) dans l’entraînement conformément aux exigences du moteur et de l’équipement qui lui est connecté. Des réglages de fréquence maximum incorrects peuvent endommager le moteur ou l’équipement et causer des blessures.
MISE EN GARDE
Avant d’inverser le sens de rotation du moteur, veiller à ce que cela ne risque pas de provoquer des blessures ou des dommages matériels.
MISE EN GARDE
S’assurer qu’aucun condensateur de correction de puissance n’est connecté à la sortie de l’entraînement ou aux bornes du moteur pour éviter un mauvais fonctionnement de l’entraînement et des dommages potentiels.
MISE EN GARDE
S’assurer que les bornes de sortie de l’entraînement (U, V, W) ne sont pas connectées à l’alimentation secteur, ce qui pourrait causer de graves dommages à l’entraînement.
xxi
MISE EN GARDE
Lorsque les bornes de commande de deux ou plusieurs unités d’entraînement sont raccordées en parallèle, la tension auxiliaire de ces connexions de commande doit être fournie par une source unique, qui peut être soit l’une des unités, soit une alimentation externe.
MISE EN GARDE
L’entraînement démarre automatiquement après une interruption de la tension d’entrée si la commande de démarrage externe est active.
MISE EN GARDE
Ne pas commander le moteur avec le dispositif de déconnexion ; à la place, utiliser les touches de marche et d’arrêt du tableau de contrôle ou les commandes du tableau des E/S de l’entraînement. Le nombre de cycles de charge maximum permis des condensateurs CC (c’est-à-dire les mises sous tension par application de puissance) est de cinq en dix minutes.
MISE EN GARDE
Fonctionnement incorrect de l’entraînement :
Si l’entraînement n’est pas mis en marche pendant une longue période, la performance de ses condensateurs électrolytiques sera réduite
S’il est arrêté pour une période prolongée, le mettre en marche au moins tous les six mois pendant au moins 5heures pour restaurer la performance des condensateurs, puis vérifier son fonctionnement. Il est recommandé de ne pas brancher l’entraînement directement sur la tension secteur. La tension doit être augmentée progressivement en utilisant une source CAréglable
Le non-respect de ces instructions peut entraîner des blessures ou des dégâts matériels.
Pour plus d’informations techniques, contacter l’usine ou le représentant commercial Eaton local.
xxii
Chapter 1—PowerXL series overview
This chapter describes the purpose and contents of this manual, the receiving inspection recommendations and the PowerXL Series Open Drive catalog numbering system.
How to use this manual
The purpose of this manual is to provide you with information necessary to install, set and customize parameters, start up, troubleshoot and maintain the Eaton PowerXL Series variable frequency drive (VFD). To provide for safe installation and operation of the equipment, read the safety guidelines at the beginning of this manual and follow the procedures outlined in the following chapters before connecting power to the PowerXL Series VFD. Keep this operating manual handy and distribute to all users, technicians and maintenance personnel for reference.
Receiving and inspection
The PowerXL Series VFD has met a stringent series of factory quality requirements before shipment. It is possible that packaging or equipment damage may have occurred during shipment. After receiving your PowerXL Series VFD, please check for the following:
Check to make sure that the package includes the Instruction Leaflet Quick Start Guide, and accessory packet. The accessory packet includes:
Rubber grommets
Control cable grounding clamps
Additional grounding screw
Inspect the unit to ensure it was not damaged duringshipment.
Make sure that the part number indicated on the nameplate corresponds with the catalog number on your order.
If shipping damage has occurred, please contact and file a claim with the carrier involved immediately.
If the delivery does not correspond to your order, please contact your Eaton Electrical representative.
ote:N Do not destroy the packing. The template printed on
the protective cardboard can be used for marking the mounting points of the PowerXL VFD on the wall or in a cabinet.
Chapter 1—PowerXL series overview
Real time clock battery activation
To activate the real time clock (RTC) functionality in the PowerXL Series VFD, the RTC battery (already mounted in the drive) must be connected to the controlboard.
