contains important instructions that should be followed during installation and maintenance of thegenerator and batteries.
Beforeoperating the generator set (genset),
readthe Operator Manual (983−0104) and becomefamiliar with it and the equipment.
Note: Safe and efficient operation can be achievedonly ifthe equipment is properly operated and main-tained. Many accidents are caused by failure to fol-low fundamental rules and precautions.
The following symbols, found throughout thismanual, alert you to potentially dangerous condi-tions to the operator, service personnel, or theequipment.
DANGER
hazards which will result in severe personal injury or death.
WARNING
unsafe practice which can result in severe per-sonal injury or death.
This symbol warns of immediate
This symbol refers to a hazard or
Lead-acid batteries emit a highly explosive
hydrogen gas that can be ignited by arcing,
sparking, smoking, etc.
EXHAUST GASES ARE DEADLY
WARNING
constituentsare known to the state of Californiato cause cancer, birth defects, and other repro-ductive harm.
Be sure the unit is well ventilated.
Providean adequate exhaust system to
Exhaust height should be tall enough to
Do not use exhaust gases to heat a compart-
ment.
Visually and audibly inspect the exhaust daily
for leaks per the maintenance schedule.
Make sure that exhaust manifolds are se-
Engine exhaust and some of its
properlyexpel discharged gases away fromenclosed or sheltered areas and areaswhere individuals are likely to congregate.
help clear gases, avoid accumulation ofsnow or in accordance with local mechani-cal code.
cured and not warped.
CAUTION
unsafepractice which can result in personal in-jury or product or property damage.
This symbol refers to a hazard or
FUEL AND FUMES ARE FLAMMABLE
Fire,explosion, and personal injury or death can re-sult from improper practices.
All persons handling propane are required to
be trained and qualified, according to NFPAcode.
Natural gas is lighter than air, and will tend
to gather under hoods. Propane is heavierthanair, and will tend to gather in sumps or
low areas.
Be sure all fuel supplies have a positive shutoff
valve.
Be sure battery area has been well-ventilated
prior to servicing near it.
MOVING PARTS CAN CAUSE SEVERE PERSONAL INJURY OR DEATH
Do not wear loose clothing or jewelery and
keep your hands away from all moving parts.
Loose clothing and jewelry can become
caught in moving parts.
If adjustment must be made while the unit is
running, use extreme caution around hotmanifolds, moving parts, etc.
Before starting work on the generator set, dis-
connect battery charger from its AC source,then disconnect starting batteries, negative (-)cablefirst. This will prevent accidental starting.
To prevent accidental air starting, make sure
the air supply line is connected until the generator set is ready to start.
Make sure that fasteners on the generator set
are secure. Tighten supports and clamps,
keep guards in position over fans, drive belts,
etc.
iii
Page 6
BATTERIES CAN EXPLODE CAUSING
SEVERE SKIN AND EYE BURNS AND
RELEASE TOXIC ELECTROLYTES
Wear safety glasses.
Do not smoke.
Do not dispose of the battery in a fire.
The battery is capable of exploding.
Do not open or mutilate the battery.
Releasedelectrolytes has been known to
be harmful to the skin and eyes, and betoxic.
Removewatches, rings and other metal ob-
jects, and use tools with insulated handles.
Batteries present the risk of high short cir-
cuit current.
To prevent arcing when disconnecting the bat-
tery, first disconnect the battery charger, thenthe negative (−) battery cable and finally thepositive (+) cable.
To prevent arcing when reconnecting the bat-
tery, first reconnect the positive (+) cable, thenthe negative (−) cable, and finally, reconnectthe battery charger.
When replacing the generator set battery, al-
ways use a 26 R, maintenance free, 12 voltbattery with a minimum battery CCA of 530.
ELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL INJURY OR DEATH
DANGER
on electrical components. High voltages cancause injury or death. DO NOT tamper with in-terlocks.
Follow all applicable state and local electrical
codes.Have all electrical installations per-formed by a qualified licensed electrician. Tagand lock open switches to avoid accidental clo-sure.
Use extreme caution when working
isolation switch or an approved paralleling device.
Remove electric power before removing pro-
tective shields or touching electrical equipment.
Use rubber insulative mats placed on dry wood
platforms over floors that are metal or concretewhen around electrical equipment.
Do not wear damp clothing (particularly wet
shoes) or allow skin surface to be damp whenhandling electrical equipment.
Do not wear jewelry.
Jewelry can short out electrical contacts
and cause shock or burning.
MEDIUM VOLTAGE GENERATOR SETS (601V to 15kV)
DANGER
sult in severe personal injury or death.
Special equipment and training is required to
work onor around medium voltage equipment.Operation and maintenance must be doneonlyby persons trained and qualified to workon such devices.
WARNING
ment, as this can cause severe personal injuryor death.
Plan the time for maintenance with authorized
personnel sothat the equipment can be de-en-ergized and safely grounded.
Due to the nature of medium voltage electri-
Unauthorizedpersonnel must not be permitted
near energized equipment.
Improper use or procedures will re-
Do not work on energized equip-
cal equipment, induced voltage remainseven after the equipment is disconnectedfrom the power source.
Do not connect the generator set directly to
any building electrical system.
CAUTION
the generator set into the utility line. This
creates a potential for electrocution or property
damage. Connect only through an approved
Hazardous voltages can flow from
iv
Page 7
GENERAL SAFETY PRECAUTIONS
WARNING
changer pressure cap while the engine is running.
DO NOT open a radiator or heat ex-
Make sure generator set is mounted in a man-
ner to prevent combustible materials from accumulating under the unit.
Remove all unnecessary grease and oil from
the unit.
Allow the generator set to cool and bleed the
system pressure first.
Coolantsunder pressure have a higher boil-
ing point than water.
WARNING
Used engine oils have been identi-fied by some state or federal agencies as caus-ing cancer or reproductive toxicity.
When checking or changing engine oil, take
care not to ingest, breathe the fumes, or con-tact used oil.
Keep multi-class ABC fire extinguishers
handy.
Class A fires involve ordinary combustible
materials such as wood and cloth(ref. NFPA No. 10)
Class B fires, combustible and flammable
liquid fuels and gaseous fuels(ref. NFPA No. 10)
Class C fires, live electrical equipment.
(ref. NFPA No. 10)
Make sure that rags are not left on or near the
engine.
Accumulated grease and oil can cause
overheating and engine damage whichpresent a potential fire hazard.
Keep the generator set and the surrounding
area clean and free from obstructions. Re-move any debris from the set and keep thefloor clean and dry.
Do not work on this equipment when mentally
or physically fatigued, or after consuming anyalcohol or drug that makes the operation ofequipment unsafe.
WARNING
Substances in exhaust gases havebeen identified by some state or federal agen-cies as causing cancer or reproductive toxicity.
Take care not to breathe or ingest or come into
contact with exhaust gases.
Do not store any flammable liquids, such as
fuel, cleaners, oil, etc., near the generator set.A fire or explosion could result.
Wear hearing protection when going near an
operating generator set.
WARNING
Avoid contact with hot metal partssuch asthe radiator, turbo charger and exhaustsystem to prevent serious burns.
KEEP THIS MANUAL NEAR THE GENSET FOR EASY REFERENCE
v
Page 8
THIS PAGE INTENTIONALLY LEFT BLANK
vi
Page 9
1. Introduction
ABOUT THIS MANUAL
This manual is a guide for the installation of the gen-erator set(s) listed on the front cover. Proper instal-lation is essential for top performance, reliable op-
eration and safety. The installation must complywith all applicable building codes. Read through this
manual before starting the installation.
Information For After Installation
WARNING
severe personal injury, death and damage toequipment. The installation must comply withallapplicable building codes. It is strongly rec-ommendedthat the installer be properly trainedand licensed to perform electrical and mechani-calequipment installations, however a personwith the proper knowledge and experience ininstallingelectrical and mechanical equipmentinstallations may also install this genset.
Refer to Appendix E. Specifications for specific in-
formation about the system and its components.
Refer toAppendix F. Outline and System Drawings
for specific information about the installation and thewiring connections.
See the Operator Manual for operation and mainte-nance instructions.
Improper installation can result in
PRE-INSTALLATION CONSIDERATIONS
The location of the generator set affects all other as-pects ofthe installation, such as the lengths of elec-tric wiring and gas lines, and is one of the first deci-sions to be made. The installation cannot be com-pletedwithout connections to an automatic transferswitch and a source of fuel, Natural Gas or Propane,which must be inspected by the gas and electric uti-lities.
Decide where to locate the generator set and auto-matictransfer switch, how fuel supply will be pro-vided, what materials are required (wiring, fuel lines,etc.),and what site preparations are necessary (ac-cess to and preparation of the site, trenches, etc.).Prior co-ordination will reduce delays and theamount of time power has to be interrupted.
IMPORTANT NOTICE: Depending on the localityand use of the generator set, it may be necessary toobtain an airquality emissions permit before instal-lation begins. Check with the local pollution controlor air quality authority.
Automatic Transfer Switch
The Model GSAA generator set is for installationonly with Cummins Onan Model RSS automatictransferswitches. Use of other makes and modelsof transfer switches voids the Model GSAA genera-tor set Warranty.
Note: Manuals are updated from time to time to re-flect changes in the equipment and its specifica-tions. See an authorized Cummins Onan representa-tive for current manuals.
Install the transfer switch in accordance with itsInstallation Manual and make connections to the
generatorset in accordance with Section 4. Electri-cal Connections.
1-1
Page 10
SPECIFICATIONS
FUEL CONSUMPTION:
@ 1/2 Load
@ Full Load
Fuel Supply Pressure
Recommended LP Tank Size (necessary to run thegenerator set for seven days)
CONTROLLER: Integrated Microprocessor-Based Engine, Generator and Transfer Switch Controller
DC SYSTEM:
Nominal Battery Voltage
Battery Group
Battery Type
Minimum Battery CCA (Cold Cranking Amps)
WEIGHT (WET): 460 lbs (209 kg)
SIZE (L x W x H): 48 x 43 x 31.5 in (1219 x 864 x 800 cm)
SOUND LEVEL: Less than 64 dB(A) @ 23 ft (7 meters) and 12 kW of Load
Natural Gas Installation
(1000 BTU/ft3)
122 ft3/hr (3.5 m3/hr)
191 ft3/hr (5.4 m3/hr)
5−11 H2O
500 Gallon (Contact you local gas company to verify
the tank size required for your application)
0.030 in (0.76 mm)
NGK-BPR6ES (P/N 167−1658)
10 ft-lbs (13.5 N-m)
0.004in (0.10 mm)
1.7 quart (1.6 liter)
12 volts
26 R
Maintenance Free
Propane Installation
(2500 BTU/ft3)
53 ft3/hr (1.5 m3/hr)
88 ft3/hr (2.5 m3/hr)
7−11 H2O
530
1-2
Page 11
Generator Set Location
WARNING
doors, windows and other openings into the house and where the exhaust gases will disperse away
from the house.
EXHAUST GAS IS DEADLY! Install the generator set out-of-doors only, away from
PALATE
(PLACE GENSET
ON STABLE,
LEVEL GROUND)
FIGURE 1-1. GENERATOR SET LOCATION
5 FEET (1.6 METERS)
FROM ALL OPENINGS
TO THE HOUSE
Generator set (genset) location is critical for safety and good performance. Follow the guidelines below :
Install out-doors only.
