contains important instructions that should be followed during installation and maintenance of thegenerator and batteries.
Beforeoperating the generator set (genset),
readthe Operator Manual (983−0104) and becomefamiliar with it and the equipment.
Note: Safe and efficient operation can be achievedonly ifthe equipment is properly operated and main-tained. Many accidents are caused by failure to fol-low fundamental rules and precautions.
The following symbols, found throughout thismanual, alert you to potentially dangerous condi-tions to the operator, service personnel, or theequipment.
DANGER
hazards which will result in severe personal injury or death.
WARNING
unsafe practice which can result in severe per-sonal injury or death.
This symbol warns of immediate
This symbol refers to a hazard or
Lead-acid batteries emit a highly explosive
hydrogen gas that can be ignited by arcing,
sparking, smoking, etc.
EXHAUST GASES ARE DEADLY
WARNING
constituentsare known to the state of Californiato cause cancer, birth defects, and other repro-ductive harm.
Be sure the unit is well ventilated.
Providean adequate exhaust system to
Exhaust height should be tall enough to
Do not use exhaust gases to heat a compart-
ment.
Visually and audibly inspect the exhaust daily
for leaks per the maintenance schedule.
Make sure that exhaust manifolds are se-
Engine exhaust and some of its
properlyexpel discharged gases away fromenclosed or sheltered areas and areaswhere individuals are likely to congregate.
help clear gases, avoid accumulation ofsnow or in accordance with local mechani-cal code.
cured and not warped.
CAUTION
unsafepractice which can result in personal in-jury or product or property damage.
This symbol refers to a hazard or
FUEL AND FUMES ARE FLAMMABLE
Fire,explosion, and personal injury or death can re-sult from improper practices.
All persons handling propane are required to
be trained and qualified, according to NFPAcode.
Natural gas is lighter than air, and will tend
to gather under hoods. Propane is heavierthanair, and will tend to gather in sumps or
low areas.
Be sure all fuel supplies have a positive shutoff
valve.
Be sure battery area has been well-ventilated
prior to servicing near it.
MOVING PARTS CAN CAUSE SEVERE PERSONAL INJURY OR DEATH
Do not wear loose clothing or jewelery and
keep your hands away from all moving parts.
Loose clothing and jewelry can become
caught in moving parts.
If adjustment must be made while the unit is
running, use extreme caution around hotmanifolds, moving parts, etc.
Before starting work on the generator set, dis-
connect battery charger from its AC source,then disconnect starting batteries, negative (-)cablefirst. This will prevent accidental starting.
To prevent accidental air starting, make sure
the air supply line is connected until the generator set is ready to start.
Make sure that fasteners on the generator set
are secure. Tighten supports and clamps,
keep guards in position over fans, drive belts,
etc.
iii
BATTERIES CAN EXPLODE CAUSING
SEVERE SKIN AND EYE BURNS AND
RELEASE TOXIC ELECTROLYTES
Wear safety glasses.
Do not smoke.
Do not dispose of the battery in a fire.
The battery is capable of exploding.
Do not open or mutilate the battery.
Releasedelectrolytes has been known to
be harmful to the skin and eyes, and betoxic.
Removewatches, rings and other metal ob-
jects, and use tools with insulated handles.
Batteries present the risk of high short cir-
cuit current.
To prevent arcing when disconnecting the bat-
tery, first disconnect the battery charger, thenthe negative (−) battery cable and finally thepositive (+) cable.
To prevent arcing when reconnecting the bat-
tery, first reconnect the positive (+) cable, thenthe negative (−) cable, and finally, reconnectthe battery charger.
When replacing the generator set battery, al-
ways use a 26 R, maintenance free, 12 voltbattery with a minimum battery CCA of 530.
ELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL INJURY OR DEATH
DANGER
on electrical components. High voltages cancause injury or death. DO NOT tamper with in-terlocks.
Follow all applicable state and local electrical
codes.Have all electrical installations per-formed by a qualified licensed electrician. Tagand lock open switches to avoid accidental clo-sure.
Use extreme caution when working
isolation switch or an approved paralleling device.
Remove electric power before removing pro-
tective shields or touching electrical equipment.
Use rubber insulative mats placed on dry wood
platforms over floors that are metal or concretewhen around electrical equipment.
