Cummins Power Generation PowerCommand 3100 Series, DFHC, DFHD, DFHA, DFHB Installation Manual

...
Caution: This document contains mixed page sizes (8.5 x 11 or 11 x
17), which may affect printing. Please adjust your printer settings according to the size of each page you wish to print.
Installation Manual
PowerCommand Control
Generator Sets
Printed in U.S.A.
Models
DFHA, DFHB, DFHC, DFHD
960-0617E 10-2002

Table of Contents

Redistribution or publication of this document,
by any means, is strictly prohibited.
SECTION TITLE PAGE
IMPORTANT SAFETY INSTRUCTIONS iii. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1 INTRODUCTION
About this Manual 1-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Installation Overview 1-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2 SPECIFICATIONS 2-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3 MOUNTING THE GENERATOR SET
General 3-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Location 3-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Mounting 3-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Access to Set 3-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Vibration Isolators 3-4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Aligning Generator with Engine
(750 kW Generator Sets and Larger) 3-5. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4 MECHANICAL CONNECTIONS
General 4-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Fuel System 4-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Exhaust System 4-4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Ventilation and Cooling 4-6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5 DC CONTROL WIRING
Control Wiring 5-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
TB1 Remote Monitor/Control Connections 5-1. . . . . . . . . . . . . . . . . . . . . . . . . .
Run Relays (K11, K12, K13) 5-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Alarm Relay (K14) 5-4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
RTD Relay (Optional) 5-5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Thermistor Relay (Optional) 5-6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Diesel engine exhaust and some of its constituents are known to the State of California to cause cancer, birth defects, and other reproductive harm.
California
Proposition 65 Warning
i
SECTION TITLE PAGE
Redistribution or publication of this document,
by any means, is strictly prohibited.
6 AC ELECTRICAL CONNECTIONS
General 6-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Insulation Resistance (Megger) & Polarization Index (PI) Testing 6-2. . . . . . .
Transfer Switch 6-4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
AC Wiring 6-5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Control Heater (Optional) 6-7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Coolant Heater 6-8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Generator Heater 6-9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Fuel Transfer Pump 6-10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Ground Fault Alarm Relay (Optional) 6-12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7 PRESTART PREPARATION
General 7-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
PCC Power On/Standby Mode 7-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical System 7-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
PCC Options Prestart Checks 7-4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Starting 7-6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8 INSTALLATION CHECKLIST
General 8-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Generator Set Support 8-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Cooling Air Flow 8-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Diesel Fuel System 8-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Exhaust System 8-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
AC and DC Wiring 8-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Generator Set Prestart 8-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9 WIRING DIAGRAMS
General 9-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ii

IMPORTANT SAFETY INSTRUCTIONS

Redistribution or publication of this document,
by any means, is strictly prohibited.
SAVE THESE INSTRUCTIONS – This manual contains important instructions that should be followed during installation and maintenance of the generator and batter­ies.
Before operating the generator set (genset), read the Operator’s Manual and become familiar with it and the equipment. Safe and efficient operation can be
achieved only if the equipment is properly operated and maintained. Many accidents are caused by failure
to follow fundamental rules and precautions. The following symbols, found throughout this manual,
alert you to potentially dangerous conditions to the oper­ator, service personnel, or the equipment.
This symbol warns of immediate hazards which will result in severe personal in­jury or death.
WARNING
This symbol refers to a hazard or un­safe practice which can result in severe person­al injury or death.
CAUTION
This symbol refers to a hazard or un­safe practice which can result in personal injury or product or property damage.
FUEL AND FUMES ARE FLAMMABLE
Fire, explosion, and personal injury or death can result from improper practices.
DO NOT fill fuel tanks while engine is running, un-
less tanks are outside the engine compartment. Fuel contact with hot engine or exhaust is a potential fire hazard.
DO NOT permit any flame, cigarette, pilot light,
spark, arcing equipment, or other ignition source near the generator set or fuel tank.
Fuel lines must be adequately secured and free of
leaks. Fuel connection at the engine should be made with an approved flexible line. Do not use zinc coated or copper fuel lines with diesel fuel.
Be sure all fuel supplies have a positive shutoff
valve.
Be sure battery area has been well-ventilated prior
to servicing near it. Lead-acid batteries emit a highly explosive hydrogen gas that can be ignited by arc­ing, sparking, smoking, etc.
EXHAUST GASES ARE DEADLY
Provide an adequate exhaust system to properly
expel discharged gases away from enclosed or sheltered areas and areas where individuals are likely to congregate. Visually and audibly inspect the exhaust daily for leaks per the maintenance schedule. Make sure that exhaust manifolds are se­cured and not warped. Do not use exhaust gases to heat a compartment.
Be sure the unit is well ventilated.
Engine exhaust and some of its constituents are
known to the state of California to cause cancer, birth defects, and other reproductive harm.
MOVING PARTS CAN CAUSE SEVERE PERSONAL INJURY OR DEATH
Keep your hands, clothing, and jewelry away from moving parts.
Before starting work on the generator set, discon-
nect battery charger from its AC source, then dis­connect starting batteries, negative (–) cable first. This will prevent accidental starting.
Make sure that fasteners on the generator set are
secure. Tighten supports and clamps, keep guards in position over fans, drive belts, etc.
Do not wear loose clothing or jewelry in the vicinity of
moving parts, or while working on electrical equip­ment. Loose clothing and jewelry can become caught in moving parts.
If adjustment must be made while the unit is run-
ning, use extreme caution around hot manifolds, moving parts, etc.
DO NOT OPERATE IN FLAMMABLE AND EXPLOSIVE ENVIRONMENTS
Flammable vapor can cause an engine to overspeed and become difficult to stop, resulting in possible fire, explo­sion, severe personal injury and death. Do not operate a genset where a flammable vapor environment can be created by fuel spill, leak, etc., unless the genset is equipped with an automatic safety device to block the air intake and stop the engine. The owners and operators of the genset are solely responsible for operating the gen­set safely. Contact your authorized Cummins Power Generation distributor for more information.
LS-14M
iii
ELECTRICAL SHOCK CAN CAUSE
Redistribution or publication of this document,
by any means, is strictly prohibited.
SEVERE PERSONAL INJURY OR DEATH
Remove electric power before removing protective
shields or touching electrical equipment. Use rub­ber insulative mats placed on dry wood platforms over floors that are metal or concrete when around electrical equipment. Do not wear damp clothing (particularly wet shoes) or allow skin surface to be damp when handling electrical equipment. Do not wear jewelry. Jewelry can short out electrical con­tacts and cause shock or burning.
Use extreme caution when working on electrical
components. High voltages can cause injury or death. DO NOT tamper with interlocks.
Follow all applicable state and local electrical
codes. Have all electrical installations performed by a qualified licensed electrician. Tag and lock open switches to avoid accidental closure.
DO NOT CONNECT GENERATOR SET DIRECT-
LY TO ANY BUILDING ELECTRICAL SYSTEM. Hazardous voltages can flow from the generator set into the utility line. This creates a potential for elec­trocution or property damage. Connect only through an approved isolation switch or an ap­proved paralleling device.
MEDIUM VOLTAGE GENERATOR SETS (601V to 15kV)
Medium voltage acts differently than low voltage.
Special equipment and training is required to work on or around medium voltage equipment. Operation and maintenance must be done only by persons trained and qualified to work on such devices. Im­proper use or procedures will result in severe per­sonal injury or death.
Do not work on energized equipment. Unauthorized
personnel must not be permitted near energized equipment. Due to the nature of medium voltage electrical equipment, induced voltage remains even after the equipment is disconnected from the power source. Plan the time for maintenance with autho­rized personnel so that the equipment can be de-en­ergized and safely grounded.
GENERAL SAFETY PRECAUTIONS
Coolants under pressure have a higher boiling point
than water. DO NOT open a radiator or heat ex­changer pressure cap while the engine is running. Allow the generator set to cool and bleed the system pressure first.
Used engine oils have been identified by some state
or federal agencies as causing cancer or reproduc­tive toxicity . When checking or changing engine oil, take care not to ingest, breathe the fumes, or con­tact used oil.
Keep multi-class ABC fire extinguishers handy.
Class A fires involve ordinary combustible materials such as wood and cloth; Class B fires, combustible and flammable liquid fuels and gaseous fuels; Class C fires, live electrical equipment. (ref. NFP A No. 10).
Make sure that rags are not left on or near the en-
gine.
Make sure generator set is mounted in a manner to
prevent combustible materials from accumulating under the unit.
Remove all unnecessary grease and oil from the
unit. Accumulated grease and oil can cause over­heating and engine damage which present a poten­tial fire hazard.
Keep the generator set and the surrounding area
clean and free from obstructions. Remove any de­bris from the set and keep the floor clean and dry.
Do not work on this equipment when mentally or
physically fatigued, or after consuming any alcohol or drug that makes the operation of equipment un­safe.
Substances in exhaust gases have been identified
by some state or federal agencies as causing can­cer or reproductive toxicity. Take care not to breath or ingest or come into contact with exhaust gases.
Do not store any flammable liquids, such as fuel,
cleaners, oil, etc., near the generator set. A fire or explosion could result.
Wear hearing protection when going near an oper-
ating generator set.
To prevent serious burns, avoid contact with hot
metal parts such as radiator, turbo charger and ex­haust system.
KEEP THIS MANUAL NEAR THE GENSET FOR EASY REFERENCE
iv

