APPENDIX A. OUTLINE AND SYSTEM DRAWINGS......................................................................83
A029V088 (Issue 13)iii
Table of Contents3-2013
This page is intentionally blank.
ivA029V088 (Issue 13)
1IMPORTANT SAFETY INSTRUCTIONS
1.1Save These Instructions
This manual contains important instructions for the generator set that should be followed during
installation, operation and maintenance of the generator and batteries.
Thoroughly read the Operator Manual before operating the generator set. Safe operation and
top performance can only be obtained when equipment is properly operated and maintained.
The following symbols in this manual alert you to potential hazards to the operator, service
person and equipment.
DANGER: Alerts you to an immediate hazard that will result in severe personal
injury or death.
WARNING: Alerts you to a hazard or unsafe practice that can result in severe personal
injury or death.
CAUTION: Alerts you to a hazard or unsafe practice that can result in personal injury or
equipment damage.
1.2General Precautions
· Keep ABC fire extinguishers handy.
· Make sure all fasteners are secure and torqued properly.
· Keep the generator set and its compartment clean. Do not store any items in the genset
compartment.
· Excess oil, oily rags (etc.) can catch fire.
· Dirt and gear stowed in the compartment will restrict cooling air flow.
· Before working on the generator set, move the Stop Switch (S2) to the Stop position,
disconnect the remote harness (P7) to disable the ATS mounted charger and then remove
the negative (-) battery cable to prevent starting.
· Use caution when making adjustments while the generator set is running, hot, moving or
when parts are electrically live, as all situations may cause personal injury or death.
· Used engine oil has been identified by some state and federal agencies as causing cancer
or reproductive toxicity. Do not ingest, inhale or come into contact with used oil or it's
vapors.
· Do not work on the generator set when mentally or physically fatigued or after consuming
alcohol or drugs.
1.3Generator Voltage is Deadly
· Generator output connections must be made by a trained and experienced electrician in
accordance with all applicable codes.
A029V088 (Issue 13)1
1. IMPORTANT SAFETY INSTRUCTIONS3-2013
· This standby generator set and the public utility may only be connected to the house
circuits by means of the automatic transfer switch.
· Improper connections can lead to electrocution of utility workers and damage to
equipment.
· Use caution when working on live electrical equipment. Remove jewelry, make sure
clothing and shoes are dry and stand on a dry wooden platform.
1.4Engine Exhaust is Deadly
· See What Is Carbon Monoxide Poisoning? to learn the symptoms of Carbon Monoxide
poisoning.
· This generator set is for outdoor installation only.
· It must be located well away from doors, windows, other openings into the house and
where the exhaust gases will disperse away from the house.
1.5Fuel is Flammable and Explosive
· Keep flames, cigarettes, sparks, pilot lights, electrical arc-producing equipment, switches
and all other sources of ignition well away from areas where fuel fumes are present and
areas sharing ventilation.
· Fuel lines must be secured, free of leaks and separated or shielded from electrical wiring.
· Leaks can lead to explosive accumulations of gas. Prevent leaks and the accumulation of
gas.
· A "rotten egg" smell indicates a possible Natural Gas or Propane leak:
· Natural Gas rises when released and can accumulate under hoods and inside
housings and buildings.
· Propane sinks when released and can accumulate inside housings and
basements and other below-grade spaces.
1.6Batteries Can Explode
Batteries can explode, causing severe skin and eye burns and can release toxic electrolytes.
· Wear safety glasses.
· Do not smoke.
· Do not dispose of the battery in a fire.
· The battery is capable of exploding.
· Do not open or mutilate the battery.
· Released electrolytes have been known to be harmful to the skin and eyes and to be
toxic.
· Batteries present the risk to high short circuit current:
· Remove watches, rings or other metal objects and use tools with insulated handles.
2A029V088 (Issue 13)
3-20131. IMPORTANT SAFETY INSTRUCTIONS
· To prevent arcing when disconnecting the battery:
· Move the Stop Switch (S2) to the Stop position, disconnect the remote harness (P7)
to disable the ATS mounted charger and then remove the negative (-) battery cable to
prevent starting.
