9PX6KP1
Eaton 9PX rack/tower UPS. 6000 VA/5400W, 120/208V, L6-30 input; (1) L14-30R, (1) L14-30R, (6) 5-20R output ENERGY STAR® qualified UPS
General
Topology Double-conversion online
Configuration Rack/Tower
Catalog Number 9PX6KP1
Color Black and silver
Rating (VA/Watts) 6000/5400
Diagnostics Full system self test at power up
Efficiency 93% with resistive load
UPS Bypass Internal to PPDM
Dimensions (H x W x D, inches) 10.2 (6U) x 17.3 x 28.4
Dimensions (H x W x D, mm) 259 (6U) x 439 x 721
Weight (kg) 91
Weight (lbs) 203
Warranty 2 years
Rail Kit Included 4-post rail kit and tower pedastals included
Remote Emergency Power off (REPO) ROO/RPO: Rear deck emergency stop connectors (for remote on/off and power off)
Contents
(Ships with the following items)
Electrical Input
Connection
9PX6K 6 kVA UPS
9PXPPDM1 PowerPass Distribution Module
Network-MS Web/SNMP card
4-post rail kit
User manual
Quick start guide
Tower pedestals
Intelligent Power Software Suite CD
RS-232 serial cable
USB cable
Cable gland for hardwire connection
Phillips head screw driver
(1) NEMA L6-30P
(6) NEMA 5-20R (1) NEMA L6-30R (1) NEMA L14-30R
Input Cord 6 feet (1.8 meters)
Input Voltage Range Full load: 176-276V, Derating: 100-276V
Nominal Voltage 120/208V default (200/208/220/230/240V)
Frequency 50/60 Hz
Frequency Range 60 Hz: 50–70 Hz, 50 Hz: 40–60 Hz
Input Power Factor >99
Input Current Distortion <5%
Electrical Output
Nominal Voltage 120/240V default (200/208/220/230/240V)
Output voltage regulation ±1% steady-state
Voltage THD <2% for linear loads
Output Receptacles
Power Factor 0.9
Transfer Time 0 ms
Circuit Breaker (1) 30A for L6-30R; (1) 30A for L14-30R; (2) 20A for 5-20R
Battery
Optional Extended Battery Module 9PXEBM180RT
Battery Description Sealed, lead-acid; maintenance free
Maximum number of extended battery
modules (EBM)
Add up to 4 extended battery modules (EBM)
Battery Management ABM technology; 3-stage charging extends battery service life by 50% and provides advance warning for battery replacement
Battery Replacement Hot-swappable internal batteries and extended battery modules (EBMs)
Start On Battery Cold-start enabled; first cold start is always forbidden
Communications
User Interface Graphical display. UPS status in a single view.
Runtime
(minutes)
Load (watts)
Show:
Standard runtime
with 1 ebm
with 2 ebms
with 3 ebms
with 4 ebms
Mouseover graph for
detailed runtime values
1000 2000 3000 4000 5000
0
100
200
300
400
500
600
700
800
Standard
runtime
with 1 ebm
with 2 ebms
with 3 ebms
with 4 ebms
Battery runtimes are approximate and may vary with equipment, configuration, battery age, temperature, etc.