Do not wear damp clothing (particularly wet
shoes) or allow skin surface to be damp whenhandling electrical equipment.
Do not wear jewelry.
Jewelry can short out electrical contacts
and cause shock or burning.
MEDIUM VOLTAGE GENERATOR SETS (601V to 15kV)
DANGER
sult in severe personal injury or death.
Special equipment and training is required to
work onor around medium voltage equipment.Operation and maintenance must be doneonlyby persons trained and qualified to workon such devices.
WARNING
ment, as this can cause severe personal injuryor death.
Plan the time for maintenance with authorized
personnel sothat the equipment can be de-en-ergized and safely grounded.
Due to the nature of medium voltage electri-
Unauthorizedpersonnel must not be permitted
near energized equipment.
Improper use or procedures will re-
Do not work on energized equip-
cal equipment, induced voltage remainseven after the equipment is disconnectedfrom the power source.
Do not connect the generator set directly to
any building electrical system.
CAUTION
the generator set into the utility line. This
creates a potential for electrocution or property
damage. Connect only through an approved
Hazardous voltages can flow from
iv
GENERAL SAFETY PRECAUTIONS
WARNING
changer pressure cap while the engine is running.
DO NOT open a radiator or heat ex-
Make sure generator set is mounted in a man-
ner to prevent combustible materials from accumulating under the unit.
Remove all unnecessary grease and oil from
the unit.
Allow the generator set to cool and bleed the
system pressure first.
Coolantsunder pressure have a higher boil-
ing point than water.
WARNING
Used engine oils have been identi-fied by some state or federal agencies as caus-ing cancer or reproductive toxicity.
When checking or changing engine oil, take
care not to ingest, breathe the fumes, or con-tact used oil.
Keep multi-class ABC fire extinguishers
handy.
Class A fires involve ordinary combustible
materials such as wood and cloth(ref. NFPA No. 10)
Class B fires, combustible and flammable
liquid fuels and gaseous fuels(ref. NFPA No. 10)
Class C fires, live electrical equipment.
(ref. NFPA No. 10)
Make sure that rags are not left on or near the
engine.
Accumulated grease and oil can cause
overheating and engine damage whichpresent a potential fire hazard.
Keep the generator set and the surrounding
area clean and free from obstructions. Re-move any debris from the set and keep thefloor clean and dry.
Do not work on this equipment when mentally
or physically fatigued, or after consuming anyalcohol or drug that makes the operation ofequipment unsafe.
WARNING
Substances in exhaust gases havebeen identified by some state or federal agen-cies as causing cancer or reproductive toxicity.
Take care not to breathe or ingest or come into
contact with exhaust gases.
Do not store any flammable liquids, such as
fuel, cleaners, oil, etc., near the generator set.A fire or explosion could result.
Wear hearing protection when going near an
operating generator set.
WARNING
Avoid contact with hot metal partssuch asthe radiator, turbo charger and exhaustsystem to prevent serious burns.
KEEP THIS MANUAL NEAR THE GENSET FOR EASY REFERENCE
v
THIS PAGE INTENTIONALLY LEFT BLANK
vi
1. Introduction
ABOUT THIS MANUAL
This manual is a guide for the installation of the gen-erator set(s) listed on the front cover. Proper instal-lation is essential for top performance, reliable op-
eration and safety. The installation must complywith all applicable building codes. Read through this
manual before starting the installation.
Information For After Installation
WARNING
severe personal injury, death and damage toequipment. The installation must comply withallapplicable building codes. It is strongly rec-ommendedthat the installer be properly trainedand licensed to perform electrical and mechani-calequipment installations, however a personwith the proper knowledge and experience ininstallingelectrical and mechanical equipmentinstallations may also install this genset.
Refer to Appendix E. Specifications for specific in-
formation about the system and its components.
Refer toAppendix F. Outline and System Drawings
for specific information about the installation and thewiring connections.
See the Operator Manual for operation and mainte-nance instructions.
Improper installation can result in
PRE-INSTALLATION CONSIDERATIONS
The location of the generator set affects all other as-pects ofthe installation, such as the lengths of elec-tric wiring and gas lines, and is one of the first deci-sions to be made. The installation cannot be com-pletedwithout connections to an automatic transferswitch and a source of fuel, Natural Gas or Propane,which must be inspected by the gas and electric uti-lities.
