voltage release is operated. A “make”
contact closes and a “break” contact
opens when the alarm/lockout switch
operates. The switch automatically
resets when the circuit breaker is reset.
For remote indication of
automatic trip operation.
Does not function with
manual switching; however, it will operate when
either a shunt trip or under-
Table 45-181.
Maximum
Voltage
F-Frame Electrical Rating Data
Frequency Maximum
Current
Amperes
Dielectric
Withstand
Voltage
Multi-Pole Circuit Breakers
600
125
250
50/60 Hz
dc
dc
6
0.50
0.25
2500
Single-Pole Circuit Breakers
125/250
28
28
Endurance: 6000 electrical operations plus
4000 mechanical operations.
Endurance: 6000 electrical operations plus
2000 mechanical operations.
Non-inductive load.
Inductive (L/R = 0.026).
Table 45-182.
Maximum
Voltage
600
125
250
Endurance: 6000 electrical operations plus
2000 mechanical operations.
Pigtail wire size: 18 AWG (0.82 mm2).
Non-inductive load.
50/60 Hz
dc
dc
J-Frame Electrical Rating Data
Frequency Maximum
50/60 Hz
dc
dc
6
3
5
Current
Amperes
6
0.50
0.25
2000
Dielectric
Withstand
Voltage
2500
Table 45-183.
Maximum
Voltage
600
125
250
Pigtail wire size: 18 AWG (0.82 mm2).
Endurance: 5,000 electrical operations plus
1000 mechanical operations.
Non-inductive load.
Table 45-184. L-Frame Electrical Rating
Data
Maximum
Voltage
600
125
250
Pigtail wire size: 18 AWG (0.82 mm2).
Endurance: 5,000 electrical operations plus
1000 mechanical operations.
Non-inductive load.
K-Frame Electrical Rating Data
Frequency Maximum
50/60 Hz
dc
dc
Frequency Maximum
50/60 Hz
dc
dc
Current
Amperes
6
0.50
0.25
Current
Amperes
6
0.50
0.25
Dielectric
Withstand
Voltage
2500
Dielectric
Withstand
Voltage
2500
45
CA08102001EFor more information visit: www.EatonElectrical.com
F-Frame circuit breakers are factory sealed. Underwriters Laboratories, requires that internal accessories be installed at the factory. Internal accesso-
B13
1288C76G09
ries are UL listed for factory installation under E7819. Where local codes and standards permit and UL listing is not required, internal accessories can
be field installed. Accessory installation should be done before the circuit breaker is mounted and connected.
Includes 24-inch (609.6 mm) external pigtail leads,18 AWG (16-.010).
A maximum of two internal accessories may be mounted in a 3-pole circuit breaker.
Suitable for mounting in right pole only of 2- or 3-pole breaker.
Table 45-186. F-Frame and HMCP (F) Alarm Switch
Number of
Contacts
(Make and
Break)
1Left
2Left
1 (Make
Only)
F-Frame circuit breakers are factory sealed. Underwriters Laboratories, requires that internal accessories be installed at the factory. Internal accesso-
Mounting
Location
(Pole)
Right
Right
SinglePole
Factory MountedField Mounted
Connection Type and LocationField Installation Kits
18-Inch (457.2 mm) Pigtail LeadsTerminal BlockPigtail LeadsTerminal Block
Same SideRear
Suffix
Number
Adder
U.S. $
B01
B05
B09
B12
B15
Suffix
Number
B02
B06
B10
B13
Adder
U.S. $
Opposite SideSame Side
Suffix
Number
B03
B07
—
—
Adder
U.S. $
Suffix
Number
B04
B08
B11
B14
Adder
U.S. $
Catalog
Number
A1L1LPK
A1L1RPK
A2L1LPK
A2L1RPK
Price
U.S. $
Catalog
Number
A1L1LTK
A1L1RTK
A2L1LTK
A2L1RTK
Price
U.S. $
———— —
ries are UL listed for factory installation under E7819. Where local codes and standards permit and UL listing is not required, internal accessories can
be field installed. Accessory installation should be done before the circuit breaker is mounted and connected.
