33-194
33
NEMA Contactors & Starters
A200
Accessories
Factory Modifications
Table 33-248. A200 Factory Modifications
Modifications Description Catalog
Control
Circuit
Overload
Relays
(Substitutions)
1 Extra Auxiliary Contact (1NO-1NC)
Non-reversing,
Reversing, 2-Speed Unwired
2 Extra Auxiliary Contact
Non-reversing,
Reversing, 2-Speed Unwired
3 Extra Auxiliary Contact
Non-reversing, Unwired
4 Extra Auxiliary Contact
Non-reversing, Unwired
Wired for Separate Control (NC) C
Omit Control Wiring (NC) X
Ambient Compensated with
Auto Reset (NC)
Fast Trip — Ambient Compensated
(Specify Motor FLA)
Overload Relay Alarm Contact
(NO) per overload
Number
Suffix
J1
J2
J3
J4
D
D7
E
February 2008
NEMA Size
00 – 123456789
Adder U.S. $
Accessories and Field Modification Kits
■ Provides two separate electrical
contact sets which wire vertically
and are color coded; black designates NC and silver designates NO.
Please note that the vertical wiring
is contrary to the horizontal wiring
of the L-56 auxiliary contacts.
■ Designed to fit within dimensions of
starter; no additional panel space is
required.
■ Provides circuit isolation (no polar-
Type J Auxiliary Contact
Type J Auxiliary Contact
■ Capable of being field mounted in a
contactor or starter (Classes A200,
A900 Sizes 00 – 6, V200, V201 vacuum
and definite purpose controllers).
ity restrictions) and single break
bifurcated contacts.
Table 33-249. Auxiliary Contact Ratings
Voltage Make Break
NEMA A600
120 – 600V AC
72 – 120V AC
28 – 72V AC
NEMA R300
28 – 300V DC 28 VA 28 VA
7200 VA
60A
60 VA
720 VA
720 VA
10A
Table 33-250. Auxiliary Contact Types
Contact
Type
1NO and 1NC
2NC
2NO
1 Coil Clearing
NC and 1NO
Max. Catalog
Number
4
J11
4
J02
4
J20
4
J1C
Price
U.S. $
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . 1CD1C
For more information visit: www.eaton.com CA08102001E
February 2008
NEMA Contactors & Starters
A200
Accessories
33-195
SS-56 Surge Suppressor
SS-56 Surge Suppressor
■ Designed to be used with magnetic
motor controllers through Size 4 in
120V, 60 Hz control circuit applications where electronic equipment is
used.
■ Steady State Coil Volts: 120, 60 Hz,
RMS
■ Peak Input Volts: 169.6, 60 Hz,
Max. Amplitude
■ Max. Ambient Temperature: 65°C
■ Nominal Limiting Volts: 270 Peak
■ Nominal Rate of Volt Rise:
.5 per mS
Table 33-251. Surge Suppressor
Type Mounting Kit Catalog
Starter SS-56
Can be used on Sizes 5 and 6 with 120V coil.
Mounting bracket required — order separately. Mounting Bracket 177C043G04.
Discount Symbol 1CD1.
Number
Price
U.S. $
Mechanical Interlock
■ Prevents closing of one member of
a reversing or multi-speed contactor
until the opposite member is completely open.
Table 33-254. Mechanical Interlock
Contactor Arrangement
(Number of Poles,
Horizontal or Vertical)
3 x 3 Horizontal
4 x 4 Horizontal
5 x 3 Horizontal
All Pole Combination, Vertical
3 x 3 Horizontal Reversing
3 x 3 Vertical Reversing
5 x 3 Horizontal
4 x 4 Horizontal
All Pole Combination Horizontal
All Pole Combination Vertical
F-56 Fuse Block
■ Facilitates installation of fuses (15A,
600V max.) in control circuits.
■ Utilizes Bussman type KTK fuses,
or equivalent.
■ Mounts in same cavity as Type J
auxiliary contact.
■ No tools or mounting hardware
needed.
■ Fuse not included.
Table 33-252. Fuse Block
Mounting Kit Catalog
Starter
Panel
Number
F56
F56-P
R-56 Interposing Relay
The R-56AA interposing relay is a low
energy solid-state device with a single
NO solid-state contact. It can be used as
a 120V AC control relay, and will operate on as little as 40V AC input. Is useful
in applications requiring long control
wiring runs where excessive voltage
drop would prevent the contactor or
relay from energizing. Will operate a
Size 4 contactor from 10,000 feet using
18 AWG wire.
Table 33-253. Interposing Relay
Type
Mounting
Starter or Panel R56-AA
Discount Symbol 1CD1.
■ Lever type mechanism assures posi-
tive action.
■ Can be factory assembled or field
mounted on A200 and A900 starters
and contactors.
Continuous
Size
0, 1
0, 1
0, 1
0, 1
2
2
2
2
3, 4
3, 4
Interlock
Catalog
Number
M-33-1B
M-33-1B
M-33-1B
M-34-1A
M-33-2B
M-34-2A
M-35-2A
M-36-2A
M-33-3B
M-34-3
Kit Catalog
Number
Price
U.S. $
Price
U.S. $
Price
U.S. $
B3NO Bell Alarm Contact
■ Isolated Normally Open Bell Alarm
Contact.
■ Mounts in Type B block-type over-
load relay.
Table 33-255. Bell Alarm Contact
Kit Catalog
Number
B3NO-2
B3NO-4
For Size 3 and 4.
Price
U.S. $
33
Table 33-256. Control Contact Ratings (B600)
AC Volts Maximum Amperes
Make Break
24 – 120
121 – 600
Continuous Current Rating: 5A
30
3600 VA
3.00
360 VA
Overload Relay Reset Extension
■ Used to adjust overload reset rod
depth of Class A200 Model J starters
and current design overload relays
to same dimensions as obsolete
B200 starters and overloads identified by suffix B, i.e., BA13B.
When replacing obsolete B200 device
with Class A200 starter and Type B
overload, order Style 6710C11H03. No
charge.
When replacing obsolete B200 device
with Class A200 starter and Type A
overload, order Style 1490C15H10. No
charge.
Power Pole Kit
■ Adds 1NO or 1NC power pole to
Size 00 – 1 A201 Class contactors.
■ Factory installed or field mountable
in load side auxiliary cavities.
■ 600V AC.
■ Continuous current rating of 18A for
Size 0, 27A for Size 1.
Table 33-257. Power Pole Kit
Continuous
Current
Rating
Normally Open
18
27
Normally Closed
18
27
Do not use with DC operated contactors.
Kit
Size
0
1
0
1
Kit
Catalog
Number
PN0-0
PN0-1
PNC-0
PNC-1
Price
U.S. $
CA08102001E For more information visit: www.eaton.com
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . 1CD1C