Call the local utilities to mark the loca-
tions of buried utility services (gas, electric,telephone)before digging trenches for fuel andelectric lines.
Locatethe genset as far away as practical from
Do not locate the genset where snow
drifts, plant growth, lawn clippings and otherobjects are likely to block the ventilation open-ings.
noise sensitive areas such as bedrooms, living
Ask the homeowner for the location of
any other buried components.
Locateand orient the genset such that the pre-
vailing winds will carry exhaust gases and fuelleaks away from the house.
Genset must be at least 5 feet (1.6 me-
ters) away from all openings to the house.
Do not locate the genset in a three-
sided niche of the house, under an overhang or
in a low-lying area or next to a basement.
room windows and neighbors.
Locate the genset where it will be protected
from vehicular traffic and vandalism.
Locate the genset as close as practical to the
house to reduce the lengths electric wiring and
fuel lines.
Place the genset on stable ground, not subject
to flooding.
Note: The area should be leveled and compacted with
sand or pea gravel.
1-3
Page 12
Natural Gas Supply
The Natural Gas supply meter may need to be exchanged for a higher capacity meter to supply the
additional gas consumed by the generator set. At
full load, the generator set alone requires 191,000
BTU/hr. To determine the required meter capacity,
generator set consumption must be added to thegas consumed for heating, cooking, clothes drying,etc. A typical installation might require a400,000BTU meter.
Considerationshould also be given to utilizing highpressure gas supply (2 psi), if available, to reducethe required size, and therefore cost, of gas piping,especially if the location of the generator set re-quires a long supply line.
Note: The wire size varies, depending on distance (see Table 4-1).
10. Communications Wiring Connectors: Up to
twelve UL listed 18 AWG fork terminals for Item
9 wires (Cummins Part Number 0332−2527).
11. DC Conduit for Item 9 wires.
12.One or two 12 volt relays for load management(optional)
Note: It is recommended that the two 18AWGwiresfrom Generator set terminals TB1-7 and TB1-8 forload management bepulled along with the other con-trol/communicationswires at the time of installationso that they are available if it is determined later thatload management is necessary.
Tools Required
Note: An older site might require upgrading and re-pair of the gas supply system, which should bescheduled to minimize power and gas supply inter-ruptions.
Materials Required
The installer must provide the following materials tocomplete the installation:
1.Gas line and step down regulators (as re-quired) for gas connections:
A.Natural Gas at 191,000 BTU/hour
B.Propane at220,000 BTU/ hr or 2.4 gallons/
hour
C.Gas pressure at generator set: 5−11 inch
WC
2.UL listed pipe dope
3.Electrical Conduit sealing putty
4.Cat 5 Ethernet cable (optional)
5.Fourwall anchors and 4 No. 6 black screws formounting the Operator Panel.
6.AC Power Output Wiring: Four 8 AWG 90Cwires for runs up to 125 feet. (L1, L2, N andGND)
7.AC Accessory Supply Wiring: Two 12 AWG90C wires for runs up to 125 feet. (Hot andNeutral)
8. AC Conduit for Items 6 and 7, which may be run
in the same conduit.
9. Control/Communications Wiring: Up to twelve
18 AWG wires, depending on Transfer Switch.
(Generator set TB1-1 through TB1-12)
Use a forklift to move the generator set and set it inplace.Alternatively, aone-man hand dolly designedto fit the generator set base is available to move thegenerator set and set it in place (P/N 0541-1624).
Hand tools required include the following:
1.Wirestripper and lug crimper for terminatingthe twelve communications wires.
2.Rachet set with 10 mm socket and extension.
3.Two pipe wrenches for gas connections.
4.Phillips-head and flat-blade screwdrivers.
Loose Parts Shipped With the Generator
The following loose parts are shipped with theGSAA generator set.
Two Keys (P/N A026G567)
Quick Connect Guide (located in the battery
box)
Literature − Operator Manual, Installation
Manual, Setup Guide, and Warranty Statement
1-4
Page 13
INSTALLATION CODES AND STANDARDS
FOR SAFETY
WARNING
sole responsibility for following all applicable
local codes and regulations.
The following list of Installation Codes and Stan-
The generator set installer bears
TABLE 1-1. INSTALLATION CODES AND SAFETY RECOMMENDATIONS
dards for Safety applies to the installation and operation of standby generator sets. This list is for reference only and not intended to be inclusive of all
applicable codes and standards. The address of
each agency is listed so that copies of the codes
may be obtained for reference. Installation codes
and recommendations are subject to change, and
may vary by location or over time.
NFPA 70National Electric CodeNFPA 37Installation and Use of Stationary Combus-
tion Engines and Gas TurbinesNFPA 54National Fuel Gas CodeNFPA 58Storage and Handling of Liquefied Petro-
National Fire Protection Association,470 Atlantic AvenueBoston, MA 02210
Canadian Standards Association,Housing and Construction Materials Section178 Rexdale Blvd.Rexdale, Ontario, Canada M9W 1R3
Documents SectionP.O. Box 1015North Highlands, CA 95660
Underwriters Laboratories, Inc.333 Pfingsten RoadNorthbrook, IL 60062-2096
1-5
Page 14
2. Step-by-Step Outline of Installation
INTRODUCTION
WARNING
plyingwith all applicable installation codes andsafety requirements.
This section is a step-by-step overview of a typicalinstallation. This section includes:
Locating the site
Generator set Clearances
Preparing the site
Moving the generator set
Placing the generator set
The installer is responsible for com-
Connecting the generator set
Review this section, then refer to the detailed in-structionsthat are given in the following sections forspecific procedures and important safety precau-tions before starting the installation.
LOCATING THE SITE
These generator sets are housed in a weather-pro-tective enclosure for installation out-of-doors on anon-combustible base.
Choose asite close to the electric service and Natu-ral Gas meter or Propane tank. The main distribu-tion, transfer switch, and sub-panels are usually in-side the house.
ELECTRIC
METER
GENERATOR
UNDERGROUND
ELECTRIC
SERVICE
SET
TRANSFER
SWITCH
DISTRIBUTION
PANEL
GAS
METER
GAS
SHUTOFF
VALVE
UNDERGROUND
GAS SERVICE
FIGURE 2-1. TYPICAL GENERATOR SET SITE
2-1
Page 15
GENERATOR SET CLEARANCES
The generator set must be a minimum of 3 ft
(915 mm) from combustible material (NFPA 37).
Leave at least 3 ft (915 mm) all around the generator set enclosure for access to the inside (NEC Art.
110-26a, Art. 110-26b). The generator set must be
at least 5 ft (1524mm) from any opening (window,door,vent, etc.) in the wall, and the exhaust must notbe able to accumulate in any occupied area.
Refer to the Outline Drawing (page F-7) for theclearancerequired to fully open the maintenanceand service doors.
PREPARING THE SITE
If the site is not on level ground prepare an arealarge enough to easily hold the generator set so thatit can be mounted level. If you add fill to the site, besure totamp the ground until it is firm and stabilized.
Preparea site at least 48 in by 34 in (1219 mm by864mm) on firm ground. Sites on inclines require
more area. Add a layer of sand or pea gravel deep
enough so that you can level the generator set. Remove any combustible material that would be under
and around the generator set.
5 FT (1.6 M) MIN TO
ANY OPENING
FIGURE 2-2. GENERATOR SET CLEARANCES
2-2
Page 16
LIFTING AND MOVING GENERATOR SET
WARNING
ping the generator set can cause severe personal injury or death. Keep feet and hands clear
when lifting the generator set.
CAUTION
in the crankcase. Keep it upright.
The generator set is heavy and must be handledwith care. Use a forklift to move the generator setand set it in place. Alternatively, a one-man handdolly designed to fit the generator set base is avail-able to move the generator set and set it in place.
The generator set is heavy. Drop-
The generator set is shipped with oil
STAKING GENERATOR SET IN PLACE
WARNING
gas, or telephone service lines can result in se-
Pounding the stakes into electric,
vere personal injury or death. Observe the utility
company markings.
Set the generator set in place and pound the four
corner stakes into the ground to secure the generator set in place.
ELECTRICAL WIRING CONNECTIONS
Refer to Appendix F Outline and System Drawings
forthe locations of the electrical conduit openingson the side of the generator set and the alternativestub-upopening in the base for all power and com-municationswiring connections between the gener-ator set and transfer switch.
Route the wires from the transfer switch throughconduit and connect the wires to the mating termi-nals in the generator set terminal board compart-ment.Two separate conduits are required. One isfor all A/C voltage connections on TB2 and TB3.The other is for all TB1 and ethernet cables.
CORNER
STAKE
WIRING TERMINAL BOARD
COMPARTMENT
ELECTRICAL WIRING
STUBUP OPENING
FIGURE 2-3. ELECTRICAL WIRING TERMINAL BOARDS AND STUBUP OPENING
2-3
Page 17
GAS LINE CONNECTIONS
WARNING
explosion that can result in severe personal injury or death. Do not smoke or allow any flame,
spark, pilot light, or other ignition sources near
fuel or in the installation area. Read the impor-tant safety precautions in the Fuel System sec-
Fuel presents the hazard of fire or
tion.
Refer to Appendix F Outline and System Drawings
for the location of the fuel supply connection through
the side of the generator set. A flexible fuel hose is
packaged inside the generator set (Assembly part
number: 0501−0776−06). Connect it between the
3/4 NPT fitting on the generator set and the fuel sup-ply line.
MEASURE INLET FUEL
PRESSURE HERE
FLEXIBLE FUEL HOSE
(P/N 0501−0776−06)
FIGURE 2-4. GAS LINE CONNECTIONS
2-4
Page 18
3. Mechanical
LOCATION AND ACCESS
These generator sets are designed for installationout-of-doors in its weather-protective enclosure.
Factors to consider when deciding where to locatethe generator set include:
Proximity of generator set, transfer switch,
loads and Natural Gas fuel lines or Propanetanks.
Access for maintenance and service. Refer to
the Outline Drawing (page F-7) for the clear-ance required to fully open the maintenanceand service doors.
Security from vandalism, flooding and vehicu-
lar traffic.
Noise levels and proximity of property lines.
Safe dispersal of engine exhaust and cooling
air away from buildings, habitable areas, andpeople.
Possible obstructions to ventilation caused by
snowdrifts,plant growth, lawn clippings, fallingleaves, etc.
See Locating the Site in Section 2.
FUEL SYSTEM
WARNING
qualifiedservice technicians. Improper installa-tion presents hazards of fire and improper op-eration,resulting in severe personal injury orproperty damage.
The generator set name plate is marked to indicatethe fuel type, Natural Gas or Propane.
WARNING
explosiveand can cause severe personal injuryor death. Do not smoke if you smell gas or arenear fuel tanks or fuel-burning equipment or arein an area sharing ventilation with such equip-ment. Keep flames, sparks, pilot lights, electri-cal arcs and arc-producing equipment and allothersources of ignition well away.Keep a typeABC fire extinguisher handy.
In all fuel system installations, cleanliness is of theupmost importance. Make every effort to prevententrance ofmoisture, dirt, excess thread sealant, orcontaminants of any kind. Clean all fuel systemcomponents before installing.
Fuel systems must be installed by
Gaseous fuels are flammable and
ENGINE EXHAUST
The exhaust system of this generator set was de-signed for this engine and is complete. Do notmodify oradd to the exhaust system of this genera-tor set.
WARNING
haust system must terminate away from build-ing vents, windows and doors and shelteredspaces that may not have ample fresh air ven-tilation.
