Cummins Power Generation Onan GGFB, Onan GGFC Installation Manual

Caution: This document contains mixed page sizes (8.5 x 11 or 11 x
Redistribution or publication of this document by any means, is strictly prohibited.
17), which may affect printing. Please adjust your printer settings according to the size of each page you wish to print.
Models
Redistribution or publication of this document by any means, is strictly prohibited.
Printed in U.S.A. 928Ć0610B 11Ć98

Table of Contents

Redistribution or publication of this document by any means, is strictly prohibited.
SECTION TITLE PAGE
SAFETY PRECAUTIONS iii. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1 INTRODUCTION
About this Manual 1-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Installation Overview 1-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2 SPECIFICATIONS 3 MOUNTING THE GENERATOR SET
General 3-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Location 3-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Mounting 3-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Access to Set 3-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4 MECHANICAL CONNECTIONS
General 4-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Fuel System 4-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Exhaust System 4-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Ventilation and Cooling 4-5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5 DC CONTROL WIRING (DETECTOR CONTROL)
Control Wiring 5-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Engine Control Monitor Board (ECM-A11) 5-2. . . . . . . . . . . . . . . . . . . . . . . . . .
Auxiliary Relay Board (Optional) 5-4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Time-Delay Module (A15) (Optional) 5-6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6 DC CONTROL WIRING (SENTINEL CONTROL)
Control Wiring 6-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Dry Contact Module (Optional) 6-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
!!
The engine exhaust from this product
contains chemicals known to the State
of California to cause cancer, birth
defects or other reproductive harm.
i
SECTION TITLE PAGE
Redistribution or publication of this document by any means, is strictly prohibited.
7 AC ELECTRICAL CONNECTIONS
General 7-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Transfer Switch 7-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
AC Wiring 7-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Control Heater (Optional) 7-5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Coolant Heater (Optional) 7-6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Generator Heater (Optional) 7-7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8 PRESTART PREPARATION (DETECTOR/SENTINEL CONTROL)
General 8-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical System 8-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Starting 8-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9 INSTALLATION CHECKLIST
General 9-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Genset Support 9-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Cooling Air Flow 9-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Fuel System 9-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Exhaust System 9-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
AC and DC Wiring 9-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Genset Prestart 9-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
10 WIRING DIAGRAMS
General 10-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ii

Safety Precautions

Redistribution or publication of this document by any means, is strictly prohibited.
Before operating the generator set (genset), read the Operator’s Manual and become familiar with it and the equipment. Safe and efficient operation can be
achieved only if the equipment is properly operated and maintained. Many accidents are caused by failure
to follow fundamental rules and precautions.
The following symbols, found throughout this manual, alert you to potentially dangerous conditions to the op­erator, service personnel, or the equipment.
This symbol warns of immediate hazards which will result in severe personal in­jury or death.
WARNING
This symbol refers to a hazard or un­safe practice which can result in severe per­sonal injury or death.
CAUTION
This symbol refers to a hazard or un­safe practice which can result in personal injury or product or property damage.
FUEL AND FUMES ARE FLAMMABLE
Fire, explosion, and personal injury or death can result from improper practices.
Be sure all fuel supplies have a positive shutoff
valve.
Be sure battery area has been well-ventilated prior
to servicing near it. Lead-acid batteries emit a highly explosive hydrogen gas that can be ignited by arc­ing, sparking, smoking, etc.
EXHAUST GASES ARE DEADLY
Provide an adequate exhaust system to properly expel discharged gases away from enclosed or sheltered areas and areas where individuals are likely to congregate. Visually and audibly inspect the exhaust daily for leaks per the maintenance schedule. Make sure that exhaust manifolds are se­cured and not warped. Do not use exhaust gases to heat a compartment.
Be sure the unit is well ventilated.
Engine exhaust and some of its constituents are
known to the state of California to cause cancer, birth defects, and other reproductive harm.
MOVING PARTS CAN CAUSE SEVERE PERSONAL INJURY OR DEATH
DO NOT fill fuel tanks while engine is running, un-
less tanks are outside the engine compartment. Fuel contact with hot engine or exhaust is a potential fire hazard.
DO NOT permit any flame, cigarette, pilot light,
spark, arcing equipment, or other ignition source near the generator set or fuel tank.
Fuel lines must be adequately secured and free of
leaks. Fuel connection at the engine should be made with an approved flexible line. Do not use copper piping on flexible lines as copper will be­come brittle if continuously vibrated or repeatedly bent.
Natural gas is lighter than air, and will tend to gather
under hoods. Propane is heavier than air, and will tend to gather in sumps or low areas. NFPA code re­quires all persons handling propane to be trained and qualified.
Keep your hands, clothing, and jewelry away from moving parts.
Before starting work on the generator set, discon-
nect battery charger from its AC source, then dis­connect starting batteries, negative (-) cable first. This will prevent accidental starting.
Make sure that fasteners on the generator set are
secure. Tighten supports and clamps, keep guards in position over fans, drive belts, etc.
Do not wear loose clothing or jewelry in the vicinity of
moving parts, or while working on electrical equip­ment. Loose clothing and jewelry can become caught in moving parts. Jewelry can short out elec­trical contacts and cause shock or burning.
If adjustment must be made while the unit is run-
ning, use extreme caution around hot manifolds, moving parts, etc.
MS-1
iii
ELECTRICAL SHOCK CAN CAUSE
Redistribution or publication of this document by any means, is strictly prohibited.
SEVERE PERSONAL INJURY OR DEATH
Remove electric power before removing protective shields or touching electrical equipment. Use rub­ber insulative mats placed on dry wood platforms over floors that are metal or concrete when around electrical equipment. Do not wear damp clothing (particularly wet shoes) or allow skin surface to be damp when handling electrical equipment.
Use extreme caution when working on electrical
components. High voltages can cause injury or death. DO NOT tamper with interlocks.
Follow all applicable state and local electrical
codes. Have all electrical installations performed by a qualified licensed electrician. Tag and lock open switches to avoid accidental closure.
DO NOT CONNECT GENERATOR SET DI-
RECTLY TO ANY BUILDING ELECTRICAL SYS­TEM. Hazardous voltages can flow from the gen­erator set into the utility line. This creates a potential for electrocution or property damage. Connect only through an approved isolation switch or an ap­proved paralleling device.
GENERAL SAFETY PRECAUTIONS
Coolants under pressure have a higher boiling point
than water. DO NOT open a radiator or heat ex­changer pressure cap while the engine is running. Allow the generator set to cool and bleed the system pressure first.
Benzene and lead, found in some gasoline, have
been identified by some state and federal agencies
as causing cancer or reproductive toxicity. When checking, draining or adding gasoline, take care not to ingest, breathe the fumes, or contact gasoline.
Used engine oils have been identified by some state
or federal agencies as causing cancer or reproduc­tive toxicity. When checking or changing engine oil, take care not to ingest, breathe the fumes, or con­tact used oil.
Provide appropriate fire extinguishers and install
them in convenient locations. Consult the local fire department for the correct type of extinguisher to use. Do not use foam on electrical fires. Use extin­guishers rated ABC by NFPA.
Make sure that rags are not left on or near the en-
gine.
Remove all unnecessary grease and oil from the
unit. Accumulated grease and oil can cause over­heating and engine damage which present a poten­tial fire hazard.
Keep the generator set and the surrounding area
clean and free from obstructions. Remove any de­bris from the set and keep the floor clean and dry.
Do not work on this equipment when mentally or
physically fatigued, or after consuming any alcohol or drug that makes the operation of equipment un­safe.
Substances in exhaust gases have been identified
by some state or federal agencies as causing can­cer or reproductive toxicity. Take care not to breath or ingest or come into contact with exhaust gases.
KEEP THIS MANUAL NEAR THE GENSET FOR EASY REFERENCE
iv

