Cutler-Hammer HV9F50AC-2M0B008, HV9F20AC-2M0B008, HV9020AC-2M0B008, HV9F30AC-2M0B008, HV9F10AC-2M0B000 User Manual

...
CONTENTS
HV9000 USER MANUAL
1 2 3 4 5 6 7 8 9
10
11
12
13
Safety.. ...................................................... 2
E&directive .............................................. 4
Receiving .................................................. 5
Technical data.. ......................................... 7
Installation ............................................... 17
.....................................................
23
HVMulti-line .................................................. 49
Startup .................................................... 61
Fault tracing ............................................ 64
Basic application .................................... 66
System parameter group 0..
...................
73
HVReady application package ............... 75
Options ................................................... 77
HV9000 HVReady APPLICATION MANUAL
A General . . . . . . . O-2
B Application selection . . . . O-2
C Restoring default values of
application parameters . . . . . . . . . . . . . . . . . . . O-2
D Language selection . . . . . . . . . . . . . . . . . . . . . . . . O-2
1 Standard Control Application . 1-l 2 Local/Remote Control Application 2-1 3 Multi-step Speed Application 3-1
4 PI-control Application . . . . . . . . . . . . . . . . . . . . 4-1
5 Multi-purpose Application . 5-1 6 Pump and fan control Application .,6-l
HOW TO USE THIS MANUAL
This manual provides you with the
information necessary to install, start-up and
Quick Start Guide must be done during
operate a Cutler-Hammer HV9000 drive. We
installation and startup.
recommend that you read this manual
If any problem occurs, please call the
carefully.
telephone number listed on the back of this
At minimum the following 10 steps of the
manual for assistance.
Quick Start Guide
1. Check the equipment received compared to what you have ordered, 7. For instructions on how to use the see chapter 3.
HVMulti-line panel see chapter 7.
2. Before doing any start-up actions
8. The basic application has only 10
carefully read the safety instructions in
parameters in addition to the motor
chapter 1.
rating plate data, the parameter and
3. Before mechanical installation, check
application package lock. All of these
the minimum clearances around the
have default values. To ensure proper
unit and verify that ambient conditions
operation verify the nameplate data of
will meet the requirements of chapter
both the motor and HV9000:
5.2. and table 4.3-l a.
- nominal voltage of the motor
4. Check the size of the motor cable, the
- nominal frequency of the motor
utility cable and the fuses. Verify the
- nominal speed of the motor
tightness of the cable connections.
- nominal current of the motor
Review chapters 6.1 .l , 6.1.2 and 6.1.2.
- supply voltage
5. Follow the installation instructions, see
Parameters are explained in chapter
chapter 6.1.4.
10.4.
6 Control cable sizes and grounding
9. Follow the start-up instructions, see
system are explained in chapter 6.2.
chapter 8.
The signal configuration for the Basic
1 O.Your Cutler-Hammer HV9000 is now
application is in chapter 10.2.
ready for use.
Remember to connect the common
terminals CMA and CMB of the digital
input groups (See figure 10.2.1).
If a different I/O configuration or different operational functions from the basic configuration are required, see chapter 12, HVReady application package for a more suitable configuration. For a more detailed description, see the separate HVReady - application manual.
Cutler-Hammer is not responsible for the use of the HV9000 differently than noted in these instructions.
HV9000
Contents
Page 1 (78)
CUTLER-HAMMER HV9000 USERS MANUAL
CONTENTS 1
2
3
4
5
6
7
Safetv
2
7.5
Reference menu 54
1 .l Warnings ........................................ .2
1.2 Safety instructions ......................... .2
1.3 Grounding and ground fault
protection ....................................... 3
1.4 Running the motor ......................... .3
Elf-directive ......................................... 4
2.1 CE-label .......................................... 4
2.2 EMC-directive ................................ .4
2.2.1 General .................................... 4
2.2.2 Technical criteria ..................... .4
8
7.6 Programmable push-button menu 55
7.7
Active faults menu . . . . . . . . . . . . . . . . . . . . 56
7.8
Fault history menu 58
7.9 Contrast menu ._,__._....................... 58
7.10 Active warning display
59
7.11 Controlling motor from the panel .60
7.11 .l Control source change from I/O - terminals to the panel 60
7.11.2Control source change from panel to I/O 60
Start-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
2.2.3 HV9000 EMC-levels ................ .4
2.2.4 Manufacturer’s Declaration of
Conformitv ................................ 4
8.1
Safety precautions ....................... .61
8.2
Sequence of operation ................. .61
,
Receiving . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
9 Fault
tracing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
3.1 Catalog number . . . . . . . . . . . . . . . . . . . . . . 5
10 Basic application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
3.2 Storing ............................................. 6
6
10.1
General ....................................... 66
3.3 Warranty ..........................................
10.2
Control connections .................. .66
Technical
6.1.2 Mot& cable
data
............................
....................................
26
6.1.3
.7
Control cable..
........................
26
4.1 General
6.1 .4 Installation instructions..
............................................
......... 7 29
6.1.4.1 Cable selection and installation for UL listing
...
4.2 Power ratings
.31
6.1.5 Cable and motor insulation
8
checks ................................... 46
6.2
..................................
4.3
Control
Specifications
connections..
...............................
...................
.46
15
6.2.1 Control cables..
.....................
Installation
.46
6.2.2
..........................................
Galvanic isolation barriers..
17
...
.46
6.2.3 Digital input function inversion.48
5.1 Ambient conditions 17 ........................
5.2 Cooling .......................................... 17
5.3 Mounting ........................................ 19
Wiring
23
..............................................
6.1 Power connections ...................... .26
6.1.1 Utilitvcable 26 .............................
HVMulti-line panel..
..........................
.49
7.1 Introduction..
.................................
.49
7.2 Panel operation
............................
.50
7.3 Monitoring menu..
..........................
51
7.4 Parameter group menu ................. 53
12.1 Application selection ....................
75
12.2
10.3
Standard Application
Control signal logic..
...................
...................
75
12.3
67
Local/Remote Application
..........
.75
10.4
12.4
Multi-step Speed Application
Parameters, group 1 ..................
......
.75
68
12.5
PI-control Application..
10.4.1 Descriptions
................
.........................
.76
12.6
69
Multi-purpose Control App.
.........
.76
12.7 Pump and Fan Control App..
......
10.5 Motor protection functions in
.76
13 Options
the Basic Application
..............................................
.................. .72
77
13.1
Filters
.........................................
10.5.1
.77
13.2 Dynamic braking
Motor thermal protection
.........................
..... .72
77
13.3
l/O-expander board
10.5.2
....................
Motor stall warning
.77
13.4 Communications
...............
.........................
72
77
13.5
HVGraphic control panel
............
.77
11
13.6
System
HVDrive
parameter group 0..
......................................
............
.77
13.7 Control panel door mount kit..
.73
.....
.77
13.8 Protected chassis cable cover for loo-150 Hp open chassis units ... 78
11 .l
Parameter table .......................... 73
11.2
Description .................................. 73
12 “HVReady”- application package
..... 75
Page 2 (78)
Safety
HV9000
q
1 SAFETY
ONLY A QUALIFIED ELECTRICIAN CAN CARRY
OUT THE ELECTRICAL INSTALLATION
1 .l Warnings
1
2
A
4 3
4 5
“, ,.,
‘6
Internal components and circuit boards (except the isolated I/O terminals) are at utility potential when the HV9000 is connected to the line. This voltage is extremely dangerous and may cause death or severe injury if you come in contact with it.
When the HV9000 is connected to the utility, the motor connections U(Tl), V(T2), W(T3) and DC-link I brake resistor connections -,+ are live even if the motor is not running.
The control l/O terminals are isolated from the line potential but the relay outputs and other I/O:s (if jumper X4 is in OFF position see figure 6.2.2-l) may have dangerous external voltages connected even if the power is disconnected from the HV9000.
The HV9000 has a large capacitive leakage current.
An upstream disconnect/protection device is to be used as noted
in the National Electric Code (NEC). Only spare parts obtained from a Cutler-Hammer authorized
distributor can be used.
1.2 Safety instructions
2
5 6 7
The HV9000 is meant only for fixed installation. Do not make any con-
nections or measurements when the HV9000 is connected to the utility.
After disconnecting the utility, wait until the unit cooling fan stops and the indicators on the control panel are extinguished (if no keypad is present, check the indicators in the cover). Wait 5 more minutes before doing any work on the HV9000 connections. Do not open the cover before this time has run out.
Do’ not make any voltage withstand or megger tests on any part of
the HVSOOO.
Disconnect the motor cables from the HV9000 before meggering the motor cables.
Do not touch the IC-circuits on the circuit boards. Static voltage
discharge may destroy the components.
&fore connecting to the utility make sure that the cover of the HV9000 is closed
Make sure that nothing but a three-phase motor is connected to the motor terminal, with the exception of factory recommended filters.
HV9000
Receiving
Page 3 (78)
1.3 Grounding and ground fault protection
The HV9000 must always be grounded with a
grounding conductor connected to the grounding terminal. @
The HV9000’s ground fault protection protects only the HV9000 if a ground fault occurs in the motor or in the motor cable.
Due to the high leakage current fault current protective devices do not necessarily operate correctly with drives. When using this type of device its function should be tested in the actual installation.
Warning Symbols
For your own safety, please pay special attention to the instructions marked with these warning symbols:
Dangerous voltage
= General warning
1.4 Running the motor
1
Before running the motor, make sure that the motor is mounted properly.
A
! *
Maximum motor speed (frequency) should never be set to exceed the motor’s and driven machine’s capability.
3
Before reversing the rotation of the motor shaft, make sure that this can be done safely.
Page 4 (78)
E&directive
HV9000
2 EU-DIRECTIVE
2.1 CE-label The CE-label on the product guarantees the
free movement of the product in the EU-area. According to the EU-rules this guarantees that the product is manufactured in accordance with different directives relating to the product.
Cutler-Hammer HV9000s are equipped with
the CE-label in accordance with the Low
Voltage Directive (LVD) and the EMC directive.
2.2 EMC-directive
2.2.1 General The EMC directive (Electra Magnetic
Compatibility) states that the electrical equipment must not disturb the environment and must be immune to other Electra Magnetic Disturbances in the environment.
A Technical Construction File (TCF) exists which demonstrates that the HV9000 drives fulfill the requirements of the EMC directive. A Technical Construction File has been used as a statement of conformity with the EMC directive as it is not possible to test all combinations of installation.
2.2.2 Technical criteria The design intent was to develop a family of
drives, which is user friendly and cost effective,
while fulfilling the customer needs. EMC
compliance was a major consideration from
the outset of the design. The HV9000 series is targeted at the world
market. To ensure maximum flexibility, yet meet the EMC needs of different regions, all
drives meet the highest immunity levels , while
emission levels are left to the user’s choice.
The HV9000 does not include the required
EMC filter, which is available as an option. For use within the EU the end user takes personal responsibility for EMC compliance.
2.2.3 EMC-levels The HV9000 series does not fulfil any EMC
emission requirements without an optional RFI-filter, either built-in or separate. With an RFI-filter, the drive fulfils the EMC emission requirements in the heavy industrial environment (standards EN50081 -2 , EN61 800-3).
All products fulfil all EMC immunity requirements (standards EN50082-l,-2 ,
EN61800-3).
2.2.4 Manufacturer’s Declaration of
Conformity
Manufacturer’s Declaration of Conformity are available upon request.
HV9000
Receiving
Page 5 (78)
3 RECEIVING
This Cutler-Hammer HV9000 drive has been subjected to demanding factory tests before shipment. After unpacking, check that the device does not show any signs of damage and that the HV9000 is as ordered (refer to the model designation code in figure 3-l).
In the event of damage, please contact and
file a claim with the carrier involved
immediately.
3.1 Catalog Number
If the received equipment is not the same as ordered, please contact your distributor immediately.
Note! Do not destroy the packing. The
template printed on the protective cardboard
can be used for marking the mounting points of the HV9000 on the wall.
HV9
015 A C-5 MO
1 TTTTTT
II I I II
Hp size at VT rating
Series (only A at this time)
II I I
Enclosure Rating
C-Compact Nema 1 (IP20)
II I I
N - Std Chassis
P - Std protected chassis (IP20) S - Std NEMA 1 J - Std NEMA 12 (IP54) G -Oversized NEMA 1
D-Oversized NEMA 12
A
00 80 T-
Control/Communication Options 0 00 - No modification 01 - 5 digital inputs, 2 analog inputs (1 Voltage,
1 Current), thermistor input, encoder input 02 - 5 digital inputs, relay output, thermistor inpu 03 - 5 digital inputs, 2 analog inputs (2 Voltage),
3 relay outputs, analog output (voltage), ther mistor input, encoder input
04 - 5 digital inputs, 3 relay outputs, analog out-
put, thermistor input, 05 - Encoder board 32 - ModBus RTU network communications 34 - LonWorks network communications 36 - Metasys@ N2 Network Communications 0 37 - APOGEETM FLN Network Communications
standard in all Compact NEMA 1 sizes)
(other than 0 denotes special)
G - HV Graphic
D Control and communlcatlon opbons for Compact NEMA 1 are included in a separate expansion box P Contact Cutler-Hammer for availability 3 208V reqwes 8 as first character in suffix B Available as a factory installed option only
Figure 3- 1 Catalog number system.
Page 6 (78) Receiving
HV9000
3.2 Storing
If the HV9000 must be stored before installation and startup, check that the ambient conditions in the storage area are acceptable (temperature -40°C - +60X; (­40°F - + 14O”F), relative humidity <95%, no condensation allowed).
3.3 Warranty This equipment is covered by the Cutler-
Hammer standard drive warranty policy.
Cutler-Hammer distributors may have a
different warranty period, which is specified in their sales terms and conditions and warranty
terms.
If any questions arise concerning the warranty,
please contact your distributor.