Simply remove the primary drive cover, locate the RTC battery directly below the keypad, and connect the white 2-wire connector to the receptacle on the control board.
Figure 1. RTC battery connection
Table 1. Common abbreviations
Abbreviation Definition
CT Constant torque with high overload rating (150%)
VT Variable torque with low overload rating (110%)
IH High overload current (150%)
I
L
VFD Variable Frequency Drive
RTC Real Time Clock
Low overload current (110%)
POWERXL DG1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040004EN1—April 2018 www.eaton.com
23
Chapter 1—PowerXL series overview
Type, Date
NAED Code
Rating label
Figure 2. Rating label
Contains
EAN Code
Contains
Date Code: 20131118
Carton labels (U.S. and Europe)
Same as rating label shown above.
Contains SN, PN,
24
POWERXL DG1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040004EN1—April 2018 www.eaton.com
Catalog number system
Figure 3. Catalog numbering system
D G1 3 4 011 N N C 21 C
Chapter 1—PowerXL series overview
Series Power Part Options
Basic Naming
D = Drive
Basic Naming
G1 = General Purpose
Phase Reference
3 = 3~ INPUT /3~OUTPUT
H1 = HVAC
Input / Output Voltage
2 = 230V (208-240V, -15%, +10%) 4 = 400V (380-500V, - 15%, +10%) 5 = 600V (525-600V, -15%, +10%)
DG1 - Output Current Rating (CT)
208-240V 380-500V 525-600V
3D7 =3.7 A, 0.55 kW, 0.75 hp 2D2 =2.2 A, 0.75 kW, 1 hp 3D3 =3.3 A, 1.5 kW, 2 hp 4D8 =4.8 A, 0.75 kW, 1 hp 3D3 =3.3 A, 1.1 kW, 1.5 hp 4D5 =4.5 A, 2.2 kW, 3 hp 6D6 =6.6 A, 1.1 kW, 1.5 hp 4D3 =4.3 A, 1.5 kW, 2 hp 7D5 =7.5 A, 3.7 kW, 5 hp 7D8 =7.8 A, 1.5 kW, 2 hp 5D6 =5.6 A, 2.2 kW, 3 hp 010 =10 A, 5.5 kW, 7.5 hp 011 =11 A, 2.2 kW, 3 hp 7D6 =7.6 A, 3 kW, 5 hp 013 =13.5 A, 7.5 kW, 10 hp 012 =12.5 A, 3 kW, 5 hp (VT) 9D0 =9 A, 4 kW, 7.5 hp (VT) 018 =18 A, 11 kW, 15 hp 017 =17.5 A, 3.7 kW, 5 hp 012 =12 A, 5.5 kW, 7.5 hp 022 =22 A, 15 kW, 20 hp 025 =25 A, 5.5 kW, 7.5 hp 016 =16 A, 7.5 kW, 10 hp 027 =27 A, 18.5 kW, 25 hp 031 =31 A, 7.5 kW, 10 hp 023 =23 A, 11 kW, 15 hp 034 =34 A, 22 kW, 30 hp 048 =48 A, 11 kW, 15 hp 031 =31 A, 15 kW, 20 hp 041 =41 A, 30 kW, 40 hp 061 =61 A, 15 kW, 20 hp 038 =38 A, 18.5 kW, 25 hp 052 =52 A, 37 kW, 50 hp 075 =75 A, 18.5 kW, 25 hp 046 =46 A, 22 kW, 30 hp 062 =62 A, 45 kW, 60 hp 088 =88 A, 22 kW, 30 hp 061 =61 A, 30 kW, 40 hp 080 =80 A, 55 kW, 75 hp 114 =114 A, 30 kW, 40 hp 072 =72 A, 37 kW, 50 hp 100 =100 A, 75 kW, 100 hp 143 =143 A, 37 kW, 50 hp 087 =87 A, 45 kW, 60 hp 125 =125 A, 90 kW, 125 hp 170 =170 A, 45 kW, 60 hp 105 =105 A, 55 kW, 75 hp 144 =144 A, 110 kW, 150 hp 211 =211 A, 55 kW, 75 hp 140 =140 A, 75 kW, 100 hp 208 =208 A, 132 kW, 200 hp 248 =248 A, 75 kW, 100 hp 170 =170 A, 90 kW, 125 hp 200 = 208 A, 200 kW, 200 hp
