The PowerCommand Network can be used to remotely operate power transfer equipment (e.g.,
transfer switches, paralleling systems) and start
and stop generator sets. All of the safety precau-tions for that equipment must be observed. Refer tothe Operator’s Manual for the equipment that is be-ing monitored and controlled by the network for im-portant safety precautions.
The following symbols, found throughout thismanual, alert you to potentially dangerous condi-tions to the operator, service personnel, or theequipment.
DANGER
hazards which will result in severe personal in-jury or death.
WARNING
unsafe practice which can result in severe per-sonal injury or death.
CAUTION
unsafepractice which can result in personal in-jury or product or property damage.
This symbol warns of immediate
This symbol refers to a hazard or
This symbol refers to a hazard or
MOVING PARTS CAN CAUSE SEVEREPERSONAL INJURY OR DEATH
•Keep your hands, clothing, and jewelry away
from moving parts.
•Before starting work on the generator set, dis-
connect battery charger from its AC source,then disconnect starting batteries, negative (-)cable first. This will prevent accidental starting.
• Make sure that fasteners on the generator set
are secure. Tighten supports and clamps, keep
guards in position over fans, drive belts, etc.
•Do not wear loose clothing or jewelry in the vi-
cinity ofmoving parts, or while working on elec-trical equipment. Loose clothing and jewelrycan become caught in moving parts. Jewelrycan short out electrical contacts and causeshock or burning.
•If adjustment must be made while the unit is
running,use extreme caution around hot man-ifolds, moving parts, etc.
ELECTRICAL SHOCK CAN CAUSESEVERE PERSONAL INJURY OR DEATH
•Remove electric power before removing pro-
tective shields or touching electrical equip-ment.Use rubber insulative mats placed on drywood platforms over floors that are metal orconcrete when around electrical equipment.Do not wear damp clothing (particularly wetshoes) or allow skin surface to be damp whenhandling electrical equipment.
•Use extreme caution when working on electri-
cal components. High voltages can cause inju-ry or death. DO NOT tamper with interlocks.
•Follow all applicable state and local electrical
codes. Have all electrical installations per-formed by a qualified licensed electrician. Tagand lock open switches to avoid accidental clo-sure.
•Jewelry is a good conductor of electricity and
should be removed before working on electri-cal equipment.
viii
MEDIUM VOLTAGE GENERATOR SETS
(601V to 15kV)
• Medium voltage acts differently than low volt-
age. Special equipment and training is required
to work on or around medium voltage equipment. Operation and maintenance must be
done only by persons trained and qualified to
work on such devices. Improper use or proce-dures will result in severe personal injury ordeath.
•Do not work on energized equipment. Unau-
thorized personnel must not be permitted nearenergizedequipment. Due tothe nature of me-dium voltage electrical equipment, inducedvoltage can remain even after the equipment isdisconnectedfrom the power source. Plan thetime for maintenance with authorized person-nel so that the equipment can be de-energizedand safely grounded.
TRANSFER SWITCHES
•AC and DC voltages in the transfer switch com-
ponents present serious shock hazards thatcan result in severe personal injury or death.Read and follow these instructions.
•Keep the transfer switch cabinet closed and
locked. Make sure only authorized personnelhave cabinet and operational keys.
•Due to the serious shock hazard from medium
voltages within the cabinet, all service and ad-justments to the transfer switch must be per-formedonly by an electrician or authorized ser-vice representative.
• If the cabinet must be opened for any reason:
1. Move the operation selector switch on the
generator set to Stop.
2. Disconnect battery charger from its AC
source. Disconnect the starting batteries
of the generator set. (Remove the negative [−] lead first to prevent arcing from ig-niting explosive battery gas.)
3.Remove ACpower to the automatic trans-fer switch. If the instructions require other-wise,use extreme caution due to the dan-ger of shock hazard.
GENERAL SAFETY PRECAUTIONS
•The PowerCommand Network allows remote
operation ofequipment. PowerCommand Soft-ware for Windows can remotely start and stop agenset or exercise a transfer switch. Networkmodules can independently control other net-work modules and operate other electrical de-vicessuch as fans or pumps etc. Make certainthat all appropriate personnel are notified be-fore remotely operating equipment and makethemaware of any equipment that can be ener-gized automatically.
•Do not work on this equipment when mentally
or physically fatigued, or after consuming anyalcohol or drug that makes the operation ofequipment unsafe.
•Use only the latest physical and logical connec-
tion diagrams for installing and maintaining thePowerCommand Network. If changes aremade to the physical or logical network con-nections, make sure the site connection dia-gramsare updated. Create a new CSV file if thenumber or type of modules changes or if thebindings change.
PCN−1
ix
CUMMINS POWER GENERATION POWERCOMMAND® SOFTWARE LICENSE AGREEMENT
By breaking the seal on the PowerCommand diskette envelope, you indicate your acceptance of the
terms of this Agreement. If you do not accept the terms of this Agreement, you may return within 5
business days of your purchase the entire contents of this kit to the Cummins distributor from which it
was purchased for a complete refund.
RECITALS:
WHERAS, Onan Corporation d/b/a Cummins Power Generation (hereinafter “CPG”) and Licensee desire toestablish a relationship pursuant to which Licensee will obtain certain rights from CPG with respect to the Li-censed Software, and CPG will provide certain information and updates to Licensee, all for the mutual benefitof CPG and Licensee; THEREFORE, in consideration of the above premise and the mutual covenants con-tained herein, CPG and Licensee agree as follows:
1.License Grant Restrictions
a.CPG hereby grants to Licensee a non-exclusive, non-transferable and non-sublicensable license to
possess and use one copy of the Licensed Software contained in this package in machine-readableform to monitor and control power generation systems manufactured or sold by CPG. The LicensedSoftware is specifically licensed for use in a single facility of Licensee for its intended purpose, andit may not be sublicensed, sold, or otherwise distributed. The license for Licensed Software is subjectto the following terms and conditions.
b.Licensee may load each copy of the Licensed Software and the “Security Key” files provided by CPG
onto a single computer as required to use the Licensed Software for its intended purpose. Licenseemay make a single backup or archival copy of the Licensed Software in machine-readable form, pro-vided that Licensee affixes to the backup or archival copy any copyright and trademark notice, serialnumber and any other legend of ownership contained on the original disk from which the archivalcopy was made.
c.Licensee agrees to use the Licensed Software, and any updates to the Licensed Software, in strict
accordance with CPG’s published service practices and/or product warranty guidelines for the solepurpose of monitoring and controlling power generation systems manufactured or sold by CPG.
d.Licenseeacknowledges that CPG may, atits option and at no cost to the Licensee, provide updates
to the Licensed Software so that the most current version of the Licensed Software is used to monitorand control power generation systems. CPG may also offer for sale upgrades of the Licensed Soft-ware which the Licensee is under no obligation to purchase.
e.All rights relating to the Licensed Software not specifically granted to Licensee pursuant to this
Agreement shall be retained by CPG.
f.Licensee acknowledges that the Licensed Software may include software that CPG has obtained
or licensed from a third party, and Licensee agrees that the terms and conditions of this Agreementshall be applicable to any such third party software. Licensee agrees to abide by any additional ormodified terms and conditions with respect to such third party software if reasonably requested inwriting by CPG and/or the third party.
2.Markings
Licensee shall use its best efforts to preserve all copyright, trademark, ownership or other notices, legends ormarkings on the Licensed Software as originally provided by CPG. In the event the Licensed Software con-tains any copyright or other message imbedded therein, Licensee shall not modify or remove such embedded
message. All copyright, trademark, ownership or other notices, legends or markings on the Licensed Software
as originally provided by CPG also shall be clearly displayed on each backup or archival copy of the Licensed
Software.
3. Materials
The PowerCommand Installation Diskettes, Security Key Diskettes, User Manual, and any updates thereto,
constitute the entire product referred to herein as the Licensed Software unless otherwise agreed to by the
parties.
x
4. Title
Title and full ownership rights to the Licensed Software and any updates thereto, and all intellectual property
rights, including, without limitation, patent, trademark, copyright and trade secret rights therein, shall remain
with CPG and/or its subsidiaries. CPG expressly retains all rights that it may have under U.S. or foreign laws or
international treaties relating to the Licensed Software, except for those rights expressly granted to Licensee
herein.
5. Licensee Expenses
Costsand expenses incurred by Licensee relating to any use of the Licensed Software, or any other costs notspecifically agreed upon by the parties in writing, shall be responsibility of Licensee.
6.Payment
The sales price does not include any federal, state, local or other governmental taxes, or other tariffs whichmay be imposed on the sale, transportation, production, storage, or export of the Licensed Software. Any andall such taxes and costs shall be paid by Licensee and CPG shall have no liability therefor.
7.Updates and Maintenance
a.CPG agrees to provide reasonable free Help Desk support for the current version and the latest prior
version of the Licensed Software at hours, and under terms and conditions determined solely byCPG.
b.In the event of an error or defect in the Licensed Software or periodic update thereto, CPG agrees
to repair or remedy such errors or effects which CPG deems necessary. Licensee shall, promptlyupon discovery thereof, notify CPG, in writing, of any errors or defects in the Licensed Software and/or periodic update thereto. CPG shall use its best efforts to remedy or repair such errors or defects,devoting reasonable resources to such task in view of the particular business situation and customerneed.
8.No Modification by Licensee
Licensee agrees not to translate, rearrange, reverse assemble, reverse compile, enhance, adapt, translate,alter,modify or change in any way the Licensed Software, or any update thereto, without the prior written au-thorization of CPG.
9.Warranties
CPG warrants that the diskettes containing the Licensed Software shall be free from defects in material orworkmanshipfor a period of ninety (90) days from the date of delivery to Licensee. CPG also warrants that theLicensed Software shall be delivered free of any rightful claim of infringement of any copyright, trademark,tradesecret or other proprietary right of any third party, provided that prompt notice of, and control over, suchclaims is provided to CPG by Licensee. In the event of such claim, CPG may, at its sole option, defend theclaim,procure for Licensee the continued rights as described herein, modify the Licensed Software so theclaim is avoided without reduced functionally, or refund Licensee’s sales price paid. CPG’soption shall be itssole obligation and Licensee’s sole remedy in such event.