Do not use generator set discharge air or engine ex-haust for heating a room or enclosed space.
WARNING
carry carbon monoxide gas (odorless and invisible) which can cause asphyxiation and death.
Never use engine discharge air or exhaust for
heating a room or enclosed space.
EXHAUST GAS IS DEADLY! The ex-
Engine discharge air and exhaust
The section of flexible fuel hose supplied with thegenerator set must be used between the engine’sfuel system and fuel supply line to protect the fuelsystem from damage caused by vibration, expan-sion and contraction. The fuel hose must beinstalled according to all applicable codes and stan-dards.
Gaseous-fuel supply system design, materials,components, fabrication, assembly,installation,testing,inspection, operation and maintenancemust comply with the applicable codes. See NFPAStandards No. 37, No. 54, and No. 58.
Mostcodes require a manual shutoff valve ahead ofa flexible fuel hose. The manual valve should be of
the indicating type. The generator set has an electric (battery-powered) shutoff valve included between the fuel supply and the carburetor.
Until the generator set is connected, cap the fuel line
stub-up at the generator set to prevent dirt from en-
3-1
Page 19
tering and gas discharging if the gas supply shutoff
valve is opened inadvertently.
Refer to Appendix E. Specifications for the fuel inlet
size.
NATURAL GAS FUEL SYSTEM
(191 cubic feet/hr) delivered to the generator set inlet at 5−11 inches (28 mm) WC (Water Column). If
the meter serves other gas appliances such as a furnace, water heater, or stove, you must consult with
the local Natural Gas utility to determine whether
the Natural Gas meter is adequate.
The generator set requires an adequate fuel supplyto operate correctly at full load. The length of the fuelsupply pipe from the gas service entrance to thegenerator set must be known to determine the cor-rectfuel pipe size. Refer to Table 3-1 to find the fuelsupply requirement for your generator set. Pipemust be minimum of schedule 40 subject to the au-thority having jurisdiction.
Natural Gas Supply Line Size
The generator set requires up to 191,000 BTU/hr
It is important to consider other loads operated fromthe fuel supply pipe. Other loads, such as spaceheating and water heating equipment, must also bedetermined to correctly size the fuel pipe. Use thetotal load requirement of the fuel supply line to de-termine the size of the fuel supply pipe. UseTable3-1 to determine the correct pipe size. (typi-cally, 1ft
Note: When the fuel delivery value falls between twocolumns, use the larger value.
GENERATOR SET
3
/hr =1000 BTU/hr, )
SHUTOFF VALVE
GAS METER
FIGURE 3-1. TYPICAL NATURAL GAS INSTALLATION
TABLE 3-1. NATURAL GAS PIPE CAPACITY—CUBIC FEET OF GAS PER HOUR
NOMINAL IRON
PIPE SIZE
(INCHES)
3/4360250200
1680465375320285260240220205195
1-1/41400950770660580530490460430400360325300280
Maximum pipe capacity in cubic feet per hour of 0.60 specific gravity Natural Gas with a pressure drop of 0.5 inches (1.27 mm)
WC over the length
102030405060708090100125150175200
LENGTH OF PIPE IN FEET
3-2
Page 20
PROPANE FUEL SYSTEM
WARNING
NFPA Standard No. 58 requires all
persons handling and operating Propane to be
trained in proper handling and operating procedures.
WARNING
Fuel leaks can lead to explosive ac-cumulations of gas. Propane sinks in air andcan accumulate inside housings, basementsand other below-grade spaces. Prevent gasleaks and the accumulation of gaseous fuel inthe event of a leak.
Converting from Natural Gas to Propane(Vapor Withdrawal)
The generator set leaves the factory set up for Natu-ral Gas. The generator set must be converted as fol-lows for use with Propane vapor:
1.Disconnect the fuel hose at the gas/air mixerand thread in the gas orifice wire-tied tothe en-gine lifting bracket (Figure 3-2).
2.Insert the air orifice supplied with the flexiblegas hose into the inlet of the air intake resonator(Figure 3-3). (Orifice used only on spec A units)
3.Configure the control for Propane (page
5−1).
RIGHT
HAND
DOOR
AIR
ORIFICE
FIGURE 3-3. INSTALLING THE AIR ORIFICE
INTAKE
RESONATOR
(SPEC A ONLY)
GAS
ORIFICE
SPEC A
GAS/AIR MIXER
FIGURE 3-2. INSTALLING THE PROPANE GAS
ORIFICE
3-3
Page 21
Propane Vapor Fuel Supply Line Size and
Pressure
Fuel line size depends on the amount of fuel needed
to run the generator set at full load at the distance
the fuel must be moved. The generator set requires
3
88ft
/hrof Propane Vapor at full load delivered to
GENERATOR
SET
SHUTOFF
VALVE
REGULATOR
SECONDARY
REGULATOR
the generator set inlet at 7−11 inches WC (Water
Column) gas pressure. Figure 3-4 shows a typical
Propane Vapor installation and Table 3-2 lists fuel
capacity for given distances and pipe size.
Size the fuel line so that the Propane vapor pressure
drops no more than 2 inches WC from no load to full
load.
TABLE 3-2. PROPANE VAPOR PIPE CAPACITY—CUBIC FEET OF GAS PER HOUR
NOMINAL IRON
PIPE SIZE
(INCHES)
3/422715712610795
1428293236201179164151138129123110101
1-1/4882598485416365333308289207252230204
1-1/21323920743624567570472434409390346315
224881732138611971058958882819768724642598
Maximum pipe capacity in cubic feet per hour of Propane vapor with a pressure drop of 0.5 inches (1.27 mm) WC over the
102030405060708090100125150
LENGTH OF PIPE IN FEET
length
3-4
Page 22
Fuel Pressure
WARNING
cause gas leaks which can lead to fire and severe personal injury or death. Gas supply pressure must be adjusted to Specifications by
trained and experienced personnel.
Satisfactoryperformance requires that the PropaneVapor be supplied at a pressure within the range of7-11 inches WC (water column).
When measuring supply pressure, the most accu-rate reading would be on the input side of the sole-noid valve.
High gas supply pressure can
Recommended Fuel
Use clean, fresh HD-5 grade Propane or equivalentproduct consisting of at least 90 percent Propane.Commercial Propane may contain more than 2.5percent butane which can result in poor fuel vapor-ization and low tank pressure resulting in poor en-gine starting in low ambient temperatures (below32F (0C).
WARNING
or explosion that can cause severe personal in-jury or death. Do not permit any flame, spark,
Propane presents the hazard of fire
arc-producing equipment, switch, pilot light,
cigarette, or other ignition source near the fuel
system. Keep an ABC type fire extinguisher
nearby.
Propane Tank Size
To assist in the proper selection of the Propane tank,follow the guidelines below.
Propanetanks are sized by the number of gal-
lons of water they can hold, not the amount offuel they hold. See Table 3-3.
Propane tanks are generally filled to only 80%
of their water capacity.Therefore, a 500 lb tankresults in 400 lb tank capacity.
Low ambient temperatures affect the amount of
fuel available from the Propane tank.
Approximately60% of the fuel (in gallons) filled
in the tank can be effectively used. Therefore,a 500 lb tank results in 300 gallon capacity.
Propane tanks must be fitted with a pressure
reducing regulator before connection to thegenerator set to prevent fuel system damage.
Propane tanks must be located at least 10 ft
(3048 mm) from any source of combustion (in-cluding the generator set).
TABLE 3-3. REQUIRED PROPANE TANK SIZE IN GALLONS (LITERS) FOR INDICATED TEMPERATURES
Before operating the set, test the Propane fuel system for leaks. Energize the fuel solenoid from a separate 12-volt DC source before testing the fuel system. Testing must conform to procedures listed in
NFPA-58, or to the UL recommended test procedure, as follows:
After assembly and before initial operation, all fuelsystem connections, hose valves, regulators, andfittings must be tested and proven free of leaks us-ing a soap-and-water (or equivalent) solution whilethe system is under gas or air pressure of at least
1.5 times the supply pressure or 3 psi (20.7 kPa)
minimum.
Other approved methods of detecting leaks can be
used if appropriate. DO NOT use a flame to test for
gas leaks.
WARNING
plosion or fire which can result in severe per-sonalinjury or death. Do not smoke or allow anyflame, spark, pilot light, arc-producing equip-ment, switch, or other ignition sources aroundfuel or fuel components.
Propane presents the hazard of ex-
3-6
Page 24
4. Electrical Connections
AC POWER SUPPLY CONNECTIONS
WARNING
made by a licenced electrician. Improper instal-lation can lead to electrocution and damage toproperty.
Automatic startup of the generator set duringinstallationcan cause severe personal injury ordeath.Push the control switch Off and discon-nect the negative (−) cable from the battery tokeep the generator set from starting.
Electrical connections must be
Wiring
Refer tothe requirements of The National ElectricalCode (NFPA No. 70) for all AC wiring connections.
For access to the wiring connection terminalboards,open the top of the generator set, swing theleft service door wide open and remove the coverfrom the terminal board compartment (Figure 4-1).
Use 8 AWG 90C conductors for the four AC poweroutput wires (L1, L2, N and GND), connect them to
the AC output terminal board (TB-2). Torque the
termninals to 25 lb−inch (2.8 N−m).
Refer toAppendix F. Outline and System Drawings
for connections at the transfer switch.
The wires must be routed to the transfer switch inapproved liquid-tight conduit. The conduit can bestubbed up through the bottom stubup opening orconnectedto the conduit opening onthe side of thegeneratorset. If the stubup opening is used, fill inthe stubup opening with duct seal or mastic tape tokeep out insects and rodents.
Note: See ACCESSORY SUPPLY WIRING (page 4-2)for AC wiring that may share the same conduit as ACoutput wiring.
CAUTION
incontrol and communications wiring. Do notroute in the same conduit.
AC wiring can induce false signals
WIRING TERMINAL
BOARD COMPARTMENT
ELECTRICAL WIRING
STUBUP OPENING
FIGURE 4-1. WIRING TERMINAL BOARDS
4-1
Page 25
ACCESSORY SUPPLY CONNECTIONS
To supply 120 VAC to power the GFCI outlet on the
side of the generator set, optional battery heater
(P/N 0333−0770) and optional engine oil and carburetor heater (P/N 0333-0771), connect two 12 AWG
90C wires to generator set terminal block TB3 (Hotand Neutral) from a 15 amp protected circuit in themain distribution panel in the house. The wires maybe run through the same conduit as the power sup-ply wires.
Grounding
The generator set, transfer switch, power supplywiring,and all connected electrical equipment mustbe bonded to a common grounding point in accor-
dance with applicable codes or standards (Figure
4-2).
WARNING
The generator set grounding terminal (TB2-4) must be connected to the grounding
terminal in the transfer switch. Do not provide a
separate grounding rod for the generator set.
Note that generator neutral is not grounded at thegeneratorset, but at the common system groundingpoint.
WARNING
Contact with electrical equipmentcan result in severe personal injury or death. It isextremely important that bonding and equip-ment grounding be properly done. All metallicparts that could become energized under ab-normal conditions must be properly grounded.
