2. Connect the high llne of the control power to terminal 4 and the grounded side of the control power trans-former to terminal 7 (see Figure A).
3.
Connect a separate earth ground from terminal 5 to the system ground bus. This connection must be a dedicated connection. DO NOT CONNNECT TERMI-
NAL 5 TO TERMINAL 7.
4.
In
order to disable the Incomplete Sequence func-tion, jumper terminal 4 to 10 and terminal 6 to These jumpers are installed at the factory. If the Incomplete Sequence function is not to be disabled then see Figure A for wiring detalls.
II
on a 120
VAC
7.
9.
5. TERMINAL 6 IS ONLY TO BE USED FOR THE
JUMPER CONNECTION TO TERMINAL 9.
6.
TERMINAL 5 IS ONLY TO BE USED FOR A DIRECT CONNECTION TO THE SYSTEM GROUND BUS. DO NOT USE TERMINALS AS A GROUNDING POINT FOR ANY OTHER DEVICE.
IQ-1000
Upgrading an IQ-1000 with an IQ-1000 control power system:
1.
DO NOT JUMPER terminals 5 to
2.
Connect the high line of the control power to terminal 4 and the grounded side of the control power trans-former to terminal 7 (see Figure A).
3.
Connect a separate earth ground from terminal 5 to the system ground bus. This connection must be a dedicated connection. DO NOT CONNECT TERMI-
NAL 5 TO TERMINAL 7.
4.
In
order to disable the Incomplete Sequence func-tion, jumper terminal 4 to 10 and terminal 6 to These jumpers are installed at the factory. If the Incomplete Sequence function is not to be disabled then see Figure A for wiring details.
5.
TERMINAL 6 IS ONLY TO BE USED FOR THE JUMPER CONNECTION TO TERMINAL 9.
II
UPGRADE
II
on a 240
6.
6. TERMINAL 5 IS ONLY TO BE USED FOR A
DIRECT CONNECTION TO THE SYSTEM
GROUND BUS.
GROUNDING POINT FOR ANY OTHER DEVICE.
DO
NOT USE TERMINALS
VAC
9.
AS
A
Effective
February
1999
Page
Courtesy of NationalSwitchgear.com
TD
B
0
17297D
0
®
1°
l::::.~ol
@'"oo
~@
@~
x::::u@
@~ ~@
@~
8@
®I
0
'
0,:
~
..J C
"'
~~t:;
~),i
Q Cl 0,:
UQ.>-
.
]L
•
~
~
~
I
.......
,01
Ml~~~l~~~~~~~~~I
@ DDDDDD
@
-
=I
!1
i
~~
@
DDDDDD DDDDDD DDDDDD DDDDDD DDDDDD
0
®
DDDDDD
,~~~~~~
101
I
II II
Yf1A
;~
;~
J l l I
l
-
-L.. -
~i
--
t.J
"'!i
!!I-
'flt
~~
I~
;~
--
]
L..
®
~:
Jo
,
\~b
D!~
c>
Iii~
-ru
;,,
uo,:
Fig.
A Wiring Diagram for IQ-1000 II Upgrade
Effective
February
1999
TD
Courtesy of NationalSwitchgear.com
17297D
All
possible contingencies which
variations
by
purchaser regarding his particular installation, operation
door-mounted, motor protection device which may be applied to 50 Hz or 60 Hz 3-phase motor starters or switch gear, including low-, medium-, and high-voltage equipment.
II
The IQ-1000
develop separate RTD Module option allows the IQ-1000 combine the monitored motor stator temperature with the motor current information. The resulting combination of data allows the IQ-1000 ture of the motor's temperature, thereby maximizing motor utilization.
The IQ-1000 takes the motor off-line when it detects a problem such as an overcurrent or over temperature condition. If operating parameter exceeds its setpoint value, the IQ-
1000
II
initiates a trip condition.
1.1
CONTENTS/USE OF MANUAL -This manual
contains the following sections:
A-
IQ-1000
monitors 3-phase
an
accurate thermal model of motor heating. A
11
operates by monitoring motor current, and
To
IQ-1000
IQ-1000
11™
is a self-contained,
AC
motor currents to
II
to
II
to develop a more detailed pic-
an
II
Upgrade.
1 -Introduction.
2 -Hardware Description. Itemizes the hardware fea-tures and lists the specifications of the IQ-1000
II.
characteristics as well as set point and control back-ground information are included.
8-
Programming the IQ-1000
Description. Lists the various application considerations
associated with each of the functions of the IQ-1000 Available setpoint ranges or settings are detailed.
9 -Troubleshooting. Provides background information on
how to use the Operator Panel to recognize malfunc-
tions. Also, a specific troubleshooting approach is listed. The manual is broad enough
familiarization, refresher training sessions, and ongoing maintenance, installation, troubleshooting and unit replacement (if necessary) of the IQ-1000
This manual contains information of specific importance tor the user application engineer who is planning the motor control system and who is determining the setpoint values for the IQ-1000
It
is strongly advised that the application engineer care-fully read Sections 2 thru 8 before beginning the applica-tion's Wiring Plan Drawings and Set Point Record Sheet.
Installation teams should carefully read all of Section Installation, and all previous sections, before starting final installation. Maintenance personnel should be familiar with Sections 2 thru 9 before attempting to service the
IQ-1000
II.
II.
II
And Set Point
in
scope for new employee
11.
11.
5,
3 -Functional Theory. Describes how the hardware and software function together to control, monitor, and protect the motor.
4 -Operator Panel. Describes the uses of the Operator Panel. Various operations such as loading setpoints examining metered data are described.
5 -Installation. Outlines the installation procedures to be followed by a plant electrician or wiring crew when installing the IQ-1000
6 -Startup. Lists step-by-step procedures to follow
when first applying power to the IQ-1000 7
-Application
the application engineer considering how and when to
apply the various features of the IQ-1000
Effective
February
1999
II.
Considerations. Intended as an aid to
II.
II.
Hardware
or
1.2 PRODUCT OVERVIEW -The IQ-1000 operating setpoints, each referred to as a function. The setpoints associated with these functions are individually entered through the Operator Panel located of the IQ-1000
The functions consist of the following types of entries:
• Alarm Relay condition settings. An Alarm Relay closes when various conditions, such as motor cur-rents or temperatures, exceed the selected setpoints. The alarm serves as an early warning. The motor's operation is not affected.
• Trip Relay condition settings. A Trip Relay closes (or opens) when various conditions, such as motor current or temperature, exceed separately selected setpoints. Action of the Trip Relay is user-selectable.
II.
II
offers 52
on
the front
Page
Courtesy of NationalSwitchgear.com
8
TD
172970
• Auxiliary Trip Relay condition setting. The auxil-
iary Trip Relay changes state when a user-selected condition, such as Instantaneous Overcurrent, exceeds a separately selected setpoint. Action of the Auxiliary Trip Relay is user-selectable.
• Specific application-related information. Entries
such as the ratio of the current transformers or the incoming 1000
Together, the functions tailor the IQ-1000 cific application. After entry is completed, the setpoint values can be examined or modified. The actual values are stored batteries or special power supplies. particular function is not required, it can usually be bypassed by entering a specific disable value.
AC
line frequency are required by the IQ-
II
to properly monitor the motor.
11
for each spe-
in
a non-volatile memory requiring no backup
In
instances where a
1.3 OPTIONS -Options associated with the IQ-1000
consist of external hardware. The following options are available:
•
RTD
Module Option. The RTD Module option
required when resistance temperature devices (RTD) are used to monitor motor winding, load and/or motor bearing temperatures. An auxiliary is
provided on the RTD Module for monitoring one
additional location (such as motor case temperature).
RTD
• Communications Option. The IQ-1000
municate motor data/status to a remote device such as a computer with the PowerNet network.
• IQ
DC
Power Supply -The IQ DC Power supply is
required only when 40 power is available.
an
optional BPONI module over
voe to 250 voe control
is
connection
II
can com-
1.6 LEVEL OF REPAIR -This manual is written with
the assumption that only unit-level troubleshooting will be
performed. If the cause of a malfunction is traced to the
II
IQ-1000
malfunctioning IQ-1000
Cutler-Hammer for factory repairs.
unit, it should be replaced with a spare. The
II
should then be returned to
1.7 FACTORY CORRESPONDENCE -All correspon-
dence with Cutler-Hammer, whether verbal or written,
should include the "software version" number. This num-ber appears mode is first entered, or the program menu is first initi-ated (this is item O number is used to identify the specific IQ-1000
being discussed.
11
in
the display window when the Program
in
Table 8.B). The software version
II
type
1.4 EXTERNAL HARDWARE
in
are required
addition to the IQ-1000
• Current transformers. Current transformers are
used by the IQ-1000 tion. Current transformers with 5 amp secondaries and ratios ranging from 10:5 to 4000:5 can be used.
• Ground fault transformer. A ground fault trans-
former with a 50:5 ratio can be used with the IQ-1000 II
in
grounded system applications to provide ground
fault protection.
1.5 PROTECTION FEATURES
features with the IEEE device numbers is contained Table 1.A.
-The
II
to obtain load current informa-
following items
II.
-A
list of protection
in
Effective
February
1999
TD
Courtesy of NationalSwitchgear.com
17297D
Page
9
TABLE 1.A: IQ-1000
Feature
Locked-rotor current Ultimate trip current Maximum allowable stall time
2
1
T alarm level
Instantaneous overcurrent
-Programmable
trip level and start delay
Zero sequence ground fault trip
-Programmable
trip level, start delay and run delay
Motor overtemp trip and alarm (Universal
with
11
RTD
-Six
stator windings
-
Two
motor bearings
-
Two
load bearings
-One
auxiliary
inputs available as
an
option)
Jam trip and alarm
-Separate
trip and alarm levels, programmable start and
Underload trip and alarm
-Separate
trip and alarm levels, programmable start and
RTD
Module
II
PROTECTION FEATURES
run
delays
run
delays
IEEE Device Number
Device Device
51 51
Device 74 Device
50
Device 50G/51 G
Device
49
Device 38 Device 38
Device 37
Phase loss and phase unbalance trip and alarm
-programmable
alarm and run delay
Number of motor "starts" allowed per time period
-programmable
starts and time period
Device 46
Device 66
Anti-backspin time delay
-programmable
timer
Transition trip for reduced voltage starters Incomplete sequence delay Device 2/19
-programmable
Phase reversal for non-reversing starters Device
timer
46
Trip mode
-Mode
-Mode
1:
Trip relay energizes
2:
Trip relay energizes
on
trip condition
on
powerup and deenergizes
on
trip condition or
loss of power
on
Selection of trip, reset, differential trip or motor stop
remote input
Frequency selection
-50
or
60
Hz
2
Selection of auto or manual reset for 1
T trip
Effective
February
1999
Page
Courtesy of NationalSwitchgear.com
10
TD
17297D
Effective
February
1999
TD
Courtesy of NationalSwitchgear.com
17297D
Page
11
SECTION 2
HARDWARE DESCRIPTION
2.0 GENERAL -This section will familiarize the reader
with the IQ-1000 the specifications of the unit.
2.1
HARDWARE DESCRIPTION
description is divided into the following areas:
• Operator Panel
• Rear access area (Par.
• Options (Par. 2.1.3}
• Specifications (Par. 2.2)
II
hardware, its nomenclature, and lists
(Par.
2.1.1)
2.1
-The
.2)
hardware
l@I
Cutler-Hammer
111-11111111
2.1.1
normally accessible from the outside of the enclosure door, provides a means to:
• Monitor the actual metered values on the Display
• Enter or modify the IQ-1000 ll's setpoint values or
• Step through the program or run-monitor menus
Operator Panel
Window. (Figure
settings.
while running.
0
Trip
Reset
-The
2.1
Operator Panel, which is
shows the Operator Panel.)
E)
Alarm
0
Fig.
2.
1 Operator Panel
Effective
February
1999
function
(
Mode
O
Protection
Q
Program
(HELP)
Set
Points
D
Step
Value
Step
@
Raise
Step
~
lower
)
Up
Down
Page
Courtesy of NationalSwitchgear.com
12
TD
17297D
• Determine that a trip means of two distinct LEDs.
• Determine the cause means trip and alarm condition is given
• Attempt to reset the unit after a trip or alarm condition has occurred by means of a Reset pushbutton.
The use of the Operator Panel is detailed in Section 4.
2.1.2 Rear Access Area -The rear of the IQ-1000
normally accessible from the rear of the mounting cabi-
net's door (see Figure 2.2). All wiring connections to the
unit are made on the back
• Terminals 24 and 25 provide a 4-20 signal.
• Terminals 1 , 2, and 3 provide access to the Transition
Relay's contacts.
of
the Display Window. (A description of each
or
alarm condition exists by
of
a trip
or
alarm condition by in
Section 8.)
of
the IQ-1000
II,
as follows:
mA
output
0
0
11
is
m
0
0 0
4-20
120V/240V
EARTH
REMOTE
REMOTE
REMOTE
INC
MA
OUTPUT
TRANSITION
AUTO
SEQUENCE
SEL
GROUND
COMMON
NEUTRAL
INPUT 8
COMMON
25 24
1
2
3
4
5
6
7
9
10
·'-
1:1
l'®'
~
~
~
J
~
l
00
= =
= =
1 I
= =
1 l
= =
1 I
~ =
~
lJ;;/,
0
0
DDDDDDD DDDDDDD
I
DDDDDDD DDDDDDD DDDDDDD DDDDDDD
=
• Terminals 4 and 7 receive the incoming AC control voltage.
• Terminal 5 is the chassis ground. A direct connection must be made between terminal 5 and the main ground bus to ensure proper operation.
0
6 can be jumpered to terminal 9 in order to
or
common, wire associ-
11
thru 23 provide access to the Trip, Aux-
as
CT
Connections
0
0
0
1~1
[Jt:J
I
'®'
~
~
~
~
I
"o
r;-
..
..
..
~
.Q.
~
~
1 )
= =
)
~
=
)
0
=
=
L
r
-
...
l
f
l
f
~
0
CoMMunico Port
Fiber-Optic Connector
23 22
\./iring
21
RTD
ALARM
AUX
Option
TRIP
20
19
18
17
16
15
14
13
12 TRIP
11
JYI
• Terminal provide the common (AC neutral) for terminals
10.
• Terminal 8 is used with the remote trip/reset function. It is the high side of a user-supplied 120 VAC signal input.
• Terminal 9 is the AC neutral, ated with terminals 8 and 10.
• Terminal 10 is used with the incomplete sequence report-back function. It is the high side of a user-supplied input signal.
• Terminals iliary Trip and Alarm Relays' contacts,
0
0
1i1
m
0
lil
0 0
m
111
0
~
.,.,..
__
~-
IQ
1000 I
8 and
well as the
tions
to
Fig.
2.2 Rear Panel
Effective
February
1999
TD
Courtesy of NationalSwitchgear.com
17297D
Page
13
wiring to the RTD Module option. (The Auxiliary Trip Relay is programmable to change state when a spe-cific user-selected trip condition is detected.)
• The fiber optic connector may be used to connect the RTD
optional
• The Communications Port is used with the optional
BPONI communications module mounted back of the IQ-1000
• The CT terminals connect with the three required,
user-provided, external current transformers and, if used, an optional user-provided zero sequence ground fault transformer.
Module is a separately purchased optional device (see Figure 2.3) which interfaces with the motor RTDs and the IQ-1000 blocks of the RTD Module as described
5.1.2 and the RTD itself connects to the IQ-1000 through the fiber optic connector and/or the communica-tions port.
2.1.3.2 Communications Option -The Product
Operated Network Interface (BPONI) is a small printed circuit communications device that is mounted onto the back of the IQ-1000 Cutler-Hammer PowerNet network. The BPONI is a sep-arately purchased option (see Figure 2.4).
2.1.3.3 IQ
Power Supply is a separately purchased option that is required only when 40 to 250 VDC is available as a con-trol power source for the IQ-1000
2.2 SPECIFICATIONS -The specifications for the IQ-
Height = 10.25 in. (26.04 cm) Width= Depth = 3.20 in. (8.13 cm)
6.72 in. (17.0 cm)
4.89 in. (12.42 cm) with PONI
5.55 in. (14.10 cm) with RTD Module
6.75 in. (17.15 cm) with RTD Module and PONI
?lbs
(15.4 kg)
Effective
Fenruary
1999
TD
Courtesy of NationalSwitchgear.com
172970
*
Network
Connection
(Green Phoenix Connection)
LED
Address Selector
Switches
I®-!
Cutler-Hammer
B UFFERED
p RODUCT
0
PERA
N
ETWORK
I
NTERF
TED
ACE
STYLE
NO
8793C52GD1
IQ
Host
Device
Connection
Page
15
Recommended:
18
gauge
twisted pair
IMPCABLEor
20
gauge
Belden 9463 class
* SHIELD
Fig.
2.4 BPONI Communications Options
WIRES
MUST
BE
4 3 2 1
TIED
TOGETHER
FUNCTION SWITCH LABEL MOUNTED
UNDERNEATH UNIT
BPONI
Effective
February
1999
Page
Courtesy of NationalSwitchgear.com
16
TD
17297D
Effective
February
1999
TD
Courtesy of NationalSwitchgear.com
17297D
Page
17
SECTION 3
FUNCTIONAL THEORY
3.0 GENERAL -This section describes how the IQ-
1000 ll's hardware and software function together to con-
trol, monitor, and protect the motor. The explanations are divided into the following areas:
• Sensing inputs (Par. 3.1)
• Protective functions (Par. 3.2)
• Metering functions (Par. 3.3)
3.1
SENSING
motor current sensing derived from 3 separate current transformers, each of which monitors one phase of an line to the motor (see Figure sequence ground fault transformer is used, the IQ-1000 monitors ground fault current levels and compares them to a user-selected setpoint. If optional RTDs are used,
INPUTS-The
3.1
).
IQ-1000
If
an
optional zero
II
receives
AC
the IQ-1000 RTDs embedded RTDs associated with the motor bearings and load bear-ings can also be monitored for temperature levels. Addi-tionally, one auxiliary temperature, can be monitored.
11
gathers winding temperature data from six
in
the stator windings of the motor. Four
RTD,
such as motor case
3.2 PROTECTIVE FUNCTIONS -Protective functions
monitor motor operating conditions (such as current and
in
an
temperature)
user-selected levels, an alarm condition is initiated, and then, if necessary, a trip condition occurs. These two con-ditions have the following functions:
•
An
alarm condition energizes the IQ-1000 ll's internal
II
Alarm Relay.
• A trip condition -other than
power from the motor by either energizing or
ongoing manner. When these exceed
AC
line loss -removes
---~
PD-II
CCM4UNICA
'---~-P-TIL£_oNAL_l
TIONS
__
-'-..
_,
::.:""IT
'-..
~AC~
1
CURRENT TRANSFORMERS
GROUND CURRENT TRANSFORMER
Fig.
3.
1 System Overview (Simplified)
FAULT
IQ-1000
TRIP
RELAYT
RTD
lt:JDULE
<OPTIONAL)
II
INTERPOSING
RELAY
AMMETER
PROGRAMMABLE:
CDNTRCLL£R
OR
HX
I
I
j
Effective
February
1999
Page
Courtesy of NationalSwitchgear.com
18
TD
17297D
de-energizing the Trip Relay. This relay is used for protective control and reporting purposes within the application.
• An auxiliary trip condition -other than
-either energizes or de-energizes the Auxiliary Trip Relay. An auxiliary trip condition, programmed by the user, occurs on one of the following trip conditions:
• Any trip condition
• Instantaneous overcurrent
AC
line loss
• 12T
• Ground fault
• Jam
• Underload
• Motor bearing temperature
• Load bearing temperature
• Winding temperature
• Phase reversal The Auxiliary Trip Relay can be wired to perform
either trip (removing power from the motor) or trip indication features.
• When a trip condition occurs, the IQ-1000 metering functions such as motor current levels, tem-peratures, etc. This "picture" is maintained for use by maintenance personnel and is stored until a Reset is performed.
The IQ-1000
prior to a trip condition indefinitely, provided that a reset from the Reset pushbutton, remote input or communica-tion Network is not received.
The IQ-1000 ll's fault monitoring can be divided into the following types:
II
maintains the metering data stored just
II
stores
• Load-associated protection (Par. 3.2.1)
• Rotor temperature protection (Par. 3.2.2)
3.2.1
level of actual motor current is used to determine when the instantaneous overcurrent trip, jam trip, and under-load trip setpoints have been reached. Actual tempera-ture feedback from the load bearing RTDs are compared with the load bearing temperature setpoint. alarm and/or trip conditions are initiated. (Refer to Table
8.B for a complete listing of these functions.)
Load-Associated Protection -The monitored
If
necessary,
3.2.2 Rotor Temperature Protection -Each design
of motor has a specific damage curve. Usually it is called the 12T curve (current squared multiplied by time). motors, the current balance between phases is of major concern due to the additional heating associated with unbalanced phase condition. Current unbalance is mainly caused by voltage unbalance, the result of single-phase loads on a 3-phase system, and/or motor winding unbalance.
With larger horsepower motors, the design is usually rotor-limited. It therefore becomes important to determine the total heating effect motor can be considered to have two rotors (see Figure
3.2). One is the effect resulting from balanced current. The other is the effect of unbalanced current. If perfect current balance existed
current, then 11 would be the line current squared with no error
in
the heating projected from this current. This posi-tive component of current generates the motor output torque or work.
on
the rotor. For analysis, the
in
each phase of the motor
In
AC
an
Fig.
3.2 Positive and Negative Sequence Current Components
Effective
February
1999
TD
Courtesy of NationalSwitchgear.com
17297D
Page
19
The second component sequence, represented
of
the current is the negative
•
as
1
It is a 3-phase current with
2
a reverse phase rotation from that of the AC source. This current generates countertorque torque, by
or
negative work. Because the torque generated
1
does not leave the rotor, it is absorbed
2
to
the motor output
as
heat and
therefore has a more significant effect on the rotor heat-
ing than the
sented
1
Any 3-phase AC current can be repre-
•
1
by
the addition of 11 plus 1
Using vector analysis
•
2
to determine the positive sequence, one rotates phase B
in
the positive direction 120 degrees and phase C in the
positive direction 240 degrees. (Refer to Figure 3.3 and
3.4.) The formula for
1
1
= IA+
1
is
1
+
(1
120)
+
Oc
+
8
3
240)
The negative sequence is determined by rotating phase
B in the opposite, and phase C rotated degrees. (Refer to Figure 3.5.) The formula for
or
negative, direction for 120 degrees
in
the negative direction for 240
1
2
becomes:
1
= IA+
(1
-120) + (lc-240)
2
Prior to the use of a microprocessor
8
3
in
a motor protection system, there was no practical way of determining the total heating effect of the positive and negative sequence on a continuous basis. Therefore, less than adequate assumptions had to be made. This resulted in nuisance tripping and actual, IQ-1000
II
microprocessor uses a unique, patented sys-
or
near-actual, motor burnouts. The
tem for determining these values.
240°
120°
Fig.
3.3 Symmetrical Components
oo
120°
240°
The current squared, as used in the calculation for rotor
heat, is:
12
=
ll
+
Kil
Here 1
2
is weighted by K because of the disproportional
2
heating caused by the negative sequence.
With the use of a microprocessor, the effects of both the
positive and negative sequence currents are accurately
taken into account. Their
combined effect is incorpo-
rated into a "rotor protection algorithm." The algorithm effectively keeps track of the temperature of the rotor.
It is not necessary to pick an arbitrary phase unbalance set point to trip the motor. As long
as
the combined effect of the positive and negative sequence currents does not approach the motor
damage
curve, the
I0-1000
II
will
allow the motor to operate.
Effective
February
1999
Fig.
3.4 Positive Sequence Currents
1
-120°
8
le
-240°
Fig.
3.5 Negative Sequence Currents
Page
Courtesy of NationalSwitchgear.com
20
TD
17297D
3.3 METERING FUNCTIONS -The IQ-1000
lates and displays the accumulated values obtained by monitoring characteristics such as motor current level,
II
calcu-
RTD
temperature levels, etc. (Section 8 describes the
II
monitoring capabilities of the IQ-1000
in
detail.)