· To prevent arcing when reconnecting the battery:
· First, reconnect the positive (+) cable, then the negative (-) cable, and finally
reconnect the battery charger.
· When replacing the generator set battery, always replace it with a battery as specified in
the Model Specifications section of this manual.
1.7Moving Parts Can Cause Severe Personal Injury or
Death
· Do not wear loose clothing or jewelry near moving parts such as fans.
· Keep hands away from moving parts.
· Keep guards in place, over fans.
1.8The Hazards of Carbon Monoxide
Engine-driven generators can produce harmful levels of carbon monoxide that can injure or kill
you.
1.8.1What Is Carbon Monoxide Poisoning?
Carbon Monoxide (CO) is an odorless, colorless, tasteless and non-irritating gas. You cannot
see it or smell it. Red blood cells, however, have a greater affinity for CO than for Oxygen.
Therefore, exposure even to low levels of CO for a prolonged period can lead to asphyxiation
(lack of Oxygen) resulting in death. Mild effects of CO poisoning include eye irritation, dizziness,
headaches, fatigue and the inability to think clearly. More extreme symptoms include vomiting,
seizures and collapse.
1.8.2What Are the Special Risks of CO Near the Home?
Residents can be exposed to lethal levels of CO when the genset is running. Depending on air
temperature and wind, CO can accumulate in or near the home.
To protect yourself and others from the dangers of CO poisoning, it is recommended that
reliable and approved CO detector alarms be installed in the home.
WARNING: Carbon Monoxide (CO) gas can cause nausea, fainting or death.
A029V088 (Issue 13)3
1. IMPORTANT SAFETY INSTRUCTIONS3-2013
1.8.3Only You Can Protect Yourself From CO Poisoning!
· Locate the generator in an area where there are no windows, doors or other access points
into the home.
· Make sure all CO detectors are working properly.
· Pay attention to the signs of CO poisoning.
· Check the exhaust system for corrosion, obstruction and leaks each time you start the
generator set and every eight hours if you run it continuously.
4A029V088 (Issue 13)
2Introduction
This generator set application is intended for stationary emergency use.
Important note for Brazil applications: The manufacturer warns that the installation, operation
and maintenance of equipment by the user must fully comply with the Manual's guidelines and
current Brazilian laws, including those of the Brazilian Agency of Petroleum, Natural Gas and
Fuels (ANP) and the Brazilian Energy Agency (ANEEL).
2.1About this Manual
This manual is a guide for the installation of the generator set models listed on the front cover.
Proper installation is essential for top performance, reliable operation and safety. Read through
this manual before starting the installation.
NOTE:The installation must comply with all applicable building codes.
See the generator set Operator Manual (A029V089) for operation and maintenance and the
Service Manual (A030A239) for service.
NOTE:Manuals are updated from time to time to reflect changes in the equipment
and its specifications. The most up-to-date version of this manual will be
found on the QuickServe website
(https://quickserve.cummins.com/info/index.html).
2.2Model Specifications
TABLE 1.GSBB AND GSBC MODEL VARIATIONS
ProductDescription
20GSBB-6713A\B60 Hz Warm
20GSBB-6714A\B60 Hz Cold *
14GSBB-6716A\B50 Hz (AU/NZ)
20GSBB-6717A\20GSBC-6927B60 Hz CSA Cold *
* Includes an engine oil heater.
NOTE:See the Cold Weather Specifications Table for recommendations.
A029V088 (Issue 13)5
2. Introduction3-2013
TABLE 2.COLD WEATHER SPECIFICATIONS TABLE
60 Hz50 Hz
Propane VaporNatural GasPropane VaporNatural Gas
Operating Temperature Range
Above 32 °F (0 °C) and lowNo dryers or starting aids required.
humidity
High humidityAlternator drying heater recommended.
Below 20 °F (-7 °C)Additional oil heater recommended for starting. Factory-installed model available.
