Cutler Hammer, Div of Eaton Corp CVX050, CVX100 Data Sheet

Technical Data TD01005002E
Effective May 2016 Supersedes November 2013
CVX surge protective device
Contents
Description Page
Product application ........................1
General description ........................2
Features, functions, and benefits. .............2
Optional features ..........................2
Standards and certifications .................2
Product specifications ......................3
Product ordering guidelines ..................4
CVX050/100 accessories ....................4
Product application
Residential/small business
Light industrial
Light commercial
Service entrance and branch panel protection
OEM applications
Control panels
Model CVX050 Model CVX100
Technical Data TD01005002E
Conduit tting
Effective May 2016
CVX surge protective device
General description
CVX050/100
With more than 20 years of experience in the surge suppression industry and extensive R&D initiatives, Eaton is considered a world leader in SPD manufacturing. All of Eaton’s products are manufactured in an ISOT 9001:2000 and ISO 14001 certified facility.
Eaton CVX050/100 models are rugged, cost-effective, high-quality SPDs that feature self-protected metal oxide varistors (MOVs) that eliminate the failure characteristics of standard metal oxide varistors. The self-protected MOV is a fail-safe device that monitors the status of the metal oxide disk and disconnects itself from the power system when the disk is approaching breakdown.
The CVX050/100 is easy to install adjacent or even internal to electrical equipment. When installing an SPD in a retrofit environment, it is important to mount the device as close to the electrical equipment as possible. Keep the wiring (lead length) between the electrical equipment and the SPD as short as possible, and twist or wire tie the conductors together to reduce the wire’s impedance factor.
Features, functions, and benets
Large diameter, self-protected metal oxide varistors provide long life and fail-safe operation
Rated 50 kA (CVX050) or 100 kA (CVX100) peak surge current
Wide range of voltage applications from 100 to 600 Vac
Rugged NEMAT 4X (IP56) enclosure
LED monitoring of each phase
Wiring systems: single-phase, split-phase, three-phase wye, three-phase delta, three-phase high leg delta, or direct current (DC)
#10 AWG (6 mm2) stranded wire included
¾-inch threaded conduit fitting included
Five-year free replacement warranty
Optional features
Available external mounting feet
Available flush mount plate
Standards and certications
ULT 1449 4th Edition for surge suppression devices
CSAT and CE marked
CE, CSA, and UL on AC unit only
Vibration tested to IEC 60255-21-1 and IEC 60255-21-2
5.67 (144.0)
4.75 (120.6)
4.17 (106.0)
3.39 (86.1)
4.75 (120.6)
A
Lid removed
Section A-A
Dimensions are in inches (mm)
Figure 1. Standard dimensions
0.75 (19.0) internal taper pipe threads
A
1.00 (25.4)
3.55 (90.2)
0.17 (4.3) (4) Mounting holes under lid
Mounting hole shafts
2.37 (60.2)
2
CVX surge protective device
Technical Data TD01005002E
Product specications
Table 1. CVX050/100 model specifications
Description Specification
Peak kA per phase 50, 100 Peak kA per mode 50 Nominal discharge current 20 kA Short-circuit current rating 100 kA Single-phase voltages 200, 208, 220, 230, 240, 277, 38 0, 400, 440, 460, 480 Split-phase voltages 100/200, 110/220/ 120/240 High leg delta voltages 240 Wye system voltages 100/175, 110/190, 120/208, 127/220, 220/380, 230/40 0, 240/415, 277/480, 305/525, 347/600 Delta system voltages 200, 208, 220, 230, 240, 380, 400, 415, 440, 480, 525, 600 Direct current voltage
b
Input power frequency 47–420 Hz (50/60 Hz typical) Protection modes Single-phase: L-N, N-G, L-G
Number of ports 1 Specific energy 100 k J/ohm Weight ≈2.0 lb (1.0 kg) Operating temperature –13 °F (–25 °C) to +140 °F (+60 °C) Vibration tested IEC 60255-21-1 and IEC 60255-21-2
a
480L, 600D, and 600Y units rated 10 kA In.
b
DC models only available in 50 kA.
