Cutler-Hammer Digitrip OPTIM 550, Digitrip OPTIM 750, Digitrip OPTIM 1050 Instruction For Operation And Maintenance

P
O
W
E
R
Q
U
A
L
I
T
Y
I.B. 29C891B
Effective 11/98 Supersedes I.B. 29C891A dated October 1996
Instructions for Operation and Maintenance of Digitrip OPTIM Trip Units
PROTECTION AND COORDINATION
COMMUNICATIONS SYSTEMS
E
N
E
R
G
Y
M
O
N
I
T
O
R
I
N
G
DSII/DSLII Power Circuit Breakers
SPB Systems Pow-R Circuit Breakers
Series C K, L, N and R Molded Case Circuit Breakers
I.B. 29C891B
Page iii
Effective 11/98
All possible contingencies which may arise during installation, operation or maintenance, and all details and variations of this equipment do not purport to be covered by these instructions. If further information is desired by purchaser regarding his particular installation, operation or maintenance of particular equipment, contact a Cutler-Hammer representative.
WARRANTY AND LIABILITY INFORMATION
NO WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OF MERCHANTABILITY, OR WARRANTIES ARISING FROM COURSE OF DEALING OR USAGE OF TRADE, ARE MADE REGARDING THE INFORMATION, RECOMMENDATIONS AND DESCRIPTIONS CON­TAINED HEREIN. In no event will Cutler-Hammer be responsible to the purchaser or user in contract, in tort (includ­ing negligence), strict liability or otherwise for any special, indirect, incidental or consequential damage or loss what­soever, including but not limited to damage or loss of use of equipment, plant or power system, cost of capital, loss of power, additional expenses in the use of existing power facilities, or claims against the purchaser or user by its cus­tomers resulting from the use of the information and descriptions contained herein.
I.B. 29C891B
Page iv
Effective 11/98
TABLE OF CONTENTS
Page
SECTION 1: INTRODUCTION
1-1 Common Terms...................................................................................................................................................1
1-2 Preliminary Comments and Safety Precautions..................................................................................................1
1-2.1 Safety Precautions .................................................................................................................................1
1-3 Product Overview ................................................................................................................................................2
1-4 Features and Functions.......................................................................................................................................5
1-4.1 Common Features of Digitrip OPTIM 750 and 1050 Trip Units..............................................................5
1-4.2 Additional Features of Digitrip OPTIM 1050 Trip Units ..........................................................................7
SECTION 2: HARDWARE DESCRIPTION AND EQUIPMENT INTERFACES
2-1 General ...............................................................................................................................................................8
2-2 General Trip Unit Details .....................................................................................................................................8
2-2.1 Trip Unit Configuration ...........................................................................................................................8
2-3 Trip Unit Packages ..............................................................................................................................................8
2-4 Series C K, L-Frame and N-Frame OPTIM Trip Units.........................................................................................9
2-4.1 K, L-Frame and N-Frame OPTIM Trip Unit Displays..............................................................................9
2-5 Series C R-Frame, SPB and DSII/DSLII OPTIM Trip Units ..............................................................................11
2-5.1 R-Frame, SPB and DSII/DSLII OPTIM Trip Unit Displays ...................................................................12
2-6 OPTIM Trip Unit Rating Plug.............................................................................................................................14
2-7 External OPTIM Trip Unit Accessories..............................................................................................................15
2-8 Specification and Protective Range Summaries ...............................................................................................15
SECTION 3: OPERATION AND FUNCTIONALITY
3-1 General .............................................................................................................................................................20
3-2 Protection and Coordination..............................................................................................................................20
3-2.1 Over-Temperature Trip.........................................................................................................................20
3-2.2 Characteristic Curve Review ................................................................................................................20
3-2.3 Protection and Curve Shaping Features ..............................................................................................25
3-2.4 Long Delay Protection ..........................................................................................................................26
3-2.5 Short Delay Protection .........................................................................................................................28
3-2.6 Instantaneous Protection......................................................................................................................30
3-2.7 Ground Fault Protection .......................................................................................................................31
3-2.8 Time-Current Curves............................................................................................................................33
3-3 System Monitoring.............................................................................................................................................33
3-3.1 Displays and LED Indicators ................................................................................................................34
3-3.2 Normal Service/Automatic Trip Current Monitoring..............................................................................34
3-3.3 Remote Signal Contacts.......................................................................................................................34
3-3.4 Power and Energy Monitoring ..............................................................................................................35
3-3.5 Power Quality (Harmonics) Monitoring.................................................................................................35
3-3.6 Power Factor ........................................................................................................................................35
3-4 Communications................................................................................................................................................35
3-4.1 IMPACC ...............................................................................................................................................36
3-5 Testing...............................................................................................................................................................36
3-5.1 Secondary Injection Testing .................................................................................................................37
3-5.2 When to Test ........................................................................................................................................37
3-5.3 Conducting Tests .................................................................................................................................37
3-5.4 Performance Testing for Ground Fault Trip Units ................................................................................38
I.B. 29C891B
Page v
Effective 11/98
Page
SECTION 4: STARTUP AND TESTING
4-1 Introduction........................................................................................................................................................40
4-2 Wiring ................................................................................................................................................................40
4-2.1 Wiring Diagrams...................................................................................................................................40
4-2.2 Wiring Plan Drawing.............................................................................................................................40
4-2.3 Network Wiring Diagram ......................................................................................................................40
4-3 Initial Startup .....................................................................................................................................................40
4-3.1 Before Power Application .....................................................................................................................40
4-3.2 Initial Power Application .......................................................................................................................41
4-4 Testing...............................................................................................................................................................41
SECTION 5: TROUBLESHOOTING AND MAINTENANCE
5-1 Level of Repair ..................................................................................................................................................43
5-2 Troubleshooting.................................................................................................................................................43
5-3 Trip Unit Replacement.......................................................................................................................................43
5-4 Maintenance and Care ......................................................................................................................................43
5-4.1 Local Indicator Battery Check and Replacement .................................................................................53
5-4.2 Rating Plug Replacement.....................................................................................................................54
5-5 Return Procedure ..............................................................................................................................................55
5-6 Technical Assistance.........................................................................................................................................55
Appendix A Instructional References ............................................................................................................56
Appendix B Checking Zone Selective Interlocking ....................................................................................58
I.B. 29C891B
Page vi
Effective 11/98
LIST OF FIGURES
Figure Title Page
1-1 Series C L-Frame Molded Case Circuit Breaker with OPTIM Trip Unit .....................................................2
1-2 SPB Systems Pow-R Circuit Breaker with OPTIM Trip Unit......................................................................2
1-3 DSII Power Circuit Breaker with OPTIM Trip Unit .....................................................................................2
1-4 Family of Digitrip OPTIM Trip Unit Rating Plugs........................................................................................3
1-5 Family of Digitrip Trip Units Comparison ...................................................................................................3
1-6 Hand Held Programmer in Use..................................................................................................................4
1-7 Breaker Interface Module in Service..........................................................................................................4
1-8 Monitor and Control from Central PC ........................................................................................................5
1-9 Typical System Configurations ..................................................................................................................6
2-1 Typical OPTIM Trip Unit Circuitry (DSII Type Circuit Breaker Shown) ......................................................8
2-2 OPTIM Trip Unit Mounted in Series C L-Frame Circuit Breaker (K-Frame is Similar)...............................9
2-3 OPTIM Trip Unit Mounted in Series C N-Frame Circuit Breaker ...............................................................9
2-4 Front View of L-Frame Type OPTIM Trip Unit (K and N-Frame Designs are Similar).............................10
2-5 K, L and N-Frame Type OPTIM Trip Unit Battery Compartment.............................................................10
2-6 K, L and N-Frame Type OPTIM Trip Unit Programming Port..................................................................11
2-7 OPTIM Trip Unit Mounted in Series C R-Frame Circuit Breaker .............................................................11
2-8 OPTIM Trip Unit Mounted in SPB Circuit Breaker...................................................................................12
2-9 OPTIM Trip Unit Mounted in DSII Circuit Breaker ...................................................................................12
2-10 Front View of R-Frame, SPB and DSII/DSLII Type OPTIM Model 1050 Trip Unit
with R-Frame Rating Plug Installed .........................................................................................................13
2-11 R-Frame, SPB and DSII/DSLII Type OPTIM Trip Unit Battery Compartment .........................................13
2-12 OPTIMizer Shown Connected to Programming Port of DSII Type Circuit Breaker .................................14
2-13 Family of OPTIM Trip Unit Ratings Plugs................................................................................................14
2-14 Power Accessory Requirements for K, L and N-Frame Circuit Breakers ................................................15
2-15 Externally Mounted Potential Transformer Module (necessary for K, L and N-Frame only) ...................16
2-16 Ground Fault Alarm Indicator (necessary for K, L and N-Frame only) ....................................................16
3-1 Sample of Partial Time-Current Trip Curve .............................................................................................21
3-2 Typical Trip Curve Horizontal Movement.................................................................................................21
3-3 Typical Long Delay Time Slope Adjustment............................................................................................21
3-4 Overcurrent Protective Function Combinations.......................................................................................25
3-5 Typical OPTIM Trip Unit Time-Current Curve (10 Curve Shaping Adjustments).....................................26
3-6 Typical Long Delay Setting Adjustment...................................................................................................27
3-7 Typical Long Delay Time Adjustment (I
2
t) Response ..............................................................................27
3-8 Typical Long Delay Time Adjustment (I
4
t) Response ..............................................................................28
3-9 Typical Short Delay Pickup Adjustment...................................................................................................28
3-10 Typical Short Delay Time Adjustment, Flat Response ............................................................................29
3-11 Typical Short Delay Time Adjustment, (I2t) Response.............................................................................29
3-12 Multi-layer Ground Fault Protection Scheme Using Zone Selective Interlocking ....................................30
3-13 Typical Instantaneous Pickup Adjustment...............................................................................................31
3-14 Ground Fault Alarm LED .........................................................................................................................32
3-15 Typical Ground Fault Pickup Adjustment.................................................................................................33
3-16 Typical Ground Fault Time Delay Adjustment, Flat Response................................................................33
3-17 Typical Ground Fault Time Delay Adjustment, (I2t) Response ................................................................33
3-18 Typical Waveform and Harmonic Display................................................................................................36
3-19 Auxiliary Power Module ...........................................................................................................................38
3-20 Typical Performance Test Record Form..................................................................................................39
I.B. 29C891B
Page vii
Effective 11/98
Figure Title Page
4-1 Typical Network Wiring Diagram .............................................................................................................42
5-1 Battery Test Pushbutton and LED Shown on Face of OPTIM Trip Unit ..................................................53
5-2 Battery Test Pushbutton and LED Shown on OPTIM Rating Plug ..........................................................53
5-3 Battery Shown Installed in Battery/Programming Port Compartment......................................................54
5-4 Battery Shown Installed Behind Rating Plug Hinged Cover ....................................................................54
5-5 Rating Plug Shown Removed (L and N-Frame Type OPTIM Trip Units) ................................................55
5-6 Rating Plug Shown Being Removed (R-Frame, SPB and
DSII/DSLII Type OPTIM Trip Units).........................................................................................................55
LIST OF TABLES
Figure Title Page
2.1 Rating Plugs Applicable to All OPTIM Trip Units .....................................................................................17
2.2 OPTIM Trip Unit/Accessory Specifications ..............................................................................................18
2.3 OPTIM Trip Unit Metering Tolerances .....................................................................................................19
3.1 Digitrip OPTIM 750 and 1050 Trip Unit Capabilities ................................................................................20
3.2 Digitrip OPTIM 550 Trip Unit System Capabilities Overview ...................................................................22
3.3 Digitrip OPTIM 750 Trip Unit System Capabilities Overview ...................................................................23
3.4 Digitrip OPTIM 1050 Trip Unit System Capabilities Overview .................................................................24
5.1 Troubleshooting Guide ............................................................................................................................43
A.1 Instructional References..........................................................................................................................56
I.B. 29C891B
Page 1
Effective 11/98
SECTION 1: INTRODUCTION
1-1 COMMON TERMS
Several commonly used terms or phrases are used throughout this manual. They are defined here to elimi­nate any confusion that might arise when reading the text.
IMPACC (Integrated Monitoring, Protection and Control Communications) – A family of communicat-
ing electrical power distribution protective devices, meters, motor control devices, communications net­works and protocols and software packages to provide power distribution monitoring and control.
INCOM (Industrial Communications) – A noise immune communications system designed specifically for power distribution monitoring and control applications.
PONI (Product Operated Network Interface) – A plug-in communications module that enables network communications.
1-2 PRELIMINARY COMMENTS AND SAFETY PRECAUTIONS
This instructional manual is intended to present specific descriptive, operational and maintenance information associated with Digitrip OPTIM Trip Units only. Digitrip OPTIM Trip Units are designed to be used with the Breaker Interface Module and OPTIMizer Hand Held Programmer. For a general overview of the entire Digitrip OPTIM Trip Unit System and certain specific application possibilities, refer to Instruction Book 29C890 entitled “Instructional Overview for Use of the Digitrip OPTIM Trip Unit System.”
Detailed instructional material relative to the installation, use and maintenance of specific devices is included under separate cover by a manual dedicated to each device. A series of four manuals brings together the wide array of capabilities offered by the most advanced programmable trip unit system - Digitrip OPTIM. Refer to Appendix A for all instruction material references.
Please read and understand this manual and all other relevant manuals before proceeding with the installation and operation of any device included in the trip unit sys-
tem. Pay particular attention to all WARNINGS and CAUTIONS. They are intended to help insure personnel safety and equipment protection. Refer to the WARN­ING and CAUTION in Paragraph 1-2.1 before proceed­ing to any other section in this manual or any other man­ual. If further information is required by the purchaser regarding a particular installation, application or mainte­nance activity, a Cutler-Hammer representative should be contacted.
1-2.1 SAFETY PRECAUTIONS
All safety codes, safety standards and/or regulations must be strictly observed in the installation, operation and maintenance of any device in this system.
THE WARNINGS AND CAUTIONS INCLUDED AS PART OF THE PROCEDURAL STEPS IN THIS DOCU­MENT ARE FOR PERSONNEL SAFETY AND PRO­TECTION OF EQUIPMENT FROM DAMAGE. AN EXAMPLE OF A TYPICAL WARNING LABEL HEAD­ING IS SHOWN ABOVE IN REVERSE TYPE TO FAMILIARIZE PERSONNEL WITH THE STYLE OF PRESENTATION. THIS WILL HELP TO INSURE THAT PERSONNEL ARE ALERT TO WARNINGS, WHICH MAY APPEAR THROUGHOUT THE DOCU­MENT. IN ADDITION, CAUTIONS ARE ALL UPPER CASE AND BOLDFACE AS SHOWN BELOW.
COMPLETELY READ AND UNDERSTAND THE MATERIAL PRESENTED IN THIS DOCUMENT BEFORE ATTEMPTING INSTALLATION, OPERATION OR APPLICATION OF THE EQUIPMENT. IN ADDI­TION, ONLY QUALIFIED PERSONS SHOULD BE PERMITTED TO PERFORM ANY WORK ASSOCIAT­ED WITH THE EQUIPMENT. ANY WIRING INSTRUC­TIONS PRESENTED IN THIS DOCUMENT MUST BE FOLLOWED PRECISELY. FAILURE TO DO SO COULD CAUSE PERMANENT EQUIPMENT DAMAGE.
WARNING
CAUTION
I.B. 29C891B
Page 2
Effective 11/98
Figure 1-1 Series C L-Frame Molded Case Circuit Breaker with OPTIM Trip Unit
Figure 1-2 SPB Systems Pow-R Circuit Breaker with OPTIM Trip Unit
Figure 1-3 DSII Power Circuit Breaker with OPTIM Trip Unit
1-3 PRODUCT OVERVIEW
The Digitrip OPTIM Trip Unit is a programmable, com­municating, microprocessor-based, low voltage trip unit. Digitrip OPTIM Trip Units are for use with Series C K­Frame, L-Frame, N-Frame and R-Frame Molded Case Circuit Breakers, SPB Systems Pow-R Circuit Breakers, and DSII/DSLII Power Circuit Breakers (Figures 1-1, 1-2 and 1-3). These circuit breakers using Digitrip OPTIM Trip Units cover a range of rated currents from 70 amperes to 5000 amperes. The Digitrip OPTIM Trip Unit provides true rms sensing and utilizes a non-adjustable interchangeable rating plug to establish the continuous current rating of the circuit breaker (Figure 1-4). Rating plugs are interlocked to prevent use between different circuit breaker frames.
The Digitrip OPTIM Trip Unit is an addition to the already expansive family of Digitrip Trip Units (Figure 1-5). Three different models are available, OPTIM 550, OPTIM 750 and OPTIM 1050. The OPTIM 1050 Trip Unit has all the features of the OPTIM 550 and 750 Trip Units plus sev­eral additional features. The OPTIM 1050 Trip Unit’s additional features are:
• Monitoring power and energy
• Monitoring current harmonics
Trip Unit
Trip Unit
Trip Unit
I.B. 29C891B
Page 3
Effective 11/98
Figure 1-4 Family of Digitrip OPTIM Trip Unit Rating Plugs
Figure 1-5 Family of Digitrip Trip Units Comparison
Refer to paragraph 1-4 for feature and function details.
A Digitrip OPTIM Trip Unit System can be tailored to meet very precise system requirements. The featured parts of an OPTIM Trip Unit System are:
• OPTIM 550, 750 or OPTIM 1050 Trip Unit
• OPTIMizer Hand Held Programmer
• Breaker Interface Module
• Communications System and Software (IMPACC)
A Digitrip OPTIM Trip Unit System always includes any number of OPTIM 550, 750 or OPTIM 1050 Trip Units with one or more OPTIMizer Hand Held Programmers. The OPTIMizer Hand Held Programmer is required with the trip units to initially:
• Assign unique device addresses
• Select baud rates
In addition, OPTIM Trip Units are compatible with the optional panel mounted Breaker Interface Module and IMPACC software. When used, the Breaker Interface Module and IMPACC software also become integral parts of the overall Digitrip OPTIM Trip Unit System. Together, the OPTIM Trip Units, the required OPTIMizer Hand Held Programmer, the optional Breaker Interface
K, L, N & R R, SPB & DSII K thru DSII R thru DSII K thru DSII R thru DSII R thru DSII K thru DSII
RMS 310 RMS 510 OPTIM 550
RMS 610 OPTIM 750 RMS 810 RMS 910 OPTIM 1050
RMS Sensing RMS Sensing RMS Sensing RMS Sensing RMS Sensing RMS Sensing RMS Sensing RMS Sensing
5 Functions 9 Functions 10 Functions 9 Functions 10 Functions 9 Functions 9 Functions 10 Functions
Front Front
Programmable
Front
Programmable
Front Front
Programmable
Adjustable Adjustable Adjustable Adjustable Adjustable
Load Load Load Load Load
Monitoring Monitoring Monitoring Monitoring Monitoring
Diagnostics Diagnostics Diagnostics Diagnostics Diagnostics
Communications Communications Communications Communications
Power & Energy Power & Energy Power & Energy Field Installed Monitoring Monitoring Monitoring communications
available Harmonics Harmonics
Applicable Circuit Breaker Types and Trip Unit Type
I.B. 29C891B
Page 4
Effective 11/98
Module, and the optional IMPACC software form a sys­tem that is capable of:
• Setting trip units
• Configuring systems
• Monitoring/protecting
• Displaying information
• Diagnosing input
• Testing trip units/circuit breakers
• Communicating on sub-networks/networks
Application of low voltage circuit breakers utilizing OPTIM Trip Units generally fall into three primary cate­gories:
Stand Alone Application (Individual Circuit Breakers)
These applications are utilized to take advantage of the superior protection and coordination features of Digitrip OPTIM, and plan to perform monitoring at the circuit breaker itself (Figure 1-6).