Effective
February
1999
TD
Courtesy of NationalSwitchgear.com
172970
Page
21
SECTION 4
OPERATOR PANEL
4.0 INTRODUCTION -This section describes the IQ-
1000 ll's Operator Panel and details its major compo-nents. Each component's function is described and the procedures for setpoint entry, modification and examining monitored motor parameters is detailed. The section is
divided into the following areas:
• General description
• Component descriptions
l@I
I.Q-UIQH
Cutler-Hammer
Function
• Entering setpoint values II
• Reviewing IQ-1000
• Monitoring metered values
4.1
GENERAL
faceplate is a plastic and polyester material designed to
withstand a variety of harsh industrial environments. All indicators, displays and pushbuttons are located
Trip
0
DESCRIPTION-The
Reul
setpoints
IQ-1000 ll's
on
the
E)
Alarm
0
Value
Fig.
4.
1 /Q-1000 II Operator Panel
Effective
February
1999
(
Made
Protection
0
Program
0
[HELP)
Set
Points
D
Step
J
Step
Up
@
Raise
step
Down
~
Lawer
Page
Courtesy of NationalSwitchgear.com
22
TD
17297D
faceplate (see Figure to the Protection mode and blue colored lettering relates to the Program mode. A keyswitch, which switches the
IQ-1000 is located on the right side of the unit's chassis as it is viewed from the rear (see Figure 4.2).
4.2 COMPONENT DESCRIPTIONS -This paragraph
and its subparagraphs provide a description of the IQ-1000 ll's display window, keyswitch, pushbuttons and LED indicators.
4.2.1 Display Window -The display window consists
of eight alphanumeric illuminated characters which indi-cate the following information and data:
• Setpoints and values
• Metered data from the monitored motor
• Alarm condition information
• Pre-trip data
• Trip condition data
• Scrolling "Help" messages. The display window shows the Function name or abbrevi-
ation
mation
II
between the Program and Protection modes,
on
the left side of the display, with the Value infor-
on
the right side.
4.1
).
White colored lettering relates
or
equipment
A
IF SETPOINT MOTOR ENTERED, ALL IQ-1000 II MOTOR PROTECTION FEATURES ARE DISABLED AND THE MOTOR UNPROTECTED UNTIL THE UNIT'S KEYSWITCH IS RETURNED TO THE PROTECTION POSITION.
4.2.2.2 Protection Mode -
the Protection position, the controlled motor can be started or stopped and is allowed to run normally, as defined by the setpoint values programmed into
II.
1000
51
IS SET TO RUN PGM AND THE
IS
RUNNING WHILE SETPOINTS ARE BEING
In
the Protection mode, the IQ-1000
CAUTION
-
'---
IS
When the keyswitch is
the_
II
monitors
]
IQ-
€
0
in
4.2.2 Keyswitch -The Program/Protection keyswitch
allows the user to select either the Program mode or the
Protection operating mode for the IQ-1000
the keyswitch is removable, providing security against
unauthorized modification of setpoints.
NOTE: The key can be removed only when the switch is
in
the Protection mode.
4.2.2.1 Program Mode -
Program position, the controlled motor cannot be started
51
if setpoint
from the factory with setpoint
PGM). With setpoint motor must first be stopped mode. Placing the keyswitch to the Program position will not initiate the Program mode if the motor is running.
When the keyswitch is can be started and/or run if setpoint
PGM. This allows the IQ-1000
without interrupting a manufacturing process.
is set to STOP PGM (all units are shipped
51
When the keyswitch is
51
set to the default, STOP
set to STOP PGM, the controlled
in
order to enter the Program
in
the Program position, the motor
II
user to program the unit
51
11.
The key for
is set to
in
RUN
the
SHltlD
~
CDtN>I
~
DATA
N
STIIIIIE
::l
~
.L~
€
't:
<O
e:.r-
~t.,
X -
i
..
"'
r--
~tN
~
-
itch--+
Keysw
i@
I o €
Fig.
4.2 Side View Showing Keyswitch
=
~
a
i
I:
=
~
~
g
I..--'
Effective
FetJruary
1999
TD
Courtesy of NationalSwitchgear.com
172970
motor parameters and provides protective functions for the controlled motor.
Individual setpoints may be examined mode, but they may not be modified.
in
the Protection
4.2.3 Set Points/Step Pushbutton -The Set Points
{white lettering)/Step {blue lettering) pushbutton function varies according to the IQ-1000 ll's operating mode
{determined by the position of the keyswitch). In
the Program mode, pressing the Step {blue lettering)
pushbutton repeatedly will cycle through the Program
To
menu in the forward direction. gram menu
Step pushbutton while repeatedly pressing the Lower (down arrow) pushbutton. While in the Program mode,
the Program LED is continuously lit.
In
the Protection mode, pressing the Set Points {white let-tering) pushbutton causes the display window to display the software version installed in the IQ-1000 desires to review the programmed setpoint values, press-
ing either the up or down arrow key causes the setpoints
to be displayed sequentially.
in
the reverse direction, press and hold the
cycle through the Pro-
II.
If the user
Page
23
In
the Program mode, the Raise and Lower pushbuttons (blue lettering) respectively increment and decrement a selected setpoint value.
4.2.5 Help Pushbutton -Pressing the Help pushbut-
ton provides a scrolling description of the displayed mes-sage, including units of measure, for any of the IQ-1000 ll's messages. The Help message may be terminated by pressing the Reset pushbutton while the Help message is displayed.
4.2.6 Reset Pushbutton -The Reset pushbutton is
primarily used to reset the IQ-1000 has occurred, assuming that the cause of the trip has been corrected.
In
the Program mode, pressing the Reset pushbutton will
in
display the first item
In
the Protection mode, pressing the Reset pushbutton will clear a trip condition if the underlying cause of the trip condition has been corrected. If the Reset pushbutton is pressed and there is no trip condition present, the display window will display the status of the motor (first item of the run-monitor table, Table 9.B).
the program menu.
II
after a trip condition
If the Set Points pushbutton is pressed again, the display window will show the message PRE-TRIP. Pre-trip refers
to the monitored motor parameters that were present the
instant before the last trip condition occurred. The pre-trip values are displayed by pressing either the up or down arrow keys. While the pre-trip information is displayed,
the Protection LED remains lit and the Trip LED blinks as
a reminder that the information being displayed pertains to a pre-trip state.
Pressing the Set Points pushbutton again will return the display to the system READY/RUN message that is first displayed upon entering the Protection mode.
Lower each have two separate functions corresponding to their lettering color. An explanation of their functions follows.
In
the Protection mode with the system READY/RUN message displayed, the Step Up and Step Down push-buttons (white lettering) scroll through run-monitor data.
This data contains information such as phase current, operations count, trip counts, etc. (see Table 9.B for a complete listing of run-monitor data).
If the software version message is displayed, the Step Up and Step Down pushbuttons scroll through the setpoint
values programmed
The Step Up/Raise and the Step Down/
in
the IQ-1000
II.
4.2.7 Protection, Program, Alarm and Trip LEDs -
The IQ-1000
Program, Alarm and Trip.
The Protection LED is lit when the keyswitch is tection position.
The Program LED is lit when the keyswitch is gram position. Additionally, the Program LED blinks con-tinuously when the keyswitch is and the Set Points/Step pushbuttons are pressed to review programmed setpoints (see ing Program LED indicates that the program menu, not protection-monitor data, is being displayed.
The Alarm LED is lit when an alarm setpoint value has been equalled or exceeded.
The Trip LED is lit when a trip condition has occurred. Additionally, the Trip LED blinks continuously when the keyswitch is Step pushbuttons are pressed to review pre-trip data (see
Par. trip data is being displayed and that a trip condition is not present.
4.3 ENTERING SETPOINT
ues may be entered or modified only when the IQ-1000 is
in
the Program mode. The following procedure details
II
has four status indicator LEDs-Protection,
in
the Pro-
in
the Pro-
in
the Protection position
Par.
4.2.3). The blink-
in
the Protection position and the Set Points/
4.3.2). The blinking Trip LED indicates that pre-
VALUES-
Setpoint val-
II
Effective
February
1999
Page
Courtesy of NationalSwitchgear.com
24
TD
17297D
how to enter or modify setpoints, assuming that actual
on
RUN
in
the
the
PGM.
RUN
setpoints for a specific application are available Set Point Record Sheet (see
Step 1 -If the associated motor is running and the key-
switch is pushbutton until the software version message is dis-played. Press the Step Down pushbutton twice. The dis-play window will display either STOP PGM or If STOP PGM is displayed, the associated motor must be stopped before attempting to enter or modify setpoint val-ues. If entered
in
the Protection position, press the Set Points
RUN
PGM is displayed, setpoint values may be
or
modified while the motor is running.
A
IF SETPOINT
MOTOR IS RUNNING WHILE SETPOINTS ARE BEING ENTERED, ALL IQ-1000 FEATURES ARE DISABLED AND THE MOTOR IS UNPROTECTED UNTIL RETURNED
Step 2 -
Program position. The display window will display the software version message and the Program LED will be continuously lit. The Protection LED will extinguish if the
unit is
in
PGM mode, the Protection LED will blink continuously.
51
IS
SET
TO
THE
PROTECTION POSITION.
Place the Program/Protection keyswitch to the
the STOP PGM mode. If the unit is
Par.
8.0 and Table 8.8).
CAUTION
TO
RUN PGM AND THE
II
MOTOR
THE
PROTECTION
UNIT'S KEVSWITCH IS
4.4 REVIEWING IQ-1000 II
setpoints have been entered, they may be verified while the unit is setpoints, ensure the keyswitch is tion and press the Set Points pushbutton until the soft-ware version message is displayed. Programmed setpoints may be reviewed by stepping up or down through the setpoints by using the Step Up or Step Down pushbuttons. If the setpoint messages are not clear, press the Help pushbutton for an unabbreviated explana-tion of the setpoint name and unit of measurement.
4.5 MONITORING METERED VALUES -The IQ-
1000
values of various metered functions (see Table 4.A).
Step 1 -Place the keyswitch
(the motor can be either running or stopped). If system message READY/RUN Points pushbutton until one or the other message is dis-played.
Step 2 -Press either the Step Up or Step Down push-
button to display individual metered values. Values appear
in
the Protection mode.
II
allows the user to monitor the actual operating
in
an abbreviated format.
SETPOINTS-Once
To
review programmed
in
the Protection posi-
in
the Protection position
is
not displayed, press the Set
all
Step 3 -Press the Step pushbutton to display menu
item 1 or the setpoint to be modified. The display window will display the setpoint name and some value (repre-
sented by
Increase or decrease the setpoint value by pressing the
Raise or Lower pushbuttons. Values change at the
approximate rate of 2 increments per second. After the
Raise or Lower pushbuttons has been held continuously
for a count of 10 changes, the rate of change increases to
20 increments per second. Setpoint values wrap from
maximum to minimum or vice versa to prevent the user
from going out of the usable range.
Step 4 -When the setpoint value is correctly set, press
the Step pushbutton to move to the next setpoint.
Step 5 -Once all setpoints have been entered correctly
according to the Set Point Record Sheet, turn the key-
switch to the Protection position. The Protection LED will
light and the Program LED will extinguish. The IQ-1000
is now fully functional and ready to monitor and protect its
associated motor.
an X in
the Set Point Record Sheet, Table 8.8).
II
Effective
February
1999
TD
Courtesy of NationalSwitchgear.com
172970
TABLE 4.A: PROTECTION-MONITOR MENU
Page
25
Item No.
0
1 2 3 4
5
6 7
Display
(Status of Motor)
READY--X/START/RUN
IA Is le IG %IA %Is
XXX XXX XXX
xx
XXX XXX XXX
Complete "Help" Description
READY TO START MOTOR -READY --1 FOR SINGLE PHASE MODE -READY --3 FOR THREE PHASE MODE/ATTEMPTING
TO START MOTOR/MOTOR
PHASE A CURRENT PHASE B CURRENT PHASE C CURRENT
GROUND
PERCENT FULL LOAD CURRENT PHASE A 1% PERCENT FULL LOAD CURRENT PHASE B 1% PERCENT FULL LOAD CURRENT PHASE C 1%
FAULT
IN IN
IN
CURRENT
IS
RUNNING
AMPS 1 amp AMPS 1 amp
AMPS
IN
AMPS 1 amp
Resolution
1 amp
19 20 RT 21 22 OST 23 24 25 126 27
28
29
30
31
32
Not displayed if RTD Module is not connected
Effective
February
1999
OCNT
RMST
IMX
WTMX
2
T IOC UL JAM GF RTD ICM
2
%1
T
xx
X
xx
XXX
xxxx
XXX
xx xx xx xx xx xx
XXX XXX
OPERATION COUNT 1 count RUNTIME
REMAINING STARTS 1 start TIME LEFT HIGHEST PHASE CURRENT SINCE LAST RESET 1 amp HIGHEST WINDING TEMP SINCE LAST RESET NUMBER OF 12T TRIPS SINCE LAST RESET 1 trip NUMBER OF IOC TRIPS SINCE LAST RESET 1 trip NUMBER OF UL TRIPS SINCE LAST RESET 1 trip NUMBER OF JAM TRIPS SINCE LAST RESET 1 trip NUMBER OF GF TRIPS SINCE LAST RESET 1 trip NUMBER OF RTD TRIPS SINCE LAST RESET ADDRESS ON THE IMPACC NETWORK 1 (hex) PERCENT OF 12T TRIP LEVEL 1%
IN
HOURS 1
ON
OLDEST START
IN
MINUTES 1 mm.
hr.
1 ° C
1 trip
Page
Courtesy of NationalSwitchgear.com
26
TD
17297D
Effective
February
1999
TD
Courtesy of NationalSwitchgear.com
17297D
Page
27
SECTION 5
INSTALLATION
5.0 GENERAL -This section describes general
mounting, wiring, and wire routing procedures to
be
fol-lowed by the electrical installation crew when installing the IQ-1000 lier sections
II.
The information listed here builds on ear-
in
this manual.
.1275
<0.324
CM>
5.1
MOUNTING -The following subparagraphs
describe the mounting of both the IQ-1000
RTD
and communication options.
5.1.1 IQ-1000 II
-The
unit which is intended to
NOT£
I
IQ-1000
be
mounted through a cutout
5.38
<13.67
CM>
CM>
NOT~!
4.45
<11.3
.1275
<0.324
CM>
5.125
(13.02
CM>
II
II
is
a self-contained
and the
in
6 HOLES
0.1875 IN. <0.5
CM)
DIAMETER
CUTOUT
IN
PANEL
NOTE
Fig.
5.
1 IQ-1000 II Chassis Cutout Dimensions
Effective
February
1999
DR
DOOR
1:
DIMENSION TOLERANCE
9.38
<23.83
4.45
<11.3
CM>
+0.000/-0.050
CM>
IN.
Page
Courtesy of NationalSwitchgear.com
28
TD
17297D
IMI
Cutler-Hammer
18:J99PB
Function
[
Mode
O
Protection
Q
P111170m
6.72
<17.06
Set
CM)
Paints
0
Q
r,.
Alarm
Value
Rael
~
)
Step
Up
~
Raise
Step
Down
10.25
(26.04
CM)
0.50
(1.27
CM)
D
Step
~
lower
'----------------~----
Fig.
5.2 /Q-1000 II Faceplate Dimensions
a panel or enclosure door. The dimensions for this cutout, along with the location of six required mounting holes,
in
are shown panel, be sure that the required three-dimensional clear-ances for the IQ-1000 desired location. (Clearances are shown and Figure 5.3).
Cutout tolerances and mounting screw hole placement are critical. between the center of the mounting holes and the cut-out's vertical edge must be within O and +0.050 in. (0.13 cm).
NOTE: Do not use a tap on the faceplate of the IQ-1000
II
Figure 5.1. Before actually cutting the metal
II
chassis allow mounting
in
In
particular, the horizontal dimension
since this will remove excessive plastic from
in
the
Figure 5.2
the holes, resulting
secure the IQ-1000
Place the IQ-1000 from the front, with the Operator Panel facing outward. Use 0.375
IQ-1000
panel.
5.1.2 RTD Option -The stand-alone enclosure containing the RTD Module. The
Universal RTD Module can be connected to the IQ-1000 II
via 3-conductor shielded cable and/or a fiber optic link.
The the IQ-1000
plied with the RTD Module) or mounted remotely from the
in.
(0.75 cm) long screws (included with the
II)
to mount the unit
RTD
Module may be mounted either
II
by using the
in
less threaded material to
II
to its mounting panel.
II
through the cutout
on
a single-thickness metal
RTD
option consists of a
RTD
mounting bracket (sup-
in
the enclosure
on
the back of
Effective
February
1999
TD
Courtesy of NationalSwitchgear.com
172970
Page
29
unit. If the installation requires mounting the RTD Module
to the IQ-1000
ance requirements. If mounting the RTD Module remotely from the IQ-1000
II, see Figure 5.4 and 5.5. Figure 5.4 shows the RTD Module chassis dimensions and Figure 5.5 is the mount-ing screw hole template pattern.
Observe Figure 5.6 which shows the RTD terminal con-nections, and note the following:
11,
see Figure 5.3 for overall depth clear-
4.39
<11.15
'w'ITH
CM)
PDNI
2.70
<6.86
'w'
/0
CM)
PDNI
• Wiring for the RTDs is connected to the RTD Module at terminals 1-35.
• The incoming 120 VAC supply line for the RTD Mod-
to
ule is wired
• Wiring between the IQ-1000 is connected using 3-conductor shielded cable at ter-minals 20, the RTD board, between the fiber optic connectors on the IQ-1000 and the RTD Module.
J3.
II
and the RTD Module
21
and 22 of the IQ-1000
and/or using a fiber optic cable
II
and at
J2
of
11
6.25
'w'ITH
(15.88
PDNI
CM)
AND
RTD
MODULE
5.05
(12.83
CM)
"
Fig.
5.3 /Q-1000 II Chassis Depth Clearances
Effective
February
1999
PONI MOUNTING
BRACKET
0
RTD
MODULE
MOUNTING
BRACKET
Page
Courtesy of NationalSwitchgear.com
30
TO
172970
• When using 3-conductor shielded cable to connect the IQ-1000 connected only to terminal 23 of the IQ-1000
• A Communications option (BPONI module) can be connected to the RTD Module for communications of temperature-only information over Cutler-Hammer's PowerNet network. Mounting and clearance informa-
Module (PONI card) can be connected to the IQ-1000 for transmission of all information from the device over the PowerNet network. A PONI mounted on can be seen mation for the PONI card is contained
Instruction Leaflet, IL 17361
5.2 WIRING -GENERAL -The wiring of the IQ-1000
II
must follow a suitable "Wiring Plan Drawing". When the starter and the IQ-1000 ler-Hammer, the wiring is factory-installed, and a suitable Wiring Plan Drawing is supplied. Otherwise, the term
refers to the drawings made for the specific application.
They describe all electrical connections between the IQ-
1000
II
and the machine or process equipment. These are made up by the user or OEM and must include at least the following items:
11
• Wiring between IQ-1000
and any interposing relays
used
• Main contactor wiring
• Current transformers, ground fault transformer, and control power transformer wiring
• The RTD Option, if included A typical wiring plan is shown
in
the application
in
Figure 5.7. Note that two jumpers are factory-installed between terminals 4 and 1 and 6 and 9. These jumpers are valid for either 120 or 240 if the Incomplete Sequence function is used
VAC
operation. Remove these two jumpers ONLY
in
VAC
the appli-
cation. If the Incomplete Sequence function is not used
the application, the two jumpers must be proper functioning of the IQ-1000
NOTE: The IQ-1000
II
can accept 120
II.
in
VAC control power. All relays can accept 120 VAC;
however, Remote Trip/Reset and Incomplete
Sequence terminals are 120
VAC
rated only.
NO and NC contacts from the Alarm, Auxiliary sition, and Trip Relays can be used to control external devices. These contacts are rated at 10 amperes (resis-
VAC
tive) for 240 and
-4/20 II
1000
or a programmable controller. See Figure 5.8 for IQ-1000
O
II
for use with external devices such as
rear panel terminals.
or 10 amperes for 30 VDC. A +4/20 mA
mA DC analog output is available from the IQ-
Typical wiring for the RTD Option is shown The exact RTD wiring for each application should be
in
included
in
the Wiring Plan Drawings.
place for
or 240
VAC
or 240
Trip,
an
ammeter
in
Figure 5.9.
VAC
Tran-
Effective
February
1999
Page
Courtesy of NationalSwitchgear.com
34
120V
4-20
MA
TRANSITION 2
/240V
EARTH
REMOTE
REMOTE
REMOTE
INC
OUTPUT
AUTO
SEL 4
GROUND COMMON
NEUTRAL 7
INPUT 8
COMMON
SEQUENCE
25
24
1
3
5 6
9 10
I
0
e,
0
1~l\1lrrl\\!rrl\1lrr!\1~r
IJ
0000000
l
0000000
0
-';j
.;:3
I
0~0~0
0
I·~
.
9·
11'111
:s..:f&.L.
0000000
1
1
0
e, 0
(g
..
~
i-,,,.
~
::
J
I\
0000000
0000000
DDDDDDD
00
0 o
""
"
CT
Connections
CoMMunlco. Port
Fiber-Optic Connector
23
'wiring
22 21
RTD
Option
20
19
18
ALARM
17
16
15
AUX
14
13
12 TRIP
11
tlons
to
TRIP
TD
17297D
Fig.
5.8 IQ-1000 II Rear Panel Terminals
A
ENSURE THAT THE INCOMING
DANGER
AC
POWER AND ALL "FOREIGN" POWER SOURCES ARE TURNED OFF AND LOCKED OUT BEFORE PERFORMING ANY WORK ON THE MOTOR STARTER OR IQ-1000
II.
FAILURE TO OBSERVE THIS PRACTICE CAN RESULT IN SERIOUS OR FATAL INJURY AND/OR EQUIPMENT DAMAGE.
5.3 WIRING GUIDELINES -The following guidelines
must be observed by the electrical crew when installing the 10-1000
11.
5.3.1 Wire Routing and Wire Types -When routing wires between the starter and the associated machine or process equipment, follow these guidelines:
Guideline 1 -Do not route the control or RTD wiring through the high-voltage compartment of the motor
so,
starter. If it is necessary to do
consult Cutler-Hammer
Electrical Components Division for specific instructions. Guideline 2 -Separate the lower voltage (120
from the higher voltage (440
as much as possible.
In
VAC,
or higher) conductors
general, maintain a minimum dis-
VAC)
tance of 1.5 ft. (45 cm) between the two types.
Guideline 3 -Any low-voltage control wiring routed out of the motor starter cabinet should be at least #14 AWG stranded copper wire.
Guideline 4
-When
connecting an 10-1000
II
to the Universal RTD Module using three-wire shielded cable, wire per connection guidelines RTD
Module IL 17367. The three-wire shielded cable
in
Table Ill of Universal
should be #16 AWG or #18 AWG. Connect the cable shield only at the 10-1000
Guideline 5 -The wiring between the the RTDs
in
the motor must be #18 AWG, 3-conductor
II
end, at terminal 23.
RTD
Module and
shielded cable.
5.3.2 Wiring Connections -Make wiring connections according to the application-specific Wiring Plan Drawing for each installation. Certain wiring connections are
noted here for emphasis.
• Unused RTD inputs
on
the RTD Module should be wired together. For example, if MW5 and MW6 are unused, MW5 terminals 13, 14 and 15 should be wired to each other and MW6 terminals 17, 18 and 19 should be wired together.
• The interconnecting cable between the
RTD
Module and the RTD must have the cable's shield connected to the RTD Module
ONLY.
