Cutler Hammer, Div of Eaton Corp C Series Installation Instructions

Instruction Leaflet IL01203001E
Effective April 2011 Supersedes IL01203001EH06 7/08
Installation Instructions for Series C F-Frame 310+ Electronic Circuit Breaker Types FDE, HFDE, FDCE
Contents
Description Page
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Manual Operation . . . . . . . . . . . . . . . . . . . . . . . . . 4
Inspection & Field Testing . . . . . . . . . . . . . . . . . . . 4
Trip Unit Settings . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Neutral Current Sensor Installation . . . . . . . . . . . . 6
FDE Zone Interlocking System . . . . . . . . . . . . . . . 7
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Instruction Leaflet IL01203001E
Effective April 2011
Installation Instructions for Series C F-Frame 310+
Electronic Circuit Breaker Types FDE, HFDE, FDCE
DWARNING
DO NOT ATTEMPT TO INSTALL, TEST, OR PERFORM MAINTENANCE ON EQUIPMENT WHILE IT IS ENERGIZED. DEATH OR SEVERE INJURY AND/ OR SUBSTANTIAL PROPERTY DAMAGE CAN RESULT FROM CONTACT WITH ENERGIZED EQUIPMENT. BEFORE INSPECTING THE CIRCUIT BREAKER IN AN ELECTRICAL SYSTEM, MAKE SURE THE CIRCUIT BREAKER IS SWITCHED TO THE OFF POSITION AND THAT THERE IS NO VOLTAGE PRESENT WHERE WORK IS TO BE PERFORMED. ALWAYS FOLLOW GENERALLY ACCEPTED SAFETY PROCEDURES.
EATON IS NOT LIABLE FOR THE MISAPPLICATON OR MISINSTALLATION OF ITS PRODUCTS.
The user is cautioned to observe all recommendations, warnings and cautions relating to the safety of personnel and equipment, as well as all general and local health and safety laws, codes and pro­cedures.
The recommendations and information contained herein are based on Eaton experience and judgement, but should not be considered to be all-inclusive or covering every application or circumstance which may arise. If any questions arise, contact Eaton for further information or instructions.
1. Introduction
The F-Frame electronic Circuit Breaker (Figure 1) is available in the 3-pole style with three rated currents (80A, 160A, 225A) and four electronic tripping options. For single-phase ground fault applica­tions, both the supply and return must be routed through the Breaker. Throughout this document, the electronic circuit breaker will be referred to as a breaker. The circuit breaker is equipped with an electronic sensing and tripping mechanism which makes the inverse time delay release independently of ambient temperature. A thermal memory is incorporated which prevents power operation immediately after an overload trip.
2. Installation
The installation procedure consists of inspecting and mounting the breaker, connecting and torquing the line and load terminations, and attaching terminal shield or barriers when supplied. To install the breaker, perform the following steps.
NOTICE
THE BREAKERS ARE FACTORY SEALED. ACCESSORY INSTALLATION SHOULD BE DONE BEFORE THE BREAKER IS MOUNTED AND CONNECTED.
Mounting hardware and unmounted terminations (where required) are supplied in separate packages.
Make sure that the breaker is suitable for the installation by compar­ing nameplate data with system requirements. Inspect the breaker for completeness and check for damage before mounting.
DWARNING
BEFORE MOUNTING THE BREAKER IN AN ELECTRICAL SYSTEM, MAKE SURE THERE IS NO VOLTAGE PRESENT WHERE WORK IS TO BE PERFORMED. THE VOLTAGES IN ENERGIZED EQUIPMENT CAN CAUSE INJURY OR DEATH.
Depending on the equipment configuration, the breaker can be mounted using different styles of hardware. The following steps describe how to mount the breaker using standard hardware. When special hardware is needed with the electrical operator, for example, the instruction leaflet describing the accessory also describes the special mounting arrangements.
NOTICE
BEFORE MOUNTING THE BREAKER, CHECK TO SEE IF THE TERMINATION DEVICES SHOULD BE INSTALLED FIRST. SEE TERMINATION INSTRUC­TIONS.
Figure 1. F-Frame 310 + Electronic Circuit Breaker.
The electronic options include with or without ground fault and a linear of I2t response for the short delay time. The LS and LSG (catalog suffixes 33 and 35) have an I2t response for the short delay time function. The LSI and LSIG (catalog suffixes 32 and 36) have a flat response for the short delay time function. The LSG and LSIG include the ground fault function. The LSI and LSIG configurations also have a zone interlock option which are specified with the 32ZG and 36ZG catalog suffixes. These breakers are designed to comply with Underwriters Laboratories, Inc. Standard UL-489 and Canadian Standards Association CSA-22.2.
