IEC Contactors & Starters
Freedom MMPs & Manual and Combination Motor Controllers
March 2009
Types A307, A308, A309 Manual Motor Protectors
Product Selection
Product Selection for Group Motor Installations
34-295
When ordering, specify Catalog Numbers
according to the following stipulations:
A307, A308 and A309 Manual Motor
Protectors are selected based on the
overload current range required for a
given motor. This current range is
determined from the motor Full Load
Ampere rating and Motor Service Factor
usually found on the motor nameplate.
For motors with service factors less
than 1.15, multiply the motor FLA by
.92 to select appropriate MMP.
Example: For motor having FLA
of 6.4A and service factor of 1.0
(6.4A x .92 = 5.88A) select Catalog
Number A307TN.
See Application Note — AP03402001E.
Table 34-385. Group Motor Installations
—
—
—
—
—
—
—
—
1
1-1/2
1-1/2
2
3
5
5
7-1/2
7-1/2
10
15
15
15
10
15
20
25
30
30
40
30
40
50
60
75
75
1/2
3/4
3/4
—
—
—
—
—
—
—
1
1-1/2
1-1/2
2
3
3
5
5
10
10
15
20
20
20
15
20
25
30
40
40
50
40
50
60
75
100
100
Maximum
Short Circuit
Current Rating
65 kA
65 kA
65 kA
65 kA
65 kA
65 kA
65 kA
1/2
65 kA
1/2
65 kA
3/4
65 kA
65 kA
65 kA
65 kA
65 kA
65 kA
65 kA
65 kA
65 kA
65 kA
65 kA
65 kA
65 kA
65 kA
65 kA
65 kA
65 kA
65 kA
65 kA
65 kA
65 kA
65 kA
65 kA
65 kA
65 kA
65 kA
65 kA
65 kA
30 kA
30 kA
30 kA
30 kA
30 kA
30 kA
30 kA
30 kA
30 kA
30 kA
30 kA
30 kA
30 kA
30 kA
30 kA
30 kA
30 kA
30 kA
30 kA
30 kA
10 kA
10 kA
10 kA
10 kA
25 kA
25 kA
25 kA
25 kA
25 kA
25 kA
25 kA
30 kA
30 kA
30 kA
30 kA
10 kA
10 kA
Catalog
Number
A307AN
A307BN
A307CN
A307DN
A307EN
A307FN
A307GN
A307HN
A307JN
A307KN
A307LN
A307MN
A307NN
A307PN
A307RN
A307SN
A307TN
A307UN
A307VN
A307WN
A307XN
A307YN
A307ZN
A307Z25N
A308LN
A308MN
A308NN
A308PN
A308RN
A308SN
A308TN
A309RN
A309SN
A309TN
A309UN
A309VN
A309WN
FLA
Adjustment
Range
Single-Phase
hp Ratings
115V 230V 200V 230V 460V 575V 460V 600V
Three-Phase hp Ratings
A307
0.11 – 0.16
0.14 – 0.2
0.18 – 0.25
0.22 – 0.32
0.28 – 0.4
0.35 – 0.5
0.45 – 0.63
0.55 – 0.8
0.7 – 1
0.9 – 1.25
1.1 – 1.6
1.4 – 2
1.8 – 2.5
2.2 – 3.2
2.8 – 4
3.5 – 5
4.5 – 6.3
5.5 – 8
7 . – 10
9 – 12.5
11 – 16
14 – 20
17 – 22
20 – 25
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
1
1-1/2
2
2
1/6
1/4
1/3
1/2
1/2
—
—
—
—
—
—
—
—
—
—
—
—
1
1-1/2
2
3
3
3
5
1/6
1/4
1/3
1/2
3/4
—
—
—
—
—
—
—
—
—
—
—
—
1
1-1/2
2
3
3
5
5
7-1/2
7-1/2
1/2
3/4
3/4
—
—
—
—
—
—
—
—
—
—
—
—
1/2
3/4
1
1
1-1/2
2
3
3
5
7-1/2
7-1/2
7-1/2
A308
11 – 16
14 – 20
18 – 25
22 – 32
28 – 40
36 – 45
40 – 50
1
1-1/2
2
3
3
5
5
3
3
5
5
7-1/2
7-1/2
10
5
5
7-1/2
10
15
15
15
5
7-1/2
10
10
15
15
20
A309
28 – 40
36 – 50
45 – 63
57 – 75
70 – 90
80 – 100
Select Manual Motor Protectors for use with group motor installations by full load amperes.
Horsepower ratings are for reference only.
3
5
5
7-1/2
10
10
7-1/2
10
15
15
20
25
15
15
15
20
20
25
25
25
30
30
40
40
34
A307
Price
U.S. $
A308
A309
For motor with service factor of 1.15
or greater, use motor nameplate Full
Load Amperes to select the appropriate
MMP.
Example: For motor having FLA of
6.4A and service factor of 1.15, select
Catalog Number A307UN.
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . 1CD-1
34
IEC Contactors & Starters
Freedom MMPs & Manual and Combination Motor Controllers
Types A307, A308, A309 Manual Motor Protectors
Product Selection for UL 508 Type E Self-Protected Manual Combination
Starter Applications
When ordering, specify Catalog Numbers
according to the following stipulations:
A307, A308 and A309 Manual Motor
Protectors are selected based on the
overload current range required for a
given motor. This current range is
determined from the motor Full Load
Ampere rating and Motor Service Factor
usually found on the motor nameplate.