The following would be used:
• OPTIM 550, 750 and/or 1050 Trip Units
• One or more OPTIMizer Hand Held Programmers
Integrated Assembly Applications (Low Voltage Assemblies)
These applications are utilized to provide on-gear or remote monitoring and even testing of compatible devices (Figure 1-7). Up to 50 OPTIM Trip Units, Digitrip RMS 810/910 Trip Units or IQ Energy Sentinels can communicate with one Breaker Interface Module.
The following would be used:
• OPTIM 550 (if field IMPACC kit installed)
• OPTIM 750 and/or 1050 Trip Units
• Digitrip RMS 810 and/or 910 Trip Units
• IQ Energy Sentinels
• One or more OPTIMizer Hand Held Programmers
• One or more assembly/remotely mounted Breaker Interface Modules
Facility Wide Application (IMPACC System)
These applications are utilized to tie together more than 50 circuit breakers and/or other compatible devices. In addition, this permits taking advantage of PC-based software to improve diagnostics, power quality and energy monitoring, or protective device coordination capabilities. The system would consist of any number of devices and software products, either within a facility or across multiple facilities (Figure 1-8).
Figure 1-6 Hand Held Programmer in Use
Figure 1-7 Breaker Interface Module in Service
I.B. 29C891B
Page 5
Effective 11/98
The following would be used:
• OPTIM 550 (if field IMPACC kit installed)
• OPTIM 750 and/or 1050 Trip Units
• Digitrip RMS 810 and/or 910 Trip Units
• Other IMPACC Compatible devices
• One or more OPTIMizer Hand Held Programmers
• One or more assembly/remotely mounted Breaker Interface Modules
• IMPACC software/central PC
Refer to Figure 1-9 for typical system configurations uti­lizing the OPTIM Trip Unit System and other compatible devices. For additional IMPACC details, refer to Section 3 of Instruction Book 29C890.
1-4 FEATURES AND FUNCTIONS
Digitrip OPTIM 550, 750 and 1050 Trip Units provide a wide range of common protection and coordination fea­tures and functions. The Digitrip OPTIM 1050 Trip Unit also provides power quality and energy monitoring capa­bilities.
1-4.1 COMMON FEATURES OF DIGITRIP OPTIM 550, 750 AND 1050 TRIP UNITS
Precise system coordination is provided by an expan­sive number of time-current curve shaping adjustments. This is accomplished by the large number of incremen­tal setpoints available for both current pickup and time settings.
Programmable Protection and Coordination Adjustments
• Long delay setting
• Long delay time with selectable I2t or I4t slopes
• Short delay setting
• Short delay time with selectable flat or I2t slopes
• Instantaneous setting
• Ground fault setting
• Ground fault time with selectable flat or I2t slopes
The trip units also have a selectable powered and unpowered thermal memory to provide protection against cumulative overheating should a number of overload conditions occur in quick succession.
The trip unit information system utilizes LEDs to indicate the trip mode following an automatic trip operation. The LEDs are complemented by trip event information that is
stored in non-volatile memory after a trip condition. This trip information can then be accessed via the Optimizer Hand Held Programmer, the Breaker Interface Module, or over the IMPACC System.
Selectable early warning alarms, such as the high load current alarm, are capable of being indicated locally and remotely. They are provided to help keep a system operating and productive.
System Monitoring
All OPTIM Trip Units are capable of monitoring the fol­lowing data:
• Steady-State value of phase and neutral or ground currents
• Minimum and maximum current values
• Average demand current
• Cause of trip
• Magnitude of fault current responsible for an automat­ic trip operation
LSI version of OPTIM 550 only monitors phase currents
Figure 1-8 Monitor and Control from Central PC
I.B. 29C891B
Page 6
Effective 11/98
Figure 1-9 Typical System Configurations
Master
Computer
Breaker
Interface
Module
Shielded Twisted Pair
SPB
Circuit
Breaker
with
OPTIM
DSII
Circuit
Breaker
with
OPTIM
Series C R-Frame
MCCB
with
OPTIM
To Other IMPACC
Compatible Devices
PONI
OPTIMizer
Series C N-Frame
MCCB
with
OPTIM
Series C L-Frame
MCCB
with
OPTIM
Circuit
Breaker
with
RMS 810
or 910
Series C F-Frame
MCCB
ES
IQ Energy Sentinel
Shielded Twisted Pair
PONI Module
(Required for IMPACC
Network Communications
to Master Computer)
Shielded
Twisted
Pair
➁ ➂
OPTIMizer
OPTIMizer
OPTIMizer
OPTIMizer
Series C K-Frame
MCCB
with
OPTIM
OPTIMizer
NOTES
OPTIMizer Hand Held Programmer compatible only with OPTIM Trip Units
Can monitor up to 50 com-
patible devices.
Circuit breakers with OPTIM
Trip Units can be directly connected to a master com­puter, and do not have to be connected through the BIM.
Universal IQ Energy Sentinel
also compatible with Breaker Interface Module.
CONFIGURATIONS 1 + 2
Network Configuration —
Breaker Interface Module with Master Computer as Master Device
CONFIGURATION 1
Sub-Network Configuration —
Breaker Interface Module Functioning as Master Device
CONFIGURATION 2
Master Computer and IMPACC Software
I.B. 29C891B
Page 7
Effective 11/98
Communications
Trip units that are capable of two way communication operate via a network twisted pair for remote monitoring and control. The circuit breaker, through the trip unit, is able to respond to open and close commands via the communication network. To close the breaker, a motor operator accessory is required. Refer to Table A.1 in Appendix A for motor operator instructional references.
Testing
An integral testing capability is part of all OPTIM Trip Systems. The breaker can be tested in either the “Trip” or “No Trip” Test Mode. System level testing is carried out by using a Hand Held Programmer, a Breaker Interface Module, or a remote computer. Bench level testing requires the Hand Held Programmer only. Trip tests with the Hand Held Programmer require an auxil­iary power module to supply the necessary power. Trip units continue to provide protection during test opera­tions.
Data Access
All programming, information display and general trip unit access is accomplished through the use of one or more of the following:
• Hand Held Programmer
• Breaker Interface Module
• Remote computer
1-4.2 ADDITIONAL FEATURES OF DIGITRIP OPTIM 1050 TRIP UNITS
The Digitrip OPTIM 1050 Trip Unit provides all the basic system protection features outlined in Paragraph 1-4.1. In addition, Digitrip OPTIM 1050 Trip Units can provide data on power quality (current harmonics) and permit energy monitoring.
Energy Monitoring
• Peak demand (kW)
• Present demand (kW)
• Forward energy (kWh)
• Reverse energy (kWh)
• Total energy (kWh)
• Power factor
Power Quality
• Percentage harmonic content
• Total harmonic distortion (THD)
• Digitized waveforms (Remote computer only)
OPTIM 550 trip units must have field IMPACC kit installed for use with BIM or remote computer
I.B. 29C891B
Page 8
Effective 11/98
SECTION 2: HARDWARE DESCRIPTION AND EQUIPMENT INTERFACES
2-1 GENERAL
The purpose of this section is to familiarize the reader with Digitrip OPTIM Trip Units, their nomenclature, the way trip units are interfaced with specific equipment, and trip unit specifications. The information presented is divided into the following four parts:
• General Trip Unit Details
• Trip Units By Type
• Trip Unit Accessories
• Specification Summary
2-2 GENERAL TRIP UNIT DETAILS
This section describes general trip unit functioning, trip unit hardware, circuit breaker specific details, and required interfaces with other external equipment.
2-2.1 TRIP UNIT CONFIGURATION
A complete OPTIM Trip Unit System consists of current sensors, electronic circuitry and a flux transfer shunt trip device contained inside the circuit breaker (Figure 2-1). The trip units are completely self-contained and, when the circuit breaker is closed, no external power is required to operate their protective systems. They operate from cur­rent signal levels and control power is derived from the current sensors integrally mounted in the circuit breakers.
Circuit protection is achieved by analyzing the sec­ondary current signals received from the circuit breaker current sensors. As signals are received and analyzed, a trip signal to the flux transfer shunt trip is initiated when programmed current levels and time delay set­tings are exceeded.
2-3 TRIP UNIT PACKAGES
The features associated with the three different OPTIM Trip Unit models (550, 750 and 1050) are outlined in Figure 1-5.
Figure 2-1 Typical OPTIM Trip Unit Circuitry (DSII Type Circuit Breaker Shown)
A
B C
N
G
A
BC
N
01
02 03
A
N
Terminal Block
Rating Plug
Trip Unit
Trip Actuator
Typical Trip Unit
Typical DSII Type Circuit Breaker
Sensors
** Alternate ground locations
may be required to meet installation requirements
Typical Current Sensor
**
I.B. 29C891B
Page 9
Effective 11/98
Models 750 and 1050 on K, L and N-Frame circuit breakers are factory sealed. Model 550 equipped circuit breakers and all R-Frame SPB and DSII circuit breakers can be upgraded in the field.
2-4 SERIES C K, L-FRAME AND N-FRAME OPTIM TRIP UNITS
The continuous frame rating of each circuit breaker is selectable via rating plugs over the following range:
K-Frame (70-400 amperes)
L-Frame (200-600 amperes)
N-Frame (400-1200 amperes)
The OPTIM Trip Unit applicable to the Series C K and L­Frame molded case circuit breakers extends approxi­mately 0.5 inches beyond the front of the breaker cover (Figure 2-2). The OPTIM Trip Unit used with the L­Frame is not applicable to any other circuit breaker.
The OPTIM Trip Unit applicable to Series C N-Frame molded case circuit breaker is nearly flush mounted to the front of the breaker cover (Figure 2-3). The OPTIM Trip Unit used with the N-Frame is not applicable to any other circuit breaker.
The side wiring brackets shown in Figures 2-2 and 2-3 are only necessary for Models 750 and 1050 on K, L
and N-Frame circuit breakers. Model 550 does not need the bracket on the same frames.
2-4.1 K, L AND N-FRAME OPTIM TRIP UNIT DISPLAYS
Readings are displayed and protective settings estab­lished or adjusted through the use of one or more of the following means:
OPTIMizer Hand Held Programmer
Breaker Interface Module
Remote Computer/IMPACC software
OPTIM Trip Units provide the following features (Figure 2-4):
Push-To-Trip Button
A Push-To-Trip button provides a local manual means for checking the circuit breakers mechanical tripping function and periodically exercising the operating mech­anism. It is located on the front of the trip unit.
Mode of Trip/Alarm Indicators
Four LED type indicators (long delay, short delay, instantaneous and ground fault trip or ground fault alarm) are provided to indicate the mode of trip after an automatic trip. The appropriate LED is lit red when acti­vated.
Figure 2-2 OPTIM Trip Unit Mounted in Series C L-Frame Circuit Breaker (K-Frame is Similar)
Figure 2-3 OPTIM Trip Unit Mounted in Series C N-Frame Circuit Breaker
I.B. 29C891B
Page 10
Effective 11/98
Notice: Trip unit should be powered from an external
control power source. If control power is not available the LEDs will temporatily operate off the battery. Refer to the wiring diagrams list­ed in Appendix A, Table A.1 for control power connections.
Battery for Trip Indicators
A replaceable 3 volt lithium battery is located behind a small access cover on the left side of the trip unit (Figure 2-5). A test pushbutton and LED test indicator are also provided. The test pushbutton will energize the LED indicator if the battery is in good working condition. Refer to paragraph 5-4.1 for battery replacement infor­mation.
Trip Indicator Reset Pushbutton
A trip reset pushbutton is provided to turn off a mode of trip LED indicator after an automatic trip. The reset pushbutton is located next to the four mode of trip led indicators.
Figure 2-4 Front View of L-Frame Type OPTIM Trip Unit (K and N-Frame Designs are Similar)
Figure 2-5 K, L and N-Frame Type OPTIM Trip Unit Battery Compartment
Push-to-Trip ButtonMode of Trip/Alarm LEDsBattery Test Pushbutton/LEDAutomatic Trip Indicator Reset
Pushbutton
Unit Status LEDINCOM Transmit LED (Model 550 requires field IMPACC kit)Battery Compartment/Pro-gramming Port Access CoverRating Plug
I.B. 29C891B
Page 11
Effective 11/98
covering the OPTIMizer Hand Held Programmer for the recommended connection and power application sequence.
2-5 SERIES C R-FRAME, SPB AND DSII/DSLII OPTIM TRIP UNITS
Model 750 and 1050 OPTIM Trip Units used in Series C R-Frame, SPB Systems Pow-R and DSII/DSLII circuit breakers are field replaceable. Model 550 is only avail­able on the R-Frame circuit breaker. For each of these circuit breaker types, rating plugs are used to select the continuous ampere rating of the circuit breaker. The rat­ing plugs and circuit breakers are keyed with a mechani­cal interlock to prevent incorrect installation. The contin­uous ampere rating of each of these circuit breakers is adjustable via the rating plugs as follows:
Series C R-Frame (800-2500 amperes) (Figure 2-7)
SPB Pow-R (200-5000 amperes) (Figure 2-8)
DSII/DSLII (100-5000 amperes) (Figure 2-9)
Refer to Table 2.1 for the available rating plug values by circuit breaker type.
Unit Status LED
The green Unit Status LED blinks with a one second on­off duty cycle when power is applied to the trip unit and it is functioning properly.
INCOM Transmit LED
The red transmit LED flashes red when the trip unit is communicating over an INCOM network.
Programming Port
A custom phone type jack programming port is located with the trip indicator battery behind the small access cover. One end of the custom phone type cord provided with the OPTIMizer Hand Held Programmer plugs into the port, and permits direct programming of the trip unit (Figure 2-6). To access the programming port, remove the access cover by pulling down on the release tab located in the center of the cover while pulling out on the cover. The port will accept either end of the custom phone cord.
Notice: When the OPTIMizer is plugged into a trip
unit, it prevents all remote IMPACC communi­cations (if present) with that trip unit. This action will also cause a No-Response alarm on the Breaker Interface Module and a master network. Refer to Instruction Book 29C892
Figure 2-6 K, L and N-Frame Type OPTIM Trip Unit Programming Port
Figure 2-7 OPTIM Trip Unit Mounted in Series C R-Frame Circuit Breaker
Push-To-Trip Button
I.B. 29C891B
Page 12
Effective 11/98
2-5.1 R-FRAME, SPB AND DSII/DSLII OPTIM TRIP UNIT DISPLAYS
Readings are not displayed and protective settings are not established or adjusted from the front of Digitrip OPTIM Trip Units. These functions are carried out through the use of one or more of the following means:
OPTIMizer Hand Held Programmer
Breaker Interface Module
Remote Computer/IMPACC software
The R-Frame, SPB and DSII/DSLII OPTIM Trip Unit dis­plays all provide the following features (Figure 2-10):
Push-To-Trip Button
A Push-To-Trip (Push-To-Open on SPB) button pro­vides a local manual means for checking the circuit breakers mechanical tripping function and periodically exercising the operating mechanism. This pushbutton is accessible from the front of the R-Frame, SPB and DSII/DSLII circuit breakers.
Mode of Trip/Alarm Indicators
Four LED type indicators (long delay, short delay, instantaneous and ground fault trip or ground fault alarm) are provided to indicate the mode of trip after an automatic trip. The appropriate LED is lit red when acti-
Figure 2-8 OPTIM Trip Unit Mounted in SPB Circuit Breaker
vated. The LEDs are presented in the form of a mimic time-current curve on the front of the OPTIM Trip Unit.
Notice: Trip unit indicators should be powered from a
control power source wired externally to the circuit breaker or alternatively via battery locat­ed in the trip unit. For connection to an exter­nal control power source, refer to the wiring diagrams listed in Appendix A, Table A.1.
Battery for Trip Indicators
A replaceable 3 volt lithium battery is located behind the hinged cover of the rating plug (Figure 2-11). A test pushbutton and LED test indicator are also provided. The test pushbutton will energize the LED indicator if the battery is in good working condition. Refer to para­graph 5-4.1 for battery replacement information.
Trip Indicator Reset Pushbutton
A trip reset pushbutton is provided to turn off a mode of trip LED indicator after an automatic trip. The reset push­button is located directly under the programming port.
Notice: For SPB and DSII/DSLII circuit breakers, this
pushbutton also functions as a trip lockout reset. It must be pressed after an automatic trip to reset the trip unit.
Figure 2-9 OPTIM Trip Unit Mounted in DSII Circuit Breaker
Push-To-Trip Button
Push-To­Open Button
I.B. 29C891B
Page 13
Effective 11/98
Unit Status LED
The green Unit Status LED blinks with a one second on-off duty cycle when power is applied to the trip unit and it is functioning properly.
INCOM Transmit LED
The red transmit LED flashes red when the trip unit is communicating over an INCOM network. Model 550 requires the field IMPACC kit for communications.
Programming Port
A custom phone type jack programming port is located just under the rating plug. One end of the custom phone type cord provided with the OPTIMizer Hand Held Programmer plugs into the port, and permits direct pro­gramming of the trip unit (Figure 2-12). The port will accept either end of the custom phone cord.
Notice: When the OPTIMizer is plugged into a trip
unit, it prevents all remote IMPACC communi­cations with that trip unit. This action will also cause a No-Response alarm on the Breaker Interface Module and a master network. Refer to Instruction Book 29C892 covering the
Figure 2-10 Front View of R-Frame, SPB and DSII/DSLII Type OPTIM Model 1050 Trip Unit with R-Frame Rating Plug Installed
Mode of Trip/Alarm LEDsAutomatic Trip Indicator Reset
Pushbutton
Unit Status LEDINCOM Transmit LEDProgramming PortRating Plug (Hinged Cover
Closed)
Figure 2-11 R-Frame, SPB and DSII/DSLII Type OPTIM Trip Unit Battery Compartment
I.B. 29C891B
Page 14
Effective 11/98
OPTIMizer Hand Held Programmer for the recommended connection and power applica­tion sequence.
2-6 OPTIM TRIP UNIT RATING PLUG
The rating plug value (In) determines the maximum con­tinuous current rating of the circuit breaker. All the pro­tection function settings are based on multiples of the plug rating. These settings are displayed as actual ampere values for ease of use.
Notice: The primary current conductors (cable or bus)
must have ampacity ratings equal to the rat­ing plug value per NEC Section 240-6(b).
OPTIM Trip Units use interchangeable rating plugs (Figure 2-13). Rating plugs are designed for use with one specific circuit breaker type. The circuit breaker type is indicated on the rating plug. Rating plugs are suitable for both 50 and 60Hz operation. A rating plug must be selected to match the desired continuous current rating of the circuit breaker as well as the installed sensor rat­ing. The available rating plugs are shown in Table 2.1.