1. Introduction

Redistribution or publication of this document,
by any means, is strictly prohibited.
ABOUT THIS MANUAL
This manual covers models produced under the Cummins tion brand names.
This manual provides installation instructions for the generator set models listed on the front cover. This includes the following information:
/Onan and Cummins Power Genera-
Mounting Recommendations - for fastening generator set to base and space requirements for normal operation and service.
Mechanical Connections Electrical Con­nections - covers most aspects of the genera-
tor set installation. Prestart – checklist of items or procedures
needed to prepare generator set for operation.
Initial Startup – test complete system to en­sure proper installation, satisfactory perfor­mance, and safe operation. Refer to Operators Manual for troubleshooting information.
Installation Checklist – reference checks upon completion of installation.
This manual DOES NOT provide application infor­mation for selecting a generator set or designing the complete installation. If it is necessary to design the various integrated systems (fuel, exhaust, cooling, etc.), additional information is required. Review standard installation practices. For engineering data specific to the generator set, refer to the
fication
tion, refer to Application Manual T-030, ”Liquid Cooled Generator Sets”.
and
Data Sheets
. For application informa-
Speci-
1-1
INSTALLATION OVERVIEW
Redistribution or publication of this document,
by any means, is strictly prohibited.
These installation recommendations apply to typi­cal installations with standard model generator sets. Whenever possible, these recommendations also cover factory designed options or modifica­tions. However, because of the many variables in any installation, it is not possible to provide specific recommendations for every situation. If there are any questions not answered by this manual, contact your nearest Cummins Power Generation distribu­tor for assistance.
Application and Installation
A standby power system must be carefully planned and correctly installed for proper operation. This in­volves two essential elements: application and installation.
Application (as it applies to generator set installa­tions) refers to the design of the complete standby power system that usually includes power distribu­tion equipment, transfer switches, ventilation equip­ment, mounting pads, and cooling, exhaust, and fuel systems. Each component must be correctly designed so the complete system will function as in­tended. Application and design is an engineering function generally done by specifying engineers or other trained specialists. Specifying engineers are responsible for the design of the complete standby
system and for selecting the materials and products required.
Installation refers to the actual set–up and assem­bly of the standby power system. The installers set up and connect the various components of the sys­tem as specified in the system design plan. The complexity of the standby system normally requires the special skills of qualified electricians, plumbers, sheetmetal workers, etc. to complete the various segments of the installation. This is necessary so all components are assembled using standard methods and practices.
Safety Considerations
The generator set has been carefully designed to provide safe and efficient service when properly installed, maintained, and operated. However, the overall safety and reliability of the complete system is dependent on many factors outside the control of the generator set manufacturer. To avoid possible safety hazards, make all mechanical and electrical connections to the generator set exactly as speci­fied in this manual. All systems external to the gen­erator (fuel, exhaust, electrical, etc.) must comply with all applicable codes. Make certain all required inspections and tests have been completed and all code requirements have been satisfied before certi­fying the installation is complete and ready for ser­vice.
Copyright2001 Cummins Power Generation. All rights reserved. Cummins, Onan and PowerCommand are registered trademarks of Cummins Inc.
1-2

2. Specifications

Redistribution or publication of this document,
by any means, is strictly prohibited.
MODEL DFHA, DFHB DFHC DFHD
Cummins Diesel Series QST30 Generator kW Rating See Genset Nameplate for rating information. Coolant Capacity
Engine and Radiator
104° F (40° C) 122° F (50° C)
Lubrication System
Oil Capacity with Filters Oil Type*
Engine Fuel Connection
Inlet/Oultet Thread Size Refer to Generator Outline Drawing
Fuel Flow
Max. Fuel Inlet Pressure Max. Fuel Inlet Restriction Max. Fuel Return Restriction
Exhaust
Outlet Size Max. Allowable Back Pressure
Electrical System
Starting Voltage Battery
Group number CCA (minimum)
Cold Soak @ 0° F (-18° C)
* Refer to Cummins engine
Operation and Maintenance Manual
10 PSI (69 kPa)
4 in. Hg. (13.5 kPa)
10 in. Hg. (33.8 kPa)
6 in. (152 mm) flange 41 in. H2O (10.2 kPa)
for lubricating oil recommendations/specifications.
53 Gal (201 L) 57 Gal (216 L)
35 Gal (132 L)
10 PSI (69 kPa)
4 in. Hg. (13.5 kPa)
20 in. Hg. (67.6 kPa)
6 in. (152 mm) flange
27 in. H2O (6.7 kPa)
24 Volts DC
Two, 12 Volt
8D
1400
MODEL DFHA DFHB DFHC DFHD
US gph (L/hr) 54.7 (207.3) 57.8 (219) 60.2 (228.2) 69.3 (262.6)
FUEL CONSUMPTION (STANDBY/FULL LOAD/60HZ)
2-1
THIS PAGE LEFT INTENTIONALLY BLANK
Redistribution or publication of this document,
by any means, is strictly prohibited.
2-2

3. Mounting the Generator Set

Redistribution or publication of this document,
by any means, is strictly prohibited.
GENERAL
Generator set installations must be engineered so the generator set will function properly under the ex­pected load conditions. Use these instructions as a general guide only. Follow the instructions of the consulting engineer when locating or installing any components. The complete installation must com­ply with all local and state building codes, fire ordi­nances, and other applicable regulations.
Requirements to be considered prior to installation:
Level mounting surface
Adequate cooling air
Adequate fresh induction air
Discharge of generator set air
Non-combustible mounting surface.
Discharge of exhaust gases
Electrical connections
Accessibility for operation and servicing
Noise levels
Vibration isolation
LOCATION
Generator set location is decided mainly by related systems such as ventilation, wiring, fuel, and ex­haust. The set should be located as near as pos­sible to the main power service entrance. Exhaust must not be able to enter or accumulate around in­habited areas.
Provide a location away from extreme ambient tem­peratures and protect the generator set from ad­verse weather conditions.
WARNING
INCORRECT INSTALLATION, SERVICE OR PARTS REPLACEMENT CAN RESULT IN SEVERE PERSONAL INJURY, DEATH, AND/OR EQUIPMENT DAMAGE. SERVICE PERSONNEL MUST BE TRAINED AND EXPERIENCED TO PERFORM ELECTRICAL AND MECHANICAL COM­PONENT INSTALLATION.
IMPORTANT
DEPENDING ON Y O U R L O C ATION AND INTENDED USE, FEDERAL, STATE OR LOCAL LAWS AND REGULATIONS MAY REQUIRE YOU TO OBTAIN AN AIR QUALITY EMISSIONS PERMIT BEFORE BEGINNING INSTALLATION OF YOUR GENSET. BE SURE TO CONSULT LOCAL POLLUTION CONTROL OR AIR QUALITY AUTHORITIES BEFORE COMPLETING YOUR CONSTRUCTION PLANS.
3-1
MOUNTING
Redistribution or publication of this document,
by any means, is strictly prohibited.
Generator sets are mounted on a steel skid that pro­vides proper support. The engine-generator as­sembly is isolated from the skid frame by rubber mounts that provide adequate vibration isolation for normal installations. Where required by building codes or special isolation needs, generator sets may be mounted on rubber pads or mechanical spring isolators. The use of unapproved isolators may result in harmful resonances and may void the genset warranty.
Mount the generator set on a substantial and level base such as a concrete pad. A non-combustible material must be used for the pad.
Use 5/8 inch or 16 mm anchored mounting bolts to secure the vibration isolators to the base. Secure the vibration isolators to the skid using flat or bevel washer and hexagonal nut for each bolt (see Figure 3-1). The 1-1/2 x 6 inch pipe inserted over the mounting bolts allows minor adjustment of the bolts to align them to the holes in the subbase or vibration isolator.
MOUNTING
BASE
SUBBASE OR
VIBRATION
ISOLATOR
FLANGE
HEX NUT
FLAT OR BEVEL
WASHER
1-1/2 x 6 INCH
PIPE
12 IN.
(305 mm)
CONCRETE
Locate the isolators as shown on the generator set
Outline Drawing
referenced in the
Data Sheet
.
ACCESS TO SET
Generally, at least 1 meter (3 feet) of clearance should be provided on all sides of the generator set for maintenance and service access. A raised foundation or slab of 150 mm (6 inches) or more above floor level will make servicing easier.
Lighting should be adequate for operation, mainte­nance and service operations and should be con­nected on the load side of the transfer switch so that it is available at all times.
MOUNTING
BOLT
FIGURE 3-1. BOLT DIAGRAM
3-2
CONDENSATION
Redistribution or publication of this document,
by any means, is strictly prohibited.
DRAIN TRAP
AC POWER
WIRING
MUFFLER
THIMBLE
SWEEPING
ELBOW
FLEXIBLE
SECTION
DC CONTROL
WIRING
AIR IN
AIR OUTLET
DUCT
VIBRATION
ISOLATORS
(5 EACH SIDE)
CONCRETE BASE
IMPORTANT!
COOLING AIR INLET MUST BE AT LEAST 1-1/2 TIMES LARGER THAN RADIATOR DUCT OUTLET AREA ON RADIATOR COOLED MODELS
FLOW OF COOLING AIR AND HEATED AIR CAN BE CONTROLLED BY AUTOMATICALLY OPERATED LOUVRES
