Production: René Wiegand
Translation: globaldocs GmbH
All rights reserved, including those of the translation.
No part of this manual may be reproduced in any form (printed, photocopy, microfilm
or any other process) or processed, duplicated or distributed by means of electronic
systems without written permission of Eaton Industries GmbH, Bonn.
Subject to alteration without notice.
Page 3
Danger!
Dangerous electrical voltage!
Before commencing the installation
• Disconnect the power supply of the device.
• Ensure that devices cannot be accidentally restarted.
• Verify isolation from the supply.
• Earth and short circuit the device.
• Cover or enclose any adjacent live components.
• Follow the engineering instructions (AWA/IL) for the
device concerned.
• Only suitably qualified personnel in accordance with
EN 50110-1/-2 (VDE 0105 Part 100) may work on this
device/system.
• Before installation and before touching the device ensure
that you are free of electrostatic charge.
• The functional earth (FE, PES) must be connected to the
protective earth (PE) or the potential equalisation. The
system installer is responsible for implementing this
connection.
• Connecting cables and signal lines should be installed so
that inductive or capacitive interference does not impair
the automation functions.
• Install automation devices and related operating elements
in such a way that they are well protected against
unintentional operation.
• Suitable safety hardware and software measures should
be implemented for the I/O interface so that an open
circuit on the signal side does not result in undefined
states in the automation devices.
• Ensure a reliable electrical isolation of the extra-low
voltage of the 24 V supply. Only use power supply units
complying with IEC 60364-4-41 (VDE 0100 Part 410) or
HD384.4.41 S2.
• Deviations of the mains voltage from the rated value must
not exceed the tolerance limits given in the specifications,
otherwise this may cause malfunction and dangerous
operation.
• Emergency stop devices complying with IEC/EN 60204-1
must be effective in all operating modes of the automation
devices. Unlatching the emergency-stop devices must not
cause a restart.
• Devices that are designed for mounting in housings or
control cabinets must only be operated and controlled
after they have been installed and with the housing
closed. Desktop or portable units must only be operated
and controlled in enclosed housings.
Eaton Industries GmbH
Safety instructions
• Measures should be taken to ensure the proper restart of
programs interrupted after a voltage dip or failure. This
should not cause dangerous operating states even for a
short time. If necessary, emergency-stop devices should
be implemented.
• Wherever faults in the automation system may cause
injury or material damage, external measures must be
implemented to ensure a safe operating state in the event
of a fault or malfunction (for example, by means of
separate limit switches, mechanical interlocks etc.).
• Depending on their degree of protection, frequency
inverters may contain live bright metal parts, moving or
rotating components or hot surfaces during and
immediately after operation.
• Removal of the required covers, improper installation or
incorrect operation of motor or frequency inverter may
cause the failure of the device and may lead to serious
injury or damage.
• The applicable national accident prevention and safety
regulations apply to all work carried on live frequency
inverters.
• The electrical installation must be carried out in
accordance with the relevant regulations (e. g. with
regard to cable cross sections, fuses, PE).
• Transport, installation, commissioning and maintenance
work must be carried out only by qualified personnel
(IEC 60364, HD 384 and national occupational safety
regulations).
• Installations containing frequency inverters must be
provided with additional monitoring and protective
devices in accordance with the applicable safety
regulations. Modifications to the frequency inverters
using the operating software are permitted.
• All covers and doors must be kept closed during
operation.
• To reduce the hazards for people or equipment, the user
must include in the machine design measures that restrict
the consequences of a malfunction or failure of the drive
(increased motor speed or sudden standstill of motor).
These measures include:
– Other independent devices for monitoring safety-
related variables (speed, travel, end positions etc.).
– Electrical or non-electrical system-wide measures
(electrical or mechanical interlocks).
– Never touch live parts or cable connections of the
frequency inverter after it has been disconnected from
the power supply. Due to the charge in the capacitors,
these parts may still be live after disconnection. Fit
appropriate warning signs.
I
Page 4
II
Page 5
Table of contents
0About this Manual .....................................................................5
Alphabetical index ..................................................................... 221
4DA1 Variable Frequency Drives 10/12 MN04020005Z-EN www.eaton.com
Page 9
0 About this Manual
0.1 Target group
0 About this Manual
0.1 Target group
This manual contains special information required for the correct selection
and connection of a DA1 variable frequency drive and its configuration to
your specific requirements using the parameters. All information applies to
the specified hardware and software versions. The manual describes all sizes
of the DA1 device series. The differences and special characteristics of each
rating level and size are listed accordingly.
The content of MN04020005Z-EN manual is written for engineers and electricians. A specialist knowledge of electrical engineering and fundamental
technical principles is needed for commissioning.
We assume that you have a good knowledge of engineering fundamentals
and that you are familiar with handling electrical systems and machines, as
well as with reading technical drawings.
0.2 Writing conventions
Symbols used in this manual have the following meanings:
Indicates instructions to be followed.
Indicates useful tips.
→
NOTICE
Warns about the possibility of material damage.
CAUTION
Warns of the possibility of hazardous situations that may possibly cause slight injury.
DANGER
Warns of hazardous situations that result in serious injury or
death.
For greater clarity, the name of the current chapter and the name of the current section are shown in the page header.
DA1 Variable Frequency Drives 10/12 MN04020005Z-EN www.eaton.com5
Page 10
0 About this Manual
0.3 Abbreviations
0.3 Abbreviations
→
→
→
The following abbreviations are used in this manual.
EMCElectromagnetic compatibility
FEFunctional earth
FSFrame Size
FWDForward run (clockwise rotating field)
GNDGround (0-V-potential)
IGBTInsulated gate bipolar transistor
LCDLiquid Crystal Display
PDSPower Drive System (magnet system)
PE
PESEMC connection to PE for screened lines
PNUParameter number
REV
UL
DS
In order to make it easier to understand some of the images
included in this manual, the housing of the variable frequency
drive, as well as other safety-relevant parts, have been left out.
However, it is important to note that the variable frequency
drive must always be operated with its housing placed properly,
as well as with all required safety-relevant parts.
All the specifications in this manual refer to the hardware and
software versions documented in it.
More information on the devices described here can be found
on the Internet under:
http://www.eaton.com/moeller
Protective earth
Reverse run (anticlockwise rotation field active)
Underwriters Laboratories
Default settings
Support
6DA1 Variable Frequency Drives 10/12 MN04020005Z-EN www.eaton.com
Page 11
0.4 Mains supply voltages
0 About this Manual
0.4 Mains supply voltages
The rated operating voltages stated in the following table are based on the
standard values for networks with a grounded star point.
In ring networks (as found in Europe) the rated operating voltage at the transfer point of the power supply companies is the same as the value in the consumer networks (e.g. 230 V, 400 V).
In star networks (as found in North America), the rated operating voltage at
the transfer point of the utility companies is higher than in the consumer network. Example: 120 V 115 V, 240 V 230 V, 480 V 460 V.
The DA1 variable frequency drive’s wide tolerance range takes into account a
permissible voltage drop of 10 % (i.e. U
gory, it takes into account the
North American mains voltage of 480 V + 10 %
(60 Hz).
The permissible power supplies for the DA1 series are listed in the Technical
Data section in the appendix.
The rated mains voltage operational data is always based on mains frequencies of 50/60 Hz within a range of 48 to 62 Hz.
- 10 %) while, in the 400-V cate-
LN
0.5 Units
Every physical dimension included in this manual uses international metric
system units, otherwise known as SI (Système International d’Unités) units.
For the purpose of the equipment's UL certification, some of these dimensions are accompanied by their equivalents in imperial units.
Table 1:Unit conversion examples
designation
Length1 in (’’)inch25.4 mm0.0394
Power
Torque
Temperature1°F (TF)Fahrenheit-17.222 °C (TC)TF=TC×9/5+32
Speed
Weight1lbpound0.4536 kg2.205
US-American
value
1HP=1.014PShorsepower0.7457 kW1.341
1lbfinpound-force inches0.113 Nm8.851
1rpmRevolutions per minute1min
US-American
designation
SI valueConversion value
-1
1
DA1 Variable Frequency Drives 10/12 MN04020005Z-EN www.eaton.com7
Page 12
0 About this Manual
0.5 Units
8DA1 Variable Frequency Drives 10/12 MN04020005Z-EN www.eaton.com
Page 13
1 DA1 device series
1.1 Introduction
1 DA1 device series
1.1 Introduction
DA1 series variable frequency drives are suited to applications involving the
frequency control of motors within an output range of 0.75 kW (at 230 V) to
160 kW (at 400 V).
DA1 series devices feature a compact and rugged design and are available in
seven sizes (FS2, ... , FS8), as well as with protection types IP20, IP40, IP55
and IP66. For protection type IP66, there is also a model with a mains switch
and controls for local control available.
Due to their ease of use and handling, the innovative technology behind
them, and a high level of reliability, DA1 variable frequency drives are particularly suitable for use in general applications. In addition, an integrated radio
interference suppression filter and a flexible interface ensure that the inverters meet a number of important needs in the machine building industry
when it comes to the optimization of production and manufacturing processes.
The computer-supported parameter configuration software ensures data
integrity and reduces the time required for commissioning and maintenance.
In addition, the comprehensive accessories available increase the inverters’
flexibility in all areas of application.
DA1 Variable Frequency Drives 10/12 MN04020005Z-EN www.eaton.com9
Page 14
1 DA1 device series
1.2 System overview
1.2 System overview
⑥
①
⏚
DC-
L1/L
L2/N
L3
②
⑤
1 2 3 4 5 6 7 8 9 10 11 12 13
COM
14 15 16 17 18
⏚
DC+
BR
U
V
W
OP
PROFIBUS DP-V1
ST
④
③
Figure 1:DA1 variable frequency drives system overview
a DA1-… variable frequency drives
b DX-LN-… main chokes, DX-LM3-… motor reactors, DX-SIN3-… sinusoidal filters
c DX-BR… braking resistance
d Fieldbus connection and expansion group
e DX-COM-STICK communication module and accessories (e. g. DX-CBL-… connection cable)
f DE-KEY-… keypad (external)
10DA1 Variable Frequency Drives 10/12 MN04020005Z-EN www.eaton.com
Page 15
1.3 Checking the Delivery
1 DA1 device series
1.3 Checking the Delivery
→
make sure that you received the correct variable frequency
drive.
⏚
DC-
L1/L
L2/N
L3
1 2 3 4 5 6 7 8 9 10 11 12 13
COM
14 15 16 17 18
⏚
DC+
BR
U
V
W
Figure 2:Location of nameplate on DA1 variable frequency drive
Before opening the package, please check the label on it to
The DA1 series variable frequency drives are carefully packaged and prepared for delivery. The devices should be shipped only in their original packaging with suitable transportation materials. Please take note of the labels
and instructions on the packaging, as well as of those meant for the
unpacked device.
Open the packaging with suitable tools and inspect the contents immediately
after delivery to ensure that they are complete and undamaged.
DA1 Variable Frequency Drives 10/12 MN04020005Z-EN www.eaton.com11
Page 16
1 DA1 device series
IL
1.3 Checking the Delivery
The packaging must contain the following parts:
•DA1 series variable frequency drive,
•an instructional leaflet
•IL04020010Z for devices with FS2 and FS3 size with IP20 protection
type,
•IL04020011Z for devices with FS4 to FS7 sizes with IP55 protection
type,
•IL04020012Z for panel-version variable frequency drives of size FS8
•A data carrier (CD-ROM) containing documentation for DA1 series vari-
able frequency drives.
⏚
DC-
L1/L
L2/N
L3
1 2 3 4 5 6 7 8 9 10 11 12 13
COM
14 15 16 17 18
⏚
DC+
BR
U
V
W
Figure 3:Equipment supplied with DA1 variable frequency drive
CD
12DA1 Variable Frequency Drives 10/12 MN04020005Z-EN www.eaton.com
Page 17
1.4 Rated data
a
Voltage categories
DA1 variable frequency drives are divided into following voltage categories:
•230 V: DA1-12…, DA1-32…
•400 V: DA1-34…
1.4.1 Rating data on the nameplate
The device-specific rated operational data for the DA1 variable frequency
drive is listed on the nameplate on the right side of the device.
The inscription of the nameplate has the following meaning (example):
Inscription Meaning
DA1-344D1FB-A20NPart no.:
Input
Output
Power
S/NSerial number
1 DA1 device series
1.4 Rated data
DA1 = DA1 series variable frequency drive
3 = Three-phase mains connection / three-phase motor connection
4 = 400 V mains voltage category
4D1 = 4.1 A rated operational current (4-decimal-1, output current)
F = Integrated radio interference suppression filter
B = Integrated brake chopper
A = LED display (7-segment text display)
20 = IP20 protection type
N = Standard basic device
Power connection rating:
Three-phase AC voltage (U
380 - 480 V voltage, 50/60 Hz frequency, input phase current (4.3 A).
Load side (motor) rating:
Three-phase AC voltage (0 - U
(0 - 500 Hz)
Assigned motor output:
1.5 kW at 400 V/2 HP at 460 V for a four-pole, internally cooled or surface-cooled
three-phase motor (1500 rpm at 50 Hz/1800 rpm at 60 Hz)
Variable frequency drive is an electrical apparatus.
Read the manual (in this case MN04020005Z-EN) before making any electrical
connections and commissioning.
3~ AC),
e
), output phase current (4.1 A), output frequency
e
IP20/Open type
25072012Manufacturing date: 07-25-2012
DA1 Variable Frequency Drives 10/12 MN04020005Z-EN www.eaton.com13
Protection type of the housing: IP20, UL (cUL) Open type
Page 18
1 DA1 device series
1.4 Rated data
1.4.2 Key to part numbers
The catalog no. or part no. for the DA1 series of variable frequency drives is
made up of four sections.
Series – Power section – Model – Version
The following figure shows it in greater detail:
D A1-124D 1FN -A20NExplanation
Type
N = Standard basic device
C = With coated printed circuit boards
Protection type
20 = IP20 / NEMA 0
40 = IP40 / NEMA 1
55 = IP55 / NEMA 3
66 = IP66 / NEMA 4X
6S = IP66 with switch / NEMA 4X, switched
Display unit (display)
A = LED display
B = OLED display
Brake Chopper
N = No internal brake chopper
B = Brake chopper
EMC (radio interference suppression filter)
N = No internal RFI filter
F = Internal RFI filter
Rated operational current (examples)
2D2 = 2.2 A
4D1 = 4.1 A
024 = 24 A
Mains voltage category
2 = 230 V (200 - 240 V ±10 %)
4 = 400 V (380 - 480 V ±10 %)
Connection in power section
1 = Single-phase mains connection / three-phase motor connection
3 = Three-phase mains connection / three-phase motor connection
Device series
DA1 = Variable frequency drive, advanced, Series 1
(D = Drives, A = Advanced, 1 = Series)
Figure 4:Key to part numbers of the DA1 variable frequency drives
14DA1 Variable Frequency Drives 10/12 MN04020005Z-EN www.eaton.com
Page 19
Catalog number examples
Inscription Meaning
1 DA1 device series
1.4 Rated data
DA1-124D3NN-A20CDA1 = DA1 series variable frequency drive
DA1-122D3FN-A20N
DA1-327D0FB-A20N
DA1-34014FB-B66N
DA1-34018FB-A20C
1 = Single-phase power supply
2 = Mains voltage category: 230 V (200 V - 240 V ±10 %)
4D3 = Rated operational current: 4.3 A
N = No internal radio interference suppression filter
N = No internal brake chopper
A = LED display
20 = IP20 protection type
C = Coated printed circuit boards
DA1 = DA1 series variable frequency drive
1 = Single-phase power supply
2 = Mains voltage category: 230 V (200 V - 240 V ±10 %)
2D3 = Rated operational current: 2.3 A
N = Internal radio interference suppression filter
N = No internal brake chopper
A = LED display
20 = IP20 protection type
N = Not coated printed circuit boards
DA1 = DA1 series variable frequency drive
3 = Three-phase mains supply voltage
2 = Mains voltage category: 230 V (200 V - 240 V ±10 %)
7D0 = Rated operational current: 7.0 A
N = Internal radio interference suppression filter
B = internal brake chopper
A = LED display
20 = IP20 protection type
N = Not coated printed circuit boards
DA1 = DA1 series variable frequency drive
3 = Three-phase mains supply voltage
4 = Mains voltage category: 400 V (380 V - 480 V ±10 %)
014 = Rated operational current: 14 A
N = Internal radio interference suppression filter
B = internal brake chopper
B = OLED display
66 = IP66 protection type
N = Not coated printed circuit boards
DA1= DA1 series variable frequency drive
3 = Three-phase mains supply voltage
4 = Mains voltage category: 400 V (380 V - 480 V ±10 %)
018 = Rated operational current: 18 A
N = Internal radio interference suppression filter
B = internal brake chopper
A = LED display
20 = IP20 protection type
C = Coated printed circuit boards
→
DA1 Variable Frequency Drives 10/12 MN04020005Z-EN www.eaton.com15
suppression
filter is required for operation as per IEC/EN 61800-3.