Cut the shield short at the
Effective
February
1999
TD
Courtesy of NationalSwitchgear.com
17297D
Page
35
CABLE SHIELD
\v'IRE
UNIVERSAL MODULE
TERMINALS
3
2
1
RTD
3
1-----------------+---'l----l•l-----f
2
RTD
CABLE SHIELD
r
\JIRING (T\JO-LEAD TYPE)
RTD TERMINALS
1
RTD
NOTESt
1.
CONNECT CUT DR
ELECTRICAL
2.
RTDs CONNECTIONS THE
3.
TERMINAL TO
AN
Fig.
5.9 RTD Wiring
RTD end and use shrink tubing or electrical tape to insulate it.
• When making connections between the RTD Module and an RTD that has only two leads, connect two of the interconnecting cable's leads to one of the RTD's leads (see Figure 5.9). Make this connection as close to the motor as possible. Tie the third interconnecting lead to the remaining RTD lead.
CABLE
SHIELD
MUST
MOTOR
EARTH
SHORT
NOT
BET\v'EEN
OR
16
OR
GROUND.
\JIRING (THREE -LEAD TYPE)
SHIELD
TAPE
BE
THE
32
AT
RTD
AT
MOTOR
TO
INSULATE.
GROUNDED
INDIVIDUAL
IQ-1000 II.
ON
THE
RTD
MODULE
END
AND
AT
THE
MODULE
• When making connections between the
• The Universal
TERMINALS
USE
SHRINK
MOTOR,
RTDs
SHOULD
SHOULD
and a three lead wire to the RTD Module terminal as shown
5.9.
power ONLY (see Figure 5.10). If the installation uses 240
VAC
control power for the IQ-1000
AND
ONLY. TUBING
NO
COMMON
BE
MADE
AT
BE
CONNECTED
RTD,
connect the shield and drain
RTD
Module accepts 120
RTD
Module
in
Figure
VAC
control
II,
a separate
Effective
February
1999
Page
Courtesy of NationalSwitchgear.com
36
TD
17297D
'r
0
00
..
i:
Oto
!
R
...
•
....
•
•
. .
00
~
0
...
00
2
,
-
-(
I
~
-i
!
I
o0
0 0 0 0
l~~\ir.\~i
0
lt-~'I
0
DDDDDDD DDDDDDD DDDDDOD DDDDDDD• DDDDDDD-DDDDDDD
g
Im
Cutler-Hammer
UNIVERSAL
RTD
MODULE
0
,.
lft'"]
.
...
·--
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
Lt
0)
..
~
..
(!t
UL...JlD
l!;l
0
0 •
,.
•-
•-
•
•
•
•
•
•
•
•
•
•
•
•
.
•
•
•
•
~
COITROL
POVER
TRANSf"DRMER
Luu.J.
=
mrr •
120
VAC
ONLY
--CUIKNT C-TIIGGIIIGMD
~
I
Fig.
5.
10
IQ-1000 II to Universal RTD Module Control Wiring
source 120 Module.
• The IQ-1000 for control power or remote inputs (see Figure All input relays are rated for 120 or 240 exception of the Incomplete Sequence and Remote Trip/Reset terminals, which are rated for 120
ONLY.
5.3.3 Grounding
tem components must be grounded as follows to ensure
proper operation:
VAC
must supply the Universal RTD
II
accepts either 120 or 240
-The
IQ-1000
II
and associated sys-
VAC
VAC
inputs
5.11
with the
VAC
• Connect the ground side of the control power trans-former to terminal 7 of the IQ-1000
• Connect one side of the CTs to the system ground.
).
System noise may disrupt the IQ-1000 are tied to a current carrying ground.
• Connect a #14 AWG wire between terminal 5 and the main ground bus of the system.
terminals 5 and 7 together.
terminal 5 to the system ground bus must be a non-current carrying ground.
11.
Do
NOT connect
The ground connecting
II
if the CTs
Effective
February
1999
TD
Courtesy of NationalSwitchgear.com
17297D
WJJJ
-rrrr
120 240VAC
?
OR
•
CONTROL
PDV[R
TRANSF"DRMER
•
~I
CUSTOK:R REMOTE INPUT
CONTACTS
DR
PUSHBUTTC,.,S
~:R~~E:DIJN{
II
,,
/Ir
Page
37
r
0
-
0
-
0
@"
~
0
0
0
1v1
1i1
Iii
J11
1¥1
lil
0 0 0
.,.,..
~
<ii•
0 0
l~I
0
0
___
IO
1000 I
0
l~I
I
0
ro
r;;-
..
..
..
I!.!
..Q.
]
~
~
=
..
=
I
= =
~
;;
-
0
-
0
DDDDDDD
I
DDDDDDD
[;:
~
DDDDDDD
[) =
DDDDDDD
[;:
I
[;:
:[)
:r:;:
-r,,.
0
0
= =
DDDDDDD
~
DDDDDDD
=
mJ
0
-
0
/
Fig.
5.
Effective
11
IQ-1000 II Remote Input Wiring for 120
February
1999
or
240
VAC
Control Power
Page
Courtesy of NationalSwitchgear.com
38
TD
17297D
Effective
February
1999
TD
Courtesy of NationalSwitchgear.com
17297D
Page
39
SECTION 6
STARTUP
6.0 GENERAL -This section describes the procedure
to follow when applying assuming that unit before. Each step with a box to the immediate left, which may checklist to reduce the chance of omitting or skipping an item.
AC
A
ONLY QUALIFIED PERSONNEL FAMILIAR WITH THE IQ-1000 II, THE MOTOR STARTER, AND ITS ASSOCI-ATED MECHANICAL EQUIPMENT SHOULD PERFORM THE STARTUP PROCEDURES LISTED HERE. FAILURE TO COMPLY CAN RESULT OUS OR FATAL INJURY AND/OR EQUIPMENT DAMAGE.
A
THE IQ-1000 USE A MEGGER TESTING WITH THE UNIT. FAILURE TO COMPLY WILL
RESULT
II
IS
ON
THE CONNECTIONS ASSOCIATED
IN
EQUIPMENT DAMAGE.
AC
power to
power has never been applied to the
in
the procedure
an
IQ-1000
is
shown below
be
II,
used as a
DANGER
IN
SERI-
CAUTION
A SOLID-STATE DEVICE. DO NOT
OR
PERFORM HIGH-POTENTIAL
6.2 INITIAL AC POWER CHECKS -The following
procedures describe the initial items to be performed when power
6.1
ure D With the power still
power line to terminal
D Connect an AC voltmeter between the wire just dis-
connected from terminal 4 and terminal
o
Turn
D Measure the voltage and verify that a level of 120
VAC
NOTE: If 240 Incomplete Sequence option and/or Remote Input option is being used, verify that only 120 present across terminals 8 and 9 and terminals 9 and
10. See Paragraph 5.2,
5.11
for additional 240
D Remove D
If
terminal
O If the AC power level
Plan Drawing and rewire, as necessary.
is
first applied to the IQ-1000
as necessary.
AC
power on.
or 240
the
VAC
AC
AC
power level
4.
VAC
power.
II.
Refer to Fig-
OFF,
disconnect the
4.
is
applied.
control power is being applied, and
Wiring-
VAC
is
correct, reconnect the wire to
is
incorrect, consult the Wiring
General and Figure
wiring information.
AC
7.
VAC
control
will be
6.1
POWER OFF CHECKS -With the incoming
power locked off at the isolation switch, perform these checks:
D Ensure that the isolation switch feeding the IQ-1000
II
is
in
the OFF position.
o Ensure that there
trol power through the control transformer, which will
result
in
voltage being present
transformer.
0 Ensure that any foreign sources of power, such as
those connected at the IQ-1000 ll's relays' external terminals, are turned off.
D Ensure that the wiring associated with the application
has been installed properly as shown Plan Drawing which was produced for the applica-tion.
Effective
February
1999
is
no possibility of backfeeding con-
on
the primary of the
on
AC
the Wiring
ON
6.3 INITIAL AC POWER
dure describes the initial items to power
is
first applied to the IQ-1000
D Place the keyswitch D Apply
The message THINKING while the IQ-1000 sion number is displayed. At this time the IQ-1000
ready to accept set point values.
NOTE: While THINKING is present on the display, the IQ-1000 Mode 2, the trip relay contacts will be blocked open
for 3 seconds.
AC
power to the application.
II
"initializes". Next, the software ver-
II
is not protecting the motor. If the unit
-The following proce-be
performed when II.
in
the Program position.
is
displayed for a few seconds
AC
II
is
is
in
Page
Courtesy of NationalSwitchgear.com
40
A
DO NOT ATTEMPT TO ENTER ANY VALUES WITH-OUT USING THE APPROPRIATE SET POINT RECORD SHEET. IMPROPER OPERATION AND/OR PERSONAL INJURY COULD RESULT IF THIS PRO-CEDURE IS NOT FOLLOWED. SEE SECTION 8 FOR IQ-1000
0 Enter setpoints as described
0 After entering all setpoints, verify that each entry has
II
PROGRAMMING INFORMATION.
the filled-in Set Point Record Sheet (Table 8.B) for the specific application.
been correctly entered as described
4.4.
A
WHEN THE KEYSWITCH IS PLACED TECTION POSITION, THE IQ-1000 ll'S TRIP RELAY WILL NO LONGER PREVENT THE MOTOR'S MAIN CONT ACTOR FROM CLOSING. AT THIS TIME THE
MOTOR ASSOCIATED WITH THE APPLICATION CAN BE STARTED. IT IS IMPORTANT TO ENSURE THAT
ALL SAFETY PRECAUTIONS ASSOCIATED WITH
ROTATING EQUIPMENT AND THE ASSOCIATED
DRIVEN MECHANISM BE TAKEN. FAILURE TO DO SO CAN RESULT AND/OR EQUIPMENT DAMAGE.
IN
DANGER
in
Paragraph 4.3. Use
in
Paragraph
DANGER
IN
THE PRO-
SERIOUS OR FATAL INJURY
TD
17297D
O Ensure that all rotating members and driven mecha-
nisms associated with the application's motor are
properly and securely connected and free of any
loose or foreign objects.
0 Ensure that all personnel are cleared from the area
of the application's motor and driven mechanics.
O Follow any startup procedures which may accom-
pany the load equipment and refer to the application engineer who developed the Set Point Record Sheet or the associated mechanics if necessary.
O Turn the keyswitch
position. Start the motor using the external start
switch or contacts.
0 Using the information supplied by the application
engineer or equipment manufacturer, verify that the
motor is operating properly.
0 With the motor running, use a clamp-on type amme-
ter to measure the
supply lines.
0 Verify that the
the IQ-1000
sured by the ammeter (see Paragraph 4.5 for the pro-cedure to monitor motor parameters). This is not meant to verify accuracy of the IQ-1000 dure is to verify proper wiring of the current trans-
formers and correct setting of the CT ratio. If there is
a difference of greater than 15%, either the CT ratio is set incorrectly and/or the current transformers are incorrectly wired.
on
the IQ-1000
AC
line current
IA,
1
and
le
,
8
II
are within 15% of the currents as mea-
currents as measured by
11
to the Protection
on
the main motor
II;
this proce-
Effective
February
1999
TD
Courtesy of NationalSwitchgear.com
17297D
120V/240V
4-20
MA
TRANSITION 2
AUTO
EARTH
REMOTE
REMOTE
REMOTE
INC
SEQUENCE
OUTPUT
SEL 4
GROUND
COMMON
NEUTRAL
INPUT
COMMON
25
24
1
3
5
6 7
8 9 10
Q_
0
'::J
~
I
J
II]
l
j I
...
~
=
~
=
I
= =
= =
I
= =
I '
0
0
0
0
)11
J~I
1i1
Iii
0 0 0 0
lil
0
~
0
JVJ
l~I
0
lei
I
G•mu£r•
0
0
DDDDDDD
DDDDDDD DDDDDDD DDDDDDD DDDDDDD DDDDDDD
0s>
"o
,.-,
..
..
..
~
..Q.
~
ti]
ti
= i::
I '
~
~
I
..
=
=
I
=
= f
=
=
I
00
-
..
l
J
lL
Fi
l
l
f
CT
Connect1o_ns
CoMMunlco. Port
Fiber-Optic Connector
23 22
w'lrlng
21
RTD
20
19 18
17 16
15
14
13
12
11
Option
ALARM
AUX
TRIP
TRIP
tlons
to
Page
41
Fig.
6.
1 /Q-1000 II Wiring Terminals
Effective
February
1999
Page
Courtesy of NationalSwitchgear.com
42
TD
17297D
Effective
February
1999
TD
Courtesy of NationalSwitchgear.com
17297D
Page
43
SECTION 7
APPLICATION CONSIDERATIONS
7.0 GENERAL -This section describes the protection
and control characteristics of the IQ-1000
intended for the engineer who is responsible for matching
an
the control to sented here is especially useful tor understanding set-
point considerations described
It may be helpful to read Section 7 and 8 quickly, and then to reread and study Section 7 carefully. After doing so,
reread Section 8 from the program menu given the specific application.
NOTE: Throughout these explanations when specific
functions are discussed, the program menu item
number is also noted. This technique will help the reader understand the concept by relating it to Table
8.B, where more details are located.
7.1
MOTOR PROTECTION
the motor, starter, and load
Motor overload protection
•
Overtemperature protection
•
Instantaneous overcurrent protection
•
Ground fault protection
•
Phase reversal protection
•
Motor bearing temperature monitoring
•
Jam protection
•
Underload protection
•
Load bearing temperature monitoring
•
Incomplete sequence protection
•
7.1.1 Overload Protection without RTDs -The
motor overload protection feature, called the 12T algo-rithm, calculates the rotor temperature of the motor based on the amount of current flowing into the motor. If no RTDs are present, the IQ-1000 a trip only when the average current level of the 3 phases is above the ultimate trip level. A programmable 12T alarm (program menu item 20) informs the user when the IQ-1000
II
is between 60% and 100% of the way to a trip.
individual application. Information pre-
in
Section
in
order to select those setpoints
in
Table 8.B which relate to
-The
in
the following ways:
II
II,
and is
8.
IQ-1000
will proceed toward
II
protects
The overload trip set point is determined as the maximum amount of 12T calculated by the IQ-1000 translated to the rotor. When the IQ-1000
lated enough 12T, (Locked Rotor/Thermal Overload) is displayed.
motor cannot restart until the temperature of the
rotor, as calculated by the IQ-1000 II, falls below the alarm level set point entered into the 1function (item 20).
and cooling calculation.) To
do this, the IQ-1000
of the motor's operation (see Figure variables are used as input data for the history:
• Motor current
• Motor current
anced," current
• Time
This data can be considered as the current feedback
from the motor.
In
addition to the current feedback from the motor, certain
motor constants are needed. They are supplied to the IQ-
1000
II
when the user-chosen setpoints are programmed
into memory. These are:
• Full-load amperes (item 42)
• Locked-rotor current (item 17)
• Maximum allowable stall time (item 18)
• Ultimate trip (item 19)
Using these motor constants, sampled motor currents,
and time, the IQ-1000
temperature, always assuming a 40°C ambient
temperature.
7.1.2 Overload Protection with RTDs
ature data obtained by employing optional RTDs
by the IQ-1000
motor:
(1) Direct measurement of the winding temperature-
versus-programmed trip temperature. (This gives a
user-set fixed trip point based on actual, measured
stator winding heating and cooling.)
a trip occurs and message
(The algorithm has both a heating
II
maintains a short-term history
(1
),
the positive sequence current
1
(1
),
the negative sequence, or "unbal-
2
II
can track the calculated rotor
II
in
the following two ways to protect the
II
which can be
II
has accumu-
2
T alarm level
7.1
).
The following
-The
LRC/12T
The
temper-
is
used
Effective
February
1999
Page
Courtesy of NationalSwitchgear.com
44
TD
17297D
(2) RTD winding temperatures -when combined with
the monitored positive/negative sequence motor cur-rent and the incorporates the anticipated cooling of the rotor based is described and 7.1.4.)
The following motor input variables are used
II
1000
• Motor current
• Motor current
• Time
when the optional RTDs are used:
anced," current
2
1
T algorithm for motor protection -
on
the actual stator winding temperature. (This
in
Data from (
RTD
Module
more detail
(1
),
the positive sequence current
1
(1
),
the negative sequence, or "unbal-
2
in
subparagraphs 7.1.3.6
Variables monitored:
Select stator
RTD
-
with
....
highest
temp.
by
the IQ-
-
,__
• Stator winding temperature This data can be considered as the feedback from the
motor.
In are needed. They are supplied to the IQ-1000 these user-chosen setpoints are programmed into mem-ory.
• Full-load amperes (item 42)
• Locked-rotor current (item 17)
• Maximum allowable stall time (item 18)
• Ultimate trip (item 19)
Stator temperature
addition to the variable data, certain motor constants
II
when
These are:
Constants
-
supplied:
Full-load amperes
Motor {
curr~nt
sensing
/
IQ-1000
-
-
II
w
V
LI
Processor
-
-+
Module
~
,..
-
,.. ,..
-
-
,..
~
-
Positive sequence current
Negative sequence current
Micro-processor
control
-
,__
~
-1,~
~
,__
12
(
I
~
-
12T
rotor protection algorithm
..
"'
"
Rotor temp. storage term history)
(short-
i+--
-
~
~
...._
+/-
temperature update
( =
maximum-.
=
12T
\
lev.el
Locked-rotor
(current
and time)
Ultimate trip
current
condition
alarm-.
condition
Trip
Alarm
~
,..
~
,..
Fig.
7.
1 Rotor Temperature Tracking
Effective
February
1999
TD
Courtesy of NationalSwitchgear.com
17297D
Page
45
• Winding temperature trip value (item The IQ-1000
II
stores the chosen setpoint levels
nonvolatile memory and accurately measures feedback
variables. Thus the unit protects the rotor by using the
3) in
its
2
1
T algorithm, while the stator is protected by direct measure-ment through the RTDs.
7.1.3 Protection Curve -The motor protection curve
defines the motor-versus-time relationship that is gener-ated by the IQ-1000 I l's application software, hardware, and programmed set point values. Note Figure 7.2. Ide-ally, this curve is located as close as possible to the motor damage curve, thus allowing maximum utilization of the motor without damage.
in
(The motor damage curve is defined as that point
the
relationship between the motor current and time where
thermal damage results.) When the motor current-versus-time relationship exceeds
this damage curve, a trip condition occurs, and the motor
is turned off. The IQ-1000
11
automatically calculates the correct motor protection curve for a specific application after the follow-ing items are entered: full-load amperes rating (item 42); locked rotor current (item 17); maximum allowable stall
time (item 18); and ultimate trip (item 19).
A brief discussion of how these values affect the motor protection curve is given The typical curve shown factors listed
7 .1.3.1 Instantaneous Overcurrent Function -The
in
these explanations.
in
the following subparagraphs.
in
Figure 7.2 is the result of the
specific instantaneous overcurrent (item 15) setpoint used
in
Figure 7.2 is 12 times (1200%} full-load amperes
In
(item 42).
general, the instantaneous overcurrent set-point for all applications should be at least 1.6 times the locked rotor current ratio. The instantaneous overcurrent
setpoint available range is 300 thru 1600% of full-load amperes.
NOTE: For the 1.0.C. trip level to be effective, set it below your fuse interrupting rating or your contactor
withstand capacity.
NOTE: The instantaneous overcurrent start delay
function (item 16) has a fixed minimum 1 cycle delay to detect the condition.
The
available setpoint range
for additional start delay is actually 1 thru 20 cycles.
7.1.3.2 Locked-Rotor Function
curves shown
in
Figure 7.2 is based upon a locked-rotor
current set point (item 17) of
-The
6.1
times (610%} the full-
AC
family of
line
load amperes function's (item 42) set point and a variable locked-rotor stall time set point (item 18).
All curves shown
in
Figure 7.2 are based
on
a maximum
allowable stall time from a cold start. Since the IQ-1000
ll's algorithm retains a history of both the operating cur-
rent and operating time of the motor, it is not necessary to program it for hot starts. The unit automatically takes into consideration whether it is a hot or cold start. The locked-rotor set point, however, should be set for a cold start.
7.1.3.3 Ultimate
Trip-The
ultimate trip function's (item 19) set point is the lowest value of current above which the motor can be damaged over time.
If
the motor has a service factor larger than 100%, the ultimate trip level can be increased accordingly. A service factor of
1.25 could be used with a 125% ultimate trip level.
7.1.3.4 Underload
Functions-When
the motor is running, a sudden current reduction indicates a malfunc-tion
in
the driven equipment. If the current level falls below the user-set underload alarm value (item 26), alarm condition exists.
If
the current falls below the
an
underload trip level (item 27), a trip condition occurs and
the motor is taken off-line.
Underload protection is used problems such as a blocked flow pressure
in
a pump, or a broken drive belt or drive shaft.
in
the event of mechanical
in
a pump, loss of back
A programmable start delay (item 28) is provided to lock-out the underload function while starting unloaded
motors to prevent nuisance tripping. The run delay (item
29) is useful
in
applications where the motor is operated
under light loads for short periods of time such as a con-
veyer system.
gram a value of alarm function, program a value of
7.1.3.5 Jam Functions -Once the motor is running, if
To
disable the underload trip function, pro-
O for item 27.
To
disable the underload
O for item 26.
the monitored current level exceeds the set point entered
for the jam trip level (item 23), a trip occurs. (See Figure
7.3
in
which the jam trip set point is 180% of full-load cur-rent.) An alarm level can also be programmed for jam (item 22).
Effective
February
1999
Page
Courtesy of NationalSwitchgear.com
46
Ultimate
trip based
on
full-load
12T
(These ar
combinat of
currents.
0/o
of
amps
(100%
shown)
curve
Ii
and
motor
1000
500
300
200
~
100
50
20
s ea/
ion
10
12
)
8 6
4
2'
1
/~
/
....
.,,,,-
~
.....
I,,
~
....
.....
....
...
,.
"
'
\.
\.
\
\ \
\ \
\\
\
\\'
~
\\
'
' '
'\ '\
'\
\.
\ \
\ \ \
[\
'\ '\
\
\
'\
'\
'\
[\ \
\
I\
\
\
"
\
'\
'
'
\
I\ [\
'\
'
I\
I\
'\
\
I\
'
\
'""
'
i\
i\
\
'
~
\
TD
Maximum allowable
stall time
(30 sec . old start)
C
(15 sec. old start)
C
(10 sec. old start)
C
(5 sec.
old start)
C
Based
upon
locked
rotor
current of
6.1
times
full-load
amps
17297D
Fig. 7.2
.5
I
0
Q)
rn
.!,;
Q)
E
:;::
Motor Protection Curve
.2
.1
.05
.02
Ins
tantaneous
vercurrent
0
set
at
12
-
-
-
.5
1 2 4 6 8 10
multiples of full-load amps
20
full-load
amps
In
stantaneous
overcurrent
set 1
(1
in
herent
100
Effective
times
start
delay
for
cycle
cycle
=
delay)
February
1999
TD
Courtesy of NationalSwitchgear.com
17297D
Page
47
In
cases where the RTD Option is used, jam protection is
especially desirable with gear train or other mechanical-
In
type loads. could cause damage. A programmable start and run
delay are provided to compensate for inrush current and momentary surges
If the jam trip function (item 23) is not desired, a value of 1200% should be entered along with a start delay of 1 second. (See Paragraph 8.10 for more details.) The jam alarm function can be disabled by programming item 22 for a value of 1200%.
7.1.3.6 Temperature Effects -Motor protection is
directly related to the temperature of the rotor. If RTDs are not used, the IQ-1000
Underload
determined underload
delay
such cases an overload or physical jam
in
the load.
II
assumes the ambient tern-
trip
level
(in%
full-load
amperes)
Delay
time
funcfion
1000
by
run
----
500
300
200
100
-----------
~
----·
_::,,ar
.
--
-
,_f-
·-
-
--
perature to be 40°C. Thus the actual ambient tempera-
ture has no effect on either the starting or running of the
motor.
The customer application engineer should take these fac-
tors into consideration and compensate for them if a higher ambient temperature is anticipated. The best solu-tion is to use RTDs since any compensation for a higher ambient temperature results during conditions of lower temperatures.