10.Warranty Disclaimer
The Licensed Software and any and all updates thereto are licensed “As Is” with the exception of the warran-ties specifically provided herein. CPG does not claim and does not warrant that the Licensed Software will runerror free. WITH THE EXCEPTION OF THE WARRANTIES PROVIDED HEREIN, CPG DISCLAIMS ALL
WARRANTIES, EITHER EXPRESSED OR IMPLIED, REGARDING THE LICENSED SOFTWARE, ITS
MERCHANTABILITY OR ITS FITNESS FOR ANY PARTICULAR PURPOSE, AND CPG WILL NOT OTHERWISE BE LIABLE FOR INDIRECT, INCIDENTAL OR CONSEQUENTIAL DAMAGES OF ANY KIND WHATSOEVER RESULTING FROM LICENSEE’S USE OF THE LICENSED SOFTWARE OR FOR ANY ERROR
OR DEFECT IN THE LICENSED SOFTWARE. CPG’S NET LIABILITY TO LICENSEE SHALL NOT EXCEED
THE TOTAL AGGREGATE PAYMENTS BY LICENSEE TO CPG WITH RESPECT TO THE LICENSED
SOFTWARE.
xi
11. Government Licensee
If Licensee is acquiring the Licensed Software as, or on behalf of, a unit of the United States Government, the
following provisions shall be applicable: The Government acknowledges and agrees that the Licensed Software and documentation relating thereto were developed at private expense and no part of the Licensed Software or documentation relating thereto is in the public domain. The Government acknowledges CPG’s representation that the Licensed Software is “Restricted Computer Software” as that item is defined in Clause
52.227-19 of the Department of Federal Acquisition Regulation Supplement (DFARS). The Government
agrees that:
(i)If the Licensed Software is supplied to the Department of Defense (DoD), the Licensed Software is
classified as “Commercial Computer Software” and the Government is acquiring only “restrictedrights” inthe Licensed Software and documentation relating thereto as that term is defined in Clause
252.227−7013(c)(1) of the DFARS, and
(ii)Ifthe Licensed Software is supplied to any unit or agency of the United States Government other than
the Department of Defense, the Government’s rights in the Licensed Software and documentationrelating thereto will be defined in Clause 52.227−19(c)(2) of the FAR.
12.Restricted Rights Legend
Use,duplication, or disclosure by the Government is subject to restrictions set forth in subparagraph (c) (1) (ii)of the Rights in Technical Data and Computer Software clause at DFARS 252.227−7013.
13.Confidentiality
a.Licensee hereby acknowledges that the Licensed Software and periodic updates thereto contain
valuable information belonging to CPG that CPG considers “confidential”. Licensee acknowledgesand agrees that the source code, object code and other information respecting the Licensed Soft-ware is confidential information of CPG. Consistent with the purpose of this Agreement, Licenseeagrees touse its best efforts not to release, disclose or otherwise permit unauthorized access to suchconfidentialinformation. In addition to any other rights or remedies which may be available to CPG,CPG (without being required to post any bond or other security) shall be entitled to appropriate injunc-tive relief against Licensee or its agents in the event of any breach of this section. Licensee acknowl-edges and agrees that any unauthorized use of disclosure will cause irreparable injury to CPG andthat money damages may not provide adequate remedy.
b.CPG and Licensee agree to clearly mark written materials as ”confidential” if they are to be treated
as confidential. Verbal communications that are confidential in nature will be identified as so before,during or immediately after the communication.
c.Licensee will use its best efforts to ensure that all individuals who are provided access to the Licensed
Software under this Agreement will observe and perform this nondisclosure covenant.
14.Termination of Agreement
a.CPG may terminate this agreement for cause in the event that Licensee becomes or is declared in-
solvent or bankrupt.
b.In the event of termination of this Agreement, all rights granted by this Agreement shall revert to CPG.
Upon termination of this Agreement, Licensee will deliver to CPG all material furnished byCPG per-taining to the Licensed Software and will also warrant that all copies thereof have been returned toCPG or destroyed.
c.In the event of termination of this Agreement, Licensee and CPG shall remain obligated with respect
to the provisions of this Agreement relating to confidentiality of information.
15. Completeness
Licensee and CPG agree that this Agreement constitutes the complete agreement and understanding between the parties relating to Licensed Software and updates thereto. This agreement supersedes all prior
agreements, understandings, and negotiations whether written or verbal with respect to the subject matter
hereof. This Agreement can only be modified by a written agreement signed by both parties.
xii
16. Export Regulations
Licensee understands that the Export Administration Regulations of the Department of Commerce of the
United States may prohibit the export of the Licensed Software to certain countries and agrees to conform to
those regulations. Licensee shall indemnify CPG against any liability or loss related to Licensee’s failure to
conform to those regulations.
17. Governing Law
This Agreement shall be governed by and construed in accordance with the laws of the State of Indiana,United States of America and NOT the UNCISG. To the extent required in order to comply with the laws andregulations of any country in which Licensed Software is distributed or used, the terms and conditions of thisAgreement shall be construed to most nearly effectuate the purposes of the Agreement as set forth herein. Ifany provision of this Agreement shall be held to be unenforceable, such holding shall not affect the enforce-ability of any other provision hereof.
18.Attorney’s Fees
In the event of any legal action or other proceeding that is brought about to enforce this Agreement, the prevail-ing or successful party shall be entitled to recover reasonable attorneys’ fees as well as other costs incurred inthat action or proceeding in addition to any compensation to which it may be entitled as a result.
19.Agreement Successors and Assigns
The terms and conditions of this Agreement shall inure to the benefit of and enforceable by CPG and the suc-cessorsand assigns of CPG’s interest in this agreement and/or CPG’s ownership of the Licensed Software.
Excerpts from the following quick start guides are reprinted with permission of
Echelon:
i.LON 100 e3 Internet Server Quick Start Guide
Excerpts from the following manuals reprinted with permission of Echelon:
i.LON 100 e3 Internet Server User’s Guide:Installing, Connecting, and
Configuring the i.LON 100;
i.LON 100 e3 Internet Server User’s Guide:Using the i.LON 100 Web Pages
to Configure Application and to Monitor and Control Data Points;
i.LON 100 e3 User’s Guide
In addition, screen shots from the i.LON 100 built-in web pages will bereproduced.
Except as expressly permitted, no part of this publication may be reproduced,stored in a retrieval system, or transmitted, in any form or by any means,electronic, mechanical, photocopying, recording, or otherwise, without the priorpermission of Fuji Electric Systems. Excerpts from the i.LON documentationmay not be reproduced, stored or transmitted without the prior permission ofEchelon Corporation.
Echelon and i.LON are trademarks of Echelon Corporation registered in theUnited States and other countries.
xiv
1. Introduction
FIGURE 1-1. THE POWERCOMMAND iWATCH 100 MONITORING SYSTEM
WELCOME
The PowerCommand iWatcht 100 isan Eche-lonti.LON100e3 baseddevicethatprovidesmonitoringand control of generators and/or trans-
The PowerCommand iWatch 100 is comprised ofthree major components:
•i.LON100e3 Software – Used to set up the
i.LON100 as a Remote Network Interface, addconfiguration Plug-Ins, and install software up-grades for LonMaker for Windows
•PowerCommand iWatch 100 Support CD – In-
cludes the factory image files for LonWork’sgensets and ModBus gensets, network data-bases, type/format files, security profiles and
®
documentation needed for the PowerCom-mand iWatch 100 application
•i.LON100e3Hardware – The PowerCommand
iWatch 100 works with LonWorks FT-10net-
®
work Automatic TransferSwitches (ATSs), gen-set controls, and 13xx series control (ModBus).
i.LON 100
Hardware
+
i.LON 100
Software
+=
Cummins
PowerCommand
iWatch 100
Software
PowerCommand
iWatch 100
1-1
ADDITIONAL HARDWARE NEEDED
Control Pages
The installer must supply the following items; they
are needed for installation and application of the
PowerCommand iWatch 100.
• DB9 female connector – Female null modem
cable (EIA-232)
•Ethernet patch cable (RJ-45 connectors)
•Powercord (type is dependent upon the power
supply, 90−230 VAC, 50−60 Hz)
SOFTWARE FEATURES
The features available through the PowerCom-mandiWatch 100 are briefly described here andare covered in more detail in the section related tothat feature.
OneLinePage – Gives an overview of the status ofthe network and provides links to each of the de-vices on the network.
Generator Summary – Web page for monitoringgenerator AC and engine data.
Generator Annunciator–Web page for monitor-ing all of the generator annunciated alarms.
ATS Summary–Web page for monitoring the ATSsource and load data.
ATS Annunciator–Web page for monitoring all oftheATS annunciated alarms.
Genset & ATS− Web page for activating the gen-
erator Start/Stop command and Fault Reset buttons as well as Test and Fault Reset for the transfer
switches.
Control – Web page for activating the relay outputs.
ABOUT THIS OPERATOR’S MANUAL
This Operator’s Manual covers software installa-tion, setup, and operation of the PowerCommandiWatch 100 application.
•Section 1 provides an overview of this manual
and some basic features.
•Section2 describes the required software to be
installed on the service technician’s computer.
•Section 3 covers installation requirements and
how to mount, wire, and connect the Power-Command iWatch 100 to aLAN/WAN orDial-upISP modem.
•Section 4 describes how to create thePower-
Command iWatch 100 projectfolders, modifycustomer specific settings, andloadthe webpagefiles onto the iLon100. It also includes set-ting up hyperterminal, setting up a remotenet-work interface, setting a static IP adresson theservice computer, configuring a dial-upconnec-tion, and commissioningthe PowerCommandiWatch 100 using LonMakerR for WindowsR.
Alarm History Log – Contains a list of the last 50alarms.
Alarm Summary Page – Contains a summary ofallof the alarms and allows for clearing and ac-knowledging alarms.
E-mail Page – Contains preconfigured e-mails.You can configure more emails and the recipients.
Digital I/O–Web page for monitoring digital inputsand outputs.
•Section 5 provides descriptions of the Power-
Command iWatch 100’s user web pages.
•Section6 provides information on alarm gener-
ation and notification, including e-mail configu-ration.
•Section 7 provides information on setting up dif-
ferent user names and passwords.
•Appendix A provides general information on
troubleshooting the network connection.
1-2
2. Software Installation
INTRODUCTION
This section covers the installation process and
setup instructions for the i.LON100e3 softwareand the PowerCommand iWatcht100 applicationfiles. This information is to be used by the tech-nician when creating the network. The end useronly needs to make sure that the monitoring com-puterhas access to Internet Explorer 6.0 or higherand the necessary hardware to support this brows-er.
Unless a new version of the PowerCommandiWatch 100 or new version of i.LON 100 is re-leased, the software described in this section onlyneeds tobeinstalled once on the technician’s com-puter. In order for the complete PowerCommandiWatch 100 application to function correctly, it isnecessary tocomplete all of the setup procedures,as described in each of the sections.
COMPUTER HARDWARE
REQUIREMENTS
• Microsoft Windows XP or Windows 2000
• LonMaker 3.1, Version 3.13.10 and LNS ver-
sion 3.08.05 (Service Pack 8)
•Terminal Emulator (for example, Windows Hy-
per Terminal)
NOTE:Cumminsrecommended updates for Lon-
Maker are included on the PowerCom-mandiWatch 100 CD if needed. You cancheckyour LonMaker version by launch-ing LonMaker. At the first dialog box, clickon the LonMaker icon in the far upper left,and select “About Echelon LonMaker”. Ifyou have questions about your LonMakerversion, contact service.
I.LON100e3 CD / SOFTWARE
INSTALLATION
NOTE:The software on the CD provided by Eche-
lon should be i.LON100 version e3.