1. Introduction

Redistribution or publication of this document by any means, is strictly prohibited.
ABOUT THIS MANUAL
This manual provides installation instructions for the GG Series generator sets (gensets) listed on the front cover. This includes the following informa­tion:
Mounting Recommendations - for fastening generator set to base and space requirements for normal operation and service.
Mechanical Connections - Location of con­nection points for fuel, exhaust, ventilation, and cooling.
Electrical Connections – Location of electri­cal connection points for the control, generator, and starting system.
Prestart – Checklist of items or procedures needed to prepare generator set for operation.
Initial Startup – Test complete system to en­sure proper installation, satisfactory perform­ance, and safe operation. Refer to Operators Manual for troubleshooting information.
Installation Checklist – Reference checks upon completion of installation.
Detector 12 Control
This manual contains separate DC Control Wiring and Prestart Preparation sections for gensets using the Sentinel control or the Detector control (Figure 1-1). Refer to the Table of Contents for specific in­formation relating to your genset. The remaining sections apply to all versions.
This manual DOES NOT provide application infor­mation for selecting a generator set or designing the complete installation. If it is necessary to design the various integrated systems (fuel, exhaust, cooling, etc.), additional information is required. Review standard installation practices. For engineering data specific to the generator set, refer to the speci­fication and product data sheets. For application in­formation, refer to Application Manual T-030, “Liq­uid Cooled Generator Sets”.
Sentinel Control
FIGURE 1-1. CONTROL PANEL CONFIGURATIONS
1-1
INSTALLATION OVERVIEW
Redistribution or publication of this document by any means, is strictly prohibited.
These installation recommendations apply to typi­cal installations with standard model generator sets. Whenever possible, these recommendations also cover factory designed options or modifica­tions. However, because of the many variables in any installation, it is not possible to provide specific recommendations for every situation. If there are any questions not answered by this manual, contact your nearest Cummins/Onan dealer or distributor for assistance.
Application and Installation
A standby power system must be carefully planned and correctly installed for proper operation. This in­volves two essential elements: application and in­stallation.
Application (as it applies to generator set installa­tions) refers to the design of the complete standby power system that usually includes power distribu­tion equipment, transfer switches, ventilation equip­ment, mounting pads, and cooling, exhaust, and fuel systems. Each component must be correctly designed so the complete system will function as in­tended. Application and design is an engineering function generally done by specifying engineers or other trained specialists. Specifying engineers are responsible for the design of the complete standby
system and for selecting the materials and products required.
Installation refers to the actual set-up and assem­bly of the standby power system. The installers set up and connect the various components of the sys­tem as specified in the system design plan. The complexity of the standby system normally requires the special skills of qualified electricians, plumbers, sheetmetal workers, etc. to complete the various segments of the installation. This is necessary so all components are assembled using standard meth­ods and practices.
Safety Considerations
The generator set has been carefully designed to provide safe and efficient service when properly in­stalled, maintained, and operated. However, the overall safety and reliability of the complete system is dependent on many factors outside the control of the generator set manufacturer. To avoid possible safety hazards, make all mechanical and electrical connections to the generator set exactly as speci­fied in this manual. All systems external to the gen­erator (fuel, exhaust, electrical, etc.) must comply with all applicable codes. Make certain all required inspections and tests have been completed and all code requirements have been satisfied before certi­fying the installation is complete and ready for serv­ice.
1-2

2. Specifications

Redistribution or publication of this document by any means, is strictly prohibited.
MODEL GGFB GGFC
Engine
Onan Modified Ford In-line 6
Generator kW Rating
(See Genset Nameplate)
Fuel System Inlet Size
Natural Gas Propane Vapor Propane Liquid
Exhaust
Connection Backpressure (Max. Allowed)
Electrical System
Starting Voltage Battery Charging Alternator (Max. Rating)
Cooling System
Capacity with Standard Radiator
Lubricating System
Oil Capacity with Filters
CSG-649 CSG-649
1 inch NPT 3/4 inch NPT 1/4 inch NPT
2 inch NPT
20.4 inch H
12 Volts DC
37 A
5.8 Gal (22 L) 5.8 Gal (22 L)
7 Qts (6.6 L) 7 Qts (6.6 L)
O
2
1 inch NPT 3/4 inch NPT 1/4 inch NPT
2 inch NPT
20.4 inch H
12 Volts DC
37 A
2
O
2-1
Redistribution or publication of this document by any means, is strictly prohibited.
2-2

3. Mounting the Generator Set

Redistribution or publication of this document by any means, is strictly prohibited.
GENERAL
Most generator set installations must be engi­neered so the generator set will function properly under the expected load conditions. Use these in­structions as a general guide only. Follow the in­structions of the consulting engineer when locating or installing any components. The complete instal­lation must comply with all local and state building codes, fire ordinances, and other applicable regula­tions. Consider these requirements before installa­tion:
Level mounting surface
Adequate cooling air
Adequate fresh induction air
Discharge of circulated air
WARNING
Non-combustible mounting surface
Discharge of exhaust gases
Electrical connections
Accessibility for operation and servicing
Noise levels
Vibration isolation
LOCATION
Generator set location is decided mainly by related systems such as ventilation, wiring, fuel, and ex­haust. The set should be located as near as possi­ble to the main power fuse box.
Provide a location away from extreme ambient tem­peratures and protect the generator set from ad­verse weather conditions. An optional housing is available for outside operation.
INCORRECT INSTALLATION, SERVICE OR REPLACEMENT OF PARTS CAN RESULT IN SE­VERE PERSONAL INJURY OR DEATH, AND/OR EQUIPMENT DAMAGE. SERVICE PERSON­NEL MUST BE QUALIFIED TO PERFORM ELECTRICAL AND MECHANICAL COMPONENT INSTALLATION.
3-1
MOUNTING
Redistribution or publication of this document by any means, is strictly prohibited.
Generator sets are mounted on a steel skid that pro­vides proper support. The engine-generator as­sembly is isolated from the skid frame by rubber mounts that provide adequate vibration isolation for normal installations. For critical installations, install vibration isolators between the skid base and foun­dation.
Mount the genset on a substantial and level base such as a concrete pad. A non-combustible materi­al must be used for the pad.
HEX NUT
FLAT WASHER
SKID
Use 3/4-inch diameter, anchored mounting bolts to secure the generator set skid to the floor to prevent movement. Secure the skid using a flat washer and a hex nut for each bolt (Figure 3-1).
ACCESS TO SET
Plan for access to the genset for servicing and pro­vide adequate lighting around the unit.
12 INCH
(305 mm)
MOUNTING BOLT
FIGURE 3-1. BOLT DIAGRAM
3-2