For DA1-xxxxxNx-xxxx devices, an external radio interference
Page 20
1 DA1 device series
1.4 Rated data
1.4.3 General rated operational data
Technical DataFormula
General
StandardsEMC: EN 61800-3:2004+A1-2012
Certifications and manufacturer’s declarations on conformityCE, UL, cUL, c-Tick
Production qualityRoHS, ISO 9001
Climatic proofingρ
Ambient air temperature
Operation
IP20 (NEMA 0)ϑ°C-10 - +50 (frost-free and condensation-free)
IP55 (NEMA 3)ϑ°C-10 - +45
IP66 (NEMA 4X)ϑ°C-10 - +40 (frost-free and condensation-free)
Storageϑ°C-10 - +60
Electrostatic discharge (ESD, EN 61000-4-2:2009V kV±4, contact discharge
Fast transient burst (EFT/B, EN 61000-4-4: 2004)V kV±1, at 5 kHz, control signal terminals
Overvoltage (surge, EN 61000-4-5: 2006)
200 - 240 VV kV±1, Phase to phase/neutral conductor
380 - 480 VV kV±2, Phase to phase
Dielectric strength (flash, EN 61800-5-1: 2007)
200 - 240 VV kV1.5
380 - 480 VV kV2.5
Radio interference class (EMC)
Category and maximum screened motor cable length
C1lm5
C2lm25
C3lm50
Mounting positionVertical, max. ±30°
AltitudeHm0 - 1000 above sea level,
Degree of protectionIP20 (NEMA 0)
Busbar tag shroudBGV A3 (VBG4, finger- and back-of-hand proof)
sign
w
UnitValue
Radio interference: EN 55011: 2010
Safety: EN 61800-5: 2007
Protection type: EN 60529: 1992
Note: FS8 units are not UL or cUL certified as of this writing
%< 95 %, average relative humidity (RH),
non-condensing (EN 50178)
±8, air discharge
±2, at 5 kHz, motor connection terminals,
single-phase mains connection terminals
±4, at 5 kHz, three-phase mains connection terminals
±2, Phase/neutral conductor to earth
±4, Phase to earth
> 1000 with 1 % load current reduction every 100 m,
max. 2000 with UL approval, max. 4000 (without UL)
IP40 (NEMA 1)
IP55 (NEMA 3)
IP66 (NEMA 4X)
16DA1 Variable Frequency Drives 10/12 MN04020005Z-EN www.eaton.com
Page 21
1 DA1 device series
1.4 Rated data
Technical DataFormula
sign
General
Main circuit / power section
Power supply system
Rated operational voltage
DA1-12…U
DA1-32…U
DA1-34…U
e
e
e
Mains frequencyfHz50/60 (48 - 62)
Power factor cos ϕ>96
Phase Imbalance%max. 3
Maximum short-circuit current (supply voltage)I
q
Mains switch-on frequencyMaximum of one time every 30 seconds
Mains network configuration (AC power supply
network)
Motor feeder
Output voltage
DA1-12…, DA1-32…, DA1-34…U
2
Output Frequency
Range, parameterizablef
2
ResolutionHz0.1
Overload current
for 60 s%150
for 3 s%200
Pulse frequency
FS2, …, FS7f
PWM
Operating modeV/Hz control, slip compensation, vector control
DC braking
Time before startts0 - 25, in the event of a stop
Motor pick-up control function (for catching spinning
motors)
Brake chopper
Braking current during continuous operation%100 (Ie)
Maximum braking current%150 for 60 s
UnitValue
V1~ 230 (200 V -10 % - 240 V +10 %)
V3~ 230 (200 V -10 % - 240 V +10 %)
V3~ 400 (380 V -10 % - 480 V +10 %)
kA5
TN and TT earthing systems with directly earthed neutral
point.
IT earthing systems with PCM insulation monitoring relays
only.
Operation on phase-earthed networks is only permissible
up to a maximum phase-earth voltage of 300 VAC.
V3~ 0 - U
e
Hz0 - 50/60 (max. 500)
kHzmax. 32
DA1 Variable Frequency Drives 10/12 MN04020005Z-EN www.eaton.com17
Page 22
1 DA1 device series
1.4 Rated data
Technical DataFormula
UnitValue
sign
General
Control section
Control Voltage
Output voltage (control signal terminal 1)U
Load rating (control terminal 1)I
Reference voltage (control terminal 5)U
Load rating (control terminal 5)I
C
1
S
5
V DC24
mA100
V DC10
mA10
Digital input (DI)
Count3 - 5
Logic (level)Increase
Response timetms<4
Input voltage range High (1)U
Input voltage range Low (0)U
C
C
V DC8 - 30
V DC0 - 4
Analog Input (AI)
Count0 - 2
Resolution12-bit
Accuracy%< 1 to the final value
Response timetms<4
Input voltage rangeU
Input current rangeI
S
S
V DC-10 - +10, (Ri ~ 72 kΩ)
mA0/4 - 20 (RB ~ 500 Ω)
Digital output (DO) / relay output (K)
Count2 (analog/digital) / 2 relay
Output voltageU
Output currentI
out
out
V DC0 - 10, 24
mA0/4 - 20
RelaysN/O contact, 6 A (250 V AC) / 5 A (30 V DC)
Changeover contacts, 6 A (250 V AC) / 5 A (30 V DC)
Interface (RJ45)OP bus, Modbus RTU, CANopen
Control levelControl signal terminal/operating unit/interface
18DA1 Variable Frequency Drives 10/12 MN04020005Z-EN www.eaton.com
Page 23
1.4.4 Features
1 DA1 device series
1.4 Rated data
Part no.
Rated opera-
tional current
I
e
[A][kW][A]
Mains supply voltage: 1 AC 230 V
Motor connection voltage: 3 AC 230 V, 50/60 Hz
DA1-124D3…
DA1-127D0…71.56.326.8FNIP20, IP66FS2
DA1-12011…112.28.739.6FN, BIP20, IP66FS2
Mains supply voltage: 3 AC 230 V, 50/60 Hz
Motor connection voltage: 3 AC 230 V, 50/60 Hz
DA1-324D3…
DA1-327D0…71.56.326.8FBIP20, IP66FS2
DA1-32011…10.52.28.739.6FBIP20, IP66FS2
DA1-32012…
DA1-32024…245.519.67.522FBIP20, IP66FS3
DA1-32024…245.519.67.522FBIP55FS4
DA1-32039…397.526.41028FBIP55FS4
DA1-32046…4611381542FBIP55FS4
DA1-32061…6115512054FBIP55FS5
DA1-32072…7218.5632568FBIP55FS5
DA1-32090…
DA1-32110…
DA1-32150…
DA1-32180…
DA1-32202…2025517375192FBIP55FS7
DA1-32248…24875233100248FBIP55FS7
1) The rated motor currents apply to normal internally and surface-cooled three-phase asynchronous motor
(1500 rpm at 50 Hz, 1800 rpm
2) Take motor data into account (6 A = normalized rated value as per UL 580 C)
Operation may be limited to a reduced motor load.
4.30.753.214.2FNIP20, IP66FS2
4.30.753.214.2FBIP20, IP66FS2
18414.8515.2FBIP20, IP66FS3
9022713080FBIP55FS6
110309640104FBIP55FS6
1503711750130FBIP55FS6
1804514160154FBIP55FS6
Assigned motor power
P
(230 V, 50 Hz)
at 60 Hz).
Radio inter-
ference
suppression
Brake
chopper
(integrated)
Protection
type
P
(220 - 240 V, 60 Hz)
1)
[HP][A]
1)
N = No
F = Yes
N = No
B = Yes
IPFS
Size
DA1 Variable Frequency Drives 10/12 MN04020005Z-EN www.eaton.com19
Page 24
1 DA1 device series
1.4 Rated data
Part no.
Rated opera-
tional current
I
e
[A][kW][A]
Assigned motor power
P
(400 V, 50 Hz)
1)
P
(440 - 480 V, 60 Hz)
[HP][A]
Radio inter-
ference
suppression
Brake
chopper
(integrated)
Degree of
protection
N = No
F = Yes
1)
N = No
B = Yes
IPFS
Mains supply voltage: 3 AC 400 V, 50 Hz / 480 V, 60 Hz
Motor connection voltage: 3 AC 400 V, 50 Hz / 440 - 480 V, 60 Hz
DA1-342D2…
2.20.751.912.1FBIP20, IP66FS2
DA1-344D1…4.11.53.623.4FBIP20, IP66FS2
DA1-345D8…5.82.2534.8FBIP20, IP66FS2
DA1-349D5…
DA1-34014…
9.548.557.6FBIP20, IP66FS2
145.511.37.511FBIP20, IP66FS3
DA1-34018…187.515.21014FBIP20, IP66FS3
DA1-34024…241121.71521FBIP20, IP66FS3
DA1-34024…
241121.71521FBIP55FS4
DA1-34030…301529.32027FBIP55FS4
DA1-34039…3918.5362534FBIP55FS4
DA1-34046…4622413040FBIP55FS4
DA1-34061…6130554052FBIP55FS5
DA1-34072…7237685065FBIP55FS5
DA1-34090…9045816077FBIP55FS6
DA1-34110…11055997596FBIP55FS6
DA1-34150…15075134100124FBIP55FS6
DA1-34180…
DA1-34202…
18090161125156FN, BIP55FS6
202110196150180FN, BIP55FS7
DA1-34240…240132231200240FN, BIP55FS7
DA1-34302…
302160279250302FN, BIP55FS7
DA1-34370…370200349300361FN, BIP40FS8
DA1-34450…
1) The rated motor currents apply to normal internally and surface-cooled three-phase asynchronous motor
(1500 rpm at 50 Hz, 1800 rpm
450250437350414FN, BIP40FS8
at 60 Hz).
Size
20DA1 Variable Frequency Drives 10/12 MN04020005Z-EN www.eaton.com
Page 25
1.5 DA1 layout
⑩
⑨
⑦
①
②
③
⑥
④
⑤
⑧
⏚
L1/L
L2/N
L3
DC-
⏚
U
DC+
BR
1 2 3 4 5 6 7 8 9 10 11 12 13
14 15 16 17 18
COM
V
W
1 DA1 device series
1.5 DA1 layout
The following drawing shows examples of named elements of the DA1
variable frequency drives in different frame sizes.
Figure 5:Designation on the DA1 variable frequency drive
a Fixing holes (screw fastening)
b Connection terminals in power section (mains side)
c Cutout for mounting on mounting rail (only for FS2 and FS3)
d Control terminals (plug-in)
e Relay terminals (plug-in)
f Connection terminals in power section (motor feeder)
g Slot for field bus card or expansion module
h Communication interface (RJ45)
i Operating unit with 5 control signal terminals and LED display
j Info card
DA1 Variable Frequency Drives 10/12 MN04020005Z-EN www.eaton.com21
Page 26
1 DA1 device series
1.6 Features
1.6 Features
DA1 series variable frequency drives convert the voltage and frequency of an
existing AC supply system into a DC voltage.
This DC voltage is used to generate a three-phase AC voltage with adjustable
frequency and assigned amplitude values for the variable speed control of
three-phase asynchronous motors.
L1/L
L2/N
②①③④⑤⑥⑦
L3
EMCVAR
⑩
DC+DC-BR
⑧⑨
+
U
-
+
-
+
-
U
V
W
M
3 ~
⑫
⑪
Figure 6:Block diagram; components in a DA1 variable frequency drive
a L1/L, L2/N, L3, PE supply, mains supply voltage U
DA1-12…: single-phase mains connection (1 AC/2 AC 230 V/240 V), motor feeder (3 AC 230 V)
DA1-32…: single-phase mains connection (3 AC 230 V/240 V), motor feeder (3 AC 230 V)
DA1-34…: single-phase mains connection (3 AC 400 V/480 V), motor feeder (3 AC 400 V)
b Internal radio interference suppression filter, EMC connection to PE
c Internal voltage filter, VAR connection to PE
d Rectifier bridge: it converts the AC voltage of the electrical supply to a DC voltage.
e Internal DC link with charging resistor, capacitor and switched-mode power supply unit
(SMPS = Switching-Mode Power Supply).
f Brake chopper for external braking resistor (DC+ and BR connection)
g Inverter. The IGBT based inverter converts the DC voltage
of the DC link (U
h Motor connection with output voltage U
The connection in the motor feeder is implemented with a screened cable that is earthed on both sides
across a large area (PES).
Rated operational current (I
DA1-12…: 4.3 - 10.5 A
DA1-32…: 4.3 - 248 A
DA1-34…: 2.2 - 450 A
100 % at an ambient temperature of +50 °C with an overload capability of 150 % for 60 s
and a starting current of 175 % for 2 s.
i Three-phase asynchronous motor,
variable speed control of three-phase asynchronous motor for assigned motor shaft power values
):
(P
2
DA1-12…: 0.75 - 2.2 kW (230 V, 50 Hz) oder 1 - 3 HP (230 V, 60 Hz)
DA1-32…: 0.75 - 75 kW (230 V, 50 Hz) oder 1 - 100 HP (230 V, 60 Hz)
DA1-34…: 0.75 - 160 kW (400 V, 50 Hz) oder 1 - 255 HP (460 V, 60 Hz)
) into a three-phase AC voltage (U2) with variable amplitude and frequency (f2).
DC
CPUSTO
1 … 11, 14 … 1812 13
at 50/60 Hz:
LN=Ue
(0 to 100 % Ue) and output frequency f2 (0 to 500 Hz)
2
, output current):
e
PES
22DA1 Variable Frequency Drives 10/12 MN04020005Z-EN www.eaton.com
Page 27
1 DA1 device series
1.6 Features
j Control section with operating unit and control buttons, 7-digital display assembly, control voltage,
plug-in control signal terminals, plug-in relay terminal
k RJ45 interface for the PC and fieldbus connection (Modbus RTU, CANopen)
l Safe Torque-Off
Safe removal of torque as per SIL 2 (EN 61508) / PL d (EN ISO 13849-1)
DA1 Variable Frequency Drives 10/12 MN04020005Z-EN www.eaton.com23
Page 28
1 DA1 device series
⏚
L1/L
L2/N
L3
DC-
⏚
U
DC+
BR
1 2 3 4 5 6 7 8 9 10 11 12 13
14 15 16 17 18
COM
V
W
P1-07
P1-08
P1-10
P1-09
P4-05
1410 min
-1
230/400 V3.2/1.9 A
50 Hz
0,75 KW
cos ϕ 0.79
1.7 Selection criteria
1.7 Selection criteria
Select the variable frequency drive according to the supply voltage ULN of the
supply system and the rated operational current of the assigned motor.
The circuit type ( / ) of the motor must be selected according to the rated
operational current.
The rated output current I
of the variable frequency drive must be greater
e
than or equal to the rated motor current.
Figure 7:Selection criteria – Rating plate data
When selecting the drive, the following criteria must be known:
•Type of motor
•Mains voltage = rated operating voltage of the motor (e. g. 3~ 400 V),
•Rated motor current (recommended value, dependent on the circuit type
and the power supply)
•Load torque (quadratic, constant),
•Starting torque,
•Ambient air temperature (rated value e. g. +40 °C).
→
variable frequency drive, the motor currents are
cally
– separated by effective and idle current components.
When you select a variable frequency drive, make sure that it
can supply the total resulting current. If necessary, for dampening and compensating the deviating current values, motor reactors or sinusoidal filters must be installed between the variable
When connecting multiple motors in parallel to the output of a
frequency drive and the motor.