Figure 2-12 OPTIMizer Shown Connected to Program­ming Port of DSII Type Circuit Breaker
Figure 2-13 Family of OPTIM Trip Unit Rating Plugs
DSII/DSL II Rating PlugSPB Pow-R Rating PlugR-Frame Rating Plug
(Hinged Access Cover Open)
N-Frame Rating PlugL-Frame Rating Plug
(K-Frame Similar)
Retention ShaftAccess to Retention DeviceConnector Pin
I.B. 29C891B
Page 15
Effective 11/98
All rating plugs are designed with a rejection feature to prevent interchanging between different circuit breaker types. In addition, the circuit breaker will trip if a rating plug is removed with the trip unit energized.
BEFORE A RATING PLUG IS INSTALLED INTO THE TRIP UNIT, BE CERTAIN TO CHECK THAT THE BREAKER TYPE AND FRAME RATING (OR SENSOR RATING IF APPLICABLE) MATCH THOSE PRINTED ON THE RATING PLUG COVER. INSTALLING A RATING PLUG THAT DOES NOT MATCH THE BREAKER TYPE AND FRAME RATING (OR SENSOR RATING IF APPLICABLE) CAN PRODUCE SERIOUS MISCOORDINATION AND/OR FAILURE OF THE PROTECTION SYSTEM.
IN ADDITION, IT IS IMPORTANT TO MAKE SURE THAT A RATING PLUG IS PROPERLY INSTALLED AND SECURED TO ENSURE PROPER FUNCTION­ING OF THE CIRCUIT BREAKER.
2-7 EXTERNAL OPTIM TRIP UNIT ACCESSORIES
Digitrip OPTIM Trip Units for K, L, and N-Frame circuit breakers utilize a number of accessory items mounted outside the circuit breaker (Figure 2-14). R-Frame, SPB and DSII circuit breakers have these devices already installed internally. Refer to Table 2.2 for specific accessory details, catalog numbers and/or approved accessory items.
Figure 2-14 Power Accessory Requirements for K, L and N-Frame Circuit Breakers
OPTIM 750 Trip Unit OPTIM 1050 Trip Unit
(Requires) (Requires)
REMOTELY MOUNTED 24 VDC POWER SUPPLY REMOTELY MOUNTED 24 VDC POWER SUPPLY
and
POTENTIAL TRANSFORMER MODULE (PTM)
Circuit
Breaker
Type
Series C L-Frame
and
Series C N-Frame
24 VDC
Power
Supply
N-Frame
L-Frame
24 VDC
Power
Supply
N-Frame
L-Frame
PTM
Control Power Source
K, L, and N-Frame circuit breakers with OPTIM Model 750 or 1050 Trip Units utilize 24 Vdc control power from an external source for IMPACC communications. The power supply needs to be a high quality, isolated type for best performance.
Potential Transformer Module (PTM)
All Digitrip OPTIM 1050 Trip Units require a potential transformer module to provide voltage for power and energy monitoring, and the power factor display. K, L and N-Frame circuit breakers utilize an externally mounted potential transformer module, which can feed up to 16 circuit breakers (Figure 2-15).
Ground Fault Alarm Indicator
K, L and N-Frame circuit breakers with OPTIM 750/1050 Trip Units utilize a remotely mounted ground fault alarm indicator (Figure 2-16). This unit provides an indicator light and relay contacts to operate other warning devices when a ground fault condition occurs. Model 550 OPTIM does not support this feature.
2-8 SPECIFICATION AND PROTECTIVE RANGE SUMMARIES
Refer to Tables 2.2, 2.3, 3.2 and 3.3 for trip unit/acces­sory specification details and trip unit protective ranges.
WARNING
I.B. 29C891B
Page 16
Effective 11/98
Figure 2-15 Externally Mounted Potential Transformer Module (necessary for K, L and N-Frame only)
Figure 2-16 Ground Fault Alarm Indicator (necessary for K, L and N-Frame only)
I.B. 29C891B
Page 17
Effective 11/98
Table 2.1 Rating Plugs Applicable to All OPTIM Trip Units
Series C Series C Series C Series C SPB Systems DSII/DSLII
K-Frame Breaker L-Frame Breaker N-Frame Breaker R-Frame Breaker Pow-R Breakers Breakers
Rating Plug (In) Frame Rating Rating Plug (In) Frame Rating Rating Plug (In) Frame Rating Rating Plug (In) Frame Rating Rating Plug (In) Frame Rating Rating Plug (In) Sensor Rating
(Amperes) (Amperes) (Amperes) (Amperes) (Amperes) (Amperes) (Amperes) (Amperes) (Amperes) (Amperes) (Amperes) (Amperes)
63 125 125 400 800 800 1600 200 400 100 200 70 63 450 1000 250 200
90 70 500 1200 300 200 300 100 90 550 1600 400 250 110 100 600 1000 2000 400 800 300 125 110 700 1200 600 200 400 125 250 125 800 1600 800 250 150 250 600 1200 2000 600 1200 300 175 125 700 1600 2500 800 400 200 150 800 2000 1000 300 600 225 175 1000 2500 1200 400 250 200 1200 800 1600 600 200 400 225 1000 400 800 225 250 1200 600 250 200 400 1600 800 300 225 1000 2000C 600 1200 350 250 1200 800 400 300 1600 1000
350 2000 1200 400 1600 2000 800 1600 300 600 2000 1000 350 1600 2500 1200 400 2000 1600 500 2500 1000 2000 600 1600 3000 1200
2000 1600 2500 2000 3000 1600 2400 2000 4000 2000 2500 2400 3000 1600 3200 3200 2000 4000 2400 3000 5000 3000 3200 3200 4000 2000 4000 5000 2400
3200 4000 3200 5000 4000 5000
Not available on Model 550
I.B. 29C891B
Page 18
Effective 11/98
Table 2.2 OPTIM Trip Unit/Accessory Specifications
Environment:
• Operating Temperature -20°C to 85°C
• Storage Temperature -30°C to 85°C
• Operating Humidity 0 to 95% Relative Humidity (non-condensing)
Frequency 50/60Hz
Protective Settings Refer to Table 3.1
Zone Selective Interlocking • Short Delay
• Ground Fault
Metering Tolerance Refer to Table 2.3
Auxiliary Switch/Bell Alarm
• Contact Ratings • AC - 6A @ 600 Vac
• DC - 0.5A @ 125 Vdc
0.25A @ 250 Vdc
Ground Fault Indicator • AC Contact Ratings (Style 1259C14G01) - 5A @ 240 Vac
- 1/6 HP @ 120 Vac
- 1/3 HP @ 240 Vac
• DC Contact Ratings
- 5A @ 28 Vdc
- 0.5A @ Vdc
• Power Source
- 120 Vac
- 50/60 Hz
• Dimensions (inches)
- 4.75 x 3.94 x 3.00
Potential Transformer Module (PTM)
(Catalog DOPTMLN, Style 7801C54G01)
• Input voltage terminals LA, LB and LC
• Rated input voltage 0 to 600 volts line to line
• Input volt amps 1 VA per phase
• Output voltage terminals A, B, C and N
• Ratio ± 2% (Input) (Output) 240V L-L 2.25V L-N 480V L-L 4.50V L-N 600V L-L 5.53V L-N
• Dimensions (inches) 4.75 x 5.75 x 3.28
• One PTM Can supply up to 16 L or N-Frame
Circuit Breakers
Power Supply
Optim Trip Units impsoe a load of 45ma at 24 Vdc. The power supply should be a high quality, isolated unit with both UL (UR) and CE labels.
Cause of Trip Battery
• Type Lithium, 3 volt
• Acceptable Replacement • Varta Batteries, Inc.
150 Clarbrook Road Elmsford, NY 10523
Type CR 1/3N
• Duracell South Broadway Tarrytown, NY 10591
Type DL 1/3N
• Sanyo Electric, Inc. Battery Div. 200 Riser Road Little Ferry, NJ 07643
Type CR 1/3N
TRIP UNITS
ACCESSORIES
I.B. 29C891B
Page 19
Effective 11/98
Table 2.3 OPTIM Trip Unit Metering Tolerances
Parameter Circuit Breaker Type Accuracy Range/Assumptions
Phase Current K, L, N ±2% Frame Current Rating 5% to 100% Frame Rating
R, SPB ±2% Frame Current Rating 5% to 100% (Current) DSII, DSLII ±2% Sensor Current Rating Sensor Rating
Ground Current K, L, N ±5% Frame Current Rating 10% to 100% Frame
R, SPB ±5% Frame Current Rating 10% to 100% Frame DSII, DSLII ±5% Sensor Current Rating 10% to 100% Current Sensor
Power and Peak K, L, N ±4% of (Frame Current Rating x 600V) x 3 ~ 1 sec. sampling window Demand R, SPB ±4% of (Frame Current Rating x 600V) x 3 - Current @ 5% to 175% of frame
DSII, DSLII ±4% of (Current Sensor Rating x 600V) x 3 or sensor rating
System Power Factor K, L, N ±0.02 Balanced three
R, SPB ±0.02 Phase Load per DSII, DSLII ±0.02 ANSI Std. C12.1-1988
Energy K, L, N ±5% of (Frame Current Rating x 600V x time) x 3 5% to 175% of Plug Rating I
n
R, SPB ±5% of (Frame Current Rating x 600V x time) x 3 DSII, DSLII ±5% of (Current Sensor Rating x 600V x time) x 3
Notes:
Metered values are displayed via:
1. OPTIMizer Hand Held Programmer
2. Breaker Interface Module
3. Remote PC via IMPACC
I.B. 29C891B
Page 20
Effective 11/98
SECTION 3: OPERATION AND FUNCTION­ALITY
3-1 GENERAL
This section describes the details associated with the operation and functional use of Digitrip OPTIM Trip Units in terms four main categories:
• Protection and Coordination
• System Monitoring
- Load Current Monitoring
- Power and Energy Monitoring
- Power Quality Monitoring
• Communications
• Testing
Four quick reference overviews outlining the features available with the Digitrip OPTIM Trip Unit System, and specifically OPTIM Trip Units, are provided in Tables
3.1, 3.2 , 3.3 and 3.4.
OPTIM Trip Units provide true RMS current sensing for proper correlation with thermal characteristics of con­ductors and equipment. The rating plug (In) determines the continuous current rating of the circuit breaker.
3-2 PROTECTION AND COORDINATION
The Digitrip OPTIM Trip Unit provides circuit breakers with an extensive degree of selective coordination potential, and permits curve shaping over a wide range of current settings. Pickup settings, delay time settings and slope selections are addressed here with respect to their effect on the resultant characteristic curve.
3-2.1 OVER-TEMPERATURE TRIP
The OPTIM Trip Unit is designed for use in environ­ments where the ambient temperatures range from ­20°C to +85°C. If, however, temperatures around the trip unit exceed this range, the trip unit performance may be degraded. To insure that the tripping function is not compromised due to an over-temperature condition, the OPTIM microcomputer chip has a built-in over- tem­perature protection feature. This protective feature is factory set to trip the circuit breaker if the chip tempera­ture exceeds 85°C ± 10°C.
3-2.2 CHARACTERISTIC CURVE REVIEW
As a review, certain aspects of a circuit breaker’s char­acteristic curve are discussed here to simplify the under­standing of later material.
The operating response of the trip unit is graphically represented by time-current characteristic curves. These curves show how and when a particular trip unit will act for given values of time and current. The more versatile the trip unit, the easier it is to accomplish close coordination and achieve optimum protection.
A characteristic curve is represented by a band created by a minimum and maximum value of time or current (Figure 3-1). Minimum and maximum values are general­ly the result of tolerances introduced by the manufactur­ing process for components and factory calibration efforts. The tolerances are usually stated as the trip unit’s accuracy and specified on the time-current curves. This accuracy is stated in terms of a plus or minus percentage and represents a permitted fluctuation on either side of a selected nominal setting point for a trip unit. OPTIM Trip Unit accuracies are specified for each protective function (long delay, short delay instantaneous and ground fault) and the type of circuit breaker in which the trip unit is installed. Refer to the applicable OPTIM time-current curves outlined in Table A.1 of Appendix A for specific accuracies.
The programmable or adjustable features of a trip unit permit movement of its characteristic curve or parts of the curve. This movement can be done in both a hori­zontal and vertical direction on the time-current grid (Figure 3-2).
The actual shape of the curve can be changed by selecting the slope, such as Flat, I
2
t and I4t (Figure 3-3). An I2t slope selection is used for an inverse curve, an I4t slope selection for an extremely inverse curve, and a Flat selection for a definite or fixed time curve.
Capability OPTIM 550 OPTIM 750 OPTIM 1050
Protection and Yes Yes Yes Coordination (10 functions) (10 functions) (10 functions)
IMPACC Field Yes Yes Communications Upgradeable
Ground Alarm No Yes
Yes
Contact
Zone Selective No Yes Yes Interlocking
Power Quality No No Yes
Energy Monitoring No No Yes
Requires external module on K, L and N-Frame breakers
Table 3.1 Digitrip OPTIM 550, 750 and 1050 Trip Unit Capabilities
I.B. 29C891B
Page 21
Effective 11/98
Before discussing protection functions individually, keep in mind that combining functional capabilities, such as long, short and instantaneous, is a coordination activity. The effects of one set of settings on another set should be carefully evaluated to determine if the results for all possible circumstances are acceptable.
Example:
• Consider programming the protective functions of a 400 ampere Series C L-Frame circuit breaker with an installed 200 ampere rating plug value (In). OPTIM trips are set up with actual values of current instead of per unit settings.
• The Long Delay Setting (Ir) is to be 100 amperes and the Short Delay Pickup is to be 200 amperes.
• The Long Delay Setting (Ir) is programmable from 0.4
- 1.0 times the rating plug value (In) for the L-Frame. For this example, the Long Delay Setting (Ir) is pro­grammed to 0.5 (In) = 0.5 (200) = 100 amperes, the required Long Delay Setting (Ir).
• The Short Delay Pickup is programmable from 1.5 -
8.0 times the Long Delay Setting (Ir) for the L-Frame. For this example, the Short Delay Pickup is pro­grammed to 2.0 (Ir) = 2.0 (100) = 200 amperes, the required Short Delay Pickup.