4. Mechanical Connections

Redistribution or publication of this document by any means, is strictly prohibited.
GENERAL
The generator set mechanical system installation includes connecting the fuel, exhaust, ventilation and cooling systems. Before starting any type of fuel installation, all pertinent state and local codes must be complied with and the installation must be inspected before the unit is put in service.
FUEL SYSTEM
Gensets can be equipped to operate on:
LPG (vapor or liquid withdrawal)
NG (natural gas) or
Combination (NG/LPG)
In all fuel system installations, cleanliness is of the upmost importance. Make every effort to prevent entrance of moisture, dirt or contaminants of any kind. Clean all fuel system components before installing
A flexible fuel hose(s) or section of flexible fuel hose(s) must be used between the engine’s fuel system and fuel supply line(s) to protect the fuel system from damage caused by vibration, expan­sion and contraction.
Installation of the fuel hose must be done according to all applicable codes and standards, and installa­tion recommendations provided by the manufactur­er. The flexible hose used must be approved by the hose manufacturer for use with the genset fuel type and product application.
Natural Gas/LPG Vapor/LPG Liquid Fuel System
WARNING
explosive and can cause severe personal injury or death. Do not smoke if you smell gas or are near fuel tanks or fuel-burning equipment or are in an area sharing ventilation with such equip­ment. Keep flames, sparks, pilot lights, electri­cal arcs and arc-producing equipment and all other sources of ignition well away. Keep a type ABC fire extinguisher handy.
NFPA Standard No. 58 requires all persons han­dling and operating LPG to be trained in proper handling and operating procedures.
Gaseous-fuel supply system design, materials, components, fabrication, assembly, installation, testing, inspection, operation and maintenance must comply with the applicable codes. See NFPA Standards No. 30, No. 37, No. 54 and No. 58.
Most codes require both manual and electric (bat­tery-powered) shutoff valves ahead of the flexible fuel hose(s). The manual valve should be of the in­dicating type. The electric valve should be wired so that the valve is closed when the genset is off.
Install a dry-type fuel filter ahead of the service pressure regulator to protect the sensitive pressure regulating components and orifices downstream from rust, scale and other solid substances carried along in the gas stream.
See Specifications section for natural gas/LPG fuel inlet size. The recommendations in Application Manual T-030, should be followed in regard to fuel supply system pipe sizes, manual shutoff valves, fuel filters and gas pressure regulators.
Gaseous fuels are flammable and
4-1
Fuel Pressure
Redistribution or publication of this document by any means, is strictly prohibited.
WARNING
gas leaks which can lead to fire and severe per­sonal injury or death. Gas supply pressure must be adjusted to Specifications by qualified per­sonnel.
The gas pressure regulators in each line provide constant gas pressure at the gas mixer under vary­ing load conditions. There are pressure test ports on both sides of the fuel regulator for measuring supply and regulated fuel pressures (NG or LPG systems). When measuring supply pressure, the most accurate reading would be on the input side of the solenoid valve.
Mixer side: The NG gas pressure should be approximately 5 inches WC at full load.
The LP gas pressure will be approximately –0.5 inches WC at no load and –1.0 inch WC at full load.
High gas supply pressure can cause
Supply side: The minimum pressure refers to sup­ply pressure under rated load (maximum gas flow).
For LPG (vapor withdrawal) and natural gas, the maximum permissible fuel supply pressure is 13.6 inches WC and the recommended minimum is 7 in­ches WC.
For LPG (liquid withdrawal), the maximum permis­sible fuel supply pressure is 300 psi (2,070 kPa) un­der any operating condition.
WARNING
Gaseous fuel leaks into an inade­quately ventilated space can lead to explosive accumulations of gas. Natural gas rises when released into the air and can accumulate under overhanging hoods and inside housings and buildings. LPG sinks when released into the air and can accumulate inside housings, base­ments and other below-grade spaces. Precau­tions must be taken to prevent gas leaks and the accumulation of gaseous fuel in the event of a leak.
4-2
EXHAUST SYSTEM
Redistribution or publication of this document by any means, is strictly prohibited.
Pipe exhaust gases to the outside of any enclosure. Locate the exhaust outlets away from any air inlets to avoid gases re-entering the enclosure. Exhaust installations are subject to various detrimental con­ditions such as extreme heat, infrequent operation and light loads. Regularly inspect the exhaust sys­tem both visually and audibly to see that the entire system remains fume tight and safe for operation.
WARNING
Hot exhaust pipes can start a fire and cause severe injury or death if improperly routed through walls. Use an approved thimble where exhaust pipes pass through walls or par­titions.
WARNING
Inhalation of exhaust gases can re­sult in severe personal injury or death. Do not use exhaust heat to warm a room, compartment or storage area.
WARNING
Inhalation of exhaust gases can re­sult in severe personal injury or death. Use ex­treme care during installation to provide a tight exhaust system. Terminate exhaust pipe away from enclosed or sheltered areas, windows, doors and vents.
For indoor installations, the exhaust system must use sealed joint type fittings, (for example NPT fit­tings) to provide a tighter exhaust system. Use of slip type fittings (secured with a muffler clamp) may allow leakage of exhaust gases into the building.
WARNING
Inhalation of exhaust gases can re­sult in severe personal injury or death. Use ex­treme care during installation to provide a tight exhaust system. Use NPT or equivalent type fit­tings for all indoor installations.
Use an approved thimble (Figure 4-1) where ex­haust pipes pass through wall or partitions. Refer to NFPA 37, Section 6-3. “Stationary Combustion En­gines and Gas Turbines” for accepted design prac­tices. Build according to the code requirements in effect at the installation site.
Rain caps are available for the discharge end of ver­tical exhaust pipes. The rain cap clamps onto the end of the pipe and opens due to exhaust discharge force from the generator set. When the generator set is stopped, the rain cap automatically closes, protecting the exhaust system from rain, snow, etc.
Use a section of flexible exhaust pipe between the engine and remainder of exhaust system. Support exhaust system to prevent weight applied to engine exhaust outlet.
CAUTION
Weight applied to the engine mani­fold can result in damage. Support the muffler and exhaust piping so no weight or stress is ap­plied to engine exhaust.
The exhaust system design should meet local code requirements.
WARNING
Liability for injury, death, damage, and warranty expense due to use of unap­proved mufflers or to modifications becomes the responsibility of the person installing the unapproved muffler or performing the modifica­tion. Contact an Onan distributor for approved exhaust system parts.
4-3
Avoid sharp bends by using sweeping, long radius
Redistribution or publication of this document by any means, is strictly prohibited.
elbows and provide adequate support for muffler and tailpipe. Pitch a horizontal run of exhaust pipe DOWNWARD (away from engine) to allow any moisture condensation to drain away from the en­gine. If an exhaust pipe must be turned upward, in­stall a condensation trap at the point where the rise begins (Figure 4-2).
Shield or insulate exhaust lines if there is danger of personal contact. Allow at least 12 inches (305 mm) of clearance if the pipes pass close to a combustible wall or partition.
WARNING
Exhaust pipes are very hot and they can cause severe personal injury or death from direct contact or from fire hazard. Shield or in­sulate exhaust pipes if there is danger of per­sonal contact or when routed through walls or near other combustible materials.
RAIN CAP
9 INCH
(230 mm)
VERTICAL
HORIZONTAL
DRIP CAP
HOLES IN
END OF INNER
SLEEVE
ROOF
9 INCH
(230 mm)
WALL OR PARTITION
FIGURE 4-1. MOUNTING EXHAUST THIMBLE
IF EXHAUST LINE MUST BE
PITCHED UPWARD, CONSTRUCT
A TRAP AT POINT OF RISE
AVOID SHARP BENDS
DRAIN CONDENSATION
TRAP PERIODICALLY
VALVE HANDLE SHOWN
IN OPEN POSITION
FIGURE 4-2. CONDENSATION TRAP
4-4
VENTILATION AND COOLING
Redistribution or publication of this document by any means, is strictly prohibited.
Generator sets create considerable heat that must be removed by proper ventilation. Outdoor installa­tions rely on natural air circulation but indoor instal­lations need properly sized and positioned vents for required airflow.
Vents and Ducts
For indoor installations, locate vents so incoming air passes through the immediate area of the installa­tion before exhausting. Install the air outlet higher than the air inlet to allow for convection air move­ment.
Size the vents and ducts so they are large enough to allow the required flow rate of air. The ”free area” of ducts must be as large as the exposed area of the radiator. Refer to the GG Series Specification Sheet for the airflow requirements and allowed airflow re­striction.
Wind will restrict free airflow if it blows directly into the air outlet vent. Locate the outlet vent so the ef­fects of wind are eliminated or utilize a wind barrier if necessary to minimize the effects of prevailing winds. See Figure 4-3.
PREVAILING WINDS PREVAILING WINDS
NOT LESS THAN
HEIGHT OF OPENING
FIGURE 4-3. WIND BARRIER
4-5
Dampers
Redistribution or publication of this document by any means, is strictly prohibited.
Dampers or louvres protect the generator set and equipment room from the outside environment. Their operation of opening and closing should be controlled by operation of the generator set.
In cooler climates movable or discharge dampers are used. These dampers allow the air to be recircu­lated back to the equipment room. This enables the equipment room to be heated while the generator set engine is still cold, increasing the engine effi­ciency.
Radiator Set Requirements
Radiator set cooling air is drawn past the rear of the set by a pusher fan that blows air through the radia­tor (Figure 4-4). Locate the air inlet to the rear of the set. Make the inlet vent opening 1-1/2 times larger than the radiator area.
must be at least as large as the radiator area. Length and shape of the air outlet duct should offer minimum restriction to airflow.
Attach a canvas or sheet metal duct to the air outlet opening using screws and nuts so duct can be re­moved for maintenance purposes. The duct pre­vents recirculation of heated air. For installations that use a radiator discharge duct, the radiator core guard can be removed. This will allow for slightly less air flow restriction.
Remote Radiator Cooling (Optional) substitutes a remote mounted radiator and an electrically driven fan for the set mounted components. Re­moval of the radiator and the fan from the set re­duces noise levels without forcing dependence on a continuous cooling water supply. The remote radia­tor installation must be completely protected against freezing.
Louvers and screens over air inlet and outlet open­ings restrict air flow and vary widely in performance. A louver assembly with narrow vanes, for example, tends to be more restrictive than one with wide vanes. The effective open area specified by the lou­ver or screen manufacturer should be used.
Locate the cooling air outlet directly in front of the ra­diator and as close as possible. The outlet opening
Remote radiator plumbing will vary with installation. Follow recommendations given in Application Man- ual T-030. See product Specification sheet for fric­tion head and static head limits.
Before filling cooling system, check all hardware for security. This includes hose clamps, capscrews, fit­tings and connections. Use flexible coolant lines with heat exchanger or remote mounted radiator.
4-6
THIMBLE
Redistribution or publication of this document by any means, is strictly prohibited.
EXHAUST
LINE
CONDENSATION
DRAIN PLUG
AIR OUT
MUFFLER
SWEEPING
ELBOW
CONTROL
WIRING
FLEXIBLE
SECTIONS
POWER
WIRING
AIR
IN
FLEXIBLE
BELLOWS
VIBRATION
ISOLATORS
IMPORTANT!
COOLING AIR INLET MUST BE AT LEAST 1-1/2 TIMES LARGER
THAN RADIATOR DUCT OUTLET AREA ON RADIATOR-COOLED
MODELS.
FLOW OF COOLING AIR AND HEATED AIR MAY BE
CONTROLLED BY AUTOMATICALLY OPERATED LOUVRES.
FIGURE 4-4. TYPICAL GENERATOR SET INSTALLATION
LEVEL
CONCRETE
BASE
4-7
Redistribution or publication of this document by any means, is strictly prohibited.
4-8

