Cutler-Hammer Digitrip OPTIM 550 Installation Instructions Manual

I.L. 29C508B
Effective September, 2000, Supersedes I.L. 29C508A dated February 1999.
Cutler-Hammer
Installation Instructions for the Digitrip OPTIM 550 3-Pole Trip Unit Installation and Operation with L-Frame Series C Circuit Breakers
Table of Contents
Description Page
2.0 UL Listed Devices . . . . . . . . . . . . . . . . . . . . . . . .2
3.0 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
4.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
4.2 Overload Trip . . . . . . . . . . . . . . . . . . . . . . . . . . .6
5.0 Testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
5.1 Functional Field Testing . . . . . . . . . . . . . . . . . . .6
5.2 Performance Testing for Ground
Fault Trip Units . . . . . . . . . . . . . . . . . . . . . . . . . .6
5.2.2 Standards Requirements . . . . . . . . . . . . . . . . . .6
6.0 Rating Plug . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
7.0 References . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
7.1 Series C L-Frame Molded Case
Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . . . .8
7.2 Internal Accessories . . . . . . . . . . . . . . . . . . . . . .8
DEATH, SEVERE PERSONAL INJURY, OR SUB­STANTIAL PROPERTY DAMAGE CAN RESULT FROM CONTACT WITH ENERGIZED EQUIPMENT. DO NOT ATTEMPT TO INSTALL OR PERFORM MAINTENANCE ON EQUIPMENT WHILE IT IS ENER­GIZED. ALWAYS VERIFY THAT NO VOLTAGE IS PRESENT BEFORE PROCEEDING WITH THE TASK, ALWAYS FOLLOW GENERALLY ACCEPTED SAFE­TY PROCEDURES.
CUTLER-HAMMER IS NOT LIABLE FOR THE MISAP­PLICATION OR MISINSTALLATION OF ITS PROD­UCTS.
The user is cautioned to observe all recommendations, warnings, and cautions relating to the safety of person­nel and equipment as well as all general and local health and safety laws, codes, and procedures.
!
WARNING
The recommendations and information contained herein are based on Cutler-Hammer experience and judge­ment, but should not be considered to be all-inclusive or covering every application or circumstance which may arise. If any questions arise, contact Cutler-Hammer for further information or instructions.
1.0 GENERAL INFORMATION
The Digitrip OPTIM 550, illustrated in Figure 1-1, is an electronic trip unit that incorporates a microprocessor­based custom application specific integrated circuit design for use with the Series C L-Frame Molded Case Circuit Breakers.
The Digitrip OPTIM 550 provides true RMS current sensing for proper correlation with thermal characteris­tics of conductors and equipment. Interchangeable rat­ing plugs are provided to establish the continuous cur­rent rating of each circuit breaker.
Figure 1-1 Digitrip OPTIM 550 Trip Unit for 3-Pole L-Frame Series C Circuit Breaker
Make sure that the trip unit is suitable for the intended installation by comparing nameplate data with any exist­ing equipment and system requirements. Inspect the trip unit for completeness, and check for damage before installing it in the circuit breaker frame.
Remove and SAVE the Jumper plug assembly (a 12 position housing) from the trip unit (see Figure 3-2).
Remove the wire-retaining bracket from the right pole of the trip unit.
Trip unit center retaining screw is captive in the trip unit conductor; the remaining retaining screws (2 for a 3-pole trip unit) are supplied with the frame.
Remove circuit breaker pan-head cover screws, and covers. Remove trip unit outer pole screws and red plastic washers from the frame. Discard red plastic washers (Figure 3-1).
The two trip unit outer pole retaining screws may be placed in the trip unit conductor holes at this time. If preferred, a 5/16 inch hexagonal-head wrench may be used to position the screws when the trip unit is in the base.
The Digitrip OPTIM 550 Trip Unit is completely self con­tained and when the circuit breaker is closed, requires no external power to operate its protection systems. It operates from current signal levels and control power derived through current sensors integrally mounted in the trip unit.
Digitrip OPTIM 550 Trip Units are suitable for 50/60 Hz AC applications only. For DC applications, a thermal­magnetic trip unit should be used.