TIME
CURRENT
Intermediate
Minimum
Maximum
Figure 3-2 Typical Trip Curve Horizontal Movement
TIME
CURRENT
I4t Slope
I2t Slope
Figure 3-3 Typical Long Delay Time Slope Adjustment
TIME
CURRENT
(Pickup Accuracy) Actual pickup will occur within ± % of any selected pickup setting
(Timing Accuracy) Actual Trip Time will be within ± % of any selected trip time setting
Trip Time Setting
Pickup Setting
Figure 3-1 Sample of Partial Time-Current Trip Curve
I.B. 29C891B
Page 22
Effective 11/98
TRIP UNIT TYPE DIGITRIP OPTIM 550
RMS Sensing Yes Programmable Yes
CIRCUIT BREAKERS
Types Series C K, L and N-Frames Series C R-Frames Ampere Range 70 - 1200A 800 - 2500A Interrupting Rating @ 480V 30 thru 100KA 65 thru 100KA
TRIP UNIT ORDERING OPTIONS
LSI
➀➁ Yes Yes
LSIG
➀➁ Yes Yes
LSIA (Remote over IMPACC only) Yes Yes
PROTECTION AND COORDINATION
Interchangeable Rating Plug (I
n
) 70-1200A 800-2500A
Over-Temperature Trip Yes Yes
LONG DELAY PROTECTION
Long Delay Setting (I
r
) 0.4 - 1.0 x In(0.01 steps) 0.4 - 1.0 x In(0.01 steps)
Long Delay Pickup 116% of I
r
116% of I
r
Long Delay Time I2t @ 6 x I
r
2-24 secs (0.10 steps) 2-24 secs (0.10 steps)
Long Delay Time I
4
t @ 6 x Ir(SDT Slope Flat only) 1-5 secs (0.10 steps) 1-5 secs (0.10 steps) Long Delay Thermal Memory (Powered or Unpowered) Yes (programmable) Yes (programmable) High Load Alarm 0.5 - 1.0 x I
r
0.5 - 1.0 x I
r
SHORT DELAY PROTECTION
Short Delay Pickup 1.5 - 8.0 x Ir(0.1 steps) 1.5 - 8.0 x Ir(0.1 steps)
Short Delay Time I
2
t @ 8 x I
r
0.1 - 0.5 secs (0.01 steps) 0.1 - 0.5 secs (0.01 steps)
Short Delay Time Flat
0.1 - 0.5 secs (0.01 steps) 0.1 - 0.5 secs (0.01 steps)
Zone Selective Interlocking No No
INSTANTANEOUS PROTECTION
Instantaneous Pickup
2.0 - 8.0 x I
n
(0.1 steps) 2.0 - 10.0 x In(0.1 steps)
(1600 & 2000A)
2.0 - 6.0 x I
n
(0.1 steps)
(2500A) Discriminator Yes Yes Override (Fixed Instantaneous)
Yes Yes
GROUND FAULT PROTECTION
Ground Fault Alarm (not to exceed 1200A) 0.2 - 1.0 x Is(0.01 steps) 0.24 - 1.0 x In(0.01 steps) Ground Fault Pickup (not to exceed 1200A)
0.2 - 1.0 x I
s
(0.01 steps) 0.24 - 1.0 x In(0.01 steps)
Ground Fault Delay I
2
t @ 0.62 x In/I
s
0.1 - 0.5 secs (0.01 steps) 0.1 - 0.5 secs (0.01 steps)
Ground Fault Delay Flat 0.1 - 0.5 secs (0.01 steps) 0.1 - 0.5 secs (0.01 steps) Zone Selective Interlocking No No Ground Fault Memory Yes Yes
SYSTEM MONITORING
Digital Display Yes (Using OPT) Yes (Using OPT) Current Yes Yes Cause of Trip LEDs Yes Yes Magnitude of Trip Information Yes Yes Remote Signal Contacts No No Power and Energy No No Power Quality - Harmonics No No Power Factor No No
COMMUNICATIONS
IMPACC Field Upgradeable Field Upgradeable
TESTING
Testing Method OPT, BIM, IMPACC OPT, BIM, IMPACC
No ground fault alarm (A) providedRefer to para. 3-2.3 and Figure 3-4 for detailsSetting Tolerance ±5%Setting Tolerance +0-30%Setting Tolerance +10-40%
Notes: I
n
= Rating Plug
I
r
= Long Delay Setting
I
s
= Sensor Rating OPT = Hand Held Programmer (OPTIMizer) BIM = Breaker Interface Module
Setting Tolerance (See time-current curves)Setting Tolerance ±10%Setting Tolerance ±20%Only available with LSIAI
s
(K, L & N-Frame), In(R-Frame, SPB)
Contact factory or Vista for K-Frame availability
Table 3.2 Digitrip OPTIM 550 Trip Unit System Capabilities Overview
11
I.B. 29C891B
Page 23
Effective 11/98
TRIP UNIT TYPE DIGITRIP OPTIM 750
RMS Sensing Yes Programmable Yes
CIRCUIT BREAKERS
Types Series C K, L and N-Frames»` Series C R-Frames SPB Pow-R DSII/DSLII Power Ampere Range 70 - 1200A 800 - 2500A 200 - 5000A 100 - 5000A Interrupting Rating @ 480V 30 thru 100KA 65 thru 100KA 50 thru 150KA 30 thru 200KA
TRIP UNIT ORDERING OPTIONS
LSI
➀➁ No Yes Yes Yes
LSIG
➀➁ Yes Yes Yes Yes
LSIA
Yes Yes Yes Yes
PROTECTION AND COORDINATION
Interchangeable Rating Plug (In) 70-1200A 800-2500A 200-5000A 100-5000A Over-Temperature Trip Yes Yes Yes Yes
LONG DELAY PROTECTION
Long Delay Setting (I
r
) 0.4 - 1.0 x In(0.01 steps) 0.4 - 1.0 x In(0.01 steps) 0.4 - 1.0 x In(0.01 steps) 0.4 - 1.0 x In(0.01 steps)
Long Delay Pickup 116% of I
r
116% of I
r
116% of I
r
105% or I
r
Long Delay Time I2t @ 6 x I
r
2-24 secs (0.10 steps) 2-24 secs (0.10 steps) 2-24 secs (0.10 steps) 2-24 secs (0.10 steps)
Long Delay Time I
4
t @ 6 x Ir(SDT Slope Flat only) 1-5 secs (0.10 steps) 1-5 secs (0.10 steps) 1-5 secs (0.10 steps) 1-5 secs (0.10 steps) Long Delay Thermal Memory (Powered or Unpowered) Yes (programmable) Yes (programmable) Yes (programmable) Yes (programmable) High Load Alarm 0.5 - 1.0 x I
r
0.5 - 1.0 x I
r
0.5 - 1.0 x I
r
0.5 - 1.0 x I
r
SHORT DELAY PROTECTION
Short Delay Pickup 1.5 - 8.0 x Ir(0.1 steps) 1.5 - 8.0 x Ir(0.1 steps) 1.5 - 8.0 x Ir(0.1 steps) 1.5 - 10.0 x Ir(0.1 steps)
(400 - 3000A)
1.5 - 6.0 x I
r
(0.1 steps)
(4000 - 5000A)
Short Delay Time I
2
t @ 8 x I
r
0.1 - 0.5 secs (0.01 steps) 0.1 - 0.5 secs (0.01 steps) 0.1 - 0.5 secs (0.01 steps) 0.1 - 0.5 secs (0.01 steps)
Short Delay Time Flat
0.1 - 0.5 secs (0.01 steps) 0.1 - 0.5 secs (0.01 steps) 0.1 - 0.5 secs (0.01 steps) 0.1 - 0.5 secs (0.01 steps)
Zone Selective Interlocking Yes Yes Yes Yes
INSTANTANEOUS PROTECTION
Instantaneous Pickup
2.0 - 8.0 x I
n
(0.1 steps) 2.0 - 10.0 x In(0.1 steps) 2.0 - 10.0 x In(0.1 steps) 2.0 - 10.0 x In(0.1 steps)
(1600 & 2000A) (400 - 3000A)
2.0 - 6.0 x I
n
(0.1 steps) 2.0 - 6.0 x In(0.1 steps)
(2500A) (4000 & 5000A) Discriminator Yes Yes Yes Yes Override (Fixed Instantaneous)
Yes Yes Yes Yes
GROUND FAULT PROTECTION
Ground Fault Alarm (not to exceed 1200A) 0.2 - 1.0 x Is(0.01 steps) 0.24 - 1.0 x In(0.01 steps) 0.24 - 1.0 x In(0.01 steps) 0.24 - 1.0 x In(0.01 steps) Ground Fault Pickup (not to exceed 1200A)
0.2 - 1.0 x I
s
(0.01 steps) 0.24 - 1.0 x In(0.01 steps) 0.24 - 1.0 x In(0.01 steps) 0.24 - 1.0 x In(0.01 steps)
Ground Fault Delay I
2
t @ 0.62 x In/I
s
0.1 - 0.5 secs (0.01 steps) 0.1 - 0.5 secs (0.01 steps) 0.1 - 0.5 secs (0.01 steps) 0.1 - 0.5 secs (0.01 steps)
Ground Fault Delay Flat 0.1 - 0.5 secs (0.01 steps) 0.1 - 0.5 secs (0.01 steps) 0.1 - 0.5 secs (0.01 steps) 0.1 - 0.5 secs (0.01 steps) Zone Selective Interlocking Yes Yes Yes Yes Ground Fault Memory Yes Yes Yes Yes
SYSTEM MONITORING
Digital Display Yes (Using OPT or BIM) Yes (Using OPT or BIM) Yes (Using OPT or BIM) Yes (Using OPT or BIM) Current Yes Yes Yes Yes Cause of Trip LEDs Yes Yes Yes Yes Magnitude of Trip Information Yes Yes Yes Yes Remote Signal Contacts Yes Yes Yes Yes Power and Energy No No No No Power Quality - Harmonics No No No No Power Factor No No No No
COMMUNICATIONS
IMPACC Yes Yes Yes Yes
TESTING
Testing Method OPT, BIM, IMPACC OPT, BIM, IMPACC OPT, BIM, IMPACC OPT, BIM, IMPACC +
Secondary Injection
Table 3.3 Digitrip OPTIM 750 Trip Unit System Capabilities Overview
No ground fault alarm (A) providedRefer to para. 3-2.3 and Figure 3-4 for detailsSetting Tolerance ±5%Setting Tolerance +0-30%Setting Tolerance +10-40%
Notes: I
n
= Rating Plug
I
r
= Long Delay Setting
I
s
= Sensor Rating OPT = Hand Held Programmer (OPTIMizer) BIM = Breaker Interface Module
Setting Tolerance (See time-current curves)Setting Tolerance ±10%Setting Tolerance ±20%Only available with LSIAI
s
(L & N-Frame), In(R-Frame, SPB, DSII/DSLII)
Contact factory or Vista for K-Frame availability
11
11
I.B. 29C891B
Page 24
Effective 11/98
TRIP UNIT TYPE DIGITRIP OPTIM 1050
RMS Sensing Yes Programmable Yes
CIRCUIT BREAKERS
Types Series C K, L and N-Frames»` Series C R-Frames SPB Pow-R DSII/DSLII Power Ampere Range 70 - 1200A 800 - 2500A 200 - 5000A 100 - 5000A Interrupting Rating @ 480V 30 thru 100KA 65 thru 100KA 50 thru 150KA 30 thru 200KA
TRIP UNIT ORDERING OPTIONS
LSI
➀➁ No Yes Yes Yes
LSIG
➀➁ Yes Yes Yes Yes
LSIA
Yes Yes Yes Yes
PROTECTION AND COORDINATION
Interchangeable Rating Plug (In) 70-1200A 800-2500A 200-5000A 100-5000A Over-Temperature Trip Yes Yes Yes Yes
LONG DELAY PROTECTION
Long Delay Setting (I
r
) 0.4 - 1.0 x In(0.01 steps) 0.4 - 1.0 x In(0.01 steps) 0.4 - 1.0 x In(0.01 steps) 0.4 - 1.0 x In(0.01 steps)
Long Delay Pickup 116% of I
r
116% of I
r
116% of I
r
105% or I
r
Long Delay Time I2t @ 6 x I
r
2-24 secs (0.10 steps) 2-24 secs (0.10 steps) 2-24 secs (0.10 steps) 2-24 secs (0.10 steps)
Long Delay Time I
4
t @ 6 x Ir(SDT Slope Flat only) 1-5 secs (0.10 steps) 1-5 secs (0.10 steps) 1-5 secs (0.10 steps) 1-5 secs (0.10 steps) Long Delay Thermal Memory (Powered or Unpowered) Yes (programmable) Yes (programmable) Yes (programmable) Yes (programmable) High Load Alarm 0.5 - 1.0 x I
r
0.5 - 1.0 x I
r
0.5 - 1.0 x I
r
0.5 - 1.0 x I
r
SHORT DELAY PROTECTION
Short Delay Pickup 1.5 - 8.0 x Ir(0.1 steps) 1.5 - 8.0 x Ir(0.1 steps) 1.5 - 8.0 x Ir(0.1 steps) 1.5 - 10.0 x Ir(0.1 steps)
(400 - 3000A)
1.5 - 6.0 x I
r
(0.1 steps)
(4000 - 5000A)
Short Delay Time I
2
t @ 8 x I
r
0.1 - 0.5 secs (0.01 steps) 0.1 - 0.5 secs (0.01 steps) 0.1 - 0.5 secs (0.01 steps) 0.1 - 0.5 secs (0.01 steps)
Short Delay Time Flat
0.1 - 0.5 secs (0.01 steps) 0.1 - 0.5 secs (0.01 steps) 0.1 - 0.5 secs (0.01 steps) 0.1 - 0.5 secs (0.01 steps)
Zone Selective Interlocking Yes Yes Yes Yes
INSTANTANEOUS PROTECTION
Instantaneous Pickup
2.0 - 8.0 x I
n
(0.1 steps) 2.0 - 10.0 x In(0.1 steps) 2.0 - 10.0 x In(0.1 steps) 2.0 - 10.0 x In(0.1 steps)
(1600 & 2000A) (400 - 3000A)
2.0 - 6.0 x I
n
(0.1 steps) 2.0 - 6.0 x In(0.1 steps)
(2500A) (4000 & 5000A) Discriminator Yes Yes Yes Yes Override (Fixed Instantaneous)
Yes Yes Yes Yes
GROUND FAULT PROTECTION
Ground Fault Alarm (not to exceed 1200A) 0.2 - 1.0 x Is(0.01 steps) 0.24 - 1.0 x In(0.01 steps) 0.24 - 1.0 x In(0.01 steps) 0.24 - 1.0 x In(0.01 steps) Ground Fault Pickup (not to exceed 1200A)
0.2 - 1.0 x I
s
(0.01 steps) 0.24 - 1.0 x In(0.01 steps) 0.24 - 1.0 x In(0.01 steps) 0.24 - 1.0 x In(0.01 steps)
Ground Fault Delay I
2
t @ 0.62 x In/I
s
0.1 - 0.5 secs (0.01 steps) 0.1 - 0.5 secs (0.01 steps) 0.1 - 0.5 secs (0.01 steps) 0.1 - 0.5 secs (0.01 steps)
Ground Fault Delay Flat 0.1 - 0.5 secs (0.01 steps) 0.1 - 0.5 secs (0.01 steps) 0.1 - 0.5 secs (0.01 steps) 0.1 - 0.5 secs (0.01 steps) Zone Selective Interlocking Yes Yes Yes Yes Ground Fault Memory Yes Yes Yes Yes
SYSTEM MONITORING
Digital Display Yes (Using OPT or BIM) Yes (Using OPT or BIM) Yes (Using OPT or BIM) Yes (Using OPT or BIM) Current Yes Yes Yes Yes Cause of Trip LEDs Yes Yes Yes Yes Magnitude of Trip Information Yes Yes Yes Yes Remote Signal Contacts Yes Yes Yes Yes Power and Energy Yes Yes Yes Yes Power Quality - Harmonics Yes Yes Yes Yes Power Factor Yes Yes Yes Yes
COMMUNICATIONS
IMPACC Yes Yes Yes Yes
TESTING
Testing Method OPT, BIM, IMPACC OPT, BIM, IMPACC OPT, BIM, IMPACC OPT, BIM, IMPACC +
Secondary Injection
Table 3.4 Digitrip OPTIM 1050 Trip Unit System Capabilities Overview
No ground fault alarm (A) providedRefer to para. 3-2.3 and Figure 3-4 for detailsSetting Tolerance ±5%Setting Tolerance +0-30%Setting Tolerance +10-40%
Notes: I
n
= Rating Plug
I
r
= Long Delay Setting
I
s
= Sensor Rating OPT = Hand Held Programmer (OPTIMizer) BIM = Breaker Interface Module
Setting Tolerance (See time-current curves)Setting Tolerance ±10%Setting Tolerance ±20%Only available with LSIAI
s
(L & N-Frame), In(R-Frame, SPB, DSII/DSLII)
Contact factory or Vista for K-Frame availability
11
11
I.B. 29C891B
Page 25
Effective 11/98
If it is later determined that the Long Delay Setting (Ir) is to be 140 amperes in lieu of the original 100 amperes. The Long Delay Setting (Ir) can be re-pro­grammed to 0.7 (In) = 0.7 (200) = 140 amperes, the new required Long Delay Setting (Ir).
The re-programming change to the Long Delay Setting (Ir) alters the Short Delay Pickup originally pro­grammed, since the Short Delay Pickup is a function of the Long Delay Setting (Ir). The new Short Delay Pickup = 2.0 (Ir) = 2.0 (140) = 280 amperes. This new Short Delay Pickup may or may not be acceptable. If it isnt, it will also have to be re-programmed.
3-2.3 PROTECTION AND CURVE SHAPING FEATURES
There are three different OPTIM Trip Unit configurations:
LSI (Except on Model 750 and 1050 K, L and N­Frame breakers)
LSIA
LSIG
LSI Configuration
The LSI configuration provides a required long delay pro­tection and a user selectable short delay protection
Figure 3-4 Overcurrent Protective Function Combinations
L
S
I
Required User Selectable Optional
(Either S or I
or Both)
POSSIBLE COMBINATIONS
LI LIG
LS LSG
LSI LSIG
LSIA
and/or instantaneous protection. Modals 750 and 1050 achieve LSI by turning off the “A” feature on the LSIA unit.
LSIA Configuration
The LSIA configuration provides the same protective functions described for the LSI configuration plus it senses ground fault conditions and provides for a local or remote alarm of the condition. It does not trip the cir­cuit breaker due to a ground fault condition. The alarm feature can be turned OFF if desired.
LSIG Configuration
The LSIG configuration provides the same protective functions described for the LSI configuration plus ground fault protection. It senses ground fault conditions and trips the circuit breaker. If a local ground alarm contact is present, it actuates also.
For any of the three configurations described, the short circuit functions (short delay and instantaneous) are user selectable using the OPTIMizer, Breaker Interface Module or Series III Software as follows:
Both short delay and instantaneous enabled
Only short delay enabled
Only instantaneous enabled
Notice: Short delay and instantaneous cannot be dis-
abled at the same time.
The three trip unit configurations are available by circuit breaker type as follows (Tables 3.2 and 3.3):
Series C L and N-Frame (LSIA and LSIG)
Series C K-Frame, R-Frame, SPB Pow-R and
DSII/DSLII (LSI, LSIA and LSIG)
All Digitrip OPTIM Trip Units are available in six overcur­rent protective function combinations of long, short, instantaneous and ground (Figure 3-4). When the pro­tection functions are combined with slope adjustments I4t, I2t or Flat, the Digitrip OPTIM Trip Unit provides the following ten programmable curve shaping possibilities:
Overload
- Long Delay Setting
- Long Delay Time, I2t Response
- Long Delay Time, I4t Response
Short Circuit
- Short Delay Pickup
- Short Delay Time, Flat Response
- Short Delay Time, I2t Response
- Instantaneous
A
G
or
I.B. 29C891B
Page 26
Effective 11/98
Ground Fault
- Ground Fault Pickup
- Ground Fault Delay, Flat Response
- Ground Fault Delay, I2t Response
The ten curve shaping possibilities are illustrated in Figure 3-5. Each portion of the curve is discussed and illustrated individually in the following paragraphs (3-2.4, 3-2.5, 3-2.6 and 3-2.7).
Notice: For the sake of simplification, many curve illus-
trations in this section will be represented as single line curves. Keep in mind, however, that a time-current curve in reality is represented by a band of minimum and maximum values, not a single line (Figures 3-1 and 3-5).
3-2.4 LONG DELAY PROTECTION
All Digitrip OPTIM Trip Units provide programmable long delay protection consisting of (Tables 3.2 and 3.3 and Figure 3-4):
Long delay current setting
Long delay time setting
Long delay thermal memory
TIME
CURRENT
1
3
5
6
4A
7A
7B
4B
2B
2A
Note: Arrows indicate direction of curve movement
Figure 3-5 Typical OPTIM Trip Unit Time-Current Curve (10 Curve Shaping Adjustments)
OVERLOAD AND SHORT CIRCUIT
1. Long Delay Setting
2A. Long Delay Time I
2
t
2B. Long Delay Time I
4
t
SHORT CIRCUIT
3. Short Delay Pickup 4A. Short Delay Time Flat Response 4B. Short Delay Time I
2
t Response
5. Instantaneous
GROUND FAULT
6. Ground Fault Pickup 7A. Ground Fault Delay Flat Response 7B. Ground Fault Delay I
2
t Response
High load alarm (in software with IMPACC, and dis­creet contact on R, SPB and DSII breakers)
Long Delay Current Setting (Ir)
The long delay current setting (Ir) is established as a multiple of the rating plug value (In). The programmable range is as follows:
0.4 to 1.0 times (In) in 0.01 increments
Example: A 600 ampere Series C L-Frame circuit break-
er with a 400 ampere rating plug installed and the long delay current setting programmed to 160 amperes results in a 40% setting.
The long delay current setting (I
r
) for OPTIM Trip Units is the nominal continuous current rating of the breaker. The breaker will carry this maximum amount of current (Ir) continuously without tripping. It is not the actual long delay pickup point. The breaker will pickup and ultimately trip at a current level that is nominally higher than the Long Delay Current Setting (Ir):
For DSII/DSLII, Long Delay Pickup is calibrated for nominally 105% (Ir)
For K, L, N and R-Frames and SPB, the calibration is for nominally 116% (Ir)
I.B. 29C891B
Page 27
Effective 11/98
Long delay pickup, which is determined from the time­current curves, establishes the current level at which the trip units long time tripping function begins timing. If after a programmed amount of time the current condition still exists, the trip units tripping system is enabled.
Alarm indicators are provided as follows:
K, L and N-Frame Breakers
- BIM Contacts
- LED (Long Delay Pickup) flashes on breaker trip unit
- Ground Alarm Contact (optional accessory for 750 and 1050 units)
R-Frame, SPB and DSII/DSLII Breakers
- BIM Contacts
- LED (Long Delay Pickup) flashes on breaker trip unit
- Discrete Contacts
Figure 3-6 graphically illustrates how the long delay set­ting portion of the overall curve can be moved horizon­tally and independently by means of the programmable settings.
Long Delay Time Setting (I2t or I4t Slopes)
The long delay time setting is established at 6 times the long delay current setting (6 x Ir). This is the reference point where the programmed long delay time setting is fixed on the time-current curve.
TIME
CURRENT
Note: Long Delay Time Setting represented by dotted lines
Figure 3-7 Typical Long Delay Time Adjustment (I2t) Response
TIME
CURRENT
Note: Long Delay Setting represented by dotted lines
Figure 3-6 Typical Long Delay Setting Adjustment
The long delay time setting is programmable to an I2t or an I4t slope over a wide range of times for all OPTIM Trip Units as follows:
I2t Slope - 2 to 24 seconds in increments of 0.10 secs.
I4t Slope - 1 to 5 seconds in increments of 0.10 secs.
Notice: (1) When an I4t slope is programmed for the
long delay time setting, the short delay time setting must be set to a FLAT slope.
(2) When an I2t slope is programmed for the
long delay time setting, the short delay time setting may be set to FLAT or I2t.
The long delay time setting is used to establish the amount of time a sustained overload condition will be carried before the circuit breaker trips. Figures 3-7 and 3-8 graphically illustrate how the long delay time portion of the overall curve can be moved vertically and inde­pendently by means of the programmable settings.