24DA1 Variable Frequency Drives 10/12 MN04020005Z-EN www.eaton.com
added geometri-
Page 29
1.8 Proper use
1 DA1 device series
1.8 Proper use
The DA1 variable frequency drives are not domestic appliances. They are
designed only for industrial use as system components.
The DA1 variable frequency drives are electrical devices for controlling variable speed drives with three-phase motors. They are designed for installation
in machines or for use in combination with other components within a
machine or system.
After installation in a machine, the variable frequency drives must not be
taken into operation until the associated machine has been confirmed to
comply with the safety requirements of Machinery Safety Directive (MSD)
89/392/EEC (meets the requirements of EN 60204). The user of the equipment is responsible for ensuring that the machine use complies with the
relevant EU Directives.
The CE markings on the DA1 variable frequency drive confirm that, when
used in a
pean Low Voltage Directive (LVD) and the EMC Directives (Directive 73/23/
EEC, as amended by 93/68/EEC and Directive 89/336/EEC, as amended by
93/68/EEC).
typical drive configuration, the apparatus complies with the Euro-
In the described system configurations, DA1 variable frequency drives are
suitable for use in public and non-public networks.
A connection of a DA1 variable frequency drive to IT networks (networks
without reference to earth potential) is permissible only to a limited extent,
since the device’s built-in filter capacitors connect the network with the earth
potential (enclosure).
On earth free networks, this can lead to dangerous situations or damage to
the device (isolation monitoring required).
→
Observe the technical data and connection requirements.
For additional information, refer to the equipment nameplate or label of the
variable frequency drive and the documentation. Any other usage constitutes
improper use.
To the output (terminals U, V, W) of the DA1 variable frequency
drive you must not:
•connect a voltage or capacitive loads (e.g. phase compensa-
tion capacitors),
•connect multiple variable frequency drives in parallel,
•make a direct connection to the input (bypass).
DA1 Variable Frequency Drives 10/12 MN04020005Z-EN www.eaton.com25
Page 30
1 DA1 device series
1.9 Maintenance and inspection
1.9 Maintenance and inspection
DA1 series variable frequency drives will be maintenance-free as long as the
general rated operational data ( Section 1.4.3, “General rated operational
data“, page16) is adhered to and the specific technical data (see appendix)
for the corresponding ratings is taken into account. Please note, however,
that external influences may affect the operation and lifespan of a DA1 variable frequency drive.
We therefore recommend that the devices are checked regularly and the following maintenance measures are carried out at the specified intervals.
Table 2:Recommended maintenance for DA1 variable frequency drives
Maintenance measuresMaintenance interval
Clean cooling vents (cooling slits)Please enquire
Check the fan function6 - 24 months (depending on the environment)
Filter in the switching cabinet doors
(see manufacturer specifications)
Check all earth connections to make sure they
are intact
Check the tightening torques of the terminals
(control signal terminals, power terminals)
Check connection terminals and all metallic
surfaces for corrosion
Motor cables and shield connection (EMC)
Charge capacitors
6 - 24 months (depending on the environment)
On a regular basis, at periodic intervals
On a regular basis, at periodic intervals
6 - 24 months; when stored, no more than 12 months later
(depending on the environment)
According to manufacturer specifications, no later than 5 years
12 months
(→ Section 1.11, “Charging the internal DC link capacitors“)
1.10 Storage
There are no plans for replacing or repairing individual components of DA1
variable frequency drives.
If the DA1 variable frequency drive is damaged by external influences, repair
is not possible.
Dispose of the device according to the applicable environmental laws and
provisions for the disposal of electrical or electronic devices.
If the DA1 variable frequency drive is stored before use, suitable ambient
conditions must be ensured at the site of storage:
•Storage temperature: -40 - +70 °C,
•Relative average air humidity: < 95 %, non condensing (EN 50178),
•To prevent damage to the RASP DC link capacitors, storage times longer
than 12 months are not recommended
( Section 1.11, “Charging the internal DC link capacitors“).
26DA1 Variable Frequency Drives 10/12 MN04020005Z-EN www.eaton.com
Page 31
1.11 Charging the internal DC link capacitors
After extended storage times or extended downtimes during which no
power is supplied (> 12 months), the capacitors in the internal DC link must
be recharged in a controlled manner in order to prevent damage. To do this,
the DA1 variable frequency drive must be supplied with power, with a controlled DC power supply unit, via two mains connection terminals (e.g. L1
and L2).
In order to prevent the capacitors from having excessively high leakage currents, the inrush current should be limited to approximately 300 to 800 mA
(depending on the relevant rating). The variable frequency drive must not be
enabled during this time (i.e. no start signal). After this, the DC voltage must
be set to the magnitudes for the corresponding DC link voltage
(U
1.41 x Ue) and applied for one hour at least (regeneration time).
DC
1 DA1 device series
1.11 Charging the internal DC link capacitors
1.12 Service and warranty
•DA1-12…, DA1-32…: about 324 V DC at U
•DA1-34…: about 560 V DC at U
= 400 V AC.
e
= 230 V AC.
e
In the unlikely event that you have a problem with your DA1 variable frequency drive, please contact your local sales office.
When you call, have the following data ready:
•The
exact variable frequency drive part number (see nameplate),
•the date of purchase,
•a detailed description of the problem which has occurred with the
variable frequency drive.
If some of the information printed on the rating plate is not legible, please
state only the data which are clearly legible.
Information concerning the guarantee can be found in the Terms and
Conditions Eaton Industries GmbH.
24-hour hotline: +49 (0)1805 223 822
E-Mail:
AfterSalesEGBonn@eaton.com
DA1 Variable Frequency Drives 10/12 MN04020005Z-EN www.eaton.com27
Page 32
1 DA1 device series
1.12 Service and warranty
28DA1 Variable Frequency Drives 10/12 MN04020005Z-EN www.eaton.com
Page 33
2 Engineering
③
②
①
L1
L2
L3
PE
⑤
④
⑦
⑩
⑨
⑧
⑥
RCD
L1/L
L2/N
PE
U
VW
L3 PE
DC+
BR
M
3
ϑ
˜
PES
PES
#
I > I > I >
⑪
2.1 Introduction
2 Engineering
2.1 Introduction
This chapter describes the most important features in the energy circuit of a
magnet system (PDS = Power Drive System), which you should take into
consideration in your project planning.
Figure 8:Example of a magnet system with a three-phase feeder unit
for a three-phase motor
a Network configuration, mains voltage, mains frequency, interaction with p.f. correction systems
b Fuses and cable cross-sections, cable protection
c Protection of persons and domestic animals with residual current protective devices
d Mains contactor
e Main choke, radio interference filter, line filter
f Variable frequency drive: mounting; installation; power connection; EMC compliance;
circuit examples
g Motor reactor, dV/dt filter, sinusoidal filter
h Motor protection; Thermistor overload relay for machine protection
i Cable lengths, motor cables, shielding (EMC)
j Motor and application, parallel operation of multiple motors on a variable frequency drive
(only for V/f), bypass circuit; DC braking
k Braking resistance; dynamic braking
DA1 Variable Frequency Drives 10/12 MN04020005Z-EN www.eaton.com29
Page 34
2 Engineering
L2
N
L1
L3
PE
L2
PEN
L1
L3
EMC
L3
U
L2/N
L1/L
VAR
PH1
M3
20 mm (0.79")
EMC
VAR
2.2 Electrical power network
2.2 Electrical power network
2.2.1 Mains connection and configuration
The variable frequency drives of the DA1 series can be connected and operated with all control-point grounded AC supply systems (see IEC 60364 for
more information in this regard).
Figure 9:AC power networks with earthed center point (TN-/TT networks)
→
to the three main poles, if multiple variable frequency drives
with single-phase incoming unit are to be connected.The total
current of all single phase consumers is not to cause an overload of the neutral conductor (N-conductor).
The connection and operation of variable frequency drives to asymmetrically
grounded TN networks (phase-grounded Delta network “Grounded Delta“,
USA) or non-grounded or high-resistance grounded (over 30 ) IT networks is
only conditionally permissible.
Operation on non-earthed networks (IT) requires the use of suit-
While planning the project, consider a symmetrical distribution
→
able insulation monitors (e.g. pulse-code measurement
method).
In networks with an earthed main pole, the maximum phase-
→
earth voltage must not exceed 300 VAC.
If DA1 series variable frequency drives are connected to an asymmetrically
earthed network or to an IT network (non-earthed, insulated), the internal
radio interference suppression filter must be disconnected (by unscrewing
the screw marked EMC).
30DA1 Variable Frequency Drives 10/12 MN04020005Z-EN www.eaton.com
Figure 10:EMC screw location
Page 35
2 Engineering
2.2 Electrical power network
The required filter winding for electromagnetic compatibility (EMC) no longer
exists in this case.
→
2.2.2 Mains voltage and frequency
The standardized rated operating voltages (IEC 60038, VDE 017-1) of power
utilities guarantee the following conditions at the connection point:
•Deviation from the rated value of voltage:
maximum ±10 %
•Deviation in voltage phase balance:
maximum ±3 %
•Deviation from rated value of the frequency:
maximum ±4 %
The broad
rated value for European as (EU: ULN = 230 V/400 V, 50 Hz) and American as
(USA: U
LN
Measures for electromagnetic compatibility are mandatory in a
magnet system, to meet the legal standards for EMC- and lowvoltage regulations.
Good earthing measures are a prerequisite for the effective
insert of further measures such as screen earth kit or filters
here. Without respective grounding measures, further steps are
superfluous.
tolerance band of the DA1 variable frequency drive considers the
= 240 V/480 V, 60 Hz) standard voltages:
2.2.3 Voltage balance
•230 V, 50 Hz (EU) and 240 V, 60 Hz (USA) at DA1-12…, DA1-32…
200 V - 10 % - 240 V + 10 % (190 V - 0 % - 264 V + 0 %)
•400 V, 50 Hz (EU) and 480 V, 60 Hz (USA) at DA1-34…
380 V - 10 % - 480 V + 10 % (370 V - 0 % - 528 V + 0 %)
The permissible frequency range for all voltage categories is 50/60 Hz
(48Hz-0%-62Hz+0%).
Because of the uneven loading on the conductor and with the direct connection of greater power ratings, deviations from the ideal voltage form and
asymmetrical voltages can be caused in three-phase AC power networks.
These asymmetric divergences in the mains voltage can lead to different
loading of the diodes in mains rectifiers with three-phase supplied variable
frequency drives and as a result, to an advance failure of this diode.
→
If this condition is not fulfilled, or symmetry at the connection location is not
known, the use of an assigned main choke is recommended.
In the project planning for the connection of three-phase supplied variable frequency drives (DA1-3…), consider only AC
supply systems that handle permitted asymmetric divergences
in the mains voltage +3 %.
DA1 Variable Frequency Drives 10/12 MN04020005Z-EN www.eaton.com31
Page 36
2 Engineering
THD
n2xx=
I
1
---------------------- -=
n=2
I
n
2
2.2 Electrical power network
2.2.4 Total Harmonic Distortion (THD)
Non-linear consumers (loads) in an AC supply system produce harmonic voltages that again result in harmonic currents. These harmonic currents at the
inductive and capacitive reactances of a mains supply system produce additional voltage drops with different values which are then overlaid on the sinusoidal mains voltage and result in distortions. In supply systems, this form of
"noise" can give rise to problems in an installation if the sum of the harmonics
exceeds certain limit values.
Non-linear consumers (harmonics producers) include for example:
•Induction and arc furnaces, welding devices,
•Current converters, rectifiers and inverters, soft starters, variable fre-
quency drives,
•Switched-mode power supply units (computers, monitors, lighting),
uninterrupted power supply (UPS).
The THD value (THD = Total Harmonic Distortion) is defined in standard
IEC/EN 61800-3 as the ratio of the rms value of all harmonic components to
the rms value of the fundamental frequency.
For example, the THD for a current is:
Where I
is the rms value of the fundamental frequency current and n is the
1
order of a harmonic with its own frequency, which is an integer multiple of
the fundamental frequency (Fourier analysis).
Example:
5th harmonic of a mains frequency of 50 Hz : 5 x 50 Hz = 250 Hz.
The THD value of the harmonic distortion is stated in relation to the rms
value of the total signal as a percentage. On a variable frequency drive, the
total harmonic distortion is around 120 %. A mains choke (such as 4 % u
the supply side of a variable frequency drive enables the
THD value with a
) on
k
single-phase supply (B2 diode rectifier bridge) to be reduced to around 80 %
and with a three-phase supply (B6 diode rectifier bridge) to around 50 %.
The supply quality is thus improved and the mains supply distortion is
reduced. The power factor is also improved.
32DA1 Variable Frequency Drives 10/12 MN04020005Z-EN www.eaton.com
Page 37
2.2.5 Idle power compensation devices
Compensation on the power supply side is not required for the variable
frequency drives of the DA1 series. From the AC power supply network they
only take on very little reactive power of the fundamental harmonics
(cos ~ 0.98).
2 Engineering
2.2 Electrical power network
2.2.6 Mains chokes
→
Main chokes (also known as commutating chokes) increase the choke of the
mains supply cable. This extends the current flow period and dampens mains
deviations.
These reduce the total harmonic distortion, the mains feedback and improve
the power factor. The apparent current on the mains side is then reduced by
around 30 %.
Towards the variable frequency drive, the main chokes dampen the interference from the supply network. This increases the electric strength of the
variable frequency drive and lengthens the lifespan (diodes of the mains rectifier, internal DC link capacitors).
→
In the AC supply systems with non-choked reactive current
compensation devices, current deviations can enable parallel
resonance and undefinable circumstances.
In the project planning for the connection of variable frequency
drives to AC supply systems with undefined circumstances,
consider using main chokes.
For the operation of the DA1 variable frequency drive, the application of main chokes is not necessary. We do recommend
however that an upstream mains choke is used since the network quality is not known in most cases.
While planning the project, consider
assigned to a single variable frequency drive for decoupling.
When using an adapting transformer (assigned to a single variable frequency drive), a main choke is not necessary.
Main chokes are designed based on the mains-side input cur-
(ILN) of the variable frequency drive.
rent
DA1 Variable Frequency Drives 10/12 MN04020005Z-EN www.eaton.com33
that a main choke is only
Page 38
2 Engineering
2.3 Safety and switching
2.3 Safety and switching
2.3.1 Fuses and cable cross-sections
The fuses and wire cross-sections allocated for power-side connections
depend on the rated mains current I
out main choke).
The recommended fuses and their assignment to the variable frequency
drives are listed in Page 218 the appendix.
of the variable frequency drive (with-
LN
NOTICE
When selecting the cable cross-section, take the voltage drop
under load conditions into account.
The consideration of other standards (e.g. VDE 0113 or
VDE 0289) is the responsibility of the user.
The national and regional standards (for example VDE 0113, EN 60204) must
be observed and the necessary approvals (for example UL) at the site of
installation must be fulfilled.
When the device is operated in a UL-approved system, use only UL-approved
fuses, fuse bases and cables. The permissible cables must have a heat resistance of 75 °C.
The connection terminals marked with and the metallic enclosure (IP66)
must be connected to the earth-current circuit.
The leakage currents to earth (as per EN 50178) are greater than 3.5 mA.
They are listed for the individual ratings in the appendix, under the specific
technical data on Page 203.
→
As per the requirements in standard EN 50178, a protective
earth (PE) must be connected. The cable cross-section must be
at least 10 mm
cables.
NOTICE
The specified minimum PE conductor cross-sections
(EN 50178, VDE 0160) must be maintained.
2
or consist of two separately connected earthing
A completely (360°) screened low impedance cable on the motor side is
required. The length of the motor cable depends on the RFI class and the
environment.
→
34DA1 Variable Frequency Drives 10/12 MN04020005Z-EN www.eaton.com
Choose the cross-section of the PE conductor in the motor lines
at least as
large as the cross-section of the phase lines (U, V, W).
Page 39
2.3.2 Residual current device
Residual current devices (RCD) are also known as residual current device
(GFCI) or residual current circuit breaker (RCCB).
Residual current devices protect people and farm animals from the presence
(not the production!) of impermissibly high touch voltages.
gerous
to prevent fires.
