Curtis 1244-45, 1244-55, 1244-44, 1244-46, 1244-64 User Manual

...
Page 1
Manual
Model 1244
MultiMode™ Electronic Motor Controller
Read Instructions Carefully!
Specications are subject to change without notice. © 2013 Curtis Instruments, Inc. ® Curtis is a registered trademark of Curtis Instruments, Inc. © The design and appearance of the products depicted herein are the copyright of Curtis Instruments, Inc. 16958 Rev E 10/2013
Curtis Instruments, Inc.
Mt. Kisco, NY 10549
www.curtisinstruments.com
Page 2
Page 3
CONTENTS
1. OVERVIEW ...........................................................................................1
2. INSTALLATION AND WIRING .........................................................4
Mounting the Controller ..................................................................4
Connections: Low Current ..............................................................6
Connections: High Current .............................................................7
Wiring: Controller ........................................................................... 8
Wiring: rottle.............................................................................10
5kΩ–0, 2-wire resistive throttle (“Type 1”) ..............................11
0–5V, current source, 3-wire pot, and electronic
single-ended throttles (“Type 2”) .....................................12
0–5kΩ, 2-wire resistive throttle (“Type 3”) ..............................15
0–5V and 3-wire pot wigwag-style throttles (“Type 4”) ............15
CAN-Nodes throttle (“Type 5”) ..............................................16
Wiring: Fault Outputs ...................................................................16
Wiring: Contactor Drivers ............................................................. 16
Wiring: Pedal Switch .....................................................................19
Wiring: Hour Meter ......................................................................19
Wiring: CAN Bus Interface ...........................................................19
Wiring: Emergency Reverse ........................................................... 19
Contactor, Switches, and Other Hardware ......................................21
CONTENTS
3. PROGRAMMABLE PARAMETERS ..................................................23
Acceleration Parameters ..................................................................26
Acceleration Rate, M1–M4 ......................................................26
Braking Rate, M1–M4 ............................................................26
Deceleration Rate ....................................................................26
Quick Start .............................................................................. 26
Taper Rate ............................................................................... 27
Speed Parameters ............................................................................27
Maximum Speed, M1–M4 ......................................................27
Creep Speed, M1–M4 ............................................................. 27
Regen Speed ............................................................................27
rottle Parameters ......................................................................... 28
Control Mode..........................................................................28
rottle Type ........................................................................... 29
rottle Deadband ..................................................................30
rottle Max ...........................................................................32
rottle Map, M1–M4 ............................................................ 34
rottle Braking Percent, M1–M4 ...........................................36
Current Limit Parameters ...............................................................36
Drive Current Limit, M1–M4 .................................................36
Braking Current Limit, M1–M4 ..............................................36
Minimum Field Current Limit ................................................ 36
Maximum Field Current Limit ................................................ 37
Restraint .................................................................................. 37
Emergency Reverse Current Limit ...........................................38
Current Ratio .......................................................................... 38
Curtis 1244 Manual, Rev. E
iii
Page 4
CONTENTS
Field Control Parameters ................................................................38
Field Map Start ........................................................................ 38
Field Map ................................................................................ 39
Fault Parameters ..............................................................................41
High Pedal Disable (HPD) ...................................................... 41
HPD reshold ....................................................................... 42
Static Return to O (SRO) ...................................................... 42
Fault Code ............................................................................... 42
Output Driver Parameters ...............................................................43
Main Contactor Driver Interlock .............................................43
Main Contactor Dropout Delay ..............................................43
Main Coil Open Check ........................................................... 44
Main Contactor Weld Check ................................................... 44
Auxiliary Driver Dropout Delay ..............................................44
Auxiliary Coil Open Check .....................................................44
Reverse Signal Open Check .....................................................45
Electromagnetic Brake Delay ...................................................45
Electromagnetic Brake Open Check ........................................45
Contactor Holding Voltage ......................................................46
Contactor Pull-in Voltage ........................................................46
Other Parameters ............................................................................ 46
Battery Voltage ........................................................................46
Anti-Tiedown ..........................................................................47
Sequencing Delay .................................................................... 47
Pedal Interlock ......................................................................... 47
Emergency Reverse Enable .......................................................48
Emergency Reverse Check ....................................................... 48
Node Address ..........................................................................48
Precharge ................................................................................ 49
Load Compensation ................................................................ 49
4. OEMSPECIFIED, FACTORYSET PARAMETERS .........................50
MultiMode™ Enable ...................................................................... 50
Accessory Driver Enable ..................................................................50
CAN Bus Enable ............................................................................51
5. INSTALLATION CHECKOUT .........................................................52
6. VEHICLE PERFORMANCE ADJUSTMENT ..................................54
Major Tuning ..................................................................................54
Tuning the active throttle range ..............................................54
Tuning the controller to the motor .........................................57
Setting the unloaded vehicle top speed ....................................59
Equalizing loaded and unloaded vehicle speed ........................60
Fine Tuning ....................................................................................62
Response to increased throttle .................................................. 62
Response to reduced throttle .................................................... 63
Smoothness of direction transitions .........................................63
Ramp climbing ....................................................................... 65
Ramp restraint ........................................................................ 66
iv
Curtis 1244 Manual, Rev. E
Page 5
7. PROGRAMMER MENUS .................................................................67
Paraneters Menu .............................................................................67
Monitor Menu ................................................................................ 70
Diagnostics Menu ........................................................................... 71
Other Menus .................................................................................. 71
8. DIAGNOSTICS AND TROUBLESHOOTING................................72
Programmer Diagnostics ................................................................. 72
LED Diagnostics ............................................................................ 74
Fault Output Drivers ...................................................................... 75
9. MAINTENANCE ................................................................................76
Cleaning ........................................................................................ 76
Diagnostic History .........................................................................76
appendix a Glossary of Features and Functions appendix b Programming Devices appendix c Specifications, 1244 Controller
CONTENTS
Curtis 1244 Manual, Rev. E
v
Page 6
FIGURES / TABLES
. 1: Curtis 1244 electronic motor controller ...................................1
. 2: Mounting dimensions, Curtis 1244 controller ........................4
. 3: Standard wiring configuration ..................................................8
. 4: Wiring for 5kΩ–0 throttle (“Type 1”) .................................... 11
. 5: Wiring for wigwag throttle,
using the 5kΩ–0 throttle input (“Type 1”) ............................. 11
. 6: Wiring for 0–5V throttle (“Type 2”) ...................................... 12
. 7: Wiring for 3-wire potentiometer throttle (“Type 2”) .............. 13
. 8: Wiring for current source throttle (“Type 2”) ......................... 13
. 9: Wiring for Curtis ET-XXX electronic throttle (“Type 2”) ......14
. 10: Wiring for 0–5kΩ throttle (“Type 3”) ....................................15
. 11: Wiring for fault outputs .........................................................16
. 12: Wiring for main and auxiliary contactor coils when using
the interlock and dropout delay features .................................18
FIGURES
. 13: Wiring for emergency reverse
(applicable to walkie vehicles only) .........................................20
. 14: Eect of adjusting the neutral deadband parameter .........30, 31
. 15: Eect of adjusting the throttle max parameter .................32, 33
. 16: rottle maps for controller with maximum speed set
at 100% and creep speed set at 0 ...........................................34
. 17: rottle maps for controller with maximum speed set
at 80% and creep speed set at 10% .......................................35
. 18: Inuence of various parameters on controller output
response to throttle demand ..................................................35
. 19: Field current relative to armature current,
with field map parameter set at 50% and 20% ......................40
TABLES
 1: Voltages at throttle wiper input ............................................ 10
 2: Mode selection ..................................................................... 22
 3: Programmable throttle types ................................................. 29
 4: Fault categories .................................................................... 43
 5: Troubleshooting chart .......................................................... 73
 6: Status LED fault codes ........................................................ 74
 7: Fault category codes ............................................................ 75
 C-1: Specifications, 1244 controller ....................................... C-1
vi
Curtis 1244 Manual, Rev. E
Page 7
1
Fig. 1 Curtis 1244
MultiMode™ electronic motor controller.
1 — OVERVIEW
OVERVIEW
Curtis 1244 MultiMode™ controllers are separately excited motor speed con­trollers designed for use in a variety of material handling vehicles. ese pro­grammable controllers are simple to install, efficient, and cost eective. Typical applications include low lifts, stackers, fork lifts, reach trucks, personnel carriers, counterbalance trucks, order pickers, boom trucks, and other industrial vehicles.
control of motor speed and torque. A four quadrant, full-bridge field winding control stage is combined with a two quadrant, half-bridge armature power stage to provide solid state motor reversing and regenerative braking power without additional relays or contactors. e 1244 controller can also be specified to be compatible with CAN Bus communication systems.
held programmer or PC programming station. Use of the programmer provides diagnostic and test capability as well as configuration exibility.
Curtis 1244 Manual, Rev. E
e 1244 MultiMode™ controller oers smooth, silent, cost eective
ese controllers are fully programmable by means of the optional hand-
1
Page 8
1 — OVERVIEW
Like all Curtis motor controllers, the 1244 oers superior operator control of the vehicle’s motor drive speed. Features include:
Full-bridge field and half-bridge armature power MOSFET design,
providing
•infinitelyvariableforward,reverse,drive,andbrakecontrol
• silenthighfrequencyoperation  • highefficiency
Regenerative braking, providing longer operation on a single battery charge
and reducing motor brush wear and motor heating
Programmability through the 1313 handheld programmer and 1314 PC
Programming Station
Complete diagnostics through the programmer and the internal Status LED
Two fault outputs provide diagnostics to remotely mounted displays
Continuous armature current control, reducing arcing and brush wear
Automatic braking when throttle is reduced from either direction; this
provides a compression braking feel and enhances safety by automatically initiating braking in an operator hands o condition
Deceleration Rate, Load Compensation, and Restraint features prevent
downhill runaway conditions; speed is controlled to within approximately 20% of level surface value
MultiMode™ allows four user-selectable vehicle operating personalities
Programmable to match individual separately excited motor characteristics
Meets or exceeds EEC fault detect requirements
Vehicle top speed is controlled and limited in each mode
Linear temperature and undervoltage cutback on motor currents; no sudden
loss of power under any thermal conditions
High pedal disable (HPD) and static return to o (SRO) interlocks prevent
vehicle runaway at startup
Creep speed adjustable from 0% to 25% in each mode
Continuous diagnostics during operation, with microprocessor power-on
self-test
Internal and external watchdog circuits ensure proper software operation
Programmable coil drivers provide adjustable contactor pull-in and holding
voltages
Hour-meter enable output is active whenever the controller is providing
motor current
Optional Electromagnetic Brake Driver provides automatic control of an
Optional Reverse Signal Driver provides a low signal any time the vehicle
2
electromagnetic brake or other similar function
is driving or braking in reverse
Curtis 1244 Manual, Rev. E
Page 9
1 — OVERVIEW
Optional Auxiliary Driver provides a low signal to power an auxiliary
contactor or other similar function
Driver outputs are short circuit protected and provide built-in coil spike
protection
Controller is programmable to provide throttle control of motor speed,
applied motor voltage, or motor torque
Can be configured for CAN Bus compatibility.
Familiarity with your Curtis controller will help you install and operate it properly. We encourage you to read this manual carefully. If you have questions, please contact the Curtis office nearest you.
Curtis 1244 Manual, Rev. E
3
Page 10
2 — INSTALLATION & WIRING: Controller
MOUNTING THE CONTROLLER
2
e outline and mounting hole dimensions for the 1244 controller are shown in Figure 2.
ratings for environmental protection against dust and water. However, the lo-
cation should be carefully chosen to keep the controller as clean and dry as possible.When selecting the mounting position, be sure to also take into
consideration (1) that access is needed at the top of the controller to plug the
INSTALLATION AND WIRING
e controller can be oriented in any position, and meets the IP64/IP67
Fig. 2 Mounting
dimensions, Curtis 1244 controller.
7.1 (0.28) dia.,
178
(7.00)
159
(6.25)
9.5
(0.375)
4 plcs
M8 thread, 3 plcs
STATUS
LED
229 (9.00)
M6 thread, 2 plcs
210 (8.25)
(3.19)
Dimensions in millimeters (and inches)
4
81
12.7
(0.50)
Curtis 1244 Manual, Rev. E
Page 11
2 — INSTALLATION & WIRING: Controller
programmer into its connector, and (2) that the built-in Status LED is visible only through the view port in the label on top of the controller.
To ensure full rated power, the controller should be fastened to a clean, at metal surface with four 6 mm (1/4") diameter screws, using the holes pro­vided. Although not usually necessary, a thermal joint compound can be used to improve heat conduction from the controller heatsink to the mounting surface.
CAUTION
Working on electric vehicles is potentially dangerous. You should pro­tect yourself against runaways, high current arcs, and outgassing from lead acid batteries:
RUNAWAYS — Some conditions could cause the vehicle to run out of control.
Disconnect the motor or jack up the vehicle and get the drive wheels o the ground before attempting any work on the motor control circuitry. : If the wrong throttle type is selected with the programming device, the vehicle may suddenly begin to move.
HIGH CURRENT ARCS — Electric vehicle batteries can supply very high power,
and arcs can occur if they are short circuited. Always open the battery circuit before working on the motor control circuit. Wear safety glasses, and use properly insulated tools to prevent shorts.
LEAD ACID BATTERIES — Charging or discharging generates hydrogen gas,
which can build up in and around the batteries. Follow the battery man­ufacturer’s safety recommendations. Wear safety glasses.
Curtis 1244 Manual, Rev. E
5
Page 12
24 23 22 21 20 19 18 17 16 15 14 13
12 11 10 9 8 7 6 5 4 3 2 1
2 — INSTALLATION & WIRING:
Controller
CONNECTIONS
Low Current Connections
ree low current connectors are built into the 1244 controller. ey are located in a row on the top of the controller:
24-pin 6-pin 4-pin
e 24-pin connector provides the logic control connections. e mating connector is a 24-pin Molex Mini-Fit Jr. connector part number 39-01-2245 using type 5556 terminals.
Pin 1 keyswitch input (KSI) Pin 2 interlock input Pin 3 Mode Select 1 input Pin 4 Mode Select 2 input Pin 5 Fault 1 output Pin 6 Fault 2 output Pin 7 emergency reverse input Pin 8 pedal switch input Pin 9 coil return input Pin 10 forward input Pin 11 reverse input Pin 12 hour meter enable output
Pin 13 throttle: 3-wire pot high Pin 14 throttle: pot low Pin 15 throttle: 3-wire pot wiper or 0–5V Pin 16 throttle: 2-wire 5kΩ–0 or 0–5kΩ input Pin 17 main contactor driver output Pin 18 auxiliary contactor driver output Pin 19 reverse signal driver output Pin 20 electromagnetic brake driver output Pin 21 (not used) Pin 22 emergency reverse check output Pin 23 (not used) Pin 24 (not used)
6
Curtis 1244 Manual, Rev. E
Page 13
B- B+M-
456
123
2 — INSTALLATION & WIRING: Controller
A 6-pin low power Molex connector is provided for the CAN Bus interface. However, the CAN Bus option must be specified for this interface to be active. e mating connector is a Molex Mini-Fit Jr. p/n 39-01-2065 using type 5556 terminals.
Pin 1 +15V supply (limited) Pin 2 ground return (B-) Pin 3 CAN H I/O line
Pin 4 L termination Pin 5 H termination Pin 6 CAN L I/O line
e +15V supply should only be used with the CAN system or speed sensor and not to power any other external systems.
e L and H terminations provide a 120Ω termination impedance for the CAN H I/O and CAN L I/O inputs if necessary. Refer to the Curtis CAN Protocol Document to determine the proper termination for a given application.
CABLE-FREE ZONES
F1
A 4-pin low power connector is provided for the handheld 1313 programmer or 1314 PC programming station. A complete programmer kit, including the appropriate connecting cable, can be ordered from Curtis.
If a programmer is already available but has an incompatible cable, the 1244 mating cable can be ordered as a separate part: Curtis p/n 16185.
High Current Connections
Five tin-plated solid aluminum bus bars are provided for the high current connec­tions to the battery and
F2). ese bus bars incorporate threaded mounting studs designed to accept
mounting bolts. e
(B+ and B-), the motor armature (M-), and the motor field (F1
B+, B-, and M- bus bars are threaded to accept M8 bolts to
a depth of 3/4". e F1 and F2 bus bars are threaded to accept M6
bolts to a depth of 5/8". is simplifies the assembly
STATUS LED
and reduces the mounting hardware necessary for the power connections. e tightening torque applied to
F2
the bolts should not exceed 16.3 N·m (12 ft-lbs) for the M6 bolts or 20 N·m (15 ft-lbs) for the M8 bolts. Exceeding these specifications could damage the bus bars’ internal threads, resulting in loose connections.
CAUTION
Power cables must not be routed over the indicated areas. Otherwise they may interfere with the proper operation of sensitive electromagnetic compo­nents located underneath.
Curtis 1244 Manual, Rev. E
7
Page 14
2 — INSTALLATION & WIRING: Controller
B- B+M-
F2F1
INTERLOCK
5 kΩ–0 THROTTLE
(TYPICAL)
FORWARD
MAIN
CONTACTOR
COIL
POLARITY
PROTECTION
DIODE
REVERSE
MODE SELECT 2
MODE SELECT 1
B+
B-
KEYSWITCH
POWER
FUSE
A
MAIN
CONTACTOR
A2 A1
F1 F2
CONTROL
FUSE
WIRING:  Standard Conguration
Figure 3 shows the typical wiring configuration for most applications. e interlock switch is typically a seat switch, tiller switch, or foot switch.
Standard Power Wiring
Motor armature winding is straightforward, with the armature’s A1 connection going to the controller’s B+ bus bar and the armature’s A2 connection going to the controller’s M- bus bar.
vious. e direction of vehicle travel with the forward direction selected will depend on how the terminals and how the motor shaft is connected to the drive wheels through the vehicle’s drive train.
e motor’s field connections (
F1 and F2 connections are made to the controller’s two field
F1 and F2) to the controller are less ob-
Fig. 3 Standard wiring configuration, Curtis 1244 controller.
8
Curtis 1244 Manual, Rev. E
Page 15
2 — INSTALLATION & WIRING: Controller
Standard Control Wiring
Wiring for the input switches and contactors is shown in Figure 3; the connector is shown in more detail below.
24-pin detail (see Fig. 3):
EMERGENCY
REVERSE
CHECK
(factory option)
ELECTRO-
MAGNETIC
BRAKE
DRIVER
REVERSE
SIGNAL DRIVER
AUX
CONTACTOR
DRIVER
MAIN
CONTACTOR
DRIVER
2-WIRE
POT
(5 kΩ)
POT
WIPER
POT
LOW
POT
HIGH
24 23 22 21 20 19 18 17 16 15 14 13
12 11 10 9 8 7 6 5 4 3 2 1
HOUR
METER
REVERSE
FORWARD
COIL
RETURN
PEDAL
SWITCH
EMERGENCY
REVERSE
(walkies only)
FAULT
2
FAULT
1
MODE
SELECT
2
MODE
SELECT
1
INTERLOCK
KEYSWITCH INPUT (KSI)
e main contactor coil must be wired directly to the controller as shown in Figure 3. e controller can be programmed to check for welded or missing main contactor faults and uses the main contactor coil driver output to remove power from the controller and motor in the event of various other faults. If the
main contactor coil is not wired to Pin 17, the controller will not be able to open the main contactor in serious fault conditions and the system will therefore not meet EEC safety requirements.
Curtis 1244 Manual, Rev. E
9
Page 16
2 — INSTALLATION & WIRING: Throttle
WIRING: Throttle
Various throttles can be used with the 1244 controller. ey are categorized as one of five types in the programming menu of the handheld programmer.
Type 1: two-wire 5kΩ–0 throttles
Type 2: 0–5V throttles, current source throttles, three-wire potentiometer throttles, and electronic throttles—wired for single-ended operation
Type 3: two-wire 0–5kΩ throttles
Type 4: 0–5V and three-wire potentiometer throttles—wired for wig­wag-style operation
Type 5: CAN-Nodes throttles e operating specifications for these throttle types are summarized in Table 1.