5. DC Control Wiring (Detector Control)

Redistribution or publication of this document by any means, is strictly prohibited.
CONTROL WIRING
The generator set control panel box contains con­nection points for remote control and monitor op­tions. These connection points are located on the engine control monitor board (ECM), the time-delay module and the optional auxiliary relay board (ARB). (Note that if the optional ARB is installed, no remote monitor connections are attached to the ECM. The ARB provides all remote monitor con­nection points.)
CAUTION
for all customer connections to the control pan­el box. Solid copper wire may break due to gen­set vibration.
The type/gauge wire to use for these connections are:
Stranded copper wire must be used
Less than 1000 feet (305m), use 18 gauge
stranded copper wire.
1000 to 2000 feet (305 to 610m), use 16 gauge
stranded copper wire.
CAUTION
a separate metal conduit from AC power cables to avoid inducing currents that could cause problems within the control.
WARNING
uninsulated high voltage parts inside the con­trol panel box can result in severe personal inju­ry or death. Control wire installation must be done with care to avoid touching uninsulated live parts.
For your protection, stand on a dry wooden plat­form or rubber insulating mat, make sure your clothing and shoes are dry, remove jewelry and use tools with insulated handles.
Always run control circuit wiring in
HAZARDOUS VOLTAGE Touching
5-1
ENGINE CONTROL MONITOR BOARD
Redistribution or publication of this document by any means, is strictly prohibited.
(ECM-A11)
The heart of the engine control system is the engine monitor (A11). It is a printed circuit board assembly mounted on the back wall of the control box (Figure 5-1). It starts and stops the engine in response to the control panel switches, engine sensors and re­mote control signals.
Remote Monitor Connections
The Detector control provides the capability of at­taching a remote monitor panel. Connections are made on the terminal blocks TB1 and TB2 located on the ECM board. A detailed connection diagram for the ECM board is provided in Section 10. (If the optional ARB is installed, remote monitor connec­tions attach to the ARB, not the ECM.)
Remote Start Connections
Connect remote start switch between A11-TB1-7 (B+) and A11-TB1-6 (RMT).
Function Selection Jumpers
The ECM board has six selection jumpers that can be repositioned to provide the following timed or non-timed warnings or timed or non-timed shut­downs with warnings:
W1 (12 light only) Jumper Position (jumper W8
must be in the B position):
A Non-timed warning under FLT 2 condi-
tions.
B (12 light only) Non-timed shutdown under
FLT 2 conditions.
C Timed warning under FLT 2 conditions.
D Timed shutdown under FLT 2 conditions.
W2 Jumper Position (jumper W9 must be in the B
position):
A Non-timed warning under FLT 1 condi-
tions.
B Non-timed shutdown under FLT 1 condi-
tions.
C Timed warning under FLT 1 conditions.
D Timed shutdown under FLT 1 conditions.
W6 Jumper Position:
A Warning under Pre-High Engine Tem-
perature conditions.
B Shutdown under Pre-High Engine Tem-
perature conditions.
W7 Jumper Position:
A Warning under Pre-Low Oil Pressure
conditions.
B Shutdown under Pre-Low Oil Pressure
conditions.
W8 (12 light only) Jumper Position:
A Warning while running or during standby
under FLT 2 conditions.
B Allows selection of functions with W1
jumper.
W9 (12 light only) Jumper Position:
A Warning while running or during standby
under FLT 1 conditions.
B Allows selection of functions with W2
jumper.
5-2
TB1
Redistribution or publication of this document by any means, is strictly prohibited.
8 7 6 5 4 3 2 1 6 5 4 3 2 1
TB2
FIGURE 5-1. ENGINE CONTROL MONITOR BOARD (ECM)
5-3
AUXILIARY RELAY BOARD (OPTIONAL)
Redistribution or publication of this document by any means, is strictly prohibited.
The following describes the design/functional crite­ria for the auxiliary relay board (ARB) with a Detec­tor control. The board is mounted directly on top of the ECM using standoffs and has access holes for the fuses located on the ECM. A detailed connec­tion diagram for the ARB is provided in Section 10.
Terminal Blocks:
TB1 – ARB TB1 and engine monitor TB1 are identically numbered and provide the same re­mote control connection points. Note that addi­tional terminals are provided for terminals 5, 7, and 10 of ARB TB1.
TB2 through TB5 – Connection points for re- lays K1 through K3. TB2 provides the N/O and N/C connections (three form ‘C’ contacts for each relay). TB3 through TB5 provide the com­mon connection points (TB3 for K1, TB4 for K2 and TB5 for K3).
TB6 and TB7 – Connection points for fault re­lays K4 through K15. Three terminals are pro­vided for each relay, which are labeled COM, N/C, N/O.
Plug-In Relays (K1, K2, K3): The ARB can be equipped with one to three 3-pole, double-throw re­lays. These relays (K1, K2, K3) are field changeable plug-in relays for easy field addition and replace­ment.
Each relay can be operated as a RUN, COMMON ALARM, or ISOLATED COIL with the changing of a jumper.
The relay contact ratings are:
10 amps at 28 VDC or 120 VAC, 80% PF
6 amps at 240 VAC, 80% PF
Jumper Position A (Run) – The relay oper-
ates as a Run relay, energizing when SW B+ is applied from the engine monitor.
Jumper Position B (Common Alarm) – The relay operates as a Common Alarm relay. The relay energizes any time there is an engine shutdown.
Jumper Position C (Isolated) – The relay op- erates as an Isolated relay. The relay coil is en­ergized by a customer applied B+ signal through the terminal block; TB3-1 for relay K1, TB4-1 for relay K2, and TB6-1 for relay K3.
Jumpers W11, W12, and W13 perform the same functions for their respective relays; W11 for relay K1, W12 for relay K2, and W13 for relay K3. They can be located in two different positions (A, B) inde­pendently of one another.
Jumper Position A – The relay operates iso- lated from the board. The customer provides the circuit completion through terminal block; TB3 for relay K1, TB4-5 for relay K2, and TB6-5 for relay K3. The customer can operate the re­lay with switched ground logic or use this relay in the middle of more complex logic circuits if needed.
Jumper Position B – The relays operate with the coils connected to ground through the board connections. The coil will require a B+ signal to energize with the jumper in this posi­tion.
Fault Relays (K4 through K15): These relay mod­ules are used to operate a remote alarm annuncia­tor that has an independent power source. This al­lows the use of either AC or DC for alarm drives. The relays are energized through the latching relays on the engine monitor and provided N/O and N/C con­tacts for each external alarm connection.
3 amps at 480 VAC, 80% PF
Jumper Positions for Plug-In Relays: Jumpers W1, W2 and W3 perform the same functions for their respective relays, W1 for relay K1, W2 for relay K2, and W3 for relay K3. They can be located in any of 3 positions (A, B, C) independently of each other.
The 12 relays with form ‘C’ contacts are rated:
10 Amp, 120 VAC
10 Amp. 30 VDC
5-4
JUMPERS JUMPERS
Redistribution or publication of this document by any means, is strictly prohibited.
K1 K2 K3
J1, J2 WIRE
HARNESS PLUG
CONNECTIONS
FROM A11
RUN RELAY MODULE(S)
FIGURE 5-2. AUXILIARY RELAY BOARD (ARB)
5-5
TIME-DELAY MODULE (A15) (OPTIONAL)
Redistribution or publication of this document by any means, is strictly prohibited.
The start delay module is adjustable from 5 to 15 se­conds and the stop delay from 30 seconds to 30 minutes. Turn the delay adjusting potentiometers clockwise to increase delay and counterclockwise to decrease delay.
Remote Control Connections
Remote control connections are made at the termi­nal block (TB1) that is located on the time-delay module (Figure 5-3). Connect one or more remote switches across the remote terminal (TB1-5) of the time-delay module and the B+ terminal of the ECM (A11).
PRIMARY START-DISCONNECT
A11 - TB1-2
SECONDARY START-DISCONNECT
(A11 – TB1-3
START DELAY
POTENTIOMETER
TB1
12345 6
RUN SIGNAL OUT (A11 - TB1-6
RUN SIGNAL IN (REMOTE START/STOP CONTROL
STOP DELAY
POTENTIOMETER
B– (A11 - TB1-5
B+ (A11 - TB1-7)
FIGURE 5-3. PREHEAT/TIME-DELAY MODULE
5-6