HV9000
Technical data
Page 7 (78)
4 TECHNICAL DATA
4.1 General Figure 4-1 shows a block diagram of the
and can be mounted externally and connected
HV9000 drive.
via a cable to the drive.
The three phase AC-Choke with the DC-link capacitor forms an LC filter which together with the Diode Bridge produce the DC voltage for the IGBT lnverterfkidge block. The AC-Choke smooths the HF-disturbances from the utility to the drive and HF-disturbances caused by the drive to the utility. It also improves the waveform of the input current to the drive.
The Control I/O block is isolated from line potential and is connected to ground via a 1 MD resistor and 4.7 nF capacitor. If needed, the Control I/O block can be grounded without a
resistor by changing the position of the jumper
X4 (GND ON/OFF) on the control board.
The IGBT bridge produces a symmetrical three phase pulse width modulated AC voltage to the motor. The power drawn from the supply is almost entirely active power.
The Motor and Application Control block is
based on microprocessor software. The microprocessor controls the motor according to measured signals, parameter value settings and commands from the Control I/O block and the Control Panel. The Motor and Application Control block gives commands to the Motor
Control AS/C which calculates the IGBT
switching positions. Gate Drivers amplify these signals for driving the IGBT inverter
bridge.
The basic Control interface and parameters (Basic application) make the inverter easy to operate. If a more versatile interface or parameter settings are needed, an optional application can be selected with one parameter from a “HVReady” application package. The application package manual describes these in more detail.
Input and Output EMC-filters are not required for the functionality of the drive, they are only required for compliance with the EU EMC­directive.
The Control Panel is a link between the user and the drive. With the panel the user can set
parameter values, read status data and give
control commands. The panel is removable
Page 8 (78)
Technical data
4.2 Power Ratings - Base Drives - Compact Size
ZOW, Compact NEMA 1
Rated HP s Output Current
Frame Size/
Variable Torque
Enclosure Size
$yscl; in Inches and (mm)
rF$t Catalog Number
HP
INlO
: 5.6 10
M3l
HV9FlOAC2MOB008
Compact
NEMA 1 4.7 x 12.0 x 304.6 x 5.9 x 149.9)
(119.4
9.9 HV9F20AC2MOB008
: 16
z
M4BI 5.3 x 15.4 x 8.1
Compact NEMA 1 (134.6 x 391.2 x 205.7)
15.4
HV9F30ACZMOB008 HV9F50AC2MOB008
7-112
HV9F75AC2MOB008
1; :;
M5B/ 7.3 x 22.8 x 8.5 Compact NEMA 1 (185.4 x 579.1 x 215.9)
33.1
HV901 HV9015AC2MOB008 OAC2MOB008
20 70
HV9020AC2MOB008
23llV, Compact NEMA 1
Rated HP & Output Current
Frame Size/
Dimensions
Variable Torque
Enclosure Size
WxHxD
HP IJt 0
in Inches and (mm)
ziiht Catalog Number
: 3
5 7-112 10
15 :z
4.7 7.0 10
:“2 30
43 5:
M3l 4.7 x 12.0 x 5.9 Compact NEMA 1 (119.4 x 304.8 x 149.9)
9.9
HV9FlOAC2MOBOO HV9F20AC2MOBOO HV9F30AG2MOBOO
HV9F50AC2MOBOO M4BI 5.3 x 15.4 x 8.1 Compact NEMA 1 (134.6 x 391.2 x 205.7)
15.4
HV9F75AC2MOBOO
HV9010AG2MOBOO
HV9015AC2MOBOO M5BI Compact NEMA 1 7.3 (185.4 x 22.8 x 579.1 x 8.5 x 215.9)
33.1
HV9020AC2MOBOO
HV9025AC2MOBOO
48llV, Compact NEMA 1
Rated HP 8 Output Current Variable Torque HP Iti 0
Frame Srzel Enclosure Size
;yr.;S
in Inches and (mm)
Weight Catalog Number
in Ibs.
: 3
5 7-112
10 15
20
z; 40
M3/ 4.7 x 12.0 x 5.9
HV9FlOAC5MOBOO HV9F20AC5MOBOO
Compact NEMA 1 (119.4 x 304.8 x 149.9)
9.9 HV9F30AC5MOBOO
HV9F50AC5MOBOO HV9F75AC5MOBOO
M4BI 5.3 x 15.4 x 8.1
15.4
HV9010AC-5MOBOO
Compact NEMA 1 (134.6 x 391.2 x 205.7)
HV9015AC5MOBOO HV9020AC5MOBOO
M5B/ 7.3 x 22.8 x 8.5
33.1
HV9025AC5MOBOO HV9030AC5MOBOO
Compact NEMA 1 (185.4 x 579.1 x 215.9)
HV9040AC5MOBOO
(1) Ivt = continuous rated input and output current (variable torque load, max. 40°C ambient).
Technical data
Page 9 (78)
4.2 Power Ratinas - Base Drives - Standard
208V,NEMAl
Rated HP 8 OutI - 3ut Current
I 1
r.___ _.__I
“,__-.‘_I& T ^.^..^
, rra,r,e 3lLW
1 Dimensions I >I, ., u . ‘)
I ,.,-.-L. I
I Y?gnr I Cr+talog Number
I
; :: MVNEMA 1 4.7 x 15.4 x 391.2 x 5.5 x (119.4 215.9) 176 HV9F20AS2M0, HV9F30AS2M0, 5 22 HV9F50AS2M0,
7-l/2
z
MBlNEMA 1 6.2 x 20.3 x 9.4
(157.5 x 515.6 x 2313.8) 35.3
HV9F75AS2M0,
10 HV9010AC-QL”“~ 15 :; HV9015A
z: MG/NEMA 1 6.7 x 25.6 x 11.4 HV9020A
83
(221 .O x 650.2 x 289.6) *4
HV9025A
30 113 HVOOROA 2: 139 165 HV9040A M7/NEMA 1 14.7x39.4x 13
(373.4 x 1000.8 x 330.2) ‘6’
HV9050A
60 200 HV9060Aa-r,v,vnuvo
75 264 MUNEMA 1 19.5 x 50.8 x 14
(495.3 x 1290.3 x 355.6)
337 HV9075AS2MOA008
208V,WEMA12
6.2 x 20.3 x 9.4
HV9075AJ-2MOA008
208V, Protected ChassWChassls
Rated HP 8 Output Current Variable Torque
UP I I\,+ m
Frame Size/ Enclosure Size
p$Si;s
in Inches and (mm)
Weight Catalog Number
in Ibs.
MWProtected
MUProtected
4.7 x 11.4 x 8.5
17.’
HV9F20AP-2MOA006
(119.4 x 289.6 x 215.9) HV9F30AP-2MOA008
6.2 x 15.9 x 9.4
HV9F50AP-2MOA008
35.3
HVSF75AP.2MOAOOg
(157.5 x 403.9 x 236.8)
HvnninAP-3MnAnnn
MG/Protected
HV9015AP-2MOP
8.7 x 20.7 x 11.4 HV9020AP-2MOP (221 .O x 525.8 x 289.6) 77’2 HV9025AP-2MOP
HV9030AP-2MOP
r008
root3 (008 \008
-I
\008 4008
mm
:: 139 165 M7/Protected 9.8 x 31.5 x 12.4
60 200 (245.9 x 800.1 x 315.0)
‘35 HV9040AN-2MOI HV9050AN-2MOE
HV9060AN-2MOE.___
75 264 MB/Chassis @ 19.5 x 35.0 x 13.9
(495.3 x 889 x 353.11
337 HV9075AN-2MOA008
0 Ivt = continuous rated input and output current (variable torque load, max. 40°C ambient). 0 Protected enclosure with option.
Page 10 (78)
Technical Data
HVWOO
4.2 Power Ratings - Base Drives - Standard
23OV, HEMA 1
Rated HP & Output Current Variable Torque HP Ivt 0
3 10
?-l/2 :“2 10 s:
15
trz 5; z
63 113
:: 139 165 75 200
Frame Size/ Enclosure Size
MWNEMA 1
M5lNEMA 1
MGINEMA 1
M7INEMA 1
;ryr$o;s in Inches and (mm)
$L$t Catalog Number
4.7 x 15.4 x 8.5 (119.4x391.2x215.9)
‘76 HV9F30AS2MOAOO
HV9F50ASZMOAOO
6.2 x 20.3 x 9.4 35’3
HV9F75AS2MOAOO
(157.5 x 515.6 x 238.8) HV9010AS2MOAOO
HV9015AS2MOAOO HV9020AS2MOAOO
8.7 x 25.6 x 11.4 HV9025AS2MOAOO
(221 .O x 650.2 x 289.6) *4 HV9030AS2MOAOO
HV9040AS-2MOAOO
14.7 x 39.4 x 13
(373.4 x 1000.6 x 330.2)
18’ HV9050AS2MOAOO HV9060AS2MOAOO
HV9075AS2MOAOO
100 264
MWNEMA 1 19.5 x 47.6 x 13.9
(495.3 x 1209.0 x 353.1)
I I
337
HV9lOOAS2MOAOO
23OV, lEMA12
Rated HP & Output Current
Dimensions
Variable Torque
Frame Size/ Enclosure Size
WxHxD
Weight Catalog Number
in Inches and (mm)
in Ibs.
HP Ivt 0 3 10 M4lNEMA 12 4.7 x 15.4 x 8.5
(119.4x391.2x215.9)
17.13 HV9F30AJ-2MOAOO
;-l/2 :“2
HV9F50AJ-2MOAOO
M5/NEMA 12
6.2 x 20.3 x 9.4
HV9F75AJ-2MOAOO
1: ::
(157.5 x 515.6 x 238.8) 35’3
HV901OAJ-PMOAOO HV9015AJ-2MOAOO
%
:;
HV9020AJ-2MOAOO
MG/NEMA 12
6.7 x 25.6 x 11.4 HV9025AJ-2MOAOO
30 z3
(221 .O x 650.2 x 289.6) 64
HV9030AJ-2MOAOO
40 HV9040AJ-2MOAOO :: 139 165 M7lNEMA 12 14.7x39.4x13 HV9050AJ-2MOAOO
75 200
(373.4 x 1000.8 x 330.2) “’
HV9060AJ-2MOAOO HV9075AJ-2MOAOO
100 264 MBINEMA 12 19.5 x 47.6 x 13.9
(495.3 x 1209.0 x 353.1)
337 HV9lOOAJ-2MOAOO
0 Ivt = continuous rated input and output current (variable torque load, max. 40°C ambient)
Technical data Page 11 (78)
4.2 Power Ratings - Base Drives - Standard
23OV, Protected Chassis/Chassis
b
3
110 MYProtected
L/2
10
2
30
M5/Protected
MB/Chassis 0
$y~Jo;
in Inches and (mm)
4.7 x 15.4 x 6.5 (119.4 x 391.2 x 215.9)
6.2 x 20.3 x 9.4 (157.5 x 515.6 x 236.6)
6.7 x 25.6 x 11.4 (221 .O x 650.2 x 269.6)
14.7 x 39.4 x 13 (373.4 x 1000.6 x 330.2)
19.5 x 47.6 x 13.9 (495.3 x 1209.0 x 353.1)
$L$t Catalog Number
HV9F75AP-2MOAOO HV9010AP-2MOAOO
HV90ZOAP-2MOAOO HV9025AP-2MOAOO HV9030AP-2MOAO0
HV9050AN-2MOAOO HV9060AN-2MOAOO
337 HV9100AN-2MOAOO
1
0 Ivt = continuous rated input and output current (variable torque load, max. 40°C ambient). 0 Protected enclosure with option.
Page 12 (78)
Technical Data
4.2 Power Ratings - Base Drives - Standard
HV!3000
48OV, IEMA 1
Rated HP 8 Output Current
I
Variable Torque
Frame Size/
HP
INto
Enclsoure Size I
5 7-112
MUNEMA 1
E t:
M5INEMA 1
25 32 30
40
MG/NEMA 1
80
177 I
75
96
100
125
125
160 M7lNEMA
1
150
160
200
260
250
320 MaINEMA
1
300
400
4nn
460 MS/NEMA
1
$e$
In Inches and (mm)
4.7
x 15.4 x 8.5
(119.4 x 391.2 x 215.9)
6.2
x 20.3 x 9.4
(157.5 x 515.6 x 238.8)
8.7x25.8x11.4 (221 .O x 850.2 x 269.6)
14.7 x 39.4 x 13.0 (373.4 x 1000.8 x 330.2)
19.5 x 47.6 x 13.9 (495.3 x 1209.0 x 353.1)
27.8 x 56.1 x 15.4 (701 .o x 1424.9 x 391.2)
Fi$rt Catalog Number
48OV, NEMA
12
Rated HP B Output Current Variable Torque
Frame Size1
Enclsoure Size
$yr$o;
HP Ivt 0
in Inches and (mm)
~~~$rt Catalog Number
5 7-l/2 ?I
HV9F50AJ-5MOAOO
MUNEMA
12 4.7
x 15.4 x 6.5
(119.4 x 391.2 x 215.9)
‘76
HV9F75AJ-2MOAOO
10
15
HV901 O/U-PMOAOO
15
21
HV9015AJ-5MOAOO
:z
:: M5/NEMA
12 6.2
x 20.3 x 9.4
(157.5 x 515.6 x 238.8)
35’3
HV9020AJ-5MOAOO HV9025AJ-5MOAOO
:;
ikj
HV9030AJ-5MOAOO HV9040AJ-5MOAOO
%
MG/NEMA
12 8.7
x 25.6
x 11.4
77
(221 .O x 650.2 x 289.6)
83’8 HV9050AJ-5MOAOO
HV9660AJ-5MOAOO
75
96
HV9075AJ-5MOAOO
100
125
125
180 M7lNEMA
12 14.7
x
39.4
x 13.0
HV91OOAJ-5MOAOO
(373.4
x 1000.8 x 330.2)
221 HV9125AJ-5MOAOO
15n
1Rn HV9150AJ-5MOAOO
._- .__
200
280
M6INEMA
12
19.5 x 47.6 x 13.9
250
320
(495.3 x 1209.0 x 353.1)
3og
HV9200AJ-5MOAOO HV9250AJ-5MOAOO
300
400
27.6 x 56.1 x 15.4
HV9300AJ-5MOAOO
400
480 MS/NEMA
12 (701 .o x 1424.9 x 391.2)
574
HV9400AJ-5MOAOO
HV9015AS5MOAOO HV9020AS5MOAOO
HV9040AS-5MOAO0 HV9050AS-5MOAOO HV9060AS5MOAOO
HV91 OOAS5MOAOO HV9125AS5MOAOO
0 Ivt = continuous rated input and output current (variable torque load, max. 40°C ambient) 0 Protected enclosure with option.