FIGURE 3-2. TYPICAL INSTALLATION
3-3
VIBRATION ISOLATORS
Redistribution or publication of this document,
by any means, is strictly prohibited.
Installation and Adjustment Procedure
1. Place the vibration isolators (Figure 3-3) on the genset support structure. The isolators should be shimmed or grouted to ensure that all of the isolator bases are within 0.25 inch (6 mm) elevation of each other. The surface that the isolator bases rest on must also be flat and lev­el.
2. Loosen the side snubber lock nuts so that the top plate of the isolator is free to move vertically and horizontally. Be sure that the top plate is correctly aligned with the base and springs.
3. Place the genset onto the isolators while align­ing the skid’s mounting with the threaded isola­tor hole. The top plates will move down and ap­proach the base of the isolator as load is ap­plied.
4. Once the genset is in position, the isolators may require adjusting so that the set is level.
The isolators are adjusted by inserting the lev­eling bolt through the skid and into the isolator (the leveling bolt’s locking nut should be threaded up towards the bolt head).
The leveling bolt will adjust the clearance be­tween the top plate and the isolator base. A nominal clearance of 0.25 inch (6 mm) or great­er is desired. This will provide sufficient clear­ance for the rocking that occurs during startup and shutdown. If the 0.25 inch (6 mm) clear­ance is not present, turn the leveling bolt until the desired clearance is achieved.
5. The genset may not be level yet; therefore, ad­just the leveling bolts until the set is level and sufficient clearance still remains. (Clearance on all isolators should be roughly equal). Once all isolators have been set, lock the leveling bolt in place with the lock nut.
6. The snubber nuts may remain loose and there­fore provide better isolation between the gen­set and support structure.
GENSET SKID
LEVELING BOLT
LOCK NUT
CLEARANCE
SNUBBER
BASE
FIGURE 3-3. VIBRATION ISOLATORS
3-4
ALIGNING GENERATOR WITH ENGINE
Redistribution or publication of this document,
by any means, is strictly prohibited.
(750 kW GENSETS AND LARGER)
Proper alignment of the generator and engine as­semblies is necessary to avoid premature wear and improper operation of the genset. Review the fol­lowing alignment conditions and procedures for aligning the generator assembly to engine flywheel housing.
Angular Misalignment
Angular misalignment is the result of the generator bearing center axis not aligning with axis of the en­gine crankshaft. This condition creates an angle between the generator shaft axis and the crank­shaft axis . The cause of this type of misalignment is usually shimming error.
Axial Misalignment
Axial misalignment is the result of the generator shaft axis not aligning with engine crankshaft axis. The tolerances in the bolted flywheel and drive disc connection may add up to displace the generator axially relative to the crankshaft axis.
Misalignment Symptoms
If the assembly is allowed to run under these condi­tions, the discs must flex in alternate directions twice for each engine revolution. It is important to minimize the amount of disc flexing since, if it is ex­cessive, the drive disc will crack. Although perfect bearing alignment is desirable, it is more important to keep disc deflection to the very minimum pos­sible. This procedure assumes that the pilot bore of the drive discs are in the exact center and the fly­wheel counterbore (pilot) has no practical runout. Under these conditions, perfect Angular alignment will be attained when no deflection of the discs is measured.
Excessive Axial alignment will cause more genera­tor vibration than Angular misalignment.
Axial misalignment needs to be checked only when an objectionable vibration is present.
Either type off misalignment may be present in a generator set assembly , with angular misalignment being the most common problem. Angular align­ment may also be ef fected by set installation condi­tions and/or mishandling during shipping of the gen­set.
GENERATOR AND ENGINE
CRANKSHAFT
CENTERLINE
SHIMS
SEE DETAIL A
CLAMP
MOUNTING BOLT
TO DISC
MEASUREMENT
FIGURE 3-4. ANGULAR ALIGNMENT MEASUREMENT
AXIAL
ALIGNMENT
DIAL INDICATOR
FLEX
DISCS
DETAIL A
3-5
Angular Alignment Procedure
Redistribution or publication of this document,
by any means, is strictly prohibited.
WARNING
set during this procedure presents the hazard of severe personal injury or death. Make sure to disconnect the negative (-) battery cable(s) be­fore beginning.
Accidental starting of the generator
-.015”.) The indicator is closer to the top and further away at the bottom. This example indicates that the generator bearing is high. Since the side readings are equal, the generator is centered side to side. T o lower the generator, remove equal shims from un­der both generator mounting feet. To approximate the amount of shims to remove or add:
Fasten a dial indicator to either the generator shaft or the cooling fan with the sensing point resting on the capscrew head or the flat surface of the drive disc at the bolt circle diameter, see Figure 3-4. Bar the engine over in a clockwise rotation as viewed from engine flywheel. Do not allow it to roll back on compression at the end of the travel of each read­ing. It is unnecessary to zero the indicator since the total indicator reading (T.I.R.) of the deflection mea­surement to the bolt heads is what is required. T.I.R. will be the sum of the maximum positive and nega­tive dial indicator readings as the engine completes one revolution.
CAUTION
Do not bar engine over by prying on fan blade. This may damage the blade and result in premature, sudden blade failure.
Sample Generator Runout Readings: When taking the deflection readings described, make a diagram similar to the example shown in Figure 3-5, with a total indicator reading of .025”. (The highest posi­tive value of +.010” and the largest negative value of
1. Measure the distance between the center of the generator shaft to the point the indicator is measuring at. (For example; a SAE 18 Disc coupling distance is 10.7”).
2. Measure the distance from the generator side of the flex discs to the center of the generator mounting bolt, refer to Figure 3-4. (For exam­ple; a HC6 Frame’s distance is 28.4”.)
3. Compare the distance measured in steps 1 and
2. (28.4” vs 10.7” or a 2.65 to 1 ratio.) Multiply this ratio times one half the T.I.R. (In our exam­ple, .025” divided by 2 is .0125”. This, times
2.65 equals .033”. Therefore, remove .033” of shims from under both mounting feet.)
In general, the T.I.R. should not be more than .001” for each inch of radius (center of shaft to indicator axis). If w e use our example of 10.7 inches, then the maximum T.I.R. would be .011”. This would only re­quire a correction of .014” from the T.I.R. of .025”. (A reading of +.002 at the top and –.009 at the bottom would fall within the satisfactory range.)
FIGURE 3-5. ANGULAR ALIGNMENT MEASUREMENT READINGS (EXAMPLE)
–.004
–.010
+.010
MEASURED AT
BOLT CIRCLE
DIAMETER
–.015
–.015
3-6
+.010
–.002
10.7 IN.
–.010
Axial Alignment Procedure
Redistribution or publication of this document,
by any means, is strictly prohibited.
Axial misalignment needs to be checked only when an objectionable vibration is present.
If excessive vibration remains after the angular alignment, check for concentric alignment of the generator shaft/engine crankshaft axis.
to the varying surface quality of the generator shaft’s drive disc mounting hub.
The goal of the Axial alignment is to reduce the vibration level of the genset while it is operating. A small improvement in the T.I.R. runout may have dramatic effects in the mechanically measured or physically observed vibration levels.
Fasten dial indicator holding device to skid base, engine block, or generator shell with a magnetic base or clamp and position so the sensor point of in ­dicator rests on the generator shaft hub, see Figure 3-6. Bar the engine over in a clockwise rotation as viewed from engine flywheel, through a couple of rotations. Record indicator readings in eight equal­ly spaced points around the shaft diameter. This will provide a T.I.R. for Axial shaft misalignment.
The maximum allowable T.I.R. runout is subjective, the optimal T.I.R. for runout would be .000 inches, however that may not be attainable. The recom­mendation of this procedure will be to reduce the measured T.I.R. runout by one half. Specific out-of­tolerance runout levels are difficult to establish due
ANGULAR ALIGNMENT
To correct for an out-of-tolerance T.I.R. indication, remove the capscrews connecting drive discs and flywheel. Mark the drive discs and flywheel with re­spect to each other. Rotate either the engine or gen­erator so that drive discs holes are repositioned 180 degrees from their original location. Put the drive discs capscrews back in and retorque. Recheck shaft alignment as before. If shaft T.I.R. runout re­mains unchanged then discs should be rotated to either 30, 60 or 90 degrees from original location to correct the out-of-tolerance condition. If the T.I.R. does not improve after repositioning, a closer in­spection of the flywheel pilot and drive disc runouts is required. This will help determine the cause of the Axial misalignment.
SEE DETAIL A
GENERATOR AND ENGINE
CRANKSHAFT
CENTERLINE
GENERATOR
SHAFT
HUB
DIAL
INDICATOR
CLAMP
FAN HOUSING
DETAIL A
FIGURE 3-6. AXIAL ALIGNMENT MEASUREMENT
3-7
THIS PAGE LEFT INTENTIONALLY BLANK
Redistribution or publication of this document,
by any means, is strictly prohibited.
3-8