4-2
Page 26
GROUNDING WITH MODEL RSS 100−6634 AND RSS 200−6635 TRANSFER SWITCHES
SERVICE ENTRANCE
2-POLE TRANSFER
SWITCH
L
TO UTILITY
SERVICE
GROUNDING WITH MODEL RSS 100−6868 AND RSS 200−6869 TRANSFER SWITCHES
N
LOADS
COMBINED SERVICE-ENTRANCE AND
2-POLE TRANSFER SWITCH
L
GENERATOR SET
GENERATOR SET
TO UTILITY
SERVICE
N
LOADS
FIGURE 4-2. TYPICAL SYSTEM GROUNDING ONE-LINE DIAGRAMS
4-3
Page 27
Transfer Switch
O
WARNING
and the public utility can lead to the electrocution of personnel working on the utility lines,
damage to equipment and fire. An approved
switching device must be used to prevent interconnections.
Interconnecting the generator set
TABLE 4-1. WIRE SIZE SPECIFICATIONS
Wire Size
(AWG)
1690
14150
12225
Distance in Feet, One Way
(Multiply by 0.3 for Meters)
The Model GSAA generator set is designed to beinstalled with Cummins Onan Model RSS automatictransferswitches. Use of other makes and modelsof transfer switches with the Model GSAA generatorwillresult in a reduced warranty. Reference the War-ranty statement for further details.
Install the transfer switch in accordance with its
Installation Manual. Refer to Appendix F. Outlineand System Drawings for wiring connections be-
tween the generator set and transfer switch.
See Wiring (page 4-1) regarding wiring to use forAC power output connections between the genera-tor set and transfer switch.
Use 18 AWG conductors for the control/commu-nications wires (generator set TB1 to transfer switchterminalTB4). It is recommended that all twelveconductors (nine conductors for RSS 100−6634and RSS 200−6635) be pulled through the conduitatthe time of installation to be ready for functionsthat might be activated later, such as load control.
Note: The wire used must be sized to accommodateany specific voltage drop. Refer to Table 4-1 to deter-mine the correct wire size.
10350
8600
61000
Block diagrams showing partial or full load coverageare shown on the following pages. Figures 4-3 and4-4 show installations without a controller (RSS100-6634and RSS 200−6635) and Figures 4-5 and4-6 show installations with a controller (RSS100−6868and RSS 200−6869). The RSS100 trans-fer switch models can be connected for full or partialload coverage equal to the capacity of the generatorset. The RSS200 transfer switch models can beconnectedfor full load coverage greater than the ca-pacity of the generator set. If the transfer switch isconnected for full load coverage which exceedsgenerator set rating, it may be necessary to shed
large loads such as air conditioners. Refer to Ap-pendix F. Outline and System Drawings for con-
necting load shed relays to generator set load con-trol terminals TB1−1 and TB1-2.
TABLE 4-2. TITLE???
CONNECTION CAPABILITIES
TRANSFER SWITCH MODELFULL LOAD
RSS 100−6634X
RSS 200−6635X
RSS 100−6868X
RSS 200−6869X
1.XXXXXXXXXXXXXXXXXXXXXXXXXXXX
Note: Model RSS100−6634 and RSS200−6635 Transfer Switches do not incorporate a utility circuit breaker and therefore must be connected through a Service Entrance Utility Panel incorporating the utility
(GREATER THAN
CAPACITY OF GENSET)
circuit breaker.
Perform GENERATOR SET CONFIGURATION
(page 5-1) when ready start up the generator set.
4-4
FULL OR PARTIAL LOAD
(EQUAL T
CAPACITY OF GENSET)
Page 28
UTILITY PANEL
UTILITY
SOURCE
LOADS
TRANSFER SWITCH
CIRCUIT
BREAKER
CIRCUIT
BREAKER
DISTRIBUTION PANEL
GENERATOR
SOURCE
LOADS
FIGURE 4-3. PARTIAL COVERAGE LOAD CONNECTIONS (TRANSFER SWITCH WITHOUT CONTROLLER)
TRANSFER SWITCH*
UTILITY
SOURCE
CIRCUIT
BREAKER
CIRCUIT
BREAKER
GENERATOR
SOURCE
MAIN
BREAKER
PANEL
ALL LOADS
FIGURE 4-4. FULL COVERAGE LOAD CONNECTIONS (TRANSFER SWITCH WITHOUT CONTROLLER,
ONE CIRCUIT BREAKER)
4-5
Page 29
UTILITY PANEL
UTILITY
SOURCE
LOADS
TRANSFER SWITCH
CIRCUIT
BREAKER
DISTRIBUTION PANEL
GENERATOR
SOURCE
LOADS
FIGURE 4-5. PARTIAL COVERAGE LOAD CONNECTIONS (TRANSFER SWITCH WITH CONTROLLER)
TRANSFER SWITCH
UTILITY
SOURCE
CIRCUIT
BREAKER
CIRCUIT
BREAKER
GENERATOR
SOURCE
MAIN
BREAKER
PANEL
ALL LOADS
FIGURE 4-6. FULL COVERAGE LOAD CONNECTIONS (TRANSFER SWITCH WITH CONTROLLER)
4-6
Page 30
OPERATOR PANEL
See the Operator Manual for operating and monitoring the generator set using the Operator Panel.
Mount the generator set Operator Panel on a wall at
a convenient location, such as next to the house
thermostat. Toinstall the Operator Panel cut out anopening in the wall as shown in Figure 4-7 and
mount it with four No. 6 wood screws or wall anchors.
Refer to Appendix F. Outline and System Drawings
for connecting the Operator Panel to the generator
set. Use the plug-in connection harness (shipped
loose with the generator set) to connect to the wiringfrom the generator set. Use 18 AWG wires.
WALL CUTOUT
PLUG-IN CONNECTION HARNESS
FIGURE 4-7. CUTOUT FOR OPERATOR PANEL AND CONNECTION HARNESS
4-7
Page 31
ETHERNET CONNECTIONS (OPTIONAL)
The generator set control board has a connector for
Cat 5 Ethernet cable for connection to a remote mo-
dem/router. See Appendix B. Ethernet/Email Inter-face for setup and operation.
along with other wiring from the control to the wiring
terminal board compartment and then into the conduit to the house.
Note: The Internet/Email interface requires “high
speed” or “broadband” cable or DSL service to the
house.
Use Cat 5 Ethernet cable and route it separately intothe house or along with the control/communicationswiring. At the generator set route the Cat 5 cable
ETHERNET
CONNECTOR ON
CONTROL BOARD
Wiring connections to the Ethernet RJ-45 plug areshown inFigure 4-9.Utilize an appropriate Ethernetstripping and crimping tool for these connections.
PIN 1
g = Green and WhiteG = Greeno = Orange and WhiteO = Orange
b = Blue and White
B = Blue
br = Brown and White
BR = Brown
FIGURE 4-8. ETHERNET CONNECTOR
FIGURE 4-9. ETHERNET RJ-45 CONNECTOR WIRING
4-8
Page 32
BATTERY
The generator set has a 12 VDC, negative-ground
control and engine cranking system. The engine
has a battery charger for recharging during generator set operation. A battery charger located in the
transfer switch keeps the battery charged during
generator set standby.
Install the heater in accordance with the kit instructions.
To prevent injury due to accidental start-up, do not
connect the battery cables to the battery until the
installation has been completed and it is time to start
the set. See Section 5. Installation Review and
Startup
Refer to Appendix E. Specifications regarding bat-
tery specifications.
An optional thermostatically controlled battery heat-er is available for more reliable starting in ambienttemperaturesdown to −20 F (−28.8 C). The heat-er wraps around the battery. The heater cord is con-nected to the 120V, accessory connection block.
BATTERY
WARNING
Automatic startup of the generatorset while performing maintenance or servicecan cause severe personal injury or death. Pushthecontrol switch to Off and disconnect thenegative (−) battery cable from the battery tokeep the generator set from starting up whileworking on it.
FIGURE 4-10. BATTERY INSTALLATION
4-9
Page 33
5. Startup and Configuration
INSTALLATION REVIEW
Before starting the genset inspect the installationand check off() each of the following questions if itcan be answered “YES”. If a question cannot bechecked off, review the appropriate section in themanual.
[]Can the top and the maintenance and service
access doors be swung fully open for opera-tion, maintenance and service?
[ ]Are the cooling air inlet and outlet openings
free of obstructions?
[ ]Have the AC output connections been made
properly?
[]Has the transfer switch been installed properly
toprevent connecting the generator set to theutility?
[]Has a properly sized battery been installed?
[ ]Are all fuel connections tight?
[ ]Is fuel supply pressure correct?
[ ]Are electrical and fuel lines properly sepa-
rated?
[]Does engine exhaust disperse away from
buildings?
STARTUP
genset, following all the instructions and precautions in the Operator Manual.
Perform GENERATOR SET CONFIGURATION(page 5-1).
Note:Before leaving the site, if the genset is ready tobe placed in service, set the control switch to theAUTO position to provide automatic standby power.
GENERATOR SET CONFIGURATION
The Operator Panel has a menu with four generatorset/transfer switch parameters that must be config-ured for the installation.
Generator Configuration
To configure the generator set:
1.Press the MENU button on the home screen.
2.Press and hold the blank button on the menuscreen for at least 5 seconds to go to the Con-fig Menu.
3.Pressthe up or down arrow button on the Con-fig Menu screen to select Generator Config.
4.Press Enter on the Config Menu to go to theGenerator Config screen.
5.Press the NEXT button on the Generator Con-fig Menu screen to select the Config, Frequen-cy or Rating field.
Whenall installation requirements have been met,connect the battery cables to the battery, positive(+) cable first.
WARNING
set during installation can cause severe per-sonalinjury or death. Push the control switchOffand disconnect the negative (−) cable fromthe battery to keep the generator set from start-ing.
Read through the Operator’s Manual and perform
the maintenance and pre-start checks instructed.
The genset is shipped from the factory with the
proper level of engine oil, but should be checked
before the genset is started. Start and operate the
Automatic startup of the generator
6.Press the up or down arrow button to increaseor decrease the configuration parameter.
A.Config:Select “12” for Natural Gas or “13”
for Propane.
B.Frequency:“60” Hz cannot be changed at
this time.
C.Rating:Select “50” Amps for Propane or
“43” Amps for Natural Gas. Select lowervalues if it is necessary to derate for high
altitude or hot climates. (Selecting the correct Amps value is necessary for displaying the correct genset load on the Operator Panel.
7. Press the BACK button to save the setting and
return to the home screen.
5-1
Page 34
Sun 10:35 AM
Battery 12.5
GENERATOR ADJUSTMENTS
Refer to Figure 5-2. To adjust the Operator Panel
voltage display and hour meter, access the Adjustment Menu Screen as follows:
1. Press the MENU button on the home screen.
Genset LoadL1L2
EXCER
Genset StatusDisplay SetupEvent Log
Fault LogEthernet Setup
hold blank button
for 5 seconds
Config Menu
Generator ConfigGenerator Adjustments
TS ConfigTS Adjustments
MENUCLOCKLOAD
ENTER
ENTER
2.Press and hold the blank button on the menuscreen for at least 5 seconds to go to the Con-fig Menu.
3.Pressthe up or down arrow button on the Con-fig Menu screen to select Generator Adjust-ments.
4.Press Enter on the Config Menu to go to theAdjustments screen.
Generator Config
Config:12
Frequency: 60
Rating:
FIGURE 5-1. GENERATOR CONFIGURATION
50
Hz
Amps
NEXT
5-2
Page 35
Sun 10:35 AM
To Adjust the Output Voltage − Use the
following procedure:
1. Connect an accurate AC volt meter across L1
and L2 while the generator set is running.