Table 1 THROTTLE WIPER INPUT: THRESHOLD VALUES
MINIMUM THROTTLE HPD THROTTLE MAXIMUM THROTTLE THROTTLE DEADBAND (25% throttle MAX THROTTLE TYPE PARAMETER FAULT (0% throttle) active range) (100% modulation) FAULT
1 Wiper Voltage 0.1 V 3.3 V 1.0 V 0.2 V 4.4 V Wiper Resistance 5.0 kΩ 3.8 kΩ 0 kΩ 7.5 kΩ
2 Wiper Voltage (none) 0.2 V 1.4 V 5.0 V 5.5 V Wiper Resistance
3 Wiper Voltage 0.1 V 0.2 V 1.0 V 3.3 V 4.4 V Wiper Resistance 0 kΩ 1.3 kΩ 5.0 kΩ 7.5 kΩ
4 Wiper Voltage 0.5 V 2.5 V (fwd)* 3.1 V (fwd) 4.4 V (fwd) 4.5 V
2.5 V (rev)* 1.9 V (rev) 0.6 V (rev) Wiper Resistance 0.5 kΩ 2.5 kΩ (fwd)* 3.1 kΩ (fwd) 4.4 kΩ (fwd) 4.5 kΩ
2.5 kΩ (rev)* 1.9 kΩ (rev) 0.6 kΩ (rev)
5 Wiper Voltage N/A N/A N/A N/A N/A Wiper Resistance N/A N/A N/A N/A N/A
Notes: The Upper and Lower Deadbands are valid for nominal 5kΩ potentiometers or 5V sources with the
default Throttle Deadband and Throttle Max parameter settings of 0% and 100% respectively. These values will change with variations in the Throttle Deadband and Throttle Max parameter settings—see
Section 3, pages 30 and 32.
The HPD threshold is a percentage of the active throttle range, which is dependent on the pro-
grammed Throttle Deadband and Throttle Max settings. The default HPD Threshold is 25%; the programmable range is 0–25%.
* With 0% Throttle Deadband, there is no neutral point on a Type 4 throttle. It is recommended that
an 8% minimum deadband be used with Type 4 throttles.
All throttle fault protection is accomplished by monitoring the wiper input. is provides throttle fault protection that meets all EEC requirements. us, no additional fault protection is required on any throttle type used with the 1244 controller.
10
Curtis 1244 Manual, Rev. E
Page 17
2 — INSTALLATION & WIRING: Throttle
Pin 14
Pot Low
Wiring for various throttles is described below. : In the text, throttles are identified by their nominal range and not by their actual operating range.
If the throttle you are planning to use is not covered, contact the Curtis office nearest you.
5kΩ–0 Throttle (“Type 1”)
e 5kΩ–0 throttle (called a “Type 1” throttle in the programming menu of the handheld programmer) is a 2-wire resistive throttle that connects between the 2-Wire Pot and Pot Low pins (Pins 16 and 14), as shown in Figure 4. It doesn’t matter which wire goes on which pin. For Type 1 throttles, zero speed corresponds to a nominal 5 kΩ measured between the two pins and full speed corresponds to 0Ω. (: is wiring is also shown in the standard wiring diagram, Figure 3.)
Fig. 4 Wiring for 5k
Ω
–0
throttle (“Type 1”).
Fig. 5 Wiring for 20k
Ω
potentiometer used as part of a wigwag-style throttle (“Type 1”).
FASTER
14 1315161718192021222324
12 11 10 9 8 7 6 5 4 3 2 1
5kΩ–0
PIN KEY
Pin 16 Pin 14
2-Wire Pot Pot Low
In addition to accommodating the basic 5kΩ–0 throttle, the Type 1 throttle can also be used to implement a wigwag-style throttle. Using a 20kΩ pot wired as shown in Figure 5, the pot wiper can be set such that the controller has 5 kΩ between Pins 16 and 14 when the throttle is in the neutral position. e throttle mechanism can then be designed such that rotating it either forward or back decreases the resistance between Pins 16 and 14, which increases the controller output. e throttle mechanism must provide signals to the controller’s forward and reverse inputs independent of the throttle pot resistance. e controller will not sense direction from the pot resistance with rottle Type 1. For true
FASTERFASTER
12 11 10 9 8 7 6 5 4 3 2 1
14 1315161718192021222324
Curtis 1244 Manual, Rev. E
20 kΩ
Pin 16
PIN KEY
2-Wire Pot
11
Page 18
14 1315161718192021222324
12 11 10 9 8 7 6 5 4 3 2 1
14 1315161718192021222324
12 11 10 9 8 7 6 5 4 3 2 1
+
-
+
B-
Pin 15
0–5V Input
PIN KEY
Pin 15 Pin 14
0–5V Input Pot Low
PIN KEY
SENSOR GROUND
SENSOR OUTPUT (0–5V)
SENSOR
2 — INSTALLATION & WIRING: Throttle
wigwag-style control—without the necessity of providing independent forward and reverse input signals—see rottle Type 4.
controller’s 4.4 V upper fault limit will be exceeded and the controller output will be disabled. is provides broken wire protection, and also serves as an indication that the potentiometer’s nominal value has increased and the pot needs to be replaced.
0–5V, 3-Wire Potentiometer, Current Source, and Electronic Single-Ended Throttles (“Type 2”)
With these throttles (“Type 2” in the programming menu) the controller looks for a voltage signal at the wiper input (Pin 15). Zero speed will correspond to 0V and full speed to 5 V. A 3-wire pot, voltage source, voltage sensor, or current source can be used with this throttle type. e wiring for each is slightly dierent.
0–5V rottle
Two ways of wiring the 0–5V throttle are shown in Figure 6. e active range for this throttle is from 0.2V (at 0% rottle Deadband) to 5.0 V (at 100% rottle Max), measured relative to B-.
If the total resistance between Pins 14 and 16 is greater than 7.5 kΩ, the
Fig. 6 Wiring for
0–5V throttles (“Type 2”).
(a)  Sensor-referenced
0–5V throttle
(b)  Ground-referenced
0–5V throttle
12
Curtis 1244 Manual, Rev. E
Page 19
Fig. 7 Wiring for 3-wire
14 1315161718192021222324
12 11 10 9 8 7 6 5 4 3 2 1
R
throttle
B-B-
source
Pin 15
0–5V Input
PIN KEY
I
potentiometer throttle (“Type 2”).
2 — INSTALLATION & WIRING: Throttle
3-Wire Potentiometer (1kΩ–10kΩ) rottle
e 3-wire potentiometer is used in its voltage divider mode, with the voltage source and return being provided by the 1244 controller. Pot High (Pin 13) provides a current limited 5V source to the pot, and Pot Low (Pin 14) provides the return path. e pot wiper is then connected to the Wiper Input (Pin15). If a 3-wire pot is used in the application, the controller will provide full throttle fault protection in accordance with EEC requirements. Potentiometers with total resistance values between 1kΩ and 10kΩ can be used with rottle Type 2. Wiring is shown in Figure 7.
Fig. 8 Wiring for current
source throttle (“Type 2”).
1kΩ–10kΩ
OFFON
12 11 10 9 8 7 6 5 4 3 2 1
Pin 15 Pin 14 Pin 13
14 1315161718192021222324
PIN KEY
Pot Wiper Pot Low Pot High
Current Sources As rottles
A current source can also be used as a throttle input, as shown in Figure 8. A resistor, R
, must be used to convert the current source value to a voltage.
throttle
e resistor should be sized to provide a 0–5V signal variation over the full current range.
Curtis 1244 Manual, Rev. E
13
Page 20
2 — INSTALLATION & WIRING: Throttle
14 1315161718192021222324
12 11 10 9 8 7 6 5 4 3 2 1
GREEN
ORANGE
BLACK
BLACK/WHITE
WHITE
WHT/BRN
B+
KEYSWITCH
connector
WHT/ GRN
Pin 15
Pin 11 Pin 10 Pin 1
0–5V Input
Reverse Forward KSI Input
PIN KEY
B-
ET-XXX
B-
Curtis ET-XXX Electronic rottle
e Curtis ET-XXX provides a 0–5V throttle and forward/reverse inputs for the 1244 controller. Wiring for the ET-XXX is shown in Figure 9.
Fig. 9 Wiring for Curtis
ET-XXX electronic throttle (“Type 2”).
throttle control. Alternatively, a complete control head assembly is available from Curtis. is control head assembly—the CH series—combines the ET­XXX throttle with a variety of standard control head switch functions for use in walkie and lift truck applications.
14
e ET-XXX can be integrated into a control head to provide wigwag-style
Curtis 1244 Manual, Rev. E
Page 21
Fig. 10 Wiring
for 0–5k
Ω
throttle
(“Type 3”).
2 — INSTALLATION & WIRING: Throttle
0–5kΩ Throttle (“Type 3”)
e 0–5kΩ throttle (“Type 3” in the programming menu) is a 2-wire resistive throttle that connects between the 2-Wire Pot and Pot Low pins (Pins 16 and 14) as shown in Figure 10. Zero speed corresponds to 0Ω measured between the two pins and full speed corresponds to 5 kΩ. is throttle type is not appropriate for use in wigwag-style applications.
FASTER
14 1315161718192021222324
12 11 10 9 8 7 6 5 4 3 2 1
0–5kΩ
PIN KEY
Pin 16 Pin 14
2-Wire Pot Pot Low
If the total resistance between Pins 14 and 16 is greater than 7.5 kΩ, the controller’s 4.4 V upper fault limit will be exceeded and the controller output will be disabled. is provides broken wire protection, and also serves as an indication that the potentiometer’s nominal value has increased and the pot needs to be replaced.
0–5V and 3-Wire Potentiometer Wigwag-Style Throttles (“Type 4”)
With these throttles (“Type 4” in the programming menu) the throttle can be used in true wigwag style. Any potentiometer value between 1 kΩ and 10 kΩ is supported. If a 5kΩ potentiometer is used, the neutral point will be with the wiper at 2.5 kΩ (measured between the Pot Wiper and Pot Low pins [Pins 15 and 14]). e controller will provide increasing speed in the forward direction as the wiper is moved toward Pot High, with maximum forward speed reached at 4.5 kΩ. e controller will provide increasing speed in the reverse direction as the wiper is moved toward Pot Low, with maximum reverse speed reached at 0.5 kΩ.
A 0–5V voltage source can also be used as the wiper input (see Figure6). However, the minimum and maximum wiper voltage must not exceed the 0.5V and 4.5V fault limits.
With a Type 4 throttle, no direction signals to the controllers’ forward and reverse inputs are required. Direction is determined by the wiper input value. e throttle interface to the controller is similar to that for Type 2 throttles.
Curtis 1244 Manual, Rev. E
15
Page 22
2 — INSTALLATION & WIRING: Fault Outputs and Contactor Drivers
CAN-Nodes Throttle (“Type 5”)
e “Type 5” throttle option is designed for use with CAN-based control systems. No connections are required to the throttle input pins (Pins 13–16) or direction pins (Pins 10 and 11), because all communications are handled through the 6-pin CAN-Nodes interface connector. Details on how to combine a given throttle with the CAN-Nodes system are provided in the Curtis CAN Protocol Document. Fault detection for Type 5 throttles is handled by the CAN CRC (Cyclic Redundancy Check) function, which is part of each node in the CAN Bus architecture.
WIRING:  Fault Outputs
e 1244 controller has two fault output drivers, at Pin 5 and Pin 6, which can be used to provide diagnostic information either to a display panel on the vehicle or to a remote location. ese outputs are rated at 10mA maximum current at the nominal battery pack voltage. For information on programming these outputs, see Section 3: Programmable Parameters.
Wiring for the Fault 1 and Fault 2 outputs is shown in Figure 11.
Fig. 11 Wiring for fault
outputs.
14 1315161718192021222324
12 11 10 9 8 7 6 5 4 3 2 1
+
Fault 1
Fault 2
-
B-
Pin 6 Pin 5
PIN KEY
Fault 2 Output Fault 1 Output
WIRING:  Contactor Drivers
e 1244 controller provides contactor coil drivers (at Pins 17–20) for the main contactor, auxiliary contactor, reverse signal, and electromagnetic brake functions. ese four outputs are low side drivers, designed to energize contactor coils. e auxiliary, reverse signal, and electromagnetic brake drivers are optional functions. ey are available only if the Accessory Driver option is specified—see Section 4, page 50.
It is not necessary to specify the contactors’ coil voltage at the nominal battery pack voltage as long as the Contactor Pull-In Voltage and Contactor Holding Voltage parameters are programmed to accommodate the coils’ volt­age rating. However, all coil voltage ratings should be the same, since only one value of pull-in and holding voltage can be specified for all four of the drivers.
e driver outputs are rated at 2 amps and overcurrent protected at 3amps. e controller can be programmed to check for missing coil faults.
16
Curtis 1244 Manual, Rev. E
Page 23
2 — INSTALLATION & WIRING: Contactor Drivers
ese checks can be disabled using a programmer—see Section 3, pages 44 and
45. A coil suppression diode is provided internally to protect the drivers from
inductive spikes generated at turn-o. To take advantage of the controller’s internal coil suppression diode, Pin 9 must be wired such that the return path to the contactor drivers cannot be opened by any switches or contactors.
e driver loads are not limited to contactor coils. Any load can be con­nected to a Pin 17–20 driver as long as it does not exceed the driver’s 2 amp current rating.
For information on programming the various contactor-related parameters, see Section 3: Programmable Parameters.
Main Contactor Driver
In the standard configuration, the main contactor driver (Pin 17) pulls low when the keyswitch input is enabled; this wiring is shown in the standard wiring diagram (Figure 3, page 8).
Alternatively, the main contactor driver can be programmed not to pull low until the interlock input as well as the keyswitch input is enabled. To do this, the Main Contactor Driver Interlock parameter must be set to “On.” If the Main Contactor Driver Interlock parameter is On, the Main Contactor Dropout Delay parameter can be set to allow the main contactor to remain engaged for up to 40 seconds after the interlock signal has been disabled. If the interlock and delay functions are used, the main contactor and the coil return (Pin 9) must both be wired to KSI. is alternative wiring is shown in Figure 12.
Auxiliary Contactor Driver
Like the main contactor driver, the auxiliary contactor driver (Pin 18) pulls low when the interlock input is enabled. e output will be pulse-width-mod­ulated at the coil holding voltage along with the main, reverse signal, and electromagnetic brake contactor drivers, if the Holding Voltage parameter is set to less than 100%.
If desired, the Auxiliary Contactor Dropout Delay parameter can be set to allow the auxiliary contactor to remain engaged for up to 40 seconds after the interlock signal has been disabled. If the delay function is used, the auxiliary contactor and the coil return (Pin 9) must both be wired to KSI rather than the interlock input. is alternative wiring is shown in Figure 12.
Reverse Signal Driver
e reverse signal driver (Pin 19) pulls low when the vehicle is moving in the reverse direction, either in drive or in braking mode. is driver is designed to drive a reverse signal beeper or warning lamp that operates when one input is pulled low. e output will be pulse-width-modulated at the coil holding voltage along with the main, auxiliary, and electromagnetic brake contactor drivers, if the holding voltage parameter is set to less than 100%.
Curtis 1244 Manual, Rev. E
17
Page 24
2 — INSTALLATION & WIRING: Contactor Drivers
14 1315161718192021222324
12 11 10 9 8 7 6 5 4 3 2 1
Pin 20 Pin 19 Pin 18 Pin 17
Pin 9 Pin 2 Pin 1
Electromagnetic Brake Reverse Signal Auxiliary Contactor Main Contactor
Coil Return Interlock Input KSI Input
PIN KEY
MAIN
CONTACTOR
COIL
KEYSWITCH
+
ELECTROMAGNETIC BRAKE
CONTACTOR
COIL
INTERLOCK
AUXILIARY
CONTACTOR
COIL
REVERSE SIGNAL
CONTACTOR
COIL
B-
Fig. 12 Wiring for main,
auxiliary, reverse signal, and electromagnetic brake contactor coils, using the interlock and dropout delay functions.
Electromagnetic Brake Driver
e electromagnetic brake driver (Pin 20) pulls low when the controller receives a throttle request or detects that the vehicle is still in braking mode. If desired, the Brake Delay parameter can be set to allow the brake to remain disengaged for up to 5 seconds after braking to neutral has been completed. If the delay function is used, the brake driver and the coil return (Pin 9) must both be wired to KSI rather than the interlock input. is alternative wiring is shown in Figure 12.
time begins when the throttle is returned to neutral and the PWM output de­celerates to zero. e output will be pulse-width-modulated at the coil holding voltage along with the main, auxiliary, and reverse signal contactor drivers, if the holding voltage parameter is set to less than 100%.
18
If the rottle Braking parameter has been set to zero, the brake delay
Curtis 1244 Manual, Rev. E
Page 25
2 — INSTALLATION & WIRING: Misc. Features
14 1315161718192021222324
12 11 10 9 8 7 6 5 4 3 2 1
Pin 22
Pin 7
Emergency Reverse Check
Emergency Reverse
PIN KEY
+
EMERGENCY
REVERSE
emergency reverse wiring check (optional)
B-
WIRING:  Pedal Switch
When the Pedal Switch option is enabled, controller output is possible only when the pedal input (Pin 8) is pulled to B+. is feature allows a switch connected to the throttle mechanism to guarantee zero controller output when the operator releases the throttle. is adds a safety feature to protect against throttle failures that cause controller output when the throttle is in neutral.
Alternatively, the pedal input can be wired into the brake pedal circuit to automatically force zero controller output when the brake pedal is depressed, regardless of throttle request.
WIRING:  Hour Meter
e hour meter output (Pin 12) pulls to B+ to enable an hour meter whenever current is owing in the motor. is allows accurate accumulation of vehicle operating hours. e output is current limited to 20 mA, and is compatible with Curtis 700 and 800 series hour meters. For wiring, consult the documentation supplied with the hour meter.
Fig. 13 Wiring for emer-
gency reverse (applicable to walkie vehicles only).
WIRING:  CAN Bus Interface
Refer to the Curtis CAN Protocol Document for information about the CAN Bus interface.
WIRING:  Emergency Reverse
If you are installing a 1244 controller in a walkie vehicle, the emergency reverse switch should be wired to Pin 7, as shown in Figure 13.
Curtis 1244 Manual, Rev. E
gency reverse input is pulled to B+ by closing the emergency reverse switch. After the emergency reverse switch is released, normal controller operation is
Emergency reverse is activated when the keyswitch is On and the emer-
19
Page 26
2 — INSTALLATION & WIRING: Misc. Features
not resumed until neutral (no direction) is selected or until the interlock switch
CAUTION
is cycled. operation of the emergency reverse feature. e forward and reverse switches and the away from the operator when the emergency reverse button is pressed.
An optional wire connected directly to the emergency reverse switch provides for broken wire protection when that feature is enabled by the OEM. e emergency reverse check feature periodically pulses the emergency reverse circuit to check for continuity in the wiring. If there is no continuity, controller output is inhibited until the wiring fault is corrected. e emergency reverse wiring check wire (see dotted line in Figure 13) should be connected to the emergency reverse switch terminals and to Pin 22.
For information about the emergency reverse parameters, see Section 3: Programmable Parameters.
CAUTION: e polarity of the F1 and F2 connections will aect the
F1 and F2 connections must be configured so that the vehicle drives
20
Curtis 1244 Manual, Rev. E
Page 27
2 — INSTALLATION & WIRING: Switches, etc.
CONTACTOR, SWITCHES, and OTHER HARDWARE
Main Contactor
A main contactor is recommended for use with any 1244 controller. A main contactor allows the controller and motor to be disconnected from the bat­tery. is provides a significant safety feature in that the battery power can be removed from the drive system if a controller or wiring fault results in battery power being applied to the motor.
A single-pole, single-throw (SPST) contactor with silver-alloy contacts is recommended for use as the main contactor. It is not necessary to specify the coils at the nominal battery pack voltage as long as the Contactor Pull-In Voltage and Contactor Holding Voltage are programmed to accommodate the coil’s voltage rating—see Section 3, page 46. e contactor coil should be specified with a continuous rating if the Holding Voltage parameter is to be set at 100%. Intermittent duty coils can be specified if they are used with ap­propriate Holding Voltage values.
Keyswitch and Interlock Switch
e vehicle should have a master on/o switch to turn the system o when not in use. e keyswitch input provides logic power for the controller. e interlock switch provides a safety interlock to prevent operation when a me­chanical brake is engaged or to ensure operator presence before the vehicle is allowed to move. e keyswitch and interlock switch provide current to drive the various contactor coils as well as the controller’s internal logic circuitry and must be rated to carry these currents.