Long Delay Thermal Memory
All Digitrip OPTIM Trip Units are provided with a selec­table (powered or unpowered) thermal memory to pro­tect against cumulative overheating should a number of overload conditions occur in quick succession.
I.B. 29C891B
Page 28
Effective 11/98
Notice: Keep in mind during testing that a faster trip time
may be observed due to the cumulative Thermal Memory Effect (powered or unpowered).
Both the powered and unpowered Thermal Memory may be enabled or disabled via the OPTIMizer, BIM or IMPACC computer.
High Load Alarm
A high load phase and neutral alarm is provided on all OPTIM Trip Units to signal a high load condition. The programmable range is as follows:
0.5 to 1.0 times (Ir)
High Load Alarm indicators are provided as follows:
IMPACC on all OPTIM units with communications
L and N-Frame Breakers
- BIM Contacts
R-Frame, SPB and DSII/DSLII Breakers
- BIM Contacts
- Automatic Trip Relay Contact
3-2.5 SHORT DELAY PROTECTION
Short delay protection is selectable with all Digitrip OPTIM Trip Units. It can be selected in combination with
instantaneous protection or without instantaneous pro­tection. Either both, one or the other (short or instanta­neous) must always be provided (Tables 3.2 and 3.3 and Figure 3-4). Short delay protection can consist of the following:
Short delay pickup setting
Short delay time setting (I2t Slope)
Short delay time setting (Flat Slope)
Zone Selective Interlocking (Model 750 and 1050 only)
Short Delay Pickup Setting
The short delay pickup setting establishes the current level at which the trip units short time tripping function begins timing. It is programmable as a multiple of the long delay current setting (Ir). The programmable range depends on the circuit breaker type as follows:
Series C K, L, N and R-Frames
- 1.5 to 8.0 times (Ir) in 0.1 increments
SPB Systems Pow-R
- 1.5 to 8.0 times (Ir) in 0.1 increments
(400-3000 ampere frames)
- 1.5 to 6.0 times (Ir) in 0.1 increments (4000/5000 ampere frames)
TIME
CURRENT
Note: Long Delay Time Setting represented by dotted lines
Figure 3-8 Typical Long Delay Time Adjustment (I4t) Response
TIME
CURRENT
Note: Short Delay Pickup represented by dotted lines
Figure 3-9 Typical Short Delay Pickup Adjustment
I.B. 29C891B
Page 29
Effective 11/98
DSII/DSLII
- 1.5 to 10.0 times (Ir) in 0.1 increments
Figure 3-9 graphically illustrates how the short delay pickup portion of the overall curve can be moved hori­zontally and independently by means of the programma­ble settings.
Short Delay Time Setting (I2t or Flat Slopes)
The short delay time setting is programmable from 0.1 to 0.5 seconds in 0.01 increments for all OPTIM Trip
Units. The short delay time setting is programmable to an I2t or a Flat slope. The 0.1 to 0.5 second setting is the nominal trip time at 8.0 times Irfor I2t slope.
Notice: (1) When an I4t slope is programmed for the
long delay time setting, the short delay time setting must be set to a FLAT slope.
(2) When an I2t slope is programmed for the
long delay time setting, the short delay time setting may be set to FLAT or I2t.
The short delay time setting establishes the amount of time a short-circuit will be carried before the circuit breaker trips. Figures 3-10 and 3-11 graphically illus­trate how the short delay time portion of the overall
TIME
CURRENT
Note: Short Delay Time Setting represented by dotted lines
Figure 3-11 Typical Short Delay Time Adjustment, (I2t) Response
TIME
CURRENT
Note: Short Delay Time Setting represented by dotted lines
Figure 3-10 Typical Short Delay Time Adjustment, Flat Response
curve can be moved vertically and independently by means of programmable settings.
Zone Selective Interlocking (OPTIM Models 750 and
1050)
Zone selective interlocking is provided for the short delay and the ground fault delay tripping functions for improved system protection. The Digitrip OPTIM Trip Unit zone selective interlocking feature is compatible with Digitrip Trip Units, Model 510 and higher.
The zone selective interlocking feature is a means of communications over a pair of wires between two or more compatible trip units. Zone selective interlocking makes it possible for programmed trip unit settings to be altered automatically to respond to different fault condi­tions and locations, thereby localizing the effects of an interruption and providing positive coordination between circuit breakers.
Figure 3-12 illustrates a typical ground fault protection scheme using zone selective interlocking. For faults out­side the zone of protection, the trip unit on the circuit breaker nearest the fault sends an interlocking signal to the trip unit of the up-stream circuit breakers. This inter­locking signal restrains immediate tripping of the upstream circuit breakers until their programmed coordi-
I.B. 29C891B
Page 30
Effective 11/98
nation times are reached. Thus zone selective interlock­ing applied correctly can reduce damage due to short circuit or ground fault conditions.
Refer to the wiring diagrams presented in Table A.1 of Appendix A for specific connection schemes. For more detailed application information, contact Cutler-Hammer.
3-2.6 INSTANTANEOUS PROTECTION
Instantaneous protection is selectable with all Digitrip OPTIM Trip Units. It can be selected in combination with short delay protection or without short delay protection. One or the other (instantaneous or short) must always be selected (Tables 3.2 and 3.3 and Figure 3-4). Instantaneous protection is provided via:
Instantaneous Pickup
Two additional functions are available to trip the circuit breaker with no intentional delay under high short circuit conditions:
Discriminator
Instantaneous Override
Instantaneous Pickup
The instantaneous pickup setting establishes the current level at which the trip units instantaneous tripping function will trip the circuit breaker with no intentional time delay. It is programmable as a multiple of the plug rating value (In). The programmable range depends on the circuit breaker type as follows:
Series C K, L and N-Frames
- 2.0 to 8.0 times (In) in 0.1 increments
Series C R-Frame
- 2.0 to 10.0 times (In) in 0.1 increments
(1600/2000 ampere frames)
- 2.0 to 6.0 times (In) in 0.1 increments
(2500 ampere frame)
SPB Systems Pow-R
- 2.0 to 10.0 times (In) in 0.1 increments
(400-3000 ampere frames)
- 2.0 to 6.0 times (In) in 0.1 increments
(4000/5000 ampere frames)
DSII/DSLII
- 2.0 to 12.0 times (In) in 0.1 increments
Load
Breaker
Number 3
Breaker
Number 2
Breaker
Number 1
Zone 1
Zone 2
Zone 3
Zone Interlock Wiring
Ground Fault Setting: 1200A Pickup
0.5 Secs. Time Delay
Ground Fault Setting: 600A Pickup
0.3 Secs. Time Delay
Ground Fault Setting: 300A Pickup No Time Delay
Fault 2
Fault 3
Fault 1
Figure 3-12 Multi-layer Ground Fault Protection Scheme Using Zone Selective Interlocking
I.B. 29C891B
Page 31
Effective 11/98
Figure 3-13 graphically illustrates how the instantaneous pickup portion of the overall curve can be moved hori­zontally and independently by means of the programma­ble settings.
Discriminator
A selectable discriminator circuit is provided on all OPTIM Trip Units. This prevents the circuit breaker from remain­ing closed for the entire duration of the programmed short delay time, if the breaker is closed on a high short circuit fault with the instantaneous protective function disabled.
The discriminator circuit (high initial current release) is pre­set at 11 times the rating plug value (11 x In). It is active for approximately ten cycles following the initial current flow through the circuit breaker, and is reset whenever the load current falls below 10% of the circuit breaker frame or current sensor rating.
In the event the circuit breaker is not intended to trip out on a circuit whose current could initially be higher than 11 x In, it is possible to make the discriminator inactive. If a circuit breaker would close onto a high short-circuit current in this situation, type LS or LSG trip units would rely on the short delay protection function. If the fault current exceeds the short-time withstand current capa­bility of the circuit breaker, override protection circuitry would trip the circuit breaker without delay.
Override (Fixed Instantaneous)
An override (fixed instantaneous) circuit is included in all circuit breakers except DSII and DSLII circuit breakers. It protects against a short-circuit current that exceeds the short-time withstand current capability of the circuit breaker. The override circuit is set to a value no greater than the short time withstand current rating of the circuit breaker in which the override circuitry is installed. Since the specific values vary by circuit breaker type and rat­ing, refer to the applicable time-current curves for the value associated with a particular circuit breaker.
3-2.7 GROUND FAULT PROTECTION
Ground fault protection is optional with all OPTIM Trip Units. It can be provided in a number of combinations with long, short and instantaneous. When ground fault trip protection is not provided, a ground fault alarm may be specified, (Tables 3.2 and 3.3 and Figure 3-4). The available trip unit options by circuit breaker type are as follows:
Series C K, L and N-Frame and SPB and DSII Circuit
Breakers
- LSIG (with ground fault trip)
- LSIA (with ground fault alarm where A may be dis-
abled)
Model 550 Series C K, L, and N-Frame or all SPB and
DSII Circuit Breakers
- LSI (without ground fault trip or alarm)
Ground fault protection and other related features are as follows:
Ground fault alarm
Ground fault pickup
Ground fault delay (I2t Slope)
Ground fault delay (Flat Slope)
Zone selective interlocking (Models 750 and 1050 only)
Ground fault memory
When an OPTIM trip assembly includes ground fault protection, the distribution system characteristics, such as system grounding, number of sources, number and location of ground points, must be considered. The manner and location in which the circuit breaker is con­nected to the system should also be considered.
OPTIM units with ground fault protection already have all the necessary equipment for a 3-phase 3-wire grounded system. This basic mode for ground fault sensing employs a residual sensing scheme which vec-
TIME
CURRENT
Note: Instantaneous Pickup represented by dotted lines
Figure 3-13 Typical Instantaneous Pickup Adjustment
I.B. 29C891B
Page 32
Effective 11/98
torially sums the outputs of the individual phase current sensors. As long as the vectorial sum is zero, no ground fault exists.
If the system is 4-wire and a neutral conductor exists, it is necessary to use an additional sensor for the purpose of properly accounting for this neutral current in the ground fault scheme. This sensor is mounted separately on the neutral conductor at the point where the neutral conduc­tor connects to the neutral bus. This sensor is usually the same as the phase sensors internal to the circuit breaker. The sensor does not have to be ordered separately since it is included when an LSIA or LSIG version is ordered.
On R-Frame, SPB and DSII circuit breakers, zero sequence ground current measurement is alternatively available.
Ground Fault Alarm
A programmable ground fault alarm alerts a user of a ground fault condition without tripping the circuit break­er. In addition to being programmable, the ground fault alarm can be enabled or disabled. A red Ground Fault Alarm LED on the front of the trip unit will indicate the presence of a ground fault condition that exceeds the programmed setting (Figure 3-14).
The ground fault alarm contact is energized when the ground current exceeds the ground fault pickup setting continuously for a time in excess of the ground fault delay setting. Refer to Tables 3.2 and 3.3 for program­mable values.
Ground Fault Pickup
The ground fault pickup establishes the current level at which the trip units ground fault function begins timing. The pickup settings are the same for both ground fault trip (LSIG) units and ground fault alarm (LSIA) units. These settings are programmable over a range of fac­tors by circuit breaker type as follows:
Series C K, L and N-Frame Circuit Breakers
- 0.2 to 1.0 times sensor rating (I
s
) in 0.01 increments
(not to exceed 1200A)
Series C R-Frame Circuit Breakers
- 0.24 to 1.0 times rating plug (I
n
) in 0.01 increments
(not to exceed 1200A)
SPB Pow-R and DSII/DSLII Circuit Breakers
- 0.24 to 1.0 times rating plug (In) in 0.01 increments
(not to exceed 1200A)
Figure 3-15 graphically illustrates how the ground fault pickup portion of the overall curve can be moved horizon­tally by means of the programmed settings.
Ground Fault Time Delay (I2t or Flat Slopes)
The ground fault time delay setting is programmable with an I2t or a Flat slope for all ground fault type OPTIM Trip Units as follows:
0.1 to 0.5 seconds in 0.01 increments at 0.62 times rating plug (In)
(for I2t slope)
0.1 to 0.5 seconds in 0.01 increments
(for Flat slope)
Figures 3-16 and 3-17 graphically illustrate how the ground fault delay portion of the overall curve can be moved vertically by means of the programmed settings.
Zone Selective Interlocking (Models 750 and 1050)
Zone selective interlocking is provided for the short delay time and the ground fault delay tripping functions for improved system coordination. Refer to paragraph 3-
2.5 under Zone Selective Interlocking and Figure 3-12
for additional details.
Ground Fault Memory
Ground faults may be sporadic in nature. As such, damag­ing ground faults can occur and then subside in less time than the programmed time for tripping the circuit breaker. Should this type of cyclical ground fault condition persist, the cumulative effect could result in equipment damage.
Figure 3-14 Ground Fault Alarm LED
I.B. 29C891B
Page 33
Effective 11/98
To protect against the the cyclical ground fault condition just described, all OPTIM Trip Units with ground fault protection are provided with a ground fault memory function. The time above pickup is retained in memory and decays slowly. If another ground fault, high enough to cause pickup, occurs before the time in memory total­ly decays, the new time adds to the memorized time. It is this cumulative time that determines whether the cir­cuit breaker will or will not trip on these types of cyclical ground fault conditions.
3-2.8 TIME-CURRENT CURVES
The specific time-current curves applicable to all Digitrip OPTIM Trip Units are identified in Appendix A, Table
A.1. Contact Cutler-Hammer for a specific curve.
3-3 SYSTEM MONITORING
Digitrip OPTIM Trip Units provide an electrical distribution system with superior programmable protection and coor­dination along with advanced warning capabilities, sys­tem diagnostics, monitoring and communications. A sig­nificant part of Digitrip OPTIMs effectiveness is a result of its system monitoring capabilities. A comprehensive list of
TIME
CURRENT
Note: Ground Fault Delay represented by dotted lines
Figure 3-17 Typical Ground Fault Time Delay Adjustment, (I2t) Response
TIME
CURRENT
Note: Ground Fault Delay represented by dotted lines
Figure 3-16 Typical Ground Fault Time Delay Adjustment, Flat Response
TIME
CURRENT
Note: Ground Fault Pickup represented by dotted lines
Figure 3-15 Typical Ground Fault Pickup Adjustment
Minimum/Maximum magnitudes all monitored currents
Automatic Trip Condition
When a system condition results in an automatic trip, the OPTIM Trip Unit monitors and stores in non-volatile memory the reason for the trip and all of the following:
Magnitude phase A, B and C trip currents
Magnitude ground trip current
Magnitude neutral trip current
3-3.3 REMOTE SIGNAL CONTACTS
Series C R-Frame, SPB Pow-R and DSII/DSLII Contacts (Models 750 and 1050)
A power relay module, described in paragraph 2-7.2, is mounted internally to Series C R-Frame, SPB Pow-R and DSII/DSLII circuit breakers to provide control power and relay contacts for remote signaling.
Series C K, L and N-Frame Contacts
The Series C L and N-Frame breakers provide alarm contacts by either of two options:
A remotely mounted ground fault indicator module may be hard wired directly to the breaker with Models 750 and 1050. This ground fault indicator module pro­vides dedicated alarming contacts for ground fault conditions only. Refer to Table 2.2 for contact ratings and Table A.1 of Appendix A for the appropriate wiring diagrams.
The remotely mounted Breaker Interface Module (BIM) has contacts that can be configured to operate under specific conditions. The signaling of the appro­priate contact operation is done via an IMPACC com­munications link between the breaker and the Breaker Interface Module. Refer to the Breaker Interface Module instruction book (I.B. 29C893) for specifics on the programming and ratings of these contacts.
UNEXPECTED SIGNALS TO CLOSE OR TRIP A CIR­CUIT BREAKER FROM A REMOTE LOCATION VIA THE COMMUNICATIONS NETWORK CAN CAUSE PERSONAL INJURY TO PERSONNEL WORKING IN THE IMMEDIATE VICINITY OF THE CIRCUIT BREAK­ER. PERMISSIVE CONTROL SWITCHES OR OTHER MEANS SHOULD BE PROVIDED LOCALLY AT THE
I.B. 29C891B
Page 34
Effective 11/98
WARNING
metered parameters are monitored and then displayed over the OPTIM information system. Local LEDs are used to indicate a number of conditions and/or operations. The LEDs are complemented by trip event information stored in non-volatile memory. Information can be accessed via the OPTIMizer Hand Held Programmer, Breaker Interface Module, or over the IMPACC System.
System monitoring encompasses the following three broad categories:
Load Current Monitoring
Power and Energy Monitoring
Power Quality Monitoring
Refer to Tables 3.2 and 3.3 for a general overview of the features included in system monitoring. The expect­ed accuracies associated with displayed parameters are also summarized in Tables 3.2 and 3.3.
3-3.1 DISPLAYS AND LED INDICATORS
All information in the trip unit may be accessed by using one or more of the following devices:
OPTIMizer Hand Held Programmer (I.B. 29C892)
Breaker Interface Module (I.B. 29C893)
Remote Computer via IMPACC (I.B. 29C890)
For detailed information on the use of a specific device, refer to the instruction book (IB) reference indicated next to the particular display device.
The trip units information system utilizes front mounted LEDs to indicate a number of trip unit functions, such as mode of trip. Refer to paragraphs 2-4.1 (K, L and N­Frame type trip units) and 2-5.1 (R-Frame, SPB and DSII/DSLII type trip units) for detailed information on the LEDs provided.
3-3.2 NORMAL SERVICE/AUTOMATIC TRIP CURRENT MONITORING
Digitrip OPTIM Trip Units monitor a variety of currents for both normal service and automatic trip conditions. The value of currents are displayed in amperes by one of the devices outlined in paragraph 3-3.1.
Normal Service Condition
During normal service conditions with the circuit breaker closed, the OPTIM Trip Unit monitors all of the following:
Present magnitude phase A, B and C currents
Present magnitude ground current or present magni-
tude neutral current
I.B. 29C891B
Page 35
Effective 11/98
CIRCUIT BREAKER FOR MAINTENANCE PERSON­NEL TO USE IN CONTROLLING REMOTE CLOSE OR TRIP SIGNALS.
The OPTIM Trip Unit can respond to commands from a remote master computer to trip the circuit breaker remote­ly. In addition, the trip unit can respond to a close com­mand from a remote master computer. Upon receipt of a command to close the circuit breaker, the reclose relay is energized for 2 seconds. This contact closure results in the circuit breaker closing, if the circuit breaker is equipped with the applicable optional electrical operator or spring release feature.
3-3.4 POWER AND ENERGY MONITORING
Only Digitrip OPTIM 1050 Trip Units can monitor and then display power and energy values via the OPTIMizer Hand Held Programmer, Breaker Interface Module or a remote computer. The displayed informa­tion is as follows:
Power (Present Demand) in kilowatts (kW)
Peak Demand in kilowatts (kW)
Total Energy in kilowatthours (kWh)
Forward Energy in kilowatthours (kWh)
Reverse Energy in kilowatthours (kWh)
An OPTIM 1050 Trip Unit installed in a Series C K, L or N-Frame Circuit Breaker uses the breakers current sen­sors and an externally mounted potential transformer module to compute power and energy values (Figure 2- 14 and paragraph 2-7.1). The values are not non­volatile in memory.