Below 0 °F (-18 °C)Additional accessory breather shield/shroud required to avoid possible engine
Intake and Exhaust Cold Valve0.004-0.006 inch (0.10 - 0.15 mm)
Lash
(Measure at 0.25" (6.35mm)
past top dead center)
Oil CapacityApproximately 80 oz (2.3 Liters)
Oil Recommendation5W-30 Synthetic Engine Oil
(See Operator Manual)
TABLE 7.GENERATOR SPECIFICATIONS TABLE
GeneratorBrush-Type, 2-Pole Rotating Field, Single Bearing
Power (kVA)------13.513.5
Rated Voltage (V)120/240120/240115/230115/230
Rated Current (Amps)162/81.25144/72117.4/58.7117.4/58.7
Phase TypeSingle Phase
Circuit Breaker (Amps)1001006060
A029V088 (Issue 13)7
60 Hz50 Hz
Propane VaporNatural GasPropane VaporNatural Gas
2. Introduction3-2013
60 Hz50 Hz
Propane VaporNatural GasPropane VaporNatural Gas
De-rating Guidelines: Maximum wattage or maximum current are subject to and limited by such factors as fuel Btu
content, ambient temperature, altitude, engine power and condition, etc. Full rated power is available at 60 °F (15.5
°C) at sea level. De-rate 3.5% for each 1000 ft (304.8 m) above sea level and 3% for each 10 °F (5.5 °C) increase in
ambient temperature above 60 °F (15.5 °C).This generator is rated in accordance with UL 2200 (Stationary Engine
Generator Assemblies) or CSA C22.2 No. 100-04 (Motors and Generators). The maximum continuous current values
that are listed on the generator set nameplate and specification tables occur at the lower limit of acceptable voltage.
Maximum current occurs at 108 and 216 volts, 10% below nominal voltage 120/240. The voltage set point of this
generator set can be adjusted from the operator panel if desired. Refer to the Operator manual procedure To Adjust
the Output Voltage.
TABLE 8.CONTROL SPECIFICATIONS TABLE
60 Hz50 Hz
Propane VaporNatural GasPropane VaporNatural Gas
ControllerIntegrated Microprocessor-Based Engine, Generator, Transfer Switch Controller
TABLE 9.DC SYSTEM SPECIFICATIONS TABLE
60 Hz50 Hz
Propane VaporNatural GasPropane VaporNatural Gas
DC System
Nominal Battery Voltage12 Volts DC
Battery Group26 R
Battery TypeMaintenance Free
Minimum Cold Crank Amps545
2.3Information For After Installation
WARNING: Improper installation can result in severe personal injury, death and damage
to equipment. The installation must comply with all applicable building
codes. It is strongly recommended that the installer be properly trained and
licensed to perform electrical and mechanical equipment installations,
however a person with the proper knowledge and experience in installing
electrical and mechanical equipment installations may also install this
genset.
Refer to the GSBB Specifications Sheet for specific information about the system and it's
components.
Refer to the Outline and System Drawings for specific information about the installation and
wiring connections.
See the Operator Manual (A029V089) for proper operation and maintenance instructions.
8A029V088 (Issue 13)
3Step-By-Step Outline of Installation
WARNING: The installer is responsible for complying with all applicable installation
codes and safety requirements. See the Installation Codes and Standards
section of this manual for more information.
The following sections create a step-by-step overview of a typical generator set installation.
Review these sections to become familiar with specific procedures and important safety
precautions before beginning the installation.
NOTE:For information on pre-installation considerations (tools, materials, locating
the genset, codes and standards and specifications) see the Introduction
chapter of this manual.
3.1Pre-Installation Considerations
Before installation begins, certain actions must be considered. Prior coordination will reduce
delays and the amount of time power has to be interrupted.
Areas of consideration:
· The location of the generator set is one of the first decisions to be made, as it affects all
other aspects of the installation, such as:
· the length of electric wiring
· the length of gas lines
· Natural Gas or Propane - both of which must be inspected by the gas utility
inspectors and building inspectors
· the site preparation
· access to the site
· trenches
· site preparation materials needed
· Fuel supply pressure.