Forward, Reverse, Mode Select, and Pedal Switches
ese input switches can be any type of single-pole, single-throw (SPST) switch capable of switching the battery voltage at 25 mA.
Reverse Polarity Protection Diode
For reverse polarity protection, a diode should be added to the control circuit. is diode will prohibit main contactor operation and current ow if the battery pack is accidentally wired with the B+ and B- terminals reversed. It should be sized appropriately for the maximum contactor coil and fault diode currents required from the control circuit. e reverse polarity protection diode should be wired as shown in the standard wiring diagram (Figure 3, page 8).
Curtis 1244 Manual, Rev. E
21
Page 28
2 — INSTALLATION & WIRING:
Switches, etc.
Circuitry Protection Devices
To protect the control circuitry from accidental shorts, a low current fuse (ap­propriate for the maximum current draw) should be connected in series with the battery feed to the keyswitch. Additionally, a high current fuse should be wired in series with the main contactor to protect the motor, controller, and batteries from accidental shorts in the power system. e appropriate fuse for each application should be selected with the help of a reputable fuse manu­facturer or dealer. e standard wiring diagram (Figure 3, page 8) shows the recommended location for each fuse.
Mode Select Switch Operation
e two mode select switches (Mode Select 1 and Mode Select 2) together define the four operating modes. e switch combinations are shown in Table 2. Wiring for the mode select switches is shown in the standard wiring diagram (Figure 3, page 8).
Table 2 MODE SELECTION
MODE MODE
MultiMode™ 1 OPEN OPEN
MultiMode™ 2 CLOSED OPEN
MultiMode™ 3 OPEN CLOSED
MultiMode™ 4 CLOSED CLOSED
OPERATING MODE SELECT SELECT
SWITCH 1 SWITCH 2
22
Curtis 1244 Manual, Rev. E
Page 29
3
3 — PROGRAMMABLE PARAMETERS
PROGRAMMABLE PARAMETERS
e 1244 controller has a number of parameters that can be programmed by means of a 1313 handheld programmer or 1314 PC Programming Station. ese programmable parameters allow the vehicle’s performance characteristics to be customized to fit the needs of individual vehicles or vehicle operators.
Each controller is shipped with the parameter settings specified by the OEM. For each programmable parameter, the specification process includes designating whether it is to have User or OEM-only access rights. e OEM specifies which—if any—parameters the user (dealer, distributor, etc.) will be able to adjust. Accordingly, Curtis oers two versions of the programmers: for example, the 1313-1109 is the User handheld programmer (which can adjust only those parameters with User access rights) and the 1313-4409 is the OEM programmer (which can adjust all the programmable parameters).
e MultiMode™ feature of these controllers allows operation in four distinct modes. ese modes can be programmed to provide four dierent sets of operating characteristics, which can be useful for operating in dierent conditions—such as slow precise indoor maneuvering in one mode; faster, long distance, outdoor travel in another mode; and application-specific special conditions in the remaining two modes.
Eight parameters can be configured independently in the four modes:
— acceleration rate (M1–M4)
— braking rate (M1–M4)
— maximum speed (M1–M4)
— creep speed (M1–M4)
— throttle map (M1–M4)
— throttle braking percent (M1–M4)
— drive current limit (M1–M4)
— braking current limit (M1–M4).
Controllers can be factory-set to allow only one mode of operation if a MultiMode™ system is not desirable for the application—see Section 4. It is not necessary to have all eight MultiMode™ parameters on or o together; one or any combination of these parameters can be specified as single-mode and the others specified as MultiMode™.
Curtis 1244 Manual, Rev. E
23
Page 30
3 — PROGRAMMABLE PARAMETERS
are listed in the text by the abbreviated names that are displayed by the pro­grammer. Not all of these parameters are displayed on all controllers; the list for any given controller depends on its specifications.
e manufacturer can specify how these parameters will be configured, but they are not programmable using the programmer. See Section 4: OEM Specified, Factory Set Parameters.
e programmable parameters are described in the following order. ey
ere are additional parameters that can only be configured at the factory.
Acceleration Parameters
Acceleration Rate, M1–M4 Braking Rate, M1–M4 Deceleration Rate Quick Start Taper Rate
Speed Parameters
Maximum Speed, M1–M4 Creep Speed, M1–M4 Regen Speed
rottle Parameters
Control Mode rottle Type rottle Deadband rottle Maximum rottle Map, M1–M4 rottle Braking Percent, M1–M4
Current Limit Parameters
Drive Current Limit, M1–M4 Braking Current Limit, M1–M4 Minimum Field Current Limit Maximum Field Current Limit Restraint Emergency Reverse Current Limit Current Ratio
24
Curtis 1244 Manual, Rev. E
Page 31
3 — PROGRAMMABLE PARAMETERS
Field Control Parameters
Field Map Start Field Map
Fault Parameters
High Pedal Disable (HPD) HPD reshold Static Return to O (SRO) Fault Code
Output Driver Parameters
Main Contactor Driver Interlock Main Contactor Dropout Delay Main Coil Open Check Main Contactor Weld Check Auxiliary Driver Dropout Delay Auxiliary Coil Open Check Reverse Signal Open Check Electromagnetic Brake Delay Electromagnetic Brake Open Check Contactor Holding Voltage Contactor Pull-In Voltage
Other Parameters
Battery Voltage Anti-Tiedown Sequencing Delay Pedal Interlock Emergency Reverse Enable Emergency Reverse Check Node Address Precharge Load Compensation
Curtis 1244 Manual, Rev. E
25
Page 32
3 — PROGRAMMABLE PARAMETERS: Acceleration Parameters
Acceleration Parameters
M1–M4, ACCEL RATE
e acceleration rate defines the time it takes the controller to accelerate from 0% output to 100% output. A larger value represents a longer acceleration time and a gentler start. Fast starts can be achieved by reducing the acceleration time, i.e., by adjusting the accel rate to a smaller value. e acceleration rate is adjustable from 0.1 second to 5.0 seconds, in 0.1 second increments. It can be set independently for each of the four operating modes.
M1–M4, BRAKE RATE
e braking rate defines the time it takes the controller to increase from 0% regen braking current to 100% regen braking current when braking is requested. A larger value represents a longer time and therefore a gentler increase in braking strength. Full braking strength is achieved more quickly when the braking rate parameter value is reduced. e braking rate is adjustable from 0.1 second to
5.0 seconds, in 0.1 second increments, and can be set independently for each of the four operating modes.
DECEL RATE
e deceleration rate defines the time it takes the controller output to respond to a decrease in applied throttle. e deceleration rate defines the vehicle’s braking characteristic for any reduction in throttle, including to neutral, that does not include a request for the opposite direction. It also defines the characteristic for braking after Emergency Reverse is released. e decel rate is adjustable from 0 to 10 seconds, in 0.1 second increments. e decel rate works in conjunction with the throttle braking percent parameter, which must be set greater than zero for the programmed decel rate to be active. e decel rate is not a MultiMode™ parameter, and its value will therefore aect all four operating modes.
QUICK START
e quick start function provides faster than normal acceleration in response to fast changes in throttle demand. Upon receiving a sudden high throttle demand from neutral, the quick start function causes the controller to exceed its normal acceleration rate. e quick start algorithm is applied each time the throttle passes through neutral and the controller is not in braking mode. Quick start is adjustable from 0 to 10, in increments of 1. Increasing the value “livens” the vehicle’s acceleration response to fast throttle movements.
26
Curtis 1244 Manual, Rev. E
Page 33
TAPER RATE
e taper rate parameter sets the rate at which the regenerative braking com­mand ramps down at the completion of regen braking. is controls the feel of the vehicle as it slows down and approaches zero speed. e taper rate should be adjusted such that during a full speed direction transition, the vehicle comes to a smooth stop before accelerating in the opposite direction. e taper rate parameter is adjustable from 0 to 64 in increments of 1, with each increment representing 1/32 of a second. is parameter is not active during plug braking.
Speed Parameters
M1–M4, MAx SPEED
e maximum speed parameter defines the maximum controller output at full throttle. is parameter is adjustable from 0% to 100%, in 1% increments.
3 — PROGRAMMABLE PARAMETERS: Speed Parameters
M1–M4, CREEP SPEED
e creep speed parameter defines the initial controller output generated when a direction is first selected. No applied throttle is necessary for the vehicle to enter the creep mode, only a direction signal. e output maintains creep speed until the throttle is rotated out of the throttle deadband (typically 10% of throttle).
Creep speed is adjustable from 0% to 25% of the controller duty cycle, in 1% increments. e specified creep speed percentage is not displayed as a throttle percent in the programmer’s Test Menu when a direction is selected and zero throttle is applied; only the throttle command is displayed.
REGEN SPEED
e regen speed parameter defines the vehicle speed above which the controller initiates regenerative braking; below this speed, plug braking is used. Once the vehicle begins regen braking, the system will continue to regen brake all the way to zero speed. is threshold is important as it will aect the smoothness of direction transitions when jockeying between forward and reverse at low speeds. Regen braking provides the most benefit when the vehicle is decelerated from fast speeds, whereas plug braking provides noticeably smoother direction changes at slow speeds. e regen speed parameter is adjustable from 0% to 100% of the vehicle speed, in 1% increments. Recommendations for adjusting the regen braking parameter are provided in Section 6: Vehicle Performance Adjustment.
Curtis 1244 Manual, Rev. E
27
Page 34
3 — PROGRAMMABLE PARAMETERS: Throttle Parameters
rottle Parameters
CTRL MODE
e control mode parameter tailors the controller’s output response to throttle commands. e two control modes allow the throttle position to define either applied motor current or applied motor voltage.
In current control mode (Type 0), the throttle position controls the current owing in the motor. e controller varies the percentage of battery voltage applied to the motor to achieve the requested motor current, thus controlling the motor torque. e operator will increase throttle demand to accelerate and reduce the throttle demand once the desired vehicle speed is reached. Any conditions that result in an increase in motor loading or more motor torque will require an increase in throttle demand to maintain the same vehicle speed. e throttle braking percent, current ratio, and decel rate parameters are not active in the current control mode.
In voltage control mode (Type 1), the throttle position controls the percentage of battery voltage and current applied to the motor. e current that is allowed to ow in the motor can be modified using the current ratio parameter; see page 38. In voltage control mode, changes in motor loading will result in only a small change in vehicle speed unless the current limit is reached.
Acceleration and deceleration characteristics of the vehicle in response to throttle changes in any of these modes will be determined by tuning parameters such as accel rate, quick start, etc.
28
Curtis 1244 Manual, Rev. E
Page 35
3 — PROGRAMMABLE PARAMETERS: Throttle Parameters
ThROTTLE TyPE
e 1244 controller accepts a variety of throttle inputs, through various com­binations of its four throttle input pins. e most commonly used throttles can be hooked up directly: 5kΩ–0 and 0–5kΩ 2-wire rheostats, 3-wire pots, 0–5V throttles, Curtis ET-XXX electronic throttles, and CAN-Nodes based throttles.
e standard throttle input signal type options—Types “1” through “5” in the throttle type programming menu—are listed in Table 3. Wiring information and performance characteristics for each throttle type are presented in Section 2.
Table 3 PROGRAMMABLE ThROTTLE TyPES
THROTTLE TYPE DESCRIPTION
1 5kΩ–0, 2-wire rheostat
2 single-ended 3-wire potentiometer (1kΩ to 10kΩ range)
or single-ended 0–5V input (from voltage throttle, Curtis ET-XXX electronic throttle, or current source)
3 0–5kΩ, 2-wire rheostat
4 wigwag 3-wire potentiometer (1kΩ to 10kΩ range)
or wigwag 0–5V input (from voltage throttle)
5 CAN-Nodes throttle
Curtis 1244 Manual, Rev. E
29
Page 36
3 — PROGRAMMABLE PARAMETERS: Throttle Parameters
0–5V Single-Ended Throttle: Type 2
5kΩ–0 Throttle: Type 1
5V
0
0.2V
30% Deadband
10% Deadband
0% Deadband
0.5V
2.0V
5V
0
3.3V
(5.0kΩ)
30% Deadband
10% Deadband
0% Deadband
3.0V
(4.5kΩ)
2.3V
(3.2kΩ)
0.2V (0Ω)
0.2V (0Ω)
0.2V (0Ω)
ThRTL DEADBAND
e throttle deadband parameter defines the throttle pot wiper voltage range the controller interprets as neutral. Increasing the throttle deadband setting increases the neutral range. is parameter is especially useful with throttle assemblies that do not reliably return to a well-defined neutral point, because it allows the deadband to be defined wide enough to ensure that the controller goes into neutral when the throttle mechanism is released.
Examples of deadband settings (30%, 10%, 0%) are shown in Figure 14 for throttle types 1 through 4, using a nominal 5kΩ–0 potentiometer. (For throttle type 5, see the Curtis CAN Protocol Document.)
Fig. 14 Eect of
adjusting the throttle deadband parameter (rottle Types 1 and 2).
30
Curtis 1244 Manual, Rev. E
Page 37
0–5V Single-Ended Throttle: Type 2
5kΩ–0 Throttle: Type 1
5V
0
0.2V
30% Deadband
10% Deadband
0% Deadband
0.5V
2.0V
5V
0
3.3V
(5.0kΩ)
30% Deadband
10% Deadband
0% Deadband
3.0V
(4.5kΩ)
2.3V
(3.2kΩ)
0.2V (0Ω)
0.2V (0Ω)
0.2V (0Ω)
3 — PROGRAMMABLE PARAMETERS: Throttle Parameters
Fig. 14, cont’d Eect of
adjusting the throttle deadband parameter
0
(rottle Types 3 and 4).
1.2V
(1.4kΩ)
0.6V
(450Ω)
0.2V (0Ω)
0
0.5V
(500Ω)
0.5V
(500Ω)
0–5kΩ Throttle: Type 3
0–5V Wigwag Throttle: Type 4
1.3V
(1.3kΩ)
2.1V
(2.1kΩ)
(2.9kΩ)
2.9V
3.3V
(5.0kΩ)
3.3V
(5.0kΩ)
3.3V
(5.0kΩ)
3.7V
(3.7kΩ)
4.5V
(4.5kΩ)
4.5V
(4.5kΩ)
5V
30% Deadband
10% Deadband
0% Deadband
5V
30% Deadband
10% Deadband
0% Deadband
0.5V
(500Ω)
Throttle
Deadband
KEY
0%
Controller
Output
100%
2.5V
(2.5kΩ)
Notes: Voltages shown are at the pot wiper relative to B-.
For throttle types 1 and 3, the deadband points are defined in terms of the nominal 5kΩ pot resistance. Using a pot of greater or lesser resistance will give different values for the deadband points.
Throttle Max parameter set at 100%.
4.5V
(4.5kΩ)
e programmer displays the throttle deadband parameter as a percent­age of the nominal throttle wiper voltage range and is adjustable from 0% to 30%, in 2% increments. e default deadband setting is 10%. e nominal throttle wiper voltage range depends on the throttle type selected. See Table 1 (page10) for the characteristics of your selected throttle type.
Curtis 1244 Manual, Rev. E
31
Page 38
3 — PROGRAMMABLE PARAMETERS: Throttle Parameters
0–5V Single-Ended Throttle: Type 2
5kΩ–0 Throttle: Type 1
0
5V
2.0V
100% Throttle Max
30% Deadband
0.2V
4.5V
0.2V
3.0V
2.0V
4.5V
90% Throttle Max 30% Deadband
90% Throttle Max 10% Deadband
60% Throttle Max 10% Deadband
0
5V
2.3V
(3.2kΩ)
0.2V (0Ω)
100% Throttle Max
30% Deadband
3.0V
(4.5kΩ)
1.7V
(2.2kΩ)
0.6V
(450Ω)
90% Throttle Max 30% Deadband
90% Throttle Max 10% Deadband
60% Throttle Max 10% Deadband
0.6V
(450Ω)
2.3V
(3.2kΩ)
3.0V
(4.5kΩ)
ThROTTLE MAx
e throttle max parameter sets the wiper voltage required to produce 100% controller output. Decreasing the throttle max setting reduces the wiper voltage and therefore the full stroke necessary to produce full controller output. is feature allows reduced-range throttle assemblies to be accommodated.
Examples are shown in Figure 15 for throttle types 1 through 4, using a nominal 5kΩ potentiometer. ese examples illustrate the eect of three dif­ferent throttle max settings (100%, 90%, 60%) on the full-stroke wiper voltage required to attain 100% controller output.
Fig. 15 Eect of adjusting
the throttle max parameter (rottle Types 1 and 2).
32
Curtis 1244 Manual, Rev. E
Page 39
0–5kΩ Throttle: Type 3
0–5V Single-Ended Throttle: Type 2
0–5V Wigwag Throttle: Type 4
0
5V
1.2V
(1.4kΩ)
3.3V
(5.0kΩ)
100% Throttle Max
30% Deadband
0.5V
(400Ω)
2.7V
(3.9kΩ)
3.0V
(4.5kΩ)
90% Throttle Max 30% Deadband
90% Throttle Max 10% Deadband
60% Throttle Max 10% Deadband
Notes: Voltages shown are at the pot wiper relative to B-.
For throttle types 1 and 3, the deadband points are defined in terms of the nominal 5kΩ pot resistance. Using a pot of greater or lesser resistance will give different values for the deadband points.
KEY
100%
Throttle
Deadband
Controller
Output
0%
0
5V
2.0V
100% Throttle Max
30% Deadband
0.2V
4.5V
0.2V
3.0V
2.0V
4.5V
90% Throttle Max 30% Deadband
90% Throttle Max 10% Deadband
60% Throttle Max 10% Deadband
1.7V
(2.2kΩ)
10% Deadband
3.0V
(4.5kΩ)
1.2V
(1.4kΩ)
0.5V
(400Ω)
3.0V
(4.5kΩ)
0
5V
100% Throttle Max
30% Deadband
90% Throttle Max 30% Deadband
90% Throttle Max 10% Deadband
60% Throttle Max 10% Deadband
3.7V
(3.7kΩ)
4.5V
(4.5kΩ)
0.5V
(500Ω)
1.3V
(1.3kΩ)
3.7V
(3.7kΩ)
4.3V
(4.3kΩ)
0.7V
(700Ω)
1.3V
1.3kΩ)
2.9V
(2.9kΩ)
4.3V
(4.3kΩ)
0.7V
(700Ω)
2.1V
(2.1kΩ)
2.9V
(2.9kΩ)
3.7V
(3.7kΩ)
1.3V
(1.3kΩ)
2.1V
(2.1kΩ)
3 — PROGRAMMABLE PARAMETERS: Throttle Parameters
Fig. 15, cont’d
Eect of adjusting the throttle max parameter (rottle Types 3 and 4).
the active throttle voltage range. e throttle max parameter can be adjusted from 100% to 60%, in 2% increments. e nominal throttle wiper voltage range depends on the throttle type selected. See Table 1 (page 10) for the char­acteristics of your selected throttle type.
Curtis 1244 Manual, Rev. E
e programmer displays the throttle max parameter as a percentage of
33
Page 40
3 — PROGRAMMABLE PARAMETERS: Throttle Parameters
THROTTLE INPUT (percent of active range)
M1–M4, ThRTL MAP
e throttle map parameter modifies the vehicle’s response to the throttle input. is parameter determines the controller output, based on the selected throttle control mode, for a given amount of applied throttle. Setting the throttle map parameter at 50% provides a linear output response to throttle position. Values below 50% reduce the controller output at low throttle settings, providing en­hanced slow speed control. Values above 50% give the vehicle a faster, jumpier feel at low throttle settings.
e throttle map can be programmed in 5% increments between 20% and 80%. e number refers to the controller output at half throttle, as a percentage of the throttle’s full active range. e throttle’s active range is the voltage or resistance between the 0% output point (throttle deadband) and the 100% output point (throttle max). For example, if maximum speed is set at 100% and creep speed is set at 0, a throttle map setting of 50% will give 50% output at half throttle. e 50% setting corresponds to a linear response. Six throttle map profiles (20, 30, 40, 50, 60, and 80%) are shown as examples in Figure 16, with the maximum speed set at 100% and the creep speed set 0.
Fig. 16 rottle maps for
controller with maximum speed set at 100% and creep speed set at 0.