Not listed with Underwriters Laboratories, for field installation.
For F-Frame HMCP, add “M” to the beginning of catalog number.
Standard pigtail lead exit location.
Standard mounting location.
Factory installation only. Leads exit load end of circuit breaker.
Table 45-187. J-Frame and HMCP (J) Alarm Switch
Number of
Contacts
(Make and
Break)
1Left
Listed with Underwriters Laboratories, for field installation on interchangeable trip unit breakers under E64983.
Standard mounting location.
Standard mounting location — leads exit rear of breaker.
Standard pigtail lead exit location.
Mounting
Location
(Pole)
Right
Factory MountedField Mounted
Connection Type and LocationField Installation Kits
18-Inch (457.2 mm) Pigtail LeadsTerminal BlockPigtail LeadsTerminal Block
Same SideRear
Suffix
The Auxiliary Switch provides circuit breaker con-
a
tact status information by monitoring the position
of the molded cross bar which contains the mov-
b
ing contact arms. The auxiliary switch is used for
tion, and consists of one or two SPDT switches housed in a
plug-in module. Each SPDT switch has one “a” and one “b”
contact. When the circuit breaker contacts are open, the “a”
contact is open and the “b” contact is closed.
Table 45-190. F-Frame Electrical Rating Data
Maximum
Voltage
125
600
125
250
Endurance: 6000 electrical operations plus 4000 mechanical operations.
Pigtail wire size: 18 AWG (0.82 mm2).
For use in electronic circuit of 100 micro amperes and 15 Vdc minimum.
Non-inductive load.
Table 45-191. J-Frame Electrical Rating Data
Maximum
Voltage
600
125
250
Endurance: 6000 electrical operations plus 4000 mechanical operations.
Pigtail wire size: 18 AWG (0.82 mm2).
Non-inductive load.
remote indication and interlock system verifica-
FrequencyMaximum
50/60 Hz
50/60 Hz
dc
dc
FrequencyMaximum
50/60 Hz
dc
dc
Current
Amperes
1
6
0.50
0.25
Current
Amperes
6
0.50
0.25
Dielectric
Withstand
Voltage
2500
Dielectric
Withstand
Voltage
2500
August 2006
Table 45-192. K-Frame Electrical Rating Data
Maximum
Voltage
600
125
250
Endurance: 5000 electrical operations plus 1000 mechanical operations.
Pigtail wire size: 18 AWG (0.82 mm2).
Non-inductive load.
FrequencyMaximum
Current
Amperes
50/60 Hz
dc
dc
6
0.50
0.25
Table 45-193. L-Frame Electrical Rating Data
Maximum
Voltage
600
125
250
Pigtail wire size: 18 AWG (0.82 mm2).
Non-inductive load.
FrequencyMaximum
Current
Amperes
50/60 Hz
dc
dc
6
0.50
0.25
Dielectric
Withstand
Voltage
2500
Dielectric
Withstand
Voltage
2500
Table 45-194. G-Frame Auxiliary Switch (RH only)
Electrical RatingsContact
VoltsFrequencyAmperes
240
240
Includes 24-inch external pigtail leads, 18 AWG (16-.010).
A maximum of two internal accessories may be mounted in a 3-pole circuit breaker. Suitable for mounting in right pole only of 2- or 3-pole breaker.
50/60 Hz
50/60 Hz
6
6
Arrangement
1a/1b
2a/2b
Factory
Suffix
A3
A6
Adder
U.S. $
Catalog
Number
1288C74G03
1288C73G03
Price
U.S. $
Table 45-195. F-Frame and HMCP (F) Auxiliary Switch
Number of
Contacts
a and b
1Left
2Left
Standard pigtail lead exit location.
Not listed with Underwriters Laboratories, for field installation.
Pigtail wire size: 18 AWG (0.82 mm2).
125 volts (Max.), 50/60 Hz switch for use in electronic circuit of 100 micro amperes and 15 Vdc minimum.