Battery 12.5
Genset LoadL1L2
EXCER
Genset StatusDisplay SetupEvent Log
Fault LogEthernet Setup
hold blank button
for 5 seconds
Config Menu
Generator ConfigGenerator Adjustments
TS ConfigTS Adjustments
MENUCLOCKLOAD
ENTER
ENTER
2. With Output Volts selected on the Adjustments
Menu screen, press the up or down arrow button to adjust the voltage to the desired setting(Figure 5-3).
3.The control allows an adjustment of 240 VAC 7% (17 VAC).
4.Press the BACK button to save the settingsand return to the home screen.
To Calibrate the Display Meter − Use thefollowing procedure:
1.Connect an accurate AC volt meter across L1and L2 while the generator set is running.
2.Press the NEXT button to select the DisplayCal field (screen not shown).
3.Press the up or down arrow to adjust the volt-age reading on the screen until it matches themeter reading.
4.Press the BACK button to save the settingsand return to the home screen.
Adjustments
Use Meter to Set
FIGURE 5-2. GENERATOR ADJUSTMENTS
Output Volts
Hr Meter
FIGURE 5-3. ADJUSTMENT MENU SCREEN
5-3
0.4
240
NEXT
Page 36
Transfer Switch Configuration
To configure the generator set for the transfer
switch being used:
1. Press the MENU button on the home screen.
2. Press and hold the blank button on the menu
screen for at least 5 seconds to go to the Con-fig Menu.
3.Pressthe up or down arrow button on the Con-fig Menu screen to select TS Config.
4.Press Enter on the Config Menu to go to theTransfer Switch screen.
5.Pressthe up or down arrow button to select be-tween two choices: “RSS100−6868 andRSS200−6869” or “RSS100−6634 andRSS200−6635,” which must match the modelnumber of the transfer switch being used.
6.Pressthe BACK button to save the setting andreturn to the home screen.
Sun 10:35 AM
Battery 12.5
Genset Load
L1L2
EXCER
Genset StatusDisplay SetupEvent Log
Fault LogEthernet Setup
hold blank button
for 5 seconds
MENUCLOCKLOAD
ENTER
Config Menu
Generator Config
Generator Adjustments
TS Config
TS Adjustments
ENTER
Transfer Switch
Model:
RSS100−6868 or
RSS200−6869
FIGURE 5-4. TRANSFER SWITCH CONFIGURA-
TION
5-4
Page 37
Transfer Switch Parameter Adjustments
Model RSS100−6634 and RSS200−6635 Transfer Switches: Refer to Transfer Switch Installation
Manual 962−0620 to set the parameters inside the
transfer switch.
Model RSS100−6868 and RSS200−6869 Trans-fer Switches:To make transfer switch parameter
adjustments:
1.Press the MENU button on the home screen.
2.Press and hold the blank button on the menuscreen for at least 5 seconds to go to the Con-fig Menu.
3.Pressthe up or down arrow button on the Con-fig Menu screen to select TS Adjustments.
4.Press Enter on the Config Menu to go to theTransfer Switch screen.
5.Press the NEXT button on the Generator Con-fig Menu screen to select the Pickup, Dropoutor Nominal field.
6.To set Nominal −Press the up or downdouble-arrow button to increase or decreasethe nominal utility voltage parameter to matchactual (Present) utility voltage. The Pickup andDropout parameters are percentages of thenominal voltage parameter.
Sun 10:35 AM
Battery 12.5
Genset Load
L1L2
EXCER
Genset StatusDisplay SetupEvent Log
Fault LogEthernet Setup
hold blank button
for 5 seconds
Config Menu
Generator Config
Generator Adjustments
TS Config
TS Adjustments
MENUCLOCKLOAD
ENTER
ENTER
7.To set Pickup−Press the up or down double-arrow button to increase or decrease the mini-mum utility voltage to which the transfer switchwill connect. Default is 90% of nominal. It canbe increased to 95% of nominal.
8.To set Dropout−Press the up or down double-arrow button to increase or decrease the mini-mum utility voltage at which the transfer switchwill disconnect. Default is 85% of nominal. Itcan be decreased to 80/75/70% of nominal.
9.Pressthe BACK button to save the setting andreturn to the home screen.
Transfer Switch
Pickup:Dropout:
90 %
85 %
Nominal: 240 VACPresent: 240 VAC
NEXT
FIGURE 5-5. TRANSFER SWITCH ADJUSTMENTS
5-5
Page 38
Appendix A. Operation
IN-HOME OPERATOR PANEL
The in-home generator set Operator Panel (Figures A-1 and A-2)isintended for wall mounting at aconvenient location inside the house. The OperatorPanel must be hard-wired to the generator set for
the generator system to operate. Refer to AppendixB. Internet / Email Interface for an alternative inter-
face to operate and monitor the generator set. Thein-home operator panel and Internet/Email inter-face can be used simultaneously.
The Operator Panel has two UTILITY status lamps,threeGENERATOR status lamps, three action but-tons(BACK, STANDBY ON/OFF and START/STOP) and an LCD display screen with four naviga-tion buttons.
BACK Button
Whennavigating through the LCD menus, press theBACKbutton to return to the main operating screen.
UTILITY
PRESENT
CONNECTED
Sun 10:35 AM
Battery 12.5
Genset Stopped
EXCER
FIGURE A-1. UTILITY PRESENT AND
CONNECTED—STANDBY OFF LAMP ON
MENUCLOCKLOAD
GENERATOR
RUNNING
STANDBY OFF
ACTION REQUIRED
STANDBY
BACK
ON/OFF
START
STOP
STANDBY ON/OFF Button
See Page A-3 to enable / disable generator setSTANDBY.
START STOP Button
See Page A-3 to manually START / STOP the gen-erator set.
TYPICAL OPERATION
Normal Operation—Utility Power Availableand Connected
As long as utility power is available and connected,both of the green UTILITY lamps (PRESENT andCONNECTED) will stay on and the LCD screen willindicate “Genset Stopped”.
If the red GENERATOR STANDBY OFF light is on,the generator set will not start up automatically if util-ity power is interrupted. See Page A-3 to enableSTANDBY so that the generator set will automati-cally supply power if utility power is interrupted.
A-1
Page 39
Emergency Operation—Utility Power
Interrupted
If utility power is interrupted,
1. The green UTILITY PRESENT lamp will go out
2.The generator set will start automatically andthegreen GENERATOR RUNNING lamp willcome
3.The UTILITY CONNECTED light will go outwhen the generator set is connected to supplypower.
The LCD screen will provide a visual indication of“Genset Load” (bar graphs). The bar graphs indi-catehow much of the available power is being usedin each supply line (L1 and L2).
If the red ACTION REQUIRED light comes on, ei-therthe generator shut down or periodic mainte-nance has come due. The LCD screen will indicatewhat maintenance is due or which fault occured.
UTILITY
PRESENT
CONNECTED
Sun 10:35 AM
Battery 12.5
Genset LoadL1 L2EXCER
MENUCLOCKLOAD
FIGURE A-2. GENERATOR SET RUNNING—ACTION
REQUIRED LAMP ON
GENERATOR
RUNNING
STANDBY OFF
ACTION REQUIRED
STANDBY
BACK
ON/OFF
START
STOP
A-2
Page 40
TO ENABLE / DISABLE STANDBY
You should normally not have occasion to disable
generator set STANDBY. STANDBY should always
be enabled (ON) except during maintenance/service.
STANDBY will have to be re-enabled (STANDBYOFF light on) if the generator set is started orstoppedmanually (normally a maintenance/servicefunction) or a fault shutdown has occurred.
CAUTION
generator set will NOT automatically start tosupply power if utility power is interrupted.
To enable or disable generator set standby:
1.Press the STANDBY ON/OFF button on theOperator Panel (Figure A-1), which takes youto the Standby ON/OFF screen (Figure A-3).
2.Pressthe up or down arrow button to select ONor OFF.
3.To enable STANDBY select ON and press theBACKbutton. The STANDBY OFF lamp will goout and the display will state: “Standby readyenabled by user.”
4.To disable STANDBY select OFF and pressthe BACK button. The STANDBY OFF lamp willcome on and the display will state: “Standbyready disabled by user.”
When STANDBY is disabled the
TO MANUALLY START / STOP
GENERATOR SET
Normally only the maintenance/service technician
has occasion to manually start and stop the generator set. Starting the generator set will result in the
generator powering the house loads.
CAUTION
generatorset disables generator set STANDBY.The generator set will not automatically start tosupply power if utility power is interrupted.
To manually start or stop the generator set:
1.Pressthe START STOPbutton on the OperatorPanel (Figure A-1), which takes you to the Gen-setSTART/STOP screen (Figure A-4). Thescreen will display “Genset Stopped” or “Gen-set Running,” as appropriate.
2.PressSTART to manually start the generatorset and connect it to supply power to the house.TheSTANDBY OFF lamp will come on and thedisplay will state: “Genset started manually(Standby Ready Disabled).”
3.Press STOPtomanually stop the generator setand disconnect it. The STANDBY OFF lamp willcome on and the display will state: “Gensetstopped manually (Standby Ready Disabled).”
Note: To start the generator set without connectingloads pick Exercise Now on the Exerciser Clockscreen (page A-10).
Manually starting or stopping the
Standby required
for automatic
start/stop
Standby: ON /OFF
FIGURE A-3. ENABLE/DISABLE STANDBY SCREEN
Manual OperationDisables Standby
Genset Stopped
STARTSTOP
FIGURE A-4. GENSET START/STOP SCREEN
A-3
Page 41
FAULT, MAINTENANCE AND NEW EVENT
SCREENS
Various warning and event screens may appear on
the Operator Panel during Normal or Emergency
Operation.
Fault Screen
If a generator set shutdown fault occurs, a FAULTwarning appears (Figure A-5) with the following in-formation:
Brief description of the warning or faultThe two-digit Fault Code NumberThe time of occurrence of the fault
Maintenance Due Screen
A maintenance due screen appears (Figure A-5)when a scheduled maintenance operation is due.Perform the maintenance due. The warning doesnot time out.
Press the BACK button to return to the homescreen.
Fault
Starting Fault
Fault Number 32Hour 10000.1
BACK
FIGURE A-5. TYPICAL FAULT SCREEN
INFO
HIST
Maintenance
Due
Air Filter
New Event Screen
A New Event screen appears (Figure A-5) whenev-er system status changes, such aswhen there is aninterruptionof utility power. The screen provides abriefdescription of the event along with the time anddate of the event.
FIGURE A-6. TYPICAL MAINTENANCE DUE
SCREEN
New Event
Auto StartLoss of Utility
07/10/2007 4:08PM
FIGURE A-7. TYPICAL NEW EVENT SCREEN
A-4
Page 42
GENSET STATUS
To check generator set output voltage and frequency and the total numbers of hours run:
1. Press the MENU button on the home screen.
2. Press the up or down arrow button on the menu
screen to select Genset Status.
3.Press the ENTER button on the menu screenand note the values displayed on the GensetStatus screen.
4.Press the BACK button to return to the homescreen.
Sun 10:35 AM
Battery 12.5
Genset Load
L1L2
EXCER
Genset StatusDisplay SetupEvent Log
Fault LogEthernet Setup
CLOCKLOAD
MENU
ENTER
Genset Status
Voltage 240VFrequency 60Hz
Hr Meter 1234.6
FIGURE A-8. GENERATOR SET STATUS SCREEN
A-5
Page 43
DISPLAY SETUP AND SOFTWARE INFO
Brightness and Contrast
To change the Brightness and Contrast of the dis-play screen:
1.Press the MENU button on the home screen.