6. DC Control Wiring (Sentinel Control)

Redistribution or publication of this document by any means, is strictly prohibited.
CONTROL WIRING
The generator set control panel box contains con­nection points for remote starting and switched B+ connections. Connections are made on the terminal block (TB1) located inside the control box (Figure 6-1).
Connect a remote switch across remote terminal (TB1-4) and B+ (TB1-3) for remote starting. Switched B+ auxiliary power is available when the generator set is running. When connecting custom­er accessories to the 12 volt B+ auxiliary terminals (TB1-1 & 2), do not allow the current exceed 7 amps.
If the distance between the genset and the remote station is less than 1000 feet (305 m), use 18 gauge stranded copper wire. If the distance is 1000 to 2000 feet (305 to 610 m), use 16 gauge stranded copper wire. Always run control circuit wiring in a separate metal conduit from AC power cables to avoid induc­ing currents that could cause problems within the control.
WARNING
HAZARDOUS VOLTAGE Touching uninsulated high voltage parts inside the con­trol panel box can result in severe personal inju­ry or death. Control wire installation must be done with care to avoid touching uninsulated live parts.
For your protection, stand on a dry wooden plat­form or rubber insulating mat, make sure your clothing and shoes are dry, remove jewelry and use tools with insulated handles.
CONTROL BOX
TB1
GROUND
5
REMOTE
4
B+
3
SWITCHED B+
2
SWITCHED B+
1
TB1
FIGURE 6-1. REMOTE CONTROL CONNECTION POINTS
6-1
DRY CONTACT MODULE (Optional)
POSITION
Redistribution or publication of this document by any means, is strictly prohibited.
The dry contract module provides the capability of attaching a remote monitor device. Connections are made to the terminals of relays K8 and K9 lo- cated on the dry contact module (Figure 6-2). A de­tailed connection diagram for the dry contact mod­ule is provided in Section 10.
The relay contact ratings are:
The following faults will activate relays K8 or K9 as follows:
RELAY K8 RELAY K9
Over Crank Low Oil Pressure High Engine Temperature Low Coolant Level Overspeed
Low Fuel Pressure
CONTACT
Max carry/break 40 A 30 A 20 A 10 A
Max make 100 A 60 A 50 A 20 A
12V COIL
VOLTAGE
N.O. N.C. N.O. N.C.
24V COIL
VOLTAGE
CONTROL BOX
DRY CONTACT
MODULE
FIGURE 6-2. DRY CONTACT MODULE
6-2

7. AC Electrical Connections

Redistribution or publication of this document by any means, is strictly prohibited.
GENERAL
This section provides the procedure that is used to connect the AC electrical system of the genset.
Disconnect the battery charger and the battery cables (negative [–] first) to prevent accidental start­ing while working on the set.
CAUTION
charger from its AC source before disconnect­ing the battery cables. Otherwise, disconnect­ing the cables can result in voltage spikes high enough to damage the DC control circuits of the set.
WARNING
set while working on it can cause severe per­sonal injury or death. Prevent accidental start­ing by disconnecting the starting battery cables (negative [–] first).
Make certain battery area has been well venti­lated before servicing battery, especially if a battery charger has been connected. Arcing can ignite explosive hydrogen gas given off by batteries, causing severe personal injury. Arc­ing can occur when cable is removed or re-at­tached, or when negative (–) battery cable is connected and a tool used to connect or discon­nect positive (+) battery cable touches frame or other grounded metal part of the set.
Always disconnect a battery
Accidental starting of the generator
Connecting the genset AC electrical system in­volves:
Installation of transfer switch (standby service
only)
Generator voltage connections
Load connection
Standard and optional AC equipment connec-
tions (e.g., control box heater, coolant heater, etc.).
Local regulations often require that wiring connec­tions be made by a licensed electrician, and that the installation be inspected and approved before op­eration. All connections, wire sizes, materials used, etc. must conform to the requirements of electrical codes in effect at the installation site.
Generator set output requires approved protective devices or means in compliance with the NEC (Na­tional Electric Code) and applicable local regula­tions.
WARNING
electrocution, resulting in severe personal inju­ry or death and/or property and equipment dam­age.
Before starting the genset, verify that all electrical connections are secure, and that all wiring is com­plete. Replace and secure any access panels that have been removed during installation. Check that the load cables from the genset are properly con­nected.
Improper wiring can cause a fire or
WARNING
this section should be done only by persons trained and experienced in electrical mainte­nance. Improper procedures may result in property damage, bodily injury or death.
Each of the operations described in
WARNING
cause electrocution or property damage. Do not connect to any building electrical system ex­cept through an approved device and after building main switch is opened.
Backfeed to utility system can
7-1
TRANSFER SWITCH
Redistribution or publication of this document by any means, is strictly prohibited.
If the installation is for standby service, a transfer switch must be used for switching the load from the normal power source to the genset (see Figure 7-1). Either a manual or automatic transfer switch may be used. Follow the installation instructions provided with the transfer switch when connecting the load and control wiring.
LOAD
NORMAL SOURCE
FIGURE 7-1. TYPICAL LOAD TRANSFER
FUNCTION
GENSET
7-2
AC WIRING
Redistribution or publication of this document by any means, is strictly prohibited.
Generator Voltage Connections
The generator output voltage and maximum current rating are specified on the generator set nameplate. Line-to-neutral voltage is always the lower voltage shown and line-to-line voltage is the higher rating.
mounted circuit breakers are provided, connections can be made directly to the circuit breakers.
The terminals of the reconnection block are stamped U, V, W and N to indicate the line and neu­tral connections. (Reference: U, V, and W corre­spond with L1, L2 and L3; and N with L0 respec­tively).
These generators can be configured for the volt­ages shown in the Reconnection Diagram on the side access cover of the control housing. Most of these voltages must be reconnected by the installer to give the voltage required by the installation. Be­fore shipping, the factory tests the generator set output by connecting the generator to produce a particular test voltage. The generator may be con­nected at the factory to produce a specified voltage per customer order. The installer must always check the stator lead terminal block connections and perform any necessary reconnect to obtain the voltage desired.
