Cutler Hammer, Div of Eaton Corp Circuit Breakers & Supplementary Protectors Catalog Number Structure

August 2006
Product Selection
Circuit Breakers & Supplementary Protectors 63 – 250 Amperes
JG-Frame
J G S 3 25O FA G
45-19
Frame
J
Standard/Application
G = IEC/CE/UL/CSA
2 = Two 3 = Three 4 = Four — Neutral 0% Protected 8 = Four — Neutral 0 – 60% Protected 9 = Four — Neutral 0 – 100 Protected
Performance
600 480 415 240
E 18 25 25 65
S 22 35 40 85
H 25 65 70 100
C 35 100 100 200
U 50 150 150 200
X 50 200 200 300
K Molded Case Switch
Table 45-24. Trip Unit Catalog Numbering System
Trip
JT
2 = Two 3 = Three 4 = Four — Neutral 0% Protected 8 = Four — Neutral 0/60% Protected 9 = Four — Neutral 0/100% Protected
Poles
Poles
JT 4 100 FA
Amperes
050 070 080 090 100 125 150 160 175 200 225 250
Amperes
T/M ETU
080
050
090
100
100
160
110
250 125 150 160 175 200 225 250
Trip Unit
AA = Adj. Adj. FA = Fixed Adj. KS = Molded Case Switch 33 = 310+ Electronic LS 32 = 310+ Electronic LSI 35 = 310+ Electronic LSG 36 = 310+ Electronic LSIG NN = Frame Only (No Trip)
Terminations/Hardware
Terminals Mounting Hardware
M = Metric End Caps E = Imperial End Caps G = Line/Load Standard
Trip Unit
AA = Adj. Adj. FA = Fixed Adj. KS = Molded Case Switch 33 = 310+ Electronic LS 32 = 310+ Electronic LSI 35 = 310+ Electronic LSG 36 = 310+ Electronic LSIG
Metric Imperial Metric
45
CA08102001E For more information visit: www.EatonElectrical.com
45-20
45
Circuit Breakers & Supplementary Protectors 63 – 250 Amperes
JG-Frame
Product Selection
Table 45-25. Complete Breaker (Includes Frame, Trip Unit, Standard Terminals and Mounting Hardware) — IC Rating at 415/480 Volts
Maximum Continuous Amperes
Magnetic Range
2-Pole 3-Pole 4-Pole 0%
Fixed Thermal Adjustable Magnetic
Catalog Number
Fixed Thermal Adjustable Magnetic
Price
Catalog
U.S. $
Number
Price U.S. $
Adjustable Thermal Adjustable Magnetic
Catalog Number
Price U.S. $
Fixed Thermal
Adjustable Magnetic
Catalog Number
IEC/CE/UL/CSA 25/25
70 90 100 125 150 160 175 200 225 250
350 – 700 450 – 900 500 – 1000 625 – 1250 750 – 1550 800 – 1600 875 – 1750 1000 – 2000 1125 – 2250 1250 – 2500
JGE2070FAG JGE2090FAG JGE2100FAG JGE2125FAG JGE2150FAG — JGE2175FAG JGE2200FAG JGE2225FAG JGE2250FAG
JGE3070FAG JGE3090FAG JGE3100FAG JGE3125FAG JGE3150FAG — JGE3175FAG JGE3200FAG JGE3225FAG JGE3250FAG
— — JGE3100AAG JGE3125AAG — JGE3160AAG — JGE3200AAG — JGE3250AAG
JGE4070FAG JGE4090FAG JGE4100FAG JGE4125FAG JGE4150FAG — JGE4175FAG JGE4200FAG JGE4225FAG JGE4250FAG
IEC/CE/UL/CSA 40/35
70 90 100 125 150 160 175 200 225 250
350 – 700 450 – 900 500 – 1000 625 – 1250 750 – 1550 800 – 1600 875 – 1750 1000 – 2000 1125 – 2250 1250 – 2500
JGS2070FAG JGS2090FAG JGS2100FAG JGS2125FAG JGS2150FAG — JGS2175FAG JGS2200FAG JGS2225FAG JGS2250FAG
JGS3070FAG JGS3090FAG JGS3100FAG JGS3125FAG JGS3150FAG — JGS3175FAG JGS3200FAG JGS3225FAG JGS3250FAG
— — JGS3100AAG JGS3125AAG — JGS3160AAG — JGS3200AAG — JGS3250AAG
JGS4070FAG JGS4090FAG JGS4100FAG JGS4125FAG JGS4150FAG — JGS4175FAG JGS4200FAG JGS4225FAG JGS4250FAG
IEC/CE/UL/CSA 70/65
70 90 100 125 150 160 175 200 225 250