An OPTIM 1050 Trip Unit installed in a Series C R­Frame, SPB Pow-R or DSII/DSLII Circuit Breaker uses the breakers current sensors and a potential trans­former module mounted internally to the circuit breaker to compute power and energy values (Figure 2-14 and paragraph 2-7.2). The values are not
non-volatile in
memory.
Power (Present Demand)
The power value, also referred to as present demand, is displayed in kilowatts (kW). It is a power value averaged over approximately one second.
Peak Demand
The peak demand, displayed in kilowatts (kW), is based on a sampling window of fifteen (15) minutes. Power is repeatedly averaged over this interval and the maximum 15 minute average is displayed as peak demand. When the trip unit is first energized, there is a delay of 15 min-
utes before the first non-zero value is displayed. The peak demand value displayed remains and is not changed until a higher peak demand is calculated in a subsequent 15 minute window.
Energy
Energy values are displayed in kilowatthours (kWh), and are a summation of the average power over time. Energy values are updated approximately once a second.
Forward energy is based on load current flow from theLine side to the Load side of the breaker.
Reverse energy is based on load current flow from theLoad side to the Line side of the breaker.
3-3.5 POWER QUALITY (HARMONICS) MONITORING
Only Digitrip OPTIM 1050 Trip Units can calculate and dis­play via the OPTIMizer Hand Held Programmer, Breaker Interface Module or a remote computer power quality information. The displayed information is as follows:
THD magnitude of phase A, B and C currents
THD magnitude of ground or neutral currents
% harmonic content phase A, B and C currents (to
27th harmonic)
% harmonic content ground or neutral currents (to 27th harmonic)
THD (Total Harmonic Distortion) indicates the amount of harmonic current present as a percentage of the RMS value of the 60 Hz component of the line current. This measure of distortion can be useful in a troubleshooting mode to detect individual circuit breaker load currents that could lead to system overheating problems and subsequent early equipment failure.
3-3.6 POWER FACTOR
Digitrip OPTIM 1050 Trip Units calculate the system power factor, which is a unit-less ratio of real power (kW) to apparent power (kVA). The power factor is dis­played by the OPTIMizer Hand Held Programmer, Breaker Interface Module or a remote computer. A pos­itive number indicates a lagging current.
3-4 COMMUNICATIONS
Model 750 and 1050 units and Model 550 with field upgrade to IMPACC have the ability to communicate both information and control signals via the INCOM Communications Network. INCOM interconnects micro­processor based electrical distribution and control prod-
DE-ENERGIZE THE CIRCUIT, REMOVE, DISCON­NECT OR MOVE THE CIRCUIT BREAKER TO AN APPROPRIATE TEST POSITION BEFORE PER­FORMING MAINTENANCE OR TESTS.
DO NOT ATTEMPT TO PERFORM DIELECTRIC (OR HIGH POT OR HIGH VOLTAGE) WITHSTAND TESTS ON THE CIRCUIT BREAKER WHILE THE VOLTAGE DISCONNECT PLUG TO THE POTENTIAL TRANS­FORMER MODULE IS INSTALLED FOR R-FRAME, SPB AND DSII/DSLII BREAKERS. FOR L AND N­FRAME BREAKERS, REMOVE THE FUSES FROM THE PTM BEFORE HIPOT TESTING (FIGURE 2-14). POTENTIAL TRANSFORMER MODULE AND/OR TRIP UNIT DAMAGE OR FAILURE CAN RESULT FROM ENERGIZING THE POTENTIAL TRANS­FORMER MODULE AT MORE THAN 600 VOLTS.
VERIFY THAT NO VOLTAGE IS PRESENT ON THE CIRCUIT BREAKER BEFORE REMOVING THE VOLTAGE DISCONNECT PLUG OR FUSES. REMOVE THE VOLTAGE DISCONNECT PLUG OR FUSES TO ISOLATE THE POTENTIAL TRANS­FORMER MODULE BEFORE PERFORMING ANY VOLTAGE TESTS ON THE CIRCUIT BREAKER. REINSTALL THE PLUG OR FUSES ONLY AFTER ALL VOLTAGE TESTS HAVE BEEN COMPLETED AND CONFIRM THAT NO VOLTAGE IS PRESENT ON THE CIRCUIT BREAKER.
I.B. 29C891B
Page 36
Effective 11/98
Figure 3-18 Typical Waveform and Harmonic Display
ucts with remote personal computers into a comprehen­sive information and control communications network. The integral communications capability of OPTIM Trip Units permits the receiving device to be the following:
Breaker Interface Module only
Remote Master Computer only
Remote Master Computer with a Breaker Interface
Module
Refer to paragraph 1-3 and Figure 1-9 for additional infor­mation on sub-network and network communications. In addition, Section 3 of Instruction Book 29C890 (Overview of Digitrip OPTIM Trip Unit System) presents more information on communications with a remote master computer. Refer to paragraph 4-6 of Instruction Book 29C893 (Breaker Interface Module) for additional information concerning communications with the Breaker Interface Module.
3-4.1 IMPACC
All OPTIM Trip Unit programming, configuration, advance warning, diagnostic, monitoring, and control capabilities can be accessed from a remote master computer using IMPACC Series III software. Other software packages are also available.
Custom Billing Software, a stand alone application specific software package, provides the capabilities to determine energy usage data by individually monitored departments in a facility. It can then create a bill based on this data.
Waveform and harmonic display software is capable of performing a waveform capture of phase currents as well as ground or neutral (Figure 3-18). In addition, total harmonic distortion (THD) and individual harmonic con­tents can be displayed.
Refer to Section 3 of Instruction Book 29C890 (Over­view of Digitrip OPTIM Trip Unit System) for more detailed information on communications with IMPACC.
3-5 TESTING
DO NOT ATTEMPT TO INSTALL, TEST OR PER­FORM MAINTENANCE ON EQUIPMENT WHILE IT IS ENERGIZED. DEATH OR SEVERE PERSONAL INJURY CAN RESULT FROM CONTACT WITH ENERGIZED EQUIPMENT.
WARNING
I.B. 29C891B
Page 37
Effective 11/98
TESTING A CIRCUIT BREAKER UNDER TRIP CON­DITIONS WHILE IN SERVICE AND CARRYING LOAD CURRENT, WHETHER DONE BY LOCAL OR REMOTE MEANS, IS NOT RECOMMENDED.
ANY TRIPPING OPERATION WILL CAUSE A DIS­RUPTION IN SERVICE AND POSSIBLE PERSONAL INJURY RESULTING FROM UNNECESSARY SWITCHING OF CONNECTED EQUIPMENT.
TESTING OF A CIRCUIT BREAKER THAT RESULTS IN TRIPPING OF THE CIRCUIT BREAKER SHOULD BE DONE ONLY WITH THE CIRCUIT BREAKER IN A TEST OR DISCONNECTED CELL POSITION, OR WHILE REMOVED TO A TEST BENCH.
Digitrip OPTIM 550, 750 and 1050 Trip Units have a test capability. No-Trip and Trip tests can be performed using any of the following:
OPTIMizer Hand Held Programmer (Figure 1-6 and I.B. 29C892))
Breaker Interface Module (Model 550 with IMPACC kit) (Figure 1-7 and I.B. 29C893)
Remote computer/IMPACC software (Figure 1-8 and I.B. 29C890)
Refer to the applicable instruction book for information on performing tests using one of the outlined methods.
3-5.1 SECONDARY INJECTION TESTING
A test current may be injected into the secondary trans­former terminals (5A level) for DSII/DSLII circuit break­ers only. For K, L, N and R-Frame and SPB Pow-R cir­cuit breakers, these terminals are either not present or not accessible.
DSII and DSLII Type Power Circuit Breakers have a field test kit receptacle that can be used for secondary injection testing to test OPTIM Trip Units. With the Auxiliary Power Module installed, the circuit breaker can be tested using secondary currents provided by an Amptector Trip Unit Test Kit. Refer to supplemental DSII/DSLII Circuit Breaker information in Table A.1 of Appendix A for secondary injection testing details.
3-5.2 WHEN TO TEST
Tests can be performed with the circuit breaker in the Connected position while carrying load current.
However, as stated in the CAUTION at the beginning of this section, good practice will limit circuit breaker in-ser­vice Trip tests to maintenance periods during times of minimum load conditions. Testing is recommended with the circuit breaker out of its cell or in an appropriate Test, Disconnected or Removed cell positions.
Notice: Since time-current settings are based on
desired system coordination and protection schemes, the protection settings selected and programmed should not be altered during or as a part of any routine test sequence.
3-5.3 CONDUCTING TESTS
CIRCUIT BREAKER OPERATING MECHANISMS OPEN AND CLOSE THE MOVING PARTS QUICKLY AND WITH VERY HIGH ENERGY. TOUCHING THE MOVING PARTS DURING OPERATION COULD RESULT IN SERIOUS BODILY INJURY. KEEP CLOTHING AND ALL PARTS OF THE BODY WELL AWAY FROM ALL MOVING PARTS. IN ADDITION, FOLLOW ALL INSTRUCTIONS GIVEN FOR TESTING A SPECIFIC TYPE CIRCUIT BREAKER IN THE APPROPRIATE INSTRUCTIONAL MATERIAL FOR THAT CIRCUIT BREAKER.
Notice: Testing will not be permitted to proceed if there
is greater than the following per unit of current flowing on a phase or ground circuit:
• No-Trip Test
- >1.0 phase or 0.2 ground
• Trip Test
- >0.5 phase or 0.2 ground
The maximum permitted current value can be determined by multiplying the appropriate per unit value times the ampere rating of the installed rating plug.
The Digitrip OPTIM test capability can be used to per­form No-Trip and Trip tests. All testing requires control power, except for No-Trip testing with the OPTIMizer Hand Held Programmer. This testing can be accom­plished using the internal battery power of the OPTIM­izer. Control power, depending on the testing method, can be supplied by an Auxiliary Power Module or by aux­iliary power supplied to the circuit breaker (Figure 3-19 and paragraph 2-7). The auxiliary power is required to activate the breakers flux transfer shunt trip.
CAUTION
WARNING
I.B. 29C891B
Page 38
Effective 11/98
Notice: Basic protection functions are not affected dur-
ing the performance of testing procedures.
Before starting a test sequence, check to be sure that the Operational Status LED on the face of the OPTIM Trip Unit is blinking at approximately a 1 second on-off duty cycle, indicating power is being applied to the trip unit and it is functioning normally (Figures 2-4 and 2-10). In the event that the LED is not blinking at this rate, check to be sure that control power is available or the battery in the OPTIMizer Hand Held Programmer is good.
When performing tests, keep in mind that different com­binations of protection features can contribute to the results of the testing, and be the cause of unexpected tripping actions. Long delay thermal memory or
ground fault memory, for example, could result in an unexpected tripping action. Paragraphs 3-2.4 and 3-
2.7 should be reviewed if there are any questions.
Keep in mind that the Trip Reset pushbutton located on the front of the trip unit will have to be pushed to reset trip unit conditions after a test is completed that causes the circuit breaker to trip and LED indicators to be lit (Figures 2-4 and 2-10).
3-5.4 PERFORMANCE TESTING FOR GROUND FAULT TRIP UNITS
Code Requirements
The National Electrical Code under Article 230-95-C requires that any ground fault protection system be per­formance tested when first installed. The test shall be conducted in accordance with approved instructions provided with the equipment. A written record of this test shall be made and available to the authority having inspection jurisdiction.
Standards Requirements
As a follow-up to the basic performance requirements stipulated by the N.E.C. in Section 6.2.1, UL Standards No. 1053 requires that certain minimum instructions must accompany each ground fault protection system. The following article plus the test record form illustrated in Figure 3-21 are intended to satisfy this requirement.
General Test Instructions
The interconnected system shall be evaluated in accor­dance with the equipment assembler’s detailed instruc- tions by qualified personnel.
The polarity of the neutral sensor connections, if used, must agree with the equipment assemblers detailed instructions to avoid improper operations following apparently correct simulated test operations. Where a question exists, consult the specifying engineer and/or equipment assembler.
The grounding point of the system shall be verified to determine that ground paths do not exist that would bypass the sensors. The use of high voltage testers and resistance bridges may be used.
Figure 3-19 Auxiliary Power Module
I.B. 29C891B
Page 39
Effective 11/98
GROUND FAULT TEST RECORD FORM
Ground Fault Test Record should be Retained by Those in Charge of the Buildings Electrical Installation in order to be available to the Authority having Jurisdiction.
TEST DATE CIRCUIT BREAKER RESULTS
NUMBER
Figure 3-21 Typical Performance Test Record Form
I.B. 29C891B
Page 40
Effective 11/98
4-3.1 BEFORE POWER APPLICATION
STARTUP PROCEDURES MUST BE PERFORMED BY QUALIFIED PERSONNEL WHO ARE FAMILIAR WITH DIGITRIP OPTIM TRIP UNITS, THE LOW VOLT­AGE CIRCUIT BREAKERS IN WHICH THEY ARE APPLIED, AND ALL OTHER ASSOCIATED ELECTRI­CAL AND/OR MECHANICAL EQUIPMENT. FAILURE TO OBSERVE THIS WARNING COULD RESULT IN PERSONAL INJURY, DEATH AND/OR EQUIPMENT DAMAGE.
After all installation wiring is complete and before power is applied to any equipment, perform the following steps:
Step 1: Verify that all wiring is correct as shown on the
applicable wiring diagrams and/or wiring plan drawings.
Step 2: Remove and discard the factory default set-
tings label covering the programming port on each trip unit.
Step 3: Verify that a correct rating plug is securely
installed in each trip unit.
Notice: Mechanical rejection means will prevent the
installation of a rating plug in a trip unit for which it was not intended.
Step 4: Press the battery test/check pushbutton. The
associated green LED should light. Refer to paragraph 5-4.1 for specific assistance.
Step 5: Use the OPTIMizer Hand Held Programmer to
assign unique device addresses and select baud rates. Refer to the OPTIMizer Hand Held Programmer Instruction Book 29C892 for spe­cific assistance.
Notice: • For applications with Breaker Interface
Modules
- the acceptable address ranges for trip units are 1-32 (HEXADECIMAL).
• For applications with a remote PC and no Breaker Interface Modules present
- the acceptable address ranges for trip units
are 1-FFE (HEXADECIMAL).
Step 6: Use the OPTIMizer Hand Held Programmer to
check and adjust, if necessary, trip unit pickup
SECTION 4: STARTUP AND TESTING
4-1 INTRODUCTION
This section addresses those procedures associated with the startup and testing of installed Digitrip OPTIM Trip Units. As a minimum, the OPTIMizer Hand Held Programmer Instruction Book 29C892 along with this instruction book will be required to complete the system setup, program the trip unit, and functionally test the trip unit and circuit breaker.
4-2 WIRING
This section references wiring diagrams that are associ­ated with specific circuit breakers and their installed Digitrip OPTIM Trip Units. All wiring must conform to applicable federal, state and local codes.
4-2.1 WIRING DIAGRAMS
Specific wiring diagrams (connection diagrams) present all the required direct connections associated with a par­ticular circuit breaker type with an installed Digitrip OPTIM Trip Unit. Wiring diagrams are identified by cir­cuit breaker type in Appendix A. These wiring diagrams are required to create an accurate wiring plan drawing.
4-2.2 WIRING PLAN DRAWING
External wiring associated with a circuit breaker and its installed Digitrip OPTIM Trip Unit must follow a suitable wiring plan drawing. The phrase “wiring plan drawing” refers to the drawing or drawings made for a specific application. All electrical connections between the circuit breaker and external equipment are described. This drawing is the responsibility of the OEM or user.
4-2.3 NETWORK WIRING DIAGRAM
A network wiring diagram would also be helpful for sub­network and network systems. This diagram is the responsibility of the OEM or user. Refer to Figure 4-1 to review a typical network wiring diagram.
4-3 INITIAL STARTUP
This information is intended to be used when applying control power to a system, including the trip units. It is especially important during the first power application.
WARNING
I.B. 29C891B
Page 41
Effective 11/98
and time settings in keeping with system coor­dination requirements.
Step 7: If the system is utilizing one or more Breaker
Interface Modules or is network connected through IMPACC, verification of circuit breaker addresses and protective/ monitoring criteria can be accomplished using a Breaker Interface Module or remote computer. As required, refer to Instruction Book 29C893 to review the use of the Breaker Interface Module or Instruction Book 29C890 for an overview of the complete Digitrip OPTIM Trip Unit System, including IMPACC communications.
4-3.2 INITIAL POWER APPLICATION
a. Apply system power and observe individual trip units
and/or other system monitoring devices, such as the Breaker Interface Module or remote computer.
b. The green Unit Status LED should blink if either
(Figures 2-4 and 2-10):
1. The circuit breaker current in at least one phase exceeds 20% of the installed rating plug value
(or)
2. Auxiliary power is supplied to the circuit breaker.
The red transmit LED will blink whenever the trip unit is communicating on the IMPACC Network.
c. Should what appears to be a problem occur, refer to
the Troubleshooting Guide (Table 5.1) of this manu- al. For additional troubleshooting assistance, refer to the Troubleshooting Guides in the OPTIMizer Hand Held Programmer and/or the Breaker Interface Module instruction books (I.B. 29C892 and I.B. 29C893 respectively). For further assistance, consult Cutler-Hammer.
4-4 TESTING
Section 3-5 provides details associated with testing OPTIM Trip Units and circuit breakers equipped with OPTIM Trip Units. It is recommended that Section 3-5 be read first. In addition, follow the testing instructions presented in the OPTIMizer Hand Held Programmer instruction book (I.B. 29C892) or the Breaker Interface Module instruction book (I.B. 29C893). Testing can also be performed using a remote computer over the IMPACC system.
I.B. 29C891B
Page 42
Effective 11/98
Figure 4-1 Typical Network Wiring Diagram
Master
Computer
Breaker
Interface
Module
Shielded Twisted Pair
SPB
Circuit
Breaker
with
OPTIM
DSII
Circuit
Breaker
with
OPTIM
Series C
R-Frame
MCCB
with
OPTIM
To Other IMPACC
Compatible Devices
PONI
OPTIMizer
Series C N-Frame
MCCB
with
OPTIM
Series C L-Frame
MCCB
with
OPTIM
Circuit
Breaker
with
RMS 810
or 910
Series C F-Frame
MCCB
ES
IQ Energy Sentinel
Shielded Twisted Pair
PONI Module
(Required for IMPACC
Network Communications
to Master Computer)
Shielded
Twisted
Pair
➁ ➂
OPTIMizer
OPTIMizer
OPTIMizer
OPTIMizer
Series C K-Frame
MCCB
with
OPTIM
OPTIMizer
For network interconnection cable,
use Belden 9463 or Cutler-Hammer IMPCABLE.
When interconnecting devices, tie
shield drain wires together for shield path continuity.
Connect the shield path to a solid
earth ground at one point only.
On last device in network, tape shield
drain wire back upon cable.
Use a 1/2 watt carbon or metal film
resistor at each end of the network as an end of line termination resistor (EOLTR). EOLTR should be 100 ohms for 9600 baud communication rate networks or 150 ohms for 1200 baud communication rate networks.
Network interconnection to computer
requires use of an IMPACC master (CONI or MINT).
Devices without built-in communica-
tions require network interface module (PONI).
For detailed network wiring specifications,
call the automatic fax retrieval system
(FRED) at 412/494-3745 and request
document 17513 or contact the
Advanced Products Support Center.