2.Pressthe up or down arrow button on the menuscreen to select Display Setup.
3.Press the ENTER button on the menu screen.
4.Press the NEXT button to select Brightness orContrast.
5.Pressthe increase or decrease arrow button toincrease or decrease brightness.
6.Change Contrast the same way as Brightness.
7.Pressthe BACK button to save the settings andreturn to the home screen.
Sun 10:35 AM
Battery 12.5
Genset Load
L1L2
EXCER
Genset StatusDisplay Setup
Display Setup
Event Log
Event Log
Fault Log
Fault Log
Ethernet Setup
Ethernet Setup
CLOCKLOAD
MENU
ENTER
ENTER
Display Setup
Brightness
Software Info
To check on the generator set and display software:
1.Press the MENU button on the home screen.
2.Pressthe up or down arrow button on the menuscreen to select Display Setup.
3.Press the ENTER button on the menu screen.
4.Press the INFO button on the Display Setupscreen and note the values displayed on theSoftware Info screen.
5.Press the BACK button to return to the homescreen.
Contrast
INFO
NEXT
Software Info
GEN SW P/N: 3261234SW VERSION: 12.34
Dis. SW P/N: 3261234
SW VERSION:10.23
FIGURE A-9. DISPLAY SETUP AND SOFTWARE
INFO SCREENS
A-6
Page 44
EVENT LOG
To Check Log of Last 20 Events
1. Press the MENU button on the home screen.
2. Press the up or down arrow button on the menu
screen to select Event Log.
3.Press the ENTER button on the menu screen.
4.Scroll through the event log with the up anddown double-arrow buttons. Each screen pro-vides abrief description of the event along withthe time and date of the event.
5.Press the BACK button to return to the homescreen.
17.“Gensetwarning − TransferSwitch Signal Fail-ure”
18.“Genset warning −Transfer Switch Failed toTransfer to Utility”
19.“Gensetwarning − Low Battery or Battery Char-ger Failure”
Sun 10:35 AM
Battery 12.5
Genset Load
L1L2
EXCER
Genset StatusDisplay Setup
Event LogFault LogEthernet Setup
Standby Enabled
05/04/2007 1:18PM
FIGURE A-10. EVENT LOG SCREEN
CLOCKLOAD
MENU
ENTER
Event Log 1 of 20
A-7
Page 45
FAULT LOG
To check the log of the last 5 faults:
1. Press the MENU button on the home screen.
2. Press the up or down arrow button on the menu
screen to select Fault Log.
3.Press the ENTER button on the menu screen.
4.Scroll through the fault log with the up and downdouble-arrow buttons. Each screen provides abriefdescription of the fault, the fault code num-ber and the time and date of the fault.
5.Press the BACK button to return to the homescreen
Note: If there are no faults recorded, the “No StoredFaults” screen will appear.
Sun 10:35 AM
Battery 12.5
Genset Load
L1L2
EXCER
Genset StatusDisplay Setup
Event LogFault LogEthernet Setup
Fault Log
CLOCKLOAD
MENU
ENTER
1of 5
Speed Sense LostFault No. 27
Hour 10000.1
BACK
or
Fault History
No Stored Faults
FIGURE A-11. FAULT LOG SCREEN
A-8
Page 46
ETHERNET SETTINGS
This feature allows for in-home or remote access to
your generator set through a web page. On this web
page, you can start or stop your generator set, adjust the exerciser day and time, determine if utility
power is available, and view the last 20 events/
faults on the generator set.
This feature is useful for homeowners who travel orhave asecond home and want to be able to remote-ly interface with their generator set. This feature canalso help to reduce troubleshooting time and ser-vice calls when the service technician has access tothe same web page.
Use of the ethernet is not required if you do not useweb access. To set up your generator set for webaccess, complete installation instructions are in-cluded in the Network Setup Guide (Appendix C).
Note: Ethernet setup must be done at the generatorset location. It cannot be done via the web from a dif-ferent location. An available Ethernet port and ahigh-speed internet are required for functionality.
dem/router probably can be configured for
DHCP to be OFF. Refer to the Network Setup
Guide (Appendix C) regarding the permanent
generator set IP address to assign.
8. Manually Enter IP Address—DHCP OFF − If
DHCP is OFF, it will be necessary to manually
enter the IP address, which consists of fourthree-digit numbers. To enter a number selectthe hundreds, tens or units field in each threedigit number field by pressing the NEXT andPREVbuttons. Push the up or down arrow to in-creaseor decrease the number in the selectedfield. Numbers inthe units fields will increase byone, in the tens fields by ten and in thehundreds field by one hundred. Refer to theNetwork Setup Guide in Appendix C to makesure setup is complete.
Note: If utilizing a remote internet access to the gen-erator set, it is recommended that a UPS batterybackup be connected to your router and/or modem.
To reset the Internet and email interface IP addressand password:
1.Press the MENU button on the home screen.
2.Pressthe up or down arrow button on the menuscreen to select Ethernet Setup.
3.Press the ENTER button on the menu screen.
4.Press the NEXT button to select the field tochange.
5.To Reset Password −If you have forgottenyour password, select the Reset Passwordfield and press an up or down arrow. The pass-word will be reset to “cummins”. Press theBACK button to go back to the home screen.
6.IP Address −If DHCP is ON (factory setting),the modem/router will assign the generator setIP address displayed here. This is the addressyou enter in your internet browser address bar
at the http:// location (page B-1). The address
assigned tothe generator set may change overtime.If, for example, the modem/router is un-plugged, it will probably re-assign new ad-
dresses to all of the devices in the home that it
serves. If the IP address you have been using
does not work any longer, copy down the new
address and enter it on the browser page.
Sun 10:35 AM
Battery 12.5
Genset Load
L1L2
EXCER
Genset StatusDisplay Setup
Event LogFault LogEthernet Setup
CLOCKLOAD
MENU
ENTER
Network Setup
DHCP ON
192.168.000.002
IP
Reset Password
NEXTPREV
7. DHCP ON/OFF − DHCP leaves the factory ON.
If more advanced features are desired, the mo-
FIGURE A-12. NETWORK SETUP SCREEN
A-9
Page 47
EXERCISE SETTINGS
To set the generator set exercise schedule:
1. Press the EXCER button on the home screen.
2. Press the NEXT button on the Exerciser Clock
screen to select the field to change.
3.Press the up or down arrow button to increaseor decrease the frequency of exercise and theday of the week and time of day for exercise.Frequency selections are: Weekly, Bimonthly,Monthly or Never.
4.Pressthe BACK button to save the settings andreturn to the home screen.
5.If you want to exercise the generator set now,select “Exercise Now”, and press either the upor down arrow.
Note: Scheduled or prompted exercise does nottransfer the house loads to the generator set.
Sun 10:35 AM
Battery 12.5
Genset Load
L1L2
EXCER
CLOCKLOAD
MENU
Exerciser Clock
Clock
Exercise: Weekly
10:
AM15Mon
Exercise Now
NEXT
FIGURE A-13. EXERCISE CLOCK SCREEN
A-10
Page 48
TIME SETUP
To set up the generator set clock for the current date
and time:
1. Press the CLOCK button on the home screen.
2. Press the NEXT button on the Time Setup
screen to select the field to change.
3.Press the up or down arrow button to increaseor decrease or change the date or time.
4.Pressthe BACK button to save the settings andreturn to the home screen.
Sun 10:35 AM
Battery 12.5
Genset Load
L1L2
EXCER
CLOCKLOAD
MENU
Time Setup
Date:
Time:
FIGURE A-14. TIME SETUP SCREEN
Jan
10:15AM
15
2007
NEXT
A-11
Page 49
LOAD MANAGEMENT
The generator set may have been set up at installation to connect and disconnect certain large loads,
such as air conditioners, to manage the total load so
as not to overload the generator set. This requires
the installation of two relays which allow for the connection of two large loads. Load management canbe set to operate in automatic or manual mode (Fig-ure A-15).
Whether in automatic or manual mode, there is adelayed start. Load 1 is enabled three minutes afterthegenerator set is connected to the house loads,and Load 2 is enabled six minutes after the genera-tor set is connected to the house loads.
Automatic Load Management
Manual Load Management
CAUTION
vice, it is highly recommended that manual load
management be undertaken only by an authorized Cummins Onan dealer.
When set to manual mode, the user is able to view,connect, and disconnect loads. If the connection ofloads L1and L2 exceeds generator capacity,the ACcircuit breaker trips.
To select manual load management when the gen-erator is running:
To reduce unnecessary loss of ser-
When set to automatic mode, the user takes no ac-tion and can only view which loads are connected.Three minutes after the generator starts, the loadthat isconnected to genset load L1 is connected. Af-ter a delay of three more minutes, the load that isconnectedto genset load L2 is connected. If theconnection of loads L1 and L2 exceeds 95% of thegenerator’sload capacity, they are disconnected bythegenerator. Following another three minutedelay, the control reconnects both loads followingthe same connection sequence used in the first at-tempt (three minutes apart). If generator load ca-pacity is exceeded again, both loads are discon-nected, and no further reconnection is tried.
To select automatic load management and viewwhether the selected loads are connected while thegenerator set is running:
1.Press the LOAD button on the home screen.
2.Pressthe up or down arrow button to select Au-tomatic.
3.Note which loads are connected or discon-nected.
1.Press the LOAD button on the home screen.
2.Press the up or down arrow button to selectManual.
3.Note which loads are connected or discon-nected.
4.Press the double-down arrow button to go thethe load connect/disconnect screen.
5.Connect ordisconnect Load 1 or Load 2 as nec-essary by pressing either button under Load 1or Load 2.
6.Press the BACK button to save the setting andreturn to the home screen.
4.Press the BACK button to return to the homescreen.
A-12
Page 50
Sun 10:35 AM
Load Management
Battery 12.5
Genset Load
L1L2
EXCER
CLOCKLOAD
MENU
Load Management
Mode: Automatic
1: Disconnected2: Connnected
AUTOMATIC MODE
FIGURE A-15. LOAD MANAGEMENT SCREEN
Mode: Manual
1: Disconnected
2: Connnected
When running:
1: Disconnected2: Connected
Connect
Load 1
MANUAL MODE
Disconnect
Load 2
A-13
Page 51
THIS PAGE INTENTIONALLY LEFT BLANK
A-14
Page 52
Appendix B. Internet / Email Interface
INTRODUCTION
Refer toSection A. Operation for use of the remote
Operator Panel to operate and monitor the genera-tor set. The Internet / Email Interface makes thesamefault, maintenance and event notices avail-able to you and to your generator set service con-tract agency wherever Internet Service is estab-lished.
HOME PAGE
Enterthe generator set IP address (listed on the MyCummins Onan Generator sheet, see page B-5) in
192.168.1.100
http://192.168.000.002
your internet browser address bar at the http:// loca-
tion. If you are on a computer that is connected to
the same network as your generator set, use Gener-ator In-Home IP address; otherwise, use the PublicIP Address. Enter your User Name and Password inthe browser dialog box that pops up. Use admin forthe Username. The password set at the factory iscummins. See ETHERNET SETUP (p. A-9) to re-set the password to “cummins” if you have forgottenthe password you set up (p. B-4).