· The installation cannot be completed without connections to an automatic transfer
switch. Decide where to locate the automatic transfer switch
· Decide what tools and materials will be needed
· Maintain the minimum distance from the Propane tank fill.
· Verify the legal minimum distance with local code officials.
· Determine what (if any) accessories will be required for the customer's application. Utility
power may be required at the generator set, make plans accordingly.
NOTE:Depending on the locality and use of the generator set, it may be necessary
to obtain an air quality emissions permit before installation begins. Check
with local pollution control or air quality authority to determine whether or
not a permit is needed.
A029V088 (Issue 13)9
3. Step-By-Step Outline of Installation3-2013
3.1.1Installation Codes and Standards for Safety
WARNING: The generator set installer bears sole responsibility for following all
applicable local codes and regulations.
The following list of Installation Codes and Standards for Safety applies to the installation and
operation of standby generator sets. This list is for reference only and not intended to be
inclusive of all applicable codes and standards. The address of each agency is listed so that
copies of the codes may be obtained for reference. Installation codes and recommendations are
subject to change, and may vary by location or over time.
TABLE 10.INSTALLATION CODES AND STANDARDS FOR SAFETY RECOMMENDATIONS
NFPA 70 - National Electric CodeNational Fire Protection Association
NFPA 37 - Installation and Use of Stationary Combustion Engines 470 Atlantic Avenue
and Gas Turbines
NFPA 54 - National Fuel Gas Code
NFPA 58 - Storage and Handling of Liquefied Petroleum Gases
CSA Electrical BulletinCanadian Standards Association
CSA C22.2 No. 100Housing and Construction Materials Section
CSA C22.2 No. 14178 Rexdale Blvd.
California Administrative Code - Title 25 Chapter 3State of California
Underwriters LaboratoriesUnderwriters Laboratories, Inc.
UL2200333 Pfingsten Road
Boston, MA 02210
Rexdale, Ontario, Canada M9Q 1R3
Documents Section
P.O. Box 1015
North Highlands, CA 95660
Northbrook, IL 60062-2096
3.1.2Required Items for Installation
Specific tools and materials are required for the installation of this generator set. These items
are identified in the following sections.
3.1.2.1Materials Required
TABLE 11.ELECTRICAL MATERIALS
RequiredOptional
Appropriately-sized gauge and length AC wires with 75 °C insulation. 4 wires; L1,X
L2, N and Gnd.
Appropriate conduit for all AC wires.X
Cummins Onan Plug-n-Play harness from Genset to ATS. (1', 50' and 100' lengthsX
available for purchase)
Appropriate conduit for DC communications wires.X
Cummins Onan Plug-n-Play harnesses for Generator Set to in home display (ifX
installing in the house). (1', 50' and 100' lengths available for purchase)
Three conductor 75 °C 300V minimum-rated wiring appropriately sized to 120 voltX
GFCI installation or to Alternator/Oil heaters (if equipped).
10A029V088 (Issue 13)
3-20133. Step-By-Step Outline of Installation
Appropriately-sized junction box and cover for heater/GFCI wiring (if installing).X
Provided on cold weather model.
Code compliant GFCI outlet and "While in Use - Wet Location" cover.X
Cat 5e for Internet installation.X
Two conductor 300V wire (18AWG) per Load Management relay.X
Low Voltage: SPDT relay min 1A 24VAC.X
High Voltage: SPDT relay sized to load (amp and voltage).X
TABLE 12.MOUNTING MATERIALS
RequiredOptional
Four base mounting spikes. Provided with generator.X
Cummins Onan Installation Wheel Kit is available for easy on-site generatorX
transportation.
TABLE 13.FUEL MATERIALS
RequiredOptional
12" Flexible fuel line. Provided with generator.X
UL Listed pipe thread sealant.X
Size Fuel line. NG: 5-7" H20, LP: 12-14" H20 fuel pressure (as measured at gensetX
fuel regulator service port). See Installation Manual guidelines.