Decide where to locate the generator set and auto-matictransfer switch, how fuel supply will be pro-vided, what materials are required (wiring, fuel lines,etc.),and what site preparations are necessary (ac-cess to and preparation of the site, trenches, etc.).Prior co-ordination will reduce delays and theamount of time power has to be interrupted.
IMPORTANT NOTICE: Depending on the localityand use of the generator set, it may be necessary toobtain an airquality emissions permit before instal-lation begins. Check with the local pollution controlor air quality authority.
Automatic Transfer Switch
The Model GSAA generator set is for installationonly with Cummins Onan Model RSS automatictransferswitches. Use of other makes and modelsof transfer switches voids the Model GSAA genera-tor set Warranty.
Note: Manuals are updated from time to time to re-flect changes in the equipment and its specifica-tions. See an authorized Cummins Onan representa-tive for current manuals.
Install the transfer switch in accordance with itsInstallation Manual and make connections to the
generatorset in accordance with Section 4. Electri-cal Connections.
1-1
SPECIFICATIONS
FUEL CONSUMPTION:
@ 1/2 Load
@ Full Load
Fuel Supply Pressure
Recommended LP Tank Size (necessary to run thegenerator set for seven days)
CONTROLLER: Integrated Microprocessor-Based Engine, Generator and Transfer Switch Controller
DC SYSTEM:
Nominal Battery Voltage
Battery Group
Battery Type
Minimum Battery CCA (Cold Cranking Amps)
WEIGHT (WET): 460 lbs (209 kg)
SIZE (L x W x H): 48 x 43 x 31.5 in (1219 x 864 x 800 cm)
SOUND LEVEL: Less than 64 dB(A) @ 23 ft (7 meters) and 12 kW of Load
Natural Gas Installation
(1000 BTU/ft3)
122 ft3/hr (3.5 m3/hr)
191 ft3/hr (5.4 m3/hr)
5−11 H2O
500 Gallon (Contact you local gas company to verify
the tank size required for your application)
0.030 in (0.76 mm)
NGK-BPR6ES (P/N 167−1658)
10 ft-lbs (13.5 N-m)
0.004in (0.10 mm)
1.7 quart (1.6 liter)
12 volts
26 R
Maintenance Free
Propane Installation
(2500 BTU/ft3)
53 ft3/hr (1.5 m3/hr)
88 ft3/hr (2.5 m3/hr)
7−11 H2O
530
1-2
Generator Set Location
WARNING
doors, windows and other openings into the house and where the exhaust gases will disperse away
from the house.
EXHAUST GAS IS DEADLY! Install the generator set out-of-doors only, away from
PALATE
(PLACE GENSET
ON STABLE,
LEVEL GROUND)
FIGURE 1-1. GENERATOR SET LOCATION
5 FEET (1.6 METERS)
FROM ALL OPENINGS
TO THE HOUSE
Generator set (genset) location is critical for safety and good performance. Follow the guidelines below :
Install out-doors only.
Call the local utilities to mark the loca-
tions of buried utility services (gas, electric,telephone)before digging trenches for fuel andelectric lines.
Locatethe genset as far away as practical from
Do not locate the genset where snow
drifts, plant growth, lawn clippings and otherobjects are likely to block the ventilation open-ings.
noise sensitive areas such as bedrooms, living
Ask the homeowner for the location of
any other buried components.
Locateand orient the genset such that the pre-
vailing winds will carry exhaust gases and fuelleaks away from the house.
Genset must be at least 5 feet (1.6 me-
ters) away from all openings to the house.
Do not locate the genset in a three-
sided niche of the house, under an overhang or
in a low-lying area or next to a basement.
room windows and neighbors.
Locate the genset where it will be protected
from vehicular traffic and vandalism.
Locate the genset as close as practical to the
house to reduce the lengths electric wiring and
fuel lines.
Place the genset on stable ground, not subject
to flooding.
Note: The area should be leveled and compacted with
sand or pea gravel.
1-3
Natural Gas Supply
The Natural Gas supply meter may need to be exchanged for a higher capacity meter to supply the
additional gas consumed by the generator set. At
full load, the generator set alone requires 191,000
BTU/hr. To determine the required meter capacity,
generator set consumption must be added to thegas consumed for heating, cooking, clothes drying,etc. A typical installation might require a400,000BTU meter.