2 Engineering
2.3 Safety and switching
They prevent dan-
(including fatal) injuries caused by electrical accidents and also serve
→
Residual current devices must be suitable for:
•the
•high leakage currents (300 mA),
•Briefly diverting surge currents
CAUTION
Marking on the residual current device
AC/DC sensitive (RCD, part no.
B)
→
Only AC/DC sensitive residual current devices (RCD, type B)
may be used with variable frequency drives (EN 50178,
IEC 755).
Variable frequency drives work internally with rectified AC currents. If an error occurs, the DC currents can block an RCD
safety device of type A from triggering and therefore disable the
protective functionality.
protection of installations with DC current component in
case of fault scenario (RCD, type B),
NOTICE
Residual current devices (RCD) are only to be installed between
the AC power supply network and the variable frequency drive.
→
Leakage currents to earth are mainly caused by foreign capacities with variable frequency drives: between the motor phases and the shielding of the
motor cable and via the star capacitor of the radio interference suppression
filter.
DA1 Variable Frequency Drives 10/12 MN04020005Z-EN www.eaton.com35
Safety-relevant leakage currents can occur while handling and
when operating the variable frequency drive, if the variable frequency drive is not earthed.
Page 40
2 Engineering
2.4 EMC compliance
2.3.3 Mains contactors
The size of the leakage currents is mainly dependent upon the:
•length of the motor cable,
•shielding of the motor cable,
•height of the pulse frequency (switching frequency of the inverter),
•Design of the radio interference suppression filter
•grounding measures at the site of the motor.
The mains contactor enables an operational switching on and off of the supply voltage for the variable frequency drive and switching off in case of a
fault.
2.4 EMC compliance
The mains contactor is designed based on the mains-side input current I
the variable frequency drive for utilization category AC-1 (IEC 60947) and the
ambient air temperature at the location of use. Mains contactors and their
assignment to the variable frequency drives belonging to the DC1 series are
listed in the appendix (Table 27, page 220).
→
Electrical components in a system (machine) have a reciprocal effect on each
other. Each device not only emits interference but is also affected by it. This
occurs as a result of galvanic, capacitive and/or inductive coupling or through
electromagnetic radiation. In practice, the limit between line-conducted interference and emitted interference is around 30 MHz. At values above 30 MHz
the lines and cables act like antennas and radiate the electromagnetic waves.
While planning the project, make sure that inching operation is
not done via the mains contactor of the variable frequency drive
on frequency-controlled drives, but through a controller input of
the variable frequency drive.
The maximum permissible mains voltage switch-on frequency
for the
(normal operation).
DA1 variable frequency drive is once every 30 seconds
LN
of
Electromagnetic compatibility (EMC) for frequency controlled drives (variable
speed drives) is implemented in accordance with product standard IEC/EN
61800-3. This includes the complete power magnet system (PDS = Power
Drive System), from the mains supply to the motor, including all components, as well as cables ( Figure 8, page 29). This type of drive system can
also consist of several individual drives.
The generic standards of the individual components in a magnet system
compliant with IEC/EN 61800-3 do not apply. These component manufacturers, however, must offer solutions that ensure standards-compliant use.
In Europe, maintaining the EMC Directive is mandatory.
36DA1 Variable Frequency Drives 10/12 MN04020005Z-EN www.eaton.com
Page 41
2 Engineering
1. Environment
Public medium-voltage system
PCC
Category C1
Category C2
Category C1 / C2Category C1 / C2
Category C3 / C4
Category C3 / C4
1.or 2. environment2. Environment
Public
low-voltage system
Private
mains
Industrial
mains
2.4 EMC compliance
A declaration of conformity (CE) refers always to a “typical“ power magnet
system (PDS). The responsibility to comply with the legally stipulated limit
values and thus the provision of electromagnetic compatibility is ultimately
the responsibility of the end user or system operator. Measures must be
taken to remove or minimize emission in the associated environment
( Figure 11). He must also utilize means to increase the interference
immunity of the devices of the system.
With their high interference immunity up to category C3, DA1 variable frequency
The DA1…-F… version (with integrated RFI filter) makes it possible to comply with the stringent limit values for conducted emission for category C1 in
the 1st environment. This requires a correct EMC installation ( Page 53)
and the observance of the permissible motor cable lengths and the maximum switching frequency (f
In the case of variable frequency drives without an internal radio interference
suppression filter, longer motor cable lengths and lower leakage currents can
sometimes be achieved for the individual categories by using a dedicated
external radio interference suppression filter.
drives are ideal for use in harsh industrial networks (2nd environment).
) of the inverter.
PWM
The required EMC measures should be taken into account in the engineering
phase. Improvements and modifications during mounting and installation or
even at the installation site involve additional and even considerably higher
costs.
Figure 11:EMC environment and categories
DA1 Variable Frequency Drives 10/12 MN04020005Z-EN www.eaton.com37
Page 42
2 Engineering
2.5 Motor and Application
2.5 Motor and Application
2.5.1 Motor selection
General recommendations for motor selection:
•For a frequency-controlled magnet system (PDS), use three-phase AC
motors with squirrel-cage rotors and surface cooling, also known as
three-phase asynchronous motors or standard motors. Other types of
motors, such as external rotor motors, wound-rotor motors, reluctance
motors, permanent-magnet motors, synchronous motors, and servomotors can also be operated with a variable frequency drive, but normally
require additional engineering in consultation with the motor's manufacturer.
•Only use motors that have insulation class F (maximum steady state
temperature of 155 °C) at least.
-1
•Choose 4 pole motors preferably (synchronous speed: 1500 min
50 Hz and 1800 min
•Take
•When operating multiple motors in parallel on one variable frequency
•Ensure that the motor is not overdimensioned. If it is underdimensioned
the operating conditions into account for S1 operation (IEC 60034-1).
drive, the motor output should not be more than three power classes
apart.
in the “speed control“ (slip compensation) operating mode, the motor
output may only be one single assigned output level lower.
-1
at 60 Hz).
at
2.5.2 Parallel connection of motors
The DA1 variable frequency drives allow parallel operation of several motors
in “V/f control mode“:
•With multiple motors with the same or different rated operational data:
The total of the motor currents must be less than the rated operational
current of the variable frequency drive.
•Connecting and disconnecting individual motors: The total of the motor
currents in operation, plus the motor’s inrush current, must be less than
the rated operational current of the variable frequency drive.
Parallel operation at different motor speeds can be implemented only by
changing the number of pole pairs and/or changing the motor’s transmission
ratio.
Connecting motors in parallel reduces the load resistance at the variable frequency drive output. The total stator inductance is lower and the leakage
capacity of the lines greater. As a result, the current distortion is greater than
in a single-motor circuit.
38DA1 Variable Frequency Drives 10/12 MN04020005Z-EN www.eaton.com
Page 43
2 Engineering
2.5 Motor and Application
To reduce the current distortion, you should use motor reactors (see in
Figure12) in the output of the variable frequency drive.
①
Q11
F1
U1 V1 W1U1 V1 W1U1 V1 W1
M
M1
3
˜
Figure 12:Parallel connection of several motors to one variable frequency drive
F2
Q12
M2
Q13
F3
M
3
˜
M3
M
3
˜
NOTICE
If multiple motors are connected in parallel to a single variable
frequency drive, make sure to dimension the individual motors’
contactors for utilization category AC-3. The
motor contactor
must be selected according to the rated operational current of
the motor that will be connected.
The current consumption of all motors connected in parallel
→
must not exceed the variable frequency drive’s rated output cur-
2N
.
rent I
When operating multiple motors in parallel, you cannot use the
→
variable frequency drive’s electronic motor protection. You will
have to protect each motor individually with thermistors and/or a
current transformer-operated overload relay.
→
variable frequency drives can result in motors being disconnected in an undefined manner and is only possible in select
applications.
DA1 Variable Frequency Drives 10/12 MN04020005Z-EN www.eaton.com39
The use of motor-protective circuit-breakers at the output of
Page 44
2 Engineering
1410 mi n
230/400 V3.2/1.9 A
50 Hz
-1
0,75 KW
cos ϕ 0.79
U1 V1 W1
W2 U2 V2
U1 V1 W1
W2 U2 V2
2.5 Motor and Application
2.5.3 Circuit types with three-phase motors
The three-phase motor’s stator winding can be connected in a star or delta
circuit as per the rated operational data on the rating plate.
Figure 13:Example of a motor
rating plate
Figure 14:Configuration types:
2.5.4 87-Hz Characteristic curve
The three-phase motor with the rating plate in Figure13 can be operated with
either a start or delta circuit. The operational characteristic curve is determined by the ratio of motor voltage to motor frequency in this case.
The 87 Hz characteristic curve is used to operate the three-phase standard
motor with the rating plate in Figure13 with a delta circuit on a 400 V network
at 87 Hz. To enable this, the variable frequency drive must deliver the higher
current for delta circuits (3.2 A) and the motor frequency (V/Hz key point)
must be set to 87 Hz on the variable frequency drive.
This results in the following advantages:
•The motor’s speed adjustment range is increased by a factor of 3 (from
50 Hz to 87 Hz)
•The motor’s efficiency is improved, since the motor speed increases
while the (absolute) slip remains the same and therefore is smaller, percentage-wise, relative to the new (higher) speed.
•Greater power can be taken from the motor (P ~ M x n), making it possi-
ble in some cases to use a motor one size smaller (and therefore more
affordable) for the application (e.g. travel motor in crane drives)
•The machine speed of existing machines can be increased without
having to change the motor and/or transmission. In other words, operation does not take place within the field-weakening range.
40DA1 Variable Frequency Drives 10/12 MN04020005Z-EN www.eaton.com
→
Due to the higher thermal load, it is recommended to only use
the next higher listed motor output and to only use motors with
an insulation class of F at the very least.
Page 45
2 Engineering
0
8750
400
U2 [V]
f [Hz]
f
max
230
ac
b
2.5 Motor and Application
→
rpm must be taken into account. Consult the manufac-
5,000
turer’s specifications.
If using 2 pole motors (p = 1), the high speed of approximately
Figure 15:V/Hz characteristic curve
for the rating plate of the motor from Figure 13
a Star connection: 400 V, 50 Hz
b Delta circuit: 230 V, 50 Hz
c Delta connection: 400 V, 87 Hz
The following Tabelle 3 shows the allocation of possible variable frequency
drives depending on the mains voltage and the type of circuit.
Table 3:Assignments between variable frequency drives and V/Hz characteristic curve
DA1 Variable Frequency Drives 10/12 MN04020005Z-EN www.eaton.com41
Page 46
2 Engineering
2.5 Motor and Application
2.5.5 Bypass operation
When it is necessary to be able to power the motor directly with mains voltage independently from the variable frequency drive (bypass operation), the
branches must be mechanically interlocked.
NOTICE
The system may only switch (S1) between the variable frequency drive (T1) and mains voltage (see Figure16) while in a
de-energized state.
CAUTION
L1
Q1
>
Q11
L1 L2 L3
UVW
T1
S1
The variable frequency drive’s outputs (U, V, W) must not be
connected to the mains voltage (destruction risk, fire hazard).
L2
L3
a
I>I>I
b
M
M1
3h
Figure 16:Bypass motor control (example)
→
→
42DA1 Variable Frequency Drives 10/12 MN04020005Z-EN www.eaton.com
When running the motor directly with mains voltage, protective
measures (circuit-breaker with thermal overload protection or
overload relay ) against overload must be in place.
Contactors and switches (S1) in the variable frequency drive output and for the direct start must be designed based on utilization
category AC-3 for the rated operational current of the motor.
Page 47
2.5.6 Connecting EX motors
①
②
f
2
5 1015202530354045
The following aspects must be taken into account when connecting explosion-proof motors:
•The variable frequency drive must be installed outside the EX area.
•All applicable industry-specific and country-specific regulations for haz-
•The specifications and instructions provided by the motor’s manufac-
•Temperature monitors in the motor windings (thermistor, Thermo-Click)
2.5.7 Sinusoidal filter
Sinusoidal filters are connected in the output of a variable frequency drive.
2 Engineering
2.5 Motor and Application
ardous locations (ATEX 100a) must be complied with.
turer with regard to operation with a variable frequency drive – e.g.,
whether motor reactors (dV/dt limiting) or sinusoidal filters are required –
must be taken into account.
must not be connected directly to the variable frequency drive, but
instead must be connected through a relay approved for the hazardous
location (e.g. EMT6).
1U1
1V1
1W1
PE
U
2
1W2
PE
1V2
1U2
M
3 ~
Figure 17:Circuit Diagram of a sinusoidal filter
U ∼
The sinusoidal filter removes high-frequency components above the set
resonance frequency from the variable frequency drive output voltage (U
This reduces the conducted and radiated emission.
a Without sinusoidal filter
b With sinusoidal filter
f: Rotating field frequency
n: Order of harmonics
).
2
Figure 18:High frequency components of the output voltage
DA1 Variable Frequency Drives 10/12 MN04020005Z-EN www.eaton.com43
Page 48
2 Engineering
U∼
U
2
2.5 Motor and Application
The output voltage of the sinusoidal filter (U~) achieves a sinusoidal shape
with a slight superimposed ripple voltage.
The THD factor of the sinusoidal voltage is normally 5 to
Figure 19: Output voltage to motor
: Variable frequency drive output voltage
U
2
U~: Simulated sinusoidal voltage
10 %.
Advantages of sinusoidal filters:
•Long motor cable lengths with reduced conducted and radiated inter-
ference
•Reduced motor losses and noise
•Longer motor lifespan
Disadvantages of sinusoidal filters:
•Voltage drop of up to 9 % caused by system
(approx. 36 V if U
= 400 V)
2
•higher heat dissipation,
•A fixed pulse frequency is required
•Require more space inside the control panel
NOTICE
Sinusoidal filters must only be used with permanently set pulse
frequencies.
44DA1 Variable Frequency Drives 10/12 MN04020005Z-EN www.eaton.com
Page 49
3 Installation
3.1 Introduction
3 Installation
3.1 Introduction
This chapter explains how to install and electrically connect DA1 series variable frequency drives.
3.2 Mounting
→
→
The instructional leaflets in this section are meant to show how to install the
device in a suitable enclosure for devices with protection type IP20 in compliance
with standard EN 60529 and/or any other applicable local regulations.
•The enclosures must be made of a material with high thermal conductiv-
ity.
•If a control panel with ventilation openings is used, the openings must
be located above and below the variable frequency drive in order to allow
for proper air circulation. The air should come in from below the variable
frequency drive and leave above it.
•If the environment outside the control panel contains dirt particles (e.g.,
dust), a suitable particulate filter must be placed on the ventilation openings and forced ventilation must be used. The filters must be maintained
and cleaned if necessary.
•An appropriate enclosed control panel (without ventilation openings)
must be used in environments containing large percentages or amounts
of humidity, salt, or chemicals.
While mounting and/or assembling the variable frequency drive,
cover all ventilation slots in order to ensure that no foreign bodies can enter the device.
Perform all installation work with the specified tools and without
the use of
excessive force.
DA1 Variable Frequency Drives 10/12 MN04020005Z-EN www.eaton.com45
Page 50
3 Installation
≦ 30º
≦ 30º
≦ 30º
≦ 30º
3.2 Mount i ng
3.2.1 Mounting position
DA1 series variable frequency drives are designed to be mounted vertically.
The maximum permissible inclination is 30°.
3.2.2 Cooling measures
Figure 20:Mounting position
In order to guarantee sufficient air circulation, enough thermal clearance
must be ensured according to the frame size (rating) of the variable frequency drive.
c
a
12345678910111213
COM
DC+ BR U V W
b
L2/N L3DC- L1/L
L2/N L3DC- L1/L
a
12345678910111213
COM
14 15 16 17 18
14 15 16 17 18
DC+ BR U V W
c
Figure 21:Space for air-cooling
46DA1 Variable Frequency Drives 10/12 MN04020005Z-EN www.eaton.com
Page 51
3 Installation
3.2 Mount i ng
Table 4:Minimum clearance and required cooling air
SizeabcdAir through-put
[mm] [in][mm][in][mm] [in][mm][in][m3/h][ft3/min]
FS2501.97461.81752.95752.9518.711
FS3501.97522.051003.941003.9444.226
FS4100.39712.82007.872007.87––
FS5100.39702.762007.872007.87––
FS6100.391405.522007.872007.87––
FS7100.391405.522007.872007.87––
The values in 4 are recommended values for an ambient air temperature of
up to +50 °C, an installation altitude of up to 1000 m, and a pulse frequency
of up to 8 kHz.