Not for use on 4-pole circuit breakers.
Mounting
Location
(Pole)
Right or
Neutral
Right or
Neutral
Factory MountedField Mounted
Connection Type and LocationField Installation Kits
18-Inch (457.2 mm) Pigtail LeadsTerminal BlockPigtail LeadsTerminal Block
Same SideRear
Suffix
The Shunt Trip provides remote controlled
tripping of the circuit breaker. The shunt trip
ST
consists of an intermittent rated solenoid with a
tripping plunger and a cutoff switch assembled
a
to a plug-in module. When required for ground
shunt trips, as noted in the Electrical Rating Table, are
suitable for operation at 55 percent of rated voltage.
fault protection applications, certain ac rated
August 2006
Select shunt trip catalog number for the voltage within the
indicated voltage range. Shunt trip coils are designed to
be applied at specific ac or dc voltages within the voltage
range shown. Electrical ratings are also shown on applicable
circuit breaker accessory nameplates.
45
Voltage
12
24
48
60
110
120
125
127
220
250
—
—
—
—
Voltage
12
24
48
60
110
120
125
—
—
—
110
120
125
127
—
—
—
—
Minimum
Operating
Voltage
9100
36100
77 55
—
—
—
—
—
—
Minimum
Operating
Voltage
8.4 50
33.61094
77
—
—
154 40
—
—
—
—
VA
400
160
66
71
72
110
140
—
—
—
—
VA
247
1698
112
138
150
—
—
—
58
—
—
—
—
—
—
Table 45-207. F-Frame Electrical Rating Data
50/60 Hzdc
Supply
Voltage
12
24
48
60
110
120
127
208
220
240
380
415
440
480
525
550
600
Average unlatching time: 6 milliseconds.
Average circuit breaker contact total opening time: 18 milliseconds.
Endurance: 6000 electrical operations plus 4000 mechanical operations.
Minimum
Operating
Voltage
6.75 75
36 92
156480
300610
300380
VASupply
300
140
570
640
180
200
240
130
330
450
530
590
Table 45-208. J-Frame Electrical Rating Data
50/60 Hzdc
Supply
Voltage
12
24
48
60
110
120
127
208
220
240
380
400
415
440
480
525
550
600
Average unlatching time: 6 milliseconds.
Average circuit breaker contact total opening time: 18 milliseconds.
Endurance: 6000 electrical operations plus 2000 mechanical operations.
Supply voltages suitable for use with Class 1 GFP devices. Marking
label included with accessory kits.
Minimum
Operating
Voltage
9 31
36 686
60.5 66
285 180
360 34
VASupply
173
1014
84
102
354
396
432
200
240
610
42
50
60
Voltage
12
24
48
60
110
120
125
—
—
—
220
250
—
—
—
—
—
—
Voltage
12
24
48
60
110
120
125
—
—
—
220
250
—
—
—
—
—
—
Minimum
Operating
Voltage
8.4 35
77
—
—
—
154 41
—
—
—
—
Minimum
Operating
Voltage
9 35
34 710
77
—
—
154
—
—
—
—
—
—
—
VA
170
710
1105
110
130
140
—
—
—
54
—
—
—
—
—
—
VA
170
1105
110
130
140
—
—
—
41
54
—
—
—
—
—
—
Table 45-209. K-Frame Electrical Rating Data
50/60 Hzdc
Supply
Voltage
12
24
48
60
110
120
127
208
220
240
380
400
415
440
480
525
550
600
Approximate unlatching time: 6 milliseconds.
Approximate total circuit breaker contact opening time: 8 milliseconds.
Endurance: 5,000 electrical operations plus 1,000 mechanical
operations.
Supply voltages suitable for use with Class 1 GFP devices. Marking
label included with accessory kits.
Minimum
Operating
Voltage
9 45
60 100
285 95
360 40
VASupply
200
830
1280
120
140
420
470
550
108
120
136
50
50
70
Table 45-210. L-Frame Electrical Rating Data
50/60 Hzdc
Supply
Voltage
12
24
48
60
110
120
127
208
220
240
380
400
415
440
480
525
550
600
Approximate unlatching time: 6 milliseconds.