Without RTDs, the IQ-1000 time, and then converts them to a calculated stator/rotor temperature. The constant the locked-rotor current and maximum allowable time functions (items 17 and 18), is assumed to adequately
I
I
I
---1-
,_
...
,..
I
I I
I
I
..-i
I
I
I
----
.~
~
-
V
---
--
---
~
--
--
1,1,
~
in
overprotecting the motor
II
calculates the current and
2
1
T curve, as established by
I I
. ------
Jam trip level
function(%
full-load
amperes)
Delay time
determined
jam run delay
function.
by
I I
-,-
-~
-f-
t
Underload
trip function
not active
during underload
start delay
function.
Fig.
7.3 Jam Protection Curve
50
20
10
8 6
4
2
v
_,,,,,,,-
I
I I
I
....
,..
i.....-
) '
.5 2
multiples of full-load amperes
....
I
~
~
~
4
..._
6 8 10
_.,
-
Jam trip function not active during -
jam start delay
function.
20
-
-
100
Effective
February
1999
Page
Courtesy of NationalSwitchgear.com
48
TD
17297D
protect the motor for all levels of motor current above the
ultimate trip set point level. Should the curve not be ade-quate to protect the motor due to stator limitations at ele-vated ambient temperatures, then the use of RTDs
recommended. RTDs allow full utilization of the power available from the motor, and they reduce unnecessary shutdowns.
7.1.4 Typical Motor Protection Curves -
the IQ-1000 ll's protection features, two sample curves are shown. Using specific motor data, typical motor pro-tection curves of the IQ-1000
in
Figure 7.4. The use of RTDs is assumed
The following data were used:
• Instantaneous overcurrent of 12 times full-load
amperes
• Locked-rotor amperes of
• Maximum allowable stall time of 15 seconds, cold
start
• Ultimate trip level of 100% of full-load amperes
• Start cycle set at 10 seconds (assumes a single-
stage motor). (See items 37 and 38.)
• Motor running; loaded at 90% of full-load amperes
• Underload protection set point is 60% of full-load
amperes
• Jam protection functions of 180% full-load amperes
for a 5-second delay
II
without RTDs are shown
in
6.1
times full-load amperes
is
To
illustrate
Figure 7.5.
7.1.5 Motor Current -The IQ-1000
positive and negative sequence currents. Each is
in
described
the following subparagraphs.
II
monitors both
7.1.5.1 Negative Sequence Currents -Throughout
the discussion of motor protection curves, the effects of negative sequence currents cannot be emphasized too strongly. For maximum motor utilization, the actual load should be matched closely to the full horsepower of the motor. However, when this voltage unbalance -that results sequence current -becomes more critical.
The IQ-1000 currents user to arbitrarily pick a specific set point percent of unbalance to shut the motor down. (However, see pro-gram items 30 and 31.) As long as the rotor temperature, as calculated by the IQ-1000 damage curve, the motor continues to operate.
II
accurately calculates negative sequence
in
an
ongoing manner.
is
done, the effect of motor
in
the negative
It
is not necessary for the
II,
does not equal the motor
7.1.5.2 Positive Sequence Currents -The IQ-1000
monitors true RMS motor current. It takes a total of samples calculate the positive and negative sequence currents.
The sampling point is constantly shifting; thus the IQ-
1000 important for applications where power factor correction capacitors and rectified systems are bus.
in
each phase during a 1 cycle period
II
also monitors non-sinusoidal wave forms. This is
on
the same main
in
order to
36
II
The difference of RTDs is shown
period after 60 seconds. (When RTDs are used, the
actual monitored temperature automatically overrides the
ultimate trip function's setpoint.) Note that the ambient conditions under which the motor
is
operating affect the top portion of the curve. The curve shifts to the left with increasing ambient temperature, and to the right with decreasing ambient temperature.
The effects of the motor winding temperature (items 3
7)
and
evident the effects of temperature curve. These functions' setpoints are based
ommended maximum stator temperature, as supplied by the motor manufacturer. Depending upon the specific
motor winding temperature setpoints, the temperature trip curve shifts to the left or right.
The IQ-1000
available from the motor by setting its trip conditions as close as possible to the motor damage curve.
setpoints, which can be used with RTDs, are not
in
in
the typical curve caused by the addition
in
Figure 7.5. It centers
Figure 7.5. These functions are independent of
on
the 12T algorithm's trip
II
allows maximum utilization of the power
on
the time
on
the rec-
7.1.6 Ground Fault Protection -The IQ-1000 ll's
ground fault function (program menu item 11) provides protection against excessive leakage current levels. (The specific level is chosen by the user.)
Use of this function is restricted to a grounded system; it may not requires that transformer be installed the secondary of the main power transformer feeding the motor is wired
The optional ground fault transformer chosen must have a current transformer ratio of 50:5 to allow the IQ-1000 to properly interpret the ground fault current level.
be
used
in
an ungrounded system. The function
an
optional ground fault (zero sequence)
in
the grounded system
in
a wye grounded configuration.
in
which
7.2 MOTOR CYCLE MONITORING -As used here,
the term "motor cycle monitoring" refers to the IQ-1000 "passively" monitoring the motor during periods of normal operation. Normal operation includes the start cycle, cycle, and stop cycle.
run
II
II
Effective
February
1999
TD
Courtesy of NationalSwitchgear.com
17297D
Page
49
Underload
trip level
60%
full-load
amperes.
Underload ru
delay: 5 sec
Motor running
with load
Underload start delay
20 sec.
Jam trip leve
180% full-loa
amperes
Jam start del
15
sec.
Motor starting
current (locked-r
condition)
6.1
times
full-load amps
1000
600
t2
300
200
n
100
50
20
10
---
8 6
4
2
I:
/
1
d
ay:
.5
.2
.1
1
u
Cl)
II)
g
.05
Cl)
:§
02
otor ·
--
l.----
t,
-
/v
V
~
i--
times
sec.
12t
(6.1)2
t
-~
_,_
15_~
I I
-~
-~~
I
I_
-
~
-
-
\-
.....
-
-
-
-
-
7
~
/
" -
~
.......
~"
~
--
-
I'
I
..
\
\
I/
-
-
~
I
\
'
I
.
I
I
I
.
I
I
.
I
~
I
I I I I I
I
I I I I I I
I
X =
1/t
2
X
~=12
2
558.15
--
=
12
= 558.15 sec.
'
.,
'
"
\
.,
-
full-load amperes
-
f--
_,....
I~
~i,,,ill~
'
'
,__
-
1---.
-
, I
~
~
'
Ultimate trip
level: 100%
Note: I is a
combination of
positive (I,) and negative (12)
sequence
motor currents.
Max. allow.
locked-rotor
amperes:
6.1
full-load amperes
Stall time:
X =
=
f'-.
~
= 558.15
1'. I I
X = l
t=12
558.15
= = 3.88 sec.
15
2
X
2
(12)2
\..
'\
\.
Instantaneous
overcurrent:
12
times
-~
~..-
_
..
..
-
---
-
--
-
full-load
~~
amperes
I
I I I
I
I
I I I
J
Instantaneous
overcurrent
start delay
set for
1 cycle
~~
_.._
_.._
-~
_.._
I
.5 1 2 4 6 8 10
multiples of full-load amperes
20
100
Fig.
7.4
Motor Protection Curve (without RTOs)
Effective
February
1999
Page
Courtesy of NationalSwitchgear.com
50
TD
17297D
Stator temperatu measured direct!
Stator
winding
temperature
(trip)
function
is
set
point.
Underload
trip
level:
60%
full-load
amperes.
Motor running
with load
Underload
delay: 5 sec.
with
Underload start
delay: 20 sec.
Jam trip level 180% full-load
Jam start dela
run
load
amperes
15
sec.
1000
re
y.
----
1----
._....._X-1
I----
I----
500
300
200
t2
--
100
50
20
---
10
8
6
4t
1--
1
-
/
;/
-11
1
-
.5
==t1=12
-
-
~
,____
y:
-2
t
2
X
~=12
2
558.15
=
(2)2
= 139.5
.....
---
-
v--
2
X = I
X
1
558.15
=---
(12)
= 3.88 sec.
2
L..::a
/
t
,,.
-..-
2
r,,..._
1--
-
V
-
"
i"I""'
.~
1 ....
""
,_.._
--
'-'-
~~
...
~
-
J.
......
-~
:
.~
~
--
..
----
I ,
I
I
I
I
I I
I
......
I
.._
\
"
"
-
--
-
'
\
-
~~
~
~-
"
l
'
~(
"""
-·
--
-
Rotor algorithm protection -
i-
trip curve shifts left and =
right depending upon
measured stator temperature .
I I I
Note: I is a
combination of
)
{1
1
Max. allow.
locked-rotor
full-load amperes
X = l
-
Instantaneous
overcurrent
./
,l.
~
I I
amperes:
6.1
times
Stall time:
15 sec -
2
t
= (6.1)
= 558.15
12
times
full-load
amperes
,_,,,,;
i..•
\
'
-
-1;,~
positive
and negative
(1) sequence
motor currents.
I./
\
\
2
(15) >-
-
~
-
-
-
-
~
f-
~
~
t.i
Q)
CJ)
;§_
Q)
E
:;:::;
Motor starting current (locke rotor) full-load amps
Fig.
7.5 Motor Protection Curve (with RTDs)
6.1
d
----
time
s
.05
.02
.2
.1
....--
--
L-
~
'-""'
~
--
--
.5 6 8 10
multiples of full-load amps _
2
4
_...,~
.-
i....-
-
20
lnstantaneou
overcurrent
start
delay
set
for
1
cycle
delay.
I I
11111
Effective
s
100
February
1999
TD
Courtesy of NationalSwitchgear.com
17297D
Page
51
The word "passive" implies that the IQ-1000
motor current levels. It does not actually switch nor directly affect the motor's contactors except when the
in
Transition Relay, described
reduced voltage starting, Relay is used to take the motor off line
The following explanations center
ated with motor starting, running, and stopping.
7.2.1 Start Cycle -The relationship between the IQ-
1000
II
and the motor current level during a start cycle is
shown The motor start cycle is initiated when the motor current
exceeds 30% of the full-load amperes setpoint (program menu item 42) assuming the motor was not dition. At this time the message "START" is displayed and the transition timer begins. The duration of the timer is determined by the motor start transition time (item 38) setpoint, which may be set to O seconds to disable the transition function.
in
Figure 7.6.
CURRENT IN
%OF
FLA
Paragraph 8.15, is used for
or
a Trip Relay or Auxiliary Trip
on
the timing associ-
II
monitors
in
a fault situation.
in
a trip con-
The IQ-1000 transition set point level (item 37). If a transition does not
occur before the transition time expires, the IQ-1000 will trip or transition at the user's choice. The run cycle begins as soon as the transition takes place. If transition time (item 38) is set to ately or a transition trip will occur, depending of Table 8.B.
Once a start is declared, start delay timers will also begin timing, unless they are disabled (start delay timers are described
• Instantaneous overcurrent start delay timer. (Pro-gram menu item 16; described and 7.1.3.1.)
• Jam start delay timer. (Program menu item 24; described
• Underload start delay timer. (Program menu item 28; described
II
will transition if the current falls below the
0,
the run cycle will begin immedi-
on
in
Paragraph 8.1.1
in
Paragraph 8.10.3.)
in
Paragraphs 8.11.3 and 7.1.3.4.)
).
This group includes:
in
Paragraphs 8.5.3
II
item 39
PROGRAMMED
TRANSITION
CURRENT
LEVEL
30%
OF FLA
I
..
STOP
r<cYCLE ..... ,
Fig. 7.6 Motor Start
Effective
February
I
..
~~~~-CYCLE
1999
CONTACTOR CLOSES
--------~----------------
and
Run Cycles
START
~~~~~.-.~,~~~~~~-CYCLE
TRANSITION
-----------
I
I
I
1
I
I
RELAY
CLOSES
TRANSITION
POINT
RUN
~~~~~..;I
CONTACTOR
OPENS
I
STOP CYCLE
TRANSITION
RELAY
OPENS
TIME
Page
Courtesy of NationalSwitchgear.com
52
TD
17297D
Disabling the motor start transition (time) function (item
38) cancels any transition time, but these timers, if used, continue to operate independently of the duration of the start cycle. (See Paragraph 8.15 for details.)
7.2.2 Run Cycle -Once the transition occurs, the motor's run cycle is initiated and the message "RUN" displayed. The run cycle continues until the monitored motor current level falls below 5% of its full-load amperes setpoint (item 42) at which point a stop the IQ-1000 (See Figure 7.6.)
The run cycle is another normal motor operating state. Protection functions with run delays are active state once the start delay has expired. The primary func-tion of run delays are:
• Ground fault run delay timer. (Program menu item 13; described
• Jam run delay timer. (Program menu item 25; described
• Underload run delay timer. (Program menu item 29; described
• Phase unbalance alarm run delay timer. (Program menu item 31; described
Keep the start delay for that function has timed out. The actual
run
delay begins timing only after a transient trip condi-
tion occurs. (See Paragraph 8.1.)
7.2.3 Stop Cycle -When the monitored motor current
level falls below 5% of the full-load amperes setpoint (program menu item 42), the stop cycle begins. When the IQ-1000 mode, Ready mode, or any trip mode.
When the anti-backspin delay time function (item 41) is used, it is initiated along with the stop cycle. The anti-backspin function prevents a start cycle's initiation until the user-selected setpoint time elapses. (The and/or Auxiliary Trip Relay is used vent a motor start. See Paragraph 8.17 for more details.)
II
returns to the "READY --3" or stop mode.
is
to prevent nuisance tripping. These
in
Paragraph 8.4.3.)
in
Paragraphs 8.10.4 and 7.1.3.5.)
in
Paragraphs 8.11.4 and 7.1.3.4.)
in
Paragraph 8.12.2.)
in
mind that run delays become enabled only after
II
is
in
the stop cycle, it can be
is
declared and
in
the Program
Trip
in
this instance to pre-
in
is
this
Relay
starts count function's setpoint (item 34) has elapsed can a start cycle be initiated (see Paragraph 8.14).
AC
LINE
7.3
ates
in
a controlled and predictable manner during
incoming shown occur during various The chart assumes a complete, or nearly complete, loss
of
Study the figure and note that at least 3
occur before any of the following events occur. What
occurs is either the IQ-1000 condition or the main contactor drops out. As indicated the figure, the factors which determine which of the con-
ditions occur are:
• The loading of the IQ-1000 ll's power supply at that
• The type of contactor being used
In
1000
the microprocessor has lost intelligence due to the low
voltage condition and will perform a power-up reset when
power
NOTE: The IQ-1000
"THINKING" for approximately three seconds after
the unit
protected during this time and will not be allowed to
start if the unit
8.20).
7.4 CONTROL SIGNAL
communicates with the motor, contactor, and the associ-
ated machine or process through the following means:
• Discrete inputs from devices such as pushbuttons or
• Outputs, Each of these topics is discussed separately
ing subparagraphs.
in
AC
line power.
time
either case, if
II
initiates a "power-down condition".
is
relay contacts
INTERRUPTIONS-The
AC
line interruptions. The events flow chart
Figure 7.7 lists the predictable events which
AC
line interrupts for a typical motor.
II
initiates a power-down
AC
power remains off, eventually the IQ-
restored.
II
will display the message
is
powered up. The motor
is
in
Mode 2 operation (see Paragraph
WIRING-The
in
the form of relay contacts
IQ-1000
AC
In
is
not being
IQ-1000
II
oper-
cycles must
this case
II
in
the follow-
in
A second function also affects the stop cycle. This is the
starts per time allowed function (program menu item 33). It
prevents a motor from being restarted once the user-
in
selected setpoint, reached. (Here again the Trip and/or Auxiliary prevents the restart.) Only when the time allowed for
number of starts per a given time, is
Trip
Relay
Additionally, there are other sensing inputs from the
optional ground fault transformer and current transform-ers. (These are not discussed here.)
The following two inputs are available and may optionally
be used:
Effective
February
1999
TD
Courtesy of NationalSwitchgear.com
172970
AC supply line interruption occurs:
Page
53
NO
4 thru 10 cycles elapse.
Depending on the type used, the main contactor may drop out before the IQ-1000 of the following will occur:
1.
If AC power is restored before the IQ-1000 the contactor can reclose, and the motor can continue running.
2. If AC power is not restored before the IQ-1000 by the loss, a power-up reset will be initiated and the system will be ready
11
is affected by the loss. If this occurs, one
II
is affected,
II
is affected
for
another start
1
•
YES
Variables are:
1. Drop-out time of different contactors varies
2. Loading of the IQ-1000 ll's power supply
6 thru
The IQ-1000
2.
Normal operation continues. Motor current levels monitored.
or
from 4 to 20
-especially to alphanumeric display.
10
cycles elapse.
1.
If a trip is detected before power loss, it will be retained on power-up.
It performs power-up reset and returns to the ready mode awaiting a new start con-dition.
more cycles.
11
detects the AC power loss, and:
1
1f
AC power is restored,
Fig.
7.
7
AC
Interrupt Events Flow Chart
Effective
February
1999
the
contactor does not automatically reclose until start pushbutton is depressed.
Page
Courtesy of NationalSwitchgear.com
54
TD
17297D
• REMOTE INPUT (terminal 8 on rear of unit). This input is used either to externally reset from a trip con-dition, to initiate a trip condition, or to detect a motor stop (see Paragraph 8.22).
• INC SEQUENCE (terminal 10 input affects the incomplete sequence report back function (program menu item 40) associated with the ransition operation (see Paragraphs 7.2.1 transition operation (see Paragraphs 7.2.1 and 8.16 for details).
7.4.1 Discrete Inputs -The discrete input terminals, if
used, accept user-supplied 120 such as switches, pushbuttons, relay contacts, etc. The IQ-1000 ll's input contacts must remain closed for a mini-mum time of 17 cycles reliably sensed by the IQ-1000 distinction to be made between electrical noise and the actual 50/60 Hz signal. The characteristics of the circuits associated with these inputs are listed
A
WHEN PLANNING DISCRETE INPUT WIRING,
ENSURE THAT THE LEAKAGE CURRENT TO THE INPUT TERMINALS DOES NOT EXCEED 10 MA. 50/60 HZ LEAKAGE CURRENTS CAN BE EXCESSIVE WHEN DISCRETE INPUT SIGNALS ARE DERIVED FROM CERTAIN CONTROL DEVICES DEVICES ARE SEPARATED FROM THE IQ-1000 LONG WIRE RUNS. OUS SITUATION COULD INVOLVE THE REMOTELY LOCATED CONTACTS OF A PROGRAMMABLE CON-TROLLER'S OUTPUT MODULE. THESE COULD HAVE A LEAKAGE GREATER THAN 10.0 MA. EXCESSIVE LEAKAGE CURRENTS CAN CAUSE SPURIOUS SIGNALS AT THE IQ-1000 ll'S DISCRETE INPUT TERMINALS. THESE MAY INTERFERE WITH THE START AND RUN CYCLES' MOTOR SEQUENCES. ERRATIC SEQUENCES MAY CAUSE PERSONAL INJURY
in
order for the new state to be
DANGER
AN
EXAMPLE OF THIS DANGER-
OR
EQUIPMENT DAMAGE.
on
rear of unit). This
VAC
from field devices
II.
This duration allows a
in
Table 7.A.
OR
INPUT
II
BY
7.4.2 Output
tacts correspond to the externally accessible terminals of the internal relays, as shown rated as:
• 240
• 30 VDC at 1 O amperes (resistive) The
Trip, cussed throughout Section graphs 8.14 thru 8.20.2. Also, see Paragraph 3.2 for the Auxiliary Trip Relay.
7.5 WIRING CONSIDERATIONS
plan that shows the interconnections between the IQ-1000
II
and the associated machine or process must be developed by the user. This paragraph contains informa-tion needed by the application engineer who is develop-ing a specific wiring plan. A typical example of a wiring plan is shown
All wiring must be trical Code as well as any other applicable state and/or
local codes.
7.5.1 Wire Routing and Wire Types -When routing
wires between the starter and the associated machine or
process equipment, follow these guidelines:
Guideline 1 -Do not route the control or RTD conduc-
tors through the high-voltage compartment of the motor
starter. Electrical Components Division for specific instructions.
Guideline 2 -Separate the lower voltage (120
from the higher voltage (440
as much as possible. tance of 1.5 ft. (45 cm) between the two types.
Guideline 3
of the motor starter cabinet should be at least #14 stranded copper wire.
If
Contacts-The
VAC
at 10 amperes (resistive)
Transition, and Auxiliary Trip Relays are dis-
in
Figure 7.9.
in
conformance with the National Elec-
it is necessary to do
In
general, maintain a minimum dis-
-Any
low-voltage control wiring routed out
IQ-1000 ll's output con-
in
Figure 7.8. These are all
8,
but especially
-A
so,
consult Cutler-Hammer
VAC,
or higher) conductors
in
suitable wiring
Para-
VAC)
AWG
TABLE 7.A: DISCRETE INPUT CIRCUIT
CHARACTERISTICS
Characteristic
Input voltage
Opto isolation
Input impedance
Input current drain
(ON)
Input current drain
(OFF,
max.)
Specification
120
VAC
ONLY
1500 volts
26K ohms
4.5mA
10.0 mA
Guideline
RTD
per,
Guideline 5 -The wiring between the RTD Module and
the RTDs
shielded cable.
7.5.2
each note the following requirements:
4-The
Module should be at least #14 AWG stranded cop-
3-conductor shielded cable.
in
RTD
Wiring
RTD
must be wired as shown
wiring between the IQ-1000
the motor must be #18 AWG, 3-conductor
-If
the optional RTD Module is used,
in
Figure 7.10. Also,
Effective
II
and the
February
1999
TD
Courtesy of NationalSwitchgear.com
17297D
120V/240V
4-20
MA
OUTPUT
TRANSITION
AUTO
EARTH
REMOTE
REMOTE
REMOTE
INC SEQUENCE
GROUND COMMON
NEUTRAL
COMMON
SEL
INPUT
25
24
1
2
3
4 5 6
7
8
9 10
0
0
':j
tl~I
~
~
Ji
l~
...
I
::::
~
~
= =
'
I l
::::
::
I I
::::
=
I I
::::
<l>
0
0
lil
J%1
0
0
JVI
l~I
0
0
(~
lil
J~I
0 0
~
•·
0
IQ 1000 I
---
DDDDDDD DDDDDDD
=
DDDDDDO
=
DDDDDDD
=
DDDDDDD DDDDDOD
=
0
191
I
0
0
0
0
r;-,
..
..
..
c!!-
..Q.
o=:
m'.i
~
ti
...
-
IE
t:
~
I )
l
:=
=
I
= =
f
= =
I
l
ra:J
r
~
~
0
0
"
Page
55
CT
Connections
CoMMunrco. Port
Frber-Dptrc Connector
23
22
\./Iring
21
RTD
20
19
18
ALARM
17
16
15
AUX
14
13
12 TRIP
11
,/
trans
to
Option
TRIP
Fig.
7.8 IQ-1000 II Rear Panel Terminals
• Use 10-ohm copper, 100-ohm platinum, 100-ohm nickel, or 120-ohm nickel RTDs. The Universal RTD Module is DIP switch selectable to read any of these
types of RTDs.
• Unused RTD inputs on the RTD Module should be wired together. For example, if MW5 and MW6 are
unused, MW5 terminals 13, 14, and 15 should be wired to each other and MW6 terminals 17, 18 and 19 should be wired together.
• The interconnecting cable between the RTD Module
and the RTD must have the cable's shield connected
to the RTD Module
RTD end and use shrink tubing or electrical tape to insulate it.
• When making connections between the RTD Module
and an RTD that has only two leads, connect two of the interconnecting cable's leads to one of the RTD's leads (see Figure 7.10). Make this connection as
Effective
February
1999
ONLY.
