Page 1 of 5
208V output, 50/60 Hz bundles
(1) L6-30R, (2) L6-20R,
(2) 6-20R
Double-conversion, online
Full system self-test at power up, ABM battery test every 30 days
2 years electronics and battery
Remote On/Off (ROO) and Remote Power Off (RPO) rear terminal blocks
Contents
(Ships with the
following items)
UPS
Safety guide
Quick Start Guide
Reference guide
Output cables (for G models)
C19 to L6-20P input cables (for 9SX2000G, 9SX3000G, 9SX3000GL)
Cable lockers (for G models)
RS-232 serial cable
USB cable
208V default (200/208/220/230/240V)
120V default (100/110/120/125V)
Full load: 190-276V,
<25% load: 120-276V
Full load: 100-138V,
<25% load: 60-144V
60 Hz: 50–70 Hz, 50 Hz: 40–60 Hz
Eaton 9SX UPS technical specifications
Model overview
Additional specifications
Due to continuing product improvement programs, specifications are subject to change without notice.
Input line cord is 8 feet long.
C19 to L6-20P input connector is 8 feet long.
TD153028EN
Page 2 of 5
9SX1000G:
1000VA / 900W
9SX1500G:
1500VA / 1350W
9SX2000G:
220/230/240V: 2000VA / 1800W
208V: 1800VA / 1620W
200V: 1600VA / 1440W
9SX3000G & 9SX3000GL:
220/230/240V: 3000VA / 2700W
208V: 2700VA / 2430W
200V: 2400VA / 2160W
9SX700:
700VA / 630W
9SX1000:
1000VA / 900W
9SX1500:
120/125V: 1500VA / 1350W
110V: 1350VA / 1215W
100V: 1200VA / 1080W
9SX2000:
120/125V: 1960VA / 1770W
110V: 1764VA / 1593W
100V: 1568VA / 1416W
9SX3000 & 9SX3000HW:
120/125V: 3000VA / 2700W
110V: 2700VA / 2430W
100V: 2400VA / 2160W
2200VA: None
3000VA: None
2000VA: None
3000VA: (3) 20A for (2) 5-20R each
208V default (200/208/220/230/240V)
120V default (100/110/120/125V)
Output voltage
regulation, steady
state
Output Voltage THD
(online)
Efficiency
(online mode
with resistive load)
9SX1000G: 88%
9SX1500G: 91%
9SX2000G: 92%
9SX3000G: 92%
9SX3000GL: 92%
9SX700: 87%
9SX1000: 88%
9SX1500: 88%
9SX2000: 88%
9SX3000: 89%
9SX3000HW: 89%
Optional extended
battery module (EBM)
9SX2000
9SX2000G
9SX3000
9SX3000HW
9SX3000G
9SX3000GL
9SXEBM96
Maximum number of
Sealed, lead-acid; maintenance free
ABM technology; 3-stage charging extends battery service life up to 50% and provides
advance warning for battery replacement
Hot-swappable internal batteries and EBMs
Cold-start enabled; first cold start is always forbidden
Graphical display. UPS status in a single view.
RS-232 (RJ45) ports; USB port as standard (HID). 6-foot RS-232 and USB cables included
TD153028EN