To use i.LON100 installation and configurationsoftware, your computer must meet or exceed thefollowing hardware requirements.
•Pentium II 600 MHz or faster
•128 MB RAM minimum
•70 MB free hard disk space
•CD-ROM drive
•Super VGA (800 x 600) or higher resolution dis-
play with 256 colors (1024 x 768 recommendedfor viewing web pages)
•Mouse or compatible pointing device
•Serial port
•Ethernet RJ45 port (NIC port)
COMPUTER SOFTWARE
REQUIREMENTS
To use i.LON100 installation and configuration
software, your computer must meet or exceed the
following software requirements.
FIGURE 2-1. INSTALLATION SOFTWARE LIST
NOTE:DO NOT install Echelon LonMaker 3.1,
Update 2 (LNS Turbo). This feature isNOTrecommended or supported by
Cummins, Inc.
This installation only needs to be performed on the
technician’s laptop. i.LON100 software is not
needed for viewing the web pages.
The i.LON100e3 software installation CD contains
the following:
2-1
• i.LON100 Configuration Plug-In (Not needed)
• LonMaker 3.1 update 2. (Do not install.)
dates separately. They are located in the
Echelon updates folder on the PowerCommand iWatch 100 CD.)
• LNS Service Pack 8
• i.LON100 User Guides
There are two different methods available for obtaining the i.LON100e3 software.
•Request it from the CPG Software Shelf.
NOTE:If you are obtaining the i.LON100e3
software from the CPG SoftwareShelf, keep in mind that it may takeseveral days to receive the software.
•Insert the i.LON100e3 CD provided with the
PowerCommandiWatch 100 and follow thesteps below.
To install the i.LON100e3 software from the CD:
1.Insert the i.LON100e3 software installationCD into your computer. If the program fails tostart,navigate to your CD-ROM drive and runsetup.exe.
2.Click on Install Products.
3.Click onthe i.LON100e3 SR2 Software only.
4.Followthe instructions in the setup wizard. Bepatient. This may take several minutes. (Ifyour LonMaker version is not at least 3.13.10and LNS version 3.08.05, the installation maypromptyou to install the updates necessary toachieve these version levels. It is recom-mended that you stop and install these up-
POWERCOMMAND iWATCH 100 CD
INSTALLATION
The support CD contains the necessary files to
load ontothe PowerCommand iWatch 100, a PDFof this manual, and the supplements described be-low:
•Network support CD
•PowerCommand iWatch 100 format files
•PowerCommand iWatch 100 LonMaker data-
basesfor 2100, 3100, and 32xx generator con-trols
•Documentation onthe PowerCommand iWatch
100,FT-10 Devices, FT-10 and ModBus Net-work Installation, and application supplements
•Read Me file
NOTE:The CD contains folders for both the 2100,
3100, 3200 genset control PowerCom-mand iWatch 100 and the 1301 gensetcontrol(ModBus) PowerCommand iWatch100 (see Figure 2-2).
For a detailed description of each of the files in-cluded,please refer to the Readme.doc file on thePowerCommand iWatch 100 CD. The Readme fileincludes the names, dates, and location of each ofthe files on the PowerCommand iWatch CD. Infor-mation onfile placement is also described in detail.
2-2
FIGURE 2-2. CD CONTENTS
2-3
This Page Intentionally Left Blank
2-4
3. PowerCommand iWatch 100 Installation
INTRODUCTION
Thissection describesthe physical installation ofthe PowerCommandiWatcht100 and the physi-cal connectionsto thei.LON100 server.
MOUNTING AND WIRING OF THE
I.LON 100
The information included in this section is taken di-rectly from Echelon’s“i.LON100 e3 User’s Guide.”This section describes the mounting of the i.LON100, the LonWorks connection, the console con-nection, the telephone line connection, the ether-net connection, and the power connection.
The locking tab is located below console port DB9
FIGURE 3-1. I.LON 100 SERVER DIN RAIL
LOCKING TAB LOCATION
For additional information on any of the other con-nections, refer to the Echelon i.LON 100 User’sGuide.
Mounting the Enclosure
WARNING
tended tobemounted inside of a suitable, safe-ty-agencyapproved enclosure that is mountedin a restricted access area. High-voltage wiringmust be performed only by a qualified serviceperson.
The i.LON 100 Internet Server mounts to a 35mm x
7.5mm or35mm x 15mm DIN rail located inside ofa suitable, safety-agency approved enclosure,and mounted in a restricted access area. All high-voltage wiring must be performed by a qualifiedservice person. The rear of the i.LON 100 server
enclosure contains a spring−loaded DIN rail lock,
which securely grabs the DIN rail onto which the
enclosure is snap mounted (see Figure 3-1). To release the enclosure from the DIN rail, insert a flat
head screwdriver into the DIN rail locking tab and
gently pull the tab upwards and away from the enclosure.
The i.LON 100 Internet Server is in-
Figure 3-2shows the dimensions of the i.LON 100server and the space required for the various con-nectors. All units are in millimeters.
Wiring Connections
The i.LON 100 Internet Server is provided with tworows of screw terminal wiring connections, anRJ-45 data connection, an RJ-11 telephone con-nection,and a DB-9 D-connector for connection toa configuration console. The screw terminals arelocated on the top and bottom edges of the chas-sis,and are numbered 1 to 12 (ascending from leftto right) on the bottom, and from 13 to 28 (ascend-ing from right to left) on the top. Figure 3-3 showsthe locations of all i.LON 100 server connectors.
The RJ-45 10/100 BaseT Ethernet Port
The RJ-45 connector must be used with an RJ-45male connector and a suitable Category 5 or Cate-gory 6 data cable connected to a 10BaseT or100BaseT channel. The i.LON 100 server will au-
tomatically adjust to the speed of the data port, and
if a 100BaseT network connection is established illuminates the “100” LED indicator on the front panel. The i.LON 100 server automatically detects
whether it is connected to an Ethernet hub or directly to a computer, so there is no need to use a
crossover Ethernet cable.
3-1
FIGURE 3-2. i.LON 100 SERVER DIMENSIONS
Service Pin
RS-485
Serial
Mains (90−240
VAC, 50/60 Hz)
RS-232
Serial
Relay
Outputs
LonTalk
+12V
<20 mA
DB-9
Console Port
DigitalInputs
RJ-11
Telephone
Line Port
RJ-45 10/
100 Base T
Ethernet Port
Reset Switch
Metering
Inputs
FIGURE 3-3. i.LON 100 SERVER DATA, CONSOLE, AND TELEPHONE CONNECTIONS
3-2
The DB-9 Console Port
The i.LON 100 server contains a console application that is accessed using a terminal emulation
program, such as Windows HyperTerminal, via the
EIA-232 DB-9 console port. This application allows you to set basic parameters such as the IP address, subnet mask, and FTP user name and
password.The DB-9 is designed to be used with aDB-9 null-modem crossover cable with femaleconnectors on both ends that connects the i.LON100 server and an available COM port on a com-puterrunning the terminal emulation program. Theconnectorpins on the DB-9 console are aligned asshown in Figure 3-4. The connector pins are de-scribed in Table 3-1.
12345
These are polarity sensitive signals, and the (+)
and (−) connections are noted adjacent to the terminals. Since RS-485 is susceptible to common
mode ground differential voltage swings, it is
imperative that you use a suitable shielded cable
when connecting RS-485 based devices. Reversing the polarity of the RS-485 bus will cause improper bus operation and must be avoided. The
connector pins are described in Table 3-2.
TABLE 3-2. i.LON 100 RS-485 PIN ASSIGNMENT
i.LON 100 RS-485 PinDescription
26Shield Grounds
27RT−
28RT+
6789
FIGURE 3-4. DB-9 CONNECTOR PINS
TABLE 3-1. i.LON 100 SERVER DB-9 PIN
ASSIGNMENT
i.LON 100 DB-9
Description
(DTE) Pin
1NC (No connect)
2RxD (Receive Data)
3TxD (Transmit Data)
4NC (No connect)
5GND (Ground)
6NC (No connect)
7NC (No connect)
8NC (No connect)
9NC (No connect)
DB-9 ShellEarth Ground
RS-485 Serial Port
The i.LON 100 server includes one isolatedRS-485 multi-drop bus port implemented on termi-nals 26 through 28.
Connecting RS-485 to the ModBus
The 1301 genset control contains data that can beread using ModBus RTU protocol on a two-wireRS-485 master/slave multi-drop bus. In this ar-rangement, the remote device (PowerCommandiWatch100) is the master and the 1301 is theslave.
The 1301 is configured at a baud rate of 19,200, 8
data bits, even parity, and 1 stop bit.
For more information about ModBus RS-485 com-munications,refer to the ModBus Application Pro-tocol v1.1a and the ModBus Serial Line Imple-mentationGuide v1.0; both are available at
www.modbus.org
TABLE 3-3. i.LON 100 RS-485 PIN ASSIGNMENT
Hi (+)283
Lo (−)274
Shield261
.
i.LON 100
Pins
1301 TB2
Connector
3-3
TB1
(CUSTOMER
INPUTS)
S1 AWAKE/SLEEP ON/
OFF SWITCH
J13
CONNECTOR
J12
CONNECTOR
DS1 LED
STATUS
INDICATOR
STARTER
RELAY
(OPTIONAL)
TB2
CONNECTOR
(RS-485
COMMUNICATIONS)
J11
CONNECTOR
FUEL
SHUTOFF
RELAY
(OPTIONAL)
FIGURE 3-5. PCC1301 CONTROL BOARD WITH RS-485 COMMUNICATIONS PORT
TABLE 3-4. TB2 CONNECTIONS FOR RS-485 MODBUS COMMUNICATIONS
Connector PinSignal NameConnected To
TB2-1RETURNNetwork Power Supply Return
TB2-2BAT+Network Power Supply
TB2-3RS485 DATA A (+)Network Data A
TB2-4RS485 DATA B (−)Network Data B
TB2-5WAKE_UP_INPUTActive Low Wake-Up Signal
NOTE:Active Low Wake-Up signal (TB2-5) and Network Power Supply Return (TB2-1) can be tied
together. Communication cable shield may be connected to TB2−1. Cummins recommendsBelden 9729 cable for ModBus communications.
3-4
The RJ-11 Telephone Line Port
WARNING
phone modem should be used only with telephone circuits equipped with proper lightning
and transient protection circuitry. This minimizes the risk of shock or damage should lightning strike on or near a telephone circuit to
which the i.LON 100 Internet Server is con-nected.
This connector must be used with a suitable maleRJ-11 connector that is connected to a two-wirePOTS connection that is compatible with the V.90internal analog modem. The i.LON 100 serveranalog modem is not compatible with ISDN cir-cuits.
CAUTION
No. 26 AWG or larger telecommunication linecord.
The i.LON 100 Internet Server tele-
To reduce the risk of fire, use only
WARNING
The high-voltage terminal block
has a plastic cover protecting the screw terminals used to connect the high-voltage inputs.