HV9OOll
Technical data
4.2 Power Ratings - Base Drives - Standard
Page 13 (78)
,2) I221
-
I Y.Y
.o x 353.1) 3og
HVYLUUAS-3MUA00
HV9250AS-5MOAOO
15.4 .9 x 391.21 574
HV9300AS-5MOAOO HV9400AS5MOAOO
0 Ivt = continuous rated input and output current (variable torque load, max. 40°C ambient).
Q Protected enclosure with option.
Page 14 (78)
Technical data
4.2 Power Ratings - Base Drives - Standard
575V, HEMA l/Chassis
6.7 x 24.3
xl 1.4
0 Ivt = continuous rated input and output current (variable torque load, max. 40°C ambient) 0 Protected enclosure with option.
HV9000
Technical data
Page 15 (78)
4.3 Specifications
Ambient operating
Altitude
Max 1000 m at continuous IyT specification Over 1000 m reduce IvT by 1% per each 100 m Absolute maximum altitude 3000 m
Vibration
(IEC 721-3-3)
Operation: max displacement amplitude 3 mm
at 2-9 Hz,
Max acceleration amplitude 0.5 G at 9-200 Hz
Shock (IEC 68-2-27)
Enclosure
Operation: max 8 G. 11 ms
Storage and shipping: max 15 G, 11 ms (in the package)
Open and protected chassis (IPOO and IP20) Compact NEMA 1 (IP20)
NEMA 1 (IP21) NEMA 12 (IP54) Oversized NEMA 1 Oversized NEMA 12
Table 4.3-1 Specifications
Page 16 (78)
Technical data HMO00
Max switching load:
x continuous load:
8Al24V
0.4A1250VDC 2 kVA/250VAC 2 A rms
Utility voltage: 230 V
Utility voltage: 480 V
Motor underload protection Yes
Short-circuit protection of Yes +24V and +l OV reference
voltages
Table 4.3- 7 Specifications.
Installation
Page 17 (78)
5 INSTALLATION
5.1 Ambient conditions
The environmental limits mentioned in table
4.3-l must not be exceeded.
5.2 Cooling The specified space around the drive
ensures proper cooling air circulation. See table 5.2-i for dimensions. If multiple units
are to be installed above each other, the dimensions must be b+c and air from the outlet of the lower unit must be directed away from the inlet of the upper unit.
With high switching frequencies and high
ambient temperatures the maximum con-
tinuous output current has to be derated
according to Table 5.2-3 and Figures 5.2-3 a-d.
M9 I Chassis’ & NEMA 12 lo-( 3)” 3 12 M9 I NEMA 1
M9 I Chassis’ & NEMA 12 9”’ ( 3 )” 3 12 M9 I NEMA 1
Ml2 I NEMA 1
I
a2 - Distance from inverter to inverter in multiple inverter
installations
* - Protected enclosure with optional cover.
** - Minimum allowable space - No space available for fan
change.
*** - Space for fan change on sides of inverter.
Figure 52 1 lnstallafion space.
480/Pmtected 8
NEMA 1112
,recrea d NEMA 1 ,tected & NEMA 1
Table 5.2 - 1 Installation space dimensions. Table 5.2-2 Required cooling air.
Page 18 (78)
Installation
HV9000
Figure 5.2-2a
3-25hp
Figure 5.2-26
30-150 HP
2 3 4 5 6
7 B 8
10 11 12
13 14 15 16
Figure 5.2-2~
200-400 HP
Figures 5.2-2a-c
Power dissipation as a function of the switching frequency for 480V
(Ir variable torque) for standard enclosures
4’
0
3’
_. _^^.
tfgure s.il-za
2-75HP
Figure 5.2-2e
30- 100 HP
Figures 5.2-2d-e: Power dissipation as a function of the switching frequency for 230 V
(Iv,, variable torque) for standard enclosures.
Installation
Page 19 (78)
figure 5.2-2f
- -tw9025
- - . H”W30
- ““9c.m
Figure 5.2-2h
Figure 5.2-29
Figures 5.2-2 f-h: Power dissipation as a function of the switching frequency for 480V
(IW variable torque), Compact Nema 1.
Page 20 (78)
Installation
HWOOO
Type
Curve
G-W
3.6kHz 1 10kHz
1 16kHz
I I I
Tab/e 5.2-3 Constant output current derating
curves for 480 V (Iw variable torque).
’ = Ask the details from the factory
45 -
40 -
35 ­30 -
25 -
20 -
15 -
10 -
5-
IvT (4
- HV9025 iVT 16 kHz
HV9010
in 10 ktiz
HV9010
I,,, 16 kHz
0’ I
0 10 20 30 40
I ‘C
50
Figure 5.2.3 a
IVI IA)
Figure 52.3 b
rrgwa O.L.J c
r,gure o.L-J 0
Figure 5.2-3a-d:Constant output current (I,) derating curves as a function of ambient temperature
HWOOO
Installation
Page 21 (78)
5.3 Mounting The HV9000 should be mounted in a vertical
position on the wall or on the back plane of a cubicle. Follow the requirement for cooling, see table 5.2-l and figure 5.2-l for dimensions.
To ensure a safe installation, make sure that the mounting surface is relatively flat. Mounting holes can be marked on the wall using the template on the cover of the cardboard shipping package.
Mounting is done with four screws or bolts depending on the size of the unit, see tables
5.3-l and 5.3-2, and figure 5.3-l for dimensions. Units, from 25 Hp to 500 Hp, have special lifting “eyes” which must be used, see figures 5.3-2 and 5.3-3.
The mounting instructions for units over 500
Hp are given in a separate manual. If further information is needed contact your Cutler­Hammer distributor.
figure 5.3-l
Mounting dimensions.
Voltage
208
I230 I480
208
/ 230 I480
208
I 230 I480
Dimensions (inches)
WI W2 Hl
H2 H3 H4 Dl Rl
R2
4.7 3.7 13.5
13.1 12
7.3 5.5 23.4
22.8 21.7
M4 M5 M6
a
M7
NEMAll12
M8
M9
Ml0
Chassis I Protected
f 38.9 l 37.3 141.1
1407 139.4 V
U 15.4 I 0.45 10.24
CONTACT FACTORY
Table 5.3-i Dimensions for open panel units.
Page 22 (78)
Installation
Figure 5.3-2 Lifting of 30-150 Hp units.
WRONG
CORRECT
1c
NOTE! Unit sizes 200 - 400 Hp - do not lift without a rod through the lifting holes in
the unit - see above.
Figure 5.3-3
Lifting of 200400 Hp units.
HV6000
Page 23 (78)
6 WIRING General wiring diagrams are shown in figures
The general wiring diagrams for Ml1 and Ml2 6-l-6-3. The following chapters have more frame sizes are provided in a separate manual. detailed instructions about wiring and cable If further information is required, contact your connections. Cutler-Hammer distributor.
/
1, Brake
Chopper (Optmnal,
Figure 6-l: Genera/ wiring diagram, open/protected chassis units frame sizes M4-M6.
Page 24 (78)
Wiring
HV9000
Figure 6-2 General wiring diagram, open/protected chassis frame size z M7and NEMA l/12 units frame
size r MB.
HV9000
Wiring Page 25 (78)
+IOV~ r--------
$i+
I
*
I
y
!
I
! I
I
I
i._-_._._._._.i
L !9!!!!!!_. A
k63
Figure 6-3 Genera/ wiring diagram, NEMA l/12 units frame sizes M4 to M7and Compact NEMA 1 units.
Page 26 (78) Wiring
HV9000
6.1 Power connections Use heat-resistant cables, +6O”C or higher.
The cable (and the fuses) must be sized in accordance with the rated output current of the unit. Installation of the cable consistent with the UL-instructions is explained in chapter 6.1.4.1.
The minimum dimensions for the Cu-cables and corresponding fuses are given in the tables 6.1-2 -6.1-5. The fuses have been selected so that they will also function as overload protection for the cables.
Consistent with UL requirements, for maximum protection of the HV9000, UL recognized fuses type RK should be used.
If the motor temperature protection (I?) is used as overload protection the cables may be selected according to that. If 3 or more cables are used in parallel, on the larger units, every cable must have it’s own overload protection.
These instructions cover the case where one motor is connected with one cable to the drive.
Always pay attention to the local authority regulations and installation conditions.
6.1 .l Utility cable Utility cables for the different EU EMC levels
are defined in table 6.1-1.
6.1.2 Motor cable Motor cables for the different EU EMC levels
are defined in table 6.1-1.
6.1.3 Control cable Control cables are specified in chapter
6.2.1.
1 Cable
1 level N I level I
Utility cable
1
1
Motor cable
2
2
Control cable
3
3
Table 6.1- 7 Cable types for the different E MC levels.
1 = The power cable suitable for the installation, ampacity and voltage.
Shielded cable is not required.
2 = The power cable contains a concentric protection wire, and is suitable for the ampacity and voltage.
For maximum EMC protection, use of shielded cable is required.
3 = The control cable has a compact low-impedance shield.
HV9000 Wiring
Page 27 (78)
Cu.cable
460V HP Iti FlSe
UTILITY & MOTOR
(Ground) 1 3 3 5 10 16 (16)
Table 6.1-2 Utility, motor cables and fuse recommendations according to Iw
output current 480V range.
Cu-cable
575V HP Ivi
Fuse
UTILITY 8 MOTOR
(Ground) 3 5
14 15 14 7.5 (14)
10 15 19 20 12 (12) 20 23 25 10 (10) 25 26 35
150 1145 1100 1 00 (2) 200 1222 1250 1 300MCM (00) 350 13117 I?“” I R=.“MCM mnnr
Table 6.1-4 Utility, motor cables and fuse
recommendations according to Ivr output current, 575V range.
Page 28 (78) Wiring
Tab/e 6.1-5 Ufilitv. motor cables and fuse
recdhmendations according to 1~ output current 230Vrange.
Yame
w3 w4 H4B w5
M5B
HP
Voltage
CABLE (AWG/MCM)
Main
Ground
All 230/480 14
14
All 230/460 10
10
All 230/460
6
6
All 230/460/575
15-25
230
25-40
460
20-40
230 2
00
30-40
460
M6 40-60
575
50-75
460
Cu, 00 Al
00
75-100
575
50-75
230
M7
100-150
460
100
230 350 MCM
2x500 MCM Al
000
D NEMA i/12 maximum 3 parallel connected cables can be used
Tab/e 6.1-6 Maximum cable sizes of the power
terminals
HV9000
Wiring
Page 29 (78)
Connecting cables:
- Motor and utility cables should be stripped according to figure 6.1.4-2 and table 6.1.4-2.
- Open the cover of the HV9000 according to figure 6.1.4-3.
- Remove sufficient plugs from the cable cover (open chassis) or from the
bottom of the NEMA l/12 units.
- Pass cables through the holes in the cable cover.
- Connect the utility, motor and control cables to the correct terminals.
See figures 6.1.4-3-I 6. HV9000 + external RFI-filter: (See RFI-filter option manual). Contact your Cutler-Hammer distributor for more information. Cable installation consistent with UL-instructions is explained in chapter 6.1.4.1.
- Check that control cable wires do not make contact with electrical
components in the device.
- Connect optional brake resistor cable (if required
- Ensure the ground cable is connected to the + -terminal of the
frequency converter and motor.
d
- For open chassis units, 200-400 Hp, connect the isolator plates of the
protective cover and terminals according to figure 6.1.4-I 1.
1
If a HV9000 open chassis unit is to be installed outside a control cabinet or a separate cubicle a protective 1P20 cover should be installed to cover the cable connections, see figure 6.1.4-3. The protective cover may not be needed if the
unit is mounted inside a control cabinet or a separate cubicle. All open chassis HV9000 units should always be mounted inside a control
cabinet. or a separate cubicle.
Locate the motor cable away from the other cables:
- Avoid long parallel runs with other cables.
- If the motor cable runs in parallel with the other cables, the minimum
distances given in table 6.1.4-l between the motor cable and control
cables should be followed.
- These minimum distances apply also between the motor cable and
signal cable of other systems.
- The maximum length of a motor cable can be 600ft (180 m) (except
for ratings 2 Hp and below max. length is 160 R (50 m) and 3 Hp max.
length 330 ft (100 m)). The power cables should cross other cables at an
angle of 90” degrees. An output dv/dt filter option is required for motor cable
lengths exceeding 33ft (1Om) for drive 2 Hp and below and IOOR (33m) for
drives 3Hp and larger.
Fi
Tab/e 6.1.4- 1 Minimum cab/e distances.
See chapter 6.1.5 for cable insulation checks.
Page 30(78)
of the drive, motor and supply panel.
-
Mount the cable cover (open chassis units) and the unit cover.
-
Ensure the control cables and internal wiring are not trapped between the
cover and the body of the unit.
5
NOTE: The connection of the transformer inside the unit in frame sizes M7-Ml9 has
to be changed if other than the default supply voltage of the drive is used. Contact your Cutler-Hammer distributor if more information is needed.