350 – 700 450 – 900 500 – 1000 625 – 1250 750 – 1550 800 – 1600 875 – 1750 1000 – 2000 1125 – 2250 1250 – 2500
JGH2070FAG JGH2090FAG JGH2100FAG JGH2125FAG JGH2150FAG — JGH2175FAG JGH2200FAG JGH2225FAG JGH2250FAG
JGH3070FAG — JGH3090FAG JGH3100FAG JGH3125FAG JGH3150FAG — JGH3175FAG JGH3200FAG JGH3225FAG
— — JGH3100AAG JGH3125AAG
JGH3160AAG — JGH3200AAG — JGH3250AAG
JGH4070FAG JGH4090FAG JGH4100FAG JGH4125FAG JGH4150FAG — JGH4175FAG JGH4200FAG JGH4225FAG JGH4250FAG
IEC/CE/UL/CSA 100/100
70 80 90 100 125 150 160 175 200 225 250
350 – 700 400 – 800 450 – 900 500 – 1000 625 – 1250 750 – 1550 800 – 1600 875 – 1750 1000 – 2000 1125 – 2250 1250 – 2500
— — — — — — — — — — —
JGC3070FAG — JGC3090FAG JGC3100FAG JGC3125FAG JGC3150FAG — JGC3175FAG JGC3200FAG JGC3225FAG JGC3250FAG
— JGC3080AAG — JGC3100AAG JGC3125AAG — JGC3160AAG — JGC3200AAG — JGC3250AAG
JGC4070FAG — JGC4090FAG JGC4100FAG JGC4125FAG JGC4150FAG — JGC4175FAG JGC4200FAG JGC4225FAG JGC4250FAG
IEC/CE/UL/CSA 150/150
70 80 90 100 125 150 160 175 200 225 250
350 – 700 400 – 800 450 – 900 500 – 1000 625 – 1250 750 – 1550 800 – 1600 875 – 1750 1000 – 2000 1125 – 2250 1250 – 2500
— — — — — — — — — — —
JGU3070FAG — JGU3090FAG JGU3100FAG JGU3125FAG JGU3150FAG — JGU3175FAG JGU3200FAG JGU3225FAG JGU3250FAG
— JGU3080AAG — JGU3100AAG JGU3125AAG — JGU3160AAG — JGU3200AAG — JGU3250AAG
JGU4070FAG — JGU4090FAG JGU4100FAG JGU4125FAG JGU4150FAG — JGU4175FAG JGU4200FAG JGU4225FAG JGU4250FAG
IEC/CE/UL/CSA 200/200
70 80 90 100 125 150 160 175 200 225 250
Change the fourth digit to 8 for adjustable 0 – 60% neutral protection, 9 for 0 – 100% neutral protection. Neutral is on LH side.
IEC-EN 60947-2 only. Adjustment is .8 and 1.0.
350 – 700 400 – 800 450 – 900 500 – 1000 625 – 1250 750 – 1550 800 – 1600 875 – 1750 1000 – 2000 1125 – 2250 1250 – 2500
— — — — — — — — — — —
JGX3070FAG — JGX3090FAG JGX3100FAG JGX3125FAG JGX3150FAG — JGX3175FAG JGX3200FAG JGX3225FAG JGX3250FAG
— JGX3080AAG — JGX3100AAG JGX3125AAG — JGX3160AAG — JGX3200AAG — JGX3250AAG
JGX4070FAG — JGX4090FAG JGX4100FAG JGX4125FAG JGX4150FAG — JGX4175FAG JGX4200FAG JGX4225FAG JGX4250FAG
Adjustable Thermal Adjustable Magnetic
Price U.S. $
Catalog Number
— — JGE4100AAG JGE4125AAG — JGE4160AAG — JGE4200AAG — JGE4250AAG
— — JGS4100AAG JGS4125AAG — JGS4160AAG — JGS4200AAG — JGS4250AAG
— — JGH4100AAG JGH4125AAG — JGH4160AAG — JGH4200AAG — JGH4250AAG
— JGC4080AAG — JGC4100AAG JGC4125AAG — JGC4160AAG — JGC4200AAG — JGC4250AAG
— JGU4080AAG — JGU4100AAG JGU4125AAG — JGU4160AAG — JGU4200AAG — JGU4250AAG
— JGX4080AAG — JGX4100AAG JGX4125AAG — JGX4160AAG — JGX4200AAG — JGX4250AAG
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . CB-2
August 2006
Price U.S. $
For more information visit: www.EatonElectrical.com CA08102001E
Circuit Breakers & Supplementary Protectors 63 – 250 Amperes
August 2006
Product Selection
Table 45-26. Thermal-Magnetic Trip Unit
Ampere Rating
70 80 90 100
125 150 160 175
200 225 250
Range Catalog
350 – 700 400 – 800 450 – 900 500 – 1000
625 – 1250 750 – 1500 800 – 1600 875 – 1750
1000 – 2000 1125 – 2250 1250 – 2500
Adjustable thermal trip units are typically used in IEC markets and are not UL or CSA listed.