Some generator sets are capable of producing a wide range of voltages and connection configura­tions, others have specific limited capabilities. Re­fer to wiring diagram and generator voltages (from the nameplate) when reviewing the voltage connec­tion information and use the electrical schematic supplied with your generator set when actually per­forming load connections.
CAUTION
Reconnecting factory connected generator sets to higher voltages can exceed the voltage capability of the specific generator windings and damage the generator. Consult with your distributor before performing recon­nection for a different voltage.
CAUTION
Reconnecting factory connected generator sets to lower voltages can reduce set ratings, and also render line circuit breakers too small. Consult with your distributor before per­forming reconnection for a different voltage.
Load Connections
Flexible conduit and stranded conductors must be used for connections to take up movement of the generator set.
All loads are connected to the generator by bolting stranded load wires to the appropriate terminals on the generator reconnection terminal block or if
Load Balancing
When connecting loads to the generator set, bal­ance the loads so the current flow from each line ter­minal (L1, L2 and L3) is about the same. This is es­pecially important if both single phase and three phase loads are connected. Any combination of sin­gle phase and three phase loading can be used as long as each line current is about the same, within 10 percent of median value and no line current ex­ceeds the nameplate rating of the generator. Check the current flow from each line after connections by observing the control panel ammeter (if provided).
Current Transformers
Current transformers (CT’s) are required on gen­sets that contain AC meters. The CT’s must be installed as noted in the following CT Installation Requirements.
Refer to the Reconnection Diagram to identify the output leads/phase that must be routed through each CT, and also appropriate transformer post selection for meter sensing leads. The transformers are labeled CT21, CT22 and CT23 on the recon­nection wiring diagram. (The Reconnection Dia­gram is located on the upper side cover of the con­trol housing.)
CT Installation Requirements:
A. The CT has a dot on one side. This dot must be
facing toward the generator (conventional cur­rent flowing into the dot). A dot is also used to indicate pin 1 of the CT.
B. CT21 – U load leads (A phase),
CT22 – V load leads (B phase) CT23 – W load leads (C phase)
C. Route the appropriate load wires through each
CT.
D. The CT’s have dual secondaries (3 pins). The
CT secondary wire marked 1 is connected to pin 1 of the CT. CT secondary wire marked 2/3 is connected to pin 2 for high voltage gensets or to pin 3 for low voltage gensets. (Refer to Re­connection Diagram.)
7-3
Grounding
Redistribution or publication of this document by any means, is strictly prohibited.
The following is a brief description of system and equipment grounding of permanently installed AC generators within a facility wiring system. It is important to follow the requirements of the local electrical code.
WARNING
Contact with electrical equipment can result in severe personal injury or death. It is extremely important that bonding and equip­ment grounding be properly done. All metallic parts that could become energized under ab­normal conditions must be properly grounded.
Figure 7-2 illustrates typical system grounding for a 3-pole and a 4-pole automatic transfer switch (ATS). In the 3-pole ATS, note that the generator neutral is connected to the ATS and is NOT bonded to ground at the generator. In the 4-pole ATS sys­tem, a grounding electrode conductor and a bond­ing jumper are used to connect the generator neu­tral to ground. In some installations, a CT may be required for ground fault monitoring (refer to Figure 7-2 for CT location).
3-POLE AUTOMATIC TRANSFER SWITCH
3
TO UTILITY
SERVICE
N
Typical requirements for bonding and grounding are given in the National Electrical Code, Article
250. All connections, wire sizes, etc. must conform to the requirements of the electrical codes in effect at the installation site.
GENERATOR SETSERVICE ENTRANCE
3
N
TO UTILITY
SERVICE
SERVICE ENTRANCE
FIGURE 7-2. TYPICAL SYSTEM GROUNDING ONE-LINE DIAGRAMS
4-POLE AUTOMATIC TRANSFER SWITCH
4 WIRES & GROUND
TO LOAD
GENERATOR SET
4 WIRES & GROUND
TO LOAD
BONDING
JUMPER
CT LOCATION IF REQUIRED FOR
GFI MONITORING
GROUNDING ELECTRODE
CONDUCTOR
7-4
CONTROL HEATER (OPTIONAL)
Redistribution or publication of this document by any means, is strictly prohibited.
A control heater (Figure 7-3) provides a means of humidity /temperature control for the Detector con­trol box interior. It protects the components when
the generator set is subjected to varying ambient air conditions during extended periods of non-use.
The heater is equipped with a power cord that termi­nates with a 120V or 220V NEMA plug.
HEATER
TO ACCESSORY BOX
A40–TB1-36 & 37
(PCC CONTROL)
FIGURE 7-3. OPTIONAL CONTROL HEATER
TO 120/240 VAC SUPPLY
(DETECTOR CONTROL)
BOTTOM VIEW OF
CONTROL BOX
7-5
COOLANT HEATER (OPTIONAL)
Redistribution or publication of this document by any means, is strictly prohibited.
A coolant heater (emersion or tank) is used to keep the engine coolant warm when the engine is shut down. It heats and circulates the coolant within the engine. This reduces startup time and lessens en­gine wear caused by cold starts. It is electrically op­erated and thermostatically controlled.
The heater is equipped with a power cord that termi­nates with a 120V or 220V NEMA plug.
Connect the heater to a source of power that will be on during the time the engine is not running. Be sure the voltage rating is correct for the heater element rating.
WARNING
The coolant heater must not be op­erated while the cooling system is empty or damage to the heater will occur.
TUBE
HOSE
OUTLET
TUBE
HOSE
HEATER
POWER
PLUG
INLET
FIGURE 7-4. COOLANT HEATER
7-6
GENERATOR HEATER (OPTIONAL)
Redistribution or publication of this document by any means, is strictly prohibited.
A generator heater(s) is used to help keep the gen­erator free of condensation when the generator set is not running. During cool and humid conditions, condensation may form within a generator, creating flashing and shock hazards.
Figure 7-5 illustrates the installation of two heater elements. Connect the heater(s) to a source of pow­er that will be on during the time the engine is not running. Power connections are made to the termi­nal block in the heater terminal box. Be sure the volt­age rating is correct for the heater element rating.
WARNING
Water or moisture inside a genera­tor increases the possibility of flashing and electrical shock, which can cause equipment damage and severe personal injury or death. Do not use a generator which is not dry inside and out.
HEATER
LEADS
HEATER
HEATER
TERMINAL BOX
(VIEW AA)
FIGURE 7-5. TYPICAL GENERATOR HEATER INSTALLATION
7-7
Redistribution or publication of this document by any means, is strictly prohibited.
7-8