Table 34-386. UL 508 Type E Self-Protected Manual Combination Starters
FLA
Adjustment
Range
A307
0.11 – 0.16
0.14 – 0.2
0.18 – 0.25
0.22 – 0.32
0.28 – 0.4
0.35 – 0.5
0.45 – 0.63
0.55 – 0.8
0.7 – 1
0.9 – 1.25
1.1 – 1.6
1.4 – 2
1.8 – 2.5
2.2 – 3.2
2.8 – 4
3.5 – 5
4.5 – 6.3
5.5 – 8
7 . – 10
9 – 12.5
11 – 16
14 – 20
17 – 22
A308
11 – 16
14 – 20
18 – 25
22 – 32
28 – 40
36 – 45
40 – 50
A309
28 – 40
36 – 50
45 – 63
57 – 75
70 – 90
80 – 100
A C320LSA1 Line Side Adapter is required to be installed on the line side of all A307 MMPs when
they are used as non-Group Installation Self-Protected Manual Combination Starters. See Page
34-299.
A C320LSA2 Line Side Adapter is required to be installed on the line side of all A309 MMPs when
they are used as non-Group Installation Self-Protected Manual Combination Starters. See Page
34-299.
Select UL 508 Type Manual Combination Starter by full load amperes. Horsepower ratings are for
reference only.
A308 MMPs do not require Line Side Adapters.
Note: A UL 508 Type F Combination Motor Controller consists of a UL 508 Type E Self-
protected Manual Combination Starter, a UL Listed Contactor and a UL Listed Line Side Adapter
(depending on the application). The Type E Self-Protected Manual Combination Starter alone is
a legitimate short-circuit protective device and disconnect means for the downstream motor,
while the contactor has been added to provide remote operation of the motor circuit.
Single-Phase
hp Ratings
115V 230V 200V 230V 460V 575V 240V
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
1/6
1/4
1/3
1/2
1/2
1
1-1/2
2
1
1-1/2
2
3
3
5
5
3
5
5
7-1/2
10
10
Three-Phase hp Ratings
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
1/6
1/2
1/4
3/4
1/2
3/4
1/2
1
3/4
1-1/2
1
2
1-1/2
3
2
3
3
5
3
5
3
7-1/2
3
5
3
5
5
7-1/2
5
10
7-1/2
15
7-1/2
15
10
15
7-1/2
15
10
15
15
20
15
25
20
30
25
40
—
—
—
—
—
—
—
—
—
—
—
—
1/2
3/4
1
1
1-1/2
2
3
3
5
7-1/2
7-1/2
5
7-1/2
10
10
15
15
20
15
20
25
25
30
40
For motors with service factors less
than 1.15, multiply the motor FLA by
.92 to select appropriate MMP.
Example: For motor having FLA
of 6.4A and service factor of 1.0
(6.4A x .92 = 5.88A) select Catalog
Number A307TN.
See Application Note — AP03402001E.
—
—
—
—
—
—
—
—
1
1-1/2
1-1/2
2
3
5
5
7-1/2
7-1/2
10
15
15
10
15
20
25
30
30
40
30
40
50
60
75
75
1/2
3/4
3/4
—
—
—
—
—
—
—
1
1-1/2
1-1/2
2
3
3
5
5
10
10
15
20
20
15
20
25
30
40
40
50
40
50
60
75
100
100
Maximum
Short Circuit
Current Rating
480Y/
277V
65 kA
65 kA
65 kA
65 kA
65 kA
65 kA
65 kA
1/2
65 kA
1/2
65 kA
3/4
65 kA
65 kA
65 kA
65 kA
65 kA
65 kA
65 kA
65 kA
65 kA
65 kA
65 kA
65 kA
65 kA
65 kA
65 kA
65 kA
65 kA
65 kA
65 kA
65 kA
65 kA
65 kA
65 kA
65 kA
65 kA
65 kA
65 kA
600Y/
347V
30 kA
30 kA
30 kA
30 kA
30 kA
30 kA
30 kA
30 kA
30 kA
30 kA
30 kA
30 kA
30 kA
30 kA
30 kA
30 kA
30 kA
30 kA
30 kA
30 kA
10 kA
10 kA
10 kA
25 kA
25 kA
25 kA
25 kA
25 kA
25 kA
25 kA
30 kA
30 kA
30 kA
30 kA
10 kA
10 kA
Catalog
Number
A307AN
A307BN
A307CN
A307DN
A307EN
A307FN
A307GN
A307HN
A307JN
A307KN
A307LN
A307MN
A307NN
A307PN
A307RN
A307SN
A307TN
A307UN
A307VN
A307WN
A307XN
A307YN
A307ZN
A308LN
A308MN
A308NN
A308PN
A308RN
A308SN
A308TN
A309RN
A309SN
A309TN
A309UN
A309VN
A309WN
Price
U.S. $
A307
A308
A309
For motor with service factor of 1.15
or greater, use motor nameplate Full
Load Amperes to select the appropriate
MMP.
Example: For motor having FLA of
6.4A and service factor of 1.15, select
Catalog Number A307UN.
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . 1CD-1