Cut the shield short at the
close to the motor as possible. Tie the third intercon-necting lead to the remaining RTD lead.
• When making connections between the RTD Module and a three lead wire to the RTD Module terminal as shown in Figure
7.10.
7.5.3
nected as follows to ensure proper operation:
• Connect the ground side of the control power trans-
• Connect a #14 AWG wire between terminal 5 and the
Grounding-The
former to terminal 7 of the IQ-1000 II.
main ground bus of the system.
terminals 5
terminal 5 to the system ground bus must be a non-current carrying ground.
RTD,
connect the shield and drain
IQ-1000
and
7 together. The ground connecting
II
should be con-
Do
NOT
connect
Page
Courtesy of NationalSwitchgear.com
56
TD
17297D
• Connect one side of the CTs to the system ground. System noise may disrupt the IQ-1000
II
if the CTs
are tied to a current carrying ground.
AC
The sizing and type of insulation for the and the grounding electrode conductor must be
supply line
in
con-
formance with the National Electrical Code.
7.6 ENVIRONMENTAL CONSIDERATIONS -
Consideration must be given to the location
L3
L2
L3
ISW
)
L2
MAIN
FUSE
II:::J]
of
the IQ-
..
C
If---<
B
..
f---<
Ll
L1
A
..
f---<
-
-
GNO
1000
II
enclosure
in
the plant. The unit operates within an ambient range between O to 70°C (32 to 158°F) with a humidity factor of 95% non-condensing.
The IQ-1000 ll's circuit boards are conformal-coated to withstand environmental contaminants. However, special
or
precautions may be required for extremely dirty
corro-sive environments (contact the Power Management application Support Team).
CTS
r-----------,
I GFCT I
GNO
T3
l2
}
Tl
.
OR
ro~
LOAD DEVICE
UNDER CONTROL
"
4
AC
SUPPLY
10
10-1000
18 19
AUXILIARY TRIP
15 16
Fig.
7.9 Partial Wiring Plan Example
CONT
• !'r•N
ACTS
PRIMARY
FUSES
-GNO
7
NON-CURRENT CARRYING
GROUND
TRIP
CONTACTS
AUX TRIP
IQ-1000
BACK WITH
CONNECTIONS
12
0
O 0
0000000 0000000 0000000 0000000 0000000 0000000
0 0
00
VIEW
JUMPER
II
Effective
February
1999
TD
Courtesy of NationalSwitchgear.com
17297D
Page
57
Fig.
7.
10
RTD Wiring Examples
CABLE
SHIELD
VIRE
UNIVERSAL MODULE
RTD
TERMINALS
3 2
1---+--+---------+----,f---'
1
T\./0
LEAD
3
2
1---~---------+---+---,Jfl----4
1
THREE
LEAD
RTD
RTD
CABLE
SHIELD
\./IRING
\./IRING
RTD
TERMINALS
Effective
February
1999
Page
Courtesy of NationalSwitchgear.com
58
TD
17297D
Effective
February
1999
TD
Courtesy of NationalSwitchgear.com
172970
Page
59
SECTION 8
PROGRAMMING THE IQ-1000
8.0 GENERAL -This section contains information
needed by an application engineer to organize the set-
II
point values for a specific IQ-1000 easily entered. Thirty-eight separate functions are pro-vided. (See Table 8.A which acts as a quick locator alphabetized listing.) It is strongly recommended that the setpoints be determined, recorded and verified
before any entry is begun. For assistance, a Set Point
Record Sheet is included to act as a permanent record of the set point values for an individual application (see Table 8.B). Copies of it should be made and stored in a number of locations, including the enclosure containing
IQ-1000 II.
the
Not all setpoint functions and associated values or set-
tings may be required
In
such cases, make one of the following notations on the
Record Sheet.
• Place
• Write in the value required to disable the function.
A copy of a correctly filled-in Set Point Record Sheet must be given to the individual responsible for value entry. The lQ-1000 fixed sequence that is duplicated on the Set Point Record Sheet. Thus, the sheet minimizes programming time. (Specific entry procedures are described
4.3.)
N/A or some other notation
function/value has no effect on operation. (For exam-ple, winding temperature, when there is no RTD Module.)
(Specific instructions on disabling set point functions are given in the following descriptions.)
by
a given IQ-1000
II
displays its setpoint functions
NOTE: Unless specifically stated otherwise, it can
assumed that when operating conditions are greater than the user-selected setpoint, the function is
initiated.
8.1
START AND RUN
delays are used with many
II
the IQ-1000
running. Attention should be paid to the units of different delays due to the varying requirements for different types of protection.
disable their related protection functions to prevent tran-
so that they may be
all
II
application.
in
the space if the
in
a
in
Paragraph
be
and run
the protection functions of
II
AND SET POINT DESCRIPTION
sient motor conditions during the motor inrush period
from creating a trip.
All start delays are tied to the transition cycle respect ated by the IQ-1000 tions are the instantaneous overcurrent and ground fault functions which react Once a start is declared, start delays may time out before or after the IQ-1000 depending on the type of protection. If a trip condition during a start is maintained past the end of the start delay, a trip may occur, never allowing the IQ-1000 transition to the run mode. See section 7.2 for a descrip-tion of start, run and stop cycles.
The start delays provided
• Ground Fault Start Delay -in line cycles
• Instantaneous Overcurrent Start Delay -in line
• Jam Start Delay -
• Underload Start Delay -
only. The beginning of most start delays are initi-
II
declaring a start; the only excep-
in
line cycles instead of seconds.
II
has transitioned to the run state
in
the IQ-1000
cycles
in
seconds
in
seconds
in
one
II
11
are as follows:
to
8.1.2 Run Delays -Run delays are used to provide a
time-based filter on transient trip conditions which might cause nuisance tripping.
The run delay is initiated by a transient trip condition
occurring after the associated start delay has timed out. Once the run delay has begun, the trip condition must be maintained for the full length of the run delay. If at any
time the condition goes away and then returns, the run
delay is reset. The trip condition must remain present for the full length of the run delay time to initiate a trip.
The fastest response for a function with both start and run delays is found by adding the two programmed delays together. This would be the response time if the trip condition were detected at any point during the start delay.
The run delays provided in the IQ-1000
• Ground Fault Run Delay -in cycles
• Jam Run Delay -
• Underload Run Delay -in seconds
in
seconds
II
are as follows:
Effective
February
1999
Page
Courtesy of NationalSwitchgear.com
60
TD
17297D
• Phase Unbalance Alarm Run Delay -
8.2 SETPOINT ITEM 1, OPERATING MODES -One
of two different operating modes may be selected by the user. One mode is used when the IQ-1000 a motor or being tested using a three-phase current source. A second mode is used when the IQ-1000 being tested or programmed using a single-phase current source.
In
all cases where three-phase current is being moni-
II,
tored by the IQ-1000 selected. The three-phase mode is displayed gram mode as:
When
in
the Program mode, pressing either the Raise or Lower pushbutton causes the display to toggle between "3 PHASE" and
In
cases where the IQ-1000 only available test method is using a single-phase current source, then the single-phase test mode must be selected. The single-phase test mode is displayed
Program mode as:
When the single-phase test mode is selected, most of the
IQ-1000
Unbalance alarm and trip features, however, can only be tested with a three-phase current source. test mode, the phase unbalance protection feature is dis-
abled. When the operating mode function is displayed, it will tog-
gle between the following two messages:
II
"1
protective features can be tested. The Phase
the three-phase mode must be
3 PHASE
PHASE" messages.
II
is to be tested, and the
1 PHASE
in
seconds
II
is protecting
in
the Pro-
in
In
single-phase
II
is
the
If
the optional RTD Module is not used with the IQ-1000
II,
there is no need to enter these values.
If the RTD Module is installed with no RTDs connected,
II
the IQ-1000 display is used for shorted or open RTDs. However, all unused RTD Module terminals should be jumpered, as described display a numeric value.
NOTE: If an RTD Module is not connected or is connected improperly, all RTD information will be removed from the metering display.
Setpoint item 2 determines whether the temperatures displayed from the RTDs are
Pressing either the Raise or Lower pushbutton causes
the display to toggle between the following messages:
The temperature range displayed is from 32-390°F, and from 0-199°C. The IQ-1000
peratures using degrees C and then displays the value degrees C When degrees C is selected, displayed RTD values are
incremented selected, RTD values increment
degree steps (this is due to rounding off the conversion calculations for display purposes; accuracy of the
setpoints is not affected).
8.3.1 Setpoint Items 3 and 7, Stator Winding
Temperature
the temperature of a motor's stator windings and using this data to determine the motor protection curve.
will display
in
Paragraph 5.3.2. All valid RTD readings will
or
degrees
in
one degree steps. If degrees F is
-The
a"-"
RTD RTD
II
F,
depending
IQ-1000
for each
in
degrees F or degrees
INF
INC
software calculates all tem-
in
II
is capable of monitoring
RTD.
This same
on
setpoint item
either one or two
RTD
2.
C.
in
3 PHASE
This menu item is numbered 1
8.3 SETPOINT ITEM 2, RTD MONITORING -Assum-
ing that optional RTDs are used, and the optional Module is installed, the IQ-1000 ing the operating temperatures at three key motor loca-tions. Both trip and alarm setpoints are available for the
three placement areas. These are the motor's:
• Stator windings
• Motor bearings
• Load bearings
1 PHASE
in
Table 8.B.
II
is capable of monitor-
RTD
Effective
February
1999
TD
Courtesy of NationalSwitchgear.com
17297D
Page
61
TABLE 8.A: ALPHABETIZED FUNCTION LISTING
Function
Anti-backspin delay Auxiliary temperature (alarm) Auxiliary temperature (trip)
Current transformer ratio
Differential trip on remote input
Paragraph
8.17
8.3.4
8.3.4
8.28
8.22 Frequency (50/60 Hz) 8.19 Full-load amperes 8.18
Winding temperature (alarm) Winding temperature (trip)
8.14.2
8.15.1
8.15.2
8.20.1
8.20.2
8.22
8.7
8.11.1
8.11.4
8.11.3
8.11.2
8.3.1
8.3.1
Individual setpoint values can be selected for both trip and alarm conditions. These settings apply to all winding RTDs. The function is displayed
WDTxxx
WD
Axxx
in
the program menu as:
Here the letters T and A represent trip and alarm, respec-tively. The letters xxx represent the user-chosen value. These program menu items are numbered 3 and 7
in
Table 8.B. The ranges of available setpoint values are:
Trip:
0-199°C
I 32-390°F
(in 1 °C increments)
Alarm:
0-199°C
I 32-390°F
(in 1 °C increments)
8.3.2 Setpoint Items 4 and 8, Motor Bearing Temperature -The IQ-1000
II
is capable of monitoring
two motor bearing RTDs.
Individual setpoints can be selected and entered for both
in
trip and alarm conditions. The function is displayed
the
program menu as:
MB T
XXX
MB
Axxx
Here the letters T and A represent trip and alarm, respec-tively. The letters xxx represent the user-chosen value. These menu items are numbered 4 and 8
in
Table 8.B.
Effective
February
1999
Page
Courtesy of NationalSwitchgear.com
62
TD
17297D
The ranges of available setpoint values are:
Trip: Alarm:
0-199°C I 32°-390°F (in 1 °C increments) 0-199°C (in 1 °C increments)
I 32-390°F
8.3.3 Setpoint Items 5 and 9, Load Bearing Temperature -
two of the motor's load bearing temperatures. Individual setpoints can be selected and entered for both
trip and alarm conditions. The function is displayed program menu as:
Here the letters T and A represent trip and alarm, respec-tively. The letters xxx represent the user-chosen value. These menu items are numbered 5 and 9
The ranges of available setpoint values are:
Trip: Alarm:
The IQ-1000
LB T
XXX
LB A
XXX
0-199°C (in 1 °C increments) 0-199°C I 32-390F (in 1 °C increments)
II
is capable of monitoring
I 32-390F
in
Table 8.B.
in
the
8.3.4 Setpoint Items 6 and 10, Auxiliary
Temperature -
one auxiliary temperature. Individual setpoints can be selected and entered for both
trip and alarm conditions. The function is displayed program menu as:
The IQ-1000
11
is capable of monitoring
in
the
leakage currents. Use of this function requires nal 50:5 ground fault current transformer to be installed the application. The turns ratio assumed by the IQ-1000 II
is always 50:5. This setpoint function can only be
applied to a grounded system, as described
an
exter-
in
Paragraph
in
7.1.6.
There are three distinct setpoints associated with this function. These are:
• Trip level (in primary amperes)
• Start delay (in cycles)
• Run delay (in cycles) Assuming a ground fault transformer is being used, all
three of these setpoint functions must be "used"
IQ-1000 ting the start delay to 1 line cycle and the run delay to 0 line cycles. If no ground fault current transformer is con-nected, these setpoints are ignored and no ground fault protection is provided.
II.
The delay functions can be defeated by set-
in
the
NOTE: If the run delay is set to 0, trips may occur at a
lower current level than specified due to the
in
sampling used
maintaining the high speed
response of this function.
8.4.1 Setpoint Item 11, Ground Fault Trip Level -
The IQ-1000
above which a trip will occur after the specified start and
run delays. The set point is defined
ground fault trip level is displayed
as:
II
has a selectable ground fault trip level
in
amperes. The
in
the program menu
GFxx
AXT
XXX
AXAxxx
Here the letters T and A represent trip and alarm, respec-tively. The letters xxx represent the user-chosen value. These menu items are numbered 6 and 10
The ranges of available setpoint values are:
Trip: Alarm:
The auxiliary RTD can be used to monitor a separate temperature, such as motor case temperature.
8.4 GROUND
function provides protection against excessive ground
0-199°C I 32-390°F (in 1 °C increments) 0-199°C (in 1
°c
increments)
FAULT-
in
Table 8.B.
I 32-390°F
The IQ-1000 ll's ground fault
Here the letters xx represent the user-determined current
level above which a trip condition occurs. This menu item
ground current that can be generated by power factor correction capacitors during starting to clear. The appli-cation of a start delay is described
The ground fault start delay function is displayed
program menu as:
II
provides a start lockout delay to allow the
in
Paragraph 8.1.1 .
in
the
GFSD xx
Effective
February
1999
TD
Courtesy of NationalSwitchgear.com
172970
Page
63
Here the letter xx represent the user-determined delay, which when reached, allows a trip condition to be initi-ated. This menu item is numbered 12
The range of available set point values is:
Start delay: 1-20 AC line cycles
(in cycle increments)
in
Table 8.B.
8.4.3 Setpoint Item 13, Ground Fault Run Delay -
The IQ-1000 tary disturbances trip. The application of a run delay is described graph 8.1.2.
The ground fault run delay function is displayed program menu as:
Here the letters xx represent the user-determined delay, which when reached, allows the trip condition. This menu item is numbered 13
The range of available setpoint values is:
Run delay: 0-10 AC line cycles
II
provides a run delay to prevent momen-
in
the system from causing a nuisance
in
GFRD
in
Table 8.B.
(in 1 cycle increments)
** Disable setting for GFRD -O cycle **
xx
in
Para-
the
8.5 INSTANTANEOUS OVERCURRENT PROTECTION
current function monitors motor current basis. It requires no more than two line cycles to detect a trip condition. Because of the magnitude of current that can be seen delay is provided.
There are three distinct setpoints associated with this function. These are:
• Instantaneous overcurrent enable/disable
• Instantaneous overcurrent trip level (in percent of
-The
in
an instantaneous overcurrent, no run
IQ-1000 ll's instantaneous over-
on
a continuous
peak full-load amperes)
• Instantaneous overcurrent start delay (in cycles) (Paragraph 7.1.3.1 details those application conditions
The display will toggle between the following two mes-sages:
IOCON
If the IOC OFF message is displayed when leaving Pro-gram mode, the IOC set points will be ignored and an IOC trip will never be acknowledged. This menu item is numbered 14
NOTE: When IOC OFF is selected, the IOC trip level (menu item 15) and IOC start delay value (menu item
16) will have
a"-"
displayed next to them
in
the
Program Display.
Level
in
% Full-load Amperes -The IQ-1000
an
vides the peak full-load amps. This provides the fastest response possible when a fault condition occurs.
instantaneous overcurrent trip level
II
pro-
in
percent of
NOTE: The chosen setpoint value must be equal to, or higher, than 1.6 times the locked-rotor current ratio (provided by the motor manufacturer).
NOTE: For the IOC trip level to be effective, set it below your fuse interrupting rating or your contactor withstand rating.
The instantaneous overcurrent function,
in
load amperes, is displayed
Here the letters level, which, when reached, allows a trip condition. This menu item is numbered 15
The range of available setpoint values is:
Trip: 300-1600% of full-load amperes
xxxx
represent the user-determined
(in 1 % increments)
the program menu as:
IOC
xxxx
in
Table 8.B.
in
percent of full-
NOTE: When IOC OFF (setpoint item 14) is selected, the IOC trip level will have in
the Program Display.
a"-"
displayed next to it
NOTE: When IOC trips occur, the displayed metered values will normally not reflect the actual fault current. This is due to the averaging used to calculate the display value.
allow the unit to ride through the first cycles of inrush cur-rent during starting. The application of a start delay is described motor's start and stop cycles, refer to Paragraph 7.2.)
The instantaneous overcurrent start delay setpoint func-tion is displayed
Here the letters xx represent the user-determined delay. This menu item is numbered 16 The range of available setpoint values is:
8.6 LOCKED-ROTOR PROTECTION -functions operate together to specify a point damage curve. These trip condition components are:
• Locked-rotor current (in percent of full-load amperes)
• Locked-rotor time or stall time (in seconds) This current level and time, when reached, create a
locked-rotor trip condition. (More information
the motor protection curve is contained
7.1.3.2 and 7.1.4.)
NOTE: The locked-rotor current and the maximum allowable stall time values must be obtained from the motor manufacturer.
in
Paragraph 8.1.1. (For more details
in
the program menu as:
Delay: 1-20
(in 1 cycle increments)
on
AC
how these setpoint functions affect
A
11
provides a start delay to
IOCSD
xx
in
line cycles
CAUTION
Table 8.B.
Two
in
Paragraphs
on
IQ-1000
on
the motor
the
II
stalled. This set point along with the stall time defines the thermal capacity of the motor.
in
The locked-rotor current function is displayed gram menu as:
LRC
xxxx
Here the letters the motor manufacturer. This menu item in
Table 8.B.
The range of available setpoint values is:
Current:
8.6.2 Setpoint Item 18, Locked-Rotor Time (Stall Time) -The maximum allowable stall time function
specifies the amount of time a locked-rotor condition can
be maintained before damage is done to the motor. This value is supplied by the manufacturer and is used junction with the locked-rotor current.
The stall time setpoint function is displayed
gram menu as:
Here the letters xx represent the maximum allowable time determined by the motor manufacturer. This menu
item is numbered 18
setpoint values is:
Time: 1-60 seconds
8.7 SETPOINT ITEM 19, ULTIMATE
mate trip function defines the current level above which a
trip will eventually happen. This value represents
asymptotic line
the motor will never be damaged.
xxxx
represent the level determined
is
300-1200%
(in
1 % increments)
in
(in 1 second increments)
on
the motor damage curve below which
of
full-load amperes
LRTxx
Table 8.B. The range of available
TRIP-The
the pro-
by
numbered 17
in
con-
in
the pro-
ulti-
an
THE ROTOR TEMPERATURE PROTECTION ALGO-RITHM USES THE LOCKED-ROTOR CURRENT AND THE MAXIMUM ALLOWABLE STALL TIME VALUES TO CALCULATE THE ROTOR PROTECTION CURVE. INCORRECTLY CHOSEN SET POINT VALUES FOR THESE FUNCTIONS CAN RESULT IN EXCESSIVE ROTOR TEMPERATURES AND EVENTUAL MOTOR DAMAGE.
8.6.1 Setpoint Item 17, Locked-Rotor
locked-rotor current value specified by the motor manu-facturer is the current a motor will draw if the rotor
Current-The
is
This setpoint is used when RTDs are not employed to
define the level above which the 12T accumulator will start
to migrate toward a trip. If a service factor is supplied with
the motor, it can be multiplied times the full-load amp rat-
ing to give the maximum ultimate trip level. For example,
a motor with a 1.25 service factor can use an ultimate trip
level of 125 percent of full load. (Paragraph 7.1.3.3 describes application considerations related to value selection.)
Some possible reasons for using a conservative
approach to set the ultimate trip below 100% are:
Effective
February
1999
TD
Courtesy of NationalSwitchgear.com
17297D
Page
65
• When ambient temperatures above 40°C are antici-pated and the optional RTD Module is
not used
in
the application. (Environmental temperature consid-
in
erations are discussed
Paragraph 7.1.3.6.)
• When the motor is properly rated, yet additional safety is critical for the application.
A
IF THE ULTIMATE TRIP SET POINT VALUE
CAUTION
IS
ABOVE 100% AND THE MOTOR DOES NOT HAVE A SER-VICE FACTOR RATING HIGHER THAN
1,
MOTOR
DAMAGE CAN RESULT.
The ultimate trip function is displayed
in
the program
menu as:
UTC XXX
Here the letters xxx represent the user-determined per-cent of full-load amperes for the ultimate trip level. This menu item is numbered 19
in
Table 8.B.
The range of available setpoint values is:
Trip: 85-125% of full-load amperes
(in 1 % increments)
8.8 SETPOINT ITEM 20, 12T ALARM -The 1
2
T alarm function refers to the current-squared multiplied-by-time algorithm discussed at Paragraph 3.2.2. The accumu-
2
lated
1
T is directly proportional to the rotor temperature.
The 12T trip is a level selected
in
percent of the 12T trip value. This gives the user some idea of how close to a trip the IQ-1000
II
is since the 12T trip point is derived from
the programmed motor parameters and maintained inter-
nally. (The maximum rotor temperature trip point is
explained
in
Section 3.)
The range of available setpoint values is:
Alarm:
60-100% of the
2
1
T trip level
(in 1 % increments)
** Disable setting for 1
The 12T alarm level is explained on the Help screen as 12T ALARM LEVEL
IN%
1
culated by the IQ-1000
2
TA
-100% of trip **
2
T
TRIP.
The actual trip level is cal-
II
internally, as discussed
in
Para-
graph 3.2.2.
NOTE: The 12T accumulator is cleared every time the IQ-1000 used to clear an 1
II
is placed
in
Program mode. This can be
2
T trip without waiting for the motor
to cool.
8.9 SETPOINT ITEM 21,
The reset function allows either manual or automatic resetting from a locked rotor or matic mode, the IQ-1000
2
1
T accumulator has cooled below the 12T alarm level dis-
in
cussed
In
the manual mode,
in
one of three ways after the 12T accumulator has cooled
Paragraph 8.8 or is cleared
2
1
T RESET FUNCTION -
2
an
1
T trip.
In
the auto-
II
will reset an 12T trip after the
in
Program mode.
2
an
1
T trip must be reset by the user
below the 12T alarm level. One is to push the Reset button on
the IQ-1000
II
operator's panel. The second is to set
the remote input setpoint to the reset mode (menu item
46) and apply 120 back of the IQ-1000
VAC
across terminals 8 and 9
II.
The third way to reset
an
on
the
2
1
T trip is to issue a command over the communications port from a host computer.
With this function, either MAN RST or AUTO RST must
be selected for every application. Pressing either the Raise or Lower pushbutton causes the display to toggle
between the two following messages:
MAN RST AUTO RST
This function also determines when the 12T trip condition can be reset, as described to 100% the alarm is set, the sooner the motor can be
restarted; however, the motor inrush may create another
trip if the motor has not been allowed to cool.
2
1
T alarm function is displayed
The
as:
Here the letters xxx represent the user-entered percent, at which level the alarm condition is initiated. This menu item is numbered 20
Effective
February
1999
in
in
Paragraph 8.9. The closer
in
the program menu
Table 8.B.
This menu item is numbered
8.10 JAM
FUNCTIONS-The
jam function for initiating
failures functions is given
in
a driven load. (More information
in
Paragraph 7.1.3.5.)