Voltage Code (VC)
Default Supply Voltage
2
230V
5 460v
6
575v
HV9000
Wiring
Page 31 (78)
6.1.4.1 Cable selection and installation
for the UL listing
For Installation and cable connections the fol-
In addition to the connecting information the
lowing must be noted. Use only with copper
tightening torque of the terminals are defined
wire temperature rating of at least 60/75”C.
in the table 6.1.4.1-2.
Units are suitable for use on a circuit capable of delivering not more than the fault RMS symmetrical amperes mentioned in the table
6.1.4.1-1, 480V maximum.
Frame
Vo,tage Mawmum RMS symmetrical
amperes on supply circuit
M3
All
35,000
M4-Ml2 All 100,000
Tab/e 6.1.4. f-1 Maximum symmefricalsupp/ycurnt.
Table 6.1.4.1-2 Tightening torque.
Page 32 (78)
HV9000
_
_
-
Figure 61.4 1 Stripping motor and utility
cables. CONTACT FACTORY
igths (ln.)
Tab/e 6.1.4-2 Stripping lengths of the cables (in).
@ Loosen screws (2 pcs)
@ Pull cover bottom outwards 6l Push cover upwards
Figure 6.1.4-2 Opening the coverot the HVYUW.
HV9000
Wiring
Page 33 (78)
Power card
Control card
Control I/O
terminals
Connect the shield to the terminal ,
Fix the control cable with a tie wrap .
Utility cable .
terminals
(LIT ~2, L3j
Ground 4 (6)
terminals
(PE)
DC-link/Brake resistor terminals (-,+)
Motor cable terminals
I I
/III II
I I
IIII II
I I
II/I II
I I
II/I II
I I I I
Control cable
Motor Cable
Utility cable
Brake resistor cable
figure 6.1.4-3 Cable assembly for open chassis: 5 - 25 Hp voltage code 4 ana Y - l:, tip coae z.
Page 34 (78)
Control card
I/O terminals
Connect the shield to the terminal
Fix the control cable with a tie wrap
resistor terminals
Ground terminal
Ground terminal
Rubber grommets
I
I
Motor cable
Brake resistor cable
Utility cable
Control cable
m4lP21
gure 6.1.4-4
Cab/e assembly for Standard NEMA 7: 5 - IO Hp voltage code 5 and 3 Hp code 2
HV9000
Wiring
Page 35 (78)
Fix the control
cable with a tie
Ground terminal
\I
\
\
Motor cable
Brake resistor cable
Control cable
Utility cable
m5lP21
Utility cable
’ terminals , DC-link/brake
resisotr terminals
_ Motor cable
terminals
A Ground terminals
- Rubber grommets
Figure 6.1.4-5 Cable assembly for Standard NEMA 1: 15 - 25 Hp voltage code 5 and 5 - 15 Hp code 2.
Page 36 (78)
HV9000
Control card
I/O terminals y
Connect the
shield to
the terminal
Ground terminal & A
-
- Internal cooling fan
Utility cable
4 terminals
DC-link/brake
Y resistor terminals
Motor cable
- terminals
, Rubber grommets
\’
\
\
Motor cable
Brake resistor cable
Control cable
Utility cable
Figure 6.1.4-6
Cable assembly for Standard NEMA 12: 15 - 25 Hp voltage code 5 and5 - 15 Hp code 2
Page 37 (78)
Fix the control
cable with a tie
Brake resistor cable
Figure 6.1.4-7 Cab/e assembly for open chassis: 30 - 75 Hp voltage code 5 and 20 - 40 Hp code 2
Page 38 (78)
Wiring
HV9000
Control card -
I/O terminals -
Connect the ­shield to the terminal
Fix the control ­cable with a tie wrap
Ground terminal _
\’
\ Motor Cable
Control cable
Brake resistor cable
Utility cable
Utility cable
terminals
DC-link/Brake resistor terminals
Motor cable
terminals
Ground terminals
Rubber grommets
Figure 6.1.4-8
Cable assembly for Standard NEMA 130 - 75 Hp voltage code 5 and 20 - 40 Hp code 2
Page 39 (78)
Connect the screen
to the terminal
Fix the control cable
with a tie wrap
DC-link/Brake
Brake resistor
Figure 6.1.4-9 Cab/e assembly for open chassis: 100 - 150 Hp voltage code 5 and 50 - 75 Hp code 2
Page 40 (78)
Wiring
HV9000
Control cable
conductor twisted of cable shield
Utility
cable
Control F;;;
cable
ChSKYTKP
Figure 6.1.4-10 Cable assembly for open chassis 200 - 400 Hp voltage code 5, 125 - 400 Hp code 6
and 100 Hp code 2; for NEMA 1200 - 400 Hp code 5 and NEMA I 100 Hp code 2.
HV9000
Wiring
Page 41 (78)
Fixing screws of
protective covers
After cable connections before swtich on the utioity supply, enusre:
1. Insert all 10 terminal isolator plates (A) VI the slots between the terminals,
see figure below
2. Insert and fiz three plastic protective covers (B, C, and D) over the terminals
Securing the terminal isolation plates
lnser plate into the slots
Bend the plate to
fit it into a slot.
Release to lock it in correct position
Ch9SUO.M
Terminal isolation plates
Figure 6.1.4-7 f Cab/e cover and terminal
assembly for open chassis
200 - 400 t/p voltage code
5,
125 - 400 Up code 6, and
100 Hp code 2; and NEMA
1200 - 400 Hp code 5 and
100
Hp code 2
Page 42 (78)
Wiring
HV9000
the terminal
Utility cable terminals
DC-link/Brake resistor terminals
Motor cable terminals
Control cable H
Utility cable H
Ground terminal
US .,“. ,” .“. . .-. -
Ch5CX6
Y Motor Cable
Brake resistor cable
igure 6.1.4-12 Cable assembly for open chassis 3 - 30 Hp voltage code 6
HV9000 Page 43 (78)
Connect the shield to the terminal
Utility cable
terminals
DC-link/Brake resistor terminals
Motor cable
terminals
Ground terminal
Ground terminal
Ch6CX6
Control cable ’
Utility cable j
Figure 6.1.4- 13 Cab/e assembly for open chassis 40 - 100 Hp voltage code 6
Page 44 (78)
Wiring
HV9000
Utility cable
DC-link/brake
Motor cable
terminals
resistor
terminals
(Li, L2, L3)
terminals (-, +)
(U v, W)
Yellow-
green
\
protective cable
Utility cable
Ground terminal
Motor cable
for the control cable
Figure 6.1.4-14 Cab/e assembly Compact NEMA 1 1 - 3 Hp. voltage code 2,1-5 Hp voltage code 5
Page 46 (78)
Wiring
HV90W
6.1.5 Cable and motor insulation checks 1
2
3
Motor insulation checks
Motor cable insulation checks Disconnect the motor cable from the
terminals U, V and W of the HV9000 unit and from the motor.
Measure the insulation resistance of the motor cable between each phase
conductor. Also measure the insulation
resistance between each phase conductor and the protective ground conductor. The insulation resistance must be >l MR
Utility cable insulation checks
Disconnect the utility cable from
terminals Ll, L2 and L3 of the HV9000
unit and from the utility. Measure the insulation resistance of the
utility cable between each phase conductor. Also measure the insulation resistance between each phase conductor and the protective ground conductor. The insulation resistance must be >l MQ
Disconnect the motor cable from the motor and open any bridging connections in the motor connection box.
Measure insulation resistance of each motor winding. The measurement voltage has to be at least equal to the utility voltage but not exceed 1 OOOV. The insulation resistance must be >l MQ
6.2 Control connections Basic connection diagram is shown in the
figure 6.2-l. The functionality of the terminals for the Basic
application is explained in chapter 10.2. If one of the HVReady applications is selected, check the application manual for the functionality of the terminals for that application.
6.2.1 Control cables The control cables should be minimum of #20
gauge shielded multicore cables, see table
6.1-l. The maximum wire size rating of the terminals is #14.
6.2.2 Galvanic isolation barriers The control connections are isolated from the
utility potential and the I/O ground is connected to the frame of the HV9000 via a 1 MRresistor and 4.7 nF capacitor. The control l/O ground can also be connected directly to the frame,
by changing the position of the jumper X4 to ON-position, see figure 6.2.2-l.
Digital inputs and relay outputs are isolated from the I/O ground.
HV9000 Wiring
Page 47 (78)
Terminal
r ~
Function
I 1 I
+lOVret
I
Reference voltage output
2
vin+
Analog signal input
3 GND
I/O ground
4
Iin+
Analog signal (+input)
5
Iin-
Analog signal (-input) 6 24V out 24V supply voltage 7 GND
I/O ground
6 DIAl Diaital inout 1 9 DIA2
IO 1 DIA3
Digital input 2 Digital input 3
11
I I
CMA
I
Common for DIAl-DIA3
I
12 1 24Vout 1 24V supply voltage
I
13 1 GND
1 I/O around
I
14 1 DIEI
I
Digital input 4
I
15 ( DIB5
I
Digital input 5 16 DIB6 17 CMB
Digital input 6
Common for 0184 - DIB6
;
/ Relay output 1
1
f 1 i-
Relay output 2 f ~ FIw
Figure 6.2- 1 Control //O-terminal signals.
Specification
Burden max 10 mA l
Signal range -10 V- +lO V DC
Signal range O(4)-20 mA
*20%, load max. 100 mA
Rr = min. 5 kR
Must be connected to GND or 24V of
I/O- terminal or to external 24V or GND
Same as terminal # 6 Same as terminal # 7 Rr = min. 5 kD
Must be connected to GND or 24V of
I/O- terminal or to external 24V or GND Signal range O(4)-20 mA,
R, max. 500 Q
Transistor output, max. Vi, = 48 VDC
max. current 50 mA
Max. switch. voltage 250 VAC, 300 VDt
Max switch. current 6 A I 24 VDC,
0.4 A I250 VDC
Max. switch. power <2 kVA I250 VAC
Max. cont. current <2 A rms
* If the potentiometer reference is used, potentiometer R = l-10 kR
Page 48 (78)
Wiring
HV9000
FE01 1 ROl 2 R01.3
R02.1
ROP.2
R02 3
3r!fzLL
Figure 6.2.2- 1 Isolation barners.
6.2.3 Digital input function inversion
The active signal level of the digital input logic depends on how the common input (CMA,
CMB) of the input group is connected. The connection can be either to +24 V or to ground. See figure 6.2.3-l.
Figure 6.2.3- 1 Positive/negative logic.
The +24V or ground for the digital inputs and common terminals (CMA, CMB) can be either external or internal (terminals 6 and 12 of the
Ground (-)
+24 V A CMA
Negative logic (0 V active signal) = input is active when the switch is closed.
HV9000
7. CONTROL PANEL
Control Panel Page 49 (78)
7.1 Introduction
The control panel of the HV9000 drive
item. The eight pushbuttons on the
has a Multiline Display with seven
control panel are used for controlling the
indicators for the Run status
drive, setting parameters and monitoring
(RUN,,-i, ‘I$, READY, STOP,
values. The panel is detachable and isolated from’the utility line potential. The display examples in this chapter show only the text and numeric lines of the Multiline Display. The Run status
indicators are not included in the
examples.
ALARM, FAULT) and two indicators for the control source (Panel/Remote). The
panel also has three text lines for the menu location, menu/submenu descriptions and the number of the
submenus or the value of the monitored
DRIVE Sl
\
~
RUN =
rsc= STOP =
READY =
FAULT =
Panel/ Remote =
1
Figure 7.1- 7 Control panel with LED display.
-ATUS INDICATORS
lights when motor is running.
shows the selected rotation.
lights when motor is not running.
lights when input voltage is supplied and the unit is ready
for use.
lights when a fault in frequency drive occurs.
Shows the active control source
Menu button fLefQ
Move forward in the menu
Menr/ button fn@h(J Move backward in the menu
Browserbutton (up)
Move in the main menu and between pages inside the same submenu. Change value.
Browser button (down)
Move in the main menu and between
pages inside the same submenu. Change value.
= Enterbutton
Acknowledgement of changed value.
Fault history reset. Function as programmable button.
= Reset button
Fault resetting
= Start button
Starts the motor if the panel is the active control source
= Stop button
Stops the motor if the panel is the active control source
Page 50 (78)
Control Panel HV9000
7.2 Control panel operation The data on the panel are arranged in
main menu using the Menu buttons. The
menus and submenus. The menus are used
symbol M on the first text line stands for the
to display and edit measurement and
main menu. It is followed by a number that
control signals, set parameters and
refers to the submenu in question. See the
reference values, and display faults.
HV9000 User’s Manual and the Application
Through the menus you can also adjust the
Manual for the specific parameters
contrast of the display and use the
available for the needed setup.
programmable buttons.
The arrow (+ in the lower right corner
indicates that a further submenu can be
The desired submenu is accessed from the
accessed by pressing the Menu button
(right).
Scroll the active fault list
Figure 7.2-7 Panel operation.
HV9000
Control Panel
Page 51 (78)
7.3 Monitoring menu
The monitoring menu can be entered
signals are listed in Table 7.3-l. The
from the main menu when the symbol
values are updated once every 0.5
Ml is visible on the first line of the
seconds. This menu is meant only for
Multiline display. How to browse through
signal checking. The values cannot be
the monitored values is presented in
altered here. See 7.4 Parameter group
Figure 7.3-l. All monitored
menu.
Figure 7.3- 1 Monitoring menu.
