Cummins Power Generation Onan PowerCommand Installation Instructions Manual

PowerCommand
Redistribution or publication of this document by any means, is strictly prohibited.
Serial Communications Kit
Installation Instructions
Powerful Solutions
Printed in U.S.A. 9000522B
1199

Table of Contents

Redistribution or publication of this document by any means, is strictly prohibited.
SECTION TITLE PAGE
SAFETY PRECAUTIONS ii, iii. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1 INTRODUCTION 1-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
About this Manual 1-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Special Tools Required 1-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2 PCC SERIAL COMMUNICATIONS 2-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Serial Communications 2-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3 HARDWARE INSTALLATION 3-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Overview 3-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Description 3-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Location 3-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
PCC Serial Communications Interface Board Installation 3-2. . . . . . . . . . . . . .
PowerCommand Cable Interface Installation 3-4. . . . . . . . . . . . . . . . . . . . . . . .
Wiring Connections 3-5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4 ALARM SETUP 4-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
About This Section 4-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
PCC Setup Menu for Alarm Reporting 4-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Installation Checkout 4-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
INCORRECT SERVICE OR REPLACEMENT OF PARTS CAN RESULT IN DEATH, SEVERE PERSONAL INJURY, AND/OR EQUIPMENT DAMAGE. SER­VICE PERSONNEL MUST BE QUALIFIED TO PERFORM ELECTRICAL AND/ OR MECHANICAL SERVICE.
i

Safety Precautions

Redistribution or publication of this document by any means, is strictly prohibited.
The PowerCommandSerial Communications In­terface Board can be used to remotely monitor and operate generator sets. All of the safety precautions for that equipment must observed. Refer to the Op­erator’s Manual for the equipment that is being re­motely monitored and controlled for important safe­ty precautions.
The following symbols, found throughout this manual, alert you to potentially dangerous condi­tions to the operator, service personnel, or the equipment.
This symbol warns of immediate hazards which will result in severe personal in­jury or death.
WARNING
safe practice which can result in severe person­al injury or death.
CAUTION
safe practice which can result in personal injury or product or property damage.
This symbol refers to a hazard or un-
This symbol refers to a hazard or un-
MOVING PARTS CAN CAUSE SEVERE PERSONAL INJURY OR DEATH
Keep your hands, clothing, and jewelry away from moving parts.
Before starting work on the generator set, dis-
connect battery charger from its AC source, then disconnect starting batteries, negative (-) cable first. This will prevent accidental starting.
Make sure that fasteners on the generator set
are secure. Tighten supports and clamps,
keep guards in position over fans, drive belts, etc.
Do not wear loose clothing or jewelry in the vi-
cinity of moving parts, or while working on elec­trical equipment. Loose clothing and jewelry can become caught in moving parts. Jewelry can short out electrical contacts and cause shock or burning.
If adjustment must be made while the unit is
running, use extreme caution around hot man­ifolds, moving parts, etc.
ELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL INJURY OR DEATH
Remove electric power before removing pro­tective shields or touching electrical equip­ment. Use rubber insulative mats placed on dry wood platforms over floors that are metal or concrete when around electrical equipment. Do not wear damp clothing (particularly wet shoes) or allow skin surface to be damp when handling electrical equipment.
Use extreme caution when working on electri-
cal components. High voltages can cause inju­ry or death. DO NOT tamper with interlocks.
Follow all applicable state and local electrical
codes. Have all electrical installations per­formed by a qualified licensed electrician. Tag and lock open switches to avoid accidental clo­sure.
Jewelry is a good conductor of electricity and
should be removed before working on electri­cal equipment.
ii
MEDIUM VOLTAGE GENERATOR SETS
Redistribution or publication of this document by any means, is strictly prohibited.
(601V to 15kV)
Medium voltage acts differently than low volt-
age. Special equipment and training are re­quired to work on or around medium voltage equipment. Operation and maintenance must be done only by persons trained and qualified to work on such devices. Improper use or pro­cedures will result in severe personal injury or death.
Do not work on energized equipment. Unau-
thorized personnel must not be permitted near energized equipment. Due to the nature of me­dium voltage electrical equipment, induced voltage can remain even after the equipment is disconnected from the power source. Plan the time for maintenance with authorized person­nel so that the equipment can be de-energized and safely grounded.
GENERAL SAFETY PRECAUTIONS
PowerCommand Software for Windows
can remotely start and stop a genset. Make certain that all appropriate personnel are noti­fied before remotely operating equipment and make them aware of any equipment that can be energized automatically.
Do not work on this equipment when mentally
or physically fatigued, or after consuming any alcohol or drug that makes the operation of equipment unsafe.
PowerCommand is a trademark of Onan Cor­poration
Windows is a registered trademark of Microsoft Corporation.
iii
Redistribution or publication of this document by any means, is strictly prohibited.
iv