205 =205 A, 110 kW, 150 hp 261 = 261 A, 250 kW, 250 hp 245 =245 A, 132 kW, 200 hp 325 = 325 A, 315 kW, 300 hp 310 = 310 A, 160 kW, 250 hp 385 = 385 A, 355 kW, 300 hp 385 = 385 A, 200 kW, 300 hp 416 = 416 A, 400 kW, 400 hp 460 = 460 A, 250 kW, 350 hp 460 = 460 A, 450 kW, 450 hp 520 = 520 A, 250 kW, 450 hp 520 = 520 A, 500 kW, 500 hp 590 = 590 A, 315 kW, 500 hp 590 = 590 A, 560 kW, 600 hp 650 = 650 A, 355 kW, 500 hp 650 = 650 A, 630 kW, 650 hp 730 = 730 A, 400 kW, 600 hp 820 = 820 A, 800 kW, 800 hp (VT) 820 = 820 A, 450 kW, 700 hp 920 = 920 A, 500 kW, 800 hp 1K0 = 1180 A, 630 kW, 1000 hp (VT)
Internal Brake Chopper
N = No brake chopper B = Brake chopper
Internal EMC Filter
D = DC choke only E = EMC lter only F = Internal EMC lter and DC choke N = No EMC lter, no DC choke
Coating of Boards
C = Coated
Enclosure (IP Rating)
00 = IP00/Open Type 20 = IP20/Open Type 21 = IP21/Type 1 54 = IP54/Type 12
Display Option
C = LCD (graphical) N = No display
POWERXL DG1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040004EN1—April 2018 www.eaton.com
25
Chapter 1—PowerXL series overview
Power ratings and product selection
PowerXL Series drives—208-230 Volt
Table 2. Type/IP20
Constant to rque (C T)/ high ove rload (IH) Variable torque (VT)/low overload (IL)
Frame size
230 V, 50 Hz kW rating
230 V, 60 Hz hpCurrent
A
230 V, 50 Hz kW rating
230 V, 60 HzhpCurrent
A
DG1 Catalog number
FR0 0.55 0.75 3.7 0.75 1 4.8 DG1-323D7EB-C20C
0.75 1 4.8 1.1 1.5 6.6 DG1-324D8EB-C20C
1.1 1.5 6.6 1.5 2 7. 8 DG1-326D6EB-C20C
Table 3. Type 1/IP21
Constant to rque (C T)/ high ove rload (IH) Variable torque (VT)/low overload (IL)
Frame size
230 V, 50 Hz kW rating
FR1 0.55 0.75 3.7 0.75 1 4.8 DG1-323D7FB-C21C
0.75 1 4.8 1.1 1.5 6.6 DG1-324D8FB-C21C
1.1 1.5 6.6 1.5 2 7. 8 DG1-326D6FB-C21C
1.5 2 7.8 2.2 3 11 DG1-327D8FB-C21C
2.2 3 11 3 12.5 DG1-32011FB-C21C
FR2 3 12.5 3.7 5 17.5 DG1-32012FB-C21C
3.7 5 17.5 5.5 7.5 25 DG1-32017FB-C21C
5.5 7.5 25 7. 5 10 31 DG1-32025FB-C21C
FR3 7.5 10 31 11 15 48 DG1-32031FB-C21C
11 15 48 15 20 61 DG1-32048FB-C21C
FR4 15 20 61 18.5 25 75 DG1-32061FN-C21C
18.5 25 75 22 30 88 DG1-32075FN-C21C 22 30 88 30 40 114 DG1-32088FN-C21C
FR5 30 40 114 37 50 143 DG1-32114FN-C21C