The Digitrip OPTIM 550 Trip Unit for the L-Frame is available in 3 different types and four different maximum ampere ratings (Table 1.1).
Ground Fault Alarm trip units do NOT provide ground fault protection.
2.0 UL LISTED DEVICES
The Digitrip OPTIM 550 Trip Unit is listed in accordance with Underwriters Laboratories, Inc. Standard UL489, under file E7819 and satisfies the applicable require­ments of the International Electrotechnical Commission (IEC) recommendations for molded case circuit break­ers.
3.0 INSTALLATION
The installation procedure consists of inspecting and installing the trip unit and rating plug. To install the trip unit, perform the following steps.
If required, internal accessory installation should be done before the circuit breaker is mounted and con­nected. Refer to the individual accessory instruction leaflets.
I.L. 29C508B
Page 2
Effective 9/00
Table 1.1 Digitrip OPTIM 550 Trip Unit Types
NOTICE
NOTICE
Catalog Number Max Amps Version Description
LEP3125T52 125A LSI Non-ground Fault LEP3125T56 125A LSIG Ground Fault LEP3125T57
125A LSIA Ground Fault Alarm LEP3250T52 250A LSI Non-ground Fault LEP3250T56 250A LSIG Ground Fault LEP3250T57
250A LSIA Ground Fault Alarm LEP3400T52 400A LSI Non-ground Fault LEP3400T56 400A LSIG Ground Fault LEP3400T57
400A LSIA Ground Fault Alarm LEP3600T52 600A LSI Non-ground Fault LEP3600T56 600A LSIG Ground Fault LEP3600T57
600A LSIA Ground Fault Alarm
Figure 3-1 Preliminary Preparation
NOTICE
Remove and Dispose of Red Spacers
Position the trip unit in the base. Make sure the latch bracket pin is properly seated in the slots in the sideplates (Figure 3-2). If necessary, move the handle toward the line end of the circuit breaker to seat the trip unit.
Screw in and tighten three trip unit retaining screws (center first). Torque to 12 Ib-ft (16.27 N.m). Make sure the holes in the trip unit conductors line up with the tapped holes of the frame load conductors for proper terminal installation.
DO NOT EXCEED A TORQUE OF 12 LB-FT (16.27 N.M). EXCESSIVE TORQUING WILL SHEAR SCREWS. FAILURE TO APPLY THE REQUIRED TORQUE MAY LEAD TO EXCESSIVE HEATING AND CAUSE NUISANCE TRIPPING OF THE BREAKER.
If a standard “L” frame internal accessory is to be installed in the right pole, cut the cable tie on wire­retaining bracket and discard the bracket. Install the attachment according to the individual accessory instruction leaflet, and attach the wires that were attached to the wire-retaining bracket to the attachment mount bracket with a cable tie.
I.L. 29C508B
Page 3
Effective 9/00
Install the wire retaining bracket into the right pole trip unit accessory retaining slots. For ground fault or ground fault alarm trip units route the white and gray wires out the frame accessory wiring channels.
Ground fault trip units are supplied from the factory with a wire harness with pigtail lead connections for a neutral current sensor (white and gray wires). A neutral current sensor is provided with each trip unit.
Install the jumper plug assembly into the trip unit (see Figure 3-2) with the keying pin in the bottom right corner. Note: Jumper plug assembly fits in one orientation only.
Digitrip OPTIM 550 Ground Fault Trip Units detect ground fault currents through Residual Sensing. They are not designed to use source ground or zero sequence ground fault sensing methods. If the system neutral is grounded, but no phase to neutral loads are used, the neutral current sensor is not necessary. In that case, the white and gray leads on the trip unit should be cut off before installation.
If the system neutral is grounded and phase to neutral loads are used, then the neutral current sensor must be used(Figure 3-3). It should be connected to the breaker according the diagram in Figure 3-4. It has the same turns ratio as the phase current sensors in the trip unit.
!