Number
JT2070FA — JT2090FA JT2100FA
JT2125FA JT2150FA JT2160FA JT2175FA
JT2200FA JT2225FA JT2250FA
Price
Catalog
U.S. $
Number
JT3070FA — JT3090FA JT3100FA
JT3125FA
JT3150FA — JT3175FA
JT3200FA JT3225FA JT3250FA
JG-Frame
Price U.S. $
Catalog Number
— JT3080AA — JT3100AA
JT3125AA — JT3160AA —
JT3200AA — JT3250AA
Price U.S. $
Range Catalog
— 64 – 100 — 80 – 100
100 – 125 — 128 – 160 —
160 – 200 — 200 – 250
Number
JT4070FA — JT4090FA JT4100FA
JT4125FA JT4150FA — JT4175FA
JT4200FA JT4225FA JT4250FA
Price U.S. $
Catalog Number
— JT4080AA — JT4100AA
JT4125AA — JT4160AA —
JT4200AA — JT4250AA
45-21
Price U.S. $
Table 45-27. Molded Case Switches
Catalog Number
JGK2250KSK JGK3250KSG JGK7250KSG
Note: Molded case switches will trip above 2500 amperes.
Price U.S. $
Table 45-28. Components — Line and Load Terminal
Wire
Maximum Breaker Amperes
Terminal Body Material
Typ e
AWG Wire Range No. Conductors
Standard Cu/AI Pressure Terminals
250 Aluminum Cu/Al 4 – 350 kcmil
250 Stainless
Standard line and load terminals.
Steel
Cu 4 – 350 kcmil
Metric Wire Range mm
25 – 185 TA250FJ
25 – 185 T250FJ
2
Catalog Number
Price U.S. $
45
CA08102001E For more information visit: www.EatonElectrical.com
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . CB-2
45-22
45
Circuit Breakers & Supplementary Protectors 63 – 250 Amperes
JG-Frame
Product Selection
Table 45-29. Components — Frame — IC Rating at 415/480 Volts
Maximum Amperes
25/25
250 JGE2250NN JGE3250NN JGE4250NN
40/35
250 JGS2250NN JGS3250NN JGS4250NN
70/65
250 JGH2250NN JGH3250NN JGH4250NN
100/100
250 JGC3250NN JGC4250NN
150/150
250 JGU3250NN JGU4250NN
200/200
250 JGX3250NN JGX4250NN
Table 45-30. Plug-in Test Kit Table 45-31. Breaker Mount Ammeter
Voltage Rating
120 Vac 230 Vac
Table 45-32. JG Electronic Trip Units
Ampere Rating
3-Pole
50 100 160 250
4-Pole
50 100 160 250
Required for 4-wire systems if neutral protection is desired.
Neutral protection 4 = 0%, 6 = 60%, 7 = 100% electronic trip unit neutral protection is not adjustable.
Note: Long time pickup — no rating plug. 250 Ampere Settings — 250, 225, 200, 175, 160, 150, 125, 100. 160 Ampere Settings — 160, 150, 125, 110, 100, 90, 80, 63. 100 Ampere Settings — 100, 90, 80, 70, 63, 50, 45, 40. 50 Ampere Settings — 50, 45, 40, 32, 30, 25, 20.
Note: Adjustable long time delay — 2 – 24 seconds at 6 x lr. Adjustable short time delay — Inst., 120, 300 ms
2-Pole 3-Pole 4-Pole 0%
Catalog Number
Price U.S. $
Catalog Number
MTST120V MTST230V
Price U.S. $
Catalog Number
Price U.S. $
Description Catalog
Breaker Mount Ammeter DIGIVIEW
Note: Use on electronic trip only.
LS Price
JT305033 JT310033 JT316033 JT325033
JT405033 JT410033 JT416033 JT425033
U.S. $
LSI Price
JT305032 JT310032 JT160323 JT325032
JT405032 JT410032 JT416032 JT425032
U.S. $
LSG Price
JT305035 JT310035 JT316035 JT325035
JT405035 JT410035 JT416035 JT425035
U.S. $
LSIG Price
JT305036 JT310036 JT316036 JT325036
JT405036 JT410036 JT416036 JT425036
Catalog Number
U.S. $
Price
U.S. $
Number
Neutral CT for LSG &
LSIG
JGFCT050 JGFCT100 JGFCT160 JGFCT250
JGFCT050 JGFCT100 JGFCT160 JGFCT250
August 2006
Digitrip 310+ Test Kit
Price U.S. $
Digitrip 310+ Test Kit Shown with JG MCCB
Price U.S. $
JG Digitrip 310+ Electronic Trip Unit
Ammeter
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . CB-2
For more information visit: www.EatonElectrical.com CA08102001E
Loading...