Number Signal name
Unit Description
Vl Output frequency
Hz
Frequency to the motor
v2 Motor speed
rpm
Calculated motor speed
v3 Motor current A
Measured motor current
v4 Motor torque %
Calculated actual torque/nominal torque of the unit
v5
Motor power
%
Calculated actual power/nominal power of the unit
V6
Motor voltage V
Calculated motor voltage
v7 DC-link voltage V
Measured DC-link voltaae V8 Temperature “C Heat sink temperature v9
Operating day counter DD.dd
Operating days’, not resettable
VlO Operating hours, “trip courter’
HH.hh Operating hours*, can be reset
Vii 1 MW hours counter
1 with programmable button #3
1 MWh 1 Total MWh, not resettable
v12 1 MWh ours, “triD counter” / MWh 1 Resettable with oroarammable button
I
v13 v14
v15
B4, section 7.6 ’
-
Voltage/analog input
V
Voltage of terminal V,“+ (term. #2)
Current/analog input
mA
Current of terms I,“+ & I,“- (term. #4, 5)
Digital input status, gr. A
See Figure 7.3-2
V16
v17 V18 v19 v20
Digital input status, gr. B Digital and relay output sta’:us Control program Unit nominal power HP Motor temperature rise %
See Figure 7.3-3
See Figure 7.3-4
Version number of the control software
Unit power size of the unit
100% = nominal motor temperature has
been reached.
’ DD = full days, dd = decimal part of day ’ HH = full hours, hh = decimal part of hour
Table 7.3- 1 Monitored signals. Table 7.3- 1 Monitored signals
Paae 52 (78)
Control Panel
HV9000
Digital input status indication
igure 7.3-2 Digital inputs, Group A status.
V16 Dig input B Stat
Exampk l”p”t
TUlll”d
101
-/
DIB4
14
clmed
I I
/
DlBS
15
open
@re 7.3-3 Digital inputs, Group B status.
Figure 7.3-4 Output signal status.
HV9000
Control Panel
Page 53 (78)
7.4 Parameter group menu The parameter group menu can be
entered from the main menu when the symbol M2 is visible on the first line of the Multiline display. Parameter values are changed in the parameter menu as shown in Figure 7.4-l :
Push the menu button (right) once to move into the parameter group menu (G) and twice to enter the desired parameter menu. Locate the parameter you want to change by using the browser buttons. Push the menu button (right) once again to enter the edit menu. Once you are in the edit menu, the symbol of
the parameter starts to blink. Set the
desired new value with the browser buttons and confirm the change by
pushing the Enter button. Consequently, the blinking stops and the new value is visible in the value field. The value will
not change unless the Enter button is
pushed.
Several parameters are locked, i.e.
uneditable, when the drive is in RUN status. If you try to change the value of such a parameter, the text *locked will appear on the display. You can return to the main menu anytime by pressing the Menu button
(left) for 2-3 seconds.
The basic application embodies only those parameters necessary for operating the device. The parameter group 0 is accessible only by opening the Application package lock. See Chapter 11 of the HV9000 User’s
Manual.
Other applications include more parameter groups.
Once in the last parameter of a parameter group, you can move directly to the first parameter of that group by pressing the browser button (up).
Page 54 (78)
Control Panel
HV9000
7.5 Reference menu
The reference menu can be entered from the main menu when the symbol
M3 is visible on the first line of the Multiline panel.
If the control panel is the active control source, the frequency reference can be changed by changing the value on the display with the browser buttons (for the selection of the active control source, see Chapter 7.6 Programmable push-
button menu). See Figure 7.5-l. Move deeper in the menu with the menu
button (right) until the symbol Rl starts to blink. Now you are able to alter the frequency reference value with the
browser buttons. Pressing the Enter
button is not necessary. Motor speed
changes as soon as the frequency
reference changes or the load inertia
allows the motor to accelerate or
decelerate.
In some applications, there might be
several references.
Figure 7.5- 1 Reference setting on the control panel
HV9000
Control Panel
Paae 55 (78)
7.6 Programmable push-button menu The programmable push-button menu
can be entered from the main menu when the symbol M4 is visible on the first line of the Multiline display. In this menu, there are four functions for the
Enter button. The functions are available
in this menu only. In other menus, the button is used for its original purpose. The status of the controlled function is shown through a feedback signal.
Enter the edit menu with the menu but­ton (right). Then, the symbol Bl starts to
blink. To change the button value, push the Enter button after which the new feedback value appears and the button
sign B is replaced with a black square
blinking together with the button number.
After releasing the Enter button, the
black square reverts to B. The new value
stops blinking when the new value (e.g.
reverse direction) has been received and
put into operation. See Figure 7.6-l.
Figure 7.6-l Programmable push-button
Button Button
Feedback information
Number Description
Function
0
1
Note
Bl Reverse
Changes the rotation Forward
Reverse
Feedback information direction of the motor. flashes as long as the Available only when
command is carried
the control panel is the
Out.
acitve control source.
82 Active
Selection between t/O Control via
Control from
control
terminals and control
VO terminals the panel
panel.
83 Operating
Resets the operating No resetting Resets the
hours, trip
hours trip counter
operating
counter
when pushed.
hours trip
reset
counter
84 MWh
Resets the MWh trip
No resetting Resets the
counter counter when pushed.
MWh trip
reset
counter
Table 7.6-l Programmable push-button descriptions
Page 56 (78)
Control Panel
HV9000
7.7 Active faults menu
The active faults menu can be entered from the main menu when the symbol M5 is visible on the first line of the Multiline display
as shown in Figure 7.7-l.
When a fault brings the frequency converter to a stop, the fault code (F#) and the descrip­tion of the fault are displayed. If there are sev-
eral faults at the same time, the list of active faults can be browsed with the browser but­tons.
The display can be cleared with the Reset
button and the read-out will return to the same display it had before the fault trip.
The fault remains active until it is cleared with Reset button or with a reset signal from the I/O terminal.
Note! Remove anv external Start sianal be­fore resettina the fault to prevent an unin­tentional restart.
Figure 7.7- 1 Active faults menu
upply is correct an internal failure has
Gable 7.7- 7 Fault codes
HV9000 Control Panel
Page 57 (78)
Fault
I I
F.Wlt Possible Cause
I
Checking
codes F14 iv9000 Temperature of heat sink over 75°C Check the cooling air flow
wertemperature
For Compact Nema 1 over 80°C
Check that the heat sink is not dirty Check ambient temperature Check that t?e witching frequency is not too high
pa$pared with ambient temperature and motor
F15 1 Motor stalled The motor stall protection has tripped
Check the motor
F16
F17
F16
FIS
F20
Motor overtemperature
Motor underload
Analog input hardware fault
Option boad identification
1ov voltage reference
The HVSOOO frequency drive motor temperature model has detected motor overheat
-motor is overloaded
Decrease motor load. Check the temperature model parameters if the motor was not overheated
The motor underload protection has tripped
Check the motor and powble belts, etc.
Component failure on control board Contact your Cutler-Hammer dlstrlbutor
Reading of the option board has failed Check the installation
- If installation is correct, contact your Cutler-Hammer distributor
+iOV reference shorted on control board Check the cabling from +iOV reference voltage or option board
F21
F22 F23
24V supply
1 option board
+24V supply shorted on control board or Check the cabling from c24V reference voltage
EEPROM checksum fault
“”
F26
Panel communication Prr”r
_ ._
Wameter restoring error
interference fault component failure
On resetting this fault the drive will automatically load the parameter default settings. Check all parameter settings after reset. If the the fault occurs again contact your Cutler­Hammer distributor
- interference fault
- component failure
The connection between panel and the HVSOOO frequency drive is not working
Reset the fault and restart. If the fault occurs again
contact your Cutler-Hammer distributor Check the panel cable
F29
Thermistor protection
Thermistor input of the I/O expander Check motor cooling and loading board has detected increase of the motor
Check the thermistor connection
temperature
If there are no thermistors, make sure the inputs are shortcircuited
F36
Analog input I,, < 4mA (slgnal
The analog input current L,, is below 4mA
Check the current loop circuitry
signal source has failed
range selected - control cable is broken
4.20mA)
F41
1 Efier”al fault
1 diaita, input
An external fault has been detected at the
Check the external fault SO”rCe
Table 7.7- 1 Fault codes (cont.)
Page 58 (78)
Control Panel
HV9000
7.8 Fault history menu
The fault history menu can be entered from
memory, the next fault will erase the oldest
the main menu when the symbol M6 is
from the memory.
displayed on the first line of the Multiline
Pressing the Enter button for about 2...3
panel.
seconds will reset the whole fault history.
The memory of the drive can store the up to
Then the symbol F# will change to 0.
the 9 latest faults in the order of appearance. The most recent fault has the
number 1, the second latest number 2 etc. If there are 9 uncleared faults in the
Figure 7.8- 1. Fault histoly menu
7.9 Contrast menu
The contrast menu can be entered from the
symbol C starts to blink. Then change the
main menu when the symbol M7 is visible
contrast using the browser buttons. The
on the first line of the Multiline display.
changes take effect immediately.
Use the menu button (right) to enter the edit menu. You are in the edit menu when the
Figure 7.9-l. Contrast setting
HV9000
Control Panel
Page 59 (78)
7.10 Active warning display When a warning occurs, a text with a
in any special way.
symbol A# appears on the display.
The warning on the display does not
Warning codes are explained in Table
disable the normal functions of the push
7.10-l.
buttons.
The display does not have to be cleared
Code 1 Warning 1 Checking
Al5 1 Motor stalled (Motor stall orotectionl. 1 Check motor. Al6
Motor overtemperature (Motor thermal protection).
Check motor loading.
A17 Motor underload (Warning can be activated in
Check motor loading.
HVReady applications).
A24
The values in the Fault History, MWh counters or operating day/hour counters might have been changed in the previous mains interruption.
Does not need any actions. Take a critical attitude to these values.
A28
The change of application has failed.
Choose tha application again and push the Enter button.
A30
Unbalance current fault: the load of the segments is not equal.
Contact your Cutler-Hammer distributor.
A45 HV9000 frequency converter overtemperature
warning: Temperature >7O”C.
Check the cooling air flow and the ambient temperature.
A46
Reference warning; the current of input lin+ <4mA Check the current loop circuitry. (Warning can be activated in HVReady applications)
A47 External warning; (Warning can be activated in
HVReady applications
Check the external fault circuit or device
Tab/e 7. lo- 1 Warning codes
Page 60 (78) Control Panel
HV9000
7.11 Controlling the motor from the panel
The HV9000 can be controlled from either the I/O terminals or the control panel. The active control source can be changed with the programmable push button b2 (see chapter
7.6). The motor can be started, stopped and the direction of rotation can be changed from the active control source.
7.11.1 Control source change from I/O terminals to the panel
After changing the control source the motor is
stopped. The direction of rotation remains the
same as with I/O control.
If the Start button is pushed at the same time as the programmable pushbutton B2, the Run state, direction of rotation and reference value are copied from the I/O terminals to the panel.
7.11.2 Control source change from panel to I/O
After changing the control source, the I/O terminals determine the run state, direction of rotation and reference value.
If the motor potentiometer is used in the application, the panel reference value can be copied as the motor potentiometer reference
by pushing the start button at the same time as the programmable push button B2. The
motor potentiometer function mode must be
“resetting at stop state” (Local/Remote Application: param. 1. 5 =4, Multi-purpose
Application : param. 1. 5 = 9).
HV9000 Page 61 (78)
8 STARTUP
8.1 Safety precautions
Before startup, observe the following warnings and instructions:
A
4
1
2
3
4
A
I
.
5
6
Internal components and circuit boards (except the isolated I/O terminals) are at line potential when the HV9000 drive is connected to the utility. This voltage is extremely dangerous and may cause death or severe injury if you come in contact with it.
When the HV9000 drive is connected to the utility, the motor connections U, V, W and DC-link / brake resistor connections -,+ are live even if the motor is not running.
Do not make any connections when the HV9000 drive is connected to the utility line.
After disconnecting the utility, wait until the cooling fan on the unit stops and the indicators in the panel are turned off (if no panel check the indicators on the cover). Wait at least 5 minutes before doing any work on the HV9000 drive connections. Do not open cover before this time has run out.
The control I/O terminals are isolated from the utility potential but the relay outputs and other I/O:s (if jumper X4 is in the OFF position, see fig. 6.2.2-l) may have dangerous external voltages connected even if the power is off from the HV9000 drive.
Before connecting the utility make sure that the cover of the HV9000 drive is closed.
8.2 Sequence of operation
1 Read and follow the safety precautions
2 After installation ensure that the:
- Drive and motor are connected to ground.
- Utility and motor cables are in accordance with the installation and connection instructions (chapter 6.1).
- Control cables are located as far as possible from the power cables (table 6.1.3-l), shields of the control cables are connected to the protective ground and wires do not have contact with any electrical components in the HV9000.
- The common input of digital input groups is connected to +24 V or ground of the l/O-terminal or external supply (See 6.2.3)
Paae 62 (78)
3 Check the quantity and quality of the cooling air (chapters 5.1 and 5.2).
4 Check that moisture has not condensed inside the HV9000 drive.
5 Check that all Start/Stop switches connected to the l/O terminals are in the Stop state.
6 Connect the HV9000 to the utility and switch the power ON.
7 Ensure that the parameters of the Group 1 match the application.
Set the following parameters to match the motor nameplate:
- nominal voltage of the motor
- nominal frequency of the motor
- nominal speed of the motor
- nominal current of the motor
- supply voltage
Look up the values from the nameplate of the motor.
8 Start-up test without motor
Perform either test A or B: A B Control from the I/O terminals:
turn Start/Stop switch to ON position
change the frequency reference check from the Monitoring page of the control panel that the
output frequency follows the frequency reference turn Start&top switch to OFF position
Control from the Control Panel:
change control from the I/O terminals to the control panel with the programmable button 82, see chapter 7.6.
push the Start button go to the Reference Page and change the frequency reference
with the buttons , see chapter 7.5
go to the Monitoring Page and check that the output frequency follows the reference, see chapter 7.3.
push the Stop button
9 If possible, make a start-up test with a motor which is not connected to the process.
If the inverter has to be tested on a motor connected to the process, ensure it is safe to be powered up. Inform all possible co-workers about the tests.
- switch the utility power OFF and wait until the HV9000 has powered down according to chapter 8.1/ point 4
HV9000
-P
Page 63 (78)
- connect the motor cable to the motor and the power terminals of the HV9000
- check that all start/stop switches connected to the I/O terminals are in the OFF state
- switch the utility power ON
- repeat test A or B of the test #8.