CAUTION
Figure 3-2 Trip Unit Installed in Circuit Breaker
Sideplate (Both Sides)
Latch Pin
Trip Unit
Retaining
Screws
(Both Sides)
Interphase
Barriers
(Both Sides)
Accessory
Retaining Slot
(Both Sides)
Frame Accessory Wiring Chanels
Orientation Keying Pin
Jumper Plug Assembly
Trip Unit Conductor
and Frame Load Conductor
Tapped Holes for Terminals
Wire-Retaining Bracket
Do not connect the neutral current sensor secondary output to ground. Connecting the secondary output to ground may cause damage to the trip unit.
The polarity of the sensor connections is critical. Always observe the polarity markings on the instal­lation drawings. The polarity markings are identified as white dots on the transformer. To insure correct ground fault equipment performance, conduct field test to comply with National Electric Code require­ments under article 230-95-C. See Section 5.2 for instructions.
Install accessory(ies), if required, using appropriate instruction leaflet listed in Section 7.2. Where acces­sories are not required, install protective barriers sup­plied with the trip unit in accessory retaining slots of the trip unit.
I.L. 29C508B
Page 4
Effective 9/00
Figure 3-3 Neutral Current Sensor Placement
1.50
Table 3.1 Digitrip L-Frame OPTIM Rating Plugs
Max Amps In Catalog Number of trip unit
125A 63 A ORPL125A063 125A 70 A ORPL125A070 125A 90 A ORPL125A090 125A 100 A ORPL125A100 125A 110 A ORPL125A110 125A 125 A ORPL125A125 250A 125 A ORPL025A125 250A 150 A ORPL025A150 250A 160 A ORPL025A160 250A 175 A ORPL025A175 250A 200 A ORPL025A200 250A 225 A ORPL025A225 250A 250 A ORPL025A250 400A 200 A ORPL40A200 400A 225 A ORPL40A225 400A 250 A ORPL40A250 400A 300 A ORPL40A300 400A 350 A ORPL40A350 400A 400 A ORPL40A400 600A 300 A ORPL60A300 600A 350 A ORPL60A350 600A 400 A ORPL60A400 600A 500 A ORPL60A500 600A 600 A ORPL60A600
.03
.281 Diam. 2 Holes
.36R
.12
1.00
Ref.
2.75
2.00 Ref.
1.07
6.17 Ref.
1.47
1.438
.28R
4.375 Ref.
5.61
5.75
.12R
Polarity Markings
.50
2.25
1.188
1.17
2.188
2.25
2.33
3.04
NOTICE
NOTICE
The pins on the circuit board are specifically cut, and the sockets in the rating plug are specifically filled to prevent an incorrect rating plug from being installed.
Screw in and tighten the rating plug screw to secure the rating plug.
Reset circuit breaker by moving handle to the reset position. Move handle to the ON position. Circuit break­er handle should remain at the ON position.
Press Push-to-trip button to check the manual tripping of the circuit breaker.
4.0 PRINCIPLE OF OPERATION
In open air at 40°C, a L-Frame circuit breaker with a Digitrip OPTIM 550 Trip Unit installed will carry continu­ously up to 600 amperes without exceeding a 50°C rise at the terminals. The calibration of the trip unit is insen­sitive to ambient temperatures over a range of -20° to +55°C. However the trip unit contains thermal tempera­ture protection circuitry that initiates a trip operation for self-protection if the internal ambient temperature at the printed circuit board (PCB) reaches approximately 100°C. This may occur for open air temperatures above 40°C with circuit breaker currents near full load.
For ambient conditions above 40°C and where the maxi­mum ampere rating plug has been installed, derating of the circuit breaker frame should be considered to avoid exceeding a safe terminal temperature operating range. Consult Cutler-Hammer for recommendations.
4.1 GENERAL
The Digitrip OPTIM 550 Trip Unit provides a tripping sig­nal to the flux transfer shunt trip when current and time delay settings are exceeded. This is accomplished by employing the Cutler-Hammer custom designed inte­grated circuit Sµre™chip, which includes a microcom­puter to perform its numeric and logic functions.
In the Digitrip OPTIM 550 Trip Unit, all required sensing and tripping power to operate its protection function is derived from the current sensors in the circuit breaker. The secondary currents from these sensors provide the correct input information for the protection functions, as well as tripping power, whenever the circuit breaker is carrying current. These current signals develop analog voltages across the appropriate calibrating resistors.