100
90
80
70
60
50
40
30
20
CONTROLLER OUTPUT (PWM percent)
10
0
THROTTLE MAP
80%
60%
50%
40%
30%
20%
SPEED PARAMETERS
0% Creep Speed
100% Max Speed
100908070605040302010 0
Lowering the max speed or raising the creep speed limits the controller’s output range. rottle map profiles with the creep speed raised from zero to 10% and the max speed reduced from 100% to 80% are shown in Figure 17. e throttle map is always a percentage of the controller’s output range. So, in these examples, the throttle map is a percentage of the 10–80% output range; a 40% throttle map setting will give 38% output at half throttle (40% of the 70% range, which is 28%, shifted up to 38% because it starts at the 10% creep speed). Controller output will begin to increase above the set creep speed as soon as the throttle is rotated out of its normal neutral range (deadband). Controller output will continue to increase, following the curve defined by the
34
Curtis 1244 Manual, Rev. E
Page 41
THROTTLE INPUT (percent of active range)
THROTTLE INPUT (percent)
CONTROLLER OUTPUT (PWM percent)
100908070605040302010 0
SPEED PARAMETERS
10% Creep Speed
80% Max Speed
THROTTLE
PARAMETERS
15% Deadband
90% Throttle Max
40% Throttle Map
80% Max Speed
40% Throttle Map (38% output at half throttle)
10% Creep Speed
15% Throttle Deadband
90% Throttle Max
HALF THROTTLE
100
90
80
70
60
50
40
30
20
10
0
3 — PROGRAMMABLE PARAMETERS: Throttle Parameters
throttle map setting, as the throttle input increases and will reach maximum output when the throttle input enters the upper deadband (crosses the throttle max threshold).
Fig. 17 rottle maps for
controller with maximum speed set at 80% and creep speed set at 10%.
100
90
80
70
60
50
40
30
20
CONTROLLER OUTPUT (PWM percent)
10
0
100908070605040302010 0
THROTTLE MAP
80%
60%
50%
40%
30%
20%
SPEED PARAMETERS
10% Creep Speed
80% Max Speed
e rottle Map operates within the window established by the Creep Speed, Max Speed, rottle Deadband, and rottle Max parameters, as shown in Figure 18. Creep Speed and Max Speed define the controller’s output range, while rottle Deadband and rottle Max define the throttle’s active range. ese four parameters, together with the rottle Map, determine the controller’s output response to throttle demand.
Fig. 18 Inuence of various
parameters on controller output response to throttle demand.
Curtis 1244 Manual, Rev. E
35
Page 42
3 — PROGRAMMABLE PARAMETERS: Current Limit Parameters
M1–M4, ThRT BRK %
e throttle braking percent parameter establishes the braking force applied to the vehicle when the throttle is reduced. rottle braking is engaged when the controller transitions from drive to neutral. e controller recognizes neutral as the condition where neither direction switch is closed, regardless of throttle input. is parameter is adjustable from 0% to 100% of the regen braking current limit specified for a given mode, in 2% increments.
Current Limit Parameters
M1–M4, DRIVE C/L
e drive current limit parameter allows adjustment of the maximum current the controller will supply to the motor during drive operation. is parameter can be used to reduce the maximum torque applied to the drive system by the motor in any of the modes. e drive current limit is adjustable from 200 amps to the controller’s full rated current, in 5 amp increments. e full rated current depends on the controller model.
M1–M4, BRAKE C/L
e braking current limit parameter allows adjustment of the maximum cur­rent the controller will supply to the motor during regen braking operations. During regen braking, this parameter controls the regen current from the motor’s armature into the battery. e braking current limit is adjustable from 100 amps up to the controller’s full rated current, in 5 amp increments. e full rated current depends on the controller model.
FIELD MIN
e minimum field current limit parameter defines the minimum allowed current in the motor’s field winding. Its setting will determine the vehicle’s maximum speed and, to some extent, the smoothness with which the vehicle starts and transitions from one direction to another. If the Field Min value is set high, the vehicle’s top speed will be reduced, but torque bumps may be evident when the vehicle is inched or changes direction.
One of the greatest advantages of the Field Min parameter is that it will prevent uncontrolled acceleration when the vehicle encounters a decline. e vehicle’s speed is limited when it goes down ramps or when it is unloaded from trucks, etc.
e Field Min parameter is adjustable from 2 to 20 amps, in 0.5 amp increments. Recommendations for adjusting the Field Min parameter are pro­vided in Section 6: Vehicle Performance Adjustment.
36
Curtis 1244 Manual, Rev. E
Page 43
3 — PROGRAMMABLE PARAMETERS: Current Limit Parameters
FIELD MAx
e maximum field current limit parameter defines the maximum allowed current in the motor’s field winding. Its setting will determine the motor’s maximum torque during both drive and braking, and will limit the power dissipation in the field winding itself. e Field Max parameter is adjustable from 7.5 amps to the controller’s full rated field current limit, in 0.5 amp incre­ments. Recommendations for adjusting the Field Max parameter are provided in Section6: Vehicle Performance Adjustment.
RESTRAINT
Because the 1244 controller is configured to provide throttle braking, overspeed will cause the controller to create a braking current and thus limit or “restrain” the overspeed condition. e restraint parameter, in combination with throttle braking percent parameter, determines how strongly the controller will attempt to limit the vehicle speed to the existing throttle setting. is function works at all throttle settings, including zero throttle. It is applicable when throttle is reduced or when the vehicle begins to travel downhill.
e restraint parameter is adjustable from 1 to 10. Setting the parame­ter to a high value will cause strong braking, in an eort to bring the vehicle speed down to the requested speed. Setting the restraint value to 1 will result in minimal regen braking.
At zero throttle, the restraint function will also attempt to keep the motor at zero speed. is will help hold the vehicle from running away down ramps when braking to neutral is completed and the mechanical or electromagnetic brake has not engaged. e higher the restraint parameter value, the stronger the braking force applied to the motor and the slower the vehicle will creep down the ramp. is creeping speed will depend on the restraint setting, the steepness of the ramp, and the vehicle load. e restraint feature can never hold a vehicle perfectly stationary on a ramp and is not intended to replace a mechanical or electromagnetic brake for this purpose. e throttle braking percent parameter is not active in this situation, and the controller will supply up to the maximum programmed regen current limit. Recommendations for adjusting the restraint parameter are provided in Section 6: Vehicle Performance Adjustment.
Curtis 1244 Manual, Rev. E
37
Page 44
3 — PROGRAMMABLE PARAMETERS: Field Control Parameters
EMR REV C/L
e emergency reverse current limit parameter defines the maximum braking current provided through the motor when the emergency reverse function is engaged. e emergency reverse current limit is adjustable from 50 amps to the controller’s full rated braking current limit, in 5 amp increments.
CURRENT RATIO
e current ratio parameter defines how much of the programmed drive current will be available to the motor at reduced throttle requests. is will determine the maximum torque the motor can provide at partial throttle. e current ratio parameter can be set to 1, 2, 4, or 8. ese settings represent a multiplication factor applied to the current that would otherwise be available. For example, if 20% throttle is requested with the current ratio set at 1, 20% of the battery voltage and 20% of the drive current will be allowed to ow in the motor (as­suming a 50% throttle map setting). If the current ratio is set at 2 under these same conditions, 40% of the current will be available; if it is set at 4, 80%. e controller will never allow more than the programmed drive current to ow in the motor. If the current ratio is set at 8 with 20% throttle requested, the controller will allow only 100% of the drive current and not 160%.
Because the current ratio parameter aects how much torque the motor can provide, high current ratio settings will result in improved ramp climbing with partial throttle, but may cause too much jumpiness at startup.
: e current ratio parameter is valid only when the control mode parameter is set to Type 1 (Voltage Control).
38
Field Control Parameters
FLD MAP START
e field map start parameter defines the armature current at which the field map starts to increase from the Field Min value. is parameter is expressed in amperes, and is adjustable from 0 to one half the controller’s full rated armature current value, in 5 amp increments. e Field Map Start parameter is used to equalize the vehicle’s maximum speed when loaded and unloaded.
Increasing the Field Map Start value increases the maximum load the vehicle can carry while still maintaining maximum speed on a level surface. Whether the vehicle’s loaded speed will actually increase depends on the arma­ture current being drawn at that load. If the armature current is already below the Field Map Start setting, increasing the Field Map Start value will not aect the vehicle’s loaded speed.
Curtis 1244 Manual, Rev. E
Page 45
3 — PROGRAMMABLE PARAMETERS: Field Control Parameters
Care should be taken to ensure that high Field Map Start values do not move the motor’s operating characteristics outside its safe commutation area. Recommendations for adjusting the Field Map Start parameter to achieve vari­ous performance characteristics are provided in Section 6: Vehicle Performance Adjustment Guidelines.
FIELD MAP
e field map parameter defines the variation of the field winding current as a function of armature current. It controls how much field current is applied for a given armature current, and is adjustable from 0% to 100%, in 5% increments.
e Field Map parameter is set as a percentage of the field current between the Field Min and Field Max values. As shown in Figure 19, the Field Map parameter increases or decreases the field current at the armature current that is halfway between the Field Map Start current and the controller’s programmed drive current limit. is point on the armature current curve is referred to as the Field Map Midpoint.
With the Field Map set at 50% and the Field Map Start set at zero, the motor’s field current increases linearly with increasing armature current—thus emulating a series wound motor. Decreasing the field map setting reduces the field current at a given armature current, i.e., it weakens the field. As the field current is reduced, the motor will be able to maintain speeds closer to the maximum speed value.
Care should be taken to ensure that excessively low Field Map values do not move the motor’s operating characteristics outside its safe commutation region. Recommendations for adjusting the Field Map parameter to achieve various performance characteristics are provided in Section 6: Vehicle Perfor­mance Adjustment Guidelines.
Curtis 1244 Manual, Rev. E
39
Page 46
3 — PROGRAMMABLE PARAMETERS: Field Control Parameters
Fig. 19 Field current
relative to armature
Field Max
current, with field map parameter set at 50% and 20%.
Field Map
(50%)
FIELD CURRENT
Field Min
0
0
Field Max
Field Map Start Field Map Midpoint 100%
ARMATURE CURRENT
Field Map
(20%)
FIELD CURRENT
Field Min
0
0
Field Map Start Field Map Midpoint 100%
ARMATURE CURRENT
40
Curtis 1244 Manual, Rev. E
Page 47
Fault Parameters
3 — PROGRAMMABLE PARAMETERS: Fault Parameters
hPD
e high pedal disable (HPD) feature prevents the vehicle from driving the motor if greater than HPD reshold throttle is applied when the controller is turned on. In addition to providing routine smooth starts, HPD also protects against acciden­tal sudden starts if problems in the throttle linkage (e.g., bent parts, broken return spring) give a throttle input signal to the controller even with the throttle released.
If the operator attempts to start the vehicle with the throttle already ap­plied, the controller will inhibit output to the motor until the throttle is reduced below HPD reshold. For the vehicle to run, the controller must receive
a KSI input [Type 1],
a KSI input and an interlock input [Type 2], or
a KSI input, an interlock input, and a direction input [Type 3], before receiving a throttle input. Either of these three types of HPD can be selected via the programmer. HPD can also be disabled [Type 0]. To meet EEC requirements, the HPD feature must be programmed to Type 1 or 2. To meet MSHA requirements, HPD must be programmed to Type 3.
Sequencing delay (see page 47) can be used to provide a variable delay before the controller is disabled, if desired.
No HPD (Type 0)
HPD function is disabled.
Interlock-type HPD (Type 1)
To start the vehicle, the controller must receive an interlock switch input in addition to a KSI input before receiving a throttle input. Controller operation will be disabled immediately if throttle input is greater than HPD reshold at the time the interlock switch is closed. Normal controller operation is regained by reducing the throttle demand to less than HPD reshold.
KSI-type HPD (Type 2)
To start the vehicle, the controller must receive a KSI input before receiving a throttle input. Controller operation will be disabled immediately if throttle input is greater than HPD reshold at the time KSI is enabled. If throttle is applied before the interlock switch is closed but after the KSI input has been enabled, the vehicle will accelerate to the requested speed as soon as the inter­lock switch is closed. Normal operation is regained by reducing the throttle demand to less than HPD reshold.
Golf-type HPD (Type 3)
To start the vehicle, the controller must receive a direction input in addition to an interlock switch input and a KSI input before receiving a throttle input. Controller operation will be disabled immediately if throttle input is greater
Curtis 1244 Manual, Rev. E
41
Page 48
3 — PROGRAMMABLE PARAMETERS: Fault Parameters
than HPD reshold at the time the direction switch is closed or is changed while driving. Normal controller operation is regained by reducing the throttle demand to less than HPD reshold.
hPD ThREShOLD
e HPD threshold parameter denes the maximum throttle allowed at startup. If throttle is greater than this threshold at startup, an HPD fault is issued. is parameter has a default setting of 25%, and is programmable from 0 to 25%.
SRO
e static return to o (SRO) feature prevents the vehicle from being started when “in gear.” SRO checks the sequencing of the interlock input—or the in­terlock input and KSI—relative to a direction input. e interlock input—or the interlock plus KSI inputs—must come on before a direction is selected. If a direction is selected before or simultaneously (within 50 msec) with the interlock input, the controller is disabled.
ree types of SRO are available (along with a “no SRO” option):
Type 0: no SRO Type 1: SRO on interlock input plus a direction input Type 2: SRO on KSI plus interlock input plus a direction input Type 3: SRO on KSI plus interlock input plus forward direction input.
If your controller is programmed so that both KSI and interlock inputs are required (SRO Type “2”), the following sequence must be followed to enable the controller:  1, turn on KSI;  2, activate interlock (input “high”); and then  3, select a direction. e interval between steps 1 and 2 is the same as between steps 2 and 3; that is, KSI input must precede interlock input by at least 50 msec. Once the controller is operational, turning o either KSI or the interlock causes the controller to turn o; re-enabling the controller requires the 3-step sequence.
Similarly, if your controller is programmed so that KSI, interlock, and forward inputs are all required (SRO Type “3”), they must be provided in that sequence in order to enable the controller. Note, however, that operation is allowed if a reverse input precedes the interlock input; this can be useful when operating a walkie on ramps.
Sequencing delay (see page 47) can be used to provide a variable delay before disabling the controller, if desired.
FAULT CODE
e 1244 controller’s fault code drivers allow faults to be displayed in either of two dierent formats: Fault Code format or Fault Category format.
42
Curtis 1244 Manual, Rev. E
Page 49
3 — PROGRAMMABLE PARAMETERS: Output Driver Parameters
With the fault code parameter specified “On,” the controller’s fault outputs will provide information in Fault Code format. With the fault code parameter specified “O,” the controller’s fault outputs will provide information in Fault Category format.
In Fault Code format, the two fault lines operate independently. When a fault is present, the Fault 1 driver (Pin 5) provides a pulsed signal equivalent to the fault code ashed by the controller’s built-in Status LED. is signal can be used to drive an LED located on the display panel to provide the fault code in­formation to an operator, or to any remote panel. e Fault 2 driver (Pin 6) pulls low (to B-) and remains on until the fault is cleared; it can also be used to drive a remote LED. When no faults are present, these outputs will both be open (o).
In Fault Category format, the two fault lines together define one of four fault categories. Table 4 describes the four fault categories, shows the state of the two outputs for each category, and lists the faults that might be present when each of the four fault category signals is transmitted.
Table 4 FAULT CATEGORIES
FAULT FAULT 1 FAULT 2
CATEGORY OUTPUT OUTPUT POSSIBLE EXISTING FAULTS
(Pin 5) (Pin 6)
0 HIGH HIGH (no faults present, or controller not operational)
1 LOw HIGH HW Failsafe; M-, Current Sensor, or Motor Fault; Throttle Fault; Emergency Reverse Wiring Fault; Contactor or Output Driver Fault; Precharge Fault
2 HIGH LOw Low Battery Voltage; Overvoltage; Thermal Cutback
3 LOw LOw HPD; SRO; Anti-Tiedown
Output Driver Parameters
MAIN CONT INTR
e main contactor driver interlock parameter allows the manufacturer to define a dual switch requirement to operate the vehicle. When this parameter is set to “On,” the controller requires that both the KSI input (Pin 1) and the interlock input (Pin 2) be pulled high (to B+) before the controller will engage the main contactor. e main contactor will open after the interlock switch is opened and the sequencing and main open delays expire. If this parameter is set to “O,” only the KSI input is required for the main contactor to be engaged.
MAIN OPEN DLy
e main contactor dropout delay parameter is applicable only if the main contactor driver interlock parameter has been set to “On.” e dropout delay
Curtis 1244 Manual, Rev. E
43
Page 50
3 — PROGRAMMABLE PARAMETERS: Output Driver Parameters
parameter can then be set to allow the main contactor to remain closed for a period of time after the interlock switch is opened. e delay time is pro­grammable from zero to 40 seconds, in 1 second intervals. e delay is useful for preventing unnecessary cycling of the main contactor and for maintaining power to auxiliary functions, such as a steering pump motor, that may be used for a short time after the brake has been applied or the operator has gotten up from the seat.
MAIN ChECK
e main coil open check parameter defines whether the controller performs missing coil checks to ensure that the main contactor has closed properly. When this parameter is set to “On,” the controller senses the voltage at the main driver input (Pin 17) to confirm that the main contactor coil is properly connected, and also tests that the main contactor has indeed closed each time it is commanded to do so. If the criteria for either of these tests are not met, the controller will inhibit operation and issue a fault. Neither of these tests is performed if the main check parameter is set to “O.”
wELD ChECK
e main contactor weld check parameter defines whether the controller tests the main contactor to ensure that it is not welded closed. If the weld check parameter is set to “On,” this check is performed when the keyswitch is first engaged and then each time the main contactor is commanded to open. is check is not performed if the parameter is set to “O.”
AUx DELAy
e auxiliary driver dropout delay parameter can be set to allow the auxiliary driver to remain active for a period of time after the interlock switch is opened. e delay time is programmable from 0 to 10 seconds, in 0.1 second intervals.
: e auxiliary driver dropout delay parameter is applicable only if the accessory driver enable has been specified “On.” e accessory driver enable is a factory-set parameter, and is described in Section 4.
AUx ChECK
e auxiliary coil open check parameter defines whether the controller per­forms missing coil checks on the auxiliary driver output. When this parameter is set to “On,” the controller senses the voltage at the auxiliary driver output (Pin18) to confirm that the auxiliary contactor coil is properly connected. If
44
Curtis 1244 Manual, Rev. E
Page 51
3 — PROGRAMMABLE PARAMETERS: Output Driver Parameters
the criteria for this test are not met, the controller will inhibit operation and issue a fault. is test is not performed if the aux check parameter is set to “O.”
Note: e aux check parameter is applicable only if the accessory driver enable has been specified “On.” e accessory driver enable is a factory-set parameter, and is described in Section 4.
REV DRVR ChECK
e reverse signal open check parameter defines whether the controller performs missing load checks on the reverse signal driver output. When this parameter is set to “On,” the controller senses the voltage at the reverse signal driver output (Pin 19) to confirm that the reverse signal driver load is properly connected. If the criteria for this test are not met, the controller will inhibit operation and issue a fault. is test is not performed if the reverse signal open check parameter is set to “O.”
Note: e reverse signal open check parameter is applicable only if the accessory driver enable has been specified “On.” e accessory driver enable is a factory-set parameter, and is described in Section 4.
EM BRAKE DELAy
e electromagnetic brake delay parameter is applicable only if the accessory driver enable has been specified “On.” e accessory driver enable is a factory-set parameter, and is described in Section 4.
e electromagnetic brake delay parameter can be set to delay engaging the electromagnetic brake for a specified period of time after the controller senses that braking has been completed and the vehicle has come to a stop. e delay time is programmable from 0 to 5 seconds, in 0.1 second intervals.
EM BRAKE ChECK
e electromagnetic brake open check parameter defines whether the con­troller performs missing coil checks on the electromagnetic brake driver output. When this parameter is set to “On,” the controller senses the voltage at the electromagnetic brake driver output (Pin 20) to confirm that the electromagnetic brake coil is properly connected. If the criteria for this test are not met, the controller will inhibit operation and issue a fault. is test is not performed if the electromagnetic brake open check parameter is set to “O.”
Note: e electromagnetic brake open check parameter is applicable only if the accessory driver enable has been specified “On.” e accessory driver enable is a factory-set parameter, and is described in Section 4.