37 50 143 45 60 170 DG1-32143FN-C21C 45 60 170 55 75 211 DG1-32170FN-C21C
FR6 55 75 211 75 100 261 DG1-32211FN-C21C
75 10 0 24 8 90 125 312 DG1-32248FN-C21C
230 V, 60 Hz hpCurrent
A
230 V, 50 Hz kW rating
230 V, 60 HzhpCurrent
A Catalog number
Table 4. Type 12/IP54
Constant to rque (C T)/ high ove rload (IH) Variable torque (VT)/low overload (IL)
Frame size
230 V, 50 Hz kW rating
230 V, 60 Hz hpCurrent
A
230 V, 50 Hz kW rating
230 V, 60 HzhpCurrent
A Catalog number
FR1 0.55 0.75 3.7 0.75 1 4.8 DG1-323D7FB-C54C
0.75 1 4.8 1.1 1.5 6.6 DG1-324D8FB-C54C
1.1 1.5 6.6 1.5 2 7. 8 DG1-326D6FB-C54C
1.5 2 7.8 2.2 3 11 DG1-327D8FB-C54C
2.2 3 11 3 12.5 DG1-32011FB-C54C
FR2 3 12.5 3.7 5 17.5 DG1-32012FB-C54C
3.7 5 17.5 5.5 7.5 25 DG1-32017FB-C54C
5.5 7.5 25 7. 5 10 31 DG1-32025FB-C54C
FR3 7.5 10 31 11 15 48 DG1-32031FB-C54C
11 15 48 15 20 61 DG1-32048FB-C54C
FR4 15 20 61 18.5 25 75 DG1-32061FN-C54C
18.5 25 75 22 30 88 DG1-32075FN-C54C 22 30 88 30 40 114 DG1-32088FN-C54C
FR5 30 40 114 37 50 143 DG1-32114FN-C54C
37 50 143 45 60 170 DG1-32143FN-C54C 45 60 170 55 75 211 DG1-32170FN-C54C
FR6 55 75 211 75 100 261 DG1-32211FN-C54C
75 10 0 24 8 90 125 312 DG1-32248FN-C54C
ote:N
26
POWERXL DG1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040004EN1—April 2018 www.eaton.com
PowerXL Series drives—380-500 Volt
Table 5. Type/IP20
Constant to rque (C T)/ high ove rload (IH) Variable torque (VT)/low overload (IL)
Chapter 1—PowerXL series overview
Frame size
400 V, 50 Hz kW rating
460 V, 60 Hz hpCurrent
A
400 V, 50 Hz kW rating
460 V, 60 HzhpCurrent
A
DG1 Catalog number
FR0 0.75 1 2.2 1.1 1.5 3.3 DG1-342D2EB-C20C
1.1 1.5 3.3 1.5 2 4.6 DG1-343D3EB-C20C
1.5 2 4.3 2.2 3 5.6 DG1-344D3EB-C20C
2.2 3 5.6 3 5 7. 6 DG1-345D6EB-C20C
Table 6. Type 1/IP21
Constant to rque (C T)/ high ove rload (IH) Variable torque (VT)/low overload (IL)
Frame size
400 V, 50 Hz kW rating
FR1 0.75 1 2.2 1.1 1.5 3.3 DG1-342D2FB-C21C
1.1 1.5 3.3 1.5 2 4.3 DG1-343D3FB-C21C
1.5 2 4.3 2.2 3 5.6 DG1-344D3FB-C21C
2.2 3 5.6 3 5 7. 6 DG1-345D6FB-C21C 3 5 7. 6 4 9 DG1-347D6FB-C21C 4 9 5.5 7. 5 12 DG1-349D0FB-C21C
FR2 5.5 7.5 12 7.5 10 16 DG1-34012FB-C21C
7.5 10 16 11 15 23 DG1-34016FB-C21C 11 15 23 15 20 31 DG1-34023FB-C21C
FR3 15 20 31 18.5 25 38 DG1-34031FB-C21C
18.5 25 38 22 30 46 DG1-34038FB-C21C 22 30 46 30 40 61 DG1-34046FB-C21C
FR4 30 40 61 37 50 72 DG1-34061FN-C21C
37 50 72 45 60 87 DG1-34072FN-C21C 45 60 87 55 75 105 DG1-34087FN-C21C
FR5 55 75 105 75 100 140 DG1-34105FN-C21C