1. Introduction

Redistribution or publication of this document by any means, is strictly prohibited.
ABOUT THIS MANUAL
These instructions cover installation of the compo­nents and wiring required for PowerCommand Control (PCC) serial communications. The kit in­cludes the PCC Serial Communications Interface Board, the PowerCommand Cable Interface and two cables. The PCC Serial Communications Inter­face Board provides direct serial communications with the PCC (installation of a control type network is not needed).
CAUTION
Electrostatic discharge will damage circuit boards and components. Do not remove the circuit board from the antistatic shipping bag until you are grounded to the PCC with a wrist strap.
The PCC operating software must be version
2.00 or higher for the PCC Serial Communications
Interface Board to communicate with the PCC. Check the version on the display menu. If the ver­sion number is below 2.00, obtain and install an EPROM upgrade kit before proceeding with this installation. Follow the installation instructions pro­vided with the EPROM kit.
The PCC Serial Communications Interface Board allows a host PC with PowerCommand for Win­dows to communicate, via a serial connection, with the PCC.
The PowerCommand Cable Interface provides a junction box between the twisted pair from TB1 and the serial cable from the host PC or modem.
The null modem cable is used to connect directly to a host PC, and the Modem cable is used to connect to a modem.
This manual is intended for service personnel with a basic understanding of serial communications who are also qualified to perform service on generator sets. Review the entire manual before starting the installation.
Section 2 provides an overview of PCC serial com­munications. Section 3 describes the hardware installation. Section 4 covers the alarm setup.
Abbreviations
ACK Acknowledgement NAK Negative Acknowledgement PC Personal Computer PCC PowerCommand PCW PowerCommand SCT Serial Configuration Tool
Control for Windows
SPECIAL TOOLS REQUIRED
Grounding wrist strap with grounding clip
Serial Communication Configuration Tool
Software
PowerCommand version 1.1) Only required if an installation checkout will be preformed
PowerCommand is a trademark of Onan Corporation.
1997 Onan Corporation
for Windows (minimum
1-1
Redistribution or publication of this document by any means, is strictly prohibited.
1-2

2. PCC Serial Communications

Redistribution or publication of this document by any means, is strictly prohibited.
SERIAL COMMUNICATIONS
The PCC serial protocol provides simple com­mands for reading bytes from–and writing bytes to– the PCC. In the single set software, a protocol com­mand is provided for alarm reporting in direct or re­mote connections. The serial communications in­terface does not support the Emergency stop fea­ture in PCW.
The PCC has the means of reporting alarm events as they transpire. When enabled, it is an event-driv­en real-time alarm reporting protocol. This means anytime the PCC senses a warning or fault, it has the ability to initiate communications to report the event to the host. This is accomplished either through remote connections via a modem or a di­rect serial link. Refer to Figures 2-1 and 2-2.
The PCC has three lines for communications that are available at the Customer Interface Terminal Block: NET_DATA 2 (TB1–15 [TX]) – Transmit NET_DATA 1 (TB1–14[RX]) – Receive NET_POWER (TB1–13[GND]) – Ground
There are no handshaking or control lines available.
The PCC’s serial communication is interrupt-driv­en. Any time data is received at the PCC, an inter­rupt is generated for the microprocessor to handle the data. Once all the data is received, it is checked for validity and errors. If the command was valid and the data was without error, the command is ex­ecuted and the proper data is returned. If the com­munication was unsuccessful, a NAK (negative ac­knowledgment) or no data will be returned. The host must then re-transmit the command.
The PCC does incorporate a simple form of error checking. The PCC uses a longitudinal redundancy check (LRC), which is the exclusive–OR (XOR) of all the bytes in the packet to be sent. This byte is attached to the end of the packet.
PCC Serial Interface
The PCC Serial Communication Protocol is de­signed for two conditions of connection:
1. The PCC is directly connected through a PC serial port (direct serial connection). Figure 2-1.
2. The PCC is remotely connected via modems and the telephone line to the host PC (remotely connected). Figure 2-2.
PowerCommand Control
PowerCommand
Cable Interface
Serial Cable
Twisted Pair
(From Connection
Box TB1)
FIGURE 2-1. DIRECT SERIAL COMMUNICATION
(DB9 to DB9)
2-1
Host Computer
PowerCommand Control
Redistribution or publication of this document by any means, is strictly prohibited.
PowerCommand
Cable Interface
Twisted Pair
(From Connection
Box TB1)
Serial Cable
(DB9 to DB25)
MODEM
Host Computer
Telephone Line
MODEM
Serial Cable
(DB25 to DB9)
FIGURE 2-2. REMOTE SERIAL COMMUNICATION VIA MODEMS
2-2