This cover MUST be replaced after the power
wires are connected and before the power is
activated.
The 90−230VAC power mains connection is used
to power the i.LON 100 Internet Server. The i.LON100 server contains an auto-ranging, auto-settingmainspower supply. It is not necessary to adjustany jumpers or other settings when connectingmains voltage.
The high voltage connection is implemented onscrew terminals 1 (earth ground), 3 (Neutral), and4 (Line): screw terminal 2 (NC) is not used andshould remain unconnected. A solid earth groundvia terminal 1 connection is required for properESD and EMC performance of the i.LON 100 de-vice. Use the following order for installation.
High Voltage Mains Power
WARNING
server presents a shock hazard that can causesevere personal injury or death. Make sure theAC power mains are turned OFF before remov-ingthe cover, handling the mains wiring, orconnectingany mains cabling to the i.LON 100server device.
DO NOT under any circumstances operate thei.LON100 server device to mains voltages out-side of the range 90−230VAC, −10% to +30%,50/60Hz2.5Hz.
WARNING
connect earth ground first, then Neutral, thenLine.This minimizes the risk of shock or equip-ment damage should power inadvertently bepresent on Line.
CAUTION
battery is replaced by an incorrect type. Dispose of used batteries in accordance to the in-structions.
AC power within the i.LON 100
Whenconnecting a unit, always
There is a risk of explosion if the
1.Insert the earth ground;
2.Insert the neutral connection; and then
3.Insert the line connection.
DO NOT apply power to the i.LON 100 server untilyou have checked all wiring connections.
NOTE:CumminsPower Generation recommends
connecting the PowerCommand iWatch100 to a UPS so the unit does not lose pow-er during a utility failure or transition fromutility to a back-up source.
WARNING
The i.LON 100 server is not
equipped with a power disconnect device.
When the device is installed and mounted, the
installer must provide a means to safely remove power, such as a power switch or a circuit breaker.
FIGURE 3-6. I.LON 100 SERVER HIGH VOLTAGE
MAINS SCREW TERMINALS
3-5
TABLE 3-5. I.LON 100 SERVER AC POWER MAINS
CONNECTIONS
Screw
Terminal
Enclosure
Marking
Mains
Connection
1EEarth ground
2NCDo not connect
3NNeutral
TABLE 3-6. I.LON 100 SERVER LONWORKS
TP/FT-10 NETWORK CONNECTIONS
Screw
Terminal
Enclosure
Marking
LONWORKS
Network
Connection
17LON BTP/FT-10 twisted pair
18LON ATP/FT-10 twisted pair
4LLine
LonWorks Network
The i.LON 100 server is provided with a TP/FT-10free topology twisted pair LonWorks channel. ThePowerCommand iWatch 100 is a TP/FT-10 device.The TP/FT-10 free topology twisted pair interfaceis polarity−insensitive and requires connecting thetwisted pair to terminals 17 and 18 (see Figure3-7).
Wiring Diagrams
Figures 3-8 through 3-11 show the genset controlwiring to the PowerCommand iWatch 100.
FIGURE 3-7. I.LON 100 SERVER LONWORKS
TP/FT-10 FREE TOPOLOGY TWISTED PAIR
TERMINALS
3-6
DIGITAL INPUTS ARE
POLARITY SENSITIVE
IWATCH 100
MAX LOAD: 230 VAC, 10 AMPS OR 24 VDC, 10 AMPS
MIN LOAD: 5V, 5 MA
FIGURE 3-8. POWERCOMMAND iWATCH 100 WITH POWERCOMMAND 3100 CONTROL
DIGITAL INPUTS AREPOLARITY SENSITIVE
IWATCH 100
MAX LOAD: 230 VAC, 10 AMPS OR 24 VDC, 10 AMPSMIN LOAD: 5V, 5 MA
FIGURE 3-9. POWERCOMMAND iWATCH 100 WITH POWERCOMMAND 2100 CONTROL
3-7
DIGITAL INPUTS ARE
POLARITY SENSITIVE
IWATCH 100
MAX LOAD: 230 VAC, 10 AMPS OR 24 VDC, 10 AMPS
MIN LOAD: 5V, 5 MA
FIGURE 3-10. POWERCOMMAND iWATCH 100 WITH POWERCOMMAND 3200 CONTROL
DIGITAL INPUTS AREPOLARITY SENSITIVE
MAX LOAD: 230 VAC, 10 AMPS OR 24 VDC, 10 AMPSMIN LOAD: 5V, 5 MA
IWATCH 100
FIGURE 3-11. POWERCOMMAND iWATCH 100 WITH POWERCOMMAND 1.X, 2.X, 3.X CONTROL
3-8
4. Connecting the i.LON100e3 to the
Network and Commissioning the
PowerCommand iWatch 100
CONFIGURING A POWERCOMMAND
iWATCH 100
The following steps are necessary to configure aPowerCommand iWatcht 100:
•Creating a project folder and copying the
image.
•Updating project settings.
•Loading the i.LON 100 Image.
•Creating an xDriver RNI.
•Opening a copy of the template database.
•Commissioning the Devices.
•Browsing the PowerCommand iWatch 100.
CREATING A PROJECT FOLDER AND
COPYING THE IMAGE
It is important to maintain a record of projects andprojectsettings. The first step is to create a projectfolder where you can store a copy of the i.LONimage that you want to customize for the project.You should give the project folder a name that willallow you to easily associate the folder with theprojects.
jects\Project Name\. Using Windows Explorer,copy the required PowerCommand iWatch 100image from the CD into the folder you created.Thereare two images on the CD. One image is forthe 2100, 3100 and 3200 genset controls, and theother image is for the 13xx genset controls. Bothimages have the ability to display ATS and a DIMmodule.
UPDATING PROJECT SETTINGS
In order to edit project settings:
1.Use Windows Explorer to open the projectfolder you created above: (C:\PowerCom-mand iWatch 3 02 20 04\Projects\ProjectName\ ).
2.Open the Web folder followed by the “user”folder and “cpg” folder as shown below:
C:\Power.....\Projects\Project
Name\Image\Web\User\CPG\
3.Openthe config.xml file using Microsoft Word.To do this:
a.Right click on Config.xml.
b.Select Open With.
For example, you may create a folder called:C:\PowerCommand iWatch 3 02 20 04\Pro-
c.Choose Microsoft Office Word (see
Figure 4-1).
4-1
FIGURE 4-1. OPEN THE XML FILE
4.The word document will open (see Figure4-2).
NOTE:If the document does not open as shown in
Figure4-2, or if you do not have MicrosoftWord,the config.xml file can also be editedwith either NotePad or WordPad. If you arenot editing the file using one of these other
options,you must not alter the tag names.For example <site_code> is the beginningtag for the site_code field and</site_code> is the end tag of the field. Ifyou modify either the beginning or endtags,the config.xml file cannot be read cor-rectly.
FIGURE 4-2. READY TO EDIT CONFIG.XML FILE
4-2
5. Change the following settings in the config.xml file as required for the customer:
• Site_Code. (32 characters, case sensi-
tive). This code can be found on the CD
that came with your PowerCommand
iWatch 100. If you do not enter this code,
you will have to type in the code each time
you view the web pages.
•Site_Name. This is the name that appears
on the oneline diagram page. If you havemultiple sites, you may wish to rename thisto the name of the site you are viewing. Youmay have up to 32 characters.
•Number_of_Gensets. This can be
changed from one to four. It is possible tohave a PowerCommand iWatch 100 dis-play more than four gensets. However,itisa custom configuration and requires a fac-tory configured unit.
•Number_of_ATS. This has the range 0 –
4. It is possible to have a PowerCommandiWatch 100 display more than four ATS.However, it is a custom configuration andrequires a factory configured unit.
•Digital_IO. This option allows you to use
digital inputs and outputs that are on thePowerCommand iWatch 100 or a Digital in-put output module. This field can either beyes or no. The PowerCommand iWatch100 can communicate with one DIM.
•Metric. This field is for the display units.
There are three options here: yes, no, andask. Select Yes to display metric units, Noto display imperial units, and Ask to ask theuser which units they want when they firstaccess the web pages.
•Gensetand ATSNames. Each device has
a label field that can be changed. You canuse 16 characters for the genset name,and 20 characters for the ATS name.
6. Save and close the config.xml file. If you are
using Microsoft Word to edit the file, select
Continue when prompted that the file is not a
word document.
If you have Digital I/O, you may also modify the xml
file to rename the inputs/outputs, change indicator
colors, and change the text on the relay labels from
their default (activate/deactivate). The file for this
is called digitalIO.xml. It is also located in C:\Pow-
er.....\Projects\Project
Name\Image\Web\User\CPG\.
As you did with the Config.xml, right click on file
name DigitalIO.xml in Windows Explorer, and
open itwith Microsoft Word in order to make modi-fications.
Each point has the following configurable fields:
•Label. This field is the description of the
point that appears on the digital I/O pageand the digital control page. This field willdisplay 21 characters.
•led_off. This is the LED image that is dis-
played when the point is in the off state.The default value is “../../images/CPG/LED_Grey.gif”. This should only bechanged if you wish to change the state ofthe point to active off.Available options arelisted in a later paragraph, “LED Images”.
•led_on. This is the LED image that is dis-
played when the point is in the on state.The default value is “../../images/CPG/LED_RED.gif.” Available options are listedin a later paragraph, “LED Images”.
•relay_off. This is the button image that is
displayed on the control page when therelay is off.There is only a value in this fieldif the point is an output. The default valuefor outputs is “../../images/CPG/Buttons/Small/Activate.gif”.
•relay_on. This is the button image that is
displayed on the control page when therelay ison. There is only a value in this fieldif the point is an output. The default valuefor outputs is “../../images/CPG/Buttons/Small/Deactivate.gif”.
•nv_in. This field should not be changed. If
it is changed, the point may not function
correctly. This is the network variable that
is used for displaying the state of an input
or output network variable.
• nv_out. This field should not be changed.
If it is changed, the point may not function
correctly. This is the network variable that
is used for control of the output.
4-3
LED Images:
The following images can be used for LEDs. The
color of the LED follows LED_ in the file name. If
_Flash follows the color, the LED will flash at
approximately 1 Hz:
The following images can be used for the relaycontrol buttons. The name of the gif file is the textthatappears on a blue button. Other images couldbe used as long as they are 110 x 31 pixels andhave been placed in the \web\images\CPG\But-tons\Small\ folder on the PowerCommand iWatch
Save and close the DigitalIO.xml file. If you are us-ing Microsoft Word to edit the file, select Continuewhen prompted that the file is not a Word docu-ment.
1. Connect the i.LON 100 to your PC using a
DB-9 null modem cable between the PC’s
COM port and the i.LON 100’s console port. (If
you have just applied power to the iLon100, it
takes two minutes to boot−up.)