Note: Ifthe internet cable/dsl is out of order, commu-nication with your generator set will be suspendeduntil your internet connection is restored.
Figure B-1. Generator Set Home Page
FIGURE B-2. HOME PAGE
B-1
Page 53
See ETHERNET SETUP (p. A-9) to view and copy
down the generator set IP address, if for some reason it has changed.
The home page displays the current status of the
system. Use the tabs to navigate in the site.
SETTING TIME AND DATE
Select the Genset Time/Date Tab on the HomeScreen toset the time and date for the generator setcontrol.
SET EXERCISE SCHEDULE
FIGURE B-3. SET GENSET TIME AND DATE
Select the Exercise Schedule Tab on the HomeScreen to set the generator set exercise schedule.
Note: The generator set will exercise on the firstscheduledday for which it is programmed. After thatit exercises on that day at the scheduled interval. Forexample, if the generator set is scheduled on aWednesdayfor Saturdays with a monthly interval,the generator set starts on the next available Satur-day. After that it exercises on Saturdays one monthapart.
LOAD CONTROL (MANAGEMENT)
Select the Load Control Tab on the Home Screen toenable Automatic or Manual Load Control. In Auto-maticmode, the user can only view which loads areconnected. In Manual mode, the user can view
loads and also connect or disconnect them. See
LOAD MANAGEMENT (p. A-12) for details.
FIGURE B-4. SET EXERCISE SCHEDULE
FIGURE B-5. GENSET LOAD MANAGEMENT
B-2
Page 54
EVENT LOG
Select the Event Log Tab on the Home Screen to review the last 20 events. See EVENT LOG (p. A-7)
for a list of all of the recordable events.
FIGURE B-6. EVENT LOG
FAULT LOG
Select the Fault Log Tab on the Home Screen to re-view the last 5 faults.
FIGURE B-7. FAULT LOG
B-3
Page 55
NETWORK SETUP
Email Addresses
Select the Network Setup Tab on the Home Screen
to set up the network parameters. Click on “Click
here to start Network Setup” to go to the first of three
screen pages to setup network and email parameters. Press the NEXT button to go to the next pageand the Done button on the last page to save thesettings on all three pages. Click on “Click here tocontinue...” to go back to the Home Page.
Change Password
You may change the password by entering 8 char-acters in the password field and clicking on “SavePassword”.See ETHERNET SETUP (p. A-9) to re-set the password to “cummins.”
Network Setup Parameters
Refer toAppendix Cfor complete setup instructionsand Appendix D for troubleshooting.
DHCP ON −All of the fields will be filled in by themodem/router.
You may enter up to three Email addresses to whom
to send generator set status and event messages.
FIGURE B-8. NETWORK SETUP SCREEN
Assess From Internet −To access your generator
set Internet site from anywhere on the Internet, askyour Internet Service Provider (ISP) for your Inter-net IP address. Alternatively, enter the Gateway ad-dressthat appears on Page 1 of the Network Setupscreens (Figure B-9).
DHCP OFF − If more advanced features are de-sired, the modem/router probably can be config-uredfor DHCP to be OFF. Refer to the manufactur-er’s instructions regarding the permanent generatorset IP address to assign.
Email Setup Parameters
Set Alert Level −Click on Alert Level drop-down
box arrow. Select “Never”, “All Events”, “Mainte-nance and Attention Required”, or “Attention Re-quired Only”. This will determine which events willinitiate emails to the selected addresses.
OutgoingServer (SMTP) Settings − Ask your In-ternet Service Provider (ISP) for the Server Name,
User Name and Password to enter.
FIGURE B-9. NETWORK SETUP PARAMETERS
FIGURE B-10. EMAIL SETUP PARAMETERS
FIGURE B-11. EMAIL ADDRESSES
Note: An Email account capable of SMTP authentication via port 25 is required. The User Name must include the domain name (i.e. username@domainname).
FIGURE B-12. RETURN TO HOME PAGE
B-4
Page 56
FIGURE B-13. MY CUMMINS ONAN GENERATOR INFORMATION SHEET
B-5
Page 57
THIS PAGE INTENTIONALLY LEFT BLANK
B-6
Page 58
Appendix C. Cummins Onan Model RS12000
Generator Set Network Setup Guide
INTERNET
(WORLD WIDE WEB)
W
Public IP: 176.196.052.094
MODEM
CAT 5 CABLE
Forward Port 80 to
192.168.000.001
(RECOMMENDED)
UPS
ROUTER/SWITCH
Device IP: 192.168.000.001
Forward Port 80 to
192.168.000.150
Static IP: 192.168.000.150
GENERATOR SET
CONTROL BOARD
Dynamic IP: 192.168.000.003
GENERATOR SET
FIGURE C-1. NETWORK CONNECTIONS
NOTE:IPs mentioned in these
instructionsare samples only.
PERSONAL COMPUTER
C-1
Page 59
SETTING UP IN-HOME NETWORK
ACCESS TO THE GENERATOR SET
1. Connect an Ethernet cable* from the generator
set control board to a router that has enough
ports to connect the generator set and a computer.
2.Write down the IP Address shown on the Net-work Setup screen (Figure C-2) on the genera-tor set’s in-home Operator Panel. (Note: Leave
DHCP on.) Add this Generator In-HomeIPAd-dress to the Information Sheet located on page
B-5 of the Operator Manual or page C-5 of theInstallation Manual under “Internet Access toGenerator Set-up Information” only if remoteaccess to the generator is not utilized.
3.Type the IP address in the address bar of theweb browser of a computer established on thesame in-home network as the generator set.The computer’s web browser will display thegeneratorset’s web page (Figure C-3).
* If you are making your own ethernet connections,followthe ethernet cable instructions in the Installa-tion Manual.
Sun 10:35 AM
Battery 1.2 VDC
Genset Load
L1 L2
EXER
MENUCLOCKLOAD
Genset StatusDisplay SetupEvent Log
Fault Log
Ethernet Setup
ENTER
Network Setup
DHCP
IP
192.168.000.002
ON
Reset Password
NEXTPREV
FIGURE C-2. NETWORK SETUP SCREEN ON THE
IN-HOME OPERATOR PANEL
192.168.1.100
FIGURE C-3. GENERATOR SET HOME PAGE
C-2
Page 60
SETTING UP CONSOLE INTERNET
ACCESS TO THE GENERATOR SET
1. Have a public IP address established for the inhome computer network. Typically, it will be
necessary to contact the customer’s ISP
(Internet Service Provider). Note: The ISP
might take several days to establish the IP ad-dressand an additional service cost may be in-
curred.Add this Public IP Address to the Infor-
mation Sheet located on page B-5 of the Oper-ator Manual or page C-5 of the InstallationManual under “Internet Access to GeneratorSet-up Information.”
2.Set up in-home computer access to the gener-ator set. See Figure C-1.
3.Click Network Setup on the home page (Fig-ure C-3).
4.Change the password and click Save Pass-word(Figure C-4)Information Sheet located on page B-5 of theOperator Manual or page C-5 of the Installa-tion Manual under “Internet Access to Genera-tor Set-up Information.”
5.ClickClick here to start Network Setupure C-4).
6.Click Off to turn off generator set DHCP (Fig-ure C-5).
1
. Add this Password to the
(Fig-
11. Follow the router setup instructions to forward
port 80 to the IP Address entered in Step 7.
Typically, this is done on a Port Forwarding or
Virtual Server setup screen. (Note: To maintain
connections to all devices connected to the
modem/router, do not turn off modem/router
DHCP.)
12.Follow the modem setup instructions to for-ward port 80 to the router IP Address(192.168.000. 001 in this example). Typically,thisis done on a Port Forwarding or VirtualServer setup screen. (Note: To maintain con-nections to all devices connected to the mo-dem/router, do not turn off modem/routerDHCP.) (Note: If the router is capable of beingset up as a switch, plug the input from the mo-dem into one of the open router outputsinstead of accomplishing this step.)
13.To access the generator set’s web page on anycomputer or wireless device not connected tothe same modem/router as the generator set,type in the customer’s public IP Address
2
(179.196.052.094 in this example)
.
14.To access the generator set’s web page on anycomputer or wireless device connected to thesame modem/router as the generator set, typein the unique in-home network address of thegenerator set (192.168.000.150 in this exam-ple).
7.In the IP Number fields enter a unique in-homenetwork address for the generator set (the
192.168.000.150 in this example) that is notlikely to have been assigned to any other de-vice.Note: You must use the same first ninedigits as the router (192.168.000 in this exam-
ple). Addthis Generator In-HomeIPAddress
to the InformationSheetlocatedonpageB-5of theOperatorManual or page C-5oftheInstallation Manualunder“InternetAccesstoGenerator Set-upInformation”.
8.TheSubnet Mask, Static DNS #1 and #2, andGateway numbers establish the connectionsbetween the modem/router and generator setand do not need to be changed.
9.Press Next on the subsequent screens to get
to page 3 of the setup screens or continue by
setting up the email alerts.
10. Press Done to complete set up and save the
settings. (Note: The web page will eventually
time out unless the new IP address is entered.)
FIGURE C-4. NETWORK SETUP SCREEN
FIGURE C-5. NETWORK SETUP (PAGE 1)
C-3
Page 61
Installation Manual under “Email Alerts from
Generator Set-up Information.”
6. Continue to the Destination Email Address-es screen (Figure C-7). Add these addresses
to the Information Sheet located on page B-5
of the Operator Manual or page C-5 of the
Installation Manual under “Email Alerts fromGenerator Set-up Information.”
7.Enter up to three different email addresses toreceive generator set alerts.
FIGURE C-6. EMAIL SETUP SCREEN (PAGE 2)
SETTING UP EMAIL ALERTS FROM THE
GENERATOR SET
1.Set up in-home computer access to the gener-ator set. See C-2.
2.Click Network Setup on the home page (Fig-ure C-3).
3.Continue to the Email Setup screen (FigureC-6).
4.Select the Alert Level you would like to re-ceive. Add this Alert Level to the InformationSheet located on page B-5 of the OperatorManualor page C-5 of the Installation Manualunder “Email Alerts from Generator Set-up In-formation.”
5.Enter your email Server Name, User Name(inclusive of domain − for example, username@yahoo.com), and Password (FigureC-6). Typically, it will be necessary to contactthe customer’s email service provider. (Note:The email account must allow SMTP via port25; verify with your ISP). Add this informationto the Information Sheet located on page B-5of the Operator Manual or page C-5 of the
8.PressDone. (Note: The web page will eventu-ally time out if a new IP address was enteredinStep 7 while setting up Internet access.)
1 −If you can’t remember your password, reset it to “cummins” by se-
lecting Reset Password on the Network Setup screen on the in-home Operator Panel and pressing the up or down arrow (FigureC-1).
2 −The customer’s public IP address must be a static IP address. If the
customer’spublic IP address is dynamic, the customer must eitherobtain astatic IP address from their service provider or set up a do-main name that manages the dynamic IP address.
C-4
Page 62
FREQUENTLY ASKED QUESTIONS
Question: What is DHCP?
Question: Do I need another router?
Answer: Yes, a router or switch is required to allow
for the connection of more than one device
(computer,generator set, etc.) with each other andtheInternet. Typically, your Internet modem alsoserves as arouter. If you have anavailable ethernetconnection on your router-enabled modem, youmay not need to add an additional router.
Question:Do I need another modem?