Fuel regulator - as required.
Manual fuel shut-off at Genset (preferred).X
TABLE 14.IN-HOME DISPLAY MATERIALS
RequiredOptional
In-home display. One (1) provided with generator.X
Four wall anchors and screws (no. 6) if mounting on stud wall.X
Standoffs and mounting fasteners if mounting on block or brick wall.X
3.1.2.1.1 Loose Parts Shipped With the Generator
The following loose parts are shipped with the generator set:
· Oil drain hose
· Flexible fuel hose assembly
· Welch plug tied to fuel regulator (Spec B only)
· Four base spikes (ground stakes)
· In-home display
· Two keys
· Literature - Operator Manual (A029V089), Installation Manual (A029V088) and Warranty
Statement
A029V088 (Issue 13)11
3. Step-By-Step Outline of Installation3-2013
3.1.2.2Tools Required
Use a forklift to move the generator set and set it in place. Alternatively, a one-man hand dolly
designed to fit the generator set base is available to move the generator set and set it in place.
Hand tools required include the following:
· Wire stripper for terminating the communications wires
· Torque wrench
· Jewelers screwdriver
· Allen wrench
· Ratchet set with 10 mm socket and extension
· Two pipe wrenches for gas connections
· Phillips-head and flat-blade screwdrivers
· Ball peen hammer
· Fuel meter (operates down to 5 in. WC)
3.1.3Choosing A Transfer Switch
Block diagrams showing partial or full load coverage are shown on the following pages:
· UL 1008 listed, Service Entrance Rated Automatic Transfer Switch (without controller):
· RSS 100-6868
· RSS 200-6869
· CSA Approved and UL 1008 listed (with controller):
· RSS 100-6634
· RSS 200-6635
· UL 1008 listed, Service Entrance Rated (without controller):
· RSS 100-6868
· RSS 200-6869
NOTE:If the transfer switch is connected for full load coverage which exceeds the
generator set rating, it may be necessary to shed large loads such as air
conditioners.
NOTE:
·· The RSS 100 transfer switch models can be connected for full or partial
load coverage equal to the capacity of the generator set.
·· The RSS 200 transfer switch models can be connected for full load
coverage greater than the capacity of the generator set.
TABLE 15.TRANSFER SWITCH CONNECTION VS. LOAD COVERAGE
Transfer Switch ModelConnection Capabilities
RSS 100-6634X
12A029V088 (Issue 13)
Full LoadFull or Partial Load
(Greater Than Capacity of Genset)(Equal to Capacity of Genset)
3-20133. Step-By-Step Outline of Installation
RSS 200-6635X
RSS 100-6868X
RSS 200-6869X
NOTE:Model RSS 100-6634 and RSS 200-6635 transfer switches do not incorporate
a utility circuit breaker and therefore must be connected through a Service
Entrance Utility Panel incorporating the utility circuit breaker.
Perform Generator Set Configuration when ready to start up the generator set.
FIGURE 1.PARTIAL COVERAGE LOAD CONNECTIONS (TRANSFER SWITCH WITHOUT
CONTROLLER)
A029V088 (Issue 13)13
3. Step-By-Step Outline of Installation3-2013
FIGURE 2.FULL COVERAGE LOAD CONNECTIONS (TRANSFER SWITCH WITHOUT
CONTROLLER, ONE CIRCUIT BREAKER)
FIGURE 3.PARTIAL COVERAGE LOAD CONNECTIONS (TRANSFER SWITCH WITH CONTROLLER)
14A029V088 (Issue 13)
3-20133. Step-By-Step Outline of Installation
FIGURE 4.FULL COVERAGE LOAD CONNECTIONS (TRANSFER SWITCH WITH CONTROLLER)
3.2Generator Set Installation Requirements
WARNING: EXHAUST GAS IS DEADLY! Install the generator set out-doors only. The
generator set must be located away from doors, windows and other openings
to the house and where exhaust gases will disperse away from the house.