Approximate total circuit breaker contact opening time: 18 milliseconds.
Endurance: 5,000 electrical operations plus 1,000 mechanical operations.
Supply voltages suitable for use with Class 1 GFP devices. Marking
label included with accessory kits.
Minimum
Operating
Voltage
9 45
34 830
60 100
266 95
336 40
VASupply
200
1280
120
140
420
470
550
108
120
136
50
50
70
For more information visit: www.EatonElectrical.comCA08102001E
Note: G-Frame circuit breakers are factory sealed. Underwriters Laboratories requires that internal accessories be installed at the factory.
Note: Internal accessories are UL listed for factory installation under E7819.
Note: Where local codes and standards permit and UL listing is not required, internal accessories can be field installed. Accessory installation
should be done before the circuit breaker is mounted and connected.
Table 45-212. F-Frame and HMCP (F) Shunt Trip
Voltage Rating
(ac Frequency = 50/60 Hz)
Left-Pole Mounting ac/dc Ratings
12 – 24 Vac or dc
48 – 127 Vac or 48 – 60 Vdc
208 – 380 Vac or 110 – 127 Vdc
415 – 600 Vac or 220 – 250 Vdc
Right- or Neutral-Pole Mounting ac/dc Ratings
12 – 24 Vac or dc
48 – 127 Vac or 48 – 60 Vdc
208 – 380 Vac or 110 – 127 Vdc
415 – 600 Vac or 220 – 250 Vdc
Not listed with Underwriters Laboratories, for field installation.
Pigtail wire size: 18 AWG (0.82 mm2).
Standard pigtail lead exit location.
120 Vac marked suitable for ground fault protection devices.
Standard mounting location.
Not for use on 4-pole circuit breakers
Factory MountedField Mounted
Connection Type and LocationField Installation Kits
Low Energy Shunt Trip
devices are designed to
operate from low energy
UV
output signals from dedicated current sensors typi-
fault protection schemes. However,
with a proper control voltage source,
they may be applied in place of
conventional trip devices for special
applications. Flux paths surrounding
permanent magnets used in the shunt
trip assembly hold a charged spring
poised in readiness to operate the
circuit breaker trip mechanism.
Table 45-216. F-, J-, K- and L-Frames and HMCPs Low Energy Shunt Trip
Mounting
Positions
(Pole)
F-Frame
Left
Right
J-Frame
Left
Right
K-Frame
Left
Right
L-Frame
Left
Right
Cutoff provisions required in control circuit.
Listed with Underwriters Laboratories for field installation under E64983.
Standard mounting location — leads exit rear of breaker.
For F-Frame HMCP, add an “M” to beginning of catalog number.
For use with thermal-magnetic trip units only.
Breakers with K-Frame OPTIM 550 can only accept accessories in left pole.
cally applied in ground
Factory MountedField Mounted
Connection Type and LocationField Installation Kits
When a 100 microfarad capacitor
charged to 28 Vdc is discharged
through the shunt trip coil, the resultant flux opposes the permanent magnet flux field, which releases the
stored energy in the spring to trip the
circuit breaker. As the circuit breaker
resets, the shunt trip reset arm is actuated by the circuit breaker handle,
resetting the shunt trip. The plug-in
module is mounted in retaining slots
in the top of the trip unit. Coil is intermittent-rated only. Cutoff provisions
required in control circuit.
Suffix
Number
NO2
NO6
NO2
NO6
NO2
NO6
NO2
NO6
Adder
U.S. $
Opposite SideSame Side
Suffix
Number
NO3
NO7
NO3
NO7
NO3
NO7
NO3
NO7
45-119
Ordering Information
Select shunt trip catalog number
for the voltage within the indicated
voltage range. Shunt trip coils are
designed to be applied at specific
ac or dc voltages within the voltage
range shown. Electrical ratings are
also shown on applicable circuit
breaker accessory nameplates.