Curtis 1244 Manual, Rev. E
45
Page 52
3 — PROGRAMMABLE PARAMETERS: Other Parameters
CONT hOLDING
e contactor holding voltage parameter defines the output duty cycle of the main, auxiliary, reverse, and electromagnetic brake drivers. is parameter is adjustable from 20% to 100% of the battery voltage, in 2% increments. It allows the OEM to reduce the average applied voltage so that a contactor coil or other load that is not rated for the full battery voltage can be used.
For example, contactor coils rated for 12V could be used with a 36V system if the contactor holding voltage parameter were set to 34%. e pa­rameter can be set lower than the rated contactor coil voltage, as long as it is set high enough to hold the contactor closed under all shock and vibration conditions the vehicle will be subjected to. Low settings minimize the current required to power the coil, thereby reducing coil heating and increasing battery life. Recommended values for the contactor holding voltage parameter should be determined with specifications or advice from the contactor manufacturer.
is parameter aects all the driver outputs, so the loads on each driver must allow operation at the set holding voltage. In addition, the loads on each driver must be compatible with a PWM signal (if the parameter is set to a value less than 100%), as the output is pulse width modulated.
CONT PULL IN
e contactor pull-in voltage parameter sets the peak voltage applied to the loads connected to the main, auxiliary, reverse and electromagnetic brake drivers. Typically these loads are contactor coils. e pull-in parameter allows a high initial voltage to be supplied when the driver first turns on, to ensure contactor closure. After 0.1 second, the driver voltage drops to the value specified by the contactor holding voltage parameter. Recommended values for this parameter should be determined with specifications or advice from the contactor manufac­turer. is parameter is adjustable from 20% to 100% of the nominal battery voltage, in 2% increments.
Other Parameters
VOLTAGE
e battery voltage parameter sets the overvoltage and undervoltage protection thresholds for the electronic system. is parameter determines when regen should be cut back to prevent damage to batteries and other electrical system components due to overvoltage. Similarly, the undervoltage threshold protects systems from operating at voltages below their design thresholds. is will ensure proper operation of all electronics whenever the vehicle is driven. e
46
Curtis 1244 Manual, Rev. E
Page 53
3 — PROGRAMMABLE PARAMETERS: Other Parameters
battery voltage parameter can be set from 2 to 7, and should always be set to the system’s nominal battery pack voltage:
   ... .. .. ...
2 24V 14V 16V 28V 31V 3 36V 22V 23.8V 43V 46V 4 48V 24V 32V 55V 61V 5 60V 37V 39V 70V 76V 6 72V 46V 49V 85V 92V 7 80V 52V 57V 97V 105V
.. = Severe Under Voltage (causes reset) . = Under Voltage . = Over Voltage .. = Severe Over Voltage (causes reset)
ANTI-TIEDOwN
e anti-tiedown feature prevents operators from taping or “tying down” the mode select switches in order to operate permanently in Mode 2 or Mode 4. On startup, when the interlock switch is first closed, the anti-tiedown feature checks which operational mode is selected. If the mode select switches are re­questing Mode 2 or Mode 4, the controller will ignore the request and default to Mode 1 or Mode 3 respectively. e controller will remain in Mode 1 or Mode 3 until the Mode Select 1 switch is released and reactivated.
Anti-tiedown is primarily used in walkie applications. It can be pro-
grammed “On” or “O.”
Curtis 1244 Manual, Rev. E
SEQUENCING DLy
e sequencing delay feature allows the interlock switch to be cycled within a set time (the sequencing delay), in order to prevent inadvertent activation of HPD or SRO. is feature is useful in applications where the interlock switch may bounce or be momentarily cycled during operation. e sequencing delay parameter can be set from 0 to 3 seconds, in increments of 0.1 second, with 0 corresponding to no delay.
PEDAL INTR
e pedal interlock parameter can be programmed as “On” or “O.” When “On,” it requires that the pedal switch input (Pin 8) be active (pulled to B+) before the controller will supply power to the motor. is feature is useful in systems that use a seat or foot switch to guarantee operator presence for vehicle operation. Alternatively, a switch connected to the brake pedal can be configured
47
Page 54
3 — PROGRAMMABLE PARAMETERS: Other Parameters
to open immediately so that motor drive is disabled and will not interfere with the mechanical braking function. In this arrangement, when the brake pedal is released the controller output accelerates through its programmed acceleration curve to the existing throttle request.
e controller does not require the pedal signal to engage the main contactor, and the main contactor will not cycle on and o when the pedal switch is opened and closed.
EMR REV ENABLE
e emergency reverse enable parameter enables or disables the emergency reverse function. When it is set to “On,” the controller will be prepared to implement the emergency reverse current limit for enhanced braking and the direction change to reverse when the emergency reverse input (Pin 7) is pulled high (to B+). When the emergency reverse enable parameter is set to “O,” the controller will not respond to any input to Pin 7 and the emergency reverse current limit and emergency reverse check parameters will not be active.
EMR REV ChECK
e emergency reverse check parameter is applicable only when the emergency reverse feature is being used in the application. If emergency reverse is not being used, this parameter should be set to “O.”
When enabled (programmed “On”), the emergency reverse check tests for continuity from the emergency reverse check output (Pin 22) to the emer­gency reverse input (Pin 7). erefore, the emergency reverse wiring should be connected as closely as possible to the controller side of the emergency reverse switch, as shown in Figure 13. If the controller detects this open wire fault, it will disable its output until the wiring fault is fixed. e emergency reverse function will still be active when this fault exists.
NODE ADDR
e node address parameter determines which address the controller will respond to when used with a CAN Bus communications system. e address can be specified from 1 to 15. is parameter is valid only when the CAN Bus function has been specified for the controller; see Section 4.
48
Curtis 1244 Manual, Rev. E
Page 55
3 — PROGRAMMABLE PARAMETERS: Other Parameters
PRECHARGE
e precharge parameter enables or disables the precharge function. When this parameter is set to “On,” the precharge function does not close the main contactor until the internal power capacitor bank charges to within 10% of the battery voltage. Charging is accomplished internally and an external precharge resistor is not required. If the capacitor voltage does not reach this theshold, a precharge fault is issued and the main contactor is never closed. is reduces inrush current stresses on the capacitor bank and provides protection against allowing full battery power to be engaged if there is a short in the output section. Setting the parameter to “O” disables the precharge function. e precharge function is required for systems using 48V (or higher) battery packs.
LOAD COMP
e load compensation parameter actively adjusts the applied motor voltage as a function of motor load current. is results in more constant vehicle speeds over variations in load and in driving surface (ramps, etc.) without the vehicle operator having to constantly adjust the throttle position. is parameter will also help equalize loaded and unloaded vehicle speeds. Higher load compensation values will cause the controller to be more aggressive in attempting to maintain vehicle speed. However, too much load compensation can result in jerky vehicle starts and speed oscillation (“hunting”) when the vehicle is unloaded.
e load compensation parameter is adjustable from 0 to 25. Recom­mendations for adjusting this parameter are provided in Section 6: Vehicle Performance Adjustment.
Curtis 1244 Manual, Rev. E
49
Page 56
4 — OEM-SPECIFIED, FACTORY-SET PARAMETERS
In addition to the programmable parameters described in Section 3, there are
4
three parameters that can be set at the factory per the OEM’s specification:
— MultiMode™ Enable — Accessory Driver Enable — CAN Bus Enable
ese parameters are not programmable with the 1313 handheld programmer or 1314 PC Programming Station. If a change is desired, the controller must be returned to an authorized Curtis facility for reconfiguration.
MULTIMODE™ ENABLE
A key feature of Curtis MultiMode™ controllers is their capability of being configured for optimized performance in four distinctly defined modes. How­ever, should the OEM prefer to oer only a single mode of operation in a given application, the MultiMode™ feature can be disabled. Each of the 1244 controller’s eight MultiMode™ parameters can be individually defined as Mul­tiMode™ or single mode. OEM specifies
OEM-SPECIFIED PARAMETERS
(SET AT FACTORy)
On or O Default setting On
ACCESSORy DRIVER ENABLE
e 1244 controller provides three accessory drivers: an auxiliary driver (Pin 18), a reverse signal driver (Pin 19), and an electromagnetic brake driver (Pin 20).
e auxiliary driver (Pin 18) provides a connection to B- when KSI and the interlock (if enabled) are activated. e driver will release after the programmed auxiliary driver dropout delay when the interlock switch is turned o.
e reverse signal driver (Pin 19) provides a connection to B- whenever the vehicle is moving in reverse, regardless of whether it is driving or braking. When the vehicle is moving forward or is in neutral, the output remains open. e reverse signal driver provides a continuous connec­tion to B- (or a 500Hz pulsed signal if the contactor holding voltage is set at less than 100%) but is not intended to pulse an audible alarm.
e electromagnetic brake driver (Pin 20) will engage (pull to B-) when the throttle is applied or when creep speed is greater than zero and a direction is selected. It will release, after the programmed electromagnetic driver delay, when the throttle is returned to neutral or when the vehi­cle has come to a stop. When the electromagnetic brake driver is used, the neutral braking parameter must be set to a value greater than zero.
50
Curtis 1244 Manual, Rev. E
Page 57
4 — OEM-SPECIFIED, FACTORY-SET PARAMETERS
When the accessory driver enable is specified “On,” these three drivers are en­abled. If none of these drivers is required, the accessory driver enable parameter should be specified as “O.”
Each accessory driver output is rated at 2 amperes and is monitored for open connection and overcurrent faults. An internal diode provides coil sup­pression through the coil return output (Pin 9). Wiring for the accessory drivers is shown in Figure 12, page 18.
When the accessory driver enable is specified “On,” it also enables various programmable parameters associated with the accessory drivers: the auxiliary driver dropout delay, the auxiliary coil open check, the reverse signal open check, the electromagnetic brake dropout delay, and the electromagnetic brake open check. For more information on these programmable parameters, see Section 3.
Any component can be controlled by any of the accessory outputs provided its current requirements do not exceed the driver’s 2 amp rating.
e three accessory drivers are enabled or disabled as a group; it is not possible, for example, to have the electromagnetic brake driver enabled and the auxiliary driver and reverse signal driver disabled. OEM specifies
On or O Default setting On
CAN BUS ENABLE
When enabled, this parameter configures the 1244 controller for use with CAN-based control systems. OEM specifies
On or O Default setting O
Curtis 1244 Manual, Rev. E
51
Page 58
5 — INSTALLATION CHECKOUT
5
INSTALLATION CHECKOUT
Before operating the vehicle, carefully complete the following checkout proce­dure. If you find a problem during the checkout, refer to the diagnostics and troubleshooting section (Section 8) for further information.
e installation checkout can be conducted with or without a 1313 hand­held programmer or 1314 PC Programmig Station. e checkout procedure is easier with a programmer. Otherwise, observe the Status LED (located in the controller’s label area) for diagnostic codes. e codes are listed in Section 8.
CAUTION
Put the vehicle up on blocks to get the drive wheels up o the ground before beginning these tests.
Do not stand, or allow anyone else to stand, directly in front of or behind the vehicle during the checkout.
Make sure the keyswitch is o, the throttle is in neutral, and the forward and reverse switches are open.
Wear safety glasses and use well-insulated tools.
1. If a programmer is available, connect it to the programmer connector.
2. Turn the keyswitch on. e programmer should power up with an initial display, and the controller’s Status LED should begin steadily blinking a single ash. If neither happens, check for continuity in the keyswitch circuit and controller ground.
3. If you are using a programmer, select the Diagnostics Menu, and open the Present Faults folder. e display should indicate “No Known Faults.” Close the interlock switch (if one is used in your application). e Status LED should continue blinking a single ash and the programmer should continue to indicate no faults.
If there is a problem, the LED will flash a diagnostic code and the
programmer will display a diagnostic message. If you are conducting the checkout without a programmer, look up the LED diagnostic code in Section 8 (Diagnostics and Troubleshooting).
When the problem has been corrected, it may be necessary to cycle
the keyswitch in order to clear the fault.
52
Curtis 1244 Manual, Rev. E
Page 59
5 — INSTALLATION CHECKOUT
4. With the interlock switch closed, select a direction and operate the throttle. e motor should begin to turn in the selected direction. If it turns in the wrong direction, first verify the wiring to the forward and reverse switches. If the wiring is correct, turn o the controller, discon­nect the battery, and exchange the motor’s field connections (
F1 and F2)
on the controller. e motor should now turn in the proper direction. e motor should run proportionally faster with increasing throttle. If not, refer to Section 8.
5. If you are using a programmer, select the Monitor Menu. Scroll down to observe the status of the forward, reverse, interlock, emergency reverse, and mode switches. Cycle each switch in turn, observing the program­mer. e programmer should display the correct status for each switch.
6. Take the vehicle down o the blocks and drive it in a clear area. It should have smooth acceleration and good top speed. Recommended procedures for tuning the vehicle’s driving characteristics are presented in Section 6: Vehicle Performance Adjustment.
7. Test the deceleration and braking of the vehicle.
8. Verify that all options, such as high pedal disable (HPD), static return to o (SRO), and anti-tiedown are as desired.
9. On walkie vehicles, check the emergency reverse feature. If you have the optional emergency reverse check wiring, verify that the check circuit is operational by momentarily disconnecting one of the emergency reverse wires. e vehicle should coast to a stop, with a fault indicated.
10. If you used a programmer, disconnect it when you have completed the checkout procedure.
Curtis 1244 Manual, Rev. E
53
Page 60
6 — VEHICLE PERFORMANCE ADJUSTMENT
e 1244 controller is a very powerful vehicle control system. Its wide variety of
6
adjustable parameters allow many aspects of vehicle performance to be optimized. is section provides explanations of what the major tuning parameters do and instructions on how to use these parameters to optimize the performance of your vehicle. Once a vehicle/motor/controller combination has been tuned, the parameter values can be made standard for that system or vehicle model. Any changes in the motor, the vehicle drive system, or the controller will require that the system be tuned again to provide optimum performance.
e tuning procedures should be conducted in the sequence given, because successive steps build upon the ones before. e tuning procedures instruct personnel how to adjust various programmable parameters to accomplish specific performance goals. It is important that the eect of these programmable pa­rameters be understood in order to take full advantage of the 1244 controller’s powerful features. Please refer to the descriptions of the applicable parameters in Section 3 if there is any question about what any of them do.
VEHICLE PERFORMANCE ADJUSTMENT
MAJOR TUNING
Four major performance characteristics are usually tuned on a new vehicle:
ese four characteristics should be tuned in the order listed.
Tuning the Active Throttle Range
Before attempting to optimize any specific vehicle performance characteristics, it is important to ensure that the controller output is operating over its full range. To do this, the throttle should be tuned using the programmer. e procedures that follow will establish rottle Deadband and rottle Max parameter values that correspond to the absolute full range of your particular throttle mechanism. It is advisable to provide some buer around the absolute full range of the throttle mechanism to allow for throttle resistance variations over time and temperature as well as variations in the tolerance of potentiometer values between individual throttle mechanisms.
Tuning the Active rottle Range
Tuning the Controller to the Motor
Setting the Unloaded Vehicle Top Speed
Equalization of Loaded/Unloaded Vehicle Speed.
54
Curtis 1244 Manual, Rev. E
Page 61
6 — VEHICLE PERFORMANCE ADJUSTMENT
-A Tuning the rottle Deadband
 1. Jack the vehicle wheels up o the ground so that they spin freely.
 2. Plug the programmer into the controller and turn on the key-
switch and interlock switch (if used).
 3. When the programmer instructs you to select a menu, select the
Monitor Menu. e rottle % should be visible at the top of the display. You will need to reference the value displayed here.
 4. Scroll down until the Forward Input is visible. e display should
indicate that the forward switch is O.
 5. Slowly rotate the throttle forward until the display indicates
that the forward switch is On. Use care with this step as it is important to identify the threshold throttle position at which the forward switch is engaged and the controller recognizes the forward command.
 6. Without moving the throttle, scroll up to display the rottle
% and read the value shown. is value should be zero. If the rottle % value is zero, proceed to Step 7. If it is greater than zero, the rottle Deadband parameter must be increased and the procedure repeated from Step 5 until the rottle % is zero at the forward direction engagement point.
 7. While observing the rottle % value in the programmer’s
Monitor Menu, continue to rotate the throttle past the forward switch engagement point. Note where the rottle % value begins to increase, indicating that the controller has begun to supply drive power to the motor. If the throttle had to be rotated fur­ther than desired before the rottle % value began to increase, the rottle Deadband parameter value must be decreased and the procedure repeated from Step 5. If the amount of rotation between the point at which the Forward switch is engaged and the rottle % value begins to increase is acceptable, the rottle Deadband is properly tuned.
 8. If a bidirectional (wigwag) throttle assembly is being used, the
procedure should be repeated for the reverse direction. e rottle Deadband value should be selected such that the throttle operates correctly in both forward and reverse.
Curtis 1244 Manual, Rev. E
55
Page 62
6 — VEHICLE PERFORMANCE ADJUSTMENT
-B Tuning the rottle Max
 1. Jack the vehicle wheels up o the ground so that they spin freely.
 2. Plug the 1313 programmer into the controller and turn on the
 3. When the programmer instructs you to select a menu, select the
 4. Rotate the throttle forward to its maximum speed position and
 5. Now that the full throttle position results in a 100% value for
keyswitch and interlock switch (if used).
Monitor Menu. e rottle % should be visible at the top of the display. You will need to reference the value displayed here.
observe the rottle % value. is value should be 100%. If it is less than 100%, the rottle Max parameter value must be decreased to attain full controller output at the maximum throt­tle position. Use the programmer to decrease the rottle Max parameter value, and repeat this step until the value is 100%.
rottle %, slowly reduce throttle until the rottle % value drops below 100% and note the throttle position. is represents the extra range of motion allowed by the throttle mechanism. If this range is large, you may wish to decrease it by increasing the rottle Max parameter value. is will provide a larger active throttle range and more vehicle control. Using the programmer, increase the rottle Max parameter value and repeat the test until an appropriate amount of extra range is attained.
 6. If a bidirectional (wigwag) throttle assembly is being used, repeat
the procedure for the reverse direction. e rottle Max value should be selected such that the throttle operates correctly in both forward and reverse.
56
Curtis 1244 Manual, Rev. E
Page 63
6 — VEHICLE PERFORMANCE ADJUSTMENT
Tuning the Controller to the Motor
e 1244 controller has the exibility to be tuned to nearly any separately excited motor from any manufacturer. Parameters in the programmer’s Parame­ters Menu allow full control of the motor’s maximum armature current during driving and braking and full control of the motor’s maximum and minimum field current as well as the field current relationship to the armature current. is exibility allows motor performance to be maximized while protecting it from operating outside its safe commutation region.
In order to properly tune the controller, the following information should be obtained from the motor manufacturer:
£ Maximum Armature Current Rating
£ Maximum Field Current Rating
£ Minimum Field Current Rating
£ Field Resistance, hot and cold.
e performance of a separately excited motor changes depending on tem­perature. is is due to the change in field winding resistance as the motor heats up through use. When the field winding temperature increases, so does its resistance and therefore the maximum current that can be forced through the winding is reduced. Reductions in the field current over the motor’s typical operating temperature range can be 10% to 50%. Since the maximum avail­able field current determines the maximum torque that can be produced by the motor, the vehicle’s performance under load and up inclines will change as the motor heats up. e change in performance can be limited by tuning the motor when it is hot rather than cold. erefore, it is recommended that the following procedure be performed with a hot motor.
 1. Using the programmer’s Parameters Menu, set the Drive Cur-
rent Limit parameter value in each mode to the smaller of: (a) the motor’s peak armature current rating, or (b) the maximum controller drive current limit. is value can later be adjusted to establish the desired vehicle driving feel in each mode.
 2. Set the Braking Current Limit parameter value in each mode to
 3. To set the Field Max parameter value, first decide whether you
Curtis 1244 Manual, Rev. E
the smaller of: (a) the maximum motor armature current rating, or (b) the maximum controller braking current limit. is value can later be adjusted to establish the desired vehicle braking feel in each mode.
want to maintain consistent vehicle operation throughout the motor’s temperature range. If you do, proceed to Step 4. If, however, maintaining operational consistency across motor temperature is not a concern, but achieving maximum torque is, proceed to Step 5.