Generator set location is critical for safety and performance. Follow the guidelines below
· Must comply with applicable codes (NFPA, NEC, etc.).
· Install out-doors only.
· Call the local utilities to mark the locations of buried utility services (gas, electric or
telephone) before digging trenches for fuel and electrical lines.
· Ask the homeowner for locations of any other buried components (gas, electric or
telephone) before digging trenches for fuel and electrical lines.
Clearances:
· The exhaust side of the generator set must be located 5 feet from combustible materials
(NFPA 37).
· The exhaust side of the generator must be located 5 feet from any opening in a wall
(window, door, vent, etc.).
· The generator must be located such that the exhaust is not able to accumulate in an
occupied area.
· The generator must have access for installation, service and maintenance as deemed
appropriate by a Cummins Onan authorized dealer or installer.
· The generator must be located to ensure ventilation openings are not blocked.
A029V088 (Issue 13)15
3. Step-By-Step Outline of Installation3-2013
3.3Generator Set Installation Suggestions/Guidelines
· Locate the generator set on stable ground, not subject to flooding.
· Locate and orient the generator set such that prevailing winds will carry exhaust gases and
fuel leaks away from the house or occupied area.
· Make sure engine vent port on the side of the enclosure is not blocked and is free of
debris.
3.4Preparing the Site
Steps to preparing a proper/safe generator set site:
1. Create a level area.
Add a layer of sand or pea gravel that is deep enough that the generator set will sit level.
2. Be sure that the area is at least 48 in by 34 in (1219 mm by 864 mm).
Sites on an incline require more area.
3. Be sure that the area is on firm ground.
4. Remove any combustible material that would be under and around the generator set.
5. Be aware of water/sprinkler systems to prevent water intrusion into enclosure openings.
3.5Lifting and Moving the Generator Set
WARNING: The generator set is heavy. Dropping the generator set can cause severe
personal injury or death. Keep feet and hands clear when lifting the generator
set.
CAUTION: The generator is shipped with oil in the crankcase. Keep the generator set upright.
The generator set is heavy and must be handled with care.
· Use a fork lift to move the generator set and set it in place.
· The lifting eyes on the engine and alternator should not be used for lifting the entire
generator set.
· Alternatively, a one-person hand dolly designed to fit the generator set base is
available to move the generator and set it in place.
3.6Staking the Generator Set in Place
WARNING: Pounding the stakes into electric, gas or telephone service lines can result in
severe personal injury or death. Observe the utility company markings and
discuss any other buried lines with the home owner.
Set the generator set in place and pound the four corner stakes into the ground to secure the
generator set in place.
16A029V088 (Issue 13)
3-20133. Step-By-Step Outline of Installation
3.7Electrical Wiring Connections
Refer to the Outline and Systems Drawings for the locations of the electrical conduit openings
on the side of the generator set and the alternative stub-up opening in the base for all power
and communications wiring connections between the generator set and transfer switch.
Route the wires from the transfer switch through the conduit and connect the wires to the mating
terminals on the generator set terminal block.
Two separate conduits are required:
· One is for all AC voltage connections on TB2 or in the AC junction box
· One is for all communications cables on P7, J4 or Ethernet cables.
CalloutComponent
Number
1Electrical Stub-up Area Through Plastic Skid
2Manual/Stop/Remote Switch
3Installer Access
4Removable Service Panel
5Battery Location
A029V088 (Issue 13)17
FIGURE 5.STUBUP OPENING
3. Step-By-Step Outline of Installation3-2013
3.7.1AC Power Supply Connections
WARNING: Electrical connections must be made by a licensed electrician. Improper
installation can lead to electrocution and damage to property.
WARNING: Automatic startup of the generator set during installation can cause severe
personal injury or death. Push the control switch OFF and disconnect the
negative (-) cable from the battery to keep the generator set from starting.
3.7.1.1Main Wiring
WARNING: Refer to the requirements of The National Electrical Code (NFPA No. 70) for
all AC wiring connections.