3. Hardware Installation

Redistribution or publication of this document by any means, is strictly prohibited.
OVERVIEW
This section describes installation of the Power­Command Serial Communications Interface Board and the Serial Cable Interface Board.
The PCC Serial Communications Interface Board
must be used with PCC operating software ver­sion 2.00 or higher for all models. Check the ver-
sion on the display menu. If the version number is below 2.00, obtain and install an EPROM upgrade kit before proceeding with this installation. Follow the installation instructions provided with the EPROM kit.
DESCRIPTION
The Serial Communications Interface Board pro­vides customers with an electrically isolated (EIA–232) RS232 serial communications interface to the PCC.
When the PowerCommand Serial Communications Interface Board is installed, the PCC control will no longer enter the sleep mode.
The Serial Cable Interface Board is used to provide a DB9 cable connection. This connection can be used for either direct serial communication with a host computer or for remote serial communication via a modem (Figures 2-1 and 2-2).
LOCATION
The PowerCommand Serial Communications Inter­face Board is mounted inside the PCC cabinet on top of the analog board (Figure 3-1). The Serial Cable Interface Board is located outside the gener­ator set connection box. Refer to the installation in­struction section.
CAUTION
Electrostatic discharge will damage circuit boards. Do not remove the circuit board from the antistatic shipping bag until you are grounded to the PCC with a wrist strap.
Circuit Board Handling Precautions
To help prevent circuit board damage due to elec­trostatic discharge (ESD), a grounding wrist strap must be worn when handling the circuit board. (The wrist strap does not provide a direct short to ground, it is typically rated at approximately 1 megohm to ground.)
Attach the wrist strap clip to a clean unpainted sur­face of the control box (see Figure 3-1) and place the strap around your wrist before handling a circuit board.
3-1
PCC SERIAL COMMUNICATIONS
Redistribution or publication of this document by any means, is strictly prohibited.
INTERFACE BOARD INSTALLATION
1. Place the genset Run/Off/Auto switch, on the control panel, in the Off position.
2. Disconnect the battery charger (if applicable). Remove all electrical supply sources.
CAUTION
Always disconnect a battery charger from its AC source before discon­necting the battery cables. Otherwise, dis­connecting the cables can result in voltage spikes high enough to damage the DC con­trol circuits of the system.
3. Disconnect the genset starting battery cable(s). Disconnect the negative (–) cable(s) first to reduce the risk of arcing.
WARNING
Accidental starting of the gen­set while working on it can cause severe personal injury or death. Prevent acciden­tal starting by disconnecting the starting battery cables. T o reduce the risk of arcing, disconnect the negative (–) cable first. When reconnecting, connect the negative (–) cable last. Make certain battery area has been well­ventilated before servicing battery. Arcing can ignite explosive hydrogen gas given off by batteries, causing severe personal inju­ry. Make certain hydrogen gas, engine fuel, and other explosive fumes are fully dissi­pated. This is especially important if battery has been connected to a battery charger.
ANALOG
BOARD
A33
WRIST STRAP
FIGURE 3-1. PREPARING FOR INSTALLATION
4. Open the control box door. Connect the wrist strap ground clip as shown in Figure 3-1.