21
in
Table 8.B.
IQ-1000
an
alarm or a trip for mechanical
II
provides a
on
the jam
There are four distinct setpoints associated with the jam
function. These are:
• Alarm level (in % FLA)
• Trip level (in % FLA)
• Start delay (in seconds)
Page
Courtesy of NationalSwitchgear.com
66
TD
172970
• Run delay (in seconds)
8.10.1 Setpoint Item 22, Jam Alarm Level -The jam
alarm level set point function specifies the current level above which measured as a percent of full-load amperes).
The jam alarm level setpoint function is displayed program menu as:
Here the letters of full-load amperes. This menu item is numbered 22 Table 8.B.
The range of available setpoint values is:
Alarm: 100-1200% of full-load amperes
If the jam alarm level is not disabled, it should be set at a
value below the jam trip level (setpoint item 23).
an
alarm condition is initiated (this level is
JMA
xxxx
represent the user-entered percent
(in 1 % increments)
** Disable setting for
xxxx
JMA
-1200% **
in
the
in
8.10.2 Setpoint Item 23, Jam Trip Level -The jam
trip level set point function specifies the current level above which a trip condition is initiated (this level is mea-sured as a percent of full-load amperes).
JAMS
Here the letters xx represent the number of seconds selected to block out the jam function. This menu item is numbered 24
The range of available setpoint values is:
Start delay: 0-60 seconds
in
Table 8.B.
(in 1 second increments)
**Disable setting for JAMS -O seconds **
8.10.4 Setpoint Item 25, Jam
1000
II
provides a jam run delay to allow for heavy loads which are loaded and unloaded, such as a conveyer belt drive. The application of a run delay is described graph 8.1.2.
The jam run delay function is displayed menu as:
JAMR
Here the letters xxx represent the user-selected delay, at which time the trip occurs. This menu item is numbered 25
in
Table 8.B.
xx
Run
Delay -The IQ-
in
the program
XXX
in
Para-
in
The jam trip level setpoint function is displayed gram menu as:
JMT
xxxx
Here the letters of full-load amperes. This menu item is numbered 23 Table 8.B. The range of available setpoint values
Trip: 100-1200% of full-load amperes
xxxx
represent the user-entered percent
1 % increments)
(in
**Disable setting for
JMT
-1200% **
the pro-
in
is:
8.10.3 Setpoint Item 24, Jam Start Delay -The IQ-
1000
11
provides a start delay to allow high inertia loads to be accelerated over a long period of time without a nui-sance trip. The application of a start delay is described Paragraph 8.1.1. The jam start delay function is displayed in
the program menu as:
in
Effective
February
1999
TD
Courtesy of NationalSwitchgear.com
172970
TABLE 8.B: SET POINT RECORD SHEET
Page
67
Program Date Unit
ID/Starter Type
Motor
HP
___________
FLA
_____________
SF
______________
Item
No.
S VER XX N/A N/A
0
SOFTWARE VERSION NUMBER
X PHASE Toggles between
1
SINGLE PHASE TEST MODE OR THREE
___________________
Program Menu Display
Mfgr.
_______
LRA
_______
RTD Type
1•2
3
______
Selected
Values
Control W. Serial. Stall Time Accel Time Other
Set Point Ranges Selection
1 PHASE and 3 PHASE
PHASE PROTECTION MODE
2 RTD
3
4
5
6
7
8
9
10
11
IN
X Toggles between
RTD TEMP
WDTXXX
WINDING TEMP TRIP
MBTXXX
MOTOR BEARING TRIP
LB
TXXX
LOAD BEARING TRIP
AXT
XX 0-199°C/32-390°F (1° incre.)
AUXILIARY TRIP
WDAXXX
WINDING TEMP ALARM
MBAXXX
MOTOR BEARING ALARM
LBAXXX
LOAD BEARING ALARM
AXAXXX
AUXILIARY ALARM
IN
DEGREES F OR DEGREES C
IN
DEGREES
IN
DEGREES
IN
DEGREES
IN
DEGREES
IN
DEGREES
IN
DEGREES
IN
DEGREES
IN
DEGREES
RTD
0-199°C/32-390°F (1° incre.)
0-199°C/32-390°F
0-199°C/32-390°F (1° incre.)
0-199°C/32-390°F (1° incre.)
0-199°C/32-390°F (1° incre.)
0-199°C/32-390°F
0-199°C/32-390°F (1° incre.)
GFXX
GROUND
FAULT
TRIP LEVEL
IN
AMPS
12 GFSD XX 1-20
GROUND
FAULT
START DELAY
IN
CYCLES
13 GFRD XX
14
GROUND
IOCXX
FAULT
RUN
DELAY
IN
CYCLES
Toggles between IOC ON and IOC OFF ENABLE OR DISABLE INSTANTANEOUS IOC OFF displays OVERCURRENT FUNCTION
15
IOCXXXX
INSTANTANEOUS OVERCURRENT
5
FLA
IN
%
Schematic"--------------
Order#
_________
______
___________
INF
and
RTD
INC
(1
° incre.)
(1
° incre.)
1-12
AC
(1
amp. incre.)
AC
cycles
(1
cycle incre.)
0-1 O AC
(1
cycles
cycle incre.)
300-1600%
(1
% incre.)
Volts
___
Set Point
Disable Value
12
0
_
_
__
_
Effective
February
1999
Page
Courtesy of NationalSwitchgear.com
68
TD
17297D
Item
No.
16
IOCSD XX 1-20 cycles
Program Menu Display
2
1
•
Selected
Values Disable Value
Set Point Ranges Selection
INSTANTANEOUS OVERCURRENT START
17
18
DELAY
LRCXXXX
LOCKED ROTOR CURRENT
LRTXX
MAXIMUM ALLOWABLE STALL TIME
IN
CYCLES
IN
% FLA
IN
SECONDS
19 UTC XXX
20
21
ULTIMATE TRIP CURRENT
2
1
TAXXX
2
1
T ALARM LEVEL
MAN RSTAUTO RST
4
4
IN%
IN
2
1
T TRIP
% FLA
Toggles between MAN RST
and AUTO RST displays
AUTO OR MANUAL 12T RESET
22
JM
AXXXX
23 JM
JAM ALARM LEVEL
TXXXX
JAM TRIP LEVEL
IN%
IN%
FLA
FLA
24 JAMS XX
JAM START DELAY
IN
SECONDS
25 JAMR XXX
JAM
RUN
26
ULA
27 UL
DELAY
XX
UNDERLOAD ALARM LEVEL
TXX
UNDERLOAD TRIP LEVEL
IN
SECONDS
IN
IN
% FLA
% FLA
28 ULSD XXX
UNDERLOAD START DELAY
IN
SECONDS
29 ULRD XX
IN
SECONDS
30
UNDERLOAD RUN DELAY
PUA
XX
PHASE UNBALANCE ALARM LEVEL (1% incre.)
31
PURD XXX
PHASE UNBLALANCE ALARM IN
32 12T TRIP
4
2 SEC
SECONDS
4
RUN
DELAY
2 SECOND DELAY OR 12T TRIP ON PHASE
UNBALANCE
33 ST/T XX
STARTS PER TIME ALLOWED
(1
cycle incre.)
300-1200%
(1% incre.)
1-60 sec.
(1
sec. incre.)
85-125%
(1% incre.)
60-100%
(1% incre.)
100-1200%
(1% incre.)
100-1200%
(1% incre.)
0-60 sec.
(1
sec. incre.)
0-240 sec.
(1
sec. incre.)
0-90%
(1
% incre.) 0-90%
(1
% incre.)
0-100 sec.
(1
sec. incre.)
0-10 sec.
(1
sec. incre.)
10-50%
0-240 sec.
(1
sec. incre.)
Toggles between
2
1
T TRIP and
2 SEC displays
1-1
O starts/
time (incre. of
1)
Set Point
100
1200
6
1200
240
0
0
1
6
50
1
Effective
February
1999
TD
Courtesy of NationalSwitchgear.com
17297D
Page
69
Item
No. Values Disable Value
T/STX
34
Program Menu Display
TIME ALLOWED FOR STARTS COUNT
2
1
,
IN
Selected
Set Point Ranges Selection
0-240 minutes duration
(1
minute incre.)
Set Point
0
MINUTES
OP COUNT4
35
RSTOCNT4
Toggles between OP COUNT OP COUNT
and
RSTOCNT
RESET FOR OPERATIONS COUNTER
36
RUN RST RT
TIME
4
4
Toggles between
and RST
RT
RUN
TIME
displays
RUN
TIME
RESET FOR RUN TIME
37
TRNCXXX
50-150%
150
MOTOR START TRANSITION CURRENT (1% incre.)
38
LEVEL
TRNTXXX
MOTOR START TRANSITION TIME
IN
% FLA
IN
0-240 sec.
(1
sec. incre.)
0
SECONDS
39 TRN TOUT4
TRP
TOUT4
TRANSITION OR TRIP ON TIME OUT
40
INSQXX
INCOMPLETE SEQUENCE REPORT BACK
TIME
IN
41
ABKS XXX
ANTI-BACKSPIN DELAY TIME
42
FLAXXXX
FULL-LOAD AMPS
43 FREQ 50
FREQ 60
4 4
50 OR 60 HERTZ LINE FREQUENCY
44
MODE 1MODE 2
4 4
TRIP MODE 1 -TRIP RELAY ENERGIZES ON TRIP CONDITIONTRIP MODE
SECONDS
2-TRIP
IN
SECONDS
4
RELAY ENERGIZES
Toggles between TRN TOUT
TRN TOUT and TRP
TOUT displays
1-60 sec.
(1
sec. incre.)
0-600 sec.
10-3000 amps
(1
amp incre.)
Toggles between
FREQ 50 and FREQ
60 displays
Toggles between
MODE 1 and MODE 2
0
ON POWER UP AND DE-ENERGIZES ON TRIP CONDITION
45 NON REV
4
REV
REVERSING OR NONREVERSING
4
4
Toggles between
REV and NONREV
displays
STARTER
Effective
February
1999
Page
Courtesy of NationalSwitchgear.com
70
TD
17297D
Item
No. Values
46
REM RSTREM TRIPDIF TRIPMTR STOP
RST DBL
Program Menu Display,,
4
4
4
4
4
2
Selected
Set Point Ranges Selection
Toggles between
REM
TRIP,
REM
RST,
DIF
TRIP,
MTR STOP
Set Point
Disable Value
REMOTE INPUT -RST FOR REMOTE RESET -TRIP FOR REMOTE TRIP -DIF
TRIP FOR DIFFERENTIAL TRIP -MTR STOP
FOR MOTOR STOP DETECTION -RST DBL FOR RESET DISABLE
47 MAX XXX
4
Toggles between
4-20 MA MAX OUTPUT -100 FOR 100 MAX100, MAX125,
PERCENT FLA -125 FOR 125 PERCENT FLA-
%12T FOR PERCENT 12T TRIP -displays
48
WRTD FOR MAXIMUM WINDING
AUXXXXX
TRIP
STATE
FOR AUX TRIP RELAY IOC, 12T,
RTD
TEMP
49 TRIP XXX Toggles between TRIP TRIP CNT
RESET FOR NUMBER OF TRIPS CNT and TRIP RST displays
50
MAXXXX
RESET FOR MAXIMUM VALUES MX R-EBL, MX RESET
51
XXX PGM Toggles between
MAX%12T and MAXWRTD
Toggles between ALL,
GFLT,
LBT,
JAM, UL,
WT,
and REV displays
MBT,
Toggles between
and MX R-DBL displays
RUN
RGM
4
4
MX R-DBL
4
ENABLE UNIT TO BE PROGRAMMED and STOP PGM
52
WHILE MOTOR
X/5
xxxx
CT RATIO -X TURNS
IS
RUNNING
Available CT
TO
5 turns:5 ratios are: 10, 20, 25,
40,50,
75,100,125,150,200,
250,300,400,500,600,800,
1000, 1200, 1500,2000,2500,
3000,4000
NOTES:
1.
The letters X used here represent the setpoint variables.
2.
Press the Help pushbutton to initiate the help display of the complete message shown here. The display scrolls right to left.
3.
The software version number
dence with Cutler-Hammer should refer to the specific software version number installed
4.
One of these choices must be selected.
5.
IOC trip setting should be lower than your Fuse Interrupting Rating or your Contactor Withstand Rating.
6.
Set start and run delays to maximum values to disable trip/alarm functions.
is
used by Cutler-Hammer. There
is
no selection associated with it. All correspon-
in
the 10-1000
Effective
II.
February
1999
TD
Courtesy of NationalSwitchgear.com
17297D
Page
71
The range of available setpoint values is:
Run delay: 0-240 seconds
(in 1 second increments)
8.11
UNDERLOAD FUNCTIONS
underload functions initiate an alarm or a trip condition if the motor's driven load drops a selected time. (More information about underload is given
in
Paragraph 7.1.3.4.)
There are four distinct setpoints associated with the underload function. These are:
• Alarm level (in % FLA)
• Trip level (in % FLA)
• Start delay (in seconds)
• Run delay (in seconds)
8.
11. 1 Setpoint Item 26, Underload Alarm Level -
The underload alarm level function specifies the current level at which the IQ-1000 because of a reduced current.
The underload alarm level setpoint function is displayed in
the program menu as:
11
ULA
-The
IQ-1000 ll's
below a selected value for
alarm contacts change state
xx
The underload trip level setpoint function the program menu as:
ULT xx
Here the letters xx represent the trip level full-load amperes. This menu item is numbered 27
Table 8.8. The range of available setpoint values is:
Trip:
** Disable value for ULT -0% of full-load
8.
11.3 Setpoint Item 28, Underload Start Delay -
The IQ-1000
be started while unloaded and to reach full speed before
the load is applied. The application of a start delay is
described The underload start delay function is displayed
gram menu as:
Here the letters xxx represent the user-selected delay, at which time the trip occurs. This menu item is numbered 28
in
Table 8.8.
0-90% of full-load amperes (in 1 % increments)
11
provides a start delay to allow a motor to
in
Paragraph 8.1.1.
ULSD
XXX
is
displayed
in
percent of
amps**
in
in
in
the pro-
Here the letters xx represent the alarm level full-load amperes. This menu item is numbered 26 Table 8.8.
The range of available setpoint values is:
Alarm: 0-90% of full-load amperes
(in 1 % increments)
** Disable value for ULA -0% of full-load amps **
If the underload alarm level is not disabled, it should be set at a value above the underload trip level (setpoint item 27).
For example, if the underload trip level is set at 80% of full load amperes, the underload alarm level should be set to some value between 81% to 90% of full load amperes. This ensures that present before a trip condition is reached.
underload trip level function specifies the current level at which the IQ-1000 trips the motor off line.
II
assumes the motor lost its load and
The range of available setpoint values is:
Delay: 0-100 seconds
(in 1 second increments)
8.
11.4 Setpoint Item 29, Underload
The IQ-1000 such as a power factor corrected motor which is run at very light loads intermittently. The application of a run delay is discussed
The underload run delay function is displayed gram menu as:
Here the letters xx represent the underload run delay. This menu item is numbered 29
The range of available setpoint values is:
Run delay: 1-10 seconds
11
provides a run delay for varying loads
in
Paragraph 8.1.2.
ULRD xx
(in 1 second increments)
in
Table 8.8.
Run
Delay -
in
the pro-
Effective
February
1999
lr.:t[•N
Page
Courtesy of NationalSwitchgear.com
72
TD
17297D
8.12 PHASE UNBALANCE FUNCTIONS -The IQ-
1000 ll's phase unbalance functions monitor the
for a possible phase unbalance condition of the actual
motor currents.
There are two distinct setpoints associated with this func-tion. These are:
• Alarm level
• Run delay (in seconds) Exceeding these two setpoints, however, does not cause
a trip condition. {The functions described
8.13 control the phase unbalance trip condition.) in
(Keep incorporated into the calculated negative sequence current become too high due to a combination of excessively high current levels and/or a phase unbalance condition, the IQ-1000 trip as a locked-rotor trip.)
mind that unbalance-detection factors are also
(in%
unbalance)
in
2
1
T protection algorithm. Should the
AC
line
Paragraph
II
will
8.12.1 Setpoint Item 30, Phase Unbalance Alarm
Level -
point where an out-of-balance phase condition initiates an ance, calculated by comparing the ratio of the negative sequence current to the positive sequence current (see Paragraph 3.2.2 for more details). If the negative . sequence is 10% of the positive sequence, there
10% unbalance between 1
The phase unbalance alarm setpoint function is dis-played
Here the letters xx represent the phase unbalance alarm
level above which an alarm condition exists. This menu item is numbered 30
The range of available setpoint values
(Same level as a phase loss trip; see Paragraph 8.13.)
The phase unbalance alarm level specifies the
alarm condition. The alarm level is
A•
1
8
in
the program menu as:
PU
Axx
in
Table 8.B.
Alarm:
**
Disable setting for
10%-50% of unbalance (in 1 % increments)
PU
A -50% unbalance
and 1
,
in
percent of unbal-
c·
is:
1s
a
**
8.12.2 Setpoint Item 31, Phase Unbalance Alarm Run
Delay-The
allow for power system voltage variations which cause short term unbalance conditions. The application of a run delay is described
The phase unbalance alarm run delay function played
Here the letters xxx represent the user-selected delay, at which time the alarm is initiated. This menu item is num-bered
The range of available setpoint values is:
in
the program menu as:
31
in
Table 8.B.
Delay:
IQ-1000
0-240 seconds (in
1 second increments)
II
provides a run delay to
in
Paragraph 8.1.2.
PURD
XXX
c_oul?
is
dis-
8.13 SETPOINT ITEM 32, TRIP/DELAY PHASE UNBALANCE FUNCTION -
condition is defined as the negative sequence being equal to half of the positive sequence or a 50% phase unbalance (see Section 3 for more details).
The phase unbalance protection function provides a choice between (1) initiating a trip 2 seconds after the phase unbalance level is reached and (2) disabling this function to wait on an 12T trip. The set 2-second delay phase unbalance is necessary to prevent nuisance trip-ping associated with momentary disturbances tem.
Waiting possible minute before tripping for critical applications where the motor must keep running as long as possible. One such application would which, if stopped, would ruin the material
With this function, one of these two choices selected for every application. Pressing either the Raise or Lower pushbutton causes the display to toggle between the two following messages:
This menu item is numbered 32
on
the 12T trip allows the motor to
A phase unbalance trip
in
run
until the last
be
a chemical process
in
the process.
must be
2 SEC
in
Table 8.B.
on
the sys-
NOTE: If a phase unbalance alarm
unbalance condition is removed, the alarm
automatically.
IF
!'r•N
is
active and the
is
reset
8.14 STARTS, TIME
setpoint functions control the number of motor starts allowed within a given period of time. These are:
• Starts (number of starts per time period allowed)
• Time period allowed (for those starts)
FUNCTIONS-Two
Effective
separate
February
1999
TD
Courtesy of NationalSwitchgear.com
17297D
Page
73
Should the user-specified number of motor starts exceed the set point within the specified time period, any further start cycles are prevented until the oldest start is returned.
These functions must be "used"
user must always make a set point entry for both. How-ever,
by following the procedures described below, they
can,
in
effect, be disabled.
in
the sense that the
NOTE: The number of starts is cleared every time the IQ-1000
II
is placed
in
the Program mode. This can be
used to clear a starts/exceeded trip.
8.14.1 Setpoint Item 33, Starts Allowed -
(per time) allowed setpoint function specifies the maxi-mum number of motor starts permitted (within a given period). If this set point is reached, appear with the message "STEX STEX stands for "starts exceeded" and the XXX is the number of minutes the user must wait before the oldest start is restored. If the motor is stopped while this mes-sage is the motor cannot be started until the oldest start is
returned.
All starts, including aborted starts, are counted by this function.
on
the screen, the alarm will become a trip and
an
alarm condition will
XXX"
on the display.
The starts
The setpoint is programmed mode. minutes remaining
The time allowed setpoint function is displayed
gram menu as:
In
the Protection mode, the display indicates the
in
the time period.
in
minutes
in
the Program
in
the pro-
T/STx
Here the letter x represents the user-selected time period in
which the maximum number of starts is allowed. This
menu item is numbered 34 The range of available setpoint values is:
Time: 0-240 minutes
(in 1 minute increments)
** Disable setting for T/ST -0 minutes **
By entering O minutes, the time allowed function effect, disabled. Additionally, this entry disables the starts allowed function (item 33), thereby permitting ited number of starts over any time period.
NOTE: When the time per allowed starts items
21
and 22
in
Table 4.A will be displayed as
in
Table 8.B.
is
is,
an
unlim-
set to
in
0,
"-"
to denote this function is disabled.
The starts allowed setpoint function is displayed program menu as:
ST!T
xx
Here the letters xx represent the user-selected maximum number of allowed starts. This menu item
in
Table 8.B.
The range of available setpoint values is:
Starts:
This function can be indirectly disabled, thereby permit-
an
ting
for details). If this function is indirectly disabled, any entry (1
unlimited number of starts (see Paragraph 8.14.2
thru 10) would be acceptable.
1-10 starts (within the time period)
is
in
the
numbered 33
8.14.2 Setpoint Item 34, Time Allowed -The time
allowed (for starts) setpoint function specifies the dura-
tion
in
which the maximum number of starts may occur. Each start has a "life span" equal to the time allowed set-point. This means every start that is used will not be returned until it has been logged for the duration of this setpoint. This function works like a sliding window and will return starts
The operations counter can be reset to zero while the IQ-1000
II
is
in
the Program mode. If RST OCNT is the last message displayed while tions counter will be set to zero when the keyswitch is placed
The display will toggle between the following two mes-sages:
As operations count after preventive maintenance has been
performed
This menu item is numbered 35
in
the Protection mode.
OP COUNT
an
example, this feature is useful for resetting the
on
the motor.
8.14.4 Setpoint Item 36, Run Time
time can be reset to zero while the IQ-1000
Program mode. If RST RT is the last message displayed
while
in
the Program mode, the run time will be set to
zero when the key-switch is placed
mode.
The display will toggle between the following two mes-
sages:
in
Program mode, the opera-
RSTOCNT
in
Table 8.B.
Reset-The
II
is
in
the Protection
in
run
the
Effective
February
1999
Page
Courtesy of NationalSwitchgear.com
74
TD
172970
TRANSITION TRANSITION
l_CURRENT
LEVEL _
MOTOR --
CURRENT
__
START
I
ACTIV
E
TRANSITION TRANSITION TIMER
F
OF OF
I
ACTIV E
TRANSITION RELAY RELAY
OF
F OF
TRIP
TRIP TRIP RELAY
RUN
FULL
VOLTAGE
TRANSITION CURRENT (ITEM 37) = N/A TRANSITION TIME (ITEM 38) = 0 SEC TRIPffRANSITION (ITEM 39)
MOTOR --CURRENT
~
START
_IRANSITl0t:!_9URRENT
START
(ACROSS-THE-LINE) LOW-HIGH
I
ACTIVE
TRANSITION TIMER
OFF
ACTIVE
TRANSITION RELAY
OFF
= TRANS
LEV~
I
~
CURRENT LEVE':_
I I
I
I
I
ACTIVE
MOTOR --
CURRENT
-
TIMER
-
_ _
START
I
I
ACTIVE
TRANSITION
F
TRIP
RELAY
RUN
VOLTAGE
TRANSITION CURRENT (ITEM 37)
TRANSITION TIME (ITEM 38) TRIPffRANSITION (ITEM 39)
MOTOR CURRENT
--
---
START
TRANSITION
;;::
NORMAL LOAD
;;::
ST ART TIME
= USER'S CHOICE
I
-1,-
1
ACTIVE
OFF
TRANSITION TIMER
I
I
I
ACTIVE I
TRANSITION RELAY
OFFi---~~~~~~~~~+1~~~-
TRANSITION
CURRENT
LEVEL
---
1
TRIP
TRIP
RELAY
RUN
FORCED TRANSITION ON TIME
TRANSITION CURRENT (ITEM 37) TRANSITION TIME (ITEM TRIPffRANSITION (ITEM 39)
Fig. 8.1
Transition/Trip on Time
38);;::
= TRANS
Out
;;::
NORMAL LOAD
START TIME
Timing
TRIP
TRIP RELAY
FORCED SHUTDOWN ON TIME
TRANSITION CURRENT (ITEM 37) TRANSITION TIME (ITEM TRIPffRANSITION (ITEM 39)
38);;::
;;::
NORMAL LOAD
START TIME
= TRIP
Effective
February
1999
TD
Courtesy of NationalSwitchgear.com
17297D
Page
75
RUNTIME
RSTRT
This feature is useful for resetting the run time after, for
example, preventive maintenance has been performed on
the motor.