Answer:A modem is required if you want to utilize
the email and remote Internet access features ofthegenerator set. If you already have an Internetconnection, you have a modem. Only one modemis required.
Question:What is an IP address?
Answer:An IP address, or Internet Protocol ad-
dress,is a unique address that devices such as acomputer or your home generator set use to com-municate with each other, both on your in-homenetwork (LAN network) or with the World WideWeb.
Question:What isthe difference between Static and
Dynamic IP addresses?
Answer:On your in-home network, the router (with
DHCP enabled) will assign a dynamic IP address toall devices (computer, home generator set, etc.)connected to the router. As devices are added andremoved from the router, the devices areautomaticallyupdated with new IP addresses. Thismeans that your computer and generator set IPaddresseswill not always be the same unless staticIP addresses are assigned. A static IP address isan unique address that is permanently assigned toa device. On the World Wide Web, your typical ISP(internetservice provider) assigns a dynamic IPaddressto your Internet connection. This is the IPaddress you type into your Internet browser toaccessyour generator set from the World WideWeb.A static IP address is required for you toestablish a constant address you can always
access from the World Wide Web. Contact your ISP
to set up a static IP address for your Internet
connection.
Answer: DCHP, or Dynamic Host Configuration Pro-
tocol, automatically assigns IP addresses, subnet
masks, and gateways to devices, allowing them to
communicate with each other. Your router and generator set are equipped with DHCP. Default is for
DHCP to be on.
Question:Why do I need a static IP address?
Answer:As discussed in the question about “differ-
ences between Static and Dynamic IP addresses”,this is required for your generator to access theWorld Wide Web.
Question:What is aUPS device and why is it recom-
mended?
Answer: A UPS (Uninterruptible Power Supply) de-
vice isbattery backup to keep devices such as com-puters and modems powered during short-termpoweroutages. We recommend that the modem/router be powered through a UPS device to ensurethat your generator set is able to send emails andbe remotely accessed at all times. For example, ifyourgenerator set shuts down during a utility poweroutage, the generator set can still send you anemailletting you know that the power has failed andthat the generator set shut down.
Question:When do I need to use a Static IP ad-
dress?
Answer:Static IP addresses are required ifyou plan
to access your generator set remotely via the Inter-net.
Question: I used the IP addresses shown on the
front of this guide, but why was I not able to accessthe generator set?
Answer: The IP addresses shown in this guide are
onlyexamples and are not likely to be the ones thatwill work on your network setup.
Question:The IP address consists of four numbers
rangingfrom 0 to 255 which are separated by dots;
179.168.052.094, for example. Are leading zerosnecessary?
Answer: No, the IP address, 192.168.0.1, for exam-
ple, is equivalent to 192.168.000.001. The address
can be entered either way.
C-5
Page 63
Question: How do I get my IP number, Subnet Mask,
and Gateway?
Answer: On a PC: 1) disable the PC’s wireless func-
tion, 2) establish an ethernet connection between
the computer and generator set via a common modem, 3) on the computer, Click Start>Run, 4) on the
run menu that appears type “cmd” and click ok, 5)type “ipconfig” on the DOS window that appears.
Question:Why do I need two IP addresses to access
my generator set?
Answer: You can access your generator set from
two networks, your in-home or local network, and
from the World Wide Web, thus requiring two addresses. Your local IP address is different from your
World Wide Web IP address. From your in-home
network you use the generator set’s Static IP address. From the World Wide Web you first need toaccessyour modem, which is accomplished by typ-ing in the Static IP address of your Internet connec-tion.Your modem will then automatically forwardyou to your generator set on the local network.
C-6
Page 64
Appendix D. Communication Troubleshooting
IN-HOME NETWORK ACCESS TO GENERATOR SET TROUBLESHOOTING
WARNING
sonal injury or death. Only trained and experienced service personnel with knowledge of fuels,electricity, and machinery hazards should perform Generator Set service.
Possible Causes: Bad connections or bad communications
Corrective Actions:
1.Check connections.a.Verify that the Ethernet cable is plugged into the generator set control and the router.
b.Verify that the computer is connected to the same router as the generator set via an Ethernet
c.Verify that the wireless card on the computer is turned off.
d.Check to see if both ends of the Ethernet cable are assembled and crimped as described in the
e.Verify that the Ethernet cable connections between the generator set and the router are solid and
2.Check communications.a.Check to see if you can access a standard web page with the computer connected to the same
b.Check to see if the green and orange lights are illuminated at the Ethernet connection port on
c.Check to see if the correct generator IP address has been entered, as described in step 3 (page
d.Check to see if you can access the generator set via the in-home network. If not, call Cummins
Some Generator Set service procedures present hazards that can result in severe per-
cable.
installationinstructions. If not, reassemble and crimp as described in the installation instructions.
correct.
f.Proceed to “Check communications.”
router as the generator set. If not, contact your router manufacturer for troubleshooting informa-tion.
the generator set control board (see Figure D-1). If not, disconnect the Ethernet cable from thegenerator control board and connect it to the computer. Check to see if you can access a stan-dard web page with the computer connected to the generator side of the Ethernet cable.
1)If you can access a standard web page, call Cummins Support at 1-800-888-6626 and selectoption 1.
2)If you cannot access a standard web page, go to “Check connections” above.
C-2) of the Network Setup Guide (i.e. http://xxx.xxx.xxx.xxx). If not, enter the correct IP address.
Support at 1-800-888-6626 and select option 1.
ETHERNET
CONNECTION
GENERATOR SET
CONTROL BOARD
FIGURE D-1. NETWORK CONNECTIONS
D-1
GENERATOR SET
Page 65
REMOTE INTERNET ACCESS TO GENERATOR SET TROUBLESHOOTING
WARNING
sonal injury or death. Only trained and experienced service personnel with knowledge of fuels,
electricity, and machinery hazards should perform Generator Set service.
Possible Causes: An improper setup, no high-speed internet connection, the public IP address is notactive orproperly set up, an incorrect IP address is entered, the computer is connect to the same router ornetwork and the generator set, or the internet connection is bad,
Corrective Actions:
1.Check to see if you are able to access the generator set with your in-home computer. If not, referto the “In-home Network Access Troubleshooting” procedures.
2.Verify that you followed the network setup procedures. Refer to the Network Setup Guide in Appen-dix C.
3.Verify that you are using a high-speed internet connection.
4.Verifythat the public IP address is active and set up properly with the ISP (Internet Service Provider).Ifnecessary, contact the ISP to verify your setup.*
5.Verify that the correct public IP address is entered into the web browser of the computer (i.e.xxx.xxx.xxx.xxx).
6.Verify that the computer is not connected to the same router or network as the generator set. Thecomputerused for internet access must be connect to a different internet connection than the gener-ator set.
7.Check tosee if you can access a standard web page from a computer. If not, contact the ISP to trou-bleshoot the internet connection.
Some Generator Set service procedures present hazards that can result in severe per-
8.Verify all settings, as described in the Network Setup Guide.
9.If the previous steps do not correct the problem, contact a computer network specialist to diagnose.
*To verify your IP address, access “whatismyipaddress.com” from the browser of a computer connected tothe internet and on the same network as the generator set. This web page displays your current IP addresswhich should match the IP address assigned to you by your ISP.
D-2
Page 66
EMAIL ALERT TROUBLESHOOTING
WARNING
Some Generator Set service procedures present hazards that can result in severe personal injury or death. Only trained and experienced service personnel with knowledge of fuels,
electricity, and machinery hazards should perform Generator Set service.
Possible Causes: An improper setup, the alert level is not set to “all events,” emails cannot be received,the outgoing email address is not included in your contact list, the email account is not capable of usingport 25 with plain SMTP for the outgoing SMTP server setup, the domain name is not included in the username filed of the Network Setup screen, or the DNS #1 and #2 values are incorrect on the Network Setupscreen.
Corrective Actions:
1.Check to see if you are able to access the generator set with your in-home computer. If not, referto “In-Home Computer Access Troubleshooting.”
2.Verify that you followed the network setup instructions. Refer to the Network Setup Guide in Appen-dix C.
3.Verify that the alert level is set to “All Events” (see Figure D-4).To verify that your generator set cansend emails, select “Disable Standby” (see Figure D-3) and wait several minutes to verify that youdid receive an email. Then select “Enable Standby” and wait a few more minutes to verify that youdid receive a second email.
4.Send an email to the destination email address and check to see if you received this email. If not,contact your email service provider or your ISP (internet service provider) to diagnose.
5.Check to see if the destination email accounts have spam filtering.
a.If spam filtering is present, add the outgoing email address to your contact list.b.If spam filtering is not present, proceed to step 6.
6.Check to see if you are using an email account capable of using port 25 with plain authenticationSMTP server setup (see Figure D-4). If necessary, obtain an email account capable of using port25 with plain authentication SMTP and enter detail into the network setup screen (see Figure D-4).
7.Verify that the domain name is included in the user name field of the Network Setup screen shownin Figure D-4 (i.e. username@domainname).**
8.Verify with your ISP that the Static DNS (Domain Name Server) #1 and #2 are correct (see FigureD-2).
9.If the previous steps do not correct the problem, contact a computer network specialist to diagnose.
** “No authentication” is possible by leaving the username and password fields blank.
IMPORTANT NOTE: Changes are not saved unless you navigate through all three Network Setup screensand click on “Done” (see Figure D-5). The message “Settings Saved Successfully” is then displayed.
NOTE: THE GENERATOR SET AND TRANSFER SWITCH
MUST BE INSTALLED IN ACCORDANCE WITH THE
INSTALLATION MANUALS THAT ARE SHIPPED WITH
EACH UNIT.
OPTIONAL LOAD MANAGEMENT RELAY CONTROL SIGNALS(B+ OUTPUTS)
MINIMUM MATERIAL REQUIRED: (SEE INSTALLATION MANUAL FOR COMPLETE
MATERIAL LIST AND INSTALLATION INSTRUCTIONS)
1.QTY (10) 18-20 GAUGE WIRES FOR COMMUNICATIONS CONNECTIONS. CUMMINS
RECOMMENDS THE USE OF TWISTED PAIR WIRES FOR TB1-9 AND TB1-10.
12 WIRES IF OPTIONAL LOAD CONTROL IS UTILIZED.
2.QTY (4) 8 GAUGE (FOR UP TO 125 FT) 90C WIRE FOR AC CONNECTIONS.
3.QTY (2) 12 GAUGE (FOR UP TO 125 FT) 90C WIRE FOR GFCI AND AC DISTRIBUTION
BLOCK.
4.QTY (10) UL LISTED FORK TERMINAL FOR 18 GAUGE WIRES (CUMMINS PART
NUMBER 0332−2527).
5.AC CONDUIT (FOR LOAD CABLES AND 15 AMP CIRCUIT CABLES).
6.DC CONDUIT (FOR ALL COMMUNICATION AND ETHERNET CABLES).
7.4 WALL ANCHORS AND 4 BLACK SCREWS FOR DISPLAY MOUNTING.
8.CAT 5 ETHERNET CABLE (OPTIONAL).
9.12 VOLT RELAY (OPTIONAL, CUMMINS PART NO. 0307−3172 OR ANY 12 VDC COIL
WITH A MINIMUM CONTACT RATING OF 1 AMP AT 24 VAC).
10CONDUIT SEALING PUTTY.11GAS LINE AND STEP DOWN REGULATOR (AS REQUIRED) FOR GAS CONNECTIONS