Adder
U.S. $
Suffix
Number
NO4
NO8
—
—
Adder
U.S. $
Catalog
Number
LST1LPK
LST1RPK
LST2LPK
LST2RPK
Price
U.S. $
Catalog
Number
LST1LTK
LST1RTK
—
—
Price
U.S. $
45
—
—
—
—
LST3LPK
LST3RPK
LST4LPK
LST4RPK
—
—
—
—
CA08102001EFor more information visit: www.EatonElectrical.com
voltage (typically a line
voltage) and trips the cir-
age falls to between 70 and 35 percent
of the solenoid coil rating.
The undervoltage release mechanism
consists of a continuous rated solenoid with a plunger and tripping lever
mounted in a plug-in module. The tab
on the tripping lever resets the undervoltage release mechanism when
normal voltage has been restored and
the circuit breaker handle is moved to
the reset (or OFF) position. With less
than pickup voltage applied to the
undervoltage release mechanism, the
circuit breaker contacts will not touch
when a closing operation is attempted.
Note: Undervoltage release mechanism
accessories are not designed for, and
should not be used as, circuit interlocks.
Ordering Information
Select handle reset undervoltage
release mechanism catalog number
for the voltage within the indicated
voltage range. Undervoltage release
mechanism coils are designed to be
applied at specific ac or dc voltages
within the voltage range shown on
applicable circuit breaker accessory
nameplates.
cuit breaker when the volt-
Table 45-217. F-Frame Electrical Rating Data
50/60 Hzdc
Supply
Voltage
12 4.2 6.3 7.61.3
24 8.4 16.8 20.41.4 24 8.4 16.8 20.41.6
48
60
110
120
127
208
220
240
380
415
440
480
525
550
600
Dropout
Voltage
Minimum Maximum MaximumMinimum Maximum Maximum
21.0 33.6 40.81.2
44.5 77.0 93.51.3
84.0145.6176.82.2
168.0266.0323.02.9
210.0367.0446.04.3
Endurance: 6,000 electrical operations plus 4,000 mechanical operations.
Pickup
Voltage
Table 45-218. J-Frame Electrical Rating Data
50/60 Hzdc
Supply
Voltage
12 4.2 8.4 10.21.9 12 4.2 8.4 10.21.6
24 8.4 16.8 20.43.9 24 8.4 16.8 20.43.1
48
60
110
120
127
208
220
240
380
415
440
480
Dropout
Voltage
Minimum Maximum MaximumMinimum Maximum Maximum
21.0 33.6 40.82.5
44.5 77.0 93.51.8
84.0145.6176.82.7
168.0266.0323.03.4
Endurance: 6,000 electrical operations plus 2,000 mechanical operations.
For electrical rating data for manual, automatic and electrical reset undervoltage release
mechanisms, refer to Eaton.
Pickup
Voltage
VA Supply
Voltage
12 4.2 8.4 10.22.8
2.5
48
1.9
60
110
1.5
120
1.7
125
220
2.4
250
2.9
—
—
3.5
—
3.9
—
4.6
—
—
4.8
—
5.8
—
VA Supply
Voltage
48
3.8
60
110
2.1
120
2.4
125
220
3.1
250
3.8
—
—
4.0
—
4.6
—
5.4
—
Dropout
Voltage
21.0 33.6 40.81.3
44.5 77.0 93.51.5
87.5
—
—
—
—
—
—
—
—
Dropout
Voltage
21.0 33.6 40.82.0
44.5 77.0 93.51.6
87.5
—
—
—
—
—
154.0
—
—
—
—
—
—
—
—
154.0
—
—
—
—
—
Pickup
Voltage
187.0
—
—
—
—
—
—
—
—
Pickup
Voltage
187.0
—
—
—
—
—
VA
2.0
1.7
1.9
2.6
3.4
—
—
—
—
—
—
—
—
VA
3.1
1.9
2.2
3.1
4.0
—
—
—
—
—
For more information visit: www.EatonElectrical.comCA08102001E