To mount the breaker, perform the following steps:
1. For individual mounting panels, make sure the mounting panel is predrilled using bolt drilling plan (Figure 2). For panel board mounting, only load end support mounting holes are required. For deadfront cover application, make sure panel cover is cut out to correct escutcheon dimensions (Figure 3).
1.375
(34,93)
Line End
Breaker Handle
Load End
Figure 2. Breaker Mounting Bolt Drilling Plan.
1.375
(34,93)
1.375
(34,93)
2.875
(73,03)
164-.32 Tap Holes (M4 x .07)
750
(19,05)
4.500
(11,43)
2
EATON CORPORATION www.eaton.com
Installation Instructions for Series C F-Frame 310+ Electronic Circuit Breaker Types FDE, HFDE, FDCE
Instruction Leaflet IL01203001E
Effective April 2011
.594
(15,09)
2.00
(50,98)
Line End
.80
(20,3)
2.906 (73,81)
2.313
(58,75)
3.40
(86,4)
3.40
(86,4)
3.64
(92,5)
Breaker Handle
Load End
R250
(6,35)
ø
.188 (4,78) Hole for access to Push-to-Trip
Figure 3. Breaker Escutcheon Dimensions.
2. If the breaker includes factory installed internal accessories, make sure accessory wiring can be reached when the breaker is mounted.
3. Position the breaker on the mounting surface.
4. Install mounting screws, washers and nuts. Tighten screws firm­ly, but do not exceed 28 pound-inches (3.16 N.m.)
If an optional terminal end cover is to be installed with the breaker (usually line end only), it must be positioned before the cable is con­nected to terminals.
Table 1. Terminal Types.
Terminal Catalog No.
3TA225FD * Aluminum 3/16
3TA225FDM * Aluminum 5mm
3TA225FDK * † Aluminum 5/16
3TA100FD * Aluminum Slotted #14-1/0 2.5-50 Cu/Al See Table 2.
3TA50FB * Aluminum Slotted #14-#4 2.5-16 Cu/Al See Table 2
3T100FB * Steel Slotted #14-1/0 2.5-50 Cu/Al See Table 2
3T150FB * Stainless
ote:N Terminal wire connectors are UL listed for standard wire size as
defined in UL 486A & UL 486B. * Package of 3. † Individual terminal identified as TA225FD1.
Terminal Body Material
Steel
Screw Head Type
Socket Hex
Socket Hex
Socket Hex
Slotted #4-4/0 25-95 Cu
AWG Wire Range
#4-40 25-95 Cu/Al 120 (13.6)
#4-40 25-95 Cu/Al 120 (13.6)
#6-300 16-150 Cu/Al 275 (31)
Metric Wire Range
Wire Type
only
Torque Value lb. in. (N-m)
See Table 2
Table 2. Terminal Torque Values of Slotted Head.
Metric Wire Range. Torque Value (N-m) AWG Wire Range Torque Value Lb in.
2.5-6 3.96 #14-10 35
10 4.52 #8 40
16-25 5.06 #6-4 45
35-95 5.65 #3-4/0 50
DCAUTION
WHEN ALUMINUM CONDUCTORS ARE USED, THE APPLICATION OF A SUITABLE JOINT COMPOUND IS RECOMMENDED TO REDUCE THE POSSIBILITY OF TERMINAL OVERHEATING. TERMINAL OVERHEATING CAN CAUSE NUISANCE TRIPPING AND DAMAGE TO THE BREAKER.
After mounting the breaker, line and load terminals and accessory leads should be connected (see accessory schematic diagram on side of breaker).
NOTICE
IF TERMINAL SHIELD OR INTERPHASE BARRIERS ARE TO BE INSTALLED ON THE BREAKER, INSTALL THEM AFTER THE TERMINALS ARE CON­NECTED.
If required, install terminal shield on breaker cover with mounting screws provided.
If required, install an interphase barrier by sliding barrier into dove­tail grooves between terminals.
After the breaker is installed, check all mounting hardware and terminal connecting hardware for correct torque loading. Torque values for line/load terminals are provided in Tables 1, 2 and 3.
Table 3. Bolted Connections (Keeper Nut or End Cap).
Termination Catalog No.
KPR1A/KPR1AM User Supplied 10-32/M5 35-(4.0)
KPEKxxx Slotted 10-32/M5 35-(4.0)
Screw Head Type) Nut Thread Size Torque Value Lb in.
(N-m)
EATON CORPORATION www.eaton.com
3
Loading...
+ 5 hidden pages