I.L. 29C508B
Page 5
Effective 9/00
Figure 3-5 Rating Plug Installation
NOTICE
Make sure interphase barriers are properly seated in the base and sliding handle barrier is properly seated in the cover.
Install circuit breaker covers and pan-head screws.Install the rating plug into the trip unit (Figure 3-5 and Table 3.1). The pins on the circuit board must line up with the sockets in the rating plug and require only minimal pressure to install. Do NOT attempt to force the rating plug into the trip unit.
Figure 3-4 Connection Diagram
Source
L C R N
Load
White
Grey
I.L. 29C508B
Page 6
Effective 9/00
The microcomputer, in cyclic fashion, repeatedly scans the voltage values across each calibrating resistor and enters these values into memory. These data are used to calculate true RMS current values, which are then repeatedly compared with the protection function set­tings and other operating data stored in the memory. The software program then determines whether to initi­ate protection functions, including tripping the breaker through the flux transfer shunt trip device in the circuit breaker.
4.2 OVERLOAD TRIP
In accordance with standards requirements, the trip unit initiates a trip of the circuit breaker within two hours for an overload of 135 percent, and will trip in less time for higher overload currents.
A "Thermal Memory" effect prevents the breaker from being re-energized immediately after an overload. A "cooling off" period of up to 5 minutes is required, which allows time for cabling to cool off.
For details on the operation and protective functions of the OPTIM 550 Trip unit and other related instructions, contact Cutler-Hammer for the following information and user’s manuals:
L-Frame and Accessories Selection Data 29-120L Instructions and Overview of
OPTIM Trip Units 29C890
Instructions on the Operation of Digitrip
OPTIMIZER Hand Held Programmer 29C892
Instructions on the Operation of Digitrip
Breaker Interface Module 29C893
Instructions on the Operation of Digitrip
OPTIM Trip Units 29C891
Digitrip OPTIM Wire Diagrams 29C894
5.0 TESTING
5.1 FUNCTIONAL FIELD TESTING
Any field testing should be done in accordance with applicable NEMA Standard. The operation of circuit breakers with Digitrip OPTIM RMS trip units can be field tested periodically using the hand held OPTIMIZER (see user’s manuals).
5.2 PERFORMANCE TESTING FOR GROUND FAULT TRIP UNITS
5.2.1 CODE REQUIREMENTS
The National Electrical Code under Article 230-95-C requires that any ground-fault protection system be per-
formance tested when first installed. The test shall be conducted in accordance with approved instructions provided with the equipment. A written record of this test shall be made and shall be available to the authority having inspection jurisdiction.
5.2.2 STANDARDS REQUIREMENTS
As a follow-up to the basic performance requirements stipulated by the N.E.C. as stated above, UL Standard No. 1053 requires that certain minimum instructions must accompany each ground fault protection system. These following statements plus a copy of the test record form illustrated in Figure 5-4 are shipped with each Digitrip OPTIM 550 Trip Unit.
5.2.3 GENERAL TEST INSTRUCTIONS
The interconnected system shall be evaluated in accor­dance with the equipment assembler's detailed instruc­tions by qualified personnel.
The polarity of the neutral sensor connections (if used) must agree with equipment assembler's detailed instruc­tions to avoid improper operations following apparently correct simulated test operations. Where a question exists, consult the specifying engineer and/or equipment assembler.
The grounding points of the system shall be verified to determine that ground paths do not exist that would bypass the sensors. The use of high-voltage testers and resistance bridges may be used.
THERE IS A HAZARD OF ELECTRICAL SHOCK OR BURN WHENEVER WORKING IN OR AROUND ELECTRICAL EQUIPMENT. ALWAYS TURN OFF POWER SUPPLYING BREAKER BEFORE CON­DUCTING TESTS.
Since the Digitrip OPTIM 550 Trip Units derive their operating power from the phase currents, and not from the neutral current, passing current through the neutral sensor only will not properly test the ground fault feature.