57
Page 64
6 — VEHICLE PERFORMANCE ADJUSTMENT
 4. For the most consistent operation across temperature, set the
 5. For the maximum torque regardless of temperature, set the
is has now set the Max Field parameter. e next step is to set the Min Field parameter. : e Field Min parameter should never be set below the rated value specified by the manufacturer. Operating the motor at lower field currents than specified will result in operation outside the motor’s safe com­mutation region and will cause arcing between the brushes and commutator significantly reducing motor and brush life. e Field Min parameter value can be increased from the manufacturer’s specified value to limit the vehicle’s top speed. (Setting the vehicle top speed will be addressed later in this section.)
If the controller is tuned such that the system is operating outside the motor’s safe commutation region, there will be audible and visual indications. Under normal operation, the motor will emit a whine with a pitch that increases with increasing rotation speed. If a “scratchy” sound is also heard, this is usually an indication that pin arcing is occurring in the motor and it is operating out­side its safe commutation region. is operation is normally accompanied by a strong smell from the motor. If the brushes and commutator bars are visible, arcing may be visible. e further outside the safe commutation region the motor is operating, the worse the arcing will be. Operation outside the safe commutation region is very detrimental to the motor. e Field Min and possibly also the Field Map parameter should be increased until the indications of arcing stop. Decreasing the Field Map Start parameter will also help to move operation back into the safe commutation region.
Field Max parameter to the maximum field current available at low battery voltage with a hot motor. To determine this current, divide the low battery voltage (typically 70% of nominal) by the high temperature field winding resistance specification provided by the manufacturer. Set the Field Max parameter to this value. is will provide good consistency between motor performance in both hot and cold states.
Field Max parameter to the motor’s rated absolute maximum eld current. To determine the absolute maximum field current, divide the nominal battery voltage by the low temperature field winding resistance specification provided by the manufacturer. Set the Field Max parameter to this value. is will provide the maximum possible torque under all conditions.
58
Curtis 1244 Manual, Rev. E
Page 65
6 — VEHICLE PERFORMANCE ADJUSTMENT
Setting the Unloaded Vehicle Top Speed
e controller and vehicle should be configured as follows prior to setting the maximum unloaded vehicle speed:
•  Max Speed = 100%, all modes
•  Drive Current Limit as established in tuning procedure 
•  Field Map = 50%
•  Field Map Start = 50% of the specified drive current limit
•  Field Min = manufacturer’s specified minimum or 3 amperes
•  Load Comp = 0
•  e vehicle should be unloaded
•  e vehicle battery should be fully charged.
e vehicle should be driven on a at surface in a clear area during this proce­dure. Since the vehicle may initially be traveling at speeds in excess of the final intended speed, precautions should be taken to ensure safety of test personnel and anyone in the test area.
 1. Select the programmer’s Program Menu and scroll down until
the Field Min parameter is at the top of the display.
 2. Power up the vehicle and apply full throttle. While driving the
vehicle with full throttle applied, adjust the Field Min parame­ter value to set the desired top speed. Increasing the Field Min value decreases the vehicle’s top speed; decreasing the Field Min value increases the vehicle’s top speed.
CAUTION: Do not decrease
the Field Min parameter value below the motor manufacturer’s recommended minimum field current value, and do not increase it above 10 amps. : If the Field Min value is too low, the vehicle speed may oscillate or surge even at constant throttle. If oscillation or surge is observed, increase the Field Min value until the vehicle speed remains constant at constant throttle.
 3. If the Field Min parameter value is increased to 10 amps and the
vehicle top speed has still not been sufficiently reduced, the Max Speed parameter should be used to bring the vehicle top speed down to the desired level. First, decrease the Field Min parame­ter, setting it to optimize smooth starting. en adjust the Max Speed parameter per Step 4 to bring the vehicle top speed down to the desired level. : If the Field Min parameter is set too high, the high initial torque created by the high field current may cause overly abrupt starts; this is why we recommend using the Max Speed parameter in those cases where a moderate Field Min setting does not sufficiently reduce the vehicle top speed.
Curtis 1244 Manual, Rev. E
59
Page 66
6 — VEHICLE PERFORMANCE ADJUSTMENT
 4. Scroll up the Program Menu until the Max Speed parameter
 5. For Walkie/Rider Applications: Typically, dierent top speeds are
Equalization of Loaded and Unloaded Vehicle Speed
e top speed of a loaded vehicle can be set to approach the unloaded top speed by tuning the 1244 controller’s Field Map Start and Load Compensation parameters. It is recommended that you review the description of the Field Map Start parameter (page 38) and Load Compensation parameter (page 49) before starting this procedure.
is at the top of the display. While driving the vehicle with the Field Min set at the value selected in Step 3, decrease the Max Speed parameter value until the desired vehicle top speed is set.
desired for walkie and rider operation. To tune a walkie/rider vehicle’s top speed, first tune it for rider operation. Use the Field Min parameter to tune the vehicle top speed. en, to set the top speed for walkie operation, leave the Field Min parameter unchanged and decrease the Max Speed parameter until the desired walking speed is reached.
 1. e vehicle’s unloaded top speed should already have been set. If
it was not, it should be set before the vehicle’s loaded top speed is established.
 2. Once the vehicle’s unloaded top speed has been set, load the
vehicle to the desired load capacity. Leave the Field Min and Speed Max parameters at the settings determined during the unloaded test.
 3. If the intent is to minimize the dierence between the loaded
and unloaded vehicle speeds, then:
(i) Drive the fully loaded vehicle on at ground with full throttle applied. When the vehicle reaches maximum speed, observe the armature current displayed in the programmer’s Test Menu.
(ii) Set the Field Map Start parameter slightly higher than the observed armature current value.
(iii) Test the loaded/unloaded speed variation. If it is unaccept­able, proceed to (iv).
(iv) Increase the Load Compensation parameter and retest the speed regulation. e Load Compensation parameter can be increased until the desired regulation is achieved or the vehicle speed begins to oscillate (“hunt”) at low throttle.
60
Curtis 1244 Manual, Rev. E
Page 67
6 — VEHICLE PERFORMANCE ADJUSTMENT
 3. If the intent is to make the loaded speed less than the unloaded speed
(for reasons of safety, efficiency, or reduced motor heating), then:
(i) Unload the vehicle and drive it on at ground with full throt­tle applied. When the vehicle reaches maximum speed, observe the armature current displayed in the programmer’s Test Menu.
(ii) Set the Field Map Start parameter to the observed armature current value.
(iii) Load the vehicle and drive it on at ground with full throttle applied. Further adjustments to the vehicle’s loaded speed can now be made by varying the Field Map parameter. Increasing the Field Map parameter value will decrease the vehicle’s loaded speed, and decreasing the Field Map parameter value will increase the vehicle’s loaded speed.
CAUTION: If the Field Map Start parameter is set too high, the motor’s
safe commutation region may be exceeded. If this is the case, reduce the Field Map Start parameter to a safe value. en, adjust the Field Map parameter as needed to reach the desired loaded top speed. Reducing the Field Map parameter will help bring the loaded speed closer to the unloaded speed. However, care must still be taken because it is possible for too low Field Map values—like too high Field Map Start values—to result in operation outside the motor’s safe commutation region.
Curtis 1244 Manual, Rev. E
61
Page 68
6 — VEHICLE PERFORMANCE ADJUSTMENT
FINE TUNING
Four additional vehicle performance characteristics can be adjusted:
ese characteristics are related to the “feel” of the vehicle and will be dierent for various applications. Once the fine tuning has been accomplished, it should not have to be repeated on every vehicle.
Response to Increased rottle ➅ Response to Reduced rottle ➆ Smoothness of Direction Transitions ➇ Ramp Climbing ➈ Ramp Restraint.
Response to Increased Throttle
e vehicle’s response to quick or slow throttle increases can be modified using the Accel Rate, Current Ratio, Quick Start, and rottle Map parameters. Optimal vehicle response is tuned by adjusting these parameters and then accelerating the vehicle from a dead stop under various throttle transition conditions.
 1.  Set Quick Start = 0 and rottle Map as desired.
 2. Drive the vehicle and adjust the Accel Rate for the best overall
acceleration response. If the vehicle starts too slowly under all driving conditions, the Accel Rate should be reduced.
 3. Increasing vehicle acceleration. If acceleration feels good for slow
or moderate throttle transitions but the vehicle initially starts too slowly, set the Current Ratio to 2 or higher. If acceleration is not satisfactory when the throttle is transitioned quickly from zero to full speed, increase the Quick Start parameter value to obtain the desired fast throttle response.
 4. Achieving better control at low speeds. If the vehicle responds
well for fast, full range throttle transitions but is too jumpy during low speed maneuvering, reduce the Quick Start, reduce
the  rottle  Map, and/or  set  the  Current  Ratio  =  1.  If  these 
adjustments are insufficient or unacceptable, you may want to define a separate operational mode for precision maneuvering. e Accel Rate, Max Speed, and Drive Current Limit parameters can be tuned exclusively for this precision-maneuvering mode to obtain comfortable vehicle response.
62
Curtis 1244 Manual, Rev. E
Page 69
6 — VEHICLE PERFORMANCE ADJUSTMENT
Response to Reduced Throttle
e way the vehicle responds when the throttle is reduced or completely released can be modified using the Decel Rate, rottle Braking %, and Restraint pa­rameters. is response is particularly noticeable when the vehicle is traveling downhill.
 1. Set the Decel Rate and rottle Braking % parameters based on
the desired time for the vehicle to stop upon release of throttle when traveling at full speed with full load. If the vehicle brakes too abruptly when the throttle is released, increase the Decel Rate and/or decrease the rottle Braking %.
 2. e default Restraint setting should work well for most vehicles.
If the vehicle exhibits excessive overspeed when driving down a ramp, increase the Restraint value. If the vehicle “speed hunts” while driving down a ramp or brakes too abruptly at small re­ductions in throttle, decrease the Restraint value.
 3. If the Restraint value has been adjusted, retest braking behavior
when throttle is reduced to ensure that it still has the desired feel. If it does not, the Decel Rate and/or rottle Braking % should be re-adjusted as in Step 1.
Smoothness of Direction Transitions
After the major performance and responsiveness tuning has been completed, additional fine tuning can be performed in the vehicle’s transitions betweeen braking and driving. ese transitions are aected by the Taper Rate, Accel Rate, Braking Rate, and Braking Current Limit parameters.
-A Drive-to-Brake Transitions
 1. If the transition is too slow: decrease the Braking Rate parameter
value for faster braking.
 2. If the transition is too abrupt: increase the Braking Rate param-
eter value for slower braking.
 3. If the braking distance is too long: increase the Braking Current
Limit parameter value or decrease the Braking Rate parameter value.
 4. If the applied braking torque is too high: reduce the Braking
Curtis 1244 Manual, Rev. E
Current Limit parameter value. Reducing the braking current will also reduce motor heating, improve brush life, and improve the forward-to-reverse transition feel. : If the braking cur­rent limit is changed, evaluation and adjustment of the rottle Braking % parameter may be necessary to obtain the response originally set in procedure ➅.
63
Page 70
6 — VEHICLE PERFORMANCE ADJUSTMENT
-B Forward-to-Reverse Transitions
 1. Begin this test set with the Taper Rate parameter set to 64. Drive
 2. If the transition is slow or the vehicle feels sluggish: reduce the
 3. If the vehicle exhibits a small bump at zero speed: increase the
-C Low Speed vs. High Speed Braking
e 1244 controller is capable of both regenerative and plug
the vehicle and transition directly from forward to reverse. A slight pause should be noticeable at the zero speed point. Reduce the Taper Rate parameter value until the pause is eliminated. Reducing the Taper Rate value further may cause a slight bump during the direction transition.
Accel Rate parameter value.
Taper Rate parameter value.
braking, and can be programmed to use one or the other as a function of vehicle speed. Plug braking provides quicker response and direction transition at low speeds, while regen braking is more powerful and efficient at high speeds. e Regen Speed parameter is used to define the threshold vehicle speed at which the type of braking changes from one to the other.
To determine the ideal Regen Speed parameter for your applica-
tion, jockey the vehicle back and forth from forward to reverse at low speeds. Increase the Regen Speed parameter value until the vehicle feels more responsive during the direction changes. en drive the vehicle at high speed and test the braking. If the braking feels weak, reduce the Regen Speed parameter value.
e Regen Speed parameter can be adjusted from 0% to 100%
of the vehicle speed. In other words, the point at which the controller enables regen braking can be set anywhere within the vehicle’s entire speed range. However, setting the Regen Speed parameter to a high percentage of the maximum vehicle speed will result in weak braking at high speeds along with increased motor heating. Additionally, no energy will be returned to the batteries to extend the total charge time and the motor brush wear will be higher than if regen braking is used. Typical Regen Speed values are between 10% and 60% of the maximum vehicle speed.
64
Curtis 1244 Manual, Rev. E
Page 71
6 — VEHICLE PERFORMANCE ADJUSTMENT
Ramp Climbing
e vehicle response to increased gradients such as loading ramps can be tuned via the Field Map parameter. Decreasing the Field Map parameter allows faster vehicle speeds while climbing ramps, but it will also have the eect of reducing the ability of the controller to generate torque in the vehicle’s mid range speeds.
 1. If faster vehicle speed is desired when climbing ramps, decrease
the Field Map parameter value until the desired ramp climbing speed is attained. It should be noted that if the motor’s torque capability is exceeded under the conditions of load and ramp gradient, vehicle speed will be limited by the motor’s capability and the desired vehicle speed may not be attainable. e system will find a compromise point at which sufficient motor torque is generated to climb the ramp at an acceptable speed. If the Field Map parameter value is reduced to 0% and the desired speed is still not attained, the system is being limited by the motor’s torque capability under these operating conditions. Caution should be used in reducing the Field Map parameter since at low Field Map values it is possible that the motor could be operated outside its safe commutation region.
 2. If the drive system cannot produce sufficient torque for a fully
loaded vehicle to climb the desired ramp, try increasing the Field Map, Field Max, and/or Drive Current Limit parameters. e impact of increasing these parameter values on other driving characteristics must be evaluated. Increasing the Field Max will provide more field current, and increasing the Drive Current Limit will provide more armature current. If the Field Max is set at the manufacturer’s specified limit and the Drive Current Limit is set at the rated maximum, then vehicle speed up the ramp is limited by the motor or the vehicle’s gearing and cannot be increased by tuning the controller. : To determine if the controller’s armature current is at its set value during ramp climbing, read the “Arm Current” in the programmer’s Test Menu.
Curtis 1244 Manual, Rev. E
65
Page 72
6 — VEHICLE PERFORMANCE ADJUSTMENT
Ramp Restraint
e Restraint parameter can be used to limit vehicle movement after the vehicle has come to a stop. If the vehicle brakes to a stop on an incline and the brake has not engaged, the Restraint function will limit the rate at which the vehicle travels down the incline. Higher values of Restraint will result in slower vehicle creeping down the incline. e Restraint function can never hold a vehicle per­fectly stationary on an incline and is not intended to replace a mechanical or electromagnetic brake for this purpose. However, it will prevent uncontrolled vehicle coasting in this situation.
e Restraint parameter also inuences the vehicle’s response to reduced throttle. If the Restraint parameter is set to a high value in order to slow the vehicle’s downhill creeping when it is stopped on an incline, this high Restraint setting will also aect the vehicle’s response to reduced throttle. erefore, the Restraint parameter should be set with both situations in mind. For tuning the vehicle’s response to reduced throttle, see tuning procedure ➅, page 63.
66
Curtis 1244 Manual, Rev. E
Page 73
7
7 — PROGRAMMER MENUS
PROGRAMMER MENUS
Items are listed for each menu in the order in which they are displayed on the programmer.
Parameters Menu (not all items available on all controllers)
V O L T A G E Nominal battery voltage, in volts M 1 D R I V E C / L Mode 1 drive current limit, in amps
M 2 D R I V E C / L Mode 2 drive current limit, in amps M 3 D R I V E C / L Mode 3 drive current limit, in amps M 4 D R I V E C / L Mode 4 drive current limit, in amps M 1 B R A K E C / L Mode 1 braking current limit, in amps M 2 B R A K E C / L Mode 2 braking current limit, in amps M 3 B R A K E C / L Mode 3 braking current limit, in amps M 4 B R A K E C / L Mode 4 braking current limit, in amps M 1 T H R T B R K % Mode 1 throttle braking, as % of brake C/L M 2 T H R T B R K % Mode 2 throttle braking, as % of brake C/L M 3 T H R T B R K % Mode 3 throttle braking, as % of brake C/L M 4 T H R T B R K % Mode 4 throttle braking, as % of brake C/L M 1 A C C E L R A T E Mode 1 acceleration rate, in seconds M 2 A C C E L R A T E Mode 2 acceleration rate, in seconds M 3 A C C E L R A T E Mode 3 acceleration rate, in seconds M 4 A C C E L R A T E Mode 4 acceleration rate, in seconds D E C E L R A T E Deceleration rate, in seconds M 1 B R A K E R A T E Mode 1 braking rate, in seconds M 2 B R A K E R A T E Mode 2 braking rate, in seconds M 3 B R A K E R A T E Mode 3 braking rate, in seconds M 4 B R A K E R A T E Mode 4 braking rate, in seconds Q U I C K S T A R T Quick-start throttle factor
T A P E R R A T E Regen braking decrease rate when approaching zero speed, in 1/32 s M 1 M A X S P E E D Mode 1 maximum speed, as % PWM output M 2 M A X S P E E D Mode 2 maximum speed, as % PWM output M 3 M A X S P E E D Mode 3 maximum speed, as % PWM output M 4 M A X S P E E D Mode 4 maximum speed, as % PWM output M 1 C R E E P S P E E D Mode 1 creep speed, as % PWM output M 2 C R E E P S P E E D Mode 2 creep speed, as % PWM output M 3 C R E E P S P E E D Mode 3 creep speed, as % PWM output M 4 C R E E P S P E E D Mode 4 creep speed, as % PWM output R E G E N S P E E D Minimum speed for regen braking, as % of vehicle speed C T R L M O D E Control mode T H R O T T L E T Y P E rottle type T H R T L D E A D B A N D rottle neutral deadband, as % of 5kΩ pot T H R O T T L E M A X rottle input req’d for 100% PWM, as % of 5kΩ pot
1
2
Curtis 1244 Manual, Rev. E
67
Page 74
7 — PROGRAMMER MENUS
Parameters Menu, cont’d
M 1 T H R T L M A P Mode 1 throttle map, as %
M 2 T H R T L M A P Mode 2 throttle map, as % M 3 T H R T L M A P Mode 3 throttle map, as % M 4 T H R T L M A P Mode 4 throttle map, as % F I E L D M I N Minimum field current, in amps
F I E L D M A X Maximum field current, in amps H P D T H R E S H O L D Allowable throttle at startup, as % active throttle range
F L D M A P S T A R T Armature current at which field map takes eect, in amps F I E L D M A P Field winding current, as % armature current C U R R E N T R A T I O Current ratio: factor of 1, 2, 4, or 8 R E S T R A I N T Ramp restraint: 1 to 10 L O A D C O M P Load compensation: 0 to 25 H P D High pedal disable (HPD) type S R O Static return to o (SRO) type S E Q U E N C I N G D L Y Sequencing delay, in seconds M A I N C O N T I N T R Main contactor interlock: On or O M A I N O P E N D L Y Main contactor dropout delay, in seconds W E L D C H E C K Main contactor weld check: On or O M A I N C H E C K Main coil open check: On or O A U X D E L A Y Auxiliary driver dropout delay, in seconds A U X C H E C K Auxiliary coil open check: On or O E M B R A K E D E L A Y Electromagnetic brake delay, in seconds E M B R A K E C H E C K Electromagnetic brake open check: On or O R E V D R V R C H E C K Reverse signal open check: On or O C O N T P U L L I N Contactor coil pull-in voltage, as % C O N T H O L D I N G Contactor coil holding voltage, as % E M R R E V E N A B L E Emergency reverse function: On or O E M R R E V C / L Emergency reverse current limit, in amps E M R R E V C H E C K Emergency reverse wiring check: On or O A N T I - T I E D O W N Anti-tiedown: On or O F A U L T C O D E Fault output type P E D A L I N T R L C K Pedal switch interlock: On or O P R E C H A R G E Precharge function: On or O N O D E A D D R CAN-Bus address: 1 through 15
5
3
4
68
Curtis 1244 Manual, Rev. E
Page 75
7 — PROGRAMMER MENUS
Parameters Menu Notes
1
Control modes (for detail, see Section 3: Programmable Parameters, page 28)
Type 0: Current control mode—throttle controls motor torque Type 1: Voltage control mode—throttle controls motor speed
2
rottle types (for detail, see rottle Wiring in Section 2)
Type 1: 5kΩ–0 Type 2: single-ended 0–5V, 3-wire pot, current source, and electronic throttles Type 3: 0–5kΩ Type 4: wigwag 0–5V and 3-wire pot Type 5: CAN-Nodes type throttles
3
HPD types (for detail, see Section 3: Programmable Parameters, page 41)
Type 0: no HPD Type 1: HPD unless KSI and interlock inputs received before throttle request Type 2: HPD unless KSI input is received before throttle request Type 3: HPD unless KSI and interlock and direction inputs received before throttle request
4
SRO types (for detail, see Section 3: Programmable Parameters, page 42)
Type 0: no SRO Type 1: SRO unless interlock input is received before a direction is selected Type 2: SRO unless KSI + interlock inputs received before direction selected Type 3: SRO unless KSI + interlock + forward inputs received in that order
5
Fault output types (for detail, see Section 3: Programmable Parameters, page 43)
On: Fault Code format O: Fault Category format
Curtis 1244 Manual, Rev. E
69
Page 76
7 — PROGRAMMER MENUS
Monitor Menu (not all items available on all controllers)
T H R O T T L E % rottle reading, as % of full throttle A R M C U R R E N T Motor armature current, in amps F I E L D C U R R E N T Motor field current, in amps A R M P W M Motor armature appl’d duty cycle, as % F I E L D P W M Motor field applied duty cycle, as % B A T T V O L T A G E Voltage at KSI C A P V O L T A G E Voltage at controller’s B+ bus bar H E A T S I N K T E M P Heatsink temperature, in °C F O R W A R D I N P U T Forward switch: on/o R E V E R S E I N P U T Reverse switch: on/o M O D E Controller operating mode: 1 to 4 I N T R L C K I N P U T Interlock switch: on/o P E D A L I N P U T Pedal switch: on/o E M R R E V I N P U T Emergency reverse switch: on/o M O T O R R P M Tachometer input: pulses per second M A I N C O N T Main contactor: open/closed A U X C O N T Auxiliary driver: open/closed R E V O U T P U T Reverse driver status: on(low)/o(high) B R A K E O U T P U T Brake driver status: on(low)/o(high) F A U L T 1 O U T P U T Fault 1 driver status: on(low)/o(high) F A U L T 2 O U T P U T Fault 2 driver status: on(low)/o(high) C O N T R O L S T A T E Controller’s functional state: 0 to 13* M O D S E L 1 Mode Select 1 switch: on/o M O D S E L 2 Mode Select 2 switch: on/o
Control states are used for diagnostic and troubleshooting purposes.