4. Mechanical Connections

Redistribution or publication of this document,
by any means, is strictly prohibited.
GENERAL
The generator set mechanical system installation includes connecting the fuel, exhaust, ventilation and cooling systems. Before starting any type of fuel installation, all pertinent state and local codes must be complied with and the installation must be inspected before the unit is put in service.
FUEL SYSTEM
Cummins engines normally use ASTM No. 2 diesel fuel. They will, however , operate on alternate diesel fuels within the specifications shown in the Cum­mins engine
In all fuel system installations, cleanliness is of the upmost importance. Make every effort to prevent entrance of moisture, dirt or contaminants of any kind into the fuel system. Clean all fuel system com­ponents before installing.
A fuel filter/strainer/water separator of 100-120 mesh or equivalent (approximately 150 microns nominal) must be fitted between either the main tank and day tank or between the main tank and the engine.
Use only compatible metal fuel lines to avoid elec­trolysis when fuel lines must be buried. Buried fuel lines must be protected from corrosion.
CAUTION
lines, fittings or fuel tanks. Condensation in the tank and lines combines with the sulfur in diesel fuel to produce sulfuric acid. The molecular structure of the copper or galvanized lines or tanks reacts with the acid and contaminates the fuel.
An electric solenoid valve in the supply line is rec­ommended for all installations and required for in­door automatic or remote starting installations. Connect the solenoid wires to the genset “Switched B+” circuit to open the valve during generator set operation.
Operation and Maintenance Manual.
Never use galvanized or copper fuel
must not contain a shutoff device. Engine damage will occur if the engine is run with the return fuel lines blocked or restricted.
CAUTION
Never install shutoff device in fuel return line(s). If fuel return line(s) is blocked or exceeds fuel restriction limit, engine damage will occur.
Fuel Return Restriction (or Pressure) Limit: Fuel
return drain restriction (consisting of friction head and static head) between the engine injector return line connection and the fuel tank must not exceed the limit stated in the
Specification
section.
Fuel Lines – Routing
A flexible fuel hose(s) or section of flexible fuel hose(s) must be used between the engine’s fuel system and fuel supply and return line(s) to protect the fuel system from damage caused by vibration, expansion and contraction. Flexible lines for con­necting between the engine and the stationary fuel lines are supplied as standard equipment.
Installation of the fuel hose must be done according to all applicable codes and standards, and installa­tion recommendations provided by the manufactur­er. The supplied flexible hose is approved by the hose manufacture for use with the genset fuel type and product application.
Support fuel lines to restrain movement and prevent chaffing or contact with sharp edges, electrical wir­ing and hot exhaust parts.
WARNING
fuel, leading to severe personal injury or death. Do not route fuel lines near electrical wiring or hot exhaust parts.
Fuel lines must be routed and secured to maintain a 1/2 inch (12.7 mm) minimum clearance from electri­cal wiring and a 2 inch (51 mm) minimum clearance from hot exhaust parts.
Sparks and hot surfaces can ignite
Separate fuel return lines to the day tank or supply tank must be provided for each generator set in a multiple-set installation to prevent the return lines of idle sets from being pressurized. Fuel return lines
Engine Fuel Connections
Identification tags are attached to the fuel supply line and fuel return line connections.
4-1
ENGINE
Redistribution or publication of this document,
by any means, is strictly prohibited.
FUEL
PUMP
DAY TANK
FUEL TRANSFER PUMP ELECTRIC
MOTOR DRIVEN
SHUTOFF
VALVE
1 INCH
120 MESH FUEL
STRAINER
VENTED FILL CAP
FLOAT
SWITCH
LARGER OVER-
FLOW LINE
BAFFLE
INJECTOR FUEL
RETURN LINE
CONNECT TO
AC OUTPUT
SUPPLY
LINE
FUEL TANK
All models require a fuel return line from injectors to tank.
VENT LINE
FILL PIPE
FIGURE 4-1. TYPICAL FUEL SUPPLY INSTALLATION
Supply Tank
Locate the f uel tank as close as possible to the gen­erator set and within the restriction limitations of the fuel pump.
Install a fuel tank that has sufficient capacity to sup­ply the genset operating continuously at full rated load for the planned period of operation or power outage. Refer to data.
WARNING
hazards which can result in severe personal in­jury or death. Always use flexible tubing be­tween engine and fuel supply to avoid line fail­ure and leaks due to vibration. The fuel system must meet applicable codes.
If the fuel inlet restriction exceeds the defined limit due to the distance/customer-supplied plumbing between the genset and the main fuel tank, a trans-
Data Sheet
for fuel consumption
Fuel leaks create fire and explosion
fer tank (referred to as a day tank) and auxiliary pump will also be required. If an overhead main fuel tank is installed, a transfer tank and float valve will be required to prevent fuel head pressures from be­ing placed on the fuel system components.
For critical start applications, where generator sets are paralleled or must satisfy emergency start-time requirements, it is recommended that a fuel tank or reservoir be located such that the lowest possible fuel level is not less than 6 inches (150 mm) above the fuel pump inlet. This will prevent air from accu­mulating in the fuel line while the set is in standby, eliminating the period during startup when it has to be purged.
Fuel Inlet Pressure/Restriction Limit:: Engine
performance and fuel system durability will be com­promised if the fuel inlet pressure or restriction limits are not adhered to. Fuel inlet pressure or restriction must not exceed the limits stated in the
section.
tion
Specifica-
4-2
Day Tank (If Used)
Redistribution or publication of this document,
by any means, is strictly prohibited.
Fuel day tanks are used when fuel inlet restriction limits can not be met, or the supply tank is overhead and presents problems of high fuel head pressure for the fuel inlet and return lines.
Supply T ank Lower Than Engine:
lation, the day tank is installed near the generator set, below the fuel injection system and within the fuel inlet restriction limit. Install an auxiliary fuel pump, to pump fuel from the supply tank to the day tank. A float switch in the day tank controls opera­tion of the auxiliary fuel pump.
The supply tank top must be below the day tank top to prevent siphoning from the fuel supply to the day tank.
Provide a return line from the engine injection sys­tem return connection to the day tank. Plumb the re-
With this instal-
turn line to the bottom of day tank as shown in Fig­ure 4-1. Provide a day tank overflow line to the sup­ply tank in case the float switch fails to shut off the fuel transfer pump.
WARNING
Spilled fuel presents the hazard of fire or explosion which can result in severe per­sonal injury or death. Provide an overflow line to the supply tank from the day tank.
Supply Tank Higher Than Engine:
Install the day tank near the generator set, but below the fuel injec­tion system. Use fuel line at least as large as the fuel pump inlet. The engine fuel return line must enter the day tank.
Include a shutoff valve in the fuel line between the fuel supply tank and the day tank to stop fuel flow when the generator set is off.
WARNING
Spilled fuel can create environmental hazards. Check local requirements for containment
and prevention of draining to sewer and ground water.
4-3
EXHAUST SYSTEM
Redistribution or publication of this document,
by any means, is strictly prohibited.
Pipe exhaust gases to the outside of any enclosure. Locate the exhaust outlets away from any air inlets to avoid gases re-entering the enclosure. Exhaust installations are subject to various detrimental con­ditions such as extreme heat, infrequent operation and light loads. Regularly inspect the exhaust sys­tem both visually and audibly to see that the entire system remains fume tight and safe for operation.
WARNING
sult in severe personal injury or death. Use ex­treme care during installation to provide a tight exhaust system. Terminate exhaust pipe away from enclosed or sheltered areas, windows, doors and vents.
For indoor installation, the exhaust system must use sealed joint type fittings, (for example NPT fit­tings) to provide a tighter exhaust system. Use of slip type fittings (secured with a muffler clamp) may allow leakage of exhaust gases into the building.
WARNING
sult in severe personal injury or death. Use ex­treme care during installation to provide a tight exhaust system. Use NPT or equivalent type fit­tings for all indoor installations.
Use an approved thimble (Figure 4-2) where ex­haust pipes pass through wall or partitions. Insu­lated wall/roof thimbles are used where exhaust pipes pass through a combustible roof or wall. This includes structures, such as wood framing or insu­lated steel decking, etc. Uninsulated wall/roof thimbles are used where exhaust pipes pass through a non-combustible wall or roof, such as concrete. Refer to NFPA 37, Section 6-3. “Station­ary Combustion Engines and Gas Turbines” for ac-
Inhalation of exhaust gases can re-
Inhalation of exhaust gases can re-
cepted design practices. Build according to the code requirements in effect at the installation site.
WARNING
Hot exhaust pipes can start a fire and cause severe injury or death if improperly routed through walls. Use an approved thimble where exhaust pipes pass through walls or partitions.
WARNING
Inhalation of exhaust gases can re­sult in severe personal injury or death. Do not use exhaust heat to warm a room, compartment or storage area.
Rain caps are available for the discharge end of ver­tical exhaust pipes. The rain cap clamps onto the end of the pipe and opens due to exhaust discharge force from the generator set. When the generator set is stopped, the rain cap automatically closes, protecting the exhaust system from rain, snow, etc.
Use a section of flexible exhaust pipe between the engine and remainder of exhaust system. Support exhaust system to prevent weight from being ap­plied to engine exhaust outlet elbow/turbocharger connection.
CAUTION
Weight applied to the engine man­ifold can result in turbocharger damage. Sup­port the muffler and exhaust piping so no weight or stress is applied to engine exhaust el ­bow.
The exhaust system design should meet local code requirements.
Liability for injury, death, damage, and warranty ex­pense due to use of unapproved mufflers or modifi­cations becomes the responsibility of the person installing the unapproved muffler or performing the modification. Contact a Cummins Power Generation distributor for approved exhaust system parts.
4-4
Avoid sharp bends by using sweeping, long radius
Redistribution or publication of this document,
by any means, is strictly prohibited.
elbows and provide adequate support for muffler and tailpipe. Pitch a horizontal run of exhaust pipe DOWNWARD (away from engine) to allow any moisture condensation to drain away from the en­gine. If an exhaust pipe must be turned upward, install a condensation trap at the point where the rise begins (Figure 4-3).
Shield or insulate exhaust lines if there is danger of personal contact. Allow at least 12 inches (305 mm) of clearance if the pipes pass close to a combustible wall or partition. Before installing insulation on ex­haust system components, check the exhaust sys­tem for leaks while operating the genset under full load and correct all leaks.
RAIN CAP
9 INCH MIN
(230 mm)
VERTICAL
DRIP CAP
HOLES IN END
OF INNER
SLEEVE
ROOF
9 INCH MIN
(230 mm)
WARNING
Exhaust pipes are very hot and they can cause severe personal injury or death from direct contact or from fire hazard. Shield or in­sulate exhaust pipes if there is danger of per­sonal contact or when routed through walls or near other combustible materials.
HORIZONTAL
WALL OR PARTITION
FIGURE 4-2. MOUNTING EXHAUST THIMBLE
IF EXHAUST LINE MUST BE
PITCHED UPWARD, CONSTRUCT
A TRAP AT POINT OF RISE
AVOID SHARP BENDS
DRAIN CONDENSATION
TRAP PERIODICALLY
FIGURE 4-3. CONDENSATION TRAP
4-5
VENTILATION AND COOLING
Redistribution or publication of this document,
by any means, is strictly prohibited.
Generator sets create considerable heat that must be removed by proper ventilation. Outdoor installa­tions normally rely on natural air circulation but in­door installations need properly sized and posi­tioned vents for required airflow.
Vents and Ducts
For indoor installations, locate vents so incoming air passes through the immediate area of the installa­tion before exhausting. Install the air outlet higher than the air inlet to allow for convection air move­ment.
Size the vents and ducts so they are large enough to allow the required flow rate of air . The ”free area” of ducts must be as large as the exposed area of the radiator. Refer to the genset flow requirements and allowed airflow restriction.
Wind will restrict free airflow if it blows directly into the air outlet vent. Locate the outlet vent so the ef­fects of wind are eliminated. See Figure 4-4.
Data Sheet
for the air-
PREVAILING WINDS PREVAILING WINDS
FIGURE 4-4. WIND BARRIER
4-6
Dampers
Redistribution or publication of this document,
by any means, is strictly prohibited.
Dampers or louvres protect the genset and equip­ment room from the outside environment. Their op­eration of opening and closing should be controlled by operation of the genset.
In cooler climates movable or discharge dampers are used. These dampers allow the air to be recircu­lated back to the equipment room. This enables the equipment room to be heated while the genset en­gine is still cold, increasing the engine efficiency.
Radiator Set Requirements
Radiator set cooling air is drawn past the control end of the set by a pusher fan that blows air through the radiator (Figure 4-5). Locate the air inlet to the to the rear of the set. Make the inlet vent opening 1-1/2 to 2 times larger than the radiator area.
Louvers and screens over air inlet and outlet open­ings restrict air flow and vary widely in performance.
A louver assembly with narrow vanes, for example, tends to be more restrictive than one with wide vanes. The effective open area specified by the lou­ver or screen manufacturer should be used.
Locate the cooling air outlet directly in front of the ra­diator and as close as possible. The outlet opening must be at least as large as the radiator area. Length and shape of the air outlet duct should offer minimum restriction to airflow.
Attach a canvas or sheet metal duct to the flange and the air outlet opening using screws and nuts so duct can be removed for maintenance purposes. The duct prevents circulation of heated air. Before installing the duct, remove the radiator core guard.
Standard Radiator Cooling uses a set mounted radiator and engine pusher fan to cool engine water jacket. Air travels from the generator end of the set, across the engine and out through the radiator. An integral discharge duct adapter flange surrounds the radiator grille.]
INLET AIR
DAMPER
COOL AIR
* Louvers should close when room ambient is above 60
° F (16° C)
FIGURE 4-5. TYPICAL RADIATOR SET INSTALLATION
THERMOSTATIC AIR RE-
CIRCULATING DAMPER
*
RADIATOR FLEXIBLE DUCT
CONNECTOR
WIND/NOISE
BARRIER
HOT AIR
D
DISTANCE SHOULD NOT BE LESS THAN HEIGHT
OF RADIATOR
4-7
Remote Radiator Cooling (Optional) substitutes
Redistribution or publication of this document,
by any means, is strictly prohibited.
a remote mounted radiator and an electrically driv­en fan in place of mounted components. Removal of the radiator and the fan from the set reduces noise levels without forcing dependence on a con­tinuous cooling water supply (necessary with heat exchanger cooling). The remote radiator installa­tion must be completely protected against freezing.
Remote radiator plumbing will vary with installation. Follow recommendations given in Application Manual T-030. See product
Data Sheet
for friction
head and static head limits.
Before filling cooling system, check all hardware for security. This includes hose clamps, capscrews, fit­tings and connections. Use flexible coolant lines with heat exchanger or remote mounted radiator.
Engine Coolant Heater (Optional)
An optional coolant heater is available to keep the
engine warm for improved starting and code com­pliance. Connect the heater to a power source that will be energized when the engine is NOT running.
Heat Exchanger (Optional)
The optional heat exchanger (Figure 4-6) uses a shell and tube type heat exchanger instead of the standard radiator and fan. Engine jacket coolant cir­culates through the shell side of the heat exchanger while the cooling water is pumped through the tubes. Engine coolant and raw water do not mix.
This system may reduce set enclosure airflow re­quirements and noise levels. Proper operation de­pends on a constant supply of raw water for heat re­moval. Adjust the flow to maintain engine coolant temperature between165
° C) while viewing the water temperature gauge.
91 The engine coolant side of the system can be pro­tected from freezing; the raw water side cannot be protected.
° F and 195° F (74° C and
COOL AIR
WATER
SOLENOID
VALVE
VENTILATING
FAN
WARM
AIR
FLEXIBLE WA-
TER
CONNECTIONS
MOUNTED HEAT
EXCHANGER
RAW WATER
SUPPLY
RAW WATER DISCHARGE
FIGURE 4-6. TYPICAL HEAT EXCHANGER INSTALLATION
4-8