Using a low voltage (0-24 volt), high current, AC source, apply a test current of 125% of the Digitrip OPTIM 550
!
WARNING
NOTICE
Ground Fault Trip Unit pick-up setting through one phase of the circuit breaker as shown in Figure 5-1. This should cause the breaker to trip and the ground fault alarm light should light in less than 1 second. Reset the breaker. Repeat the test on the other two phases.
If the system is a 4-wire system with a neutral current sensor, apply the same current as described above through one phase of the breaker returning through the neutral sensor as shown in Figure 5-2. The breaker should not trip and the ground fault alarm light should not light. Repeat the test on the other two phases.
If the system is a 3-wire system with no neutral current sensor, apply the same current as described above through any two phases of the breaker with the connec­tions exactly as shown in Figure 5-3. The breaker should not trip and the ground fault alarm light should not light. Repeat the test using the other two combina­tions of breaker phases.
FIELD TESTING SHOULD BE USED FOR FUNCTION­AL TESTING AND NOT FIELD CALIBRATION OF THE DIGITRIP OPTIM 550 GROUND FAULT TRIP UNIT.
ANY TEMPORARY CONNECTION MADE FOR THE PURPOSE OF CONDUCTING TESTS SHOULD BE RESTORED TO PROPER OPERATING CONDITIONS BEFORE RETURNING THE BREAKER TO SERVICE.
The results of the test are to be recorded on the test form provided with the equipment.
6.0 RATING PLUG
The rating plug, as illustrated in Figure 3-5, is used to establish the continuous ampere rating of the related cir­cuit breaker.
The Long Delay protection function of the trip unit is set at the rating plug value (In). The Short Delay and Instantaneous protection functions are set as a multiple of In. The Ground Fault protection function is indepen­dent of In.
Different rating plugs are available to match the desired current rating and type of circuit breaker into which the trip unit is to be installed (Table 3.1).
I.L. 29C508B
Page 7
Effective 9/00
!
CAUTION
Figure 5-1 Connections for Ground Fault Trip Test
Source
Low Voltage Source
L C R N
Load
Current Limiting Resistor (if required)
Source
Low Voltage Source
L C R N
Load
Current Limiting Resistor (if required)
Figure 5-2 Connections for Ground Fault No-Trip Test, with a Four-Wire System
I.L. 29C508B
Page 8
Effective 9/00
7.0 REFERENCES
7.1 SERIES C L-FRAME MOLDED CASE CIRCUIT BREAKERS
29C105 Frame Instruction Leaflet AD 29-167L Typical Time-Current Characteristic
curves for L Frame Breakers
7.2 INTERNAL ACCESSORIES
The following types of internal accessories, which mount on the trip unit, are available for use. The number of the instruction leaflet covering the installation of each accessory is shown.
• Alarm (Signal)/Lockout (ASL) Switch . . . .I.L. 29C183
• Auxiliary Switch . . . . . . . . . . . . . . . . . . . . .I.L. 29C123
• Shunt Trip . . . . . . . . . . . . . . . . . . . . . . . . .I.L. 29C146
• Low Energy Shunt Trip . . . . . . . . . . . . . . .I.L. 29C147
• Undervoltage Release Mechanism
(HandleReset . . . . . . . . . . . . . . . . . . . . . .l.L. 29C170
Figure 5-3 Connections for Ground Fault No-Trip Test, with a Three-Wire System
Low Voltage Source
Source
L C R
Current Limiting Resistor (if required)
I.L. 29C508B
Page 9
Effective 9/00
GROUND FAULT TEST RECORD FORM
Ground Fault Test Record should be Retained by Those in Charge of the Building’s Electrical Installation in order to be Available to the Authority having Jurisdiction
Test Date
Circuit Breaker Number
Results Tested By:
Figure 5-4 Typical Performance Test Record Form
I.L. 29C508B
Page 10
Effective 9/00
I.L. 29C508B
Page 11
Effective 9/00
Cutler-Hammer
Pittsburgh, Pennsylvania U.S.A.
Effective 9/00 (ISI) Style 6603C85H03 Printed in U.S.A.
Page 12
I.L. 29C508B
Loading...