8. Prestart Preparation (Detector/Sentinel)

Redistribution or publication of this document by any means, is strictly prohibited.
GENERAL
Before attempting the initial start of the generator set, be sure to complete the Installation Checklist in Section 9.
ELECTRICAL SYSTEM
Verify all electrical connections are secure and all wiring is complete and inspected. Replace and se­cure any access panels that may have been re­moved during installation.
Battery Connections
WARNING
set can cause severe personal injury or death. Make sure that the Run/Off/Auto switch on the control panel is set to the Off position before connecting the battery cables.
Starting the unit requires a 12 volt battery. Connect positive battery cable before connecting negative battery cable to prevent arcing.
Accidental starting of the generator
Service the battery as necessary. If an automatic transfer switch is installed without a built-in charge circuit, connect a separate battery charger.
WARNING
can cause severe personal injury. Always con­nect battery negative last to prevent arcing.
WARNING
ventilated prior to servicing near it. Lead-acid batteries emit a highly explosive hydrogen gas that can be ignited by arcing, sparking, smok­ing, etc.. Ignition of these gases can cause se­vere personal injury.
Ignition of explosive battery gases
Be sure battery area has been well-
STARTING
Refer to the generator set Operator’s manual for im­portant safety precautions and recommended pro­cedures to start the genset and to confirm proper operation. Start the generator set and verify all en­gine and generator gauges are displaying the cor­rect values.
8-1
Redistribution or publication of this document by any means, is strictly prohibited.
8-2

