I.L. 29C104C
File 29-000
Effective June 1998 Supersedes I.L. 29C104-B dated August 1997.
Cutler-Hammer
Installation Instructions for DK, KDB, KD, HKD, KDC, KW, HKW,
KWC, CKD, CHKD Circuit Breakers and Molded Case Switches
The recommendations and information contained herein
are based on Cutler-Hammer experience and judgment,
but should not be considered to be all-inclusive or covering every application or circumstance which may arise. If
any questions arise, contact Cutler-Hammer for further
information or instructions.
1. INTRODUCTION
General Information
The K-frame Series C circuit breaker (Figure 1-1) types
KD, HKD, and KDC are 600 Vac maximum rated
devices with interchangeable thermal-magnetic or electronic (Seltronic) trip units rated 400A maximum continuous current. Circuit breaker types KW, HKW, and KWC
are 660 Vac maximum rated devices using interchangeable adjustable thermal/adjustable magnetic or electronic trip units rated up to 400A continuous current. The
type KDB noninterchangeable trip circuit breaker is rated
600 Vac maximum with a maximum continuous current
rating of 400A. The type DK 240 Vac maximum circuit
breaker is also a noninterchangeable trip device with trip
unit ratings from 250A to 400A. Refer to Table 4-1 on
page 8 for all available trip unit ratings. Model D circuit
breakers are listed in accordance with Underwriters
Laboratories, Inc. Standard UL489 and satisfy the (P1)
requirements of the International Electrotechnical
Commission Recommendations No. IEC 157-1. Model
W circuit breakers satisfy the requirements of IEC C947-
2. Molded case switches are listed in accordance with
UL1087. For more information, see Frame Book 29-103.
100 Percent Rated K-Frame Circuit Breakers
CKD and CHKD circuit breakers are suitable for continuous operation at 100 percent of the frame rating if
used with an 90°C insulated wire and AL9CU terminals
in an enclosure which measures at least 24” high x 15”
wide x 6” deep. Ventilation is not required in an enclosure having these minimum dimensions. CKD and
CHKD 100 percent rated circuit breakers use electronic
trip units only.
This instruction leaflet (IL) gives procedures for installation and field testing of K-frame Series C circuit breakers. Instructions are also provided for replacement of
existing Cutler-Hammer circuit breaker types DA, LB,
LBB, HLB, JA, KA, and HKA. For this publication, the
term circuit breaker shall also include the molded case
switch.
DO NOT ATTEMPT TO INSTALL OR PERFORM
MAINTENANCE ON EQUIPMENT WHILE IT IS ENERGIZED. DEATH, SEVERE PERSONAL INJURY, OR
SUBSTANTIAL PROPERTY DAMAGE CAN RESULT
FROM CONTACT WITH ENERGIZED EQUIPMENT.
ALWAYS VERIFY THAT NO VOLTAGE IS PRESENT
BEFORE PROCEEDING WITH THE TASK, AND
ALWAYS FOLLOW GENERALLY ACCEPTED SAFETY PROCEDURES.
CUTLER-HAMMER IS NOT LIABLE FOR THE MISAPPLICATION OR MISINSTALLATION OF ITS PRODUCTS.
The user is cautioned to observe all recommendations,
warnings, and cautions relating to the safety of personnel and equipment as well as all general and local
health and safety laws, codes, and procedures.
Figure 1-1 K-Frame Model D Series C Circuit Breaker
Frame with KT Trip Unit Installed
WARNING