75 10 0 14 0 90 125 170 DG1-34140FN-C21C 90 125 170 110 150 205 DG1-34170FN-C21C
FR6 110 150 205 132 200 261 DG1-34205FN-C21C
150 200 245 160 250 310 DG1-34245FN-C21C
460 V, 60 Hz hpCurrent
A
400 V, 50 Hz kW rating
460 V, 60 HzhpCurrent
A Catalog number
POWERXL DG1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040004EN1—April 2018 www.eaton.com
27
Chapter 1—PowerXL series overview
Table 7. Type 12/IP54
Constant to rque (C T)/ high ove rload (IH) Variable torque (VT)/low overload (IL)
Frame size
400 V, 50 Hz kW rating
FR1 0.75 1 2.2 1.1 1.5 3.3 DG1-342D2FB-C54C
1.1 1.5 3.3 1.5 2 4.3 DG1-343D3FB-C54C
1.5 2 4.3 2.2 3 5.6 DG1-344D3FB-C54C
2.2 3 5.6 3 5 7. 6 DG1-345D6FB-C54C 3 5 7. 6 4 9 DG1-347D6FB-C54C 4 9 5.5 7. 5 12 DG1-349D0FB-C54C
FR2 5.5 7.5 12 7.5 10 16 DG1-34012FB-C54C
7.5 10 16 11 15 23 DG1-34016FB-C54C 11 15 23 15 20 31 DG1-34023FB-C54C
FR3 15 20 31 18.5 25 38 DG1-34031FB-C54C
18.5 25 38 22 30 46 DG1-34038FB-C54C 22 30 46 30 40 61 DG1-34046FB-C54C
FR4 30 40 61 37 50 72 DG1-34061FN-C54C
37 50 72 45 60 87 DG1-34072FN-C54C 45 60 87 55 75 105 DG1-34087FN-C54C
FR5 55 75 105 75 100 140 DG1-34105FN-C54C
75 10 0 14 0 90 125 170 DG1-34140FN-C54C 90 125 170 110 150 205 DG1-34170FN-C54C
FR6 110 150 205 132 200 261 DG1-34205FN-C54C
150 200 245 160 250 310 DG1-34245FN-C54C
PowerXL Series drives—380, 500 Volt
460 V, 60 Hz hpCurrent
A
400 V, 50 Hz kW rating
460 V, 60 HzhpCurrent
A Catalog number
Table 8. Type 0/IP00
Constant to rque (C T)/ high ove rload (IH) Variable torque (VT)/low overload (IL)
Frame size
400 V, 50 Hz kW rating
480 V, 60 Hz hpCurrent
A
400 V, 50 Hz kW rating
480 V, 60 HzhpCurrent
A Catalog number
FR7 160 250 311 200 300 385 DG1-34310FN-C00C
200 300 385 250 350 460 DG1-34385FN-C00C 250 350 460 250 450 520 DG1-34460FN-C00C 250 450 520 315 500 590 DG1-34520FN-C00C
FR8 315 500 590 355 500 650 DG1-34590FN-C00C
355 500 650 400 600 730 DG1-34650FN-C00C 400 600 730 450 700 820 DG1-34730FN-C00C 450 700 820 500 800 920 DG1-34820FN-C00C 500 800 920 560 900 104 0 DG1-34920FN-C00C 500 800 920 630 1000 1180 DG1-341K0FN-C00C
ote:N
28
POWERXL DG1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040004EN1—April 2018 www.eaton.com
Chapter 1—PowerXL series overview
PowerXL Series Drives—600 volt
Table 9. Type 1/IP21
Constant to rque (C T)/ high ove rload (IH) Variable torque (VT)/low overload (IL)
Frame size
600 V, 60 Hz kW rating
FR1 1.5 2 3.3 2.2 3 4.5 DG1-353D3FB-C21C
2.2 3 4.5 3.7 5 7.5 DG1-354D5FB-C21C