9. Installation Checklist

Redistribution or publication of this document by any means, is strictly prohibited.
GENERAL
Generator set wattage capacity is sufficient to handle maximum anticipated load.
At least 3 feet of clearance is provided around entire genset for servicing and ventilation.
Generator set is located in an area not subject to flooding.
All operating personnel have read and are familiar with Operator’s Manual.
All operators have been thoroughly briefed on correct operation and exercise procedures.
All operators have been thoroughly briefed on preventive maintenance procedures.
All operators have read and understand all Safety Precautions in Operator’s Manual.
GENSET SUPPORT
Floor, roof or earth on which the genset rests is strong enough and will not allow shifting or movement. Observe local codes on soil bearing capacity due to freezing and thawing.
Generator set is properly supported and retained to approved base which is separate and inde­pendent of the surface on which it sits. Vibration isolators are installed between base and set.
Supporting base is large enough and is of non-combustible material - extends 12-inches all around set.
COOLING AIR FLOW
Generator set air inlet is faced into direction of strongest, prevailing winds.
Air inlet openings are unrestricted and at least 1-1/2 times larger than air outlet area.
Cooling air outlet is on downwind side of building (if not, wind barrier is constructed).
Proper ducting material (sheet metal, canvas) is used between radiator and air outlet.
FUEL SYSTEM
Fuel tanks meet or exceed all local, state or national codes.
Fuel lines are properly installed, supported and protected against damage.
Approved flexible fuel line is installed between main fuel supply line and the generator set’s fuel system, near the generator set, to protect the fuel system from damage caused by vibration, expansion and contraction.
Fuel line shutoff valves are installed to prevent fuel flow in case of leaks.
No fuel leaks are found in supply line or engine fuel system.
9-1
EXHAUST SYSTEM
Redistribution or publication of this document by any means, is strictly prohibited.
Operators are thoroughly briefed on the dangers of carbon monoxide gas, preventing the buildup of this gas in inhabited areas.
Areas around set are well ventilated. No possibility of exhaust fumes entering building doors, windows, or intake fans.
Exhaust gases are piped safely outside and away from building.
The correct length of approved rigid pipe is connected to the genset flexible pipe using approved securing methods with no weight resting on engine exhaust components. There are no bends in flex section.
Condensation drain is provided in lowest section of exhaust piping.
Exhaust piping is insulated to guard against burns to personnel.
Exhaust piping passing through walls or ceilings have approved fire-proof materials and are in compliance with all codes.
Exhaust piping is large enough in diameter to prevent back pressure on engine.
Rain cap is installed if required.
AC AND DC WIRING
Wire sizes, insulation, conduits and connection methods all meet applicable codes.
AC and DC wires are separated in their own conduit to prevent electrical induction.
All load, line and generator connections are proper and correct.
GENSET PRESTART
Generator set engine is properly serviced with oil and coolant.
Batteries are properly installed, serviced and charged.
Battery charger and engine coolant heater are connected and operational.
All genset covers and safety shields are installed properly.
All fuel and coolant shutoff valves are operational.
9-2

10. Wiring Diagrams

Redistribution or publication of this document by any means, is strictly prohibited.
GENERAL
This section consists of the schematic and connec­tion wiring diagrams referenced in the text. The fol­lowing drawings are included.
Detector Control
Page 10-2 – Customer Connections at the En-
gine Monitor Board (Detector Control)
Page 10-3 – Customer Connections at the Aux-
iliary Relay Board (Detector Control)
Page 10-4 – Accessory Interconnect Diagram
(Detector Control)
Sentinel Control
Page 10-5 – DC Wiring (Sentinel)
10-1
10-2
CUSTOMER CONNECTIONS AT THE ENGINE MONITOR BOARD (DETECTOR CONTROL)
TB2-1 (FAULT 2) GROUND INPUT FROM SENDER
TB2-2 (FAULT 2) GROUND OUTPUT TO LIGHT/RELAY*
TB2-3 (FAULT 1) GROUND INPUT FROM SENDER
TB2-4 (FAULT 1) GROUND OUTPUT TO LIGHT/RELAY*
TB2-6 (OVERCRANK FAULT) GROUND OUTPUT TO LIGHT/RELAY*
TB2-7 (OVERSPEED FAULT) GROUND OUTPUT TO LIGHT/RELAY*
TB2-8 (HIGH ENGINE TEMPERATURE FAULT) GROUND OUTPUT TO LIGHT/RELAY*
TB2-9 (LOW OIL PRESSURE FAULT) GROUND OUTPUT TO LIGHT/RELAY*
TB2-11 (PRE-LOW OIL PRESSURE WARNING) GROUND OUTPUT TO LIGHT/RELAY*
TB2-13 (LOW ENGINE TEMPERATURE WARNING) GROUND OUTPUT TO LIGHT/RELAY*
TB2-5 (REMOTE RESET) MOMENTARY CONTACT TO GROUND
TB2-10 (PRE-HIGH ENGINE TEMPERATURE WARNING) GROUND OUTPUT TO LIGHT/RELAY*
TB2-12 (SWITCH OFF WARNING) GROUND OUTPUT TO LIGHT/RELAY*
TB2-14 (LOW FUEL WARNING) GROUND INPUT FROM SENDER
TB2-15 (LOW FUEL WARNING) GROUND OUTPUT TO LIGHT/RELAY*
TB2-16 (EMERGENCY SHUT DOWN) MOMENTARY CONTACT TO GROUND
TB1-9 (B+ INPUT) BATTERY POSITIVE (+) CONNECTION
TB1-8 (START SOLENOID) FUSED AT 20 AMPS
TB1-7 (B+ OUTPUT) OUTPUT TO TIME DELAY START/STOP MODULE A15 (WHEN USED),
FUSED AT 15 AMPS, AVAILABLE WHEN THE STARTING BATTERIES ARE CONNECTED
TB1-6 (REMOTE START) CONNECTED TO TIME DELAY START/STOP MODULE A15 (WHEN USED). CONNECT
REMOTE START CONTACT OF THE AUTOMATIC TRANSFER SWITCH TO TERMINAL TB1-5 OF MODULE A15
(WHEN USED) OR TB1-6 OF EMB
TB1-5 (GROUND)
TB1-4 (COMMON ALARM B+ OUTPUT) 4 AMP RATED DEVICE MAXIMUM
TB1-3 (RUN) CONNECTED TO TIME DELAY START/STOP MODULE A15 (WHEN USED)
TB1-2 (DC DISCONNECT) CONNECTED TO TIME DELAY START/STOP MODULE A15 (WHEN USED)
+
TB1-10 (SWITCHED B+ OUTPUT) FUSED AT 20 AMPS, ENERGIZED WHEN THE
START SIGNAL IS APPLIED AND DE-ENERGIZED AT SHUTDOWN (NORMAL AND FAULT)
CUSTOMER SUPPLIED WIRING
FACTORY WIRING
* 0.5 AMP RATED DEVICE MAXIMUM
K12
K11
A15
Redistribution or publication of this document by any means, is strictly prohibited.
CUSTOMER CONNECTIONS AT THE AUXILIARY RELAY BOARD (DETECTOR CONTROL)
10-3
THE TERMINALS IN THE SHADED BOXES ARE FOR CUSTOMER CONNECTIONS
625-2712
NO. 300Ć4111 REV. B MODIFIED
THIS IS A REPRESENTATIVE (GENERIC) SCHEMATIC/WIRING DIAGRAM. FOR TROUBLESHOOTING, REFER TO THE WIRING DIAGRAM PACKAGE THAT WAS INCLUDED WITH YOUR GENSET.
Redistribution or publication of this document by any means, is strictly prohibited.
10-4
ACCESSORY INTERCONNECT DIAGRAM (DETECTOR CONTROL)
No. 630Ć1345 sh 3 Rev. H Modified 02/28/96
THIS IS A REPRESENTATIVE (GENERIC) SCHEMATIC/WIRING DIAGRAM. FOR TROUBLESHOOTING, REFER TO THE WIRING DIAGRAM PACKAGE THAT WAS INCLUDED WITH YOUR GENSET.
Redistribution or publication of this document by any means, is strictly prohibited.
DC DIAGRAM (SENTINEL)
10-5
No. 612Ć6697 sh 3 of 4 Rev. M Sys: ProE Modified 4/13/98
Redistribution or publication of this document by any means, is strictly prohibited.
Cummins Power Generation
Redistribution or publication of this document by any means, is strictly prohibited.
1400 73rd Avenue N.E. Minneapolis, MN 55432 1-800-888-6626 763-574-5000 International Use Fax: 763-528-7229
Cummins is a registered trademark of Cummins Inc.
Loading...