5. DC Control Wiring

Redistribution or publication of this document,
by any means, is strictly prohibited.
CONTROL WIRING
The generator set accessory box (Figure 5-1), which is located on the backside of the control hous­ing, contains connection points for remote control and monitor options.
CAUTION
Stranded copper wire must be used for all customer connections to the Accessory Box. Solid copper wire may break due to genset vibration.
TB1 REMOTE MONITOR/CONTROL
CONNECTIONS
Customer monitor/control connections are at­tached to terminal block TB1 (Figure 5-1). Optional equipment such as a remote annunciator panel, sensing devices used to monitor genset operation, remote start/stop switches, control box heater, bat­tery charger and etc. are attached to TB1. Refer to PCC Customer Connections diagram in Section 9.
TB1 Wiring
CAUTION
a separate metal conduit from AC power cables to avoid inducing currents that could cause problems within the control.
Always run control circuit wiring in
Digital Connections: Connection points, other
then relayed outputs, network, switched B+ and B+ are considered digital connections to terminal strip TB1. The type/gauge wire to use for these connec­tions are:
Less than 1000 feet (305m), use 20 gauge
stranded copper wire.
1000 to 2000 feet (305 to 610m), use 18 gauge
stranded copper wire.
Relay Connections: Due to the wide variety of de­vices that can be attached to the relay outputs of TB1, the electrical contractor must determine the gauge of the stranded copper wire that is used at this installation site. Refer to PCC Customer Con­nections diagram in Section 9 for the relay specifi­cations.
Network Connections: Refer to 900-0366
Command Network Installation and Operation
manual for the type/gauge wire to use for these con­nections.
Switched B+: (Fused at 10 amps.) Same as Relay Connection description.
B+: (Fused at 20 amps.) Same as Relay Connec­tion description.
Power-
5-1
TB1-40
Redistribution or publication of this document,
by any means, is strictly prohibited.
TB1-1
OPTIONAL
COMMON ALARM
RELAY K14
OPTIONAL RUN RELAYS
K11, K12 & K13
OPTIONAL RTD
RELAY
GOVERNOR
OUTPUT MODULE
A38
PT/CT BOARD A36
FIGURE 5-1. ACCESSORY BOX COMPONENTS
OPTIONAL
THERMISTOR
RELAY 160/140
VOLTAGE
REGULATOR
OUTPUT MODULE
A37
° C
5-2
RUN RELAYS (K11, K12, K13)
Redistribution or publication of this document,
by any means, is strictly prohibited.
The optional run relays are rail mounted inside the accessory box (Figure 5-1). The rail mount allows you to easily remove and replace the snap-on re­lays. The generator set can be equipped with one, two or three run relays.
The three-pole, double-throw run relays (Figure 5-2) are used to control auxiliary equipment such as
K11, K12, K13
fans, pumps and motorized air dampers. The run relays are energized when the generator set control receives a start signal.
The contacts are rated:
10 amps at 28 VDC or 120 VAC, 80%PF
6 amps at 240 VAC, 80%PF
3 amps at 480/600 VAC, 80%PF
A40-TB1-2
(SWITCHED B+)
K11, K12, K13
K11, K12, K13
K11
RUN RELAY
NO NC
COIL
COM
A40-TB1-4
(B-)
CUSTOMER
CONNECTIONS
K12
RUN RELAY
NO NC
K13
RUN RELAY
NO NC
FIGURE 5-2. OPTIONAL RUN RELAYS (K11, K12, K13)
5-3
ALARM RELAY (K14)
Redistribution or publication of this document,
by any means, is strictly prohibited.
The optional alarm relay is rail mounted inside the accessory box (Figure 5-1). The rail mount allows you to easily remove and replace the snap-on relay.
The three-pole, double-throw alarm relay (Figure 5-3) is often used to energize warning devices such
K14
as audible alarms. Any generator set warning or shutdown will energize the alarm relay.
The contacts are rated:
10 amps at 28 VDC or 120 VAC, 80%PF
6 amps at 240 VAC, 80%PF
3 amps at 480/600 VAC, 80%PF
A40-TB1-4
(GND)
A40-TB1-8
(COMMON ALARM)
K14
K14
JUMPER WIRE
REQUIRED FOR K14
RELAY OPTION
A40-TB1-1
(B+)
CUSTOMER
CONNECTIONS
K14
COMMON ALARM
NO NC
COIL
COM
A40-TB1-7
(COMMON ALARM)
FIGURE 5-3. OPTIONAL ALARM RELAY (K14)
5-4
RTD RELAY (OPTIONAL)
Redistribution or publication of this document,
by any means, is strictly prohibited.
The optional RTD relay is rail mounted inside the accessory box (Figure 5-1). This relay is used to monitor six separate temperature zones in the gen­erator windings using resistive temperature detec­tors (R TDs). The relay determines the sensed tem­perature and acts to isolate, alarm, or initiate cor­rective action.
LED’s indicate the state of the output relay (green for normal, red for tripped). Additional red LED’s are used to indicate which inputs exceed the setpoint.
The relay terminals 1 1, 12 and 14 are for customer connection. These terminals can be attached to any one of the four Customer Fault inputs on TB1 to pro­vide a warning/shutdown condition or to other cus­tomer warning devices.
The RTD relay (Figure 5-4) compares the six inputs to the predetermined setpoint (temperature set­point is factory adjusted). If one or more of the inputs exceed the setpoint, the output relay is energized.
TEMPERATURE RELAY CONNECTIONS
The contacts are rated:
240 VAC, 5 amps non-inductive
24 VDC, 25 amps resistive
TO RTD TERMINAL
BLOCK
OUTPUT RELAY
(CUSTOMER USE)
(–)(+)
A40TB1-4
24 VDC
FIGURE 5-4. RTD RELAY (OPTIONAL)
(GROUND) A40TB1-2
(SWITCHED B+)
5-5
TO RTD TERMINAL
BLOCK
THERMISTOR RELAY (OPTIONAL)
Redistribution or publication of this document,
by any means, is strictly prohibited.
(trip) when the thermistor chain resistance reaches 3000 ±500 ohms.
The optional thermistor relays are rail mounted in­side the accessory box (Figure 5-1). Each relay monitors three thermistors (one per phase) that are connected in series inside the generator. One se­ries or chain of thermistors are rated at 140 the other at 160
° C. The 140° C relay is commonly
° C and
used in a pre-alarm circuit. The relay will energize
THERMISTORS
BLUE
A BC
The relay terminals 1, 2 and 3 are for customer con­nection and are normally connected to a breaker shunt trip or a load shed circuit (Figure 5-5).
The contacts are rated:
3 amps at 250 VAC
1 amp at 480 VAC
WHITE/RED
A40-TB1-4
(GROUND)
A40-TB1-2
(SWITCHED B+)
FAULT CHANNELS
(CUSTOMER
CONNECTIONS)
RELAY CONTACTS
FIGURE 5-5. THERMISTOR RELAY (OPTIONAL)
5-6