→
≧ 15 mm
(≧ 0.59”)
Figure 22:Minimum required clearance
conditions.
in front of the variable frequency drive
Please note that the mounting makes it possible to open and
Typical heat loss makes up about 3 % of the operational load
→
close the control signal terminal covers without any problems.
When variable frequency drives with internal fans are installed vertically over
each other, an air baffle must be placed between the devices. Failure to do
so may expose the device on top to a thermal overload caused by the guided
air flow (device fan).
DA1 Variable Frequency Drives 10/12 MN04020005Z-EN www.eaton.com47
Page 52
3 Installation
3.2 Mount i ng
V
d
c
Figure 23:Air baffle due to increased circulation with device fan
→
Devices with high magnetic fields (e.g. reactors or transformers)
should not be installed close to the variable frequency drive.
V
48DA1 Variable Frequency Drives 10/12 MN04020005Z-EN www.eaton.com
Page 53
3.2.3 Control panel installation
⏚
L1/L
L2/N
L3
DC-
⏚
U
DC+
BR
1 2 3 4 5 6 7 8 9 10 11 12 13
1
4 15 16 17 18
COM
V
W
d
d
b
c
a
3 Installation
3.2 Mount i ng
Figure 24:Control panel dimensioning
Calculation of control panel surface:
P
A=
V
[m2]
ΔT x K
A= Control panel surface [m
P
= Total heat dissipation [W] of all fitted devices
V
2
] calculated according to IEC 890)
T = Temperature difference [K], (default value = 5.5 K)
K= Heat transfer coefficient [W/(m2xK)]
(standard value = 5.5 for steel control panels)
DA1 Variable Frequency Drives 10/12 MN04020005Z-EN www.eaton.com49
Page 54
3 Installation
3.2 Mount i ng
3.2.4 Fixing
Variable frequency drives with frame sizes of FS2 and FS3 can be fastened
with screws or on a mounting rail. Sizes FS4 to FS8 can only be fastened
using screws.
3.2.4.1 Fixing with screws
→
→
→
→
Install the variable frequency drive only on a nonflammable
mounting base (e.g., on a metal plate).
Dimension and weight specifications for the DA1 variable frequency drive can be found in the appendix ( Page 209).
The number and layout of required mounting dimensions a1 and
b1, the tightening torque for the screws, etc. are listed in
Section 9.2, “Dimensions and frame size“.
Use screws with a washer and split washer with the permissible tightening torque in order to protect the enclosure and safely
and reliably mount the device.
a1
EMC
VAR
c1
c
Figure 25:Mounting dimensions
b1
50DA1 Variable Frequency Drives 10/12 MN04020005Z-EN www.eaton.com
Page 55
3 Installation
1
2
3
b1
a1
25
35
1
7.5
15
3.2 Mount i ng
Figure 26:Mounting preparation
First fit the screws at the specified positions, mount the variable fre-
quency drive and then fully tighten all screws.
→
3.2.4.2 Fixing on mounting rails
As an alternative to screw mounting, DA1 variable frequency drives of sizes
FS2 and FS3 can also be mounted on a mounting rail as per IEC/EN 60715.
Figure 27:Mounting rail conforming with IEC/EN 60715
To do this, place the variable frequency drive on the mounting rail from
above [1] and press it down until it snaps into place [2].
The permitted maximum tightening torque for the fixing screws
is 1.3 Nm.
DA1 Variable Frequency Drives 10/12 MN04020005Z-EN www.eaton.com51
Page 56
3 Installation
2
1
3
EMC
VAR
f 5 mm
(f 0.197“)
3.2 Mount i ng
1
EMC
VAR
EMC
VAR
2
Figure 28:Fixing to the mounting rail
Dismantling from mounting rails
To remove the device, push down the spring-loaded clip. A cutout
marked on the lower edge of the device is provided for this purpose.
A flat-bladed screwdriver (blade width 5 mm) is recommended for pushing down the clip.
Figure 29:Dismantling from mounting rails
52DA1 Variable Frequency Drives 10/12 MN04020005Z-EN www.eaton.com
Page 57
3.3 EMC installation
3 Installation
3.3 E MC in st allat i on
The responsibility to comply with the legally stipulated limit values and thus
the provision of electromagnetic compatibility is the responsibility of the end
user or system operator. This operator must also take measures to minimize
or remove emission in the environment concerned ( Figure 11, page 37).
He must also utilize means to increase the interference immunity of the
devices of the system.
In a magnet system (PDS) with variable frequency drives, you should take
measures for electromagnetic compatibility (EMC) while doing your engineering, since changes or improvements to the installation site, which are
required in the installation or while mounting, are normally associated with
additional higher costs as well.
The technology and system of a variable frequency drive cause the flow of
high frequency leakage current during operation. All grounding measures
must therefore be implemented with low impedance connections over a
large surface area.
With leakage currents greater than 3.5 mA, in accordance with VDE 0160 or
EN 60335, either
•the cross-sectional area of the protective conductor must be 10 mm
•The protective conductor must be open-circuit monitored, or
•the second protective conductor must be fitted.
2
,
For an EMC-compliant installation, we recommend the following measures:
•Installation of the variable frequency drive in a metallically conductive
housing with a good connection to ground,
•screened motor cables (short cables).
→
Ground all conductive components and housings in a magnet
system using as short
ble cross-section (Cu-drain wire).
3.3.1 EMC measures in the control panel
For the EMC-compatible installation, connect all metallic parts of the device
and the switching cabinet together over broad surfaces and so that high-frequencies will be conducted. Mounting plates and control panel doors should
make good contact and be connected with short HF-drain wires. Avoid using
painted surfaces (Anodized, chromized). An overview of all EMC measures is
provided in Figure31 on Page 53.
→
Install the variable frequency drive as directly as possible (without spacers) on a metal plate (mounting plate).
a
line as possible with the greatest possi-
→
DA1 Variable Frequency Drives 10/12 MN04020005Z-EN www.eaton.com53
Route mains and motor cables in the switch cabinet as close to
the ground potential as possible. This is because free moving
cables act as antennas.
Page 58
3 Installation
3.3 E MC in st allat i on
3.3.2 Earthing
→
→
The protective earth (PE) in the control panel should be connected from the
mains supply to a central earth point (mounting plate, system earth). The PE
conductor's cross-sectional area must be at least as large as that of the
incoming mains supply cable.
Every variable frequency drive must be individually connected to the power
supply system's protective earth directly at the location of installation (system earthing). This protective earth must not pass through any other devices.
When laying HF cables (e.g. shielded motor cables) or suppressed cables (e.g. mains supply cables, control circuit and signal cables) in parallel, a minimum clearance of 300 mm should
be ensured in order to prevent the radiation of electromagnetic
energy. You should also use separate cable entries if there is a
great difference in voltage potentials. Any necessary crossed
cabling between the control signal and power cables should
always be implemented at right angles (90 degrees).
Never lay control- or signal cables in the same duct as power
cables. Analog signal cables (measured, reference and correction values) must be screened.
3.3.2.1 Protective earth
All protective conductors should be routed in a star topology starting from
the central earth point, and all of the drive system's conductive components
(variable frequency drive, motor reactor, motor filter, main choke) should be
connected.
The earth-fault loop impedance must comply with all locally applicable industrial safety regulations. In order to meet UL requirements, UL-listed ring
cable lugs must be used for all earth wiring connections.
→
This refers to the legally required protective earth for a variable frequency
drive. An earthing terminal on the variable frequency drive, or the system
earth, must be connected to a neighboring steel element in the building
(beam, ceiling joist), an earth electrode in the ground, or a mains earth bus.
The earth points must meet the requirements set forth by the applicable
national and local industrial safety regulations and/or regulations for electrical
systems.
Avoid ground loops when installing multiple variable frequency
drives in one control panel. Make sure that all metallic devices
that
are to be grounded have a broad area connection with the
mounting plate.
54DA1 Variable Frequency Drives 10/12 MN04020005Z-EN www.eaton.com
Page 59
3.3.2.2 Motor earthing
EMC
L3
U
L2/N
L1/L
VAR
PH1
M3
20 mm (0.79")
EMC
VAR
The motor earth must be connected to one of the earthing terminals on the
variable frequency drive and to a neighboring steel element in the building
(beam, ceiling joist), an earth electrode in the ground, or a mains earth bus.
3.3.2.3 Earth-fault protection
A fault current to earth can be produced by variable frequency drives due to
their system characteristics. DA1 series variable frequency drives have been
designed in such a way that the smallest possible fault current will be produced in compliance with standards applicable worldwide. This fault current
must be monitored by a residual current device (RCD, type B).
3.3.3 EMC screw
3 Installation
3.3 E MC in st allat i on
Figure 30:EMC and VAR screws in a DA1
variable frequency drive with protection type IP20
NOTICE
The screw labeled EMC must not be manipulated as long as the
variable frequency drive is connected to the mains.
The EMC screw galvanically connects the EMC filter’s capaci-
→
tors to earth. The screw must be screwed in all the way to the
stop (factory setting) in order for the variable frequency drive to
comply with the EMC standard.
Due to their system characteristics, variable frequency drives with an internal
EMC filter will produce a larger fault current to earth than devices without a
filter. For applications in which this larger leakage current may cause malfunction messages or disconnections (residual current device), the EMC filter’s internal protective earth can be disconnected (remove the EMC screw
to do this). Local EMC regulations must be taken into account when doing
so. If necessary, a specific low-leakage-current EMC filter must be connected upstream.
DA1 Variable Frequency Drives 10/12 MN04020005Z-EN www.eaton.com55
Page 60
3 Installation
3.3 E MC in st allat i on
3.3.4 VAR screw
In connections to isolated power sources (IT networks), the EMC screw
should be removed. The earth fault monitors required for IT networks must
be suitable for operation with power electronic devices (IEC 61557-8).
DA1 series variable frequency drives are equipped with an overvoltage filter
for the input supply voltage that is designed to protect the devices from
noise pulses in the mains voltage. Pulse spikes are typically caused by lightning strikes or by switching operations in other high-power devices on the
same supply.
If high potential tests are performed on a system, these overvoltage protection components may cause the system to fail the test. In order to make it
possible to perform this type of hipot tests, the overvoltage protection components can be disconnected by removing the VAR screw. The screw must
be screwed back in after the high potential tests are performed and the test
must then be repeated. The system must then fail the test, indicating that
the overvoltage protection components have been reconnected.
3.3.5 Screen earth kit
NOTICE
The screw labeled VAR ( Figure 30, page 55) must not be
manipulated as long as the variable frequency drive is connected to the mains.
Cables that are not screened work like antennas (sending, receiving).
→
The effectiveness of the cable shield depends on a good shield connection
and a low shield resistance.
→
→
For a proper EMC connection, cables emitting interference (e.g.
motor cables) and susceptible cables (analog signal and measurement values) must be screened and laid separately from
each other.
Use only shields with tinned or nickel-plated copper braiding.
Braided steel shields are unsuitable.
Control and signal lines (analog, digital) should always be
grounded on one end, in the immediate vicinity of the supply
voltage source (PES).
56DA1 Variable Frequency Drives 10/12 MN04020005Z-EN www.eaton.com
Page 61
3 Installation
⏚
L1/L
L2/N
L3
DC-
⏚
U
DC+
BR
1 2 3 4 5 6 7 8 9 10 11 12 13
14 15 1617 18
COM
V
W
PE
W2
U2
V2
U1
V1
W1
PE
24 V DC
②
②
①
①
②
①
≧ 300 mm
(≧ 11.81“)
115/120 V AC
230/240 V AC
400 V AC
460/480 V AC
24 V DC
115/120 V AC
230/240 V AC
400 V AC
460/480 V AC
PES
15 mm
(0.59“)
PES
3.3 E MC in st allat i on
Figure 31:EMC-compliant surface mounting
a Power cable: mains voltage, motor connection, braking resistance
b Control and signal lines, fieldbus connections
Large-area connection of all metallic control panel components.
Mounting surfaces of variable frequency drive and cable screen must be free from paint.
Cable screen of cables at variable frequency drive’s output with earth potential (PES) across large surface
area
Large-area cable screen contacts with motor.
Large-area earth connection of all metallic parts.
DA1 Variable Frequency Drives 10/12 MN04020005Z-EN www.eaton.com57
Page 62
3 Installation
3.4 Electrical Installation
3.4 Electrical Installation
CAUTION
Carry out the wiring work only after the variable frequency drive
has been correctly mounted and secured.
DANGER
Electric shock hazard - risk of injuries!
Carry out wiring work only if the unit is de-energized.
NOTICE
Fire hazard!
Only use cables, protective switches, and contactors that feature the indicated permissible nominal current value.
NOTICE
In DA1 variable frequency drives, earth leakage currents are
greater than 3.5 mA (AC). According to product standard IEC/EN
61800-5-1, an additional equipment grounding conductor must
be connected, or the cross-section of the equipment grounding
2
conductor must be at least 10 mm
.
→
DANGER
The components in the variable frequency drive’s power section
remain energized up to five (5) minutes after the supply voltage
has been switched off (intermediate circuit capacitor discharging
time).
Pay attention to hazard warnings!
.
Complete the following steps with the specified tools and without using force.
58DA1 Variable Frequency Drives 10/12 MN04020005Z-EN www.eaton.com
Page 63
3.4.1 Power section connections
The connection to the power section is normally made via the connection
terminals:
•L1/L, L2/N, L3, PE for
The phase sequence does not matter.
•DC+, DC-, PE for DC voltage supplies
•U, V, W, PE for the input wiring to the motor
•BR, DC+ for an external braking resistance
⏚
⏚
3 Installation
3.4 Electrical Installation
the mains-side supply voltage.
L1/L
L1/L
L2/N
L2/N
L3
L3
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9
10
10
11
11
⏚
⏚
U
U
V
V
W
W
Figure 32:Connection in power section (schematic)
The number and the arrangement of the connection terminals used depend
on the variable frequency drive’s size and model.
NOTICE
The variable frequency drive must always be connected with
ground potential via a grounding conductor (PE).
DA1 Variable Frequency Drives 10/12 MN04020005Z-EN www.eaton.com59
Page 64
3 Installation
PE
A1
3.4 Electrical Installation
3.4.1.1 connection cables
PE
MainsMotorDC link, Brake Resistor
Figure 33:connection cables
Table 5:Stripping lengths in the power section
SizeA1
FS28 (0.3)
FS3
FS4
FS5
FS6
FS7
mm (in)
8 (0.3)
–
–
–
–
A1
PE
A1
Mains = Electrical supply system,
Motor = Motor connection,
DC-Link = Internal DC link,
Brake Resistor = Braking resistance
60DA1 Variable Frequency Drives 10/12 MN04020005Z-EN www.eaton.com
Page 65
3.4.1.2 Terminals in power section
DC-L1/LL2/NL3
⏚
LN
PE
DC-L1/LL2/NL3
L1L2PEL3
Table 6:Terminations
Frame
size
TerminationsDescription
3 Installation
3.4 Electrical Installation
FS2
FS3
FS4
FS5
FS6
FS7
PES
→
Connection with single-phase supply voltage:
• DA1-12… (230 V)
Connection with three-phase supply voltage:
• DA1-32… (230 V)
• DA1-34… (400 V, 480 V)
⏚
DC+BRUVW
R
B
M
3
Motor connection for three-phase motors:
• DA1-12… (230 V)
• DA1-32… (230 V)
• DA1-34… (400 V, 460 V)
optional: External braking resistance (R
B
In sizes FS2 and FS3, the DC+, DC-, and BR terminals are covered with plastic covers at the factory. They can be uncovered if
necessary.
)
3.4.1.3 connection cables
In all single-phase supply variable frequency drives terminal L3
is covered with a plastic cover. Do not uncover this terminal!
The screened cables between the variable frequency drive and the motor
should be as short as possible.
Connect the screening, on both sides and across a large area (360° over-
lap), to the protective earth (PE) . The power screening’s protective
earth (PES) connection should be in the immediate proximity of the variable frequency drive.and directly on the motor terminal box.