2. Connect the i.LON 100 to your PC using an
Ethernet patch cable or Ethernet crossover
cable.From your PC’s Ethernet Port, connectthe cable directly to the i.LON 100’s Ethernetport.(This will keep your laptop and the i.LON100 isolated from the customer’sLAN/WAN-whileconfiguring it.) Be sure the LAN “link”light on the iLon is illuminated.
3.Format the i.LON 100.
4.FTP the image.
Formatting the i.LON 100
Oncethe i.LON 100 is connected to the PC, openHyperTerminal and connect to the i.LON 100. Todo this:
1.Click on Start³All Programs³Accesso-ries³Communication³HyperTerminal
2.If asked to make HyperTerminal your defaulttelnet program, select No.
LOADING THE I.LON 100 IMAGE
The following steps are required to prepare thei.LON 100 and load the PowerCommand iWatch100 image.
4-4
3. Name the HyperTerminal connection iWatch.
(see Figure 4-3). In that way you can open it
again without having to remember your settings.
6. Assign the following communications port settings (see Figure 4-5):
Bits per second= 9600
4. Once you have named the connection, click
OK.
5.The HyperTerminal displays a list of availableCOM ports for your computer (see Figure4-4). Select the serial communication port towhich you connected the i.LON 100, then clickOK.
Data Bits = 8
Parity = No Parity
Stop Bit = 1
Flow Control, NONE.
7.Click OK to continue.
8.You should now be connected to the i.LON100 console. If the i.LON 100 has finishedboot up, press Enter.
9.The i.LON 100 prompt should appear:(iLon100>). If nothing appears, check yourconnections and settings. If you see other in-formation onthe screen, wait for the i.LON100to finish booting.
FIGURE 4-3. NEW CONNECTION DESCRIPTION
FIGURE 4-4. PORT CONNECTION
FIGURE 4-5. PORT SETTINGS
4-5
The i.LON 100 needs to be formatted before send-
ing it an image. To format:
1. Type Format at the HyperTerminal prompt
(see Figure 4-6 ), and then press Enter.
After formatting the i.LON 100, it will go into the
BOOTROM mode. In this mode, you can only reboot, set the IP Address, subnet mask, and transfer files. Other operations are not permitted.
1. Verify the IP Address. The IP address will be
displayed when the i.LON 100 finishes rebooting (see Figure 4-7).
2.Answer“y” and press Enter when asked if youwant to proceed with the format.
FIGURE 4-6. FORMATTING THE I.LON 100
2.You can also type show, and press Enter tosee the information shown in Figure 4-7.
FIGURE 4-7. I.LON 100 IN THE BOOTROM MODE AFTER FORMATTING
4-6
NOTE: Figure 4-7 shows you what IP address is
assigned to your iLon and other information. Every iLon100 comes from the
factory with the IP address 192.168.1.222
assigned.
NOTE: Leave HyperTerminal running until the
project is completely finished; it is a veryuseful tool. Youcan minimize the window ifyou need to use other applications.
3.Set your computer IP address to 192.168.1.25with a subnet mask of 255.255.255.0.
Setting a Static IP Address on yourComputer
1. On the desktop of your computer, right click on
My Network Places and select Properties. A
window is displayed (see Figure 4-8).
NOTE: Before you can proceed, your PC’s Ether-
net port must be connected to another live
Ethernet port on another piece of equipment in order to dynamically change or set
a static IP address on your PC. In this caseyou should be connected directly to thei.LON 100 using either a patch or cross-over cable. The i.LON 100 will automati-cally reconfigure it’s port to accept eithertype ofcable. If you are not connected to alive Ethernet port, you will be required toreboot your PC before the changes takeplace (see Figure 4-8). If you are con-nected to a live port, the Status columnshould show “Connected”.
You can set a static IP address on your computerby using the following steps:
FIGURE 4-8. NETWORK CONNECTIONS PROPERTIES WINDOW
2.Select your wired connection, right click, andselect Properties.
4-7
3. A window is displayed (see Figure 4-9).Scroll
down to “Internet Protocol (TCP/IP)”, select it,
and click Properties.
4. Click the Use the following IP address radio
button.
5.Fill in the IP address and subnet mask asshown in Figure 4-10.
You need to know what subnet you require before
you can assign one to your computer. To connect
to an i.LON 100 right out of the box, you need the
192.168.1 subnet.
The example in Figure 4-10 assigns .25 to this PC.
You may use numbers between 25 and 253. You
may not use an address already assigned to
another device on the same subnet. Therefore,you may not use .222, because it is already as-signed to the iLon.
6.Click OK.
7.ClickClose at the next window. WXP maytake some time to complete this process.
FIGURE 4-9. LOCAL AREA CONNECTION
PROPERTIES WINDOW
FIGURE 4-10. INTERNET PROTOCOL
PROPERTIES
4-8
You now have a static address assigned to your
computer. Make sure to repeat this procedure
again when you are done, and select Obtain an IPaddress automatically, or you may have trouble
connecting to your company’s LAN.
Ping Test
To ping a device on the Ethernet, follow these in-structions:
1.Click Start³Run.
2. Enter cmd as shown in the Run window. A
command prompt window opens (see Figure
4-11).
FIGURE 4-11. COMMAND PROMPT WINDOW
4-9
3. Try to ping a device on your subnet
(192.168.1.x). Type ping 192.168.1.222, and
press Enter (see Figure 4-12). If the device is
FIGURE 4-12. PINGING A DEVICE ON THE SUBNET
alive, you should get four replies, proving the
ping test is successful (see Figure 4-13).
FIGURE 4-13. PING TEST SUCCESSFUL
4-10
FTP Transfer
Now you can open the Internet Browser (Internet
Explorer), and type the following command to
open the FTP site: ftp://192.168.1.222. The
iLon100 will require you to log−in. The default ID is
ilon. The default PW is ilon (see Figure 4-14).
FIGURE 4-14. FTP LOG-IN
4-11
After opening the site, you should see only three
folders (see Figure 4-15). Make sure you have
closed all xml files before you initiate the FTP
transfer.
1. Copy the contents of the PowerCommand
iWatch100 project folder and paste to the FTP
site.
NOTE: It important to copy only the contents of the
image folder when you FTP your project
folder files to the PowerCommand iWatch
100.
FIGURE 4-15. FTP SITE
4-12
2. You should be asked if you want to overwrite
existing files. Choose yes to all. Although a
long transfer time may be indicated, it should
take less than 15 minutes.
CREATING AN XDRIVER REMOTE
NETWORK INTERFACE
The i.LON 100 can be used as a remote network
interface (RNI). The RNI takes the place of a
PCC10 network interface. To create an xDriver Remote Network Interface , start by opening “LonWorks Interfaces” in the control panel.
1.Click Start, then click on Control Panel.
2.Double click on LonWorks Interface (seeFigure 4-16).
3.When copying is complete, go back to the Hy-perTerminal prompt and type reboot.
4.Choose “y” to confirm you want to reboot thei.LON100. This should take approximatelytwo minutes.
5.After the i.LON100 is finished booting up, itsaddress changes to 192.168.0.5. This ad-dress is defined in the image files created byCummins. You will need to set the IP addresswith the customer’s requirements using thehyperterminal connection and the ipaddresscommand.You must also change the staticaddress ofyour computer to match the subnet(xxx.xxx.xxx.25)that you eventually assign tothei.Lon100.
3.When the “LonWorks Interfaces” page opens,make sure the RNI tab is selected.
FIGURE 4-16. LONWORKS INTERFACE ICON
4-13
4. Make sure “Default” is selected (see Figure
4-17).
5. Click Add to install a new RNI.
6. Name the Network Interface iWatch, and click
Next (see Figure 4-18).
7.On the “Network Interface Type” window,choose Other, and click Next (see Figure4-19).
FIGURE 4-17. LONWORKS INTERFACES
FIGURE 4-18. NAMING THE NETWORK INTERFACE
FIGURE 4-19. NETWORK INTERFACE TYPE
4-14
8. Enter the PowerCommand iWatch 100 IP Address, 192.168.0.5, or the customer defined
address previously assigned to the PowerCommand iWatch 100 in HyperTerminal, then
click Finish (see Figure 4-20).
9.Afterfinishing the set−up of a new RNI, selectthex.default.iWatch name and click the Testbutton. Then click Start. Upon successfulcompletion of this test, you will see “xDriverdiagnostics test passed” in the bottom of thedialog box.
NOTE: If the test did not pass:
• The address you assigned to the xDriver
does not match the address assigned to
the PowerCommand iWatch 100
• A problem exists with the Ethernet cable
connection between your computer and
the PowerCommand iWatch 100
•The PowerCommand iWatch 100 is not
powered
•The IP address subnet setting on your
computer is not the same as the Power-CommandiWatch 100 (xxx.xxx.xxx)
FIGURE 4-20. ENTERING THE IP ADDRESS
4-15
OPENING A COPY OF THE TEMPLATE
DATABASES
Three template databases have been included on
the PowerCommand iWatch 100 CD:
• IW100E3A2100, 2100 Gensets and OTPC ATS
2. Open LonMaker for Windows from the Start
Menu by choosing Start³Programs³Lon-
Maker for Windows, or you can use the shortcut icon on the desktop.
3. Click the Restore button, and browse to the
template databases.
•IW100E3A3100, 3100 Gensets and OTPC ATS
•IW100E3A3200, 3200 Gensets and OTPC ATS
NOTE:If you have different combinations, select
the template that best fits your applicationand customize it.
For first time use, restore the databases from thebackups.
1.Copy the database backups to yourC:\LM\backup\ folder.
4.Follow the prompts to restore the database.
NOTE:You will not need to open the database or
re−commissiondevices, so answer Nowhen prompted to do so.
5.Once you have restored the template data-bases,select the template database you wantto use.
6.Select Open Copy.
7.Whenasked if you want to continue, click Yes(see Figure 4-21).
FIGURE 4-21. OPENING A TEMPLATE DATABASE
4-16
8. After choosing to continue, enter a network
name for this project. Give your database a
name that will allow you to associate the network with the project (see Figure 4-22). Click
Next.
FIGURE 4-22. RENAMING YOUR NETWORK
9.When the box shown in Figure 4-23 appears,make sure that Network Attached is un-
checked. If checked, deselect it, then click
Next.
FIGURE 4-23. NETWORK ATTACHED NOT
SELECTED
10.ClickNext. The box in Figure 4-24appears.
11.Leave the “Domain Length” at the default val-ue of 1, and the Use randomly generated
domain ID checked. Then click Finish.
FIGURE 4-24. DOMAIN DEFINITION
4-17
Once the database is opened and saved, you can
connect to the network interface as follows:
1. Select the LonMaker Menu and then Network
FIGURE 4-25. CONNECTING TO THE NETWORK INTERFACE
Properties (see Figure 4-25.)
2. On the Network Properties box, select the
“Network Interface” tab (see Figure 4-26).
4-18
3. Check Network Attached.
NOTE: When you click OK, you may need to up-
grade your network interface.