6. AC Electrical Connections

Redistribution or publication of this document,
by any means, is strictly prohibited.
GENERAL
This section provides the procedure that is used to connect the AC electrical system of the genset.
Before making any AC electrical connections, make certain the generator set cannot be accidentally started. Move the Run/Off/Auto switch on the con­trol panel to the OFF position. T urn off or remove AC power from the battery charger and then remove the negative (–) battery cable from the set starting battery.
WARNING
can cause severe personal injury or death. Arc­ing at battery terminals, light switch or other equipment, flame, pilot lights and sparks can ig­nite battery gas. Do not smoke, or switch trouble light ON or OFF near battery. Discharge static electricity from body before touching bat­teries by first touching a grounded metal sur­face.
Ignition of explosive battery gases
WARNING
Each of the operations described in this section should be done only by persons trained and experienced in electrical mainte­nance. Improper procedures may result in prop­erty damage, bodily injury or death.
Connecting the genset AC electrical system in­volves:
Generator insulation check
Installation of transfer switch
Generator output voltage selection
Load cable connection
Standard and optional AC equipment connec-
tions (e.g., control box heater, coolant heater, etc.
Local regulations often require that wiring connec­tions be made by a licensed electrician, and that the installation be inspected and approved before op­eration. All connections, wire sizes, materials used, etc. must conform to the requirements of electrical codes in effect at the installation site.
Ventilate battery area before working on or near battery—Wear goggles—Stop genset and dis­connect charger before disconnecting battery cables—Disconnect negative (–) cable first and reconnect last.
CAUTION
Disconnect battery charger from AC source before disconnecting battery cables. Otherwise, disconnecting cables can result in voltage spikes damaging to DC control circuits of the set.
WARNING
Accidental starting of the generator set can cause severe personal injury or death. Prevent accidental starting by disconnecting the negative (–) cable from the battery terminal.
WARNING
Improper wiring can cause a fire or electrocution, resulting in severe personal inju­ry or death and/or property and equipment dam­age.
Before starting the genset, check to make sure that all electrical connections are secure, and that all wiring is complete. Replace and secure any access panels that have been removed during installation. Check that the load cables from the genset are properly connected.
WARNING
Backfeed to utility system can cause electrocution or property damage. Do not connect to any building electrical system except through an approved device and after building main switch is opened.
6-1
INSULATION RESISTANCE (MEGGER) &
Redistribution or publication of this document,
by any means, is strictly prohibited.
POLARIZATION INDEX (PI) TESTING
Megger and PI testing must be performed on all medium voltage (601 through 15,000 volts) genera­tor sets before initial start-up. PI testing for low volt­age (less than 600 volts) generator sets is recom­mended by Cummins Power Generation.
These tests are used to verify that the windings are dry before the generator set is operated and devel­ops a base line for future test comparison.
Before these tests can be performed on medium voltage generator sets, you must first perform the generator grounding procedure.
Generator Set Grounding Procedure
Prior to performing service or inspection proce­dures that may expose personnel to conductors normally energized with voltages greater than 600 volts, the following generator set grounding proce­dure must be followed.
3. Put on high voltage gloves with leather protec­tors.
4. Using two pre-tested voltage detection devices (of the proper rating), verify de-energized con­dition in the work area. (Retest voltage detec­tion devices immediately after verification of de-energized condition.)
5, Remove the metal cover from the generator
output box to gain access to generator load ter­minals.
6. Securely install the Grounding Cluster ground clamp to a verified “grounded” conductor.
WARNING
Hazardous voltage. Can cause severe personal injury or death. After DC voltage from the test equipment has been applied to the windings and ground, there will be a definite static charge on the wind­ings. Reconnect Grounding Cluster to re­move static charge from the winding after each generator test.
WARNING
No person should attempt to per­form these procedures unless they are fully trained in medium voltage grounding proce­dures and have the necessary safety tools and equipment. Persons who attempt these proce­dures without these qualification are at risk of severe injury or death due to high voltage elec­trical shock.
1. Open, lock-out and tag-out all sources of power to the immediate work area.
2. Disable the starting system of the generator set:
a. Disconnect the battery charger from its AC
source.
b. Remove the negative battery cable from
the battery.
c. Install a lockout device on the battery
cable end. (For engines equipped with an air-powered starting system, close air valve and install valve locking device.)
7. With the Grounding Cluster in place, you are protected from all static and/or induced charges that may have been present in the generator stator.
Leave grounds connected for one minute to in­sure static charge dissipation. Remove ground cluster and perform PI and/or any other tests required on the stator winding. Reconnect grounds if additional generator service is nec­essary.
8. When work on the generator set is complete, remove the Grounding Cluster in the reverse order of installation.
9. After getting clearance from all personnel in­volved in the lock-out/tag-out procedure, re­move all lock-out devices in reverse order of installation.
6-2
Megger and PI Test
Redistribution or publication of this document,
by any means, is strictly prohibited.
WARNING
volts, present special hazards of severe person­al injury or death. Even after genset shutdown, an electrical shock hazard may exist. Service personnel must be well trained and qualified to work with distribution voltages.
WARNING
through 15,000 volts) generator sets must be dry before the generator is operated. Failure to ensure dry windings before start-up may result in catastrophic failure, severe personal injury and death.
Megger Test: The megger test consists of applying
voltage for up to one minute. The highest resistance values shown in Table 6-1 should be obtained for a new generator with dry windings. For a set that has been in service, the resistance reading should not be less than the lower value shown.
PI Test: The PI test consists of applying a voltage between the winding and ground for ten minutes and recording resistance values at one minute and at ten minutes. The PI is the ratio of a ten minute reading in megohms divided by a one minute read­ing in megohms. A ratio of two or greater is consid­ered good for new and in-service sets.
If low readings are obtained, investigate the cause and correct before the generator set is returned to service.
1. Perform the
dure
Medium-voltage, 601 to 15,000
Windings of medium voltage (601
Generator Set Grounding Proce-
.
2. Disconnect plug J10 from the voltage regulator output stage module and the AC control input leads from the generator output terminals. The AC control leads are marked 4, 5, 6, 7 and 8. Refer to the reconnection diagram, which is lo­cated on the upper side cover of the control housing.
3. If the RTD (resistive thermal device) option is installed, ground all six resistive thermal device temperature leads. Each RTD has three leads, one red and two white leads. Total of 18 leads must be grounded.
Main Stator:
4. Remove and separate the neutral leads of the generator from the generator load terminal marked “N”.
5. Connect the megger between one phase of the stator and ground while grounding the other two phases and conduct the test. Refer to Table 6-1 for megger voltage selection and required resistance values.
Repeat this step in turn for the other two phases.
Main Rotor:
6. Disconnect the main rotor and voltage sup­pressor leads from terminals F1+ and F2– on the rotating rectifier assemblies and isloate them from ground. Tag and mark each lead with its terminal number (F1+ or F2–).
7. Connect the megger between one of the rotor leads and ground and conduct the test. Refer to Table 6-1 for megger voltage selection and re­quired resistance values.
GENERATOR VOLTAGE MEGGER VDC
600 VAC or less
601 thru 5000 VAC 2500 400 – 50
5001 thru 15000 VAC 5000 1000 – 200
TABLE 6-1. GENERATOR INSULATION RESISTANCE
MINIMUM RESISTANCE (MEG)
SETTING
500 5.0 – 1.0 5.0 – 1.0
1000
1000 5.0 – 1.0
MAIN STATOR MAIN ROTOR
6-3
5.0 – 1.0
TRANSFER SWITCH
Redistribution or publication of this document,
by any means, is strictly prohibited.
If the installation is for standby service, a transfer switch must be used for switching the load from the normal power source to the genset (see Figure 6-1). Follow the installation instructions provided with the transfer switch when connecting the load and con­trol wiring.
LOAD
NORMAL SOURCE
FIGURE 6-1. TYPICAL LOAD TRANSFER
FUNCTION
GENSET
6-4
AC WIRING
Redistribution or publication of this document,
by any means, is strictly prohibited.
Generator Voltage Connections
The available generator output voltages and maxi­mum current ratings are specified on the generator set nameplate. Line-to-neutral voltage is always the lower voltage shown and line-to-line voltage is the higher rating.
All loads are connected to the generator by bolting stranded load wires to the appropriate terminals on the generator reconnection terminal block or circuit breaker lugs. The terminals are stamped U, V, W and N to indicate the line and neutral connections. (Reference: U, V, and W correspond with L1, L2 and L3; and N with L0 respectively).
Load Balancing
These generators can be configured to the name­plate voltages as shown on the Reconnection Dia­gram located on the side access cover of the control housing. Many of the voltages listed will require re­configuration of the generator output leads on the connection terminal block. This reconfiguration must only be done by service personnel that are trained and experienced to perform electrical instal­lation. The generator set was adjusted to produce a specified voltage during production verification test­ing prior to shipment. The installer must always check the stator lead terminal block connections and perform any necessary reconnect to obtain the voltage required.
Some generator sets are capable of producing a wide range of voltages and connection configura­tions, others have specific limited capabilities. Re­fer to wiring diagram and generator voltages (from the nameplate) when reviewing the voltage connec­tion information and use the wiring diagram sup­plied with your generator set when actually perform­ing load connections.
CAUTION
Reconfiguring generator sets to higher voltages can exceed the voltage capabil­ity of the specific generator windings and dam­age the generator and also decrease line cur­rent, rendering line circuit breakers too large. Consult with your distributor before performing reconnection for a different voltage.