For access to the wiring connection terminal block (TB2):
· Open the top of the generator set
· Swing the service door wide open, or gently lift up on each side of the front cover to
remove it completely
· Remove the finger guard cover from the terminal block compartment
Connections:
· Use minimum 8 AWG 75 °C conductors for the four AC power output wires (L1, L2, N and
GND). Wire size is determined by the length of the run.
· Connect them to the AC output terminal block (TB-2)
· Torque the terminals per the table on the side of TB-2
· The wires must be routed to the transfer switch in approved liquid-tight conduit
· The conduit can be stubbed up through the bottom stub-up opening or connected to
the conduit opening on the side of the generator set
· If the stub-up opening is used, fill in the stub-up opening with duct seal or mastic tape
to keep out insects and rodents
CAUTION: AC wiring can induce false signals in control and communications wiring. Do not
route in the same conduit.
3.7.2Grounding
Use the Typical System Grounding One-Line Diagrams in this section to be sure that the
generator set, transfer switch, power supply wiring and all connected electrical equipment are
bonded to a common grounding point in accordance with the applicable codes and standards.
WARNING: The generator set grounding terminal (TB2-4) must be connected to the
grounding terminal in the transfer switch. Do not provide a separate
grounding rod for the generator set.
NOTE:Generator neutral is not grounded at the generator set, but at the common
system grounding point.
WARNING: Contact with electrical equipment can result in severe personal injury or
death. It is extremely important that bonding and equipment grounding be
properly done. All metallic parts that could become energized under
abnormal conditions must be properly grounded.
18A029V088 (Issue 13)
3-20133. Step-By-Step Outline of Installation
FIGURE 6.TYPICAL SYSTEM GROUNDING ONE-LINE DIAGRAMS
3.7.3Automatic Transfer Switch
Install the transfer switch in accordance with its Installation Manual and make connections to the
generator set in accordance with the Electrical Connections section of this manual.
3.7.3.1Transfer Switch Communications Wires
WARNING: Interconnecting the generator set and the public utility can lead to the
electrocution of personnel working on the utility lines, damage to equipment
and fire. An approved switching device must be used to prevent
interconnections.
Install the transfer switch in accordance with its Installation Manual.
A029V088 (Issue 13)19
3. Step-By-Step Outline of Installation3-2013
Wiring harnesses are available in various lengths for quick connection between the generator
set and transfer switch. See the Outline and System Drawings Appendix for harness details.
3.7.4Heater and Outlet Connections
3.7.4.1120 Volt Optional Accessories
NOTE:Engine oil heaters are factory installed on models 20GSBB-6714, 20GSBC-
6727, 15GSBB-6720
To supply 120 VAC to power the following accessories, connect 12 AWG 75 °C wires to the
accessory wires in the 120 volt junction box from a 15 amp protected circuit in the main
distribution panel in the house.
· Optional battery heater
· Optional engine heater and alternator drier assembly
· Optional installer-supplied GFCI outlet
· Optional breather shroud/heater
NOTE:The wires my be run through the same conduit as the AC power output wires.
3.7.5Operator Panel
3.7.5.1Operator Panel Communication Wires
NOTE:There are two unmarked connectors on the back of the display, either one
may be used for connecting the display to the generator set.
Wiring harnesses are available in various lengths for quick connection between the generator
set and in-home display. See the Outline and System Drawings Appendix for harness details.
Class 1 wiring methods should be used for the in-home display, Ethernet and transfer switch
communication conductors between the generator set and transfer switch. Separation of Class 2
and power circuits should be maintained per Article 725.136 of 2008 NFPA 70: National
Electrical Code.
See the Operator Manual (A029V089) for information regarding using the operator panel to
operate and monitor the generator set.
3.7.5.2Operator Panel Installation In The Home
Mount the generator set operator panel on a wall, in a convenient location such as next to the
house thermostat.
To install the operator panel:
· In drywall or paneled walls:
1. Drill a hole that is large enough to clear the harness connector on the back of the
operator panel.