Prevent the screening from becoming unbraided, e.g. by pushing the
opened plastic sheath over the end of the screening or with a rubber
grommet on the end of the screening. As an alternative, in addition to a
broad area cable clip, you can also twist the shielding braid at the end
DA1 Variable Frequency Drives 10/12 MN04020005Z-EN www.eaton.com61
Page 66
3 Installation
3.4 Electrical Installation
and connect to protective ground with a cable clip. To prevent EMC disturbance, this twisted shielding connection should be made as short as
possible ( Figure 35).
15 mm
(0.59’’)
PES
Figure 34:Screened connection cable
Figure 35:Connection with twisted cable screen
Recommended value for twisted cable shielding:
b 1/5 a
Screened, four-wire cable is recommended for the motor cables. The greenyellow line of this cable connects the protective ground connections from the
motor and the variable frequency drive and therefore minimizes the equalizing current loads on the shielding braid.
62DA1 Variable Frequency Drives 10/12 MN04020005Z-EN www.eaton.com
Page 67
3 Installation
b
a
e
d
c
PH2
1 Nm
(8.85 lb-in)
3.4 Electrical Installation
The following figure shows the construction of a four-wire, screened motor
line (recommended specifications).
Figure 36: Four-core screened motor supply cable
a Cu shield braid
b PVC outer casing
c Drain wire (copper strands)
d PVC core insulation, 3 x black, 1 x green–yellow
e Textile and PVC fillers
If there are additional subassemblies in a motor feeder (such as motor contactors, overload relays, motor reactor, sinusoidal filters or terminals), the
shielding of the motor cable can be interrupted close to these subassemblies
and connected to the mounting plate (PES) with a large area connection.
Free or non-screened connection cables should not be any longer than about
300 mm.
3.4.1.4 Configuration and terminal capacities
The connection terminals’ layout depends on the size of the power section.
The cross-sections to be used in the connections and the tightening torques
for screws are listed in the following.
Table 7:Cross-sectional areas and tightening torques
M3
Sizemm
FS2 …
FS7
DA1 Variable Frequency Drives 10/12 MN04020005Z-EN www.eaton.com63
2
AWGMMinN/mMM
0.2 - 2.524 - 1280.310.50.6 x 3.5
Page 68
3 Installation
1 2 3 4 5 6 7 8 9 10 11
12 13
14 15 16
17 18
15 mm
(0.59’’)
PES
3.4 Electrical Installation
3.4.2 Connection on control section
The 13-terminal and 5-terminal strips have a plug-in design and are mounted
in the front.
Figure 37:Location of plug-in control signal terminals
The control cables should be screened and twisted. The screening is applied
on one side in the proximity of the variable frequency drive (PES).
→
Prevent the screening from becoming unbraided, i.e. by pushing
the separated plastic covering over the end of the shielding or
with a rubber grommet on the end of the screening.
Figure 38:Preventing the screening from becoming unbraided
Alternatively, in addition to the broad area cable clip, you can also twist the
shielding braid at the end and connect to the protective ground with a cable
lug. To prevent EMC disturbance, this twisted shielding connection should
be made as short as possible ( Figure 35, page 62).
64DA1 Variable Frequency Drives 10/12 MN04020005Z-EN www.eaton.com
Prevent the screen from becoming unbraided at the other end of the control
cable, e.g. by using a rubber grommet. The shield braid must not make any
connection with the protective ground here because this would cause problems with an interference loop.
Page 69
Figure 39:Example for an insulated end of the control cable
56
7
12
3
+10 V AI1
0 V
+24 V DI1
DI2
PE
PES
PES
M
4K7
R1
M
FWDREV
ZB4-102-KS1
15 mm
(0.59”)
M4
2
Cu 2.5 mm
1
2
3
≦ 20 m
(≦ 65.62 ft)
3.4.2.1 Arrangement and designation of the control signal terminals
ESD measures
Discharge yourself on a grounded surface before touching the
control signal terminals and the circuit board to prevent damage
through electrostatic discharge.
3 Installation
3.4 Electrical Installation
The following figure shows the layout and designations for the DA1 variable
frequency drive's control signal terminals.
1234567891011
+24
DI1
DI2
DI3
+10 V
AI11
0 V
AO1
Figure 40:Arrangement and factory designations for the control signal terminals
0 V
DI4
12
AO1
13
STO+
STO-
14
K11
15 16 17
K14
K12
K23
18
K24
DA1 Variable Frequency Drives 10/12 MN04020005Z-EN www.eaton.com65
Page 70
3 Installation
3.4 Electrical Installation
3.4.2.2 Functions of control signal terminals
The functions that are set in the ex-factory and the electrical connection data
of control signal terminals are listed in the following table.
Table 8:Factory-set functions of the control terminals
Terminal
SignalDescriptionDefault settings
1+24VControl voltage for DI1 - DI5,
output (+24 V)
2DI1
Digital input 18 - +30 V (High, Ri>6kΩ)Start enable FWD
3DI2Digital Input 28 - +30 V (High, Ri>6kΩ)Start enable REV
Maximum load 100 mA,
Reference potential 0 V
–
1)
1)
4DI3Digital Input 38 - +30 V (High, Ri>6kΩ)Fixed frequency FF1/FF2
5+10VReference voltage,
Output (+10 V)
6AI1
DI4
Analog input 1
Digital Input 5
Maximum load 10 mA
Reference potential 0 V
• Analog: 0 - +10 V (Ri>72kΩ)
0/4 - 20 mA (R
=500Ω)
B
–
Frequency reference value
Can be switched with parameter P2-30
• digital: 8 - 30 V (high)
70VReference potential0 V = connection terminal 9–
8AO1
DO1
Analog output 1
Digital output 1
• Analog: 0 - +10 V, maximum 20 mA
Can be switched with parameter P2-11
Output frequency
1)
• digital: 0 - +24 V
90VReference potential0 V = connection terminal 7–
10DI4
AI2
Digital Input 4
Analog input 2
• Analog: 0 - +10 V (Ri>72kΩ)
0/4 - 20 mA (R
=500Ω)
B
Fixed frequency FF2
1)
Can be switched with parameter P2-30
• digital: 8 - 30 V (high)
11AO2
DO2
Analog output 2
Digital output 2
• Analog: 0 - +10 V, maximum 20 mA
Can be switched with parameter P2-13
66DA1 Variable Frequency Drives 10/12 MN04020005Z-EN www.eaton.com
Page 71
3 Installation
2
DI1
FWD
+24 V
4
DI3
FF1/FF2
3
DI2
REV
10
DI4
(AI2)
FF2
1
+24 V Out
< 100 mA
6
AI1
(DI5)
CPU
8
AO1
(DO1)
f-Out
0...+10 V/20 mA
f-Soll
0...+10 V/20 mA
11
AO2
(DO2)
A-Out
0...+10 V/20 mA
3.4 Electrical Installation
The DA1 variable frequency drive has four control inputs (control signal terminals 2, 3, 4, 6 and 10). Three of these are permanently set as digital control
inputs; while the others can be set to work as digital or analog control inputs.
The variable frequency drive comes with the following default setting:
•Control signal terminal 2 as digital input 1 (DI1),
•Control signal terminal 3 as digital input 2 (DI2),
•Control signal terminal 4 as digital input 3 (DI3),
•Control signal terminal 6 as analog input 1 (AI1).
•Control signal terminal 10 as digital input 4 (DI4),
Control signal terminals 8 and 11 can be used as digital or analog outputs.
They are set up as analog outputs (AO) in the default configuration that
comes with the variable frequency drive when it is delivered.
Figure 41:Control signal terminals (digital / analog)
DA1 Variable Frequency Drives 10/12 MN04020005Z-EN www.eaton.com67
Page 72
3 Installation
3.4 Electrical Installation
3.4.2.3 Analog input signals
Depending on how parameters P1-12 and P1-13 are set, control signal terminals 6 (AI1) and 10 (AI2) can be connected to analog signals.
•0 - +10 V
•0 - 10 V with scaling and operating direction change
•0 - 20 mA
•4 - 20 mA or 20 - 4 mA with open-circuit monitoring (< 3 mA)
3.4.2.4 Analog output signal
An analog signal is available at control signal terminals 8 and 11. These outputs can handle a maximum load of 20 mA. The output signal is configured
using parameters P2-11 (AO1) and P2-13 (AO2) ( Table 10, Page 87).
Parameters P2-12 (AO1) and P2-14 (AO2) are used to configure the formats
for the analog inputs:
Parameter
value
0
110 - 0 V
20 - 20 mA
3
4
520 - 4 mA
→
→
The assignments between the values and functions are
described in Section 6.2.2, “Analog Input (AI)“, page136.
Control signal terminals 7 and 9 are the common 0 V reference
potential for all analog and digital input signals.
Configuration
0 - 10 V
20 - 0 mA
4 - 20 mA
AO
< 20 mA
OV
8
9
f-Out
0...+10 V
+
-
Figure 42:Analog output (AO) (connecting example)
Control signal terminals 7 and 9 are the common 0 V reference
→
68DA1 Variable Frequency Drives 10/12 MN04020005Z-EN www.eaton.com
potential for all analog and digital output signals.
Page 73
3.4.2.5 Digital Input Signals
Control signal terminals 2, 3, 4, 6 and 10 all have the same function and
mode of operation as digital inputs (DI1 to DI5).
A logic level of +24 V (positive logic) is used:
•8 - +30 V = High (logic “1“)
•0 - +4 V = Low (logic “0“)
The internal control voltage from control terminal 1 (+24 V, maximum
100 mA) or an external voltage source (+24 V) can be used for this.
The permissible residual ripple must be less than ±5 % U
The parameter configuration and the way functions are assigned are
described in Section 6.2.1, “Digital Input (DI)“, page135.
3 Installation
3.4 Electrical Installation
.
a/Ua
→
Control signal terminals 7 and 9 are the common 0 V reference
potential for all analog and digital input signals.
DA1 Variable Frequency Drives 10/12 MN04020005Z-EN www.eaton.com69
Page 74
3 Installation
3.4 Electrical Installation
3.4.2.6 Digital output (Transistor)
Control signal terminals 8 and 11 are set up as analog outputs (AO) in the
default configuration that comes with the variable frequency drive when it is
delivered. Parameters P2-11 and P2-13 ( Table 10, Page 87) can be used
to set them up as digital outputs (DO) instead.
Transistor outputs DO1 and DO2 can deliver a digital signal via control signal
terminals 8 and 11 using the device’s internal control voltage (+24 V). The
maximum permissible load current is 20 mA.
+ 24 V
< 20 mADOOV
89
Figure 43:Connection example (interposing relay with free-wheeling diode:
→
3.4.2.7 Digital Output (Relay)
Control signal terminals 14, 15 (N/O), and 16 (N/C) are connected to the DA1
variable frequency drive’s internal relay 1 in a potential-free manner.
Control signal terminals 17 and 18 are connected to internal relay 2 (N/O) in a
potential-free manner.
The relay function can be configured using parameters P2-15 and P2-18
( Table 10, Page 87).
The electrical connection specifications for control signal terminals are:
•250 V AC, max. 6 A
•30 V DC, max. 5 A
+
ETS4-VS3; article no. 083094)
Control signal terminals 7 and 9 are the common 0 V reference
potential for all analog and digital output signals.
We recommend connecting any connected loads as follows:
70DA1 Variable Frequency Drives 10/12 MN04020005Z-EN www.eaton.com
Page 75
250 V ∼ : ≦ 6A
Error
RUN
16 17 1814 15
I
AC
DC
AC
Varistor
(+)
(
-
)
DC
Diode
AC
RC filter
30 V ⎓ : ≦ 5A
Figure 44:Connection examples with suppressor circuit
3 Installation
3.4 Electrical Installation
3.4.2.8 RJ 45 interface
The RJ45 port located on the bottom part of the DA1 variable frequency drive
makes it possible to connect directly to communication modules and fieldbus
connections.
The internal RS485 connection handles transmissions for the OP bus,
Modbus RTU, and CANopen field bus systems.
⏚
DC-
L1/L
L2/N
L3
PIN 8
(PIN2)
PIN 7
(PIN 1)
Figure 45:RJ45 port on DA1 variable frequency drive
X1
RS485
RJ45
1 2 3 4 5 6 7 8 9 10 11 12 13
COM
⏚
14 15 16 17 18
DC+
BR
U
V
W
→
nation resistor.
Use DX-CBL-TERM if necessary.
DA1 Variable Frequency Drives 10/12 MN04020005Z-EN www.eaton.com71
DA1 variable frequency drives do not have an internal bus termi-
Page 76
3 Installation
⏚
⏚
DC+
BR
DC-
3 AC 230 V
WVU
M
3 ~
13
STO-
1
+24 V Out
< 100 mA
24 V
2
DI1
FWD
REV
FF1/FF2
FF2
3
DI2
4
DI310DI4
AI2
12
STO+
L1/L
EMC
5
+10 V Out
< 10 mA
6
AI1
DI5
0 V
7
L2/N
VAR
CPUSTO
10 V
0 V
f-Soll
1 AC 230 V
50/60 Hz
PES
X1
①
+
-
1516
Error
RUN
17188
14
911
6 A, 250 V AC
5 A, 30 V DC
6 A, 250 V AC
5 A, 30 V DC
A-Out
0 V0 V
f-Out
+24 V DO
+24 V DO
PIN 8
(PIN2)
PIN 7
(PIN 1)
RS485
3.4 Electrical Installation
3.4.3 Block diagrams
3.4.3.1 DA1-12…
The following block diagrams show all the connection terminals on a DA1
variable frequency drive and their functions when in their default settings.
Figure 46:DA1-12… block diagram
Variable frequency drive with
phase motor connection
72DA1 Variable Frequency Drives 10/12 MN04020005Z-EN www.eaton.com
External braking resistors can be connected to devices of size FS2 to
FS8
.
single-phase supply system voltage and three-
Page 77
3.4.3.2 DA1-32…, DA1-34…
⏚
⏚
DC+
BR
DC-
WVU
M
3 ~
13
STO-
1
+24 V Out
< 100 mA
24 V
2
DI1
FWD
REV
FF1/FF2
FF2
3
DI2
4
DI310DI4
AI2
12
STO+
EMC
5
+10 V Out
< 10 mA
6
AI1
DI5
0 V
PIN 8
(PIN 2)
PIN 7
(PIN 1)
7
VAR
RS485
CPU
STO
10 V
0 V
f-Soll
PES
X1
①
+
-
1516
Error
RUN
17188
14
911
6 A, 250 V AC
5 A, 30 V DC
6 A, 250 V AC
5 A, 30 V DC
A-Out
0 V0 V
f-Out
L1/L
L3
L2/N
3 AC 230 V
3 AC 400/480 V
50/60 Hz
+24 V DO
+24 V DO
3 Installation
3.4 Electrical Installation
Figure 47:DA1-32…, DA1-34… block diagram
Variable frequency drive
motor connection
External braking resistors can be connected to devices of size FS2 to
.
FS8
DA1 Variable Frequency Drives 10/12 MN04020005Z-EN www.eaton.com73
with three-phase mains supply voltage and three-phase
Page 78
3 Installation
3.4 Electrical Installation
3.4.4 Insulation test
The variable frequency drive of the DA1 series are tested, delivered and
require no additional testing.
CAUTION
If insulation testing is required in the power circuit of the PDS, you must consider the following measures.
3.4.4.1 Testing the motor cable insulation
Disconnect the motor cable from the connection terminals U, V and W of
the variable frequency drive and from the motor (U, V, W). Measure the
insulation resistance of the motor cable between the individual phase
conductors and between the phase conductor and the protective conductor.
The insulation resistance must be greater than 1 M.
On the control signal and the connection terminals of the variable frequency drive, no leakage resistance tests are to be performed with an insulation tester.
CAUTION
Wait at least 5 minutes after switching the supply voltage off
before you disconnect one of the connection terminals (L1/L,
L2/N, L3, DC-, DC+, BR) of the variable frequency drive.
3.4.4.2 Testing the mains cable insulation
Disconnect the power cable from the mains supply network and from
the connection terminals 1/L, L2/N and L3 of the variable frequency
drive. Measure the insulation resistance of the mains cable between the
individual phase conductors and between each phase conductor and the
protective conductor.
The insulation resistance must be greater than 1 M.
3.4.4.3 Testing the motor insulation
Disconnect the motor cable from the motor (U, V, W) and open the
bridge circuits (star or delta) in the motor terminal box.