Refer to the paragraph entitled
“Technical Assistance” in this document.
I.B. 29C891B
Page 43
Effective 11/98
SECTION 5: TROUBLESHOOTING AND MAINTENANCE
5-1 LEVEL OF REPAIR
This manual is written based on the assumption that only unit-level troubleshooting will be performed. If the cause of a malfunction is traced to a Digitrip OPTIM Trip Unit, the device should be replaced. The malfunctioning device may be returned to Cutler-Hammer for further evaluation.
5-2 TROUBLESHOOTING
OPTIM Trip Units can be used with or without auxiliary power. In addition, guidelines can vary to some degree by circuit breaker type. To make the guidelines of Table
5.1 as user friendly as possible, the troubleshooting table is divided by circuit breaker type, with and without auxiliary power.
5-3 TRIP UNIT REPLACEMENT
If a trip unit or a circuit breaker must be replaced, con­sult Cutler-Hammer for specific replacement instruc­tions.
5-4 MAINTENANCE AND CARE
Except for the rating plug and the battery for the local indicator, the Digitrip OPTIM Trip Unit is designed to be a self contained and maintenance free device.
The Digitrip OPTIM Trip Unit should be stored in an environment that does not exceed the temperature range of -30° to +85°C. The environment should also be free of excess humidity. Store the device in its original packing material.
K, L and N-Frame Circuit Breakers with Auxiliary Power
Unit Status LED is not Auxiliary power is not present or is Measure voltage at +30VDC and NEG on side Table A.1 blinking at approximately reversed. terminal block to be 30 ± 3 volts. Check polarity. Wiring Diagrams a one second on-off duty cycle. Open connection on breaker Check orange and black wires on the side term- Table A.1
internal wiring. inal block. Wiring Diagrams
Trip unit may be the problem. Replace breaker. Refer to Note 1 at end of Para. 5-3
Table 5.1
As soon as auxiliary power Rating plug is not installed or pins Install rating plug and/or check connections. Para. 2-6 & 5-4.2 is applied, instantaneous are not making good connection. trip LED comes on and breaker trips if initially Rating plug is open internally Replace rating plug Para. 5-4.2, Table 2.1 closed.
Trip unit may be the problem. Replace breaker. Refer to Note 1 at end of Para. 5-3
Table 5.1
LED does not come on Battery installed backwards Install correctly Para. 5-4.1 when battery check button is pressed. Dead battery Replace battery Para. 5-4.1, Table 2.2
Trip unit may be the problem. Replace breaker. Refer to Note 1 at end of Para. 5-3
Table 5.1
Table 5.1 Troubleshooting Guide (continued on next page)
Symptom Probable Cause Possible Solution(s) References
Power values are grossly Connections from PT Module to Check connections Table A.1 in error (1050 Trip Units breaker not made or are incorrect. Wiring Diagrams only).
Line frequency incorrect Verify operating frequency with OPTIMizer. I.B. 29C892, Para. 3-6
Trip unit may be the problem Replace breaker. Refer to Note 1 at end of Para. 5-3
Table 5.1
“Connection Failure” FIRST DISCONNECT AUXILIARY POWER TEMPORARILY, THEN CHECK THE FOLLOWING: displayed when OPTIMizer is plugged in. OPTIMizer not working or cord not Verify OPTIMizer operation on another breaker. I.B. 29C892
properly plugged into OPTIMizer. Para. 2-2.2 & 3-2
Cord not properly plugged into Check connection. If unit status LED is blinking, Para. 2-4.1 breaker. connection is OK.
Rating plug is not installed or is Instantaneous LED will be on. Install rating plug Para. 2-6 & 5-4.2 loose. and/or check for loose connections.
Rating plug is open internally Instantaneous LED will be on. Replace rating Para. 5-4.2, Table 2.1
plug.
Trip unit may be the problem. Replace breaker. Refer to Note 1 at end of Para. 5-3
Table 5.1
RECONNECT AUXILIARY POWER
BIM will not communicate Breaker address is > 32 (HEX) Check address with OPTIMizer and change as I.B. 29C892 with trip unit. required. Para. 3-5.1
No auxiliary power If possible, open breaker or reduce breaker Symptom: “Unit
current to <20% of frame rating. Then, check Status LED is not that unit status LED is blinking. If not, see first blinking.” symptom in this table.
Rating plug is not installed or is Instantaneous LED will be on. Install rating plug Para. 2-6 & 5-4.2 loose. and/or check for loose connections.
Rating plug is open internally Instantaneous LED will be on. Replace rating Para. 5-4.2, Table 2.1
plug.
Open INCOM connection Check INCOM connections on side terminal Table A.1
block. The transmit LED should flash when there Wiring Diagrams is communication. With INCOM connector unplugged, the resistance “looking into” the INCOM terminals should be approximately 2.5 ohms.
Trip unit may be the problem. Replace breaker. Refer to Note 1 at end of Para. 5-3
Table 5.1
I.B. 29C891B
Page 44
Effective 11/98
Table 5.1 Troubleshooting Guide (continued from previous page)
Symptom Probable Cause Possible Solution(s) References
Ground fault alarm unit Connections to ground fault alarm Check connections Table A.1 does not operate on a unit are incorrect. Wiring Diagrams ground fault.
Ground fault alarm is not operating Press test button on ground fault alarm unit. Table A.1
Button should illuminate. If it does not, check Instructions for that 120V is being supplied to unit. If it is, ground fault alarm replace the ground fault alarm unit.
Breaker is not providing an alarm Temporarily disconnect the wires to L1 and L2 on Table A.1 signal. the ground fault alarm unit. With these connec- Intstructions for
tions open, approximately 5 volts should appear ground fault alarm between GF, AL and COM when the ground fault current exceeds pickup. On ground fault alarm breakers, this voltage will be present as long as pickup is exceeded. On ground fault trip break­ers, this voltage appears only transiently after a trip and must be observed with an oscilloscope. If the voltage is not present, the problem may be in the breaker. Refer to Note 1 at the end of Table 5.1.
Breaker trips on ground There actually is a ground fault Find the location of the fault and remove it. N.A. fault.
On four wire systems the neutral (1) Check that the neutral sensor and neutral Table A.1 current sensor may not have the sensor connections on side terminal block are Wiring Diagrams correct ratio or be properly con- good. (2) Check that the neutral current sensor nected. ratio matches the breaker. (3) Check that con-
nections from the neutral current sensor to the breaker are not reversed polarity.
Trip unit may be the problem. Replace breaker. Refer to Note 1 at end of Para. 5-3
Table 5.1
Breaker trips too rapidly GOUT to GIN and/or SOUT to SIN Add connections Table A.1 on ground fault or short are not connected. Wiring Diagrams delay (zone selective inter­locking not used). Trip unit settings are not correct Change settings I.B. 29C892, Section 3
or
I.B. 29C893, Section 4
Trip unit may be the problem. Replace breaker. Refer to Note 1 at end of Para. 5-3
Table 5.1
Breaker trips too rapidly Powered thermal memory may If powered thermal memory is not required, I.B. 29C892, Para 3-6 on long delay. cause breaker to trip too soon. turn it off using OPTIMizer.
Trip unit settings are not correct Change settings I.B. 29C892, Section 3
or
I.B. 29C893, Section 4
I.B. 29C891B
Page 45
Effective 11/98
Table 5.1 Troubleshooting Guide (continued from previous page)
Symptom Probable Cause Possible Solution(s) References
I.B. 29C891B
Page 46
Effective 11/98
Trip unit may be the problem. Replace breaker. Refer to Note 1 at end of Para. 5-3
Table 5.1.
Zone selective interlocking on ground fault and/or See directions for checking zone selective interlocking Appendix B
short delay does not work.
Communication over No auxiliary power Check that the Unit Status LED is blinking. If not, Symptom: “Unit IMPACC is not working. see first symptom in this table. Status LED is not (Direct with BIM not involved) blinking.”
Open INCOM connection Check INCOM connections on side terminal Table A.1
block. The transmit LED should flash when there Wiring Diagrams is communication. With INCOM connector un­plugged, the resistance “looking into” the INCOM terminals should be approximately 2.5 ohms.
Trip unit may be the problem. Replace breaker. Refer to Note 1 at end of Para. 5-3
Table 5.1.
K, L and N-Frame Circuit Breakers without Auxiliary Power
Unit Status LED is not Current thru breaker is < 20% of No problem. Status LED will not operate with N.A. blinking at approxi- frame rating. breaker currents < 20% of frame rating. mately a one second on-off duty cycle Trip unit may be the problem Replace breaker. Refer to Note 1 at end of Para. 5-3
Table 5.1.
As soon as current starts Rating plug is not installed or is Install rating plug and/or check for loose Para 2-6 & 5-4.2 to flow thru the breaker, loose. connections. it trips and the instantan­eous trip LED comes on. Rating plug is open internally Replace rating plug Para. 5-4.2, Table 2.1
Trip unit may be the problem. Replace breaker. Refer to Note 1 at end of Para. 5-3
Table 5.1.
LED does not come on Battery installed backwards Install correctly Para. 5-4.1 when battery check button is pressed. Dead battery Replace battery Para. 5-4.1, Table 2.2
Trip unit may be the problem Replace breaker. Refer to Note 1 at end of Para. 5-3
Table 5.1.
Power values are grossly Connections from PT Module to Check connections Table A.1 in error (1050 trip units breaker not made or are incorrect. Wiring Diagrams only).
Frequency incorrect Verify operating frequency with OPTIMizer I.B. 29C892, Para 3-6
Trip unit may be the problem. Replace breaker. Refer to Note 1 at end of Para. 5-3
Table 5.1.
Table 5.1 Troubleshooting Guide (continued from previous page)
Symptom Probable Cause Possible Solution(s) References
“Connection Failure” when OPTIMizer not working or cord not Verify OPTIMizer operation on another breaker. I.B. 29C892 OPTIMizer is plugged in. properly plugged into OPTIMizer. Para. 2-2.2 & 3-2
Cord not properly plugged into Check connection. If unit status LED is blinking, Para. 2-4.1 breaker. connection is OK.
Rating plug is not installed or is Instantaneous LED will be on. Install rating plug Para. 2-6 & 5-4.2 loose. and/or check for loose connections.
Rating plug is open internally Replace rating plug Para. 5-4.2, Table 2.1
Trip unit may be the problem. Replace breaker. Refer to Note 1 at end of Para. 5-3
Table 5.1.
Ground fault alarm unit Connections to ground fault alarm Check connections Table A.1 does not operate on a unit are incorrect. Wiring Diagrams ground fault.
Ground fault alarm is not operating Press test button on ground fault alarm unit. Table A.1
Button should illuminate. If it does not, check Instructions for that 120V is being supplied to unit. If it is, ground fault alarm replace the ground fault alarm unit.
Breaker is not providing an alarm Temporarily disconnect the wires to L1 and L2 Table A.1
on the ground fault alarm unit. With these con- Instructions for nections open, approximately 5 volts should ground fault alarm appear between GF, AL and COM when the and wiring diagrams ground fault current exceeds pickup. On ground fault alarm breakers, this voltage will be present as long as pickup is exceeded. On ground fault trip breakers, this voltage appears only trans­iently after a trip and must be observed with an oscilloscope. If the voltage is not present, the problem may be in the breaker. Refer to Note 1 at the end of Table 5.1.
Breaker trips on ground There actually is a ground fault Check circuit to find the location of the fault. N.A. fault.
On four wire systems the neutral (1) Check neutral sensor and neutral sensor Table A.1 current sensor may not have the connections on side terminal block are good. Wiring Diagrams correct ratio or be properly con- (2) Check that the neutral current sensor ratio nected. matches the breaker. (3) Check that connections
from the neutral current sensor to the breaker are not reversed.
Trip unit may be the problem. Replace breaker. Refer to Note 1 at end of Para. 5-3
Table 5.1.
I.B. 29C891B
Page 47
Effective 11/98
Table 5.1 Troubleshooting Guide (continued from previous page)
Symptom Probable Cause Possible Solution(s) References
I.B. 29C891B
Page 48
Effective 11/98
Table 5.1 Troubleshooting Guide (continued from previous page)
Symptom Probable Cause Possible Solution(s) References
Breaker trips too rapidly GOUT to GIN and/or SOUT to SIN Add connections Table A.1 on ground fault or short are not shorted. Wiring Diagrams delay (zone selective interlocking not used). Trip unit settings are not correct. Change settings I.B. 29C892, Section 3
or
I.B. 29C893, Section 4
Trip unit may be the problem. Replace breaker. Refer to Note 1 at end of Para. 5-3
Table 5.1.
Breaker trips too rapidly on Unpowered thermal memory may If unpowered thermal is not required, turn it off I.B. 29C892, Para. 3-6 long delay. cause breaker to trip too soon. using OPTIMizer.
Trip unit settings are not correct. Change settings I.B. 29C892, Section 3
or
I.B. 29C893, Section 4
Trip unit may be the problem. Replace breaker. Refer to Note 1 at end of Para. 5-3
Table 5.1.
Zone selective interlocking on ground fault and/or See directions for checking zone selective interlocking Appendix B short delay does not work.
R-Frame, SPB Pow-R and DSII/DSLII Circuit Breakers with Auxiliary Power
Unit status LED is not No voltage or incorrect voltage input. Measure voltage at terminals C9 - C10 on RD Table A.1 blinking. and SPB breakers or 5 - 6 on DSII breakers, Wiring Diagrams
should be 115V 60Hz or 230V 50Hz per breaker label.
Trip unit may be the problem. Replace trip unit Para. 5-3
As soon as auxiliary power Rating plug not installed or pins not Install rating plug and/or check for loose con- Para. 2-6 & 5-4.2 is applied, instantaneous making good connection. nections. trip LED comes on. Note: Breaker cannot be closed if
rating plug is not installed.
Rating plug is open internally Replace rating plug Para. 5-4.2, Table 2.1
Trip unit may be the problem. Replace trip unit Para. 5-3
LED does not come on Battery installed backwards Install correctly Para. 5-4.1 when battery check button inside rating plug is Dead battery Replace battery Para. 5-4.1, Table 2.2 pressed.
Bad rating plug Replace rating plug Para. 5-4.2, Table 2.1
Power values are grossly No voltage input to trip unit. Check PT disconnect plug is installed. in error. (1050 Trip Units only) Frequency incorrect Verify operating frequency with OPTIMizer. I.B. 29C892, Para. 3-6
Trip unit may be the problem. Replace trip unit Para. 5-3
“Connection Failure” when FIRST DISCONNECT VOLTAGE SUPPLY TO TERMINALS C9 AND C10 ON RD AND SPB OPTIMizer is plugged in. BREAKERS OR 5 AND 6 ON DSII BREAKERS TEMPORARILY. (Place drawout breakers
in disconnect position which will remove voltage supply)
OPTIMizer not working or cord not Verify OPTIMizer operation on another breaker. I.B. 29C892 properly plugged into OPTIMizer. Para. 2-2.2 & 3-2
Cord not properly plugged into Check connection. If unit status LED is blinking, Para. 2-5.1 breaker. connection is OK.
Rating plug is not installed or is Instantaneous LED will be on. Install rating plug Para. 2-6 & 5-4.2 loose. and/or check for loose connections.
Rating plug is open internally Instantaneous LED will be on. Replace rating Para. 5-4.2, Table 2.1
plug.
Trip unit may be the problem. Replace trip unit Para. 5-3
RECONNECT VOLTAGE SUPPLY
BIM will not communicate Breaker address is > 32 (HEX) Check address with OPTIMizer and change as I.B. 29C892 with trip unit. required. Para. 3-5.1
No auxiliary power If possible, open breaker or reduce breaker Symptom: “Unit
current <20% of frame rating. Then check that Status LED is not unit status LED is blinking. If not, see first blinking.” symptom in this portion of the table.
Rating plug is not installed Instantaneous LED will be on. Install rating Para. 2-6 & 5-4.2
plug and/or check for loose connections.
Rating plug is open internally Instantaneous LED will be on. Replace rating Para. 5-4.2, Table 2.1
plug.
Open INCOM connection Check connections at terminals C11 and C12 on Table A.1
RD and SPB breakers or C6 and C7 on DSII Wiring Diagrams breakers. The transmit LED should flash when there is communication. With the external con­nections to C11 and C12 or C6 and C7 opened temporarily, the resistance across C11 and C12 or C6 and C7 should be approximately 2.5 ohms.
Trip unit may be the problem. Replace trip unit Para. 5-3
I.B. 29C891B
Page 49
Effective 11/98
Table 5.1 Troubleshooting Guide (continued from previous page)
Symptom Probable Cause Possible Solution(s) References
Breaker trips on ground There actually is a ground fault Find the location of the fault and remove it. N.A. fault.
On four wire systems the neutral Check the connections at terminals at D6 and D7 Table A.1 current sensor may not have the on RD and SPB breakers or 19 and 20 on DSII Wiring Diagrams correct ratio or be properly con- breakers. Check that the neutral current sensor nected. ratio matches the breaker. Check that connec-
tions from the neutral current sensor to the breaker are not reversed. Check that the short­ing straps on the four point ground fault term­inal block on RD and SPB breakers are connected D5 - D6 and D7 - D8.
Trip unit may be the problem. Replace trip unit Para. 5-3
Breaker trips too rapidly Connections from C4 to C5 and/or Add connections Table A.1 on ground fault or short D9 to D10 missing on RD or SPB Wiring Diagrams delay (zone selective breakers. interlocking not used).
Connections from Z2 to Z3 and/or Z4 Add connections Table A.1 to Z5 missing on DSII breakers. Wiring Diagrams
Trip unit settings are not correct Change settings I.B. 29C892, Section 3
or
I.B. 29C893, Section 4
Trip unit may be the problem. Replace trip unit Para. 5-3
Breaker trips too rapidly Powered thermal memory can cause If powered thermal memory is not required, I.B. 29C892, Para. 3-6 on long delay. breaker to trip too soon. turn it off with the OPTIMizer.
Trip unit settings are not correct Change settings I.B. 29C892, Section 3
or
I.B. 29C893, Section 4
Trip unit may be the problem. Replace trip unit Para. 5-3
Zone selective interlocking on ground fault and/or See directions for checking zone selective interlocking Appendix B short delay does not work.
Communication over Address incorrect Verify both the IMPACC address and trip unit Review Section 3 IMPACC is not working. address are properly setup. of IB 29C890 (Direct with BIM not involved) No auxiliary power If possible, open breaker or reduce breaker Symptom: “Unit
current to <20% of frame rating. Then check Status LED is not that unit status LED is blinking. If not, see first blinking.” symptom in this portion of the table.
Open INCOM connection Check connections at terminals C11 and C12 on Table A.1
(Continues on next page) RD and SPB breakers or C6 and C7 on DSII Wiring Diagrams
I.B. 29C891B
Page 50
Effective 11/98
Table 5.1 Troubleshooting Guide (continued from previous page)
Symptom Probable Cause Possible Solution(s) References
breakers. The transmit LED should flash when there is communication. With the external con­nections to C11 and C12 or C6 and C7 opened temporarily, the resistance “looking into” C11 and C12 or C6 and C7 should be approximately
2.5 ohms.
R-Frame, SPB Pow-R and DSII/DSLII Circuit Breakers without Auxiliary Power
Unit Status LED is not Current thru breaker is < 20% of No problem. Status LED will not operate with N.A. blinking. frame rating. breaker currents < 20% of frame rating.