CAUTION
Reconfiguring generator sets to lower voltages can reduce generator set rat­ings, and also increase line current, rendering line circuit breakers too small. Consult with your distributor before performing reconnec­tion for a different voltage.
Load Connections
Flexible conduit and stranded conductors must be used for connections to take up movement of the generator set.
When connecting loads to the generator set, bal­ance the loads so the current flow from each line ter­minal (L1, L2 and L3) is about the same. This is es­pecially important if both single phase and three phase loads are connected. Any combination of single phase and three phase loading can be used as long as each line current is about the same, with­in 10 percent of median value and no line current ex­ceeds the nameplate rating of the generator . Check the current flow from each line after connections by observing the control panel ammeter.
Current Transformers
Current transformers (CT’s) are required on gen­sets that contain AC meters. The CT’s must be installed as noted in the following CT Installation Requirements.
Refer to the Reconnection Diagram to identify the output leads/phase that must be routed through each CT, and also appropriate transformer post selection for meter sensing leads. The transformers are labeled CT21, CT22 and CT23 on the recon­nection wiring diagram. (The Reconnection Dia­gram is located on the upper side cover of the con­trol housing.)
CT Installation Requirements:
A. The CT has a dot on one side. This dot must be
facing toward the generator (conventional cur­rent flowing into the dot). A dot is also used to indicate pin 1 of the CT.
B. CT21 – U load leads (A phase),
CT22 – V load leads (B phase) CT23 – W load leads (C phase)
C. Route the appropriate load wires through each
CT.
D. The CT’s have dual secondaries (3 pins). The
CT secondary wire marked 1 is connected to pin 1 of the CT. CT secondary wire marked 2/3 is connected to pin 2 for high voltage gensets or to pin 3 for low voltage gensets. (Refer to Re­connection Diagram.)
6-5
Grounding
Redistribution or publication of this document,
by any means, is strictly prohibited.
The following is a brief description of system and equipment grounding of permanently installed AC generators within a facility wiring system. It is impor­tant to follow the requirements of the local electrical code.
Figure 6-2 illustrates typical system grounding for a 3-pole and a 4-pole automatic transfer switch (ATS). In the 3-pole ATS, note that the generator neutral is connected to the ATS and is NOT bonded to ground at the generator. In the 4-pole ATS sys­tem, a grounding electrode conductor and a bond­ing jumper are used to connect the generator neu­tral to ground. In some installations, a CT may be re­quired for ground fault monitoring (refer to Figure 6-2 for CT location).
3-POLE AUTOMATIC TRANSFER SWITCH
3
TO UTILITY
SERVICE
N
Make sure the genset is grounded to earth in one location only. On generators without a circuit break­er, ground to the point indicated on the top of the generator. O n gensets with circuit breakers, use the ground lug provided in the circuit breaker box.
WARNING
Electric current can cause severe personal injury or death. Bonding and ground­ing must be done properly. All metallic parts that could become energized under abnormal conditions must be properly grounded.
Typical requirements for bonding and grounding are given in the National Electrical Code, Article
250. All connections, wire sizes, etc. must conform to the requirements of the electrical codes in effect at the installation site.
GENERATOR SETSERVICE ENTRANCE
3 N
TO UTILITY
SERVICE
SERVICE ENTRANCE
FIGURE 6-2. TYPICAL SYSTEM GROUNDING ONE-LINE DIAGRAMS
4-POLE AUTOMATIC TRANSFER SWITCH
4 WIRES & GROUND
TO LOAD
GENERATOR SET
4 WIRES & GROUND
TO LOAD
BONDING
JUMPER
CT LOCATION IF REQUIRED FOR
GFI MONITORING
GROUNDING ELECTRODE
CONDUCTOR
6-6
CONTROL HEATER (OPTIONAL)
Redistribution or publication of this document,
by any means, is strictly prohibited.
A control heater (Figure 6-3) provides a means of humidity /temperature control of the control box in-
TO ACCESSORY BOX
A40–TB1-36 & 37
terior. I t protects the components when the genera­tor set is subjected to varying ambient air conditions during extended periods of non-use.
HEATER
BOTTOM VIEW OF
CONTROL BOX
FIGURE 6-3. OPTIONAL CONTROL HEATER
6-7
COOLANT HEATER
Redistribution or publication of this document,
by any means, is strictly prohibited.
The coolant heater keeps engine coolant warm when the engine is shut down. It heats and circu­lates the coolant within the engine. This reduces startup time and lessens engine wear caused by cold starts. It is electrically operated and thermo­statically controlled.
CAUTION
erated while the cooling system is empty or damage to the heater will occur.
Figure 6-4 shows a typical coolant heater. Connect the heater to a source of power that will be on during the time the engine is not running. Be sure the sup-
The coolant heater must not be op-
ply voltage and circuit amperage is correct for the heater element rating.
Refer to the Single/Dual Coolant Heater Diagram i n Section 9 for coolant heater power connections/ voltage selections.
A battery charger is required to prevent battery dis­charge. The heater control relay draws 83 mA of cur­rent when the heater(s) is off. The heater is off when the engine has reached the proper temperature or the engine is running.
CAUTION
Do not connect AC power to the heater before connecting battery cables. Heater will run continuously without DC power and can overheat and damage heater.
THERMOSTAT
COOLANT
FLOW
AC ELECTRICAL CONNECTION
BOX (ELECTRICAL DIAGRAM
INSIDE COVER)
DC SUPPLY
LINE
COOLANT
FLOW
DC CONTROL
LINE
DRAIN
AC POWER
LINE
FIGURE 6-4. TYPICAL COOLANT HEATER
6-8
GENERATOR HEATER
Redistribution or publication of this document,
by any means, is strictly prohibited.
A generator heater(s) is used to help keep the gen­erator free of condensation when the generator set is not running. During cool and humid conditions, condensation can form within a generator, creating flashing and a shock hazard.
WARNING
tor increases the possibility of flashing and electrical shock, which can cause equipment damage and severe personal injury or death. Do not use a generator which is not dry inside and out.
Water or moisture inside a genera-
HEATER LEADS
Figure 6-5 illustrates the installation of two heater elements. Connect the heater(s) terminals to a source of power that will be on during the time the engine is not running. Be sure the supply voltage and circuit amperage is correct for the heater ele­ment rating.
HEATER
FIGURE 6-5. TYPICAL GENERATOR HEATER INSTALLATION
HEATER LEADS
HEATERS
TERMINAL BOX
HEATER
VOLT/WATTS
LABEL
TERMINAL
BLOCK
6-9
FUEL TRANSFER PUMP
Redistribution or publication of this document,
by any means, is strictly prohibited.
A fuel transfer pump and control are available when a sub-base or in-skid day tank are provided. The au­tomatic control operates the fuel pump to maintain a reservoir of fuel in the day tank.
WARNING
Diesel fuel is highly combustible. Improper installation of this kit can lead to spill­age of large quantities of fuel and loss of life and property if the fuel is accidentally ignited. Instal­lation and service must be performed by trained and experienced persons in accordance with the applicable codes.
Do not smoke near fuel and keep flames, sparks, pilot lights, arcing switches and equip­ment, and other sources of ignition well away.
CONTROL
FLEXIBLE FUEL
RETURN LINE
FLEXIBLE FUEL
SUPPLY LINE
FUEL PUMP
AND MOTOR
FLOAT SWITCH
ASSEMBLY
FIGURE 6-6. TYPICAL IN-SKID DAY TANK INSTALLATION
DAY
TANK
FUEL
GAUGE
6-10
FUEL FILL
CAP
Fuel Pump Control AC Connections
Redistribution or publication of this document,
by any means, is strictly prohibited.
The control can be powered by 120 VAC or 240 VAC. The control is set up at the factory for connec­tion to 240 VAC.
1. To convert the day tank controller from 240 VAC to 120 VAC, perform the following steps.
A. Remove the two jumpers between termi-
nals TB1-6 and TB1-7 in the control box and connect one between terminals TB1-5 and TB1-6 and the other between terminals TB1-7 and TB1-8.
2. To convert the day tank controller from 120 VAC to 240 VAC, perform the following steps.
A. Remove the jumpers between terminals
TB1-5 and TB1-6, and TB1-7 and TB1-8 in the control box and connect the two jumpers between terminals TB1-6 and
TB1-7.
B. Move selector switch S103 on the control
PCB to the down position for 240 VAC.
C. If the control is equipped with a transform-
er, remove the jumpers between terminals H1 and H3, and H2 and H4 and connect the two jumpers between H2 and H3.
B. Move selector switch S103 on the control
PCB to the up position for 120V.
C. If the control is equipped with a transform-
er, remove the two jumpers between ter­minals H2 and H3 and connect one be- tween H1 and H3 and the other between H2 and H4.
3 Attach a tag to the control box indicating the
supply voltage.
4 Terminals TB1-8 and TB1-5 are available for
connection of a 120 or 240 VAC electric fuel shutoff valve rated not more than 0.5 amps. The voltage rating of the valve must corre­spond with the voltage utilized for the pump. See Item 2 above.
FIGURE 6-7. FUEL PUMP CONTROL TERMINAL BOARD
6-11
GROUND FAULT ALARM RELAY
Redistribution or publication of this document,
by any means, is strictly prohibited.
(OPTIONAL)
The optional Ground Fault Relay (GFR) (Figure 6-8) is typically located behind the lower control housing grille. The ground fault relay continuously monitors the neutral to ground connection and acti­vates a fault alarm when the connection is broken. During genset operation, the relay continuously monitors the line to neutral and activates a fault alarm when a ground fault is sensed.
After the installation of the genset is complete, per­form the following procedure to test the operation of the ground fault relay.
A. Verify that the N-G Fault Indicator on the
GFR is not lit. If lit, it indicates that the bonding jumper circuit (neutral to ground) is open. If genset does not require bonding jumper, a bonding jumper must be installed at the facility service entrance.
The relay alarm contacts are typically connected to the genset control to provide a “Ground Fault Alarm” indication.
A control reset will clear the fault at the control panel and will also reset the ground fault relay.
The relay has a time delay setting of zero to one second and a current setting of 5 to 1200 amperes.
Adjust the Current and the Time Delay controls on the ground fault relay to the customers specifica­tions.
A. Move the control switch to the Run posi-
tion.
B. Press the TEST switch on the ground fault
relay.
C. Verify that the control panel warning mes-
sage is displayed and the Fault Indicator (>I) on the GFR is lit.
D. Reset the control panel fault (this will also
reset the ground fault relay).
6-12
CONTROL
Redistribution or publication of this document,
by any means, is strictly prohibited.
HOUSING
GROUND FAULT
RELAY
ASSEMBLY
GRILLE
TEST BUTTON
FAULT INDICATORS
> I
(OVER CURRENT)
N–G
(OPEN CIRCUIT)
FIGURE 6-8. GROUND FAULT ALARM RELAY
ON INDICATOR
RESET BUTTON
(N.U., FACTORY SET
TO AUTO RESET)
TIME DELAY CONTROL
CURRENT CONTROL
6-13
THIS PAGE LEFT INTENTIONALLY BLANK
Redistribution or publication of this document,
by any means, is strictly prohibited.
6-14