10 Connect the motor to the process (if the previous tests were done without the process)
- ensure it is safe to power up
- inform all possible co-workers about the tests.
- repeat test A or B of the test #8.
Page 64 (78)
Fault Tracing
HV9000
9 FAULT TRACING
When a fault trip occurs, the fault indicator is illuminated and the fault code and its description are displayed. The fault can be cleared with the Reset button or via an
I/O terminal. The faults are stored to the fault history from where they can be viewed (see chapter 7.8). The fault codes
are explained in table 9-1.
Fault codes
Fault Possible Cause
Fl Overcurrent
HV9000 frequency converter has measured too high a current (>4’ln) in the motor output:
- sudden heavy load increase
- short circuit in the motor cables
- unsuitable motor
F2
Overvoltage
The voltage of the internal DC-link of the HV9000 frequency converter has exceeded the nominal voltage by 35%
- deceleration time is too fast
high overvoltage spikes at utility
F3
Ground fault Current measurement detected that
the sum of the motor phase current is not zero
- insulation failure in the motor or the
cables
F4 lnverter fault HV9000 frequency converter has
detected faulty operation in the gate drivers or IGBT bridge
- interference fault
- component failure
F5
Charging switch Charging switch open when START
command active
- interference fault
-component failure
F9 Undervoltage
)C-bus voltage has gone below 55% of the nomlnal voltage
mast common reason IS failure of the utility supply internal failure of the HV9000 frequency converter can also cause an undervoltaqe trip
Input line suoervislon
Input line phase is missing
Fll Output phase
Current measurement has detected
supervision
that there is no curent in one motor phase
Check motor cables
F12
Brake chopper brake resistor not installed Check brake resistor supervision - brake resistor broken
If resistor is OK the chopper is broken.
- brake chopper broken
Contact your Cutler-Hammer distributor
F13
HV9000 Temperature of heat sink below
undertemperature -10°C
Checking
Check loading Check motor size Check cables
Adjust the deceleration time
Check the motor cables
Reset the fault and restart again. If the faul occurs again contact your Cutler-Hammer distributor.
Reset the fault and restart again. If the faul occurs again contact your Cutler-Hammer
distributor.
In case of temporary supply voltage break, reset the fault and start again.
Check utility input. If utility supply IS correct an internal failure has occurred. Contact your Cutler-Hammer distributor.
Check the utiltly connection
HV9000
Fault Tracing
Page 65 (78)
Fault
HV9000 overtemperature
Motor stalled Motor
overtemperature
Motor underload
Analog input
hardware fault Option boad
identification
1 OV voltage
reference 24v supply
EEPROM checksum fault
Microprocessor watchdog
Temperature of heat sink over 75°C
The motor stall protection
has tripped
The HV9000 frequency drive motor temperature model has detected motor overheat
-motor is overloaded The motor underload protection has
tripped Component failure on control board
Rezing of the option board has
+iOV reference shorted on control board or option board
+24V supply shorted on control board or option board
Parameter restoring error
- interference fault
- component failure
- interference fault
-component failure
Checking
Check the cooling air flow Check that the heat sink is not dirty Check ambient temperature Check that the switching frequency is not too high compared with ambient temperature and motor load
Check the motor Decrease motor load.
Check the temperature model parameters if the motor was not overheated
On resetting this fault the drive will automatically load the parameter default settings. Check all parameter settings after reset. If the the fault occurs again contact your Cutler-Hammer distributor
Reset the fault and restart. If the fault occurs again contact your Cutler-Hammer distributor
F26
t
F29
communication
The connection between panel and the HV9000 frequency drive is not
board has detected increase of the
Check the thermistor connection If there are no thermistors, make sure the
F36
Analog input I,, < 4mA (signal range selected 4­20mA)
The analog input current L,, is below 4mA
- signal source has failed
- control cable is broken
Check the current loop circuitry
F41
I I
External fault An external fault has been detected Check the external fault source
at the digital input I
Page 66 (78)
Basic Application
HV9000
10 BASIC APPLICATION
10.1 General
The Basic Application is the default setting as Parameters are explained in chapter 10.4. The
delivered from the factory. Control I/O signals function of motor thermal and stall protection of the Basic application are fixed (not in the Basic Application is explained in chapter
programmable) and it only has parameter 10.5. Group 1.
10.2 Control Connections
* NOTE! Remember to connect the CMA
and CMB inputs.
Reference potentiometer Terminal
Signal Description
5
- 1
+l O”,B,
Reference output
Voltage for a potentiometer, etc.
2 vi,+
Analog input, voltage
Frequency reference activated if
--­range 0-l 0 V DC
terminals 14 and 15 open and
L----- 3 GND l/Oground
parameter 1 ,17 = 0 (default value) Ground for reference and controls
4
lin+
Analog input, current
Frequency reference activated If
5
II”-
range O-20 mA
terminals 14 and 15 closed, or ope and Darameter 1.17 = 1
_ i 6 +24V Control voltage output ,
Voltage for switches, etc. max. 0.1 P
j
7
GND
I/O ground
c 6 DlAl Start forward
Ground for reference and controls
Contact closed = start forward
Contact closed = start reverse
i READY 1
k a-f-­l
L&‘-I
FAULT
220 ----­“AC ___
0
-
M&X
\-
Figure 1.2- 1 Contra/connection
example.
HV9000
10.3 Control Signal Logic
Basic Application
Page 67 (78)
Figure 10.3.-l shows the logic of the I/O control signals and push buttons.
BASIC PARAMETERS
Group 1
1.5 Multi-step speed reference 1
I
Panel reference Start/Stop buttons
RST
klulti-step speed select 1
-.-.-.-.-.-.-.-.-._
vlulti-step speed select 2
-.-.-.-.-.-.-._.-.-.
l7 ,
!
frequency
0
reference
+
Internal
i
Internal reverse
V
I
Internal ,,.
-4 I
ram reser
Iault reset input
ixternal fault input
-.-
= control
- line
CHOIZKOO
Figure 10.3- 1 Control signal logic
If Start forward and Start reverse are both activated when the utility line is connected to the HV9000
then Start forward will be selected for the direction.
If Start forward and Start reverse are both activated when the control source is changed from
the panel to the l/O-terminals then Start forward will be selected for the direction.
If both directions are selected the first selected direction has higher priority than the second
selected.
Page 68 (78)
Basic Application
HV9000
10.4 Parameters, Group 1
I
Tab/e 10.4-I Group 7 basicparameters
Note!
sea
1’ = Parameter value can be changed only * If 1. 2 zmotor synchr. speed, check suitability
when the HV9000 is stopped.
of motor and drive system.
** Default value for a four pole motor and a
nominal size HV9000.
HV9000
Basic Application
Page 69 (78)
10.4.1 Descriptions
1.1,1.2 Minimum/maximum frequency
1.3,1.4
Defines the frequency limits of the HV9000. Default maximum value for parameters 1. 1 and 1. 2 is 120 Hz. By setting 1.2 =
120 Hz in Stop state (RUN indicator not lit) and pressing the Enter key the maximum value of parameters 1. 1 and 1. 2 is changed to 500 Hz. At the same
time the panel reference display resolution is changed from
0.01 Hz to 0.1 Hz.
The max. value is changed from 500 Hz to 120 Hz when parameter 1.2 is set to
119 Hz in Stop state and the Enter key is pressed. Acceleration time, deceleration time :
1.51.6
These limits correspond to the time required for the output frequency to accelerate from the set minimum frequency (par. I. I) to the set maximum frequency (par. 1.2).
Multi-step speed reference 1, Multi-step speed reference 2: Parameter values are limited between minimum and maximum frequency.
AflW
Fief lin
. - - - - - - - - - - - - -
Figure 10.4. l-l Example of Multi-step speed references.
1.7
Current limit
1.8
This parameter determines the maximum motor current that the HV9000 will
provide short term. V/Hz ratio selection
t
Linear: The voltage of the motor changes linearly with the frequency from
0
0 Hz to the nominal frequency of the motor. The nominal voltage of the motor is supplied at this frequency. See figure 10.4.1-2.
Linear V/Hz ratio should be used in constant torque applications.
This default setting should be used if there is no special requirement for
another setting.
Page 70 (78)
Basic Application
HV9000
Squared: The voltage of the motor changes following a squared curve from 0 Hz
1
to the nominal frequency of the motor. The Nominal voltage of the motor is supplied at this frequency. See figure 10.4.1-2.
The motor runs undermagnetized below the nominal frequency and it produces less torque and electromechanical noise. A squared V/Hz ratio can be used in applications where the torque demand from the load is proportional to the square of the speed, e.g. in centrifugal fans and pumps.
Figure 10.4.1-Z Linear andsquared V/Hz curves.
1.9
V/Hz optimization Automatic The voltage to the motor changes automatically which allows the
torque
motor to produce sufficient torque to start and run at low frequencies.
boost
The voltage increase depends on the motor type and
horsepower.Automatic torque boost can be used in applications where starting torque due to starting friction is high, e.g. in conveyors.
NOTE!
In high torque - low speed applications - it is likely the motor will overheat.
A
!
If the motor has to run for a prolonged time under these conditions,
special attention must be paid to cooling the motor. Use external cooling
for the motor if the operating temperature rise is too high.
1.10
Nominal voltage of the motor
Find the rated voltage V, from the nameplate of the motor.
Note!
If the nominal motor voltage is lower than the supply voltage, check
that the insulation level of the motor is adequate.
1.11
Nominal frequency of the motor Find the value f, from the nameplate of the motor.
1.12
Nominal speed of the motor Find the value n, from the nameplate of the motor.
1.13
Nominal current of the motor Find the value In from the nameplate of the motor. The internal motor protection
function uses this value as a reference value.
HV9000
Basic Application
Page 71(78)
1.14
1.15
1.16
1.17
1.18
Supply voltage
Set parameter value according to the nominal voltage of the supply. Values are predefined for voltage codes 2,4, 5 and 6 see table 10.4-l.
Application package lock The application package lock can be opened by setting the the value of the parameter
1.15 to 0. It will then be possible to enter the parameter group 0 from parameter 1 .l by pressing arrow down button (see figure 11-l). The number of the Application can be selected from the table 11-l and it is selected by the value of parameter 0.1. After this, the new Application is in use and its parameters will be found in the HVReady Application manual.
Parameter value lock Defines access to the changes of the parameter values:
0 = parameter value changes enabled 1 = parameter value changes disabled
Basic frequency reference selection
0
Analog voltage reference from terminals 2-3, e.g. a potentiometer
1 Analog current reference trom terminals 4-5, e.g. a transducer.
2 Panel reference is the reference set from the Reference Page (REF), see
chapter 7.5. Analog input I,, range Defines the minimum value of the Analog input Iin signal (terminals 4,5).
Page 72 (78)
Basic Application
HV9000
10.5 Motor protection functions in the Basic Application
10.5.1 Motor thermal protection
Motor thermal protection protects the motor from overheating. In the Basic application, Motor thermal protection uses constant settings and always causes a fault trip if the motor is overheated. To switch off the protection or to change the settings, see HVReady application manual.
Your HV9000 is capable of supplying higher than nominal current to the motor. If the load requires this high current there is a risk that motor will be thermally overloaded. This is true especially at low
frequencies, as the cooling effect and
thermal capacity of the motor are reduced. The motor thermal protection is based on a calculated model which uses the output current of the drive to determine the load on the motor.
The thermal current IT specifies the load current above which the motor is overloaded. See figure 10.5.1-l. If the motor current is above the curve, the motor temperature is increasing.
Figure 10.5. l- 1 Motor thermal current I, curve.
CAUTION! The calculated mode/ does not protect the motor if the airflow to the
motor is reduced by an air intake grill that is blocked
10.5.2 Motor Stall warning
In the Basic application, motor stall protection gives a warning of a short time overload of
the motor e.a. a stalled shaft. The reaction time of this stall orotection is shorter than the
n
motor thermal protection time. The stall state is defined’ by Stall Current and Stall
Frequency.
1
Both parameters have constant values. See figure 10.5.2-l. If the current is
t’
higher than the set limit and the output is lower than the set limit the stall state is true.lf the stall state lasts longer than 15 s the stall warning is given on the display. To change the stall warning to a
fault trip or to change the protection
settings, see the HVReady application manual
25HZ
I
Figure 10.5.2-I Stall state.
HV9000
System parameter group 0
Page 73 (78)
11 System parameter group 0
When the application package lock is open
(par. 1.15 = 0) the system parameter group 0 can be accessed. Parameter group 0 can be entered from parameter 1 .l by the pressing arrow down button. The parameters of group 0 are shown in table ii-l.
Figure II- 1 Group 0.
11 .l Parameter table
Number Parameter
0.1
Application selection
Range
1-7
Description
1 = Basic Application 2 = Standard Application 3 = Local / Remote Control Application 4 = Multi-step Speed Application 5 = PI-control Application 6 = Multi-purpose Control Application 7 = Pump and fan control Application
Page
74
0.2
Parameter loading
O-5
0 = Loading ready / Select loading
1 = Load default settings 2 = Read up parameters to user’s set 3 = Load down user’s set parameters 4 = Read parameters up to the panel
(possible only with the graphic panel)
5 = Load down parameters from the panel
(possible only with graphic panel)
75
0.3 Language selection
O-5
L
-.. ^
/aDIe It- 7
^ ^
system parameters, tiroup u.
0 = English 1 = German 2 = Swedish 3 = Finnish 4 = Italian 5 = French 6 = Spanish
75
11.2 Parameter descriptions
0.1 Application selection
With this parameter the Application type can be selected. The default setting is the Basic Application. Applications are described in chapter 12.
Page 74 (78) System parameter group 0
HV9000
0.2 Parameter loading
With this parameter it is possible to do several types of parameter load operations. After the operation is completed this parameter value changes automatically to 0 (loading ready).