4. Choose x.Default.iWatch from the dropdown
list of interfaces, and click OK.
5. If you see the message shown in Figure 4-27,
select Yes.
FIGURE 4-26. NETWORK INTERFACE
FIGURE 4-27. NETWORK INTERFACE UPGRADE
4-19
6. Reopen the Network Properties box, and select the “Onnet /Offnet” tab (see Figure 4-28).
7. Select Onnet and click OK. The Network In-
FIGURE 4-28. SELECTING ONNET
terface should change from yellow to green
(see Figure 4-29).
FIGURE 4-29. NETWORK INTERFACE CHANGES FROM YELLOW TO GREEN
4-20
COMMISSIONING THE DEVICES
To commission devices, you first start with the
i.LON 100. The i.LON100 is commissioned using
the following procedure:
1. Right click on the PowerCommand iWatch
100 device, and select Commission from the
menu (see Figure 4-30).
2. When you choose “Commission”, options will
appear on the Commission Device Wizard
box (see Figure 4-31). Choose Online for a
“State.”
3. The “Source of Configuration Property Values” is not important. Click Next.
FIGURE 4-30. COMMISSIONING THE I.LON 100
FIGURE 4-31. SELECTING ONLINE FOR STATE
4-21
4. Select Service Pin as the device identification
method, then click Finish (see Figure 4-32).
FIGURE 4-32. SELECTION OF DEVICE
IDENTIFICATION
7. Repeat the commissioning process for all other devices present.
8. Reset all devices either through LonMaker or
the device’s reset pin.
9. Save and close LonMaker for Windows.
Set the PowerCommand iWatch 100 IPAddress.
To set the PowerCommand iWatch IP address,use the following procedure:
1.Switch to the HyperTerminal session.
2.Assign the customer’s IPaddress to the Pow-erCommandiWatch 100 using the followingcommands:
Ipaddress xxx.xxx.xxx.xxx
Subnet xxx.xxx.xxx.xxx
Gateway xxx.xxx.xxx.xxx
5.When prompted, press the service pin on thei.LON100.
6.Oncethe commissioning process is complete,thei.LON100 should turn green if it was suc-cessful.
DNSprimary xxx.xxx.xxx.xxx
NOTE:All commands must be followed by the
customer’s specified settings. The DNSaddress is required if you need to send e-mail via a named e-mail server.
4-22
THE CUSTOMER’S CONFIGURATION
The following procedure allows you to connect the
PowerCommand iWatch 100 to the Customer’s
network. If you are going to use the PC that you
used to configure the PowerCommand iWatch
100, you will need to connect your PC to the customer’s network and set your PC to obtain an IPaddress automatically.
1. Open the internet browser (Explorer).
2. Type the following in the address bar:
http://xxx.xxx.xxx.xxx
address you assigned the PowerCommand
iWatch 100.)
3. When the new page opens, choose Service,which will allow you to enter the customer’sconfigurationrequirements (see Figure 4-33).
. (xxx.xxx.xxx.xxx is the
FIGURE 4-33. SERVICE OPTION FOR CUSTOMER CONFIGURATION REQUIREMENTS
4-23
The Service Webpages
a. Network− LAN/WAN
The following additional network LAN/WAN setup
procedure allows you to verify:
• IP Address, Subnet Mask and Gateway
• DNS server IP Address
•SMTP server
•E-mail account information
•Modem setup
1.From the web page, choose Service (seeFigure 4-33).
2.You must long−in to the PowerCommandiWatch100. The default ID is ilon, and the de-fault PW is ilon.
3.Under setup choose:
b. On the tree in the left hand pane under
LAN, select “mail.company.com” (see
Figure 4-34).
4. Provide the name of the customer’s mail server in “Server Property Value” (see Figure
4-34).
5.On the tree in the left hand pane of the page,click Email (Default) and provide the requiredinformation. Be sure to contact the customer’sIT department to get the correct informationfor Server Email Address and User Name andPassword, if required.
6.When you are finished, click Submit for allchanges to take effect. The requested infor-mation is displayed (see Figure 4-35).
FIGURE 4-34. LAN/WAN NETWORK SETUP
4-24
FIGURE 4-35. E-MAIL DEFAULT OPTION
4-25
After the changes are made, you need to verify that
the information is correct. To do this:
It is possible that one of the following functions
might go wrong:
1. Click Setup³Verify. The screen in Figure
4-36 appears.
2. At “Send test email to,” fill in your e-mail address or someone else’s to verify that the
SMTP server connection is working correctly.
3.You only need to check the e-mail and LANconnections.Deselect the other choices (seeFigure 4-36).
4.Click Start Tests.
• No DNS server address entered
• Unable to access the DNS server
• Unable to access the mail server
•Sender e-mail address invalid
NOTE:The PowerCommand iWatch 100 must be
connected tothe customer’s LAN/WAN forthese tests to work.
FIGURE 4-36. E-MAIL AND LAN TEST CONNECTIONS
4-26
DIAL-UP CONNECTION
An PowerCommand iWatch 100 webserver installation can include an optional built-in modem that
provides a direct dial-in connection to the PowerCommand iWatch 100’s web pages. This section
provides information on setting up configuration
parameters for a direct dial-in to the PowerCom-mand iWatch 100.
NOTE:The PowerCommand iWatch 100 internal
analog modem is not compatible withISDN circuits.
To set up the PowerCommand iWatch 100 for di-rect dial-in to the web pages,
1.OpenInternet Explorer and enter the followingURL:
3. Log−in and enter the user name and pass-
word (see Figure 4-37).
Username: ilon
Password: ilon
http://xxx.xxx.xxx.xxx (IP address of the
PowerCommand iWatch 100)
2.Click on Service.
FIGURE 4-37. USERNAME AND PASSWORD
4.Place the cursor over Setup and select Mo-dem from the drop-down list .
4-27
5. For the modem type, select Internal Analog.
(see Figure 4-38).
b. Select Set up my connection manually.
c. Select Connect using a dial up modem.
6. Click on the Submit button.
7. On your PC, open the Start Connect To program. Click on Show all connections and
select Create a new connection from the lefthand side.
8.Follow the Wizard to set up the new connec-tion.
a.Select Connect to the Internet.
d. ISP Name = ilon
e. Phone number = the number of the land
line your i.LON 100 is connected to
f. Username = ilon (This is setup in the built-
in web pages as shown above)
g.Password =ilon (This is set up in the built-
in web pages as shown above)
h.Click on Finish.
FIGURE 4-38. MODEM SETUP
4-28
5. PowerCommand iWatch 100 Web Pages
INTRODUCTION
This section describes and shows the flow andfunctions of the PowerCommand iWatcht 100web pages used for monitoring and controlling thenetwork devices.
IMPORTANT POWERCOMMAND iWATCH
100 WEB PAGE INFORMATION
Units ofMeasurements−You can select either a
Metric or Imperial System of measurement. If youdid not configure the units of measurementsthroughthe XML file, then you will be prompted forthe units at the launching of this page.
FIGURE 5-1. SELECTING UNITS OF MEASUREMENT
5-1
To view the PowerCommand iWatch 100’s web
pages:
1. Open Internet Explorer.
3. Choose Standard on the screen. See figure
5-2.
2. Type in the IP address of the PowerCommand
iWatch 100.
http://xxx.xxx.xxx.xxx
NOTE:“xxx.xxx.xxx.xxx”refers to the address
assigned to the PowerCommandiWatch 100 by the installer.
4. Save this link as one of your Internet Favorites
for quick access in the future.
Figure 5-3 shows the configuration of one gensetand one transfer switch configured through theXML file as described in Chapter 4.
FIGURE 5-2. WEBPAGE ACCESS
FIGURE 5-3. ONELINE DIAGRAM WEB PAGE
5-2
GENSET WEB PAGES
There is a Generator Summary page available for
each of the four separate generators. Each generator summary page includes a link to its Annunciator page. This means there is a total of eight web
pages that can be used to monitor up to four generators. They all can be used to monitor different
variables and display the various states of the gen-set.
Genset AC Data and Engine Data
FIGURE 5-5. GENSET ANNUNCIATOR DATA WEB
PAGE
To view the Generator Summary page from theOneLine web page, select View GeneratorSummary, or click on the Summary button abovethe generator graphic. The Generator Summarypage displays Genset AC Data and Engine Data(see Figure 5-4).
FIGURE 5-4. GENSET AC AND ENGINE DATA
PAGE
Genset Annunciator Data
To view the Generator Annunciator web page fromtheGenerator Summary web page, click on theAnnunciator button above the generator graphic.The Genset Virtual Annunciator web page (seeFigure 5-5) displays active NFPA110 and the ex-tendedset of generator alarms. This web page dis-plays more information than a standard annuncia-tor displays. For information on alarm notification,see Section 6.
Digital I/O Web Page
To view the Digital I/O web page from the OneLineweb page, select View Digital I/O.
The Digital I/O web page shows the status of boththe PowerCommand iWatch 100’s on−board in-puts and outputs, and the DIM’s inputs and out-puts. See figure 5-6.
FIGURE 5-6. DIGITAL I/O WEB PAGE
ATS WEB PAGES
There is an ATS summary page available for eachof the four separate transfer switches. Each ATSsummary page includes a link to its Annunciatorpage.This amounts to a total of eight web pagesthat can be used to monitor up to four transferswitches.They all provide the functionality of mon-itoring different variables and displaying the vari-ous states of the ATS(s).
ATS AC Data
To view the ATSSummary web page from the One-
Line web page, select View ATS Summary, or
click on the Summary button above the ATS
graphic.
This web page displays the values for both AC
sources and the load side of the transfer switch.
5-3
NOTE: A level 2 OTPC switch control with the load
monitoring package installed is required to
provide all of the data shown in Figure 5-7.
If the load monitoring package is not
installed, the load side data will show
65,535 for voltages, and 32,767 for currents.
ATS Annunciator
To view the ATS Annunciator web page from the
ATS Summary web page, click on the Annuncia-tor button above the ATS graphic.
The ATS Virtual Annunciator web page displays
active NFPA110 and the extended set of ATS
alarms. This web page displays more informationthan astandard annunciator displays. For informa-tion on alarm notification, see Section 6.
FIGURE 5-7. ATS SOURCE AND LOAD DATA
FIGURE 5-8. ATS ANNUNCIATOR PAGE
5-4
CONTROLS WEB PAGE
The Controls web page is a secure web page
where control functions for the genset, ATS, DIM,
and PowerCommand iWatch 100 on-board outputs are found.
The Controls web page
Figure 5-9) allows the user to issue remote start and
reset commands for the gensets, and test and faultreset commands for the transfer switches.
for the gensets and ATS (see
ther logged out using the Log-off button at
the far upper right of the webpage, or all Internet Explorer sessions are closed. Cum-
mins Power Generation recommends
always using the Log-off button to ensure that control functions are protected by a secure log-on procedure.
Fromthe main page, select Control Genset &ATS, or Control Control (for the DIM and Power-CommandiWatch 100 on-board relays).