This menu item is numbered 36
8.15 MOTOR START
TRANSITION-The
in
Table 8.B.
IQ-1000
II provides a relay which can be set to energize on certain current levels
or
timing delays. User-programmmed set-
points are required for the transition current level (item
37), the transition time (item 38), and action to take on transition time out (item 39). This transition relay can be used to control:
• Soft-start type motor starts
• Low-and high-voltage reduced voltage motor
starters
• Any type of clutch between the motor and the driven
load. (The clutch will be engaged after the motor attains the desired speed.)
8.15.1 Setpoint Item 37, Motor Start Transition (Current
Level)-
The motor start transition (current level) function specifies the current level below which the IQ-1000 ll's transition relay will be energized. The current level is measured as a percent of full-load amperes.
The primary transition function is based on current. The transition time (item 38) is used as a backup
in
case the
motor stalls during starting. When 30% of full load is
detected
in
any phase by the IQ-1000
II,
a start
is declared. The normal inrush currents of a motor (even a solid-state starter with the voltage phased back) will exceed any of the allowable transition current levels
in
immediately. If the current
any phase falls below the transition level within the transition time, the transition relay is energized and will remain so until a stop or trip condition occurs (see Figure
8.1
).
Once a start has occurred, the current must go above the transition level within 8 line cycles or an immediate transition may be ini-tiated.
The motor start transition setpoint function
is
displayed
in
the program menu as:
TRNC
XXX
Here the letters xxx represent the user-selected current
level below which point the transition relay will be ener-
in
gized. This menu item is numbered 37
Table 8.B.
The range of available setpoint values is:
Current: 50-150% of the full-load amperes rating
(in 1 % increments)
If the transition relay is not used, the transition current
should be set to the maximum setting of 150%
8.15.2 Setpoint Item 38, Motor Start Transition (Time) -
maximum duration,
The motor start transition (time) specifies the
in
seconds, of the motor's start or transition cycle. The transition time is used as a backup timer only when the IQ-1000
II
has not transitioned
on
l'6-----
ACTIVE
0
OFF
i------'
ACTIVE
ACTIVE
OFF'--------------'
Fig.
8.2 Incomplete Sequence Timing
Effective
February
1999
MOTOR -
CURRENT
TRANSITION TIMER
INCOMPLETE SEQUENCE TIMER
TERMINALS
START
9-10
TRANSITION LEVEL
ON
IQ-1000 II
0-60 SEC
120 VAC REPORT BACK MUST OCCUR BEFORE INCOMPLETE SEQUENCE TIMER EXPIRES.
Page
Courtesy of NationalSwitchgear.com
76
TD
17297D
current. If this happens, the IQ-1000
tion or create a transition trip depending
II
will force a transi-
on
the trip/transi-
tion set point (item 39). (For more details
on
the motor's start and run cycles,
refer to Paragraph 7.2.)
The motor start transition (time) setpoint function is dis-
in
played
the program menu as:
TRNT
XXX
Here the letters xxx represent the user-selected duration of the start or "transition" cycle. This menu item is num-bered 38
in
Table 8.B.
The range of available setpoint values is:
Time: 0-240 seconds
(in 1 second increments)
** Disable setting for TRNT -0 seconds **
If
the transition relay is not used (as
in
across the line starts), the transition current (item 37) should be set to a maximum (150%) and the transition time to O seconds to
force
an
immediate transition (see Figure
8.1
).
However,
if the transition current setpoint is set to a minimum to
II
force the IQ-1000
to transition on time, the transition
relay can be used as a generic timer controlled by the
transition time. Care must be taken to insure the current will never fall below 50% (minimum transition current
level setpoint) before the transition time elapses.
8.15.3 Setpoint Item 39, Trip/Transition on Time Out Function
-The
IQ-1000
II
allows the user two alterna-
tives when the transition time (item 38) expires before a
transition
on
current is made. One alternative is to force the transition and energize the transition relay as shown in
Figure 8.1. The other
shut down the motor as
is
to create a transition trip to
in
Figure 8.1. A transition trip will
generate a message of "TRANS" on the display. With this function, pressing either the Raise or Lower
pushbutton causes the display to toggle between the messages:
TRN TOUT TRP TOUT
This menu item is numbered 39
8.16 SETPOINT ITEM 40, INCOMPLETE SEQUENCE TIME -
operates
The incomplete sequence time (in seconds)
in
conjunction with the incomplete sequence
terminals on the rear of the IQ-1000
in
Table 8.B.
11
(terminals 9 and
10, see Figure 8.3). As the IQ-1000
11
enters the
RUN mode, the incomplete sequence timer starts its count. If the timer runs out (i.e., the time programmed at menu item 40 expires) before 120 across terminals 9 and 10, then the IQ-1000
VAC
has been received
11
will gener-ate a trip condition and will display the message "INC SEQ."
If
120
VAC
is received at terminals 9 and 10 before
the timer runs out, the IQ-1000
VAC
signal, and the 120
is no longer monitored. The tim-
ing cycle of events is shown
II
will acknowledge the
in
Figure 8.2.
One common use of this report back is with auxiliary con-tacts
on
a contactor to make sure that it closed. For
example, it could be used
two motors are controlling segments
an
If using
IQ-1000 input into the IQ-1000 on
the conveyer line has started (i.e., the contactor has
in
a conveyer belt line, where
in
the conveyer line.
II
on the first motor, a signal could be
II
to ensure that the second motor
closed).
In
another example, the report-back timer could be used
in
an
application having
an
oil pump and a compressor. By wiring the oil pump control circuit into the incomplete sequence contacts, the IQ-1000
11
can verify that the pump is running When the compressor is running. If the report-back contacts do not see 120
VAC
from the pump
before the timer runs out, the compressor will be shut off. The incomplete sequence report-back function is dis-
played
in
the program menu as:
INSQ
xx
Here the letters xx represent the incomplete sequence timer duration. This menu item is numbered 40
in
Table
8.B. The range of available setpoint values is:
Time: 1-60 seconds
(in 1 second increments)
NOTE: This function is disabled from the factory with jumpers from terminals 4 to 1 O and 6 to 9. If using this function, remove the two jumpers.
8.17 SETPOINT ITEM 41, ANTI-BACKSPIN
DELAY-
The anti-backspin delay function prevents a motor restart for the duration of the user-specified time.Timing begins concurrently with a trip or stop condition. This function guards against any attempt to start the motor while it is
rotating
in
a reverse direction, as may be caused with certain types of loads. A typical example is the backspin of a pump and motor caused by the descent of a column
of water after pumping is terminated.
Effective
February
1999
TD
Courtesy of NationalSwitchgear.com
172970
CT
Connections
Page
77
4-20
120V
/240V
EARTH GROUND.5
REMOTE
REMOTE
REMOTE
INC
Fig.
8.3 IQ-1000 II Terminals
l"tA
OUTPUT
TRANSITION 2
AUTO
SEL 4
COMMON
NEUTRAL 7
INPUT B
COMMON
SEQUENCE
25
24
1
3
6
9 10
00
0~®~0~0
1r!\\!r(l\\!r(l\\t11:\\~1
lfflU:.~.
0
=
'j
.;:I = =
=
J
~DDDDDDD
l
=
DDDDDDD
=
~
=
DDDDDDD
==
=
DDDDDDD
p
DDDDDDD"
==
DDDDDDD
p
I
00
.,
0 0
0
':'-
•'
,•
..
..
-'-"
1
1
0
.Q.
11P"
_..;;.,,
TE
~
'
~
p
~
• =
'
,
• =
~
= =
-
f
l:I
,::
L
r
I.
0
Col"tl'l\..mlco. Port
F"lber-Optlc Connector
23 22
'w'lrlng
21
RTD
ALARM
AUX
Option
TRIP
20
19
18
17 16
15
14
13
12 TRIP 11
tlons
to
00
The anti-backspin delay feature can also be used for spe-cial motors that must sit idle for a time before being
restarted. For example, many air-conditioning motor manufacturers recommend that their motors not be
restarted for one minute after they have been turned off, to ensure that the motor has stopped. the IQ-1000
prevent the motor from being restarted until the timer
runs out. The anti-backspin delay function is displayed
gram menu as:
Here the letters xxx represent the user-specified dura-tion. This menu item is numbered
The range of available setpoint values is:
Time: 0-600 seconds
II
could be programmed for 60 seconds to
ASKS
(in 1 second increments)
** Disable setting for ASKS -O seconds **
XXX
In
a case like this,
41
in
Table 8.8.
in
the pro-
8.18 SETPOINT ITEM 42, FULL-LOAD
The full-load amperes function specifies the maximum continuous RMS current that can be permitted stator.This value is determined by the motor manufac-turer's full-load ampere rating at unity service factor.
Proper performance of the IQ-1000 dependent upon this user-entered variable.
load ampere function rent transformer ratio (item 39) to scale the incoming cur-rents into a per unit basis for calculation and then again
to display metered values of current.
MANY OF THE IQ-1000 ll'S PROTECTION FUNC-
TIONS, INCLUDING THE MOTOR TEMPERATURE
PROTECTION ALGORITHM, USE THE FULL-LOAD AMPERE SETPOINT VALUE TO CALCULATE TRIP
POINTS. IF THE USER ENTERS DETERMINED SETPOINT, MOTOR DAMAGE CAN RESULT.
is
A
used
in
conjunction with the cur-
CAUTION
AN
AMPERES-
in
a motor
II
is directly
The full
INCORRECTLY
Effective
February
1999
Page
Courtesy of NationalSwitchgear.com
78
TD
172970
NOTE: When in the run mode, the run-monitor percent of full-load current (monitor menu
,
% 1
%
le)
6
setpoint function.
The full-load amperes function is displayed
gram menu as:
Here the letters ommended full-load amperes specification for the motor. This menu item is numbered 42
The range of available setpoint values is:
Current: 10-3000 amperes
This function
8. 19 SETPOINT ITEM 43, FREQUENCY -The IQ-
1000 A selection must be made by means of the 50/60 Hz line frequency function. There are no hardware settings nec-
essary.
The 50/60 Hz line frequency function is displayed
program menu as:
is established by the full-load amperes
FLA
xxxx
xxxx
represent the manufacturer's rec-
in
Table 8.B.
(in 1 ampere increments)
must
be
programmed into the IQ-1000
II
may operate from either a 60 Hz or 50 Hz
FREQ 50
FREQ 60
items%
in
the pro-
AC
in
IM
II.
line.
the
One of these two selections must be made for each appli-cation. The selection depends AC
power loss
graphs 8.20.1 and 8.20.2.
8.20.1 Mode 1 -When Trip Mode 1 function is
selected, the Trip and Auxiliary Trip Relays will energize
on
only The Trip/Auxiliary Trip Relays are state when any of the following conditions occur:
• When
• When certain IQ-1000
• During normal motor run operations
• During the normal The Trip/Auxiliary Trip Relays are only energized when a
trip/auxiliary trip condition(s) is/are detected. The user should tie to the normally-closed contacts for normal
operation.
The advantage of this setting is that the application's
motor can continue to operate even though the IQ-1000 has shut down.This situation could occur where the continuation of the process or running of the machine is more important than the immediate protection of the motor.
a trip and auxiliary trip condition, respectively.
rupted
blown fuse or failed power supply -experiences an internal failure
on
an
application, as described
AC
line power to the IQ-1000
AC
on
the desired effect of
in
the de-energized
11
is lost or inter-
II
hardware -such as a
power-up sequence
in
those cases
in
an
Para-
11
With either of these two displays showing, pressing either
the Raise or Lower pushbutton causes the other to
appear.
This menu item is numbered 43
NOTE: Selecting the wrong frequency can create an
opto error trip if voltage is applied to the Remote
Input terminal (8) or the Incomplete Sequence
terminal (10).
8.20 SETPOINT ITEM 44, TRIP RELAY MODES -
One of two different Trip Relay reaction modes may be
selected by the user ing conditions. These are:
Mode
Mode 2:
Trip Relay is de-energized normally and
1:
energizes during a trip condition
Trip Relay is energized normally and de-
energizes during a trip condition or loss of AC control power
in
response to a number of operat-
in
Table 8.B.
NOTE: It is the application engineer's responsibility to choose the NO/NC pair of Trip Relay and Auxiliary Trip Relay contacts to properly enable the motor contactor.
The
Trip
Mode 1 function is displayed
menu as:
MODE1
In
this case, pressing either the Raise or Lower pushbut-
ton causes the MODE 2 display to appear.
This menu item is numbered 44
8.20.2 Mode 2 -When Trip Mode 2 function is
selected, the Trip and Auxiliary Trip Relays energize after power up initialization (approximately 6 seconds) and de-energize iary Trip Relays are the following conditions occur:
• After the normal
on
a trip/ auxiliary trip condition. The Trip/Auxil-
in
the energized state when any of
AC
power-up sequence
in
in
Table 8.B.
the program
I'
!'f•N
Effective
February
1999
TD
Courtesy of NationalSwitchgear.com
17297D
• During normal motor run operations The Trip/Auxiliary Trip Relay(s) is/are de-energized when
a trip/auxiliary trip condition is/are detected. The user should tie to the normally-open contacts for normal oper-ation.
The advantage of this setting is that the application's
II
motor is turned off when the IQ-1000 Here the continuation of the process or running of the machine is seen to be less valuable than the protection of the motor.
stops operating.
NOTE: It is the application engineer's responsibility to choose the NO/NC pair of Trip Relay and Auxiliary Trip Relay contacts to properly enable the motor contactor.
The Trip Mode 2 function is displayed in the program
menu as:
MODE2
In
this case, pressing either the Raise or Lower pushbut-
ton causes the MODE 1 display to appear.
in
This menu item is numbered 44
Table 8.B.
Page
79
In
the trip (REM TRIP) mode, the IQ-1000 a trip and display the message "REMOTE" on the display. If the Reset button is pushed or a reset command sent over INCOM, the trip will reset only if voltage has been removed from terminal
When this function is placed mode, the IQ-1000 present mode of the unit. For example, if the unit is Program mode, it will return to the top of the program list.
in
If the unit is tus of the motor. This reset function will react manner as pushing the Reset pushbutton.
In
the differential trip (DIF TRIP} mode, the IQ-1000 will generate a trip and display the message "DIF TRIP" on the display. If the Reset button is pushed or a reset command sent over age has been removed from terminal
In
this case, the normally open relay of a separate, exter-nal differential relay should be wired to the REMOTE INPUT (terminal 8) on the rear of the IQ-1000 II. When
the external relay detects a trip, the normally open relay
will close, applying 120
the back of the IQ-1000 II. At this time, the IQ-1000 ll's trip relay will activate and the message "DIF TRIP" will be
starter function specifies the type of starter actually used in the application.
The reversing/non-reversing starter is displayed as one of the following in the program menu:
REV
With either of these two displays showing, pressing either the Raise or Lower pushbutton causes the other to
appear. This menu item is numbered 45
This function
according to application requirements. If non-reversing is selected and the motor is reversed, a phase reversal trip will occur and the message "PH REVRS" will be dis-played.
function specifies which one of three available ways the
REMOTE INPUT (terminal 8 on the back of the IQ-1000
II}
will function. The remote input must be a 120
nal.
The trip/reset/differential trip on remote input
VAC
sig-
When the the IQ-1000 VAC primarily designed for applications using synchronous motors, when the motor is used for power factor correc-tion. zero, causing the IQ-1000 mode. When the IQ-1000
mode, the anti-backspin timer is initiated and all protec-
tion features (except for RTD temperature protection) are
disabled. In
order to operate in applications similar to the one described above, a normally open auxiliary contact on the motor starter or contactor should be connected minals 8 and 9 on the IQ-1000 II. When the contactor opens, 120 VAC will be removed from these terminals. The IQ-1000 received a signal from the Remote Input terminal.
In
the reset disable (RESET DBL) mode, the Reset
pushbutton on the faceplate of the IQ-1000
following a trip condition. When this mode is selected, the
only way to reset the unit following a trip is 120 VAC to terminal 8 of the IQ-1000 II. This feature can be used to prevent unauthorized personnel from resetting
the unit and restarting the motor after a trip. This could be
motor stop (MTR STOP) function is selected,
II
will exit the "RUN" mode only when 120
has been removed from terminal
In
these applications, motor current can drop to
11
to enter the "READY
II
enters the "READY --3"
II
will only exit the "RUN" mode after it has
8.
This feature is
11
is disabled
by
--
3"
toter-
applying
Effective
February
1999
Page
Courtesy of NationalSwitchgear.com
80
TD
17297D
accomplished, for example, by connecting a pushbutton
9.
with padlock attachment between terminals 8 and
Only personnel with a key to the padlock would be able to reset the unit. The faceplate reset will operate as long as
a trip or alarm is not present -as soon as trip or alarm
is
present faceplate reset will be disabled.
When this function is displayed, it will toggle between the following five messages:
RST DBL REM TRIP REM RST DIF TRIP MTR STOP
This menu item is numbered 46
in
Table 8.B.
8.23 SETPOINT ITEM 47, 4-20 MA OUTPUT
II
SIGNAL -The IQ-1000 output signal at terminals 23 and 24
1000
II
(see Figure 8.3). This signal can be input into
provides a 4-20 mA analog
on
the rear of the IQ-
an
ammeter or programmable controller for external manipu-
lation of parameters monitored by the IQ-1000
II.
If an input device to receive the analog signal is not present, there is no need to enter these values.
The 4-20 mA analog output is proportional to a user-selected parameter that is measured by the IQ-1000
II.
The following parameters can be selected:
(1) 100% of Full Load Amps -the 4-20 mA signal is
proportional to the average of the three-phase cur-
rent values, with 100% of FLA equal to 20 mA. The 100% FLA analog output function is displayed
in
the
program menu as:
MAX 100
(2) 125% of Full Load Amps -the 4-20 mA signal is
proportional to the average of the three-phase cur-
rent values, with 125% of FLA equal to 20 mA. The 125% FLA analog output function is displayed
in
the
program menu as:
MAX 125
(3) Percent 12T Trip Level -the 4-20 mA signal is pro-
portional to the percent
2
1
T trip level equal to 20 mA. The percent 12T trip ana-
log output function is displayed
2
1
T trip level, with 100% of the
in
the program menu
as:
point item ature analog output function is displayed
3)
is equal to 20 mA. The winding temper-
in
the
program menu as:
MAXWRTD
When this function is used, it will toggle between the fol-
lowing four messages:
MAX 100 MAX 125
MAXWRTD
In
the Program mode, pressing either the Raise or Lower pushbutton causes the display to step through the items displayed above.
This menu item is numbered 47
in
Table 8.B.
8.24 SETPOINT ITEM 48, TRIP STATE FOR AUXILIARY TRIP RELAY
programmable form-C
-The
relay,
relay can be programmed to activate only
IQ-1000
II
the Auxiliary Trip
on
has one
relay.
This
certain trip conditions. This relay is labeled as terminals 14, 15 and 16
on
the rear of the IQ-1000
II
(see Figure 8.3). The fol-
lowing trip states can be programmed for the Auxiliary
Trip relay:
AUX ALL -Auxiliary trip relay will change state for any
trip condition detected by the IQ-1000
II.
AUX IOC -Auxiliary trip relay will change state only when the IQ-1000
II
detects an Instantaneous Overcur-
rent trip condition (see Paragraph 8.2).
2
AUX
1
T -Auxiliary trip relay will change state only when
II
the IQ-1000
detects
2
an
1
T trip condition (see Para-
graph 8.8). AUX GFLT -Auxiliary trip relay will change state only
when the IQ-1000
II
detects a Ground Fault trip condition
(see Paragraph 8.4). AUX JAM -Auxiliary trip relay will change state only
when the IQ-1000 Paragraph
8.1
II
detects a Jam trip condition (see
O).
(4) Winding Temperature -the 4-20 mA signal is pro-
portional to the maximum winding if RTDs are used. The winding RTD trip level (set-
RTD
temperature
AUX UL
-Auxiliary the IQ-1000 Paragraph
II
8.11
trip relay will change state only when
detects
an
Underload trip condition (see
).
Effective
February
1999
TD
Courtesy of NationalSwitchgear.com
17297D
Page
81
AUX MBT -Auxiliary trip relay will change state only when the IQ-1000 tion (see Paragraph 8.3.2).
AUX LBT -Auxiliary trip relay will change state only
when the IQ-1000
(see Paragraph 8.3.3).
AUX WT -Auxiliary trip relay will change state only
when the IQ-1000
Paragraph 8.3.1).
AUX REV -Auxiliary trip relay will change state only
when the IQ-1000
tion (see Paragraph
When this function is displayed
following messages can be scrolled through using the
Raise and Lower step buttons:
AUX ALL AUX IOC
AUX 12T AUX GFLT
AUX JAM
This menu item is numbered 48
II
detects a Motor Bearing trip condi-
II
detects a Load Bearing trip condition
II
detects a Winding trip condition (see
II
detects a Motor Reversal trip condi-
8.21
).
in
the Program mode, the
AUX UL
AUX MBT
AUX LBT AUX
WT
AUX REV
in
Table 8.B.
Each of these items can be reset to zero while the IQ-1000
II
is
in
the Program mode. If the RST TRIP mes-
in
sage is displayed last while counter values will be reset to zero when the keyswitch is placed
The display will toggle between the following two mes-sages:
This menu item is numbered 49
in
the Protection mode.
TRIP CNT TRIP RST
the Program mode, all trip
in
Table 8.B.
8.26 SETPOINT ITEM 50, RESET MAXIMUM VALUES -
lowing maximum values:
• Maximum phase current (in "RUN" cycle)
• Maximum winding RTD temperature Both of these items can be reset to zero while the IQ-
1000 maximum value reset feature is displayed as one of the following
MX R-DBL MX RESET MX R-EBL
The IQ-1000
II
is
in
either the Protection or Program mode. The
in
the program menu:
II
is capable of storing the fol-
NOTE: The Alarm relay will change state when any
alarm condition is detected by the IQ-1000 II.
The Trip relay will change state when any trip condition is
detected by the IQ-1000
The Auxiliary Trip relay will only change state when the
programmed trip state condition(s) has/have been
detected by the IQ-1000
The Trip relay on the IQ-1000
at the same time that the Auxiliary Trip relay changes
state.
11.
II.
II
will always change state
8.25 SETPOINT ITEM 49, RESET NUMBER OF
TRIPS -
of trips for most trip conditions. It will store the following:
• Number of Locked Rotor CurrenVPT trips
• Number of Instantaneous Overcurrent trips
• Number of Underload trips
• Number of Jam trips
• Number of Ground Fault trips
• Number of
The IQ-1000
RTD
trips
II
is capable of storing the number
These items can be displayed individually by pressing the Raise or Lower pushbutton.
If the max reset disable (MX R-DBL) setpoint is selected, the IQ-1000 mum values stored ory when the keyswitch is returned to the Protection mode.
max reset (MX RESET) setpoint is selected, the
If the
IQ-1000
when the keyswitch is returned to the Protection mode.
If
the max reset enable (MX selected, the IQ-1000 mum values stored ory when the keyswitch is returned to the Protection mode. However, each maximum value can zero individually while it is being displayed plate of the IQ-1000 to be reset while the motor is running.