a
48 Vdc, 125 Vdc
Split-phase: L-N, N-G, L-G, L-L High leg delta: L-N, N-G, L-G, L-L, H-N, H-G, H-L Wye: L-N, N-G, L-G, L-L Delta: L-G, L-L Direct current (DC): L-L, L-G
b
Effective May 2016
Table 2. CVX050/100 voltage ratings
a
Model
CVX050
Syste m configuration
Nominal system voltage
MCOV UL 1449 -4 VPR
L-L L-N L-G N-G L-L L-N L-G N-G
230L Single-phase two-wire + ground 200, 208, 220, 230, 240, 277 320 640 320 12 00 1200 1200 480L Single-phase two-wire + ground 380, 4 00, 440, 460, 480 550 1100 550 1800 4000 1800 240S Split-phase three-wire + ground 100/200, 110/220, 120/240 300 150 300 150 1200 700 12 00 800 208Y Three-phase wye (star) four-wire + ground 100/175, 110/190, 120/208, 127/220 300 150 300 15 0 1200 700 1200 800 480Y Three-phase wye (star) four-wire + ground 220/380, 230/400, 240/415, 2 77/480 640 320 640 320 2500 1200 2000 1200 600Y Three-phase wye (star) four-wire + ground 305/525, 347/600 840 420 840 420 2500 1500 2500 1500 240D Three-phase delta three-wire + ground 200, 208, 220, 230, 240 640 320 2000 1200 — 240H Three-phase high leg delta 240 300 15 0 150 640 1500 700 1200 700 480D Three-phase delta three-wire + ground 38 0, 400, 415, 44 0, 480 110 0 550 3000 18 00 — 600D Three-phase delta three-wire + ground 525, 600 1100 700 3000 2500 — 048DC Direct current 48 Vdc 125DC Direct current 125 Vdc
CV X100
b
b
130 65 — 288 144
230L Single-phase two-wire + ground 200, 208, 220, 230, 240, 277 320 320 320 1200 12 00 1200 480L Single-phase two-wire + ground 380, 4 00, 440, 460, 480 550 550 550 1800 180 0 180 0 240S Split-phase three-wire + ground 100/200, 110/220, 120/240 300 150 150 150 12 00 700 800 700 208Y Three-phase wye (star) four-wire + ground 100/175, 110/190, 120/208, 127/220 300 150 15 0 150 1000 600 700 700 480Y Three-phase wye (star) four-wire + ground 220/380, 230/400, 240/415, 2 77/480 640 320 320 320 18 00 1200 12 00 1200 600Y Three-phase wye (star) four-wire + ground 305/525, 347/600 840 420 420 420 2500 1500 1500 1500 240D Three-phase delta three-wire + ground 200, 208, 220, 230, 240 640 320 18 00 1200 — 240H Three-phase high leg delta 240 300 15 0 150 15 0 1200 700 700 700 480D Three-phase delta three-wire + ground 38 0, 400, 415, 44 0, 480 110 0 550 3000 18 00
a
UL 1449 4th Edition VPR (voltage protection rating) test environment: all tests performed with 6-inch lead length, positive polarity.
b
DC Units available in 50 kA only. Voltages shown are the maximum suggested operating voltages and are not UL certified.
3
Technical Data TD01005002E
Mounting hardware
Effective May 2016
Product ordering guidelines
CVX surge protective device
CVX 050 230L
Per phase peak
surge current
050 = 50 kA
a
a
DC models only available in 50 kA.
100 = 100 kA
CVX050/100 accessories
Table 3. CVX050/100 accessories
Description Catalog number
External mounting feet MNTGFT X Flush mount plate FLUSHMNTPLATE12
3.39 (86.1)
(four places)
installer supplied
Configuration and voltage ranges
230L = Single-phase—200, 208, 220, 230, 240, 277 Vac 480L = Single-phase—380, 400, 440, 460, 480 Vac 240S = Split-phase—100/200, 110/220, 120/240 Vac 240H = Three-phase high leg delta—120/240 Vac 208Y = Three-phase wye (star)—100/174, 110/190, 120/208, 127/220 Vac 480Y = Three-phase wye (star)—220/380, 230/400, 240/415, 277/480 Vac 600Y = Three-phase wye (star)—305/525, 347/600 Vac 240D = Three-phase delta—200, 208, 220, 230, 240 Vac 480D = Three-phase delta—380, 400, 415, 440, 480 Vac 600D = Three-phase delta—525, 600 Vac (600D available in 50 kA only) 048DC = Direct current—48 Vdc 125DC = Direct current —125 Vdc
a
a
6.50
(165.1)
4X
0.22 (5.6)
6.50
(165.1)
4.73
(120.1)
7.75
(196.9)
4X
0.80
(20.3)
7.75
(196.9)
4.73
(120.1)
Mounting foot
and screw
(four places)
5.85 (148.6)
Mounting dimensions
Dimensions are in inches (mm)
torque 15 in-lb
Mounting surface
Figure 2. Wall mounting with external mounting feet
Figure 3. Optional flush mount plate
Eaton is a registered trademark.
All other trademarks are property of their respective owners.
Loading...