7. Prestart Preparation

Redistribution or publication of this document,
by any means, is strictly prohibited.
GENERAL
Before attempting the initial start of the generator set, be sure to complete the
Section 9
.
Installation Checklist
in
PCC POWER ON / STANDBY MODE
WARNING
can cause severe personal injury or death. Arc­ing at battery terminals, light switch or other equipment, flame, pilot lights and sparks can ig­nite battery gas. Do not smoke, or switch trouble light ON or OFF near battery. Discharge static electricity from body before touching bat­teries by first touching a grounded metal sur­face.
Ventilate battery area before working on or near battery—Wear goggles—Stop genset and dis­connect charger before disconnecting battery cables—Disconnect negative (–) cable first and reconnect last.
Ignition of explosive battery gases
CAUTION
Disconnect battery charger from AC source before disconnecting battery cables. Otherwise, disconnecting cables can result in voltage spikes damaging to DC control circuits of the set.
WARNING
Accidental starting of the generator set can cause severe personal injury or death. Prevent accidental starting by disconnecting the negative (–) cable from the battery terminal.
Before opening the PCC control cabinet to make the following Power On/Standby Mode selection, remove the negative (–) battery cable(s) from the generator set starting battery as follows:
1. Move the Run/Off/Auto switch on the control panel to the OFF position.
2. Turn off or remove AC power from the battery charger.
3. Remove the negative (–) battery cable from the generator set starting battery.
7-1
Selecting Power On or Standby Mode
Redistribution or publication of this document,
by any means, is strictly prohibited.
CAUTION
circuit boards. To prevent this damage, always wear a grounding wrist strap when working in­side control box.
Set the Power On / Standby Mode switch (S5 in Fig­ure 7-1) to the desired position.
Power On Mode: Slide the switch to the left to se­lect the Power On (awake) mode. It is recom­mended that switch S5 be left in the Power On mode in all applications, except those where battery charging is not available.
The PCC will initialize the operating software and permit operation of the menu display panel. Power will stay on until the switch is reset to the Standby Mode.
Standby Mode: Slide the switch to the right to se­lect the Standby (sleep) Mode. In this mode, the PCC operating software will be initiated by:
Electrostatic discharge will damage
moving the Run/Off/Auto switch to the Run
position,
pressing the Self Test button,
a remote start input signal (genset in Auto
mode), or
any one of several “wake-up” signals from ex-
ternal switches.
With the switch set to Standby mode, pressing the Self Test button will allow you to activate and view the menu displays without starting the generator set. If no menu selections are made, a software tim­er will shut down the power after 30 seconds.
When left in the Standby Mode, and a “Warning” signal is sensed by the PCC (for example, low en­gine temp), the control will wake up and display the warning message. The control will remain active until the warning condition is corrected and the Re­set button is pressed to clear the warning message.
DISPLAY BOARD
(A35)
PCC POWER ON / STANDBY
MODE SWITCH (S5)
ANALOG BOARD
ENGINE INTERFACE
(A31)
DIGITAL BOARD
(A32)
(A33)
CUSTOMER INTERFACE
(A34)
FIGURE 7-1. CABINET INTERIOR (PCC 3100)
7-2
ELECTRICAL SYSTEM
Redistribution or publication of this document,
by any means, is strictly prohibited.
Verify all electrical connections are secure and all wiring is complete and inspected. Replace and se­cure any access panels that may have been re­moved during installation.
Battery Connections
WARNING
set can cause severe personal injury or death. Make sure that the Run/Off/Auto switch on the control panel is set to the Off position before connecting the battery cables.
Starting the unit requires 24 volt battery current, us­ing two 12 volt batteries (see Connect the batteries in series (negative post of first battery to the positive post of the second battery) as shown in Figure 7-2.
Accidental starting of the generator
Specification
section).
POSITIVE
NEGATIVE
Service the batteries as necessary. If an automatic transfer switch is installed without a built-in charge circuit, connect a separate battery charger. A bat­tery charger is required when the PowerCommand control is set to the Power On (awake) mode.
WARNING
Ignition of explosive battery gases can cause severe personal injury or death. Al­ways connect negative (–) battery cable last to prevent arcing.
WARNING
Ventilate battery area before work­ing on or near battery. Arcing at battery termi­nals, light switch or other equipment, flame, pi­lot lights and sparks can ignite battery gas. Do not smoke, or switch trouble light ON or OFF near battery. Discharge static electricity from body before touching batteries by first touching a grounded metal surface.
TWO, 12 VOLT
BATTERIES
FIGURE 7-2. GENERATOR SET BATTERY
CONNECTIONS
7-3
PCC OPTIONS PRESTART CHECKS
Redistribution or publication of this document,
by any means, is strictly prohibited.
All generator set configuration options are set at the factory except for site related options, (e.g., Start/ Stop Time Delays, Cycle Crank, Customer Fault 1 and 2, etc..
START DELAY submenu:
This delay applies only to remote starting in the Auto mode. Use the buttons next to the “
” and “” symbols to set the start delay .
The start delay adjustment range is 0 to 300 sec­onds.
Adjustment of these options are divided into two categories within the menu driven system. These two categories are
The
Setup/Calibrate
Adjust
and
Setup/Calibrate
submenus are intended for
.
qualified service personnel only and require a pass­word to modify these submenus. The
Adjust
sub­menus are intended for service personnel and site personnel.
The
Adjust
submenus allow site personnel to cali­brate the generator set voltage/frequency, idle speed and start/stop time delays. For the prestart checks, adjustment of only the start/stop delays is required.
Adjust Menu
To adjust the start and stop delays, press the button next to the word “ADJUST” in the Main Menu. Fig­ure 7-3 shows a block representation of the AD­JUST menu. After you press the button next to the word “ADJUST” in the display, the VOLTAGE sub­menu will appear.
STOP DELAY submenu:
This delay applies only to remote stopping in the Auto mode. From the START DELAY submenu, press the button next to the “>>” in the display to move to the STOP DELAY submenu. Use the buttons next to the “
” and “
symbols to set the stop delay. The stop delay adjust­ment range is 0 to 600 seconds.
IDLE SPEED submenu:
From the STOP DELAY submenu, press the button next to the “>>” in the display to move to the IDLE SPEED submenu. Use the buttons next to the “
” and “” symbols to set the
idle speed. The idle speed adjustment range is 800 RPM
±100 RPM. (Default value is 800 RPM.)
The idle speed can be adjusted only when the gener­ator set is running in the idle mode. When not in idle mode, N/A is displayed in RPM field.
SAVE/EXIT submenu:
From the STOP DELAY submenu, press the button next to the “>>” in the display to move to the SAVE/EXIT submenu. Select SAVE to save your changes. At the CHANGES SAVED submenu, select EXIT to return to the Main menu.
As shown in the diagram, the ADJUST menu has five submenus, including a save/exit procedure. To move through the VOLTAGE and FREQUENCY submenus, press the button next to the ’>>’ to dis­play the STOP DELAY submenu.
If you select SAVE, the adjustments will be retained after shutdown, and will be in effect when the set is restarted. If you select EXIT without saving first, the adjustments will remain in effect until the genset is shut down and return to the previous settings when the set is restarted.
7-4
ADJUST MENU
Redistribution or publication of this document,
by any means, is strictly prohibited.
<>
ENGINE GEN ADJUST >>
<>
<
VOLTAGE
<>
_______ >>
<
FREQUENCY
<>
_______ >>
<
START DELAY
<>
_______ SEC >>
<
STOP DELAY
<>
_______SEC >>
IDLE SPEED
<
_______RPM >>
<>
<
SAVE EXIT >>
<>
<
SAVE EXIT >>
<>
<
SAVE EXIT >>
<>
CHANGES SAVED EXIT >>
<>
CHANGES SAVED EXIT >>
<>
ENGINE GEN ADJUST >>
<>
<
VOLTAGE
<>
_______ >>
<>
ENGINE GEN ADJUST >>
<>
<
VOLTAGE
<><>
_______ >>
Indicates OR" Condition
FIGURE 7-3. ADJUST MENU
7-5
STARTING
Redistribution or publication of this document,
by any means, is strictly prohibited.
Refer to the generator set
Operator’s
manual for im­portant safety precautions and recommended pro­cedures for starting the genset and verifying proper operation. Start the generator set and verify all en­gine and generator gauges are displaying the cor­rect values.
7-6

8. Installation Checklist

Redistribution or publication of this document,
by any means, is strictly prohibited.
GENERAL
Generator set wattage capacity is sufficient to handle maximum anticipated load.
At least 3 feet of clearance (or greater for housing door) is provided around entire generator set for servic-
ing and ventilation.
Generator set is located in an area not subject to flooding.All operating personnel have read and are familiar with Operator’s Manual.All operators have been thoroughly briefed on preventive maintenance procedures.All operators have read and understand all Important Safety Instructions in Operator’s Manual.
GENERATOR SET SUPPORT
Floor, roof or earth on which the generator set rests is strong enough and will not allow shifting or move­ment. Observe local codes on soil bearing capacity due to freezing and thawing.
Generator set is properly supported and retained to approved base.Supporting base is large enough and is of non-combustible material – extends 6-inches all around set.
COOLING AIR FLOW
Generator set air inlet is faced into direction of strongest, prevailing winds.
Air inlet openings are unrestricted and at least 1–1/2 times larger than air outlet area.Cooling air outlet is on downwind side of building (if not, wind barrier is constructed).Proper ducting material (sheet metal, canvas) is used between radiator and air outlet.
DIESEL FUEL SYSTEM
Fuel tanks meet or exceed all Local, State or National codes.
Fuel lines are properly installed, supported and protected against damage.Approved flexible fuel line is installed between main fuel supply line and generator set’s fuel system, near
the generator set, to protect the fuel system from damage caused by vibration, expansion and contrac­tion.
Strainer or fuel screen (100 to 120 mesh) is installed in the fuel supply line to protect the fuel lift pump, day
tank transfer pump or float valve seat from fuel supply tank debris.
Fuel supply line shutoff valves are installed to prevent fuel flow in case of leaks.No shutoff valves are installed on engine fuel return line.External fuel pumps are connected and operational at all times (generator set started or shut down).Fuel system is properly primed.No fuel leaks are found in supply line or engine fuel system.
8-1
EXHAUST SYSTEM
Redistribution or publication of this document,
by any means, is strictly prohibited.
Operators are thoroughly briefed on the dangers of carbon monoxide gas.
Areas around set are well ventilated. No possibility of exhaust fumes entering building doors, windows, or
intake fans.
Exhaust gases are piped safely outside and away from building.The correct length of approved rigid pipe is connected to the generator set flexible pipe using approved
securing methods with no weight resting on engine exhaust components. There are no bends in flex sec­tion.
Condensation drain is provided in lowest section of exhaust piping.Exhaust piping is insulated to guard against burns to personnel.Exhaust piping passing through walls or ceilings have approved fire-proof materials and are in com-
pliance with all codes.
Exhaust piping is large enough in diameter to prevent excessive back pressure on engine.
AC AND DC WIRING
Wire sizes, insulation, conduits and connection methods all meet applicable codes.
AC and DC wires are separated in their own conduit to prevent electrical induction.All load, line and generator connections are proper and correct.Flexible conduit between generator set and building or surrounding structure.
GENERATOR SET PRESTART
Generator set engine is properly serviced with oil and coolant.
Batteries are properly installed, serviced and charged.Battery charger and engine coolant heater are connected and operational.All generator set covers and safety shields are installed properly.All fuel and coolant shutoff valves are operational.
8-2

9. Wiring Diagrams

Redistribution or publication of this document,
by any means, is strictly prohibited.
GENERAL
This section consists of the schematic and connec­tion wiring diagrams referenced in the text. The fol­lowing drawings are included.
Page 9-2 – Customer Connections Diagram
Page 9-3 – Accessory Interconnect Diagram
Page 9-4 – Single/Dual Coolant Heater Wiring
Diagram
9-1
THIS IS A REPRESENTATIVE (GENERIC)
Redistribution or publication of this document,
by any means, is strictly prohibited.
SCHEMATIC/WIRING DIAGRAM. FOR TROUBLESHOOTING, REFER TO THE WIRING DIAGRAM PACKAGE THAT WAS INCLUDED WITH YOUR GENSET.
No. 6126658 sh 3 of 3 Rev. D Sys: HP Modified 8/13/97
PCC CUSTOMER CONNECTIONS
9-2
GENERATOR SET
Redistribution or publication of this document,
by any means, is strictly prohibited.
WITH PCC CONTROL
OT AND BT 2 WIRE START
UTILITY TO GENSET
THIS IS A REPRESENTATIVE (GENERIC) SCHEMATIC/WIRING DIAGRAM. FOR TROUBLESHOOTING, REFER TO THE WIRING DIAGRAM PACKAGE THAT WAS INCLUDED WITH YOUR GENSET.
No. 6301345 sh 1 Rev. J Modified 11/96
PCC ACCESSORY NTERCONNECT DIAGRAM
9-3
THIS IS A REPRESENTATIVE (GENERIC)
Redistribution or publication of this document,
by any means, is strictly prohibited.
SCHEMATIC/WIRING DIAGRAM. FOR TROUBLESHOOTING, REFER TO THE WIRING DIAGRAM PACKAGE THAT WAS INCLUDED WITH YOUR GENSET.
SINGLE COOLANT HEATER DIAGRAM DUAL COOLANT HEATER DIAGRAM
SINGLE/DUAL COOLANT HEATER DIAGRAMS
No. 5003104 sh 1 of 1 Rev. A Modified 9/23/96
SINGLE/DUAL HEATER WIRING DIAGRAM
9-4
Cummins Power Generation
Redistribution or publication of this document,
by any means, is strictly prohibited.
1400 73rd Avenue N.E. Minneapolis, MN 55432 1-800-888-6626 763-574-5000 International Use Fax: 763-528-7229
Cummins is a registered trademark of Cummins Inc.
Loading...