*
70
Curtis 1244 Manual, Rev. E
Page 77
7 — PROGRAMMER MENUS
Diagnostics “Menu”
is is not a menu as such, but simply a list of the possible messages you may see displayed when you select the Diagnostics Menu. e messages are listed in alphabetical order for easy reference.
A N T I - T I E D O W N Mode 2 or 4 selected at startup A R M S E N S O R Armature sensor fault B B W I R I N G C H E C K Emergency reverse wiring check failed C O N T D R V R O C Contactor driver overcurrent F I E L D O P E N Field winding open or disconnected F L D S E N S O R Field sensor fault H P D High pedal disable (HPD) activated H W F A I L S A F E 1 Power-on self test fault H W F A I L S A F E 2 External watchdog fault H W F A I L S A F E 3 Internal watchdog fault L O W B A T T E R Y V O L T A G E Battery voltage too low M - S H O R T E D M- output shorted to B- M A I N C O N T D N C Main contactor did not close M A I N C O N T W E L D E D Main contactor welded M I S S I N G C O N T A C T O R Missing contactor N O K N O W N F A U L T S No known faults O V E R V O L T A G E Battery voltage too high P R E C H A R G E F A U L T Precharge fault S R O Static return to o (SRO) activated T H E R M A L C U T B A C K Cutback, due to over/under temperature T H R O T T L E F A U L T 1 rottle out of range T H R O T T L E F A U L T 2 rottle low fault
Other Menus
e System Info Menu shows information uploaded from your 1244 controller: model number, serial number, etc. e HHP Settings Menu allows you to select the 1313 handheld programmer’s display language, adjust its display contrast, etc. e Program Menu allows you to save and restore parameter settings les.
Curtis 1244 Manual, Rev. E
71
Page 78
8 — DIAGNOSTICS & TROUBLESHOOTING
DIAGNOSTICS AND TROUBLESHOOTING
8
e 1244 controller provides diagnostics information to assist technicians in troubleshooting drive system problems. e diagnostics information can be ob­tained by observing the appropriate display on the 1313 handheld programmer or 1314 PC Programming Station, the fault codes issued by the Status LED, or the fault display driven by the controller’s Fault 1 and Fault 2 outputs. Refer to the troubleshooting chart (Table 5) for suggestions covering a wide range of possible faults.
PROGRAMMER DIAGNOSTICS
e programmer presents complete diagnostic information in plain language. Faults are displayed in the Diagnostics Menu (see column 2 in the trouble­shooting chart), and the status of the controller inputs/outputs is displayed in the Monitor Menu.
Accessing the Diagnostic History Menu provides a list of the faults that have occurred since the diagnostic history file was last cleared. Checking (and clearing) the diagnostic history file is recommended each time the vehicle is brought in for maintenance.
e following 4-step process is recommended for diagnosing and trou­bleshooting an inoperative vehicle: (1) visually inspect the vehicle for obvious problems; (2) diagnose the problem, using the programmer; (3) test the circuitry with the programmer; and (4) correct the problem. Repeat the last three steps as necessary until the vehicle is operational.
Example: A vehicle that does not operate in “forward” is brought in for repair.
 1: Examine the vehicle and its wiring for any obvious problems, such
as broken wires or loose connections.
 2: Connect the programmer, select the Diagnostics Menu, and read
the displayed fault information. In this example, the display shows “No
Known Faults,” indicating that the controller has not detected anything
out of the norm.
 3: Select the Test Menu, and observe the status of the inputs and out-
puts in the forward direction. In this example, the display shows that the
forward switch did not close when “forward” was selected, which means the
problem is either in the forward switch or the switch wiring.
 4: Check or replace the forward switch and wiring and repeat the test.
If the programmer shows the forward switch closing and the vehicle now
drives normally, the problem has been corrected.
72
Curtis 1244 Manual, Rev. E
Page 79
8— DIAGNOSTICS & TROUBLESHOOTING
Table 5 TROUBLESHOOTING CHART
LED PROGRAMMER FAULT
CODE LCD DISPLAY CATEGORY
1,2 H W F A I L S A F E 1 - 2 - 3 1 self-test or watchdog fault 1. Controller defective.
EXPLANATION
POSSIBLE CAUSE
M - S H O R T E D 1 internal M- short to B- 1. Controller defective.
F I E L D O P E N 1 field winding fault 1. Motor field wiring loose.
1,3 2. Motor field winding open.
A R M S E N S O R 1 armature current sensor fault 1. Controller defective.
F L D S E N S O R 1 field current sensor fault 1. Controller defective.
T H R O T T L E F A U L T 1 1 wiper signal out of range 1. rottle input wire open.
2. rottle input wire shorted to B+ or B-.
2,1
T H R O T T L E F A U L T 2 1 pot low fault 1. rottle pot defective.
2. Wrong throttle type selected.
2,2 S R O 3 SRO fault 1. Improper sequence of KSI, interlock, and
direction inputs.
2. Wrong SRO type selected.
3. Interlock or direction switch circuit open.
4. Sequencing delay too short.
2,3 H P D 3 HPD fault 1. Improper seq. of direction and throttle inputs.
2. Wrong HPD type selected.
3. Misadjusted throttle pot.
4. Sequencing delay too short.
5. HPD threshold set too low.
2,4 B B W I R I N G C H E C K 1 emergency reverse wiring fault 1. Emergency reverse wire open.
2. Emergency reverse check wire open.
3,1 C O N T D R V R O C 1 cont. driver output overcurrent 1. Contactor coil shorted.
3,2 M A I N C O N T W E L D E D 1 welded main contactor 1. Main contactor stuck closed.
2. Main contactor driver shorted.
3,3 P R EC H A R G E F A U L T 1 internal voltage too low at startup 1. Controller defective.
2. External short, or leakage path to B- on external B+ connection.
M I S S I N G C O N T A C T O R 1 missing contactor 1. Any contactor coil open or not connected.
3,4
M A I N C O N T D N C 1 main contactor did not close 1. Main contactor missing or wire to coil open.
4,1 L O W B A T T E R Y V O L T A G E 2 low battery voltage 1. Battery voltage <undervoltage cutback limit.
2. Corroded battery terminal.
3. Loose battery or controller terminal.
4,2 O V E R V O L T A G E 2 overvoltage 1. Battery voltage >overvoltage shutdown limit.
2. Vehicle operating with charger attached.
3. Battery disconnected during regen braking.
4,3 T H E R M A L C U T B A C K 2 over-/under-temperature cutback 1. Temperature >85°C or < -25°C.
2. Excessive load on vehicle.
3. Improper mounting of controller.
4. Operation in extreme environments.
4,4 A N T I - T I E D O W N 3 Mode 2 or Mode 4 selected at 1. Mode switches shorted to B+.
startup 2. Mode switches “tied down” to select Mode 2 or Mode 4 permanently.
Curtis 1244 Manual, Rev. E
73
Page 80
8 — DIAGNOSTICS & TROUBLESHOOTING
LED DIAGNOSTICS
A Status LED is built into the 1244 controller. It is visible through a window in the label on top of the controller. is Status LED displays fault codes when there is a problem with the controller or with the inputs to the controller. During normal operation, with no faults present, the Status LED ashes steadily on and o. If the controller detects a fault, a 2-digit fault identification code is ashed continuously until the fault is corrected. For example, code “3,2”—welded main contactor—appears as:
( 3 , 2 ) ( 3 , 2 ) ( 3 , 2 )
e codes are listed in Table 6.
LED CODES EXPLANATION
LED o no power or defective controller
solid on controller or microprocessor fault
0,1
¤ ¤ ¤ ¤ ¤ ¤ ¤ ¤ ¤ ¤ ¤ ¤ ¤ ¤ ¤
Table 6 STATUS LED FAULT CODES
¤ controller operational; no faults
1,1 ¤ ¤ [not used] 1,2 ¤ ¤¤ hardware failsafe fault 1,3 ¤ ¤¤¤ M-, current sensor, or motor fault 1,4 ¤ ¤¤¤¤ [not used]
2,1 ¤¤ ¤ throttle fault 2,2 ¤¤ ¤¤ static return to o (SRO) fault 2,3 ¤¤ ¤¤¤ high pedal disable (HPD) fault 2,4 ¤¤ ¤¤¤¤ emergency reverse circuit check fault
3,1 ¤¤¤ ¤ contactor driver overcurrent 3,2 ¤¤¤ ¤¤ welded main contactor 3,3 ¤¤¤ ¤¤¤ precharge fault 3,4 ¤¤¤ ¤¤¤¤ missing contactor, or main cont. did not close
4,1 ¤¤¤¤ ¤ low battery voltage 4,2 ¤¤¤¤ ¤¤ overvoltage 4,3 ¤¤¤¤ ¤¤¤ thermal cutback, due to over/under temp. 4,4 ¤¤¤¤ ¤¤¤¤ anti-tiedown fault
Note: Only one fault is indicated at a time, and faults are not queued up. Refer to the troubleshooting chart (Table 5) for suggestions about possible causes of the various faults.
74
Curtis 1244 Manual, Rev. E
Page 81
8 — DIAGNOSTICS & TROUBLESHOOTING
FAULT OUTPUT DRIVERS
e 1244 controller provides two fault output drivers designed for use with a display to provide fault information to the operator. e fault output drivers, Fault 1 (Pin 5) and Fault 2 (Pin 6), are open collector drivers rated at 10 mA maximum current at the nominal battery voltage. ey are intended to drive display LEDs but can be used to drive anything that operates within the drivers’ limits. ese outputs can be configured to display faults in Fault Code format or Fault Category format—see Section 3, page 42.
In Fault Code format, the two fault outputs operate independently. e Fault 1 line ashes the same codes, at the same time, as the controller’s built­in Status LED (see Table 6). is line can therefore be used to drive an LED located on the display panel in order to provide fault code information directly to the operator. e Fault 2 line pulls to ground (B-) when a fault is present; it can be used to drive a remote LED that simply indicates whether or not there is a fault. When no faults are present, both of the fault lines are in their normal state (high).
In Fault Category format, the two fault outputs together define one of four fault categories, as listed in Table 7. When a fault occurs, the Fault 1 and Fault 2 lines (Pins 5 and 6) go to the state indicating the category of the particular fault: fault ouputs return to their normal state (i.e.,
LOw/HIGH, HIGH/LOw, or LOw/LOw. When the fault is cleared, the
HIGH/HIGH).
Table 7 FAULT CATEGORy CODES
FAULT 1 FAULT 2 FAULT DRIVER DRIVER CATEGORY POSSIBLE FAULT
HIGH HIGH 0 (no known faults)
LOw HIGH 1 Hardware failsafe fault M-, current sensor, or motor fault Throttle fault Emergency reverse wiring fault Contactor or output driver fault Precharge fault
HIGH LOw 2 Low battery voltage Overvoltage Thermal cutback, due to over/under temp
LOw LOw 3 Static return to off (SRO) fault High pedal disable (HPD) fault Anti-tiedown fault
Curtis 1244 Manual, Rev. E
75
Page 82
9 — MAINTENANCE
9
MAINTENANCE
ere are no user serviceable parts in the Curtis 1244 controller. No attempt should be made to open, repair, or otherwise modify the controller. Doing
so may damage the controller and will void the warranty.
It is recommended that the controller be kept clean and dry that its diagnostics history file be checked and cleared periodically.
CLEANING
Periodically cleaning the controller exterior will help protect it against corrosion and possible electrical control problems created by dirt, grime, and chemicals that are part of the operating environment and that normally exist in battery powered systems.
CAUTION
When working around any battery powered vehicle, proper safety precau­tions should be taken. ese include, but are not limited to: proper training,
wearing eye protection, and avoiding loose clothing and jewelry.
Use the following cleaning procedure for routine maintenance. Never use a high pressure washer to clean the controller.
1. Remove power by disconnecting the battery.
2. Discharge the capacitors in the controller by connecting a load (such as a contactor coil or a horn) across the controller’s B+ and B- terminals.
3. Remove any dirt or corrosion from the power and signal connector areas. e controller should be wiped clean with a moist rag. Dry it before reconnecting the battery.
4. Make sure the connections are tight. Refer to Section 2, page 7, for maximum tightening torque specifications for the battery and motor connections.
DIAGNOSTIC HISTORy
e programmer can be used to access the controller’s diagnostic history file, via its Diagnostics Menu. e programmer will display all the faults that the controller has experienced since the last time the diagnostic history file was cleared. After a problem has been diagnosed and corrected, it is a good idea to clear the diagnostic history file. is allows the controller to accumulate a new file of faults. By checking the new diagnostic history file at a later date, you can readily determine whether the problem was indeed fixed.
76
Curtis 1244 Manual, Rev. E
Page 83
APPENDIX A: GLOSSARY
APPENDIX A
GLOSSARY OF FEATURES AND FUNCTIONS
Acceleration rate
e acceleration rate is the time required for the controller to increase from 0 to 100% drive output. e acceleration rate is a MultiMode™ parameter and is programmable from 0.1 to 5.0 seconds—see Section 3, page 26.
e accel rate parameter together with the Current Ratio, Quick Start,
and rottle Map parameters allows the OEM to tune the vehicle’s performance in response to increased throttle—see Section 6, page 62.
Access rights
Each programmable parameter is assigned an access level—OEM or User—that defines who is allowed to change that parameter. ese levels are assigned by the OEM when the controller is originally specified. Restricting parameter access to the OEM reduces the likelihood of important performance characteristics being changed by someone unfamiliar with the vehicle’s operation. In some cases, it may be necessary to restrict a parameter’s access to ensure that it is not set to a value in violation of EEC or other safety regulations. e 1313-1109 User programmer, for example, can adjust only those parameters with User access. e 1313-4409 OEM programmer can adjust all the parameters with User or OEM access rights. Typically, OEMs supply 1313-1109 programmers to their dealers and distributors so that the User-access parameters (for example, the acceleration rate and maximum speed) can be set to each customer’s liking, and so that the programmer’s testing and diagnostics capabilities can be used.
Curtis 1244 Manual, Rev. E
Anti-tiedown
e anti-tiedown feature is designed to discourage operators from taping or otherwise “tying down” the mode select switches in order to operate permanently in Mode 2 or Mode 4. At startup, when the interlock switch is first closed, the anti-tiedown feature checks which operational mode is selected. If the mode switches are requesting Mode 2 or Mode 4 (Mode Select 1 switch closed), the controller will ignore the request and default to Mode 1 or Mode 3. e controller will remain in Mode 1 or Mode 3 until the Mode Select 1 switch is released and reactivated.
Auxiliary driver
e auxiliary driver is a low side driver capable of pulling a 2 ampere load to B-. is output is overcurrent protected. It is designed to drive a contactor coil, but can be used to drive any load requiring less than 2 amperes.
A-1
Page 84
APPENDIX A: GLOSSARY
Braking rate
e braking rate is the time required for the controller to increase from 0 to 100% braking current when braking is requested. e braking rate is a MultiMode™ parameter and is programmable from 0.1 to 5.0 seconds—see Section3, page 26.
CAN Bus
CAN (Controller Area Network) Bus provides a two-wire communications system for electric vehicles. It is widely used in automotive applications and is also well suited to electrically controlled material handling systems. Use of the CAN Bus system considerably reduces the complexity of the vehicle’s wire harness. Additionally, the CAN Bus communications protocol provides error and fault detection to ensure proper signal and command transmission and reception. e CAN Bus system carries a high level of immunity to electro­magnetic interference, as well. For information regarding the CAN-Nodes protocol that Curtis uses in its controllers, refer to the Curtis CAN Protocol Document—available from local Curtis offices.
Control mode
e control mode parameter determines whether throttle position controls applied current (Type 0) or applied voltage (Type 1). Selection is made with the programmer—see Section 3, page 28.
Creep speed
Creep speed is activated when a direction is first selected. e output maintains creep speed until the throttle is rotated out of the throttle deadband (typically 10% of throttle). Creep speed is a MultiMode™ parameter and is programmable from 0 to 25% of the PWM duty cycle—see Section 3, page 27.
Current limiting
Curtis controllers limit the motor current to a preset maximum. is feature protects the controller from damage that might result if the current were limited only by motor demand. PWM output to the armature and field power sections is reduced until the motor current falls below the set limit level.
In addition to protecting the controller, the current limit feature also provides some protection to the rest of the system. By eliminating high current surges during vehicle acceleration, stress on the motor and batteries is reduced and their efficiency enhanced. Similarly, there is less wear and tear on the vehicle drivetrain, as well as on the ground on which the vehicle rides.
e drive and braking current limits are programmable independently in each of the four modes—see Section 3, page 36.
A-2
Curtis 1244 Manual, Rev. E
Page 85
APPENDIX A: GLOSSARY
Current ratio
e 1244 controller’s current limit increases with increased throttle, according to an algorithm developed to produce smooth starts and good overall vehicle driving characteristics. e current ratio parameter allows the OEM to adjust the amount of current available at low throttle requests in order to provide quicker startups and improved ramp climbing at partial throttle if that is de­sired for a specific application. Refer to Section 3, page 38, for the range of programmable settings, and to Section 6 for instructions on how to use this parameter to tune vehicle performance.
Decel rate
e deceleration rate defines the time the controller takes to reduce its PWM output to zero when the throttle request is reduced from 100% to zero. e decel rate is programmable from 0 to 10 seconds—see Section 3, page 26.
e decel rate parameter together with the Restraint and rottle Braking Percent parameters allows the OEM to tune the vehicle’s performance in response to reduced throttle, especially when traveling downhill—see Section 6, page 63.
Emergency reverse
Emergency reverse is activated when the keyswitch is On and the emergency reverse input is pulled high, provided the controller is configured with this feature active. Typically, 1244 controllers are used on rider vehicles. Emergency reverse is only applicable to walkies. If you plan to install your 1244 controller on a walkie, refer to Section 2, page 19, and to Section 3, page 48, for instructions regarding emergency reverse.