The Controls web page for the DIM and Power-CommandiWatch 100’s on-board outputs (seeFigure 5-10)allows the user to activate the DIM re-lays and the PowerCommand iWatch 100 on−board relays.
To access the Control function pages, the user willbe required to log-in to the PowerCommandiWatch 100. See Section 7 for instructions on howto make changes to the default log-in credentials.
NOTE:The PC that logged into the PowerCom-
mand iWatch 100 stays logged in until ei-
NOTE:The 1301 control currently does not sup-
port fault reset commands through theModBus registers.
NOTE:Any command issued to the genset, ATS,
or DIM via the PowerCommand iWatchControl web page will need to be deacti-vated from the PowerCommand iWatchControl web page interface. Commandsturningfunctions on will be on continuouslyuntil turned off through the Control webpage. These commands do not deactivatewhen the web page is closed.
FIGURE 5-9. CONTROLS WEB PAGE
5-5
FIGURE 5-10. RELAY OUTPUTS
5-6
ALARM SUMMARY PAGE
The Alarm Summary page is used to acknowledge
and clear alarms. To acknowledge an alarm, check
the Ack box and click on Submit. All alarms have
an acknowledgment-required default setting. If
you would like to change the default acknowledgeand clear alarm settings, refer to the previous sec-tion. For more information on Alarm Summary, re-fer to i.LON 100 Web Page User’sGuide.
The Alarm Summary web page is located in i.LON
100’s internal web pages. To view the Alarm Summary web page,
1. Open Internet Explorer.
2. Go to your PowerCommand iWatch 100’s IP
address.
3.Log in to the i.LON 100.
4.Place the cursor over View and select Alarm
Summary from the drop-down list.
FIGURE 5-11. ALARM SUMMARY
5-7
ALARM HISTORY WEBPAGE
The Alarm History web page is a versatile page for
viewing Alarm History. It defaults to show the history of one alarm, but can easily be set up to show the
last 50 alarms, date range of alarms, or the history
of one specific alarm. The page also allows the
user to keep track of the amount of memory the
alarm logs are using and allows for erasing someor all of these logs.
These logs can also be configured to be a circularfile. That is, once the user sets a certain memorylimit, the i.LON 100 sends an e-mail with the at-
tachment of the log(s) to the e-mail recipient and
starts a new log. For more information on this feature and Alarm History, refer to the i.LON 100 Web
Page User’s Guide.
To view the Alarm History web page,
1. Open Internet Explorer.
2.Type in your IP address.
3.Choose Standard. from the web page.
4.Place the cursor over Alarm and select Alarm
Summary from the drop-down list.
FIGURE 5-12. ALARM HISTORY
5-8
6. Alarm Generation and Notification
INTRODUCTION
The PowerCommand iWatcht 100 is pre-set withalarms for all four generators and all four transferswitches: communications failure, fault type, andfaultcode. If you are commissioning less than alleight ofthese devices, then you should disable thealarmsfor the devices that do not exist in your net-work project.
If you do not disable the alarms for non-existent de-vices, a communication alarm will be sent eachtime the PowerCommand iWatch 100 boots up,which could occur from a power failure. After thealarms for non-existent devices are disabled, youshould delete the alarm summary and history asthese alarms will have already been logged.
There are also 16 alarm inputs on the LonMakerproject.You may bind any SNVT switch output totheseinputs. You can then custom configure thesealarms in the PowerCommand iWatch 100.
Working with the alarm set-up does require patience, because the web pages that you access to
make changes take time to load.
NOTE:The SMTP setup must be completed for
alarms to be delivered. See page 4-24.
SENDING FAULT CODES AND TYPES VIA
E-MAIL
The PowerCommand iWatch 100 is pre-config-ured tosend fault codes and fault types through e-mail for all of the devices that are connected to thenetwork (except DIM and annunciator modules).
To send e-mails you must first configure your des-tination e-mail address and e-mail content as fol-lows:
1.Open the browser.
2.Open the PowerCommand iWatch 100 web-page.
3.Choose the Standard button (see Figure 6-1).
FIGURE 6-1. POWERCOMMAND iWATCH 100 WEB PAGE
6-1
4. From the main menu, choose Alarms³Email
(see Figure 6-2).
5. When the new window appears, click on
Email Alarm. The screen in Figure 6-3 appears.
Command iWatch 100. The following symbols
are also included by default in the subject
field:
%pd − data point description
%ua − data point value units
NOTE: Multiple e-mail addresses can be sepa-
rated by a semi-colon.
6.Enter the destination e-mail address where itsaysusername@company.com.
7.Modifythe Subject field if you need a more de-scriptive name for the site. Default is Power-
%va − data point value
NOTE:For a description of the symbols you can
add, click on Help at the top of the AlarmNotifier page (see Figure 6-5).
8.In the message field, configure what informa-tion you want to send in the e-mail.
FIGURE 6-2. SELECTING E-MAIL FROM MAIN MENU
FIGURE 6-3. ENTER DESTINATION E-MAIL ADDRESS
6-2
Cummins has pre-configured the alarm to send the
IP address for this PowerCommand iWatch 100
device in the alarm message. We have also preconfigured the text message instructing the e-mail
receiver to go to the PowerCommand iWatch 100
web pages for explanations of the alarms in the email. You may reconfigure this text string to suit
your customer’s needs.
To include specific pieces of information from thesite inthe e-mail, use the Variable substitution areaat the bottom of the dialog box. Choose whetheryou are adding this information to the subject lineor to the body of the e-mail.
You can refer to the Help page or the i.LON manualfora complete listing of data you can include in thee-mail.
9. After your e-mail configuration is complete,
click OK.
10. Click Submit at the top, left corner of the page.
To disable alarms for non−commissioned devices,use the following procedure:
1.Open the Service webpage (Figure 6-4).
2.Go to the Configure tab, and select Alarm No-
tifier.
FIGURE 6-4. SELECTING SERVICE BUTTON ROM WEB PAGE
6-3
3. The Alarm Notifier Dialog Box appears (see
Figure 6-5).
4. There are two input arrows on the screen.
Click on Input Values.
8. If an alarm appears in the Alarm Summary, delete the sumlog1.dat and histlog0.dat files
from the PowerCommand iWatch 100. These
files are located in the alarm log folder on the
PowerCommand iWatch 100.
5. The right-hand pane opens and displays all of
the pre-defined alarms. At the top of that pane,select the Show Advanced properties radiobutton.
6.Clickthe box in the Disabled column next to analarm to disable it.
7.When finished with making modifications, se-lect Submit in the upper left corner of thescreen.
ALARM ACKNOWLEDGMENT
By default all alarms require an acknowledgement.If you desire to change that default:
1.Navigate to the Alarm Log Data Point web-page (see Figure 6-5).
2.Removethe check for an alarm in the Ac-knowledgment Required column.
3.Select Submit in the upper left corner of thescreen.
FIGURE 6-5. ALARM NOTIFIER DIALOG BOX
6-4
FIGURE 6-6. ALARM NOTIFIER LOG DATA POINTS
CUSTOMIZING THE 16 USER DEFINED
DIGITAL ALARMS
There are 16 pre-defined digital alarm points thatyou may assign to network variable outputs. SeeFigure 6-7. You use these pre-defined digitalalarms by binding a digital nvo from a network de-vice toone of the digital alarm points on the Power-Command iWatch 100 (nvi) and then renaming it.
Inthe example below, DIM Input 1 is bound toAlarm Point 1. In the i.LON config, this alarm maybe named appropriately for the point wired to theDIM input.
6-5
FIGURE 6-7. 16 DIGITAL ALARM POINTS
To rename alarm points, use the following procedure:
1. Open the internet browser, then the PowerCommand iWatch 100 web page.
4. On the “Configure Data Points” screen, click
on the left hand side (+ sign) next to the i.LON
100 (see Figure 6-9).
2. Select Service (see Figure 6-4) to open the
Data Point Selection screen (see Figure 6-8).
3.From the main menu, choose Configure³Data Points.
5. Next click on the (+ sign) next to NVL.
6.Then click on the (+ sign) next to dynamic.This page loads slowly.
FIGURE 6-8. DATA POINT SELECTION
FIGURE 6-9. AVAILABLE ALARMS
6-6
7. A tree will be populated with the names of
available alarms. Scroll down until you see
customer alarms 1 through 16 (see Figure
6-10).
8. Choose the customer alarm, and rename the
Alias name to a name that describes thealarm.
9. Choose the customer alarm, and rename the
description to a name that describes the
alarm.
10. Save the changes by clicking Submit.
NOTE: You can modify multiple alarms before you
click Submit.
For another reference on how to configure alarms,please refer to the i.LON 100 User’sGuide.
FIGURE 6-10. SCROLL DOWN THE TREE
6-7
ALARM NOTIFICATION VIA A DIAL-UP
PROVIDER
To enable the PowerCommand iWatch 100 to connect to a dial-up provider, use the following procedure. From the Service page:
1.Move your mouse over Network, and clickLAN/WAN.
3. In the right hand pane, name the new connection.
4. Enter the necessary phone number, user id,
and password for connection to your ISP (see
Figure 6-11).
5. Right click on the new connection just added
in the left hand pane, and select Add Server.
6.Type in the IP Address or name of your SMTPServer (see Figure 6-12).
2.In the left hand pane, right click on the i.LON100 at the top of the tree, and select Add Con-
nection.
FIGURE 6-11. NEW CONNECTION
7.In the left hand pane, right click on the newSMTP server you added, and select Add Ser-
vice.
FIGURE 6-12. NEW SMTP SERVER
6-8
8. When the Add Service menu is displayed, select Email (SMTP). Click on OK (see Figure
6-13).
ARCHIVING /CAPTURING ALARM LOG
DATA
9. Beneath your SMTP server icon is an Email
(Default) icon. Click on it and enter your
source e-mail address, user name, and password.
10.Click on the Submit button to save this infor-mation to the PowerCommand iWatch 100.
E-mailsthrough modem are sent just like the LANconfiguration.
FIGURE 6-13. SERVICE PROVIDER
The PowerCommand iWatch 100 stores its log
data in a binary file. To copy this data to Excel, follow these steps:
1.Navigate to the log file you are interested in(Summary or History).
2.While viewing the data points, use yourmouse to highlight all of the data on the webpage you want to capture (hold down leftmousebutton and swipe mouse over the webpage).
3.With your mouse over one of the data points,right click, and select Copy.
4.Open Excel, click on cell A1, right click overcellA1, and select Paste.
You cannot adjust column width and row height.You can manipulate the data to suit your needs.
6-9
This Page Intentionally Left Blank
6-10
7. User Names and Passwords
It is possible to setup different user names and
passwords by using iLON100 Web Security.
The PowerCommand iWatcht 100 comes withtwo levels of security as the default. Default doesnotrequire a log-in in order to view data webpages. However, log-in is required for access tocontrolfunction web pages. The username userand the password user are required for access tothe control functions. And username ilon and thepasswordilonare required to change configura-tion pages including alarm notification settings.