0 Loading ready / Select loading
Loading operation has been completed and the drive is ready to operate.
1 Load default settings
By setting the value of parameter 0.2 to 1 and then pressing the Enter-button the parameter default values for the application selected with parameter 0.1 are loaded. Use this when you want to restore the default set.
2 Read up parameters to User’s set
Set the value of parameter 0.2 to 2 and press the Enter-button to store the active parameter values, set A, in back-up memory as the User’s parameter value set B. The parameter values can later be reloaded as the active set by setting pa-
rameter 0.2 to 3 and pressing the Enter button. See Figure
3 Load down user’s set parameters
Set the value of parameter 0.2 to 3 and press the Enter-button to reload the users’ set B as the active set A. The User’s set is intended to function as a backup in the case you have a good set of parameters that for some reason is
lost or changed.
See Figure 11-2
4 Read parameters up to the panel (possible only with the graphic panel).
Copies the active parameter set A to the memory in the graphical panel
5 Load down parameters from the panel (possible only with the graphic panel).
Copies the parameter set in the graphical panel as the active parameter set A
NOTE! The panel read and load oDerations work onlv on drives of the same
size.
0.3 Language selection
his parameter selects the language of the text displayed on the panel.
igure 11-2
Relation of the various parameter sets
HV9000
HVReady application package
12 HVReady application package
12.1 Application Selection
Page 75 (78)
To use one of the HVReady applications, first open the Application package lock (parameter
1.15). Group 0 then comes visible (see figure 11-l). Changing the value of parameter 0.1
changes the active application. See table 11-l. Applications are presented in sections 12.2 - 12.7 and in more detail in the following,
separate HVReady application manual.
12.2 Standard Application
The Standard Application has the same l/O signals and same Control logic as the Basic application.
Digital input DIA3 and all outputs are freely programmable.
Other additonal functions:
- Programmable V/Hz curve and switching frequency
- Autorestart function
- Motor Thermal and Stall protection fully
programmable
- Motor Underload protection
- Unused analog input functions
- Programmable StarVStop and Reverse signal logic
- Reference scaling
- One frequency limit supervision
- Second set of ramps and choice of linear or S curve
12.4 Multi-step Speed Application
- Programmable start and stop functions
- DC-braking at stop
- One prohibit frequency lockout range
- Programmable V/Hz curve and switching frequency
- Autorestart function
- Motor Thermal and Stall protection off / warning /fault programming
The Multi-step Speed Control Application can be used where fixed speed references are required. 9 different speeds can be
programmed: one basic speed, 7 multi-step
speeds and one jogging speed. The speed
steps are selected with digital signals DIB4,
DIB5 and DIB6. If the jogging speed is used DIA3 can be programmed for jogging speed
select
12.3 Local/Remote Application
The basic speed reference can be either voltage or current signal via analog input terminals (2/3 or 4/5). All outputs are freely
programmable. Other additonal functions:
Utilizing the Local/Remote Control Application the use of two different control and frequency reference sources is programmable. The active control source is selected with digital input DIB6. All outputs are freely programmable.
Other additonal functions:
- Programmable StarVstop and Reverse
signal logic
- Analog input signal range selection
- Two frequency in band limit indications
-Torque in band limit indication
- Reference in band limit indication
- Second set of ramps and choice of linear
- Programmable Start/stop and Reverse signal logic
-Analog input signal range selection
-Two frequency in band limit indications
-Torque in band limit indication Reference in band limit indication
- Second set of ramps and choice of linear or S curve
- DC-braking at start and stop
-Three prohibit frequency lockout ranges
- Programmable V/Hz curve and switching frequency
- Autorestart function
- Motor Thermal and Stall protection fully
or S curve
programmable
- DC-braking at start and stop
- Motor Underload protection
-Three prohibit frequency lockout ranges
- Unused analog input functions
Page 76 (78)
HVReady application package HV9000
12.5 PI-control Application
In the PI-control Application, there are two I/
O-terminal control sources. Source A is a
PI-controller and source B is a direct
frequency reference. The control source is
selected with the DIB6 input.
Other additonal functions:
The PI-controller reference can be selected from the analog inputs, motor potentiometer,
or panel reference. The actual value can be selected from the analog inputs or from a
mathematical function acting on the analog
inputs. The direct frequency reference can be used for control without the PI-controller. The frequency reference can be selected from the analog inputs or the panel
reference.
- Programmable Start/stop and Reverse signal logic
- Analog input signal range selection
-Two frequency in band limit indications
-Torque in band limit indication
- Reference in band limit indication
- Second set of ramps and choice of linear
or S-curve
All outputs are freely programmable. Other additonal functions:
- DC-braking at start and stop
- Three prohibit frequency lockout ranges
- Programmable V/Hz curve and switching frequency
- Autorestart function
- Motor Thermal and Stall protection fully
programmable
- Motor Underload protection
- Free analog input functions
12.7 Pump and Fan Control Application
- Programmable Start/stop and Reverse signal logic
-Analog input signal range selection
-Two frequency in band limit indications
-Torque in band limit indication
- Reference in band limit indication
- Second set of ramps and choice of linear or S curve
The Pump and Fan Control Application can be used to control one variable speed drive and O-3 auxiliary drives. The PI-controller of the frequency converter controls the speed of the variable speed drive and gives control signals to Start and Stop auxiliary drives to control the total flow.
- DC-braking at start and stop
The application has two control sources on
- Three prohibit frequency lockout ranges
I/O terminal. Source A is Pump and fan
- Programmable V/Hz curve and switching
control and source B is direct frequency
frequency
reference. The control source is selected
- Autorestart function
with DIB6 input.
- Motor Thermal and Stall protection fully programmable
All outputs are freely programmable.
- Motor Underload protection
Other additonal functions:
12.6 Multi-purpose Control Application
In the Multi-purpose Control Application, the frequency reference can be selected from the analog inputs, joystick control, motor potentiometer, or a mathematical function of the analog inputs. Multi-step speeds and jog speed can also be selected if the digital inputs are programmed for these functions
Digital inputs DIAI and DIA2 are reserved
for Start/stop logic. Digital inputs DIA3 -
DIB6 are programmable for multi-step speed select, jog speed select, motor potentiometer, external fault, ramp time select, ramp prohibit, fault reset and DC-
brake command function. All outputs are freely programmable.
- Programmable Start/stop and reverse signal logic
- Analog input signal range selection
-Two frequency in band limit indications
-Torque in band limit indication
- Reference in band limit indication
- Second set of ramps and choice of linear or S curve
- DC-braking at start and stop
- Three prohibit frequency lockout ranges
- Programmable V/Hz curve and switching frequency
- Autorestarl function
- Motor Thermal and Stall protection fully
programmable
- Motor Underload protection
HV9000
Options
Page 77 (78)
13 Options
13.1 External filters
13.5 HVGraphic control panel
Information of HV9000 external input and output filters (RFI, dV/dT, and Sinusoidal­filters) can be found in their separate manuals.
The HVGraphic control panel can be used inplace of the standard 3 line LCD panel. It provides:
13.2 Dynamic braking
Effective motor braking and short deceleration times are possible by using an
external or internal braking chopper with an
external brake resistor. The internal braking chopper is assembled
in the factory (available in certain models). It
has the same continuous current
specification as the unit itself.
Select the correct brake resistor to get the
desired braking effect. More information can
be found in the separate brake manual.
- parameters, monitored items etc. in text format
- 3 monitored items at the same time in display
- one monitored item can be shown in increased text size with a graph bar
- The selected parameter value is shown on a graph bar
- 3 monitored items can be shown on the graphical trend display
- the parameters of the frequency converter can be uploaded to the panel and then downloaded to another inverter.
13.3 I/O- expander board The available I/O can be increased by using
the I/O- expander boards. I/O-expander
boards can be installed in the option board position inside the open, protected, NEMA 1 and NEMA 12 HV9000 models. For the Compact NEMA 1 model the board needs to be installed in a separate l/O-expander box.
More information can be found in the l/O­expander board manuals.
13.4 Communication
More information can be found in the
HVGraphicTM Panel manual.
13.6 HVDRIVE HVDrive is the PC based tool for control
and monitoring of the HV9000. With HVDrive:
HV9000 frequency converters can be connected to DeviceNet, Modbus RTU,
InterbusS, Profibus-DP and Lonworks
systems by using the fieldbus option board. The fieldbus board can be installed in the
option board position inside the open,
protected, NEMA 1 and NEMA 12 HWOOO models, For the compact NEMA 1 model the board needs to be installed in a separate I/ O-expander box.
More information can be found in the
separate communication manuals.
- parameters can be loaded from the HV9000, changed, saved to a file or loaded back to the HV9000 - parameters can be printed to paper or to a file
- references can be set
- the motor can be started and stopped
- signals can be examined in graphical form
- actual values can be displayed
The HV9000 can be connected to a PC with a special RS232-cable, catalog
number HVDRIVECABLE. The same cable can be used for downloading specialized applications to the HV9000.
13.7 Operator panel door installation kit
An adapter kit is available to mount the operator display panel on an enclosure door.
Page 78 (78)
13.8 Protected chassis cable cover for 100-150 HP open panel units
This optional cable cover provides a protected chassis capability equivalent to
IP20.
Notes:
HV9000 Page O-1
HV9000 HVReady APPLICATION MANUAL
CONTENTS
A
B C
General.. ............................................ O-2
Application selection ....................... O-2
Restoring default values of
application parameters.. .................. O-2
Language selection ......................... O-2
Standard Control Application .......... l-1
Local/Remote Control Application 2-1
Multi-step Speed Application.. ...... ..3- 1
PI-control Application ..................... .4-i
Multi-purpose Application ............. ..5- 1
Pump and fan control Application ..6- 1
Page O-2
General
HV9000
A General
This manual provides you with the information
Each application is described in its own
needed to apply these applications.
chapter. Section B tells how to select the application.
B Application selection
If the Basic Application is in use, first open the
To change from one application to another,
application package lock (parameter 1 .15 = 0)
simply change the value of parameter 0.1 to
Group 0 appears. By changing the value of
that of the application desired: see table B-l. parameter 0.1 a different application can be selected. See table B-l.
Number Parameter
0. 1
Application
Range
l-7
Description
1 = Basic Application
2 = Standard Application
3 = Local / Remote Control Application 4 = Multi-step Speed Application 5 = Pi-control Application 6 = Multi-purpose Control Application 7 = Pump and Fan Control Application
_ . . ^ _ . . . . .
lame u- 7 ,4pp/rcaaon selecrlon paramerers.
C Restoring default values of
application parameters
Besides the parameter group 1, the
Default values of the parameters of the applications also have parameter groups 2 - applications 1 to 7 can be restored by selecting 8 available (see fioure B-l).
the same application again with parameter 0.1
_
Parameters of the groups sequentially follow
or by setting the value-of parameter 0.2 to 1.
each other and changing from the last
See User’s manual chapter 12. parameter of one group to the first parameter
If parameter group 0 is not visible, make it of the next group or vice versa is done simply
visible as follows:
by pushingihe arrow up/arrow down buttons.
I
Groups 2-8
I
I
Group 0
I
1.
2.
D
If parameter lock is set on, open the lock, parameter 1. 16, by setting the value of the parameter to 0.
If parameter conceal is set on, open the conceal parameter 1. 15, by setting the value of the parameter to 0. Group 0 becomes visible.
Language selection
The language of the text shown on the operator’s panel can be chosen with parameter
0.3. See HV9000 User’s Manual, chapter 11.
Figure B- 1 Parameter Groups.
HV9000
Standard Application Page l-l
STANDARD CONTROL APPLICATION
(par. 0.1 = 2)
q
CONTENTS
1 Standard Application.. ....................... l-1
1.1 General.. ....................................... l-2
1.2 Control I/O .................................... l-2
1.3 Control signal logic ....................... l-3
1.4 Parameters Group 1 .................... l-4
1.4.1 Parameter table.. ................. l-4
1.4.2 Description of Group1 par ... l-5
1.5 Special parameters, Groups 2-8 l-8
1.51 Parameter tables ................ l-8
1.52 Description of Groups. ..... 1-12
Page l-2 Standard Application
HWOOO
1 STANDARD APPLICATION
1.1
General
The Standard application has the same I/O setting the value of parameter 0. 1 to 2. signals and same Control logic as the Basic
Basic connections of inputs and outputs are application. Digital input DIA3 and all outputs shown in the figure 1.2-l. The control signal are programmable. logic is shown in the figure 1.3-i.
The Standard Application can be selected by
Programming of I/O terminals-is explained
in chapter 1.5.
1.2 Control I/O
Reference potentiometer
*
--
L---
I----
---
I----_
I I
p____
I
I
r
L--+?I-
I
I- I
--+-
+--I_
L
r-
READY 1
I- -B- -I-
I I
RUN
L
I--@__
FAULT
220 - - - -
VAC ___ _
MZX.
0
\-
7
w_
Terminal / Signal 1 Description
Figure 1.2-I Default I/O configuration and connection example of the Standard Application.
1.3 Control signal logic
HMO00 Standard Application
Page 1-3
BASIC PARAMETERS
Group 1
I
lin+
o-
DIBd
e-
DIB!
e-
DlAl
s
ej) !.A
i
Multi-step speed sel. 1
-.-.-.-.-.-.-.-.-.-.-.- j j
i
Multi-step spaed sd. 2
i
i
-.-.-.-.-._.___.~~~-.-
- i
Start forward ~programmatne)
Starvstql
Q !
and reverse
Start reverse
logic
Reverse
~programmaDle)
reference
k
Internal start/stop
*
Internal
reverse
k
Internal
DIA;
*
fault reset
DIB6 Fault reset input
0-c
21
b
D’A3 External fault input
(programmable)
*
-
-.-.
=wlii
- =sgnallire
CH012K01
-.