Measure the insulation resistance of the individual motor windings. The
measurement voltage must at least match the rated operating voltage of
the motor but is not to exceed 1000 V.
The insulation resistance must be greater than 1 M.
→
Consider the notes from the motor manufacturer in testing the
insulation resistance.
74DA1 Variable Frequency Drives 10/12 MN04020005Z-EN www.eaton.com
Page 79
4 Operation
4.1 Checklist for commissioning
Before placing the variable frequency drive into operation, use the checklist
below to make sure that all the following requirements are met:
No.Activity Notes
4 Operation
4.1 Checklist for commissioning
1
2
3
4
5
6
7
8
9
10
11
12
13
Mounting and wiring have been carried out in accordance
with the corresponding instructional leaflet (
IL04020015Z, IL04020011Z, IL04020012Z, IL04020010Z).
All wiring and line section leftovers, as well as all the tools
used, have been removed from the variable frequency
drive’s proximity.
All terminals in the power section and in the control section
were tightened with the specified torque.
The lines connected to the output terminals (U, V, W, DC+,
DC-, BR) of the variable frequency drive are not short-circuited and are not connected to ground (PE).
The variable frequency drive has been earthed properly
(PE).
All electrical terminals in the power section (L1/L, L2/N, L3,
U, V, W, DC+, DC-, BR, PE) were implemented properly
and were designed in line with the corresponding requirements.
Each single phase of the supply voltage (L or L1, L2, L3) is
protected with a fuse.
The variable frequency drive and the motor are adapted to
the mains voltage.
( Section 1.4.1, “Rating data on the nameplate“,
page13, connection type (star, delta) of the motor tested).
The quality and volume of cooling air are in line with the
environmental conditions required for the variable frequency drive and the motor.
All connected control cables comply with the corresponding stop conditions (e.g., switch in OFF position and setpoint value= zero).
The parameters that were preset at the factory have been
checked with the list of parameters ( Table 10, page 87).
The effective direction of a coupled machine will allow the
motor to start.
All emergency switching off functions and safety functions
are in an appropriate condition.
DA1 Variable Frequency Drives 10/12 MN04020005Z-EN www.eaton.com75
Page 80
4 Operation
4.2 Hazard warnings for operation
4.2 Hazard warnings for operation
Please observe the following notes.
DANGER
Commissioning is only to be completed by qualified technicians.
DANGER
Hazardous voltage!
The safety instructions on pages I and II must be followed.
DANGER
The components in the variable frequency drive’s power section
are energized if the supply voltage (mains voltage) is connected.
For instance: L1/L, L2/N, L3, DC+, DC-, BR, U/T1, V/T2, W/T3
power terminals.
The control signal terminals are isolated from the line power
potential.
There can be a dangerous voltage on the relay terminals (10, 11)
even if the variable frequency drive is not being supplied with
mains voltage (e.g., integration of relay contacts in control systems with voltage > 48 V AC / 60 V DC).
DANGER
The components in the variable frequency drive’s power section
remain energized up to five (5) minutes after the supply voltage
has been switched off (intermediate circuit capacitor discharging time).
Pay attention to hazard warnings!
DANGER
Following a shutdown (fault, mains voltage off), the motor can
start automatically (when the supply voltage is switched back
on) if the automatic restart function has been enabled (
parameters P2-36).
76DA1 Variable Frequency Drives 10/12 MN04020005Z-EN www.eaton.com
Page 81
4 Operation
4.3 Commissioning with control signal terminals (default settings)
NOTICE
Any contactors and switchgear on the power side are not to be
opened during motor operation. Inching operation using the
power switch is not permitted.
Contactors and switchgear (repair and maintenance switches)
on the motor side must not be opened while the motor is in
operation.
Inching operation of the motor with contactors and switchgear
in the output of the variable frequency drive is not permitted.
NOTICE
Make sure that there is no danger in starting the motor. Disconnect the driven machine if there is a danger in an incorrect operating state.
→
If motors are to be operated with frequencies higher than the
standard 50 or 60 Hz, then these operating ranges must be
approved by the motor manufacturer. The motors could be damaged otherwise.
4.3 Commissioning with control signal terminals (default settings)
DA1 variable frequency drives are set in the factory and can be started
directly via the control signal terminals by connecting the motor outputs allocated for the mains voltage (see connection example below).
→
Following are a series of simplified connecting examples that use the default
settings.
You can skip this section if you want to set up the parameters
directly for optimal operation of the variable frequency drive
based on the motor data (rating plate) and the application.
DA1 Variable Frequency Drives 10/12 MN04020005Z-EN www.eaton.com77
Page 82
4 Operation
PE
PE
WVU
M
3 ~
675
123
+24 V
FWD
0...+10 V
0 V
+10 V
L3
L1/L
L2/N
L
N
L3L1
L2
REV
f-Soll
12
13
STO+
STO-
4.3 Commissioning with control signal terminals (default settings)
Connecting example for three-phase motor
Connecting example for three-phase motorTerminaldesignation
L1/LSingle-phase power supply
L2/N
L3–
Ground connection
1Control voltage +24 V (output, maximum 100 mA)
2FWD, Start release clockwise rotating field
3REV, Start release left rotating field
UConnection for three-phase ac motor
V
W
5Setpoint value voltage +10 V (Output, maximum 10 mA)
6Frequency reference value f-Set (Input 0 – +10 V)
7Reference potential (0 V)
12Safe Torque Off +
13Safe Torque Off -
connection
(DA1-12…)
(three-phase motor)
Three-phase power supply
connection
(DA1-32…, DA1-34…)
Connect the variable frequency drive according to the connecting exam-
ple above for the simple commissioning with the specified default settings (see connecting example above).
The potentiometer should have a fixed resistance (connection to control signal terminals 5 and 7) of at least 1 k, up to a maximum of 10 k. A standard
fixed resistance of 4.7 k is recommended.
Make sure that the enable contacts (FWD/REV) are open and the STO is connected correctly before switching on the mains voltage.
If the connections for the setpoint value potentiometer cannot
→
be clearly allocated with terminals 5, 6 and 7, you should set the
potentiometer to about 50 % before giving the start release
(FWD/REV) for the first time.
When the specified supply voltage is applied at the mains connection terminals (L1/L, L2/N, L3), the switched-mode power supply unit (SMPS) in the
internal DC link will be used to generate the control voltage and light up the
78DA1 Variable Frequency Drives 10/12 MN04020005Z-EN www.eaton.com
7-segment LED display (STOP).
At this point, the variable frequency drive will be ready for operation (correct
operating status) and in Stop mode.
Page 83
4 Operation
4.3 Commissioning with control signal terminals (default settings)
The start release is done by actuating one of the digital inputs with +24 V:
•Terminal 2: FWD = Clockwise rotating field (Forward Run)
•Terminal 3: REV = Counterclockwise rotating field (Reverse Run)
The FWD and REV control commands are interlocked (exclusive OR) and
require a rising voltage edge.
The frequency is shown with a minus sign with a start release with a left
rotating field (REV).
You can now set the output frequency (0 - 50 Hz) and, as a result, the
speed of the connected three-phase motor (0 - n
potentiometer via terminal 6 (0 - +10 V proportional voltage signal). The
change in output frequency here is delayed based on the specified accel-
In
eration and deceleration ramps.
the default settings, these times are
set to 5 seconds and to 10 seconds from a frame size FS4.
The acceleration and deceleration ramps specify the time change for the output frequency: from 0 to f
(WE = 50 Hz) or from f
max
) by using the
Motor
back to 0.
max
Figure48 shows a good example of the process, if the release signal (FWD/
REV) is switched on and the maximum setpoint voltage (+10 V) is applied.
The speed of the motor follows the output frequency depending on the load
and moment of inertia (slip), from zero to n
max
.
If the release signal (FWD, REV) is switched off during operation, the inverter
is blocked immediately (STOP). The motor comes to an uncontrolled stop
(see in Figure48). The acceleration time is set in parameter P1-03.
FWD
REV
+24 V
t
RUNSTOP
f
= 50 Hz
P1-07
f
~ n
max
max
①
0
P1-03
Figure 48:Start-Stop command with maximum setpoint value voltage
DA1 Variable Frequency Drives 10/12 MN04020005Z-EN www.eaton.com79
t
Page 84
4 Operation
4.3 Commissioning with control signal terminals (default settings)
80DA1 Variable Frequency Drives 10/12 MN04020005Z-EN www.eaton.com
Page 85
5 Error messages
5.1 Introduction
DA1 series variable frequency drives come with several internal monitoring
functions. When a deviation from the correct operating state is detected, an
error message will be displayed; in the inverter’s default settings, the relay
contact will open (control signal terminals 14 and 15).
5.1.1 Error messages
The most recent four error messages will be stored in the order in which
they occurred (with the most recent one in the first place). Error messages
can be read from parameter P0-13 and the P0-... monitor values.
5.1.2 Acknowledge fault (Reset)
To acknowledge and reset the current error message, you can either switch
off the supply voltage or press the STOP pushbutton.
5 Error messages
5.1 Introduction
5.1.2.1 Fault log
The fault log (P0-13) stores the most recent four error messages in the order
in which they occurred. The most recent error message will always be
shown as the first value when P0-13 is accessed. To see the remaining error
messages one after the other, press the (Up) button. Their order will be
indicated by means of flashing dots in the 7-segment digital display assembly.
→
To get more information regarding the fault, go to the “Monitor“
menu (P0-…).
The values in the fault log (P0-13) will not be deleted if the variable frequency drive is reset to its default settings!
DA1 Variable Frequency Drives 10/12 MN04020005Z-EN www.eaton.com81
Page 86
5 Error messages
5.1 Introduction
The example below shows how to access the fault log.
IndicatorExplanation
Operating state Stop
Press OK button
The parameter that was last accessed will be shown.
The last digit on the display will flash.
Use the ▲ (Up) or ▼ (Down) arrow key to select parameter P1-14
and confirm your selection by pressing the OK pushbutton.
The last digit on the display will flash.
Use the ▲ (Up) or ▼ (Down) arrow key to set a parameter value of 101
or 201 and confirm your selection by pressing the OK pushbutton.
Use the ▲ (Up) or ▼ (Down) arrow keys to select parameter P0-13 and
confirm your selection by pressing the OK pushbutton.
The last digit on the display will flash.
Use the arrow button ▲ (Up) to go to the next error message.
Second most recent error message:
Example: V-Volt (undervoltage message). The dot on the right will
flash.
The third most recent error message will be shown after pressing
the ▲ arrow key (Up).
Example: E-trip (external error message)
The two dots on the right will flash.
The oldest error message will be shown after you press the ▲ arrow key
(Up) once more.
Example: V-Volt (undervoltage message)
The three dots on the right will flash.
82DA1 Variable Frequency Drives 10/12 MN04020005Z-EN www.eaton.com
Page 87
5 Error messages
5.1 Introduction
5.1.3 Error list
The following table lists the failure codes, the possible causes and indicates
corrective measures.
Table 9:Error messages list
Indicator
no-Flt00no error ––
0I-b01Overcurrent braking resis-
OL-br
0- I03Overcurrent motor• Overcurrent at output
I .t-trP
SAFE-I
Ovolts06Overvoltage DC linkOvervoltage at DC linkPower supply problem
V-volts
O-t08OvertemperatureHeat sink overtemperatureCheck the variable frequency drive's ambient air
V-t09Excessively low tempera-
Fault CodeDesignationPossible causeNotes
Brake chopper overcurrentOvercurrent in braking resistor circuit
tance
02Braking resistor thermal
overload
04Thermal motor overloadThe DA1 variable frequency drive
05Safe Torque Off faultPower supply at STO input inter-
07DC link undervoltageDC link undervoltageNormally occurs if the power is switched off.
ture (frost)
Braking resistance overloadIncrease the deceleration time (P1-04), reduce the
• Motor overload
• Overtemperature at heat sink
was switched off after more than
100 % of the value set in P1-08
was delivered for a period of time.
rupted
Heat sink undertemperatureThe variable frequency drive will be switched off if
Check the wiring to the braking resistance.
Check the brake resistor value (P6-19). Make sure
that the minimum resistance values are being
adhered to.
load's moment of inertia, or connect additional
braking resistors in parallel.
Make sure that the minimum resistance values are
being adhered to.
Motor with constant speed: Determine the overload or fault.
Motor starts: The load stalled or has seized, or the
brake is not open.
Check whether there is a star/delta motor wiring
error.
Motor accelerates/decelerates: The excessively
short acceleration/deceleration time is requiring
too much power.
If P1-03 or P1-04 cannot be increased, a more
powerful variable frequency drive is required.
Cable fault between variable frequency drive and
motor.
Check whether the decimal places are flashing
(variable frequency drive overloaded) and either
raise the acceleration ramp (P1-03) or reduce the
motor load.
Make sure that the cable length matches the variable frequency drive specifications.
Check the load mechanically in order to make sure
that it is free, that nothing is getting jammed or
locked, and there are no other mechanical faults.
Increase the deceleration ramp time P-04.
If it occurs during running, check the power supply
voltage.
temperature. Check whether additional clearance
or cooling is required.
the ambient temperature < -10 °C. Raise the
temperature over -10 °C in order to start the variable frequency drive.
DA1 Variable Frequency Drives 10/12 MN04020005Z-EN www.eaton.com83
E-triP11External faultExternal shutdown (on digital
SC-ObS
FLt-dc
P-LoSS
h0-I
th-Flt16Thermistor faultDefective thermistor on heat sinkPlease contact your closest Eaton representative.
dAtA-F17Data errorInternal memory errorParameter not stored; default settings loaded back.
4-20F
dAtA-E
V- dEF
F-Ptc21Motor thermistor faultDefective thermistor in motorReduce the load on the motor.
FAn-F
O-hEAt
O- tor9
V- tor9
OVt- F
SAFE- 229Safe Torque Off faultPower supply at STO input inter-
12Communication faultCommunication loss errorCheck the communications connection between
13Large residual ripple in DC
link
14Mains connection phase
fault
15Instantaneous motor over-
current
18Live zero errorAnalog input current outside rangeMake sure that the input current falls within the
19Data errorInternal memory errorParameter not stored; default settings loaded back.
20User parameter default
22Internal fan faultInternal fan faultCheck the internal fan and replace if necessary.
23Excessively high ambient
temperature
24Torque exceededTorque has exceeded the limit
25Torque fallen belowExcessively low torqueOnly visible if hoisting mode (P2-18 = 8) is enabled.
26Output faultFault at variable frequency drive
has been loaded.
input 3)
Excessively large residual ripple in
DC link
Shutdown caused by input phase
loss
Excessively high ambient temperature
value
output
rupted
Press the STOP pushbutton.
The DA1 variable frequency drive is ready for an
application-specific configuration.
External safety shutdown on digital input 3.
The normally-closed contact opened for some
reason.
If a motor thermistor is connected, check whether
the motor is too hot.
the variable frequency drive and external devices.
Make sure that each individual variable frequency
drive on the network has a unique address.
Check to make sure that all three phases are
present and have a voltage tolerance of less than
3%.
Reduce the motor load
A variable frequency drive intended for use with a
three-phase power supply has lost one of its input
phases.
If the problem occurs again, please contact your
closest Eaton representative.
range defined by P-16.
If the problem occurs again, please contact your
closest Eaton representative.
Make sure that the internal fan is working.
Reduce the pulse frequency (P2-24).
Reduce the load on the motor.
Make sure that hot air is not flowing into the variable frequency drive from surrounding devices.
Reduce the load on the motor.
Increase the acceleration time (P2-03).
Check the brake settings in the variable frequency
drive.
84DA1 Variable Frequency Drives 10/12 MN04020005Z-EN www.eaton.com
Page 89
IndicatorFault CodeDesignationPossible causeNotes
5 Error messages
5.1 Introduction
Enc- 0130Encoder feedback error
Enc- 02
Enc- 0332Incorrect PPRs configured
Enc- 0433Channel A faultChannel A is faulty.
Enc- 0534Channel B faultChannel B is faulty.
Enc- 0635Channel A and B fault Channels A and b are faulty.
AtF- 0140Auto-tune errorWinding resistance errorThe winding resistance varies between the indi-
AtF- 0241Winding resistance errorThe winding resistance is too high.