5. Use a Phillips screwdriver to remove the four leftmost analog board mounting screws shown in Figure 3-1.
6. Install four new standoffs in place of the analog board mounting screws removed in step 5 (Figure 3-2). Tighten the standoffs securely.
FIGURE 3-2. INSTALLING STANDOFFS
3-2
7. Mount the board as shown in Figure 3-3, using
Redistribution or publication of this document by any means, is strictly prohibited.
the screws removed from the analog board. Tighten the mounting screws securely.
8. Orient the J6 harness connector as shown in Figure 3-4. Push the J6 plug securely into the connector on the engine interface board.
9. Spread locking tabs apart on the J7 connector . Fold the ribbon cable, as shown in Figure 3-4, align key on plug with socket cutout. Insert the J7 harness plug into the J7 connector on the engine interface board. Press in on the harness connector, at the location indicated by the ar­row, until the locking tabs lock into place.
10. Proceed to PowerCommand Cable Interface Installation.
ENGINE INTERFACE
LOCKING
TABS
BOARD A31
FIGURE 3-3. BOARD MOUNTING
ALIGN KEY
WITH CUTOUT
FOLD RIBBON
CABLE HERE
J7 CONNECTOR
J6 CONNECTOR
FIGURE 3-4. INSTALLING J6 AND J7 CONNECTORS
3-3
POWERCOMMAND CABLE INTERFACE
Redistribution or publication of this document by any means, is strictly prohibited.
INSTALLATION
Location
Choose a clean, vibration-free mounting surface within 100 ft. (30.5 M) of the generator set. Avoid locations that are hot, damp or dusty . The tempera­ture range must not exceed –40°F (–40°C) to 158°F (70°C).
The board is designed for panel mounting within other equipment enclosures. The board is potted in a molded shell.
2.95 (75)
Mounting
Figure 3-5 shows the outline dimensions. The out­side dimensions do not include clearance for wire connections.
If mounting the module to a wall, make sure that no wires, plumbing, gas or exhaust lines run behind the wall before drilling the mounting holes.
0.875 (22.2)
0.51 (13)
3.94 (100)
3.15 (80)
0.39 (10)
2.17 (55)0.39 (10)
0.47 (12)
FIGURE 3-5. POWERCOMMAND CABLE INTERFACE OUTLINE DRAWING
3-4
0.23 (5.9)
DIMENSIONS IN
INCHES (mm)
CUSTOMER CONNECTIONS TB1
Redistribution or publication of this document by any means, is strictly prohibited.
OPTIONAL SHIELD
CONNECTION
TB115 (TX)
TB114 (RX)
TB113 (GND)
POWERCOMMAND CABLE
INTERFACE BOARD
MOUNTING SCREW
UNSHIELDED 22 AWG UL LEVEL IV OR EIA
CAT. 4 TWISTED PAIR COMMUNICATION WIRE
FIGURE 3-6. GENSET (TB1) TO POWERCOMMAND CABLE INTERFACE CONNECTIONS SCHEMATIC
WIRING CONNECTIONS
22 AWG UL level IV or EIA CAT . 4 twisted pair com­munication wire.
Serial data wiring connections are made between TB1 in the accessory box (Figure 3-7) and TB1 on the PowerCommand Cable Interface. Refer to Fig­ure 3-6 for the connection diagram. Use unshielded
For Local Connection to Host PC:
Cable (Figure 3-8).
For Remote Connection via Modem:
Cable (Figure 3-8).
Use Null Modem
Use Modem
3-5
TB1-1
Redistribution or publication of this document by any means, is strictly prohibited.
HC 6/7
TB1-1
HC 4/5
FIGURE 3-7. ACCESSORY BOX
3-6
MODEM CABLE
Redistribution or publication of this document by any means, is strictly prohibited.
(DB to DB25)
72 ± 6
(183 ± 15)
NULL MODEM CABLE
(DB9 to DB9)
FIGURE 3-8. WIRE HARNESS DRAWINGS
TABLE 3-1. RS232 (SERIAL) D CONNECTOR
PINOUTS
25 – Pin D Connector 9 – Pin D Connector
Pin Descriptor Pin Descriptor 2 TX 1 DCD 3 RX 2 RX 4 RTS 3 TX 5 CTS 4 DTR 6 DSR 5 GND 7 GND 6 DSR 8 DCD 7 RTS 20 DTR 8 CTS 22 RI 9 RI
72 ± 6
(183 ± 15)
DIMENSIONS IN
INCHES (cm)
3-7
Redistribution or publication of this document by any means, is strictly prohibited.
3-8