Figure 1.3-1 Control signal logic of the Standard Application
Page l-4
Standard Application HV9000
1.4 PARAMETERS, GROUP 1
1.4.1 Parameter table
Tab/e 1.4- 1 Group 1 basic parameters.
*
Note!m=
Parameter value can be changed only
If 1. 2 > motor synchr. speed, check suitability
for motor and drive system.
when the drive is stopped.
Selecting 120 Hz/500 Hz range see page l-5.
** Default value for a four pole motor
and a nominal size drive.
***Up to MIO. Bigger classes case by case
HV9000
Standard Application
1.4.2 Description of Group 1 parameters Minimum/maximum frequency 1.1,1.2
Defines the frequency limits of the drive. The default maximum value for parameters 1. 1 and 1. 2 is 120 Hz. By setting the
value of the parameter 1.2 to 120 Hz when the drive is stopped (RUN indicator not lit) parameters 1. 1 and 1.2 are changed to 500 Hz. At the same time the resolution of the display panel is changed from 0.01 Hz to 0.1 Hz.
Changing the max. value from 500 Hz to 120 Hz in done by setting parameter 1.2 to 119 Hz while the drive is stopped.
1.3,1.4 Acceleration timel, deceleration time 1:
These limits correspond to the time required for the output frequency to accelerate from the set minimum frequency (par. 1. 1) to the set maximum frequency (par. 1.2).
Ref. Iin
f’
Par. 1.6
DIB5
R”” --­stop
ChWWce
1.5,l.B
Multi-step speed reference 1, Multi-step speed reference 2:
Figure 1.4-1 Example of Multi-step speed references.
1.7
Parameter values are automatically limited between minimum and maximum frequency ( par 1.1, 1.2).
Current limit This parameter determines the maximum motor current that the HV9000 will provide
short term.
1.8 V/Hz ratio selection
Page l-5
1
Linear: The voltage of the motor changes linearly with the frequency in the
0
constant flux area from 0 Hz to the field weakening point (par. 6. 3) where a constant voltage (nominal value) is supplied to the motor. See figure 1.4-2.
A linear V/Hz ratio should be used in constant torque applications.
Page l-6
Standard Application HV9000
This default setting should be used if there is no special requirement for another setting.
Squared: The voltage of the motor changes following a squared curve form
with the frequency in the area from 0 Hz to the field weakening
1
point (par. 6. 3) where the nominal voltage is also supplied to
the motor. See figure 1.4-2. The motor runs undermagnetized below the field weakening point
and produces less torque and electromechanical noise. A squared V/Hz ratio can be used in applications where the torque demand of the
V”
u WI
Default: Nominal
Field weakening point
Default: Nominal frequency of the motor
_j WI
load is proportional to the square of the speed, e.g. in centrifugal fans and pumps.
Figure 1.4-2 Linearand squared V/Hzcurves.
Programm.The V/Hz curve can be programmed with three different points.
Y
Parameter
6.4
Parameter 6.6
Default 10% Parameter 6.7
Default 1.3 %
/ i
I
1 Default: nominal frequency
1 of the motor
/
Parameter 6.5 Parameter 6.3 [Hz] ’
1
(Default 5 Hz)
V/Hz curve The parameters for programming are explained in chapter 1.5.2.
A programmable V/Hz curve can be used if the standard settings
2
do not satisfy the needs of the application. See figure 1.4-3.
Figure 1.4-3 Programmable V/Hz curve.
1.9 V/Hz optimization Automatic The voltage to the motor changes automatically which allows the
torque motor to produce enough torque to start and run at low frequencies.
The boost voltage increase depends on the motor type and horsepower.
HV9000
Standard Application
Page l-7
Automatic torque boost can be used in applications where starting torque due to starting friction is high, e.g. in conveyors.
1.10
1.11
1.12
1.13
1.14
1.15
1.16
1.17
NOTE! In high torque - low speed applications - it is likely that the motor will
overheat.
A
If the motor has to run for a prolonged time under these conditions, special attention must be paid to cooling the motor. Use external cooling for the motor if the operating temperature rise is too high.
Nominal voltage of the motor
Find this value from the nameplate of the motor.
This parameter sets the voltage at the field weakening point, parameter 6.4, to 100% XVnmoW
Note!
If the nominal motor voltage is lower than the supply voltage, check that the insulation level of the motor is adequate.
Nominal frequency of the motor Find the nominal frequency f, from the nameplate of the motor.
This parameter sets the field weakening point, parameter 6. 3, to the same value.
Nominal speed of the motor Find this value n,, from the nameplate of the motor. Nominal current of the motor Find the value In from the nameplate of the motor.
The internal motor protection function uses this value as a reference value. Supply voltage
Set parameter value according to the nominal voltage of the supply. Values are predefined for voltage codes 2,4,5, and 6. See table 1.4-l.
Parameter conceal
Defines which parameter groups are available:
0 = all groups are visible
1 = only group 1 is visible Parameter value lock Permits access for changing the parameter values:
0 = parameter value changes enabled
1 = parameter value changes disabled
Basic frequency reference selection
0 = Analog voltage reference from terminals 2-3, e.g. a potentiometer
1 = Analog current reference from terminals 4-5, e.g. a transducer.
2 = Panel reference is the reference set from the Reference Page (REF),
see chapter 7.5.
Page l-8
Standard Application
1.5 SPECIAL PARAMETERS, GROUPS 2-9
1.51 Parameter tables
HV9000
Group 2, Input signal parameters
zz Parameter
I Range
-
StarKStop logic selection
2.2 DIA3 function (terminal 10)
2.3 Reference offset O--l for current
input
I
2.4
Reference scaling, minimumvalue
+par. 2.5
2.5 Reference scaling,
0-fin,,
maximum value
2.6
Reference invert
I
(rl
2.7
Reference filtertime 1 0.00-10.00s
pag
-
l-l
l-l
l-l
l-l
l-l
­l-l
l-1,
-
Default 0 Custom Description
w
0 = Not used 1 = Ext. fault, closing contact 2 = External fault, opening contact 3 = Run enable 4 = Acc./dec. time selection 5 = Reverse (if par. 2.1 = 3)
O=@-20mA 1=4_20mA
Selects the frequency that corresponds to the minimum reference signal
Selects the frequency that
corresponds to the maximum
reference signal 0 = Scaling off >O = Maximum frequency value
0 = No inversion 1 = Reference inverted
0 = No filtering
1 Hz
OHz
1 Hz
OHz
0.01s 0.10s
Group 3, Output and supervision parameters
oxk
Parameter
Default 1 Custom Description IPace
3.1 Analog output function
1
0 = Not used Scale 100%
l-15
1 = O/P frequency (&fmax) 2 = Motor speed (0-max. speed) 3 = O/P current
(o--a.oxl”Hv9)
4 = Motor torque (0-2xT,,& 5 = Motor power (o-2xP,,& 6 = Motor voltage (o-100%xV.,.,,,) 7 = DC-link volt.
10-1000 v1
0 = no filterina
Il.15
Analog output minimum
3.5 - Analog output scale
Note! m =
Parameter value can be changed only when the drive is stopped.
HV9000 Standard Application
Page l-9
Group 3, Output and supervision parameters
-
code
L
3.6
Iefault
custcm
-w
&14
Description
0 = Not used
1 = Ready
2=Run
3 = Fault
-16
4 = Fault inverted
5 = HV9000 overheat warning 6 = External fault or warning 7 = Reference fault or warning 6 = Warning 9 = Reversed 10 = Multi-step speed selected 11 =At speed 12 = Motor regulator activated 13 = Output frequency limit supen 14 = Control from I/O-terminal
As parameter3.6 -16
As parameter 3.6
-16
O=No 1 = Low limit 2 = High limit
-16
-16
As parameter3. 1 -15
As parameter 3.5
-15
‘ammeter Ggital output function
q
1
2
3
elayoutput 1 function s14
O-14
&2
1
0.1 Hi
0
0.0 Hz
).0-f,,,
par. 1.2)
3.11 l/O-expander option bow analog output function
&7
1
3
3.12 I/O-expander opbon boar< analog output scale
&lOOO%
1% 100%
Group 4, Drive control parameters
code Parameter
Step Default Custom Description Page
0.0 s
I I
0 = Linear
1-17
>O = S-curve acc.ldec. bme
I I
Acc.lDec. ramp 1 shape
4.6 Start function %l 1 0 0 = Ramp 1-17 1 = Flying start
4.7 Stop function &l 1 0 0 = Coasting 1-16
1 = Ramp
4.6 DC-braking current 0.15-l 5x 0.1 A 0.5 x lnHVg l-16
hv9 (A)
4.9 DC-braking time at Stop 0.00-250.00 s 0.01 s 0.00 s 0 = DC-brake is off 1-16
Note! fl= P
arameter value can be changed only when the drive is stopped
Page l-10
Standard Application
HV9000
Group 5, Prohibit frequency parameters
code Parameter
Range Step
Default Custom Description
Page
5.1 Prohibit frequency
fIni”_f,,
0.1 Hz O.OHz
l-19
range low limit
per. 5.2
5.2 Prohibit frequency
fnlin-fInax
0.1 Hz O.OHz 0 = no prohibit frequency range
1-19
range high limit (1.1) (1.2) (mex limit = par. 1.2)
Group 6, Motor control parameters
0 = Controller is off
Note! m = Parameter value can be changed only when the drive is stopped
Group 7, Protections
7.3 Phase supervision of c-2 the motor
7.6 Stall protection &2
Stso 1 Default 1 Custom
1
0
!
1
2
++
2
2
+I
1
2
1 I 1 I
Description 0 = No action
1 = Warning 2 = Fault, stop according per. 4.7 3 = Fault, always coasting stop
0 = No action
1 = Warning 2 = Fault, stop according per. 4.7 3 = Fault, always coasting stop
0 = No action
2 = Fault 0 = No action
2 = Fault 0 = No action
1 = Warning 2 = Fault
0 = No action
1 = Warning
2 = Fault
‘age
l-21
!
l-21
1-21
l-21
l-22
1
l-22
HV9000
Standard Application
Page l-1 1
Group 8, Autorestatl parameters
code Parameter
Range
step
Default
Custom Description Page
8.1 Automatic restart:
O-10
1
0 0 = no action l-23
number of tries
I 8.2 I Automatic
restart: multi- 1-6000s
1s 30s
l-23
attempt max. trial time
1
1 1 1
I /
8. 3 Automatic restart: start function
Table 1.51 Special parameters, Groups 2-8.
Page 1-12
Standard Application
1.52 Description of Group 2-9 parameters
2.1
Start/Stop logic selection
HV9000
0 DlAl : closed contact = start forward
DIA2: closed contact = start reverse, See figure 1.5-l.
Figure I. 5 1
Start forward/Start reverse
a
The first selected direction has the highest priority
0
When DIAl contact opens, the direction of rotation starts to change
0
If Stat-l forward (DIAl) and Star-l reverse (DIA2) signals are active simultaneously, the Start forward signal (DIAl) has priority.
1 DlAl : closed contact = start open contact = stop
DIA2: closed contact = reverse open contact = forward See figure 1.5-2.
HV9000
Standard Application
Paae 1-13
2: DIAl : closed contact = start
open contact = stop
DIA2: closed contact = start enabled open contact = start disabled
3: 3-wire connection (pulse control):
DIAI : closed contact = start pulse DIA2: closed contact = stop pulse (DIA3 can be programmed for reverse command) See figure 1.5-3.
Figure 1.53
Startpulse/Stop pulse
2. 2 DIA3 function
1: External fault, closing contact = Fault is shown and motor is stopped when
the contact is closed.
2: External fault, opening contact = Fault is shown and motor is stopped when
the contact is open.
3: Run enable contact open
= Start of the motor disabled
contact closed = Start of the motor enabled
4: Act. I Dee contact open
= Acceleration/Deceleration time 1 selected
time select.
contact closed = Acceleration/Deceleration time 2 selected
5: Reverse contact open
= Forward
II
Can be used for reversing if
contact closed = Reverse
parameter 2. 1 has value 3
2.3 Reference offset for current input
0: Nooffset 1: Offset 4 mA, provides supervision of zero level signal. The response to reference
fault can be programmed with the parameter 7. 1.
Page 1-14
Standard Application
HWOOO
2.4,2.5 Reference scaling, minimum
value/maximum value
Setting value limits: 0 5 par. 2. 4
spar.2.55par.1.2.
If parameter 2. 5 = 0 scaling is set off. See figures 1.54 and 1.5-5.
2.6
Reference invert Inverts reference signal:
max. ref. signal = min.set freq. min. ref. signal = max. set freq. See figure 1 A-6.
2.7
Reference filter time
Figure 1.5-4 Reference scaling.
Filters out disturbances from the incoming reference signal. A long
filtering time makes regulation
response slower. See figure 1.5-7.
f
OUtpUt
frequency
0
10 Ch012K13
Figure 7.5-5 Reference scaling,
parameter2. 5 = 0.
i t
OUtpUt
frequency
Ml” freq. par 1. 1
Figure 1.5-6
Reference invert.
Par. 2. 7
-I
1
Figure 1.5-7
Reference filtering.
3.1
Analog output function
See table “Group 3, output and
supervision parameters” on the
page l-8.
3.2
Analog output filter time
Filters the analog output signal.
See figure 1.58.
HV9000
Standard Application
Page 1-15
3.3
Analog output invert
Inverts analog output signal: max. output signal = minimum
set value
min. output signal = maximum
set value
See figure 1.5-9
3.4
3.5
Analog output minimum Defines the signal minimum to
be either 0 mA or 4 mA. See figure
1.510.
Analog output scale Scaling factor for analog output.
See figure 1.5-l 0.
Max. speed (n,xf,,Jf,)
I
%
t
Unfiltered signal
Par. 3. 2
-I
Figure 1.5-8 Analog output filtering.
Figure 1.59
Analog oofput invert.
Figure 1.510 Analog output scale.
Loading...