AtF- 03
AtF- 04
AtF- 05
Out- Ph
Sc- t01
Sc- t02
Sc- t0352Plug-in module (field bus)
Sc- t04
31Speed errorThe difference between the measured speed and
42Motor inductance errorThe motor inductance is too low.
43Motor inductance errorThe motor inductance is too high.
44Motor data errorThe measured motor data does not match.
49Motor connection phase
50Modbus communications
51Communication fault
53I/O plug-in module commu-
(visible only if the DXAEXT-ENCOD encoder
module is plugged in and
fastened)
fault
error
CANopen
communications error
nications error
Communication faultCommunications and data errors
the calculated speed in the variable frequency
drive is too large.
vidual windings.
Check the motor's wiring.
Check the motor’s wiring.
Use the motor output to check whether the motor
and the variable frequency drive are compatible.
Check the motor’s wiring.
Check the motor’s wiring.
Use the motor output to check whether the motor
and the variable frequency drive are compatible.
Check the motor’s wiring.
Use the motor output to check whether the motor
and the variable frequency drive are compatible.
Motor phase faultAn output phase is not connected to the motor.
Check the motor’s wiring.
Use the motor output to check whether the motor
and the variable frequency drive are compatible.
Increase P5-06 to an appropriate value.
Check whether the PLC is still running.
Check the cable connections.
A CANopen frame was not
received within the time set in
P5-06.
Internal loss of communications
between variable frequency drive
and optional module
Internal loss of communications
between variable frequency drive
and optional module
Increase P5-06 to an appropriate value.
Check whether the PLC is still running.
Check the cable connections.
Check to make sure that the module is plugged in
correctly.
Check to make sure that the module is plugged in
correctly.
DA1 Variable Frequency Drives 10/12 MN04020005Z-EN www.eaton.com85
Page 90
5 Error messages
5.1 Introduction
86DA1 Variable Frequency Drives 10/12 MN04020005Z-EN www.eaton.com
Page 91
6 Parameters
6 Parameters
→
parameter P1-14 must be set to 201 for access to all parameters.
Table 10:Description list for DA1 parameters
PNUIDAccess rightValueDescriptionDS
RUNro/rw
Parameter group P1 – quick-start
P1-01129✓rwMaximum frequency / maximum speed50.0
P1-10 = 0 → P1-02 - 5 x P1-09 → Hz
P1-10 > 0 → P1-02 - 5 x P1-09 x 60 s → rpm
The maximum output frequency / motor speed limit in Hz or
rpm. If P-10 > 0, the value entered / displayed will be shown in
rpm.
P1-02102✓rwMinimum frequency / minimum speed0
P1-10 = 0 → 0-P1-01→ Hz
P1-10 > 0 → 0 - P1-01 → rpm
The minimum output frequency / minimum speed limit in Hz or
rpm. If P-10 > 0, the value entered / displayed will be shown in
rpm.
P1-03103✓rwAcceleration time (acc1)5 (10 from
FS4)
0.1 - 600 s
When first switching on or after activating the default settings
P1-04104✓rwDeceleration time (dec1)5 (10 from
0.1 - 600 s
P1-05✓rwStop Function1
0Ramp, deceleration =
Regenerative braking. Deceleration time with the value set
under P1-04 (dec1).
If the energy that is fed back by the motor during the dynamic
braking is too high, the deceleration time has to be extended.
In devices with an internal braking transistor, the excess
energy can be dissipated with an external braking resistance
(optional)
1Free coasting =
After the start enable (FWD/REV) is switched off
or the STOP pushbutton is pressed (P1-12 and P1-13), the motor
will coast uncontrolled.
2Ramp, quick stop = regenerative braking.
Deceleration time 2 with the value set under P2-25 (dec2).
If the energy that is fed back by the motor during the dynamic
braking is too high, the deceleration time has to be extended.
In devices with an internal braking transistor, the excess
energy can be dissipated with an external braking resistor
(optional).
FS4)
DA1 Variable Frequency Drives 10/12 MN04020005Z-EN www.eaton.com87
Page 92
6 Parameters
PNUIDAccess rightValueDescriptionDS
RUNro/rw
3Free coasting, with activated braking chopper =
After the start enable (FWD/REV) is switched off
or the STOP pushbutton is pressed (P1-12 and P1-13), the motor
will coast uncontrolled.
If the energy that is fed back by the motor during the dynamic
braking is too high, the deceleration time has to be extended.
In devices with an internal braking transistor, the excess
energy can be dissipated with an external braking resistor
(optional).
P1-06106✓rwEnergy optimization0
0Deactivated
1Activated
If it is selected, the energy optimization function will attempt
to reduce the total energy consumed by the variable frequency
drive and the motor during operation at constant speeds and
with light loads. The output voltage applied at the motor will be
reduced. The energy optimization function is intended for applications in which the variable frequency drive is run for specific
periods at a constant speed and with a light load, independently of whether the torque is constant or varies.
P1-07107–rwNominal voltage of the motor230
Setting range: 0. 20 - 250 / 500 V (→ Motor ratings plate)
Pay attention to the supply voltage and the type of circuit in the
stator winding!
Note:
This parameter value has a direct influence on the V/f characteristic curve (e.g. operation with 87 Hz characteristic curve).
This must be especially taken into account in the case of values
(P1-07) that deviate from the variable frequency drive’s rated
operational data (U
= 100 %). This may cause the over-exci-
LN
tation of the motor and thus lead to an increased thermal load.
P1-08
108–rwRated motor current4.8
Setting range: 0.2 x Ie - Ie [A] (→ Motor rating plate)
I
= Variable frequency drive’s rated operational current
e
P1-09109–rwNominal frequency of the motor50.0
Setting range: 25 - 500 Hz (→ Motor rating plate)
1)
1)
1)
Note:
This parameter value is also automatically applied as the cutoff frequency for the V/Hz characteristic curve.
88DA1 Variable Frequency Drives 10/12 MN04020005Z-EN www.eaton.com
Page 93
6 Parameters
PNUIDAccess rightValueDescriptionDS
RUNro/rw
P1-10110✓rwNominal speed of the motor0
0 - 30000 rpm (→ motor rating plate)
Note:
This parameter can be optionally set to the motor’s rated speed
(revolutions per minute, rating plate). If it is set to the factory
default setting of 0, all speed-related parameters will be
shown in Hz; slip compensation for the motor will be disabled.
Entering the value on the motor's rating plate will enable the
slip compensation function, and the variable frequency drive's
display will show the motor speed in the estimated rpm.
All speed-related parameters (such as the minimum and
maximum frequencies and the fixed frequencies) will also be
shown in rpm.
P1-11111–rwOutput voltage at zero frequency3.0
0.00 - 20.0 %
Voltage amplification is used in order to increase the motor
voltage applied at low output frequencies so as to improve the
torque at low speeds, as well as the starting torque.
P1-12
Note:
A high start voltage enables a high torque at the start.
Notice:
A high torque at low speed causes a high thermal load on the
motor. If temperatures are too high, the motor should be
equipped with an external fan.
140–rwControl level0
0Control signal terminals (I/O)
The variable frequency drive will respond directly to signals
applied to the control signal terminals.
1Keypad (KEYPAD FWD)
The variable frequency drive can only be controlled in the
forward direction if an external or remote control keypad is
used.
2Keypad (KEYPAD FWD/REV)
The variable frequency drive can be controlled in both the
forward and reverse directions by using an external or remote
control keypad. Pressing the START pushbutton will toggle
between the forward and reverse directions.
3PID controller
The output frequency will be controlled by the internal PID
controller.
4Field bus
Control via Modbus RTU (RS485) interface or optional fieldbus
connection (e.g., PROFIBUS DP).
5Slave mode
The variable frequency drive will run in slave mode; in this
mode, the output frequency will depend on the master variable
frequency drive and can only be changed there. The variable
frequency drives are connected to each other using the variable
frequency drive's RJ45 interface.
6Field bus (CANopen) via RJ45 interface
DA1 Variable Frequency Drives 10/12 MN04020005Z-EN www.eaton.com89
Page 94
6 Parameters
PNU
P1-13113–roDigital input (analog input) function
P1-14114✓rwParameter range access code 0
Extended parameter range Level 2 (access: P1-14 = 101 or P1-14 = 201)
Parameter group P2 - functions
P2-01
P2-02
P2-03
IDAccess rightValueDescriptionDS
RUNro/rw
(Depends on P2-40 or P6-30 Extended parameter access code)
Set the value to 101 (default setting) to enable access to the
extended parameter menu. Modify via P2-40.
To enable access to all parameters, set the value to 201.
Change using P6-30.
0.00 Hz (P1-02) up to the maximum frequency value (P1-01).
Activation via digital inputs depending on parameters P1-12
and P1-13 according to the "Input value DA1" table.
The skip frequency function is used to prevent the variable
frequency drive from being run at a specific output frequency,
e.g. at a frequency that will cause mechanical resonance in a
specific machine.
Parameter P2-10 is used to define the center of the skip
frequency band and is used together with parameter P2-09. The
output frequency will run through the specified band at the
speeds set in P1-03 or P1-04 without holding an output
frequency that falls within the defined band. If the frequency
reference value applied to the variable frequency drive falls
within the band, the output frequency will remain at the upper
or lower limit of the band.
DA1 Variable Frequency Drives 10/12 MN04020005Z-EN www.eaton.com91
Page 96
6 Parameters
PNUIDAccess rightValueDescriptionDS
RUNro/rw
P2-11211✓rwAO1 signal8
Digital output → +24 V DC
0RUN, enable (FWD, REV)
1READY, ready for operation
2Output frequency = frequency reference value
3Output frequency > zero speed
4Output frequency closing threshold > P2-16
Switch off threshold < P2-17
5Output current closing threshold > P2-16
6Output torque closing threshold > P2-16
7AI2 signal level closing threshold > P2-16
8Output frequency f-Out → 0 - 100 % f
9Output current → 0 - 200 % Ie (P1-08)
10Torque MN → 0 - 200 % (calculated value)
11Output power PN → 0 - 150 % (Ie)
P2-12212✓rwAO1, signal rangeA0-10
A0-100 - 10 V
A10-010 - 0 V
A0-200 - 20 mA
A20-020 - 0 mA
A4-204 - 20 mA
A20-420 - 4 mA
Switch off threshold < P2-17
Switch off threshold < P2-17
Switch off threshold < P2-17
Analog output → P2-12
max
(P1-01)
92DA1 Variable Frequency Drives 10/12 MN04020005Z-EN www.eaton.com
Page 97
6 Parameters
PNUIDAccess rightValueDescriptionDS
RUNro/rw
P2-13213✓rwAO1 signal9
Digital output → +24 V DC
0RUN, enable (FWD, REV)
1READY, ready for operation
2Output frequency = frequency reference value
3Output frequency > zero speed
4Output frequency closing threshold > P2-19
Switch off threshold < P2-20
5Output current closing threshold > P2-19
6Output torque closing threshold > P2-19
7AI2 signal level closing threshold > P2-19
8Output frequency f-Out → 0 - 100 % f
9Output current → 0 - 200 % Ie (P1-08)
10Torque MN → 0 - 200 % (calculated value)
11Output power PN → 0 - 150 % (Ie)
P2-14214✓rwAO1, signal rangeA0-10
A0-100 - 10 V
A10-010 - 0 V
A0-200 - 20 mA
A20-020 - 0 mA
A4-204 - 20 mA
A20-420 - 4 mA
Switch off threshold < P2-20
Switch off threshold < P2-20
Switch off threshold < P2-20
Analog output → 0 - 10 V DC
max
(P1-01)
DA1 Variable Frequency Drives 10/12 MN04020005Z-EN www.eaton.com93
Page 98
6 Parameters
PNUIDAccess rightValueDescriptionDS
RUNro/rw
P2-15215✓rwK1 signal (Relay Output 1)1
Used to select the function assigned to the relay output. The
relay has three output terminals (changeover contacts): Logic 1
indicates that the relay is active: This is why terminals 14 and
15 are connected to each other.
0RUN, enable (FWD, REV)
1READY, ready for operation
2Output frequency = frequency reference value
3Output frequency > 0 Hz
4Output Frequency
Closing threshold > P2-16
Switch off threshold < P2-17
5Output current
Closing threshold > P2-16
Switch off threshold < P2-17
6Output torque (calculated value)
7Analog Input (AI2)
P2-16216✓rwAO1 / K1 upper limit100.0
P2-17217✓rwAO1 / K1 lower limit0.0
Closing threshold > P2-16
Switch off threshold < P2-17
Closing threshold > P2-16
Switch off threshold < P2-17
The adjustable upper limit value that is being used in connection with settings 4 to 7 of P2-11 and P2-15
0.0 - 200.0 %
The adjustable lower limit value that is being used in connection with settings 4 to 7 of P2-11 and P2-15
0.0 - 200.0 %
94DA1 Variable Frequency Drives 10/12 MN04020005Z-EN www.eaton.com
Page 99
6 Parameters
PNUIDAccess rightValueDescriptionDS
RUNro/rw
P2-18218✓rwK2 signal (Relay Output 1)0
Used to select the function assigned to the relay output. The
relay has two output terminals: Logic 1 indicates that the relay
is active: This is why terminals 17 and 18 are connected to each
other.
0RUN, enable (FWD, REV)
1READY, variable frequency drive ready for operation
2Output frequency = frequency reference value
3Output frequency > 0 Hz
4Output Frequency
Closing threshold > P2-16
Switch off threshold < P2-17
5Output current
Closing threshold > P2-16
Switch off threshold < P2-17
6Output torque (calculated value)
7Analog input (AI) 2
8PLC for external (hub) brake.
P2-19
P2-20220✓rwAO2/K2 lower limit0.0
P2-21
P2-22222✓rwscaled display value0
219✓rwAO2/K2 upper limit100.0
221✓rwScaling factor for value0.00
0Output Frequency
1Output current
2Analog input 2
3P0-80 value
Closing threshold > P2-16
Switch off threshold < P2-17
Closing threshold > P2-16
Switch off threshold < P2-17
This setting also enables the special operating mode for
hoisting gear. Please contact your sales office for details.
The adjustable upper limit value that is being used in connection with settings 4 to 7 of P2-13 and P2-18
0.0 - 200.0 %
The adjustable lower limit value that is being used in connection with settings 4 to 7 of P2-13 and P2-18
0.0 - 200.0 %
The variable selected with P2-22 is scaled with the factor
selected in P2-21.
-30.00 - 30.00
Used to select the variable that should be scaled with the
factor specified in P2-21.
DA1 Variable Frequency Drives 10/12 MN04020005Z-EN www.eaton.com95
Page 100
6 Parameters
PNU
P2-23223✓rwHolding time for speed of 00.2
P2-24224✓–Clock frequencyFS2: 16 kHz
P2-25
P2-26226✓rwFlying restart circuit0
P2-27227✓rwDelay time in Standby mode0.0
IDAccess rightValueDescriptionDS
RUNro/rw
Used to define the time that the variable frequency drive will
continue to output 0 Hz (after reaching 0 Hz) before stopping.
0.0 - 60.0 s
FS3, FS4,
FS5: 8 kHz
FS6, FS7:
4kHz
4 - 32 kHz
RMS switching frequency of power stage.
A higher frequency will reduce motor noise and improve the
output current's waveform, while causing increased heat loss
in the variable frequency drive.
225✓rwQuick stop deceleration ramp time/deceleration time (dec 2)0.0
Ramp time for quick deceleration ramp
Note:
In the event of a power failure, it is selected automatically or
via a digital input (DI) if P2-38 = 2.
If the parameter is set to 0.0, the motor will coast until it stops.
0.0 - 240.0 s
If this parameter is enabled, the variable frequency drive will
attempt, upon starting, to determine whether the motor is
already turning and to reduce its current speed in a controlled
manner. A brief deceleration will occur if motors that are not
already turning are started.
0Deactivated
1Enabled
Activates the Standby mode
0.0Standby mode deactivated
> 0 - 250 sThe drive will switch to standby mode (the output will be deac-
tivated) if the minimum speed (P1-02) is maintained for the time
specified in this parameter. Operation will resume automatically as soon as the setpoint frequency increases to a
frequency higher than P1-02.
96DA1 Variable Frequency Drives 10/12 MN04020005Z-EN www.eaton.com
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.