Environmental protection
e 1244 controller is housed in a rugged ABS plastic case providing environ­mental protection that meets the requirements of IP64/IP67. e controller should be kept clean and dry to ensure long life. Additional protection is rec­ommended if the controller is mounted in a location exposed to dirt or water splash.
ET-series electronic throttles
e ET-XXX is a wigwag-style throttle control assembly. It provides a 0–5V signal in both the forward and reverse directions. Use of this throttle control assembly requires that the controller’s throttle input be configured for a Type2 (single-ended 0–5V) throttle.
Curtis 1244 Manual, Rev. E
A-3
Page 86
APPENDIX A: GLOSSARY
Fault categories
e 1244 controller is equipped with two fault drivers. ese drivers can be configured to provide information in “fault category” or “fault code” format. If the drivers are configured in “fault category” format, they will indicate one of three categories of faults. e Fault Categories are defined in Table 7—see
Section 8, page 75.
Fault codes
e 1244 controller provides fault information by ashing Fault Codes. When a fault occurs, the fault code can be read directly from the Status LED built into the controller’s cover. In addition, the controller has two output drivers that can be configured to provide information in “fault category” or “fault code” format. If the drivers are configured in “fault code” format, they will drive fault indicator LEDs located on a remote panel. e information displayed by these remote panel LEDs will be identical to that displayed by the controller’s built­in Status LED. e Fault Codes are defined in Table 6—see Section 8, page 74.
Fault detection and response
An internal microcontroller automatically maintains surveillance over the functioning of the controller. When a fault is detected, the appropriate fault code is signalled via the controller’s built-in Status LED, which is externally visible through the label on top of the controller. If the fault is critical, the controller is disabled. More typically, the fault is a remediable condition and temporary—for example, an HPD fault is cleared when the throttle is returned to neutral. e faults covered by the 1244 controller’s automatic fault detection system are listed in Table 5—see Section 8, page 73.
Fault recording
Fault events are recorded in the controller’s diagnostic history file. Multiple occurrences of the same fault are recorded as one occurrence. is fault event list can be loaded into the programmer for readout. e programmer’s Diagnos­tics Menu provides access to the controller’s diagnostic history file—the entire fault event list created since the diagnostic history file was last cleared. e Diagnostics Menu also provides information about the currently active faults.
A-4
Curtis 1244 Manual, Rev. E
Page 87
APPENDIX A: GLOSSARY
Fault recovery (including recovery from disable)
Almost all faults require a cycling of the keyswitch or interlock switch to reset the controller and enable operation. e only exceptions are these:
FAULT RECOVERY
anti-tiedown when Mode Select 1 switch is released contactor overcurrent when condition clears HPD when throttle is lowered below HPD threshold overvoltage when battery voltage drops below overvoltage SRO when proper sequence is followed thermal cutback when temperature returns to acceptable level throttle faults when condition clears undervoltage when battery voltage rises above undervoltage (all other faults) (cycle keyswitch or interlock switch)
Field map
e field map parameter determines the relationship between the shunt field winding current and the armature current. e field map parameter aects vehicle acceleration and midrange torque characteristics. is parameter is programmable—see Section 3, page 39.
Field map and the other field current parameters (field map start, field max, field min) allow the OEM to tune the vehicle’s performance characteris­tics—see Section 6, pages 57–61.
Field map start
e field map start parameter defines the armature current at which the field map starts to increase. e field map start parameter is used to help equalize the vehicle’s maximum speed when loaded and unloaded. is parameter is programmable—see Section 3, page 38.
Field map start and the other field current parameters (field map, field max, field min) allow the OEM to tune the vehicle’s performance characteris­tics—see Section 6, pages 57–61.
Full bridge
e 1244 controller uses a full bridge design for control of the field winding. is eliminates the need for external direction contactors. e result is a higher reliability product that is smaller and simpler to install.
Half bridge
e 1244 controller uses a half bridge topology for the armature drive. is provides reliable and highly efficient vehicle control with full all-electronic regenerative braking to zero speed.
Curtis 1244 Manual, Rev. E
A-5
Page 88
APPENDIX A: GLOSSARY
High-pedal-disable (HPD)
e HPD feature prevents the vehicle from driving the motor if the controller is turned on when greater than HPD threshold throttle is applied. ree types of HPD are available (along with a “no HPD” option). Selection is made with the programmer—see Section 3, page 41.
Interlock switch
is switch is a controller-enable input intended to provide a secondary op­erational interlock for the controller in addition to the keyswitch input. If an interlock switch is used, it must be closed—providing a high signal to the in­terlock pin (Pin 2)—in order for the controller to operate. is safety interlock is used on most material handling vehicles. Cycling the interlock switch or the keyswitch clears most faults and re-enables operation.
KSI
KSI (Key Switch Input) provides power to the controller’s logic board, initializes the microprocessor, and starts diagnostics. In combination with the interlock switch input, KSI enables all logic functions.
Load compensation
e load compensation feature automatically adjusts the applied motor voltage as a function of motor load current. is results in more constant vehicle speeds over variations in motor loading due to ramps and cargo weights—without the operator having to constantly adjust the throttle position. e load compensa­tion parameter is programmable—see Section 3, page 49.
e load compensation and Field Map Start parameters allow the OEM to tune the vehicle’s loaded top speed to approach its unloaded top speed—see
Section 6, pages 60–61.
M- fault detect
is feature determines if the M- power connection is being held low (to B-) by an internal or external fault condition. If an M- fault is detected, the controller will inhibit PWM output and release the main and auxiliary contactors. M­fault detection is not performed if greater than 85% throttle is being requested or if emergency reverse is activated.
MOSFET
A MOSFET (metal oxide semiconductor eld eect transistor) is a type of transistor characterized by its fast switching speeds and very low losses.
A-6
Curtis 1244 Manual, Rev. E
Page 89
APPENDIX A: GLOSSARY
MultiMode™
e MultiMode™ feature of the 1244 controller allows the vehicle to be operated with four distinct sets of characteristics. e four modes can be programmed to be suitable for operation under dierent conditions, such as slow precise indoor maneuvering in one mode; faster, long distance, outdoor travel in an­other mode; and application-specific special conditions in the remaining two modes. For more information about MultiMode™ operation, refer to Section 3.
OEM
(= Original Equipment Manufacturer)
Overtemperature
Because of their efficiency and thermal design, Curtis controllers should barely get warm in normal operation. Overheating can occur, however, if the controller is undersized for its application or otherwise overloaded. e 1244 controller constantly monitors its internal heatsink temperature. Starting at 85°C, the drive and braking current limits are linearly decreased from full set current down to zero at 95°C.
Full current limit and performance return automatically after the con­troller cools down. Although occasional overtemperature operation is usually not damaging to the controller, it does suggest a mismatch. If thermal cutback occurs often in normal vehicle operation, the controller is probably undersized for the application and a higher current model should be used. Continuous operation in overtemperature will overstress the power components and reduce the lifetime and reliability of the controller.
Overvoltage cutoff
e overvoltage protection feature inhibits the PWM and shuts down the controller, if the voltage exceeds the factory-set limit. Overvoltage can result during battery charging or from an improperly wired controller. Controller operation resumes when the voltage is brought within the acceptable range. e cuto voltage and re-enable voltage are percentages of the battery voltage, and are defined by the Battery Voltage parameter setting—see Section 3, page 46.
Plug braking
e 1244 controller uses plug braking as well as regen braking to apply braking torque to the vehicle’s motor. Plug braking takes place when braking is requested and the vehicle speed is less than the programmed regen speed. During plug braking, the current is limited to the drive current limit.
Curtis 1244 Manual, Rev. E
A-7
Page 90
APPENDIX A: GLOSSARY
PWM
Pulse width modulation (PWM), also called “chopping,” is a technique that switches battery voltage to the motor on and o very quickly, thereby con­trolling the speed of the motor. Curtis 1200 series controllers use high frequency PWM—in this case, 16 kHz—which permits silent, efficient operation.
Quick-start
Upon receiving a quick throttle demand from neutral, the controller will momentarily exceed normal acceleration in order to overcome inertia. e “quick-start” algorithm is applied each time the vehicle passes through neutral and is not in braking mode. If the vehicle is braking, the quick-start function is disabled, allowing normal braking to occur. e quick-start parameter is programmable—see Section 3, page 26.
Regenerative braking
Regenerative braking occurs when current generated by the motor during braking is allowed to ow back into the batteries. Regen braking results in less motor heating and reduced brush wear compared with plug braking. Regen braking also provides some return of energy to the battery pack, allowing longer vehicle operating periods.
e braking rate defines the time it takes the controller to increase from 0% to 100% regen braking current when braking is requested. e braking rate is a MultiMode™ parameter and is programmable from 0.1 to 5.0 seconds—see
Section 3, page 26.
e regen speed parameter defines the threshold vehicle speed above which the controller initiates regen braking. Below this speed, plug braking is used. e regen speed is programmable from 0 to 100% of the vehicle speed—see
Section 3, page 27.
Restraint
When the vehicle speed exceeds the requested throttle, the restraint feature causes the motor to apply a braking force and “restrain” the vehicle to the re­quested speed. e restraint parameter defines the amount of braking current the controller allows in the motor when it attempts to prevent the vehicle from overspeed—see Section 3, page 37.
Percent parameters allows the OEM to tune the vehicle’s performance in response to reduced throttle, especially when traveling downhill—see Section6, page 63.
downhill creeping when it is stopped on an incline and the brake has not engaged—see Section 6, page 66.
A-8
e restraint parameter together with the Decel Rate and rottle Braking
e restraint parameter also can be used to limit the vehicle’s rate of
Curtis 1244 Manual, Rev. E
Page 91
APPENDIX A: GLOSSARY
Reverse polarity protection
Reverse voltage will damage the controller. Reverse polarity protection is provided by including a diode in series with the control line as shown in the standard wiring diagram, Figure 3. When this diode is used, reversing the battery’s B+ and B- connections to an otherwise properly wired controller will not allow the main contactor to be engaged. is protects the controller from being damaged by the reverse polarity.
Safe commutation region
e safe commutation region includes all the combinations of field current and armature current that allow proper commutation between the motor’s brushes and the armature. If the motor operates outside this region, arcing and severe heating and brush wear will occur. e motor manufacturer should be able to provide curves defining the safe combinations of field and armature current. We highly recommend that you obtain these curves and use them when tuning the 1244 controller to a particular motor.
Sequencing delay
Sequencing delay allows the interlock switch to be momentarily opened within a set time (the sequencing delay), thus preventing inadvertent activation of HPD or SRO. is feature is useful in applications where the interlock switch may bounce or be momentarily cycled during operation. e sequencing delay is programmable from 0 to 3 seconds, with 0 corresponding to no delay—see Section 3, page 47.
Speed limiting
e maximum speed can be limited in each of the four modes. is is done in two ways: through the maximum speed parameter (see Section 3, page 27) and through the minimum field current limit parameter (see Section 3, page 36). e latter (the Min Field parameter) is the primary means of adjusting vehicle top speed. Guidelines for adjusting maximum speed are presented in Section 6: Vehicle Performance Adjustment.
Static-return-to-off (SRO)
e SRO feature prevents the vehicle from being started when “in gear” (i.e., with a direction already selected). ree types of SRO are available (along with a “no SRO” option). Selection is made with the programmer—see Section 3, page 42.
Curtis 1244 Manual, Rev. E
A-9
Page 92
APPENDIX A: GLOSSARY
Status LED
A Status LED (Light Emitting Diode) is built into the controller. It is visible through the label located on top of the controller. e Status LED ashes a 2-digit fault identification code when a fault is detected by the controller. e fault code continues to ash until the fault has been corrected and the fault condition has been cleared. Clearing the fault condition typically requires cy­cling KSI for faults detected during startup, and cycling the interlock switch for faults detected during operation. e fault codes are defined in Table 6—see Section 8, page 74.
Taper rate
e taper rate defines how gradually the vehicle slows down at the completion of regen braking. e taper rate is programmable—see Section 3, page 27.
Temperature compensation for current limits
Full temperature compensation provides constant current limits throughout the normal operating range (heatsink temperatures of -25°C to +85°C). e temperature sensor that regulates the current limits is also used to calculate the heatsink temperature displayed by the programmer.
Throttle braking
e throttle braking feature provides automatic braking when the controller’s throttle input is reduced. e strength of braking is determined by the pro­grammed rottle Braking Percent parameter value. rottle braking can be disabled (i.e., set to 0%) if this feature is not desired. rottle Braking Percent is a MultiMode™ parameter—see Section 3, page 36.
e rottle Braking Percent parameter together with the Decel Rate and Restraint parameters allows the OEM to tune the vehicle’s performance in response to reduced throttle, especially when traveling downhill—see Section6,
page 63.
Throttle deadband (neutral deadband)
e throttle deadband is the pot wiper voltage range that the controller inter­prets as neutral. e throttle deadband is typically set at 10%. A higher setting increases the neutral range, which can be useful with throttle assemblies that do not return reliably to a well-defined neutral point. e throttle deadband parameter is programmable—see Section 3, pages 30–31, and Section 6, page 55.
A-10
Curtis 1244 Manual, Rev. E
Page 93
APPENDIX A: GLOSSARY
Throttle map
e throttle map parameter determines the controller’s static throttle map, ad­justing the throttle characteristics to suit your specific application and enhance your vehicle’s performance. e throttle map parameter modifies the controller’s PWM output relative to the requested throttle amount. e throttle map is a MultiMode™ parameter—see Section 3, page 34.
Throttle max
e throttle max parameter allows accommodation of throttles that do not provide the standard full range of voltage or resistance variation at the throttle input. Reducing the throttle max parameter value allows full controller output with a throttle input less than that specified in Table 1 (page 10). e throttle max parameter can be programmed to fit your specific vehicle’s requirements—see Section 3, pages 32–33, and Section 6, page 56.
Throttle types
e 1244 controller accepts a variety of throttle inputs, through various combi­nations of its three throttle input pins. e most commonly used single-ended and wigwag throttles (5kΩ–0 and 0–5kΩ pots, 3-wire pots, 0-5V throttles, and the Curtis ET-XXX electronic throttle) can be used simply by selecting the appropriate throttle type in the programmer’s Program Menu—see Section3, page 29. e controller can also be specified to receive throttle signals from a CAN-based communications system—see Section 4, page 51.
Tuning
e 1244 controller provides a variety of programmable parameters to assist in tuning the vehicle to meet the customer’s needs. Section 6: Vehicle Performance Adjustment presents information and procedures for tuning specific operating characteristics on any vehicle.
Undertemperature
When the controller is operating at less than -25°C, the drive current limit is cut back to approximately one-half its rated value. e controller will warm itself at this reduced current and when its internal temperature rises above -25°C, full current will become available.
Curtis 1244 Manual, Rev. E
A-11
Page 94
APPENDIX A: GLOSSARY
Undervoltage protection
Undervoltage protection automatically cuts back the controller output if bat­tery voltage is detected below the undervoltage point at startup, or when the battery voltage is pulled below the undervoltage point by an external load. e under voltage cutback point is determined by the battery voltage parameter, which should be identical to the system’s nominal battery pack voltage—see Section 3, page 46.
During normal operation, the controller duty cycle will be reduced when the batteries discharge down to less than the undervoltage level. If the motor current is such that the batteries are being pulled below the minimum point, the duty cycle will be reduced until the battery voltage recovers to the minimum level. In this way the controller “servos” the duty cycle around the point which maintains the minimum allowed battery voltage.
If the voltage continues to drop below the undervoltage level to a severe undervoltage condition (due to battery drain or external load), the controller continues to behave in a predictable fashion, with its output disabled.
Watchdog (external, internal)
e external watchdog timer guards against a complete failure of the micropro­cessor, which would incapacitate the internal watchdog timer. is independent system check on the microprocessor meets the EEC’s requirement for backup fault detection.
e external watchdog timer safety circuit shuts down the controller (and the microprocessor) if the software fails to generate a periodic external pulse train. is pulse train can only be created if the microprocessor is operating. If not periodically reset, the watchdog timer times out after 15–20 msec and turns o the controller. e external watchdog also directly shuts down the PWM drive to the MOSFETs. It can only be reset by cycling KSI.
e internal watchdog timer must be reset periodically by correct sequen­tial execution of the software. If not reset, the internal timer times out and the microprocessor is “warm booted.” is causes the microprocessor to shut down its outputs—thus shutting down the controller—and attempt to restart.
Welded contactor checks
e 1244 controller checks for a welded main contactor at startup. If a welded contactor is detected, the controller inhibits its output until the fault is removed and the keyswitch power is cycled. A welded main contactor fault is indicated in the programmer’s Diagnostics Menu as well as by the controller’s Status LED.
A-12
Curtis 1244 Manual, Rev. E
Page 95
APPENDIX B: PROGRAMMING DEVICES
APPENDIX A: GLOSSARY
APPENDIX B
PROGRAMMING DEVICES
Curtis programmers provide programming, diagnostic, and test capabilities for the 1244 controller. e power for operating the programmer is supplied by the host controller via a 4-pin connector. When the programmer powers up, it gathers information from the controller.
Two types of programming devices are available: the 1314 PC Program­ming Station and the 1313 handheld programmer. e Programming Station has the advantage of a large, easily read screen; on the other hand, the handheld programmer (with its 45×60mm screen) has the advantage of being more por­table and hence convenient for making adjustments in the eld.
Both programmers are available in User, Service, Dealer, and OEM ver­sions. Each programmer can perform the actions available at its own level and the levels below that—a User-access programmer can operate at only the User level, whereas an OEM programmer has full access.
PC PROGRAMMING STATION (1314)
e Programming Station is an MS-Windows 32-bit application that runs on a standard Windows PC. Instructions for using the Programming Station are included with the software.
HANDHELD PROGRAMMER (1313)
e 1313 handheld programmer is functionally equivalent to the PC Program­ming Station; operating instructions are provided in the 1313 manual. is programmer replaces the 1307 and 1311, earlier models with fewer functions.
PROGRAMMER FUNCTIONS
Programmer functions include:
Parameter adjustment — provides access to the individual programmable pa-
rameters.
Monitoring — presents real-time values during vehicle operation; these include
all inputs and outputs.
Diagnostics and troubleshooting — presents diagnostic information, and also a
means to clear the fault history file.
Programming — allows you to save/restore custom parameter settings les and
also to update the system software (not available on the 1307 or 1311).
Favorites — allows you to create shortcuts to your frequently-used adjustable
parameters and monitor variables (not available on the 1307 or 1311).
Curtis 1244 Manual, Rev. E
A-13
B-1
Page 96
APPENDIX A: GLOSSARY
APPENDIX C: SPECIFICATIONS
APPENDIX C
SPECIFICATIONS
Table C-1 SPECIFICATIONS: 1244 CONTROLLER
Nominal input voltage 24 –36 V, 36–48 V, and 48–80V
PWM operating frequency 16 kHz
Electrical isolation to heatsink 500 V ac (minimum)
KSI input voltage (minimum) 16.8 V for 24–36 V systems
KSI input current (no contactors engaged) 160 mA without programmer; 200 mA with programmer
Logic input voltage >7.5 V High; <1 V Low
Logic input current 10 mA
Operating ambient temperature range -40°C to 50°C (-40°F to 122°F)
Heatsink overtemperature cutback 85°C (185°F)
Heatsink undertemperature cutback -25°C (-13°F)
Package environmental rating IP64 / IP67
Weight 3.9 kg (8.5 lb)
Dimensions (L×W×H) 229 × 178 × 81 mm (9.0" × 7.0" × 3.2")
NOMINAL ARMATURE ARMATURE ARMATURE FIELD BATTERY CURRENT 2 MIN 1 HOUR 2 MIN MODEL VOLTAGE LIMIT RATING RATING * RATING NUMBER (volts) (amps) (amps) (amps) (amps)
1244-44XX 24–36 400 400 160 60 1244-45XX 24–36 500 500 175 60 1244-46XX 24–36 600 600 190 60 1244-47XX 24–36 700 700 † 190 60
1244-54XX 36–48 400 400 140 50 1244-55XX 36–48 500 500 160 50 1244-56XX 36–48 600 600 160 50
1244-64XX 48–80 400 400 125 50 1244-65XX 48–80 500 500 140 50 1244-66XX 48–80 600 600 † 140 50
* at 25°C ambient temperature 1-minute rating
A-14