4. Alarm Setup

Redistribution or publication of this document by any means, is strictly prohibited.
ABOUT THIS SECTION
This section describes procedures for using the PCC setup menu for Alarm Reporting. In order to perform this setup the PowerCommand Serial Communications Interface Board must be installed.
NOTE: For remote alarm reporting, the setup must be performed with the Serial Configuration Tool (SCT). Use the instructions provided with the SCT software. Also use SCT for installing a password (optional). The password default is eight nulls (∅).
PCC SETUP MENU FOR ALARM
REPORTING
The PCC Alarm Reporting Menu (Figure 4-1) will only appear if the serial communication module is installed.
SITE ID, and PHONE #1 are editable fields in the Setup Menu. Refer to the generator set service manual Control Service and Calibration section for instructions on entering the Setup Menu.
A maximum of 8 digits can be entered for SITE ID, and 16 digits for PHONE #1. A carriage return must be entered as a termination character at the end of the phone number. The symbol for a carriage re­turn is a ‘ê’ (an ‘e’ with a cap on it). Scroll past the numbers to reach the special characters. Without this termination character, the phone number is in­valid and the PCC will not dial out.
NOTE: When SCT is used to configure the Phone #1, the termination character is automatically added.
PCW COMM ON/OFF:
Enables or disables the
alarm reporting protocol.
MODEM COMM ON:
Enables remote communica-
tion using the alarm reporting protocol.
MODEM COMM OFF:
Enables direct serial con-
nection using the alarm reporting protocol.
LANGUAGE ENGLISH >>
PCW COMM.
ON >>
MODEM COMM
ON >>
00000000 SITE ID >>
0000000000000000 PHONE # 1
FIGURE 4-1. PCC ALARM REPORTING SETUP MENU
PCW COMM.
OFF >>
MODEM COMM
OFF >>
00000000 SITE ID >>
SAVE EXIT >>
4-1
Direct Serial Communication
Redistribution or publication of this document by any means, is strictly prohibited.
PHONE #1 can be entered into the PCC either by
the service tool (SCT) or the PCC Setup menu. From the PCC Setup Menu, set PCW COMM to ON and set the MODEM COMM to OFF. This allows the
PCC Setup Variables(for Alarm Reporting)
PCC to enable the alarm reporting protocol and initi­ate the communication in the direct serial connec­tion.
Table 4-1 lists the PCC Setup Variables and pro-
vides a description of how they are configured. Note
three variable (not shown) the MODEM INIT
Remote Serial Communication
STRING, DIAL_PREFIX, and PASSWORD can
only be configured with the Serial Configuration From the PCC Setup Menu, set both the PCW
COMM and MODEM COMM to ON. A phone num­ber followed by a carriage return (‘ê’) must be en­tered in PHONE #1. This allows the PCC to enable the alarm reporting protocol and the PCC to initiate
Tool (SCT). Refer to the instructions provided with
the SCT software.
NOTE: The password default is eight nulls (). The
only way it can be changed is with the Serial Configu-
ration Tool (SCT).
the remote communications, such as dialing out alarms.
TABLE 4-1. PCC SETUP VARIABLES
VARIABLES DESCRIPTION SITE_ID The site_id is a 8 character (byte) ASCII string, This string is intended to define the
actual genset site location. The site_id is passed as part of the alarm message by the alarm reporting protocol. e.g. SITE_ID = {“Onan”}
PHONE_NO_1 The Phone No 1 is a 16 character (byte)ASCII string. This string should be num-
bers only, but will take any character the modem will recognize as valid for a dial string. This string contains the phone number of the location the PCC will call in case of an alarm. This location should be a Computer with a modem set to auto– answer. If the phone number is not terminated by a carriage return the PCC will not call out. Therefore the phone number can be a maximum of 15 digits long with the last character in the phone string being a carriage return. MODEM COMM in the Setup menu of the PCC must be set to ON, to enable the PCC to dial out. e.g. PHONE_NO_1 = {6125745400,0x0D} Note: 0x0D = ‘ê’
4-2
INSTALLATION CHECKOUT
Redistribution or publication of this document by any means, is strictly prohibited.
Record the site ID and phone number for the site. If used, also record the password, modem init string, and dial prefix. Keep this information in a safe place.
To checkout the site thoroughly, the installer will need to have PowerCommand for Windows (PCW) beginning at version 1.1. Refer to the PCW manual (900-0365) for instructions on installing and running
PCW. Operate PCW to thoroughly check out the
installation.
If installation problems are detected, make sure that
all electrical connections are making good contact,
check the password (if used), and return to SCT to
check the configuration settings.
If error messages or warnings are displayed in the
PCC display, refer to the appropriate service manu-
al Troubleshooting section.
4-3
Redistribution or publication of this document by any means, is strictly prohibited.
4-4
Cummins Power Generation
Redistribution or publication of this document by any means, is strictly prohibited.
1400 73rd Avenue N.E. Minneapolis, MN 55432 1-800-888-6626 763-528-7229 International Use Fax: 763-528-7229
Cummins is a registered trademark of Cummins Inc.
Loading...