3.7 5 7.5 5.5 7. 5 10 DG1-357D5FB-C21C
FR2 5.5 7.5 10 7.5 10 13.5 DG1-35010FB-C21C
7.5 10 13.5 11 15 18 DG1-35013FB-C21C 11 15 18 15 20 22 DG1-35018FB-C21C
FR3 15 20 22 18.5 25 27 DG1-35022FB-C21C
18.5 25 27 22 30 34 DG1-35027FB-C21C 22 30 34 30 40 41 DG1-35034FB-C21C
FR4 30 40 41 37 50 52 DG1-35041FN-C21C
37 50 52 45 60 62 DG1-35052FN-C21C 45 60 62 55 75 80 DG1-35062FN-C21C
FR5 55 75 80 75 100 100 DG1-35080FN-C21C
75 10 0 10 0 90 125 125 DG1-35100FN-C21C 90 125 125 110 150 144 DG1-35125FN-C21C
FR6 110 150 144 150 200 208 DG1-35144FN-C21C
150 200 208 187 250 250 DG1-35208FN-C21C
600 V, 60 Hz hpCurrent
A
600 V, 60 Hz kW rating
600 V, 60 HzhpCurrent
A Catalog number
Table 10. Type 12/IP54
Constant to rque (C T)/ high ove rload (IH) Variable torque (VT)/low overload (IL)
Frame size
600 V, 60 Hz kW rating
FR1 1.5 2 3.3 2.2 3 4.5 DG1-353D3FB-C54C
2.2 3 4.5 3.7 5 7.5 DG1-354D5FB-C54C
3.7 5 7.5 5.5 7. 5 10 DG1-357D5FB-C54C
FR2 5.5 7.5 10 7.5 10 13.5 DG1-35010FB-C54C
7.5 10 13.5 11 15 18 DG1-35013FB-C54C 11 15 18 15 20 22 DG1-35018FB-C54C
FR3 15 20 22 18.5 25 27 DG1-35022FB-C54C
18.5 25 27 22 30 34 DG1-35027FB-C54C 22 30 34 30 40 41 DG1-35034FB-C54C
FR4 30 40 41 37 50 52 DG1-35041FN-C54C
37 50 52 45 60 62 DG1-35052FN-C54C 45 60 62 55 75 80 DG1-35062FN-C54C
FR5 55 75 80 75 100 100 DG1-35080FN-C54C
75 10 0 10 0 90 125 125 DG1-35100FN-C54C 90 125 125 110 150 144 DG1-35125FN-C54C
FR6 110 150 144 150 200 208 DG1-35144FN-C54C
150 200 208 187 250 250 DG1-35208FN-C54C
600 V, 60 Hz hpCurrent
A
600 V, 60 Hz kW rating
600 V, 60 HzhpCurrent
A Catalog number
POWERXL DG1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040004EN1—April 2018 www.eaton.com
29
Chapter 1—PowerXL series overview
PowerXL Series drives—525—600 Volt
Table 11. Type 0/IP00
Constant to rque (C T)/ high ove rload (IH) Variable torque (VT)/low overload (IL)
Frame size
600 V, 50 Hz kW rating
FR7 187 250 261 224 300 325 DG1-35261FN-C00C
224 300 325 298 400 385 DG1-35325FN-C00C 224 300 385 336 450 416 DG1-35385FN-C00C
FR8 298 400 416 336 450 460 DG1-35416FN-C00C
336 450 460 373 500 520 DG1-35460FN-C00C 373 500 520 448 600 590 DG1-35520FN-C00C 448 600 590 485 650 650 DG1-35590FN-C00C 485 650 650 522 700 750 DG1-35650FN-C00C 485 650 650 597 800 820 DG1-35820FN-C00C
ote:N
600 V, 60 Hz hpCurrent
A
600 V, 50 Hz kW rating
600 V, 60 HzhpCurrent
A Catalog number
30
POWERXL DG1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040004EN1—April 2018 www.eaton.com
Loading...
+ 282 hidden pages