45-26
Circuit Breakers & Supplementary Protectors
250 – 630 Amperes
August 2006
LG-Frame
LG-Frame
Typical LG-Frame Circuit Breaker
Interrupting Capacity Ratings
Table 45-41. UL 489/IEC 60947-2 Interrupting Capacity Ratings
Circuit
Breaker
Type
LGE630 3, 4 65 65 35 35 35 18 12 6 10 10 10
LGS630 3, 4 85 85 50 50 50 25 20 10 22 22 22
LGH630 3, 4 100 100 70 70 65 35 25 13 42 42 35
LGC630 3, 4 200 200 100 100 100 50 30 15 42 42 42
LGU630 3, 4 200 200 150 150 150 65 35 18 42 42 42
LGX630 3, 4 300 200 200 200 200 65 35 18 50 50 50
Number
of Poles
dc rating apply to substantially non-inductive circuits.
2-pole circuit breaker, or two poles of 3-pole circuits.
Time constant is 3 milliseconds minimum at 10 kA and 8 milliseconds minimum at – kA.
3-poles in series. 750 Vdc ratings available (4-poles in series, not UL listed). Contact Eaton.
Interrupting Capacity (kA rms Symmetrical Amperes) (kA)
Volts ac (50/60 Hz)
240 – 240 380 – 415 480 600 690 250
Icu Ics Icu Ics Icu Ics Icu Ics
Volts dc
600
45
For more information visit: www.EatonElectrical.com CA08102001E