There isanother security file included on the Pow-erCommand iWatch 100 CD. If loaded, it requireslogging in to view the data web pages. The user-nameguest and the password guest allow view-ing PowerCommand iWatch 100 web pages only.Usernameuser and password user are requiredfor access to the control functions. Username ilonand password ilon are required for access to con-figuration pages.
NOTE:The PC that logged into the PowerCom-
mand iWatch 100 stays that way until ei-ther logged out by means of the Log Offbutton located at the right side of the webpage, or all Internet Explorer sessions areclosed. Cummins Power Generation
recommends always using the Log Offbutton to make sure that control func-tions are protected by a secure log-onprocedure.
in your project-specific folder in the Image folder. If
the project requires the higher level of security,
copy the webparams.dat file from the Security Options folder to your project’s Image folder.
ADDING NEW USERS/MODIFYING USER
PERMISSIONS
NOTE:Do not make modifications to the files in
the secuity options folder. Modify the secu-ritysettings in your customer specific proj-ect folder.
Cummins Power Generation suggests that youlimit modifications of these files to adding and de-leting users, and adding and moving users be-tween already defined groups. Directions beyondthis point are not provided in this manual.
When you create the project folder, the “no log-infor viewing” web pages is loaded into the Power-CommandiWatch 100 by default. The file wherethe security settings are located is called webpa-rams.dat. Itislocated at the root level of the Power-CommandiWatch 100’s directory structure.
Modifications can be made directly to this file, orthe restricted access security file can be loadedand modified also. The restricted access file is lo-cated in the Security Options folder that is copiedto your computer when you copy the PowerCom-mand iWatch 100’s CD contents toyour PC for thefirsttime: C:\PowerCommandiWatch 3 02 2004\Security Options.
Administrative level log-on for setup and configu-ration is gained by username ilon and passwordilon.This allows complete access to the Power-Command iWatch 100.
Choose which security file you want to load into thePowerCommandiWatch 100. If you want to usethe lower level of security, you already have the file
NOTE:Make sure you are using the copy of the
webparams.dat file in the project-specificfolder. The original files should never bemodified.
Open the webparams.dat file in the project folderusing this program: “ilon web server security pa-rameter”.
7-1
You can locate this file as follows:
1. Choose Start from your PC.
4. Choose “i.LON 100 Web Server Security and
Parameters”. See Figure 7-1.
5. Choose File³Open.
2. Open All Programs.
3. Choose Echelon i.LON 100.
6. Browse to the location of the webparam file.
7. Open it. See Figure 7-2.
FIGURE 7-1. WEB SERVER SECURITY AND PARAMETERS
FIGURE 7-2. OPEN WEBPARAMS FILE
7-2
The active tab is Users. You will see two users
listed at the bottom of the window, or three users if
you started with the restricted security file. See Figure 7-3. Create new entries in the following order:
a. Define new User if required
b. Assign user to a group
c. Save the webparams.dat file
d. Copy webparams.dat file back to the
PowerCommand iWatch 100 and reboot
FIGURE 7-3. USER’S TAB
Adding a User
To add a user:
1.Select the User’s tab from the i.LON 100 WebServer Parameters main dialog box. Theuser’s dialog box appears.
2.In the Username field, enter the name of theuser you are adding. The username must beunique and cannot include spaces or colons.The limit is 16 characters.
3.Enter the password in the password field. Itwill appear as asterisks.
4. Re-enter the password to confirm it.
5. Click Add User. at the right side of the dialog
box. Your new username appears in the window in the lower part of the dialog box.
Deleting a User
NOTE:The user must not be in any group in order
to be deleted from the list of users. See theprocedure for removing a user from agroup.
To delete a user:
1.Select the user’s name from the list in the win-dow.
2.ClickRemove at the right side of the dialogbox.
Assigning Users to a Group
To assign users to a group:
1.Select the Groups tab from the i.LON 100 Web
Server Parameters main dialog box. The
Groups dialog box appears.
2. In the Groups window, select the group to
which you want to assign users.
3. At the far right of the screen, select the user
you want from the list in the user’s window.
7-3
4. Click Add User at the right side of the dialog
box. The username appears in the group window.
Removing Users from a Group
To save the security profile:
1. From the i.LON 100 Web Server Parameters
main dialog box, select “Validate” from the file
menu.
To remove a user from a group:
1.Select the Groups tab from the i.LON 100 WebServer Parameters main dialog box. TheGroups dialog box appears.
2.In the Groups window,select the group fromwhich you want to remove a user.
3.Inthe middle window named Users in aGroup, select the user you want to removefrom the list.
4.ClickRemove.. The username disappearsfrom the list.
Saving the Webparam.dat File
NOTE:The WebParams.dat file should never be
editedwith a text editor.The i.LonWebPa-rams program performs consistencychecking on the web page security infor-mationthat you define. A text editor cannotperform the necessary checking.
2. At the very bottom left of the dialog box, review
the Status message. You need to see “All data
consistent” before you proceed.
3.If you see another message, fix the problem.Then run “Validate” again.
4.Select Save. from the file menu. The Savedialog box appears.
NOTE:Do not change the name of the file from
WebParams.dat. You should save this fileback tothe Image folder under the specificproject folder you are using.
5.Whenasked if you want to replace the existingfile, click Yes..
6.Copy this file back to your PowerCommandiWatch 100 using the FTP process. This filegoes at the root of the PowerCommandiWatch 100 directory structure (fttp://xxx.xxx.xxx.xxx).
7.Reboot the PowerCommand iWatch 100 forchanges to take effect.
7-4
Appendix A. Troubleshooting the Network
Connection
This appendix is a general troubleshooting guide for
connecting to the PowerCommand iWatcht 100with your computer.The operating system used forthis Appendix is Windows XP SP2.
This section is a help section only. Cumminstakes no responsibility for any problems thatmay arise in the use of the information of thissection. It isrecommended that you contact thecustomer’s IS/IT group before putting thePowerCommand iWatch 100 on the network.
If you are having troubles setting up the PowerCom-mand iWatch 100 to the network, it is best to start byconnecting it directly to your computer.
NOTE:For Cummins Employees using Power-
Swept machines, this will require adminrights.
Connecting the PowerCommand iWatch 100 di-rectly to your computer:
1.Plug an Ethernet patch cable from the Power-CommandiWatch 100 directly into your com-puter.
2.Launch a Command Prompt. Open StartRun, and type cmd.
3. Type the command “ipconfig” in the command
window. This will display the addresses thatyour computer has assigned to its Ethernetadapters.Your Local Area Connection musthave an address with a compatible subnet tothe PowerCommand iWatch 100 (the first threeoctetsmust match the PowerCommandiWatch100’s xxx.xxx.xxx). See Figure A-2.
The subnet mask of your Local Area Connec-tion and the PowerCommand iWatch 100 mustmatch if you are connecting directly from yourcomputer to the PowerCommand iWatch 100.
If your computer is not on the same subnet, orthesubnet mask does not match your Power-CommandiWatch 100, refer to the procedureunder Setting a Static Address on your Com-puter later in this section.
4.In the Command Prompt window, try toping thePowerCommandiWatch 100. Type “Pingxxx.xxx.xxx.xxx” asshown in Figure A-3. If youare successful, a reply will be returned indicat-ing the turn-around time of the request and re-ply.
Remember that the default address of the Power-Command iWatch 100 is 192.168.1.222. If you haveloaded a CPG image, or changed the IP addressperthe customer’s requirements, you will have toping the appropriate address. If the PowerCom-mandiWatch 100 is not found, the message “Re-quest timed out” is displayed (see Figure A-4).
FIGURE A-1. COMMAND PROMPT
If you successfully ping your i.LON, simply retry
to open the i.LON 100’s internal or custom web
pages using Internet Explorer 6.0 or higher. If
you are not successful, continue to the next
step.
Ifthe ping failed, make sure that your computer’sIPsettings are compatible with the PowerCommandiWatch 100 and that the PowerCommand iWatch100 is powered. Check to see that the PowerCom-mand iWatch 100 has a link light illuminated, whichindicates a good Ethernet patch cable connection.
Verify the i.LON 100’s IP address using HyperTerminal.
If you successfully ping your PowerCommand
iWatch 100, re-attempt to open its internal or custom web pages using Internet Explorer 6.0 or higher.
A-1
FIGURE A-2. ENTERING THE IPCONFIG COMMAND
FIGURE A-3. PINGING THE POWERCOMMAND iWATCH 100
FIGURE A-4. PING FAILURE MESSAGE
A-2
SETTING A STATIC ADDRESS ON YOUR
COMPUTER
To be able to dynamically change your IP address
or set a static address on your computer, the computer must be connected to a live Ethernet port. You
can verify this by looking at the Ethernet jack on the
back of your computer. With the patch cable con-nected to a live Ethernet port, there should be anLED illuminated at the jack, either green or amber.
2.Fromthe My Network Places window, selectView Network Connections from the NetworkTasks window on the left side of the screen (seeFigure A-6.
FIGURE A-5. OPENING “MY NETWORK PLACES”
FIGURE A-6. SELECTING “VIEW NETWORK CONNECTIONS”
A-3
3. From the Network Connections page, right
click on your Local Area Network connection,
and select Properties (see Figure A-7).
FIGURE A-7. LOCAL AREA NETWORK CONNECTION
The screen shown in Figure A-8 is displayed.
FIGURE A-8. LOCAL AREA CONNECTION PROPERTIES
A-4
CAUTION
The following steps will affect your
connection to your LAN. You must restore your
original settings to get back on your LAN after
you are done with the PowerCommand iWatch
100.
NOTE: For Cummins Employees using Pow-
er-Swept machines, the following
steps will require Admin rights on thecomputer in use.
4.From the Local Area Connection Propertieswindow,scroll down and select “Internet Proto-col (TCP/IP),” and click on Properties. Thewindow in Figure A-9 is displayed.
5.Select “Use the following IP address” and enterthe information shown in Figure A-10.
6.Select OK when finished. Then select Close inthe Local Area Connection Properties window.This will apply your changes.
NOTE:If you are asked to reboot your computer,
your computer is not currently connected toa live Ethernet jack. You may either reboot,or connect your computer to a live Ethernetjack and repeat this process.
FIGURE A-9. INTERNET PROTOCOL (TCP/IP)
PROPERTIES
7.Using the Command window, try to ping thePowerCommandiWatch 100 again. It shouldwork now.
8.If this doesn’t work, refer to the procedure in theConsole Connection portion of Section 4 anduse the Show command to confirm the addressand subnet mask of you PowerCommandiWatch 100.
9.Then adjust the appropriate settings above tocommunicate.
NOTE:Your subnet mask must match that of
thePowerCommand iWatch 100 forcommunication.
10.Rememberto restore you settings in the LocalArea Connection Properties when you are
done to obtain an IP address automatically.