Considerationshould also be given to utilizing highpressure gas supply (2 psi), if available, to reducethe required size, and therefore cost, of gas piping,especially if the location of the generator set re-quires a long supply line.
Note: The wire size varies, depending on distance (see Table 4-1).
10. Communications Wiring Connectors: Up to
twelve UL listed 18 AWG fork terminals for Item
9 wires (Cummins Part Number 0332−2527).
11. DC Conduit for Item 9 wires.
12.One or two 12 volt relays for load management(optional)
Note: It is recommended that the two 18AWGwiresfrom Generator set terminals TB1-7 and TB1-8 forload management bepulled along with the other con-trol/communicationswires at the time of installationso that they are available if it is determined later thatload management is necessary.
Tools Required
Note: An older site might require upgrading and re-pair of the gas supply system, which should bescheduled to minimize power and gas supply inter-ruptions.
Materials Required
The installer must provide the following materials tocomplete the installation:
1.Gas line and step down regulators (as re-quired) for gas connections:
A.Natural Gas at 191,000 BTU/hour
B.Propane at220,000 BTU/ hr or 2.4 gallons/
hour
C.Gas pressure at generator set: 5−11 inch
WC
2.UL listed pipe dope
3.Electrical Conduit sealing putty
4.Cat 5 Ethernet cable (optional)
5.Fourwall anchors and 4 No. 6 black screws formounting the Operator Panel.
6.AC Power Output Wiring: Four 8 AWG 90Cwires for runs up to 125 feet. (L1, L2, N andGND)
7.AC Accessory Supply Wiring: Two 12 AWG90C wires for runs up to 125 feet. (Hot andNeutral)
8. AC Conduit for Items 6 and 7, which may be run
in the same conduit.
9. Control/Communications Wiring: Up to twelve
18 AWG wires, depending on Transfer Switch.
(Generator set TB1-1 through TB1-12)
Use a forklift to move the generator set and set it inplace.Alternatively, aone-man hand dolly designedto fit the generator set base is available to move thegenerator set and set it in place (P/N 0541-1624).
Hand tools required include the following:
1.Wirestripper and lug crimper for terminatingthe twelve communications wires.
2.Rachet set with 10 mm socket and extension.
3.Two pipe wrenches for gas connections.
4.Phillips-head and flat-blade screwdrivers.
Loose Parts Shipped With the Generator
The following loose parts are shipped with theGSAA generator set.
Two Keys (P/N A026G567)
Quick Connect Guide (located in the battery
box)
Literature − Operator Manual, Installation
Manual, Setup Guide, and Warranty Statement
1-4
INSTALLATION CODES AND STANDARDS
FOR SAFETY
WARNING
sole responsibility for following all applicable
local codes and regulations.
The following list of Installation Codes and Stan-
The generator set installer bears
TABLE 1-1. INSTALLATION CODES AND SAFETY RECOMMENDATIONS
dards for Safety applies to the installation and operation of standby generator sets. This list is for reference only and not intended to be inclusive of all
applicable codes and standards. The address of
each agency is listed so that copies of the codes
may be obtained for reference. Installation codes
and recommendations are subject to change, and
may vary by location or over time.
NFPA 70National Electric CodeNFPA 37Installation and Use of Stationary Combus-
tion Engines and Gas TurbinesNFPA 54National Fuel Gas CodeNFPA 58Storage and Handling of Liquefied Petro-
National Fire Protection Association,470 Atlantic AvenueBoston, MA 02210
Canadian Standards Association,Housing and Construction Materials Section178 Rexdale Blvd.Rexdale, Ontario, Canada M9W 1R3
Documents SectionP.O. Box 1015North Highlands, CA 95660
Underwriters Laboratories, Inc.333 Pfingsten RoadNorthbrook, IL 60062-2096
1-5
2. Step-by-Step Outline of Installation
INTRODUCTION
WARNING
plyingwith all applicable installation codes andsafety requirements.
This section is a step-by-step overview of a typicalinstallation. This section includes:
Locating the site
Generator set Clearances
Preparing the site
Moving the generator set
Placing the generator set
The installer is responsible for com-
Connecting the generator set
Review this section, then refer to the detailed in-structionsthat are given in the following sections forspecific procedures and important safety precau-tions before starting the installation.
LOCATING THE SITE
These generator sets are housed in a weather-pro-tective enclosure for installation out-of-doors on anon-combustible base.