Trip unit may be the problem. Replace trip unit Para. 5-3
As soon as current starts Rating plug is not installed or is Install rating plug and/or check for loose con- Para. 2-6 & 5-4.2 to flow thru the breaker, loose. Breaker cannot be closed nections. it trips and the instantan- without rating plug installed. eous trip LED comes on.
Rating plug is open internally Replace rating plug Para. 5-4.2, Table 2.1
Trip unit may be the problem. Replace trip unit Para. 5-3
LED does not come on Battery installed backwards Install correctly Para. 5-4.1 when battery check button is pressed. Dead battery Replace battery Para. 5-4.1, Table 2.2
Bad rating plug Replace rating plug Para. 5-4.2, Table 2.1
“Connection Failure” when OPTIMizer not working or cord not Verify OPTIMIzer operation on another breaker. I.B. 29C892 OPTIMizer is plugged in. properly plugged into OPTIMizer. Para. 2-2.2 & 3-2
Cord not properly plugged into Check connection. If unit status LED is blinking, Para. 2-5.1 breaker. connection is OK.
Rating plug is not installed or is Instantaneous LED will be on. Install rating plug Para. 2-6 & 5-4.2 loose. and/or check for loose connections.
Rating plug is open internally. Replace rating plug Para. 5-4.2, Table 2.1
Trip unit may be the problem. Replace trip unit Para. 5-3
Breaker trips on ground There actually is a ground fault. Find location of the fault N.A. fault.
On four wire systems the neutral Check connections at terminals D6 and D7 on Table A.1 current sensor may not have the RD and SPB breakers or 19 and 20 on DSII Wiring Diagrams correct ratio or be properly con- breakers. Check that the neutral current sensor nected. ratio matches the breaker. Check that the con-
nections from the neutral current sensor to the
(Continues on next page) breaker are not reversed. Check that the shorting
I.B. 29C891B
Page 51
Effective 11/98
Table 5.1 Troubleshooting Guide (continued from previous page)
Symptom Probable Cause Possible Solution(s) References
straps on the four point ground fault terminal block on the RD and SPB breakers are con­nected D5 - D6 and D7 - D8.
Trip unit may be the problem. Replace trip unit Para. 5-3
Breaker trips too rapidly Connection from C4 to C5 and/or Replace connections Table A.1 on ground fault or short from D9 to D10 is missing on RD Wiring Diagrams delay (zone selective or SPB breakers. interlocking not used).
Connection from Z2 to Z3 and/or Replace connections Table A.1 Z4 to Z5 missing on DSII breakers. Wiring Diagrams
Trip unit settings are not correct. Change settings I.B. 29C892, Section 3
or
I.B. 29C893, Section 4
Trip unit may be the problem. Replace trip unit Para. 5-3
Breaker trips too rapidly Unpowered thermal memory can If unpowered thermal memory is not required, I.B. 29C892, Para. 3-6 on long delay. cause breaker to trip too soon. turn it off with the OPTIMizer.
Trip unit settings are not correct Change settings I.B. 29C892, Section 3
or
I.B. 29C893, Section 4
Trip unit may be the problem. Replace trip unit Para. 5-3
Power values are grossly No voltage input to trip unit. Check PT disconnect plug is installed. Table A.1 in error. (1050 Trip Units Wiring Diagrams only)
Frequency incorrect Verify operating frequency with OPTIMizer I.B. 29C892, Para. 3-6
Trip unit may be the problem. Replace trip unit Para. 5-3
Zone selective interlocking on ground fault and/or See directions for checking zone selective interlocking Appendix B short delay does not work.
I.B. 29C891B
Page 52
Effective 11/98
Table 5.1 Troubleshooting Guide (continued from previous page)
Symptom Probable Cause Possible Solution(s) References
Notes: (1) OPTIM Trip Units are not replaceable on Series C LD and ND circuit breakers. Because replacing the complete circuit breaker is difficult,
consult the factory before attempting replacement.
I.B. 29C891B
Page 53
Effective 11/98
type or equivalent 3 volt lithium battery. Refer to Table
2.2 for acceptable battery replacements.
Notice: Care should be exercised when replacing the
battery to insure that the correct polarities are observed.
Series C K, L and N-Frame Replacement - The battery is located behind the access cover for the battery and programming port compartment of OPTIM Trip Units used with Series C K, L and N-Frame circuit breakers (Figure 5-3). To remove the access cover, pull down on the release tab located in the center of the cover while pulling out on the cover. Pull out on the battery tab to remove the battery. When replacing the battery, be cer­tain that the negative side is pointing to the left when fac­ing the front of the trip unit. Replace the access cover.
Series C R-Frame, SPB and DSII/DSLII Replacement ­The battery is located behind the hinged cover of the rating plug (Figure 5-4). Lower the cover and remove the battery by pulling out on the battery tab. When replacing the battery, be certain that the negative side is pointing left when facing the front of the trip unit. Polarity markings are also shown on the inside of the hinged cover. Close the rating plug’s hinged cover.
Figure 5-1 Battery Test Pushbutton and LED Shown on Face of OPTIM Trip Unit
Figure 5-2 Battery Test Pushbutton and LED Shown on OPTIM Rating Plug
5-4.1 LOCAL INDICATOR BATTERY CHECK AND REPLACEMENT
The battery is a 3 volt lithium battery. Following a trip operation and with no supplementary control power available, the battery should maintain the mode of trip LED for approximately 60 hours continuously. The ready status of the battery can be checked at any time by depressing the battery check/test pushbutton and observing the battery test LED. If the LED does not light with the pushbutton depressed, the battery should be replaced. The correct polarity should, however, first be checked (Figure 5-1 and 5-2). The battery test pushbut­ton and LED are located on the face of OPTIM Trip Units used with Series C K, L and N-Frame circuit breakers, and in the rating plug of OPTIM Trip Units used with Series C R-Frame, SPB Systems Pow-R, and DSII/DSLII circuit breakers.
Notice: The battery can be replaced at any time with
the circuit breaker in service without affecting the operation of the circuit breaker and its pro­tection function.
The battery can easily be replaced from the front of the trip unit. The replacement battery should be the same
I.B. 29C891B
Page 54
Effective 11/98
Figure 5-3 Battery Shown Installed in Battery/Program­ming Port Compartment
Figure 5-4 Battery Shown Installed Behind Rating Plug Hinged Cover
5-4.2 RATING PLUG REPLACEMENT
Notice: Mechanical rejection means will prevent the
installation of a rating plug in a trip unit for which it was not intended.
The fixed type interchangeable rating plugs used in OPTIM Trip Units can be simply removed and replaced using a small common flathead screwdriver. Refer to Figures 5-5 and 5-6 and proceed with the following steps:
Step 1: Make sure that the circuit breaker in which the
trip unit is installed is open.
Step 2: Figure 5-5 shows the rating plug location in
OPTIM Trip Units used with Series C L and N­Frame circuit breakers. If Figure 5-5 is applica­ble, proceed with Step 3. If not, proceed to Step 5.
Step 3: Remove the rating plug by turning the small
positioning screw in a counterclockwise direc­tion until it is loose. Use two fingers to remove the rating plug by pulling out on the small mold­ed top and bottom lips.
Step 4: Install a new rating plug by pushing it gently
into the rating plug cavity until it is seated.
Secure the rating plug in position by turning the positioning screw in the clockwise direction until it is snug. Do not over tighten the screw.
Step 5: Figure 5-6 shows the rating plug location in
OPTIM Trip Units used with Series C R-Frame, SPB Pow-R and all DSII/DSLII circuit breakers. If Figure 5-6 is applicable, proceed with Step 6.
Step 6: Lower the rating plug’s hinged cover to access
the positioning screw. Remove the rating plug by turning the screw in a counterclockwise direction until it is loose. Use two fingers to re­move the rating plug by pulling out on the plug.
Step 7: Install a new rating plug by pushing it gently
into the rating plug cavity until it is seated. Secure the rating plug in position by turning the positioning screw in the clockwise direction until snug. Do not over tighten the screw. Close the hinged cover.
Notice: • For the Series C R-Frame trip unit, the
rating plug screw is engaged/disen­gaged with only a 1/4 turn.
• For the SPB and DSII/DSLII trip unit, the rating plug screw is engaged/disen­gaged with several turns.
I.B. 29C891B
Page 55
Effective 11/98
Figure 5-5 Rating Plug Shown Removed (L and N-Frame Type OPTIM Trip Units)
Figure 5-6 Rating Plug Shown Being Removed (R-Frame, SPB and DSII/DSLII Type OPTIM Trip Units)
5-5 RETURN PROCEDURE
The Troubleshooting Guide (Table 5.1) is intended for service personnel to identify whether a problem being observed is external or internal to the device. If a prob­lem is determined to be internal, the device should be returned to the factory for replacement. To have a Digitrip OPTIM Trip Unit returned, contact your local Cutler-Hammer authorized distributor.
5-6 TECHNICAL ASSISTANCE
For information, technical assistance or referral to a local authorized distributor, contact the Customer Support Center at 1-800-356-1243.
I.B. 29C891B
Page 56
Effective 11/98
APPENDIX A - INSTRUCTIONAL REFERENCES
A list of instructional references is provided in Table A.1 to identify instructional documents that could be of assis­tance.
Table A.1 Instructional References (continued on next page)
DOCUMENT DESCRIPTION DOCUMENT NUMBER
Circuit Breakers
Series C K-Frame Frame Book IL 29-120K
Series C L-Frame Frame Book IL 29-120L
Series C N-Frame Frame Book IL 29-120N
Series C R-Frame Frame Book IL 29-120R Series C R-Frame Supplement IL 29C713
SPB Systems Pow-R Breaker Supplement IL 29849
DSII/DSLII Breaker Supplement IL 8700C39
Digitrip OPTIM Trip Unit System
OPTIM Trip Unit System Overview IB 29C890
OPTIM Trip Units IB 29C891
OPTIMizer Hand Held Programmer IB 29C892
Breaker Interface Module IB 29C893
Digitrip RMS Trip Units
Digitrip RMS 810 IL 29-888
Digitrip RMS 910 IL 29-889
Digitrip OPTIM Wiring Diagrams
Series C K, L and N-Frame Wiring IL 29C894
Series C R-Frame Wiring IL 29C714
SPB Systems Pow-R Wiring IL 15545
DSII/DSLII Wiring IL 1A33600
Energy Monitoring Devices
IQ Energy Sentinel
Series C F-Frame IL 17537 Series C J-Frame IL 17538 Series C K-Frame IL 17539
Universal IQ Energy Sentinel
Internal IL 17540 External IL 17541
Communication Devices
Communications Module (PONI)
INCOM PONI IL 17547 RS-232 PONI IL 17202 Modem PONI IL 17203 Buffered PONI IL 17361 CONI IL 17436 IMPACC Wiring Spec. IL 17513
I.B. 29C891B
Page 57
Effective 11/98
Table A.1 Instructional References (continued from previous page)
DOCUMENT DESCRIPTION DOCUMENT NUMBER
Accessories
Potential Transformer Module (K, L and N-Frame) 29C126
Ground Fault Indicator 1259C14G01
Digitrip OPTIM Time-Current Curves
Series C K-Frame Curves
I2t Long & Short Delay Phase SC-6924-98 I2t Long & Flat Short Delay Phase SC-6925-98 I4t Long & Flat Short Delay Phase SC-6926-98 400A Instantaneous & Override Phase SC-6927-98 250A Instantaneous & Override Phase SC-6928-98 125A Instantaneous & Override Phase SC-6929-98 Ground Fault Protection SC-6930-98
Series C L-Frame Curves
I2t Long & Short Delay Phase SC-6323-96 I2t Long & Flat Short Delay Phase SC-6324-96 I4t Long & Flat Short Delay Phase SC-6325-96 600A Instantaneous & Override Phase SC-6326-96 400A Instantaneous & Override Phase SC-6327-96 Ground Fault Protection SC-6330-96
Series C N-Frame Curves
I2t Long & Short Delay Phase SC-6331-96 I2t Long & Flat Short Delay Phase SC-6332-96 I4t Long & Flat Short Delay Phase SC-6333-96 Instantaneous & Override Phase SC-6334-96 Ground Fault Protection SC-6335-96
Series C R-Frame Curves
1600/2000A I2t Long & Short Delay Phase SC-6336-96 1600/2000A I2t Long & Flat Short Delay Phase SC-6337-96 1600/2000A I4t Long & Flat Short Delay Phase SC-6338-96 2500A I2t Long & Short Delay Phase SC-6339-96 2500A I2t Long & Flat Short Delay Phase SC-6340-96 2500A I4t Long & Flat Short Delay Phase SC-6341-96 1600A Instantaneous & Override Phase SC-6342-96 2000A Instantaneous & Override Phase SC-6343-96 2500A Instantaneous & Override Phase SC-6344-96 1600A Ground Fault Protection SC-6345-96 2000A Ground Fault Protection SC-6346-96 2500A Ground Fault Protection SC-6347-96
SPB Systems Pow-R Curves
400-1200A I2t Long & Short Delay Phase SC-6348-96 400-1200A I2t Long & Flat Short Delay Phase SC-6349-96 400-1200A I4t Long & Flat Short Delay Phase SC-6350-96 1600-3000A I2t Long & Short Delay Phase SC-6351-96 1600-3000A I2t Long & Flat Short Delay Phase SC-6352-96 1600-3000A I4t Long & Flat Short Delay Phase SC-6353-96 4000-5000A I2t Long & Short Delay Phase SC-6354-96 4000-5000A I2t Long & Flat Short Delay Phase SC-6355-96 4000-5000A I4t Long & Flat Short Delay Phase SC-6356-96 400-1200A Instantaneous & Override Phase SC-6357-96 1600-3000A Instantaneous & Override Phase SC-6358-96 4000-5000A Instantaneous & Override Phase SC-6359-96 Ground Fault Protection SC-6360-96
DSII/DSLII Curves
400-1200A I2t Long & Short Delay Phase SC-6275-95 400-1200A I2t Long & Flat Short Delay Phase SC-6276-95 400-1200A I4t Long & Flat Short Delay Phase SC-6277-95 1600-5000A I2t Long & Short Delay Phase SC-6278-95 1600-5000A I2t Long & Flat Short Delay Phase SC-6279-95 1600-5000A I4t Long & Flat Short Delay Phase SC-6280-95 400-1200A Instantaneous & Override Phase SC-6281-96 1600-5000A Instantaneous & Override Phase SC-6282-96 Ground Fault Protection SC-6283-96
I.B. 29C891B
Page 58
Effective 11/98
APPENDIX B - CHECKING ZONE SELECTIVE INTERLOCKING
Notice: See wiring diagrams for specifications on wire
size, number of permissible breakers and other details. See Table A.1 for a list of wiring dia­grams.
Step 1: To test the short delay interlocks, follow steps
2 thru 4.
Step 2: With no current flowing in any of the breakers
in the system and with no auxiliary power applied, temporarily connect the short delay output to the short delay input on each breaker (both upstream and downstream) in the sys­tem one by one. The designations of the breaker terminals which should be connected are:
NEP/LEP Trip Units REP Trip Units
SOUT TO SIN RD and SPB DSII
D9 to D10 Z2 to Z3
Temporarily set the short delay time to .2 sec­onds or greater and a flat response. Set the instantaneous trip to maximum. If the breaker has a Digitrip 750 or 1050 trip unit, an OPTIMizer or BIM must be used to change settings. If the breaker has a Digitrip 510, 610, 810 or 910 trip unit, the settings can be changed by the switches on the trip unit. Then run a short delay test with a simulated current 20% above the short delay pick up. If the breaker has a Digitrip 750 or 1050 trip unit, the test must be run using an OPTIMizer or BIM. The trip time should be a bit less than the short delay time setting. If the time is less than .1 seconds, there is a problem with the breaker. After the test on each breaker is complete, return all connections and settings to their orig­inal condition.
Step 3: Next, and still with no current flowing in any of
the breakers in the system and with no auxil­iary power applied, temporarily connect 5 to 6 volts dc from a battery or other convenient source in parallel with the short delay interlock output on one downstream breaker. The desig-
nations for the breaker terminals to which this voltage is to be applied are:
NEP/LEP Trip Units REP Trip Units
(RD and SPB) (DSII)
+ side of voltage SOUT D9 Z2
- side of voltage COM C1 Z1
Step 4: Next on the upstream breaker that is fed from
this downstream breaker temporarily set the short delay time to .2 seconds or greater and a flat response. Set the instantaneous trip to maximum. If the upstream breaker has a Digitrip 750 or 1050 trip unit, an OPTIMizer or BIM must be used to change settings. If the upstream breaker has a Digitrip 510, 610, 810 or 910 trip unit, the settings can be changed by the switches on the trip unit.
Then run a short delay test on the upstream breaker with a simulated current 20% above the short delay pick up. If the upstream break­er has a Digitrip 750 or 1050 trip unit, the test must be run using an OPTIMizer or BIM. If the zone selective system is working properly, the trip time will be a bit less than the short delay time setting on the upstream breaker. If the time is less than .1 seconds, a wiring error is indicated. Then disconnect the voltage at the downstream breaker and repeat the test on the upstream breaker. Now the trip time should be less than .1 second. Note these tests must be run with the temporary voltage applied at each downstream breaker. Furthermore, if there is more than one upstream breaker fed from downstream breakers, each upstream breaker must be tested with each downstream breaker. After all tests are complete, return all settings to their original condition.
Step 5: To test the ground fault interlocks on breakers
with NEP or LEP trip units, repeat steps 2 thru 4 except substitute GOUT for SOUT and GIN for SIN. To test the ground fault interlocks on RD or SPB breakers with REP trip units, repeat steps 2 thru 4 except substitute C4 for D10 and C5 for D9. To test the ground fault interlocks on DSII breakers with REP trip units, repeat steps 2 thru 4 except substitute Z4 for Z2 and Z5 for Z3.
I.B. 29C891B
Cutler-Hammer
Pittsburgh, Pennsylvania U.S.A.
Effective 11/98 Style 7801C96H03 Printed in U.S.A.
This instruction booklet is published solely for informa­tion purposes and should not be considered all inclu­sive. If further information is required, you should con­sult Cutler-Hammer.
Sale of product shown in this literature is subject to terms and conditions outlined in appropriate Cutler­Hammer selling policies or other contractual agreement between the parties. This literature is not intended to and does not enlarge or add to any such contract. The sole source governing the rights and remedies of any purchaser of this equipment is the contract between the purchaser and Cutler-Hammer.
NO WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING WARRANTIES OF FITNESS FOR A PAR­TICULAR PURPOSE OR MERCHANTABILITY, OR WARRANTIES ARISING FROM COURSE OF DEAL­ING OR USAGE OF TRADE, ARE MADE REGARDING THE INFORMATION, RECOMMENDATIONS AND DESCRIPTIONS CONTAINED HEREIN. In no event will Cutler-Hammer be responsible to the purchaser or user in contract, in tort (including negligence), strict lia­bility or otherwise for any special, indirect, incidental or consequential damage or loss whatsoever, including but not limited to damage or loss of use of equipment, plant or power system, cost of capital, loss of power, addition­al expenses in the use of existing power facilities, or claims against the purchaser or user by its customers resulting from the use of the information, recommenda­tions and description contained herein.
Loading...