Cutler Hammer, Div of Eaton Corp A307, A308, A309 General Product Line Information

IEC Contactors & Starters
Freedom MMPs & Manual and Combination Motor Controllers
Types A307, A308, A309 Manual Motor Protectors
March 2009
34
Contents
Description Page
Manual Motor Protectors
Standards and
Certifications . . . . . . . . . . . 34-294
Note: For more information, see CA03801001E.
A307, A308 and A309 Manual Motor Protectors
Product Description
The Cutler-Hammer® A307, A308 and A309 family of Manual Motor Protec­tors (MMPs) from Eaton’s electrical business feature a rotary ON/OFF manual disconnect, Class 10 adjust­able bimetallic overload relay and fixed magnetic short circuit trip capa­bility in one compact unit. Three
frame sizes are available: A307 (45 mm)
for motors with FLA ratings up to 25A,
A308 (55 mm) covers motor FLA ratings up to 50A and the A309 (70 mm) is suit­able for motor FLA ratings to 100A.
Application Description
The A307, A308 and A309 MMPs can be used in the following applications:
Manual Motor Protectors
All of the MMPs are UL Listed under UL508 as Manual Motor Controllers. They provide an economical solution for applications requiring simple man­ual starting and stopping of motors. When used as an MMP, they are typically installed in an enclosure. IP55 enclosures are offered as acces­sories for the MMPs. Separate short­circuit protective devices, such as circuit breakers or fuses, are wired ahead of the MMPs. The short-circuit protective device should be sized per the NEC code and should not exceed 400% of the maximum FLA dial setting of the MMP.
Group Motor Installations
A Group Motor Installation can be defined as more than one motor circuit protected by a single set of fuses or cir­cuit breaker on a motor branch circuit. This eliminates the need for individual fuses or circuit breakers for each motor circuit. Substantial component cost savings, panel space savings and reduced wiring installation time can be achieved in Group Motor Installations.
Table 34-384. Short Circuit Ratings
Description Specification
UL 508 Type E Manual Combination Starter/Motor Controller
A307
A308
A309
See Pages 34-295 – 34-296 for individual ratings.
65 kA @ 240V, 480Y/277V 30 kA @ 600Y/347V up to 12.5A
65 kA @ 240V, 480Y/277V 25 kA @ 600Y/347V
65 kA @ 240V, 480Y/277V 30 kA @ 600Y/347V up to 75A
Features
ON/OFF Rotary Handle with Lockout
Provision
Visible Trip Indication
Class 10 Overload Protection
Phase Loss Sensitivity
Ambient Temperature Compensation
to 140°F
Fixed Short Circuit Trip — 13 times
maximum setting of overload FLA dial
Type 2 Coordination per IEC 947
Identification Markers Standard on
Starter Faceplate
Motor Applications from 0.11A to
100A
Built-in heater and magnetic trip
elements to protect the motor
Adjustment dial for setting motor
FLA
DIN Rail or Panel Mount
Accessories include:Front and Side Auxiliary Contacts
Trip Indicating ContactsTamperproof Cover for OLR DialUndervoltage ReleaseShunt TripThru-the-Door OperatorsEnclosures3-Phase Line Side Connecting
Links
Standards and Certifications
UL File No. E176513, Category NKJH
(A307, A308, A309) UL File No. E37317, Category NKCR (Accessories)
CSA File LR12530, Class 3211-05
IEC 947-1; IEC 947-2; IEC947-4-1
DIN VDE 0660 Part 100, Part 101 and
Part 102
Instructional Leaflets
IL49490 — A307 Manual Motor
Protectors
IL49491 — A308 Manual Motor
Protectors
IL49492 — A309 Manual Motor
Protectors
IL49493 — C320TR11 Trip Indicating
Contacts
IL49494 — IP55 Enclosures and Front
Plates
IL49495 — C320HN Thru-the-Door
Operators
IL49496 — Indicating Lights
See Application Note — AP03402001E.