The display will toggle between the following three mes-sages:
MX R-DBL MXRESET MXR-EBL This menu item is numbered 50
11
will reset all of the maximum values to zero
11
will not reset any of the maxi-
in
the IQ-1000 ll's non-volatile mem-
R-EBL)
II
will not reset any of the maxi-
in
the IQ-1000 ll's non-volatile mem-
II.
This menu selection allows values
setpoint
in
Table 8.B.
be
reset to
on
the face-
is
Effective
February
1999
Page
Courtesy of NationalSwitchgear.com
82
TD
17297D
8.27 SETPOINT ITEM 51, RUN PROGRAM/STOP
PROGRAM -
options when programming setpoints
This setpoint is displayed
Pressing the Raise or Lower pushbutton toggles the dis-play between these two options.
If
RUN
PGM is selected, the motor may be started and/or
run while programming the IQ-1000
IF SETPOINT MAY BE MING
THE
IN
THE
RUN PGM MODE, ALL IQ-1000 PROTECTION FEATURES MOTOR IS UNPROTECTED IS RETURNED TO
If
STOP PGM is selected, the motor must be stopped order to program setpoints into the IQ-1000 the keyswitch to the Program position will not initiate the Program mode if the motor is running.
This menu item is numbered
8.28 SETPOINT ITEM 52, RATIO -
the turns ratio of the application's current transformers.
BE
CAREFUL RATIO. AN IMPROPER 1000
II
TO
DATA.
MOTOR
This setpoint provides the user with two
in
the IQ-1000
in
the Program menu as:
RUN
PGM
STOP PGM
II.
A
51
IS SET
STARTED
IQ-1000 II.
The current transformer ratio function specifies
A
WHEN DETERMINING
RECEIVE
DAMAGE
CAUTION
TO
RUN PGM,
AND/OR RUN WHILE PROGRAM-
WHEN
THE
ENTERING SETPOINTS
ARE
DISABLED
UNTIL
PROTECTION POSITION.
51
in
CURRENT
THE
II
MOTOR
THE
KEYSWITCH
II.
Table 8.B.
TRANSFORMER
CAUTION
CT
TURNS
VALUE
INCORRECT
CAN CAUSE
COULD
MOTOR
RESULT.
CURRENT
II.
MOTOR
AND
THE
Placing
THE
IQ-
in
Only the first factor of the ratio is entered for this setpoint.
Thus, the entry of 250 represents 250:5. This value is
X/5
XXX
in
Table 8.B.
= 3.75
II.
400:5 500:5
600:5
800:5 1000:5 1200:5
amperes
1500:5 2000:5 2500:5 3000:5 4000:5
in
the program
used internally by the IQ-1000 Available CT turns ratio setpoint values are:
10:5 20:5 25:5 40:5 50:5 75:5
The CT turns ratio function is displayed menu as:
Here the letters xxx represent the digiVdigits that appear in
front of the ratio
This item is numbered 52
For setpoint entry purposes, refer to the application's wir-ing plan drawings for the correct CT ratio. Use the follow-ing criteria to select a current transformer:
• For optimum metering accuracy at low loads, select a unit which, at 100% full-load amperes, delivers from
3.5 to 4 amperes at the secondary. A CT which deliv-ers 2.5 to 4 secondary amperes at 100% FLA is also adequate for reliable motor protection.
• Select the CT which supplies as close to 3.75 amperes as possible at 100% full-load amperes.
For example, assuming an application where the motor starter delivers 300 full-load amperes, a 400:5 primary-
to-secondary ratio will deliver:
This is within the recommended range of 3.5 to 4.0 amperes. The CT ratio for this example would be 400:5.
100:5 125:5 150:5 200:5 250:5 300:5
in
the list above.
300
x
~
4
0
Effective
February
1999
TD
Courtesy of NationalSwitchgear.com
17297D
Page
83
SECTION 9
TROUBLESHOOTING
9.0 GENERAL -This section is designed to assist
maintenance personnel carry out troubleshooting proce-dures. It is divided into three general areas of informa-tion:
Operator Panel monitoring procedures (Par. 9.1)
•
Troubleshooting monitored equipment (Par. 9.2)
•
Troubleshooting the IQ-1000
•
A
ALL MAINTENANCE PROCEDURES MUST
FORMED ONLY BY QUALIFIED PERSONNEL WHO ARE FAMILIAR WITH THE IQ-1000 CIATED MOTOR AND MACHINES. FAILURE TO OBSERVE THIS WARNING CAN RESULT OUS OR FATAL PERSONAL INJURY AND/OR
EQUIPMENT DAMAGE.
All correspondence with Cutler-Hammer, whether verbal or written, should include the software version number which appears as the first display
9.1.3 Reviewing Setpoints -All 52 setpoints can be
reviewed while the IQ-1000 when the motor is actually running.
To
review setpoints Points pushbutton once to enable the Program menu. At this time the Step Up or Step Down pushbuttons can be
used to step through the Program menu
tion to the desired IQ-1000
menu is listed as Table 8.B)
9.1.4 Monitoring Characteristics -The run-monitor
menu allows maintenance personnel/operators to
observe selected operating parameters associated with the motor and motor starter. A listing and description of these electrical characteristics is contained
The metering functions are averaged over time to give
stability to the readings presented. As a result, the
retained metering function data may be data which
occurred up to one second before the trip occurred. This
is
in
contrast to the instantaneous response of certain trip
conditions such as:
• Instantaneous overcurrent
• Ground fault Because the instantaneous overcurrent function is actu-
ated within one line cycle of the trip condition occurring,
the frozen trip values for the phase currents will not
reflect the actual current value that caused the trip.
in
II
is
in
the Run mode -even
the Run mode, press the Set
in
either direc-
II
function. (The program
in
Table 9.8.
9.1.1
dow provides a reporting function during the normal operation of the IQ-1000
9.1.2 Programming Setpoints -The Operator Panel,
values. See Paragraph 4.3 for a detailed procedure to
System Status Messages -The Display Win-
referred to as the system status messages. Table 9.A lists the normal operation reporting messages.
its controls and the keyswitch are used to enter setpoint enter or modify setpoint values.
Effective
February
1999
II.
This group of messages is
Page
Courtesy of NationalSwitchgear.com
84
TABLE 9.A: SYSTEM STATUS MESSAGES (Normal Operational Reporting)
TD
172970
Display Complete Help Message
READY--X READY TO START MOTOR -
READY READY
START ATIEMPTING TO START MOTOR
RUN
Display Complete Help Message
IA
Is
le
IG
%
IA
%
Is
MOTOR
XXX PHASE A CURRENT XXX PHASE B CURRENT XXX PHASE C CURRENT
XX GROUND
XXX PERCENT FULL LOAD CURRENT PHASE A The percents of the actual monitored current
XXX PERCENT FULL LOAD CURRENT PHASE B
--
1 SINGLE PHASE MODE
--
3 THREE PHASE MODE
IS
RUNNING
TABLE 9.B: RUN-MONITOR MENU DISPLAYS
IN
AMPS
IN
AMPS
IN
AMPS
FAULT
CURRENT
IN
AMPS Actual ground current
XXX PERCENT FULL LOAD CURRENT PHASE C
Description
Indicates motor can be started.
Displayed during motor start cycle. Indicates normal condition when motor is running
with no alarm or trip condition. This message is displayed after a transition has occurred.
Description
Actual AC line motor current
(in
amps)
OCNT XX OPERATION COUNT
The number of motor starts logged since unit went into seNice, or since the counter has been reset
Effective
February
1999
TD
Courtesy of NationalSwitchgear.com
172970
TABLE 9.8: RUN-MONITOR MENU DISPLAYS
Page
85
RT
RMST
OST
IMX
WTMX
2
1
T
IOC UL
JAM
GF RTD
ICM
2
1
T
%
*Values
X
RUN
TIME
IN
HOURS
xx
REMAINING STARTS
XXX
TIME LEFT ON OLDEST START
xxxx
HIGHEST PHASE CURRENT SINCE LAST RESET
XXX
HIGHEST WINDING TEMP SINCE LAST RESET 1000
xx
NUMBER OF 12T TRIPS SINCE LAST RESET
xx
NUMBER OF IOC TRIPS SINCE LAST RESET
xx
NUMBER OF UL TRIPS SINCE LAST RESET NUMBER OF JAM TRIPS SINCE LAST RESET
xx
xx
NUMBER OF GF TRIPS SINCE LAST RESET NUMBER OF WINDING TEMP TRIPS SINCE
xx
LAST RESET ADDRESS ON THE INCOM NETWORK Address of device if
XXX
XXX
PERCENT OF 12T TRIP LEVEL
in
the shaded area are not displayed if the Universal
IN
MINUTES
Total motor run time, as accumulated by the IQ-
1000
II,
to date from the first time
applied, or since the counter has been reset Number of starts remaining before motor will not
be allowed to start. This is the remainder of OCNT minus actual starts.
This is the remaining time allowed for count minutes) function (program menu item 34). If the motor starts/time is exceeded, this is the time which must elapse before a restart is possible.
Highest phase current monitored by IQ-1000 since last reset (see setpoint item 50, Table 8.8)
Highest winding temperature monitored by IQ-
II
since last reset (see set point item 50,
Table 8.B)
Number of respective trips since last reset (see setpoint item 49, Table 8.8).
on
IMPACC communications
network
2
1
T trip level as calculated by the IQ-
II.
At 100%, the IQ-1000
is
not connected or
is
improperly connected.
RTD
Percent of
1000
trip.
Module
AC
II
will initiate
power was
(in
II
an
1
2
T
9.2 TROUBLESHOOTING IQ-1000
If
EQUIPMENT -
tions, certain troubleshooting information can be used to assist
in
localizing the problem. When a malfunction
occurs, the Operator Panel displays specific messages
relating to alarm or trip conditions. The unit's monitoring
abilities provide valuable information, which are divided
into two categories:
• Alarm conditions (Par. 9.2.1)
• Trip conditions (Par. 9.2.2)
9.2.1 Alarm Conditions -An alarm condition occurs
when one of the electrical characteristics exceeds its pro-grammed setpoint value. Note, however, that some alarm
Effective
February
the monitored equipment malfunc-
1999
II
MONITORED
characteristics must exceed the setpoint value for a pro-
grammed time value
When this condition happens, the red Alarm LED lights,
and a message appears
with the isolation process.
TROUBLESHOOTING PROCEDURES AT TIMES
INVOLVE WORKING IN EQUIPMENT AREAS WHERE POTENTIALLY LETHAL VOLTAGES ARE PRESENT. PERSONNEL MUST EXERCISE EXTREME CAUTION
TO AVOID INJURY, INCLUDING POSSIBLE FATAL
INJURY.
before the alarm condition occurs.
in
the Display Window to assist
A
DANGER
Page
Courtesy of NationalSwitchgear.com
86
TD
17297D
External devices connected to the IQ-1000 ll's Alarm relay can be used to give additional warning.
Alarm conditions all have the following
• The IQ-1000 ll's Alarm relay is energized when the condition occurs.
• The form C relay contacts (available at terminals 17,
18, and 19) are brought out from the Alarm
• The condition is automatically cleared if the charac-teristic causing the condition falls to or below the set-
point. At this time the Alarm LED and Alarm relay reset.
NOTE: The Alarm relay will change state when any alarm condition is detected by the IQ-1000
The Trip relay will change state when any trip condition is detected by the IQ-1000
The Auxiliary Trip relay will only change state when the programmed trip state condition(s) has/have been detected by the IQ-1000
The Trip relay on the IQ-1000 at the same time that the Auxiliary Trip relay changes state.
All possible alarm conditions are listed
Related probable causes and solutions are also shown.
9.2.2 Trip Conditions -A trip condition is a situation
that changes the state of the Trip relay and,
cases, the Auxiliary Trip relay, thereby causing the main
contactor to open and the motor to stop running. These
conditions fall into two groups:
11.
II
(see Paragraph 8.24).
II
will always change state
in
common:
in
Table 9.C.
in
relay.
II.
some
• A picture of the metering functions just prior to the occurrence of a trip is stored
recalled by pressing the Step Up or Step Down push-buttons to step through the run-monitor menu. The order of the electrical characteristics displayed is
identical to the listing
• The display window automatically alternates between the last run-monitor menu or program menu item dis-
played and the trip condition's cause. If two trip con-
ditions occur at the same time, the display alternates
between the menu item and the cause of each trip.
• The internal Trip (and,
relay
is
actuated when the condition occurs.
• The form C relay contacts (terminals 11, 12, and 13) are brought out from the Trip
relay contacts are terminals 14, 15 and 16; see Fig-ure 9.1).
• The trip condition must be manually reset by using the Reset pushbutton. The remote reset input (termi-
nal 8), REMOTE INPUT, or INCOM command can also be used to reset the trip condition.
NOTE: The picture of the metering function data is retained by the IQ-1000 II, as described
9.1.4. Pressing the Reset pushbutton clears the
electrical characteristics stored when the trip condition occurred.
pushbutton, the overload) or STEX (starts per allowed time exceeded) message appears, wait for the trip to reset itself.
Trip conditions which are not the result of a possible inter-
nal malfunction are listed causes and solutions are also shown.
LRC/12T (locked rotor or thermal
in
If,
after depressing the Reset
in
in
memory and can be
Table 9.B .
in
some cases, Auxiliary Trip)
relay.
(Auxiliary Trip
in
Paragraph
Table 9.D. Related probable
• When the selected characteristics are greater than the programmed setpoint values (including,
cases, a time setpoint), a trip condition occurs. The red Trip LED lights, and a message appears display window to assist the operator.
• The IQ-1000
may be external to the control -such as a broken report-back signal wire from the machine or process. There also are conditions which may be internal to the control -such as an opto-coupler failure (see Paragraph 9.3).
NOTE: The STEX alarm is conditional. While the motor is running, it is an alarm. If the motor stopped, it becomes a trip.
Trip conditions have these characteristics
II
may also detect a malfunction. These
is
in
common:
in
in
some
the
Effective
February
1999
TD
Courtesy of NationalSwitchgear.com
172970
TABLE 9.C: ALARM CONDITIONS
Page
87
Display
2
1
TA
STEX ALLOWED STARTS All of the allowed starts have been Wait the number of minutes shown
WDAA
MBAA
LBAA
PUAA
JAMA
AA
ULA
AA
Complete Help
Message
I
SQUAREDT
ALARM LEVEL exceeded the alarm level setpoint
EXCEEDED, WAIT MINUTES
WINDING TEMP ALARM
MOTOR BEARING
ALARM
LOAD
BEARING
ALARM PHASE
UNBALANCE ALARM
JAM
ALARM
UNDERLOAD ALARM
IN
The monitored rotor temperature
(60 to 100% of max. temp.).
used
In
value monitored is equal to or
greater than the alarm setpoint function to further isolate the
value for the function displayed.
Probable Cause
each case the actual electrical
Solution
Monitor electrical characteristics to
further isolate the malfunction to
AC
in
line,
°C,
area such as the incoming or motor/load.
on
display or reset by entering
program mode.
With each of the 6 different displays
(at left), perform a monitoring
malfunction. Note: If the actual temperature of one or more of the RTDs does not correspond to the reading suspect the RTDs, RTD wiring, or the RTD Module.
an
NOTE: If the Program menu is being examined while the IQ-1000 occurs, the run-monitor menu will not be automatically displayed. Press the Set Points
pushbutton to display the protection-monitor menu
(Table 9.B).
9.3 TROUBLESHOOTING THE IQ-1000
Troubleshooting the IQ-1000
Operator Panel is inoperative (either the LEDs and dis-
play window are off, or they are not responding properly),
use the procedures listed
keep
in plest to verify are listed first. For this reason, always fol-low the order of the table's suggestions.
Effective
II
is
in
the Run mode and a trip condition
II
UNIT-
II
is straightforward. If the
in
Table 9.E. When doing so,
mind that the most probable problems or the sim-
February
1999
A
IF THE IQ-1000 TO REPROGRAM ALL SETPOINT VALUES THAT APPLY TO THE SPECIFIC IQ-1 000
DO
NOT ATTEMPT TO RESTART THE MOTOR UNTIL ALL VALUES ARE ENTERED AND VALIDATED. (USE THE APPLICATION'S SET POINT RECORD SHEET AND PARAGRAPH 4.3.) DAMAGE TO EQUIPMENT AND/OR PERSONNEL INJURY MAY OCCUR IF THIS
PROCEDURE IS NOT FOLLOWED.
II
IS REPLACED, IT IS NECESSARY
DANGER
II
APPLICATION.
Page
Courtesy of NationalSwitchgear.com
88
TD
CT Connections
17297D
120V
4-20
MA
OUTPUT
TRANSITION 2
/240V
REMOTE
REMOTE
AUTO
EARTH
REMOTE
INC SEQUENCE
GROUND COMMON
NEUTRAL 7
COMMON
SEL 4
INPUT
25
24
1
3
5
6
8 9
10
2.
':J
~
I
J
fi
n
0
0
0
Jll
1i1 0 1i1
Iii
0
l~I
0 0
0
~
ti·-~..:..
0
DDDDDDD
,
ODDDDDD
= "
~
=
DDDDDDD
~
=
DDDDDDD
~
=
~
=
DDDDDDD
= =
DDDDDDD
~
=
= =
0
0
l~
JYI
0
I
0
M
0
00
ro
r;-
•'
•'
•'
~
..Q.
~
I
fl
l
= =
=
~
= = =
~
l
I
00
.,
\:1
fi
l
r
l
f
CoMMUnlca Port
Flloer-Optlc Connector
23
'Wiring
22
21
RTD
ALARM
AUX
TRIP
Option
TRIP
20
19
18
17 16
15
14 13
12
11
tlons
to
Fig.
9.
1 IQ-1000 II Rear Terminals
The IQ-1000 checks. If a malfunction is detected during a diagnostic check, one of the messages listed
played. in
the table occurs, a trip condition is initiated. The follow-
ing actions should be taken:
• Press the Reset pushbutton to clear the display, if possible.
• Try to restart the motor.
If the same display occurs again, the IQ-1000
functioning, and the unit should be replaced.
II
performs continuous internal diagnostic
in
Table 9.F is dis-
In
each case, if any of the failure messages listed
II
is mal-
Effective
February
1999
TD
Courtesy of NationalSwitchgear.com
17297D
TABLE 9.D: TRIP CONDITIONS
Page
89
Display
IOC
Complete Help
Message
In
INSTANTANEOUS
OVERCURRENT monitored is greater than the trip TRIP
each case the actual electrical value Monitor the associated electrical
setpoint value for the function
Probable Cause Solution
displayed. problem.
GND
FLT
JAM
UNDER L
MB
TEMP
LB
TEMP
WDTEMP
LRC/12T
GROUND FAULT TRIP
LOAD JAM TRIP
UNDERLOAD RUN TRIP
MOTOR BEARING OVER
TEMPERATURE TRIP
LOAD BEARING OVER TEMPERATURE TRIP
STATOR TEMPERATURE TRIP
LOCKED ROTOR/THERMAL as directed by the IQ-1000 I l's motor characteristics associated with
OVERLOAD TRIP
WINDING OVER
The rotor winding temperature storage,
temperature algorithm, has exceeded the motor current to further the maximum allowable value of the 12T isolate a problem to areas such protection curve (motor overload as the curve).
INC SEQ INCOMPLETE The INC SEQUENCE input
SEQUENCE TRIP (terminal 10) was not energized within
the incomplete sequence time after a circuits connected to terminal transition has taken place. such as incomplete sequence,
REMOTE REMOTE TRIP The REMOTE INPUT (terminal 8),
used to initiate the remote trip, was determine external cause of trip. energized.
DIFTRIP
DIFFERENTIAL TRIP The REMOTE INPUT (terminal 8),
used to initiate the differential trip, was differential relay energized
PH
UNBAL
PH
REVRS PHASE REVERSAL TRIP
PHASE UNBALANCE TRIP
Single phasing of motor. Monitor the incoming
During initial startup a phase reversal Rotate two of the incoming power
condition exists. leads L
characteristics (as listed
in
Table
9.B) to further isolate the
If
the actual temperature of one or
more of the RTDs does not correspond to the reading suspect the RTDs,
RTD
(in
°C),
wiring, or
the RTD Module.
Monitor the electrical
AC
line or motor overload.
Monitor terminal 10 after a transition to the run mode. Check
10,
field loss, pull-out protection, etc. Check wiring to terminal 8 to
Check status of external
AC
line.
1,
L2,
or
L3.
Check for
proper motor rotation.
Effective
February
1999
Page
Courtesy of NationalSwitchgear.com
90
TABLE 9.D: TRIP CONDITIONS
TD
17297D
Alternately, change the IQ-1000 current transformer wiring by rotating the current transformer wiring terminal
H1
B with Clearly mark the new wiring and update the drawings for future
reference.
T BYPASS
INCOM
STEX
TRIP BYPASS A trip condition is active, yet the IQ-
(JUMPER BYPASS
OF IQ-1000
RELAY) INCOM REMOTE TRIP
II
TRIP
1000
II
still monitors motor current. This indicates Trip relay's contacts have condition. been "bypassed."
The INCOM communication option has Determine and correct cause of
initiated a trip condition.
MAX#
TIME REACHED, WHILE RUNNING ALARM
STARTS PER
ONLY,
Too
many starts were used
allowed period of time.
in
the
Examine wiring of Trip relay's
contacts and remove bypass
remote trip external to the IQ-1000
II.
Wait for the starts to be returned or
clear starts by entering
Program mode. IF STOPPED BECOMES TRIP
TRANSIT
1.
1
LOW TO HIGH VOLTAGE TRANSITION ERROR TRIP
IQ-1000 before the transition time was start and restart motor. complete.
II
did not transition on current
Reset trip, check reason for slow
This trip is initiated only if program menu item 39 is selected for the trip on time out function (TRP TOUT) and the
motor current remained too high during the motor's start cycle. Paragraph 8.15 describes transition timing.
(Refer to the electrical drawings to further isolate a
deficient
AC
line.)
(±15%) exists between terminals
Verify that all connections to the terminal blocks are secure. Turn keyswitch to the Program position for 5 seconds, then
return to the Protection position.
If all connections are secure and the Operator Panel
inoperative, then replace the IQ-1000
11.
is
still
Check frequency setting
Match CT's, CT ratio to deliver
2.5-4
amps secondary
Effective
February
1999
TD
Courtesy of NationalSwitchgear.com
17297D
TABLE 9.F: INTERNAL DIAGNOSTIC FAILURE MESSAGES
Display Complete Help Message
Page
91
AID ERR AID CONVERTER ERROR RAM ERR
RAM
ERROR TRIP
ROM ERR ROM ERROR TRIP OPTO X-CTR
ERR OPTO COUPLER FAILURE TRIP
THE RATIO OF
EXCEEDED FLA
SETTING OR INCREASE
RATI0.
1
Note: This help message may be different some of the early production units.
ZRAM ERR NON VOLATILE MEMORY ELEMENT
SHOULD BE REPLACED
NOTES:
5. The current transformer ratio (item 39) and/or full load ampere (item
32) setpoint values are incorrectly selected. Verify that the setpoints for these menu items on the application's Set Point Record Sheet are entered correctly.
6.
Refer to Table
There are no user serviceable parts
9.
E.
on
the IQ-1000
11.
The user should no attempt servicing this equipment.
Please contact you local Cutler-Hammer representative
or the Cutler-Hammer Power Management Application
Support (PMAS) for service information or additional
questions.
TRIP
FLA
TO
CT
5.
PLEASE REDUCE
2
RATIO
CT
on
PMAS
1 (800) 809-2772 1 (800) 542-7883
(412) 490-6714 FAX BBS FRED
(412) 490-6712
(412) 490-6711
(412) 490-6710 Email: pmpapps@ch.etn.com
Internet: http://www.ch.cutler-hammer.com/pmp
Effective
February
1999
Page
Courtesy of NationalSwitchgear.com
92
TD
17297D
Cutler-Hammer
Pittsburgh,
Effective Printed
Pennsylvania
February
in
U.S.A./CCI
U.S.A.
1999
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.