2. Route the wires inside the wall, to hide the wires.
3. Mount the operator panel with four No. 6 wood screws or wall anchors.
· On brick, stone or block walls:
1. Mount with spacers to clear the harness connector on the back of the operator panel.
20A029V088 (Issue 13)
3-20133. Step-By-Step Outline of Installation
2. Mount with the appropriate wall anchors.
3. Connect the operator panel to the generator set harness using either of the two 8 pin
connectors on the back of the operator panel.
Refer to the Outline and System Drawings Appendix of this manual for guidelines on how to
connect the operator panel to the generator set.
3.7.5.3Operator Panel Installation In The Generator Set
The operator panel may be installed inside of the generator set.
To install the operator panel in the generator set:
NOTE:The control panel bezel must be removed for installation in the generator set.
1. Remove the bushing in the 1" hole on the control panel.
2. Remove the 4 small screws from the control panel.
3. Pulling the harness through the 1" hole, connect J4 directly to the back of the operator
panel into the connector that lines up with the hole in the metal panel.
4. Replace the 4 small screws.
3.7.6Load Shed Communications Wires
The control cable has the load control wires brought out of the genset (P7-7 and P7-8). Class 1
wiring methods should be used for the in-home display, Ethernet and transfer switch
communication conductors between the generator set and transfer switch. Separation of Class 2
and power circuits should be maintained per Article 725.136 of 2008 NFPA 70: National
Electrical Code.
A029V088 (Issue 13)21
FIGURE 7.OPERATOR PANEL BEZEL
3. Step-By-Step Outline of Installation3-2013
Use 300V 18 gauge 75 °C wire for wiring the relay.
See the following figures for the different ways the relays can be wired.
No.DescriptionNo.Description
1Normally Closed2Load control pin 7 or 8
3Ground pin 44From thermostat
5To air conditioner (load)
Relay Requirement:
· Input: 12Vdc, Max 0.5 Amp
· Contact: Low voltage current, < 40 Amp
· Mounting: No restrictions
FIGURE 8.LOW VOLTAGE RELAY SPDT
22A029V088 (Issue 13)
3-20133. Step-By-Step Outline of Installation
No.DescriptionNo.Description
1Normally Closed2Load Control Pin 7 or 8
3Ground Pin 44From Circuit Breaker
5To Load
Relay Requirement:
· Input: 12Vdc, Max 0.5 Amp
· Contact: 120 V AC, Amp rating for load
· Mounting: Typically in distribution panel
FIGURE 9.HIGH VOLTAGE RELAY SPDT 120V AC LOAD
A029V088 (Issue 13)23
3. Step-By-Step Outline of Installation3-2013
No.DescriptionNo.Description
1Normally Closed2Load Control Pin
3Ground Pin 44From Circuit Breaker
5To Load
Relay Requirements:
· Input: 12Vdc, Max 0.5 Amp
· Contact: 120 V AC, Amp rating for load
· Mounting: Typically in distribution panel
FIGURE 10.HIGH VOLTAGE RELAY DPDT 220V AC LOAD
3.7.7Ethernet Connections Wire
The generator set control board has a connector for Cat 5 Ethernet cable for connection to a
remote modem/router. See Ethernet/Email Interface for setup and operation.
Use Cat 5 Ethernet cable and 300V 18 gauge 75 °C wire for wiring the relay.
Class 1 wiring methods should be used for the in-home display, Ethernet and transfer switch
communication conductors between the generator set and transfer switch. Separation of Class 2
and power circuits should be maintained per Article 725.136 of 2008 NFPA 70: National
Electrical Code.
NOTE:The Internet/Email interface requires “high speed" or “broadband" cable or
DSL service to the house. See Ethernet/Email Interface for a full list of
requirements.
3.7.8Battery
The generator set has a 12 VDC, negative-ground control and engine cranking system. The
engine has a battery charger for recharging during generator set operation.
A battery charger located in the transfer switch keeps the battery charged during generator set
standby.
Refer to the GSBB Specifications Table for battery specifications.
24A029V088 (Issue 13)
Loading...
+ 74 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.