Choose asite close to the electric service and Natu-ral Gas meter or Propane tank. The main distribu-tion, transfer switch, and sub-panels are usually in-side the house.
ELECTRIC
METER
GENERATOR
UNDERGROUND
ELECTRIC
SERVICE
SET
TRANSFER
SWITCH
DISTRIBUTION
PANEL
GAS
METER
GAS
SHUTOFF
VALVE
UNDERGROUND
GAS SERVICE
FIGURE 2-1. TYPICAL GENERATOR SET SITE
2-1
GENERATOR SET CLEARANCES
The generator set must be a minimum of 3 ft
(915 mm) from combustible material (NFPA 37).
Leave at least 3 ft (915 mm) all around the generator set enclosure for access to the inside (NEC Art.
110-26a, Art. 110-26b). The generator set must be
at least 5 ft (1524mm) from any opening (window,door,vent, etc.) in the wall, and the exhaust must notbe able to accumulate in any occupied area.
Refer to the Outline Drawing (page F-7) for theclearancerequired to fully open the maintenanceand service doors.
PREPARING THE SITE
If the site is not on level ground prepare an arealarge enough to easily hold the generator set so thatit can be mounted level. If you add fill to the site, besure totamp the ground until it is firm and stabilized.
Preparea site at least 48 in by 34 in (1219 mm by864mm) on firm ground. Sites on inclines require
more area. Add a layer of sand or pea gravel deep
enough so that you can level the generator set. Remove any combustible material that would be under
and around the generator set.
5 FT (1.6 M) MIN TO
ANY OPENING
FIGURE 2-2. GENERATOR SET CLEARANCES
2-2
LIFTING AND MOVING GENERATOR SET
WARNING
ping the generator set can cause severe personal injury or death. Keep feet and hands clear
when lifting the generator set.
CAUTION
in the crankcase. Keep it upright.
The generator set is heavy and must be handledwith care. Use a forklift to move the generator setand set it in place. Alternatively, a one-man handdolly designed to fit the generator set base is avail-able to move the generator set and set it in place.
The generator set is heavy. Drop-
The generator set is shipped with oil
STAKING GENERATOR SET IN PLACE
WARNING
gas, or telephone service lines can result in se-
Pounding the stakes into electric,
vere personal injury or death. Observe the utility
company markings.
Set the generator set in place and pound the four
corner stakes into the ground to secure the generator set in place.
ELECTRICAL WIRING CONNECTIONS
Refer to Appendix F Outline and System Drawings
forthe locations of the electrical conduit openingson the side of the generator set and the alternativestub-upopening in the base for all power and com-municationswiring connections between the gener-ator set and transfer switch.
Route the wires from the transfer switch throughconduit and connect the wires to the mating termi-nals in the generator set terminal board compart-ment.Two separate conduits are required. One isfor all A/C voltage connections on TB2 and TB3.The other is for all TB1 and ethernet cables.
CORNER
STAKE
WIRING TERMINAL BOARD
COMPARTMENT
ELECTRICAL WIRING
STUBUP OPENING
FIGURE 2-3. ELECTRICAL WIRING TERMINAL BOARDS AND STUBUP OPENING
2-3
GAS LINE CONNECTIONS
WARNING
explosion that can result in severe personal injury or death. Do not smoke or allow any flame,
spark, pilot light, or other ignition sources near
fuel or in the installation area. Read the impor-tant safety precautions in the Fuel System sec-
Fuel presents the hazard of fire or
tion.
Refer to Appendix F Outline and System Drawings
for the location of the fuel supply connection through
the side of the generator set. A flexible fuel hose is
packaged inside the generator set (Assembly part
number: 0501−0776−06). Connect it between the
3/4 NPT fitting on the generator set and the fuel sup-ply line.
MEASURE INLET FUEL
PRESSURE HERE
FLEXIBLE FUEL HOSE
(P/N 0501−0776−06)
FIGURE 2-4. GAS LINE CONNECTIONS
2-4
3. Mechanical
LOCATION AND ACCESS
These generator sets are designed for installationout-of-doors in its weather-protective enclosure.
Factors to consider when deciding where to locatethe generator set include:
Proximity of generator set, transfer switch,
loads and Natural Gas fuel lines or Propanetanks.
Access for maintenance and service. Refer to
the Outline Drawing (page F-7) for the clear-ance required to fully open the maintenanceand service doors.
Security from vandalism, flooding and vehicu-
lar traffic.
Noise levels and proximity of property lines.
Safe dispersal of engine exhaust and cooling
air away from buildings, habitable areas, andpeople.
Possible obstructions to ventilation caused by
snowdrifts,plant growth, lawn clippings, fallingleaves, etc.
See Locating the Site in Section 2.
FUEL SYSTEM
WARNING
qualifiedservice technicians. Improper installa-tion presents hazards of fire and improper op-eration,resulting in severe personal injury orproperty damage.
The generator set name plate is marked to indicatethe fuel type, Natural Gas or Propane.
WARNING
explosiveand can cause severe personal injuryor death. Do not smoke if you smell gas or arenear fuel tanks or fuel-burning equipment or arein an area sharing ventilation with such equip-ment. Keep flames, sparks, pilot lights, electri-cal arcs and arc-producing equipment and allothersources of ignition well away.Keep a typeABC fire extinguisher handy.
In all fuel system installations, cleanliness is of theupmost importance. Make every effort to prevententrance ofmoisture, dirt, excess thread sealant, orcontaminants of any kind. Clean all fuel systemcomponents before installing.
Fuel systems must be installed by
Gaseous fuels are flammable and
ENGINE EXHAUST
The exhaust system of this generator set was de-signed for this engine and is complete. Do notmodify oradd to the exhaust system of this genera-tor set.
WARNING
haust system must terminate away from build-ing vents, windows and doors and shelteredspaces that may not have ample fresh air ven-tilation.
Do not use generator set discharge air or engine ex-haust for heating a room or enclosed space.
WARNING
carry carbon monoxide gas (odorless and invisible) which can cause asphyxiation and death.
Never use engine discharge air or exhaust for
heating a room or enclosed space.
EXHAUST GAS IS DEADLY! The ex-
Engine discharge air and exhaust
The section of flexible fuel hose supplied with thegenerator set must be used between the engine’sfuel system and fuel supply line to protect the fuelsystem from damage caused by vibration, expan-sion and contraction. The fuel hose must beinstalled according to all applicable codes and stan-dards.
Gaseous-fuel supply system design, materials,components, fabrication, assembly,installation,testing,inspection, operation and maintenancemust comply with the applicable codes. See NFPAStandards No. 37, No. 54, and No. 58.
Mostcodes require a manual shutoff valve ahead ofa flexible fuel hose. The manual valve should be of
the indicating type. The generator set has an electric (battery-powered) shutoff valve included between the fuel supply and the carburetor.
Until the generator set is connected, cap the fuel line
stub-up at the generator set to prevent dirt from en-
3-1
tering and gas discharging if the gas supply shutoff
valve is opened inadvertently.
Refer to Appendix E. Specifications for the fuel inlet
size.
NATURAL GAS FUEL SYSTEM
(191 cubic feet/hr) delivered to the generator set inlet at 5−11 inches (28 mm) WC (Water Column). If
the meter serves other gas appliances such as a furnace, water heater, or stove, you must consult with
the local Natural Gas utility to determine whether
the Natural Gas meter is adequate.
The generator set requires an adequate fuel supplyto operate correctly at full load. The length of the fuelsupply pipe from the gas service entrance to thegenerator set must be known to determine the cor-rectfuel pipe size. Refer to Table 3-1 to find the fuelsupply requirement for your generator set. Pipemust be minimum of schedule 40 subject to the au-thority having jurisdiction.
Natural Gas Supply Line Size
The generator set requires up to 191,000 BTU/hr
It is important to consider other loads operated fromthe fuel supply pipe. Other loads, such as spaceheating and water heating equipment, must also bedetermined to correctly size the fuel pipe. Use thetotal load requirement of the fuel supply line to de-termine the size of the fuel supply pipe. UseTable3-1 to determine the correct pipe size. (typi-cally, 1ft
Note: When the fuel delivery value falls between twocolumns, use the larger value.
GENERATOR SET
3
/hr =1000 BTU/hr, )
SHUTOFF VALVE
GAS METER
FIGURE 3-1. TYPICAL NATURAL GAS INSTALLATION
TABLE 3-1. NATURAL GAS PIPE CAPACITY—CUBIC FEET OF GAS PER HOUR
NOMINAL IRON
PIPE SIZE
(INCHES)
3/4360250200
1680465375320285260240220205195
1-1/41400950770660580530490460430400360325300280
Maximum pipe capacity in cubic feet per hour of 0.60 specific gravity Natural Gas with a pressure drop of 0.5 inches (1.27 mm)
WC over the length
102030405060708090100125150175200
LENGTH OF PIPE IN FEET
3-2
PROPANE FUEL SYSTEM
WARNING
NFPA Standard No. 58 requires all
persons handling and operating Propane to be
trained in proper handling and operating procedures.
WARNING
Fuel leaks can lead to explosive ac-cumulations of gas. Propane sinks in air andcan accumulate inside housings, basementsand other below-grade spaces. Prevent gasleaks and the accumulation of gaseous fuel inthe event of a leak.
Converting from Natural Gas to Propane(Vapor Withdrawal)
The generator set leaves the factory set up for Natu-ral Gas. The generator set must be converted as fol-lows for use with Propane vapor:
1.Disconnect the fuel hose at the gas/air mixerand thread in the gas orifice wire-tied tothe en-gine lifting bracket (Figure 3-2).
2.Insert the air orifice supplied with the flexiblegas hose into the inlet of the air intake resonator(Figure 3-3). (Orifice used only on spec A units)
3.Configure the control for Propane (page
5−1).
RIGHT
HAND
DOOR
AIR
ORIFICE
FIGURE 3-3. INSTALLING THE AIR ORIFICE
INTAKE
RESONATOR
(SPEC A ONLY)
GAS
ORIFICE
SPEC A
GAS/AIR MIXER
FIGURE 3-2. INSTALLING THE PROPANE GAS
ORIFICE
3-3
Propane Vapor Fuel Supply Line Size and
Pressure
Fuel line size depends on the amount of fuel needed
to run the generator set at full load at the distance
the fuel must be moved. The generator set requires
3
88ft
/hrof Propane Vapor at full load delivered to
GENERATOR
SET
SHUTOFF
VALVE
REGULATOR
SECONDARY
REGULATOR
the generator set inlet at 7−11 inches WC (Water
Column) gas pressure. Figure 3-4 shows a typical
Propane Vapor installation and Table 3-2 lists fuel
capacity for given distances and pipe size.
Size the fuel line so that the Propane vapor pressure
drops no more than 2 inches WC from no load to full
load.
TABLE 3-2. PROPANE VAPOR PIPE CAPACITY—CUBIC FEET OF GAS PER HOUR
NOMINAL IRON
PIPE SIZE
(INCHES)
3/422715712610795
1428293236201179164151138129123110101
1-1/4882598485416365333308289207252230204
1-1/21323920743624567570472434409390346315
224881732138611971058958882819768724642598
Maximum pipe capacity in cubic feet per hour of Propane vapor with a pressure drop of 0.5 inches (1.27 mm) WC over the
102030405060708090100125150
LENGTH OF PIPE IN FEET
length
3-4
Fuel Pressure
WARNING
cause gas leaks which can lead to fire and severe personal injury or death. Gas supply pressure must be adjusted to Specifications by
trained and experienced personnel.
Satisfactoryperformance requires that the PropaneVapor be supplied at a pressure within the range of7-11 inches WC (water column).
When measuring supply pressure, the most accu-rate reading would be on the input side of the sole-noid valve.
High gas supply pressure can
Recommended Fuel
Use clean, fresh HD-5 grade Propane or equivalentproduct consisting of at least 90 percent Propane.Commercial Propane may contain more than 2.5percent butane which can result in poor fuel vapor-ization and low tank pressure resulting in poor en-gine starting in low ambient temperatures (below32F (0C).
WARNING
or explosion that can cause severe personal in-jury or death. Do not permit any flame, spark,
Propane presents the hazard of fire
arc-producing equipment, switch, pilot light,
cigarette, or other ignition source near the fuel
system. Keep an ABC type fire extinguisher
nearby.
Propane Tank Size
To assist in the proper selection of the Propane tank,follow the guidelines below.
Propanetanks are sized by the number of gal-
lons of water they can hold, not the amount offuel they hold. See Table 3-3.
Propane tanks are generally filled to only 80%
of their water capacity.Therefore, a 500 lb tankresults in 400 lb tank capacity.
Low ambient temperatures affect the amount of
fuel available from the Propane tank.
Approximately60% of the fuel (in gallons) filled
in the tank can be effectively used. Therefore,a 500 lb tank results in 300 gallon capacity.
Propane tanks must be fitted with a pressure
reducing regulator before connection to thegenerator set to prevent fuel system damage.
Propane tanks must be located at least 10 ft
(3048 mm) from any source of combustion (in-cluding the generator set).
TABLE 3-3. REQUIRED PROPANE TANK SIZE IN GALLONS (LITERS) FOR INDICATED TEMPERATURES
Before operating the set, test the Propane fuel system for leaks. Energize the fuel solenoid from a separate 12-volt DC source before testing the fuel system. Testing must conform to procedures listed in
NFPA-58, or to the UL recommended test procedure, as follows:
After assembly and before initial operation, all fuelsystem connections, hose valves, regulators, andfittings must be tested and proven free of leaks us-ing a soap-and-water (or equivalent) solution whilethe system is under gas or air pressure of at least
1.5 times the supply pressure or 3 psi (20.7 kPa)
minimum.
Other approved methods of detecting leaks can be
used if appropriate. DO NOT use a flame to test for
gas leaks.
WARNING
plosion or fire which can result in severe per-sonalinjury or death. Do not smoke or allow anyflame, spark, pilot light, arc-producing equip-ment, switch, or other ignition sources aroundfuel or fuel components.
Propane presents the hazard of ex-
3-6
4. Electrical Connections
AC POWER SUPPLY CONNECTIONS
WARNING
made by a licenced electrician. Improper instal-lation can lead to electrocution and damage toproperty.
Automatic startup of the generator set duringinstallationcan cause severe personal injury ordeath.Push the control switch Off and discon-nect the negative (−) cable from the battery tokeep the generator set from starting.
Electrical connections must be
Wiring
Refer tothe requirements of The National ElectricalCode (NFPA No. 70) for all AC wiring connections.
For access to the wiring connection terminalboards,open the top of the generator set, swing theleft service door wide open and remove the coverfrom the terminal board compartment (Figure 4-1).
Use 8 AWG 90C conductors for the four AC poweroutput wires (L1, L2, N and GND), connect them to
the AC output terminal board (TB-2). Torque the
termninals to 25 lb−inch (2.8 N−m).
Refer toAppendix F. Outline and System Drawings
for connections at the transfer switch.
The wires must be routed to the transfer switch inapproved liquid-tight conduit. The conduit can bestubbed up through the bottom stubup opening orconnectedto the conduit opening onthe side of thegeneratorset. If the stubup opening is used, fill inthe stubup opening with duct seal or mastic tape tokeep out insects and rodents.
Note: See ACCESSORY SUPPLY WIRING (page 4-2)for AC wiring that may share the same conduit as ACoutput wiring.
CAUTION
incontrol and communications wiring. Do notroute in the same conduit.
AC wiring can induce false signals
WIRING TERMINAL
BOARD COMPARTMENT
ELECTRICAL WIRING
STUBUP OPENING
FIGURE 4-1. WIRING TERMINAL BOARDS
4-1
ACCESSORY SUPPLY CONNECTIONS
To supply 120 VAC to power the GFCI outlet on the
side of the generator set, optional battery heater
(P/N 0333−0770) and optional engine oil and carburetor heater (P/N 0333-0771), connect two 12 AWG
90C wires to generator set terminal block TB3 (Hotand Neutral) from a 15 amp protected circuit in themain distribution panel in the house. The wires maybe run through the same conduit as the power sup-ply wires.
Grounding
The generator set, transfer switch, power supplywiring,and all connected electrical equipment mustbe bonded to a common grounding point in accor-
dance with applicable codes or standards (Figure
4-2).
WARNING
The generator set grounding terminal (TB2-4) must be connected to the grounding
terminal in the transfer switch. Do not provide a
separate grounding rod for the generator set.
Note that generator neutral is not grounded at thegeneratorset, but at the common system groundingpoint.
WARNING
Contact with electrical equipmentcan result in severe personal injury or death. It isextremely important that bonding and equip-ment grounding be properly done. All metallicparts that could become energized under ab-normal conditions must be properly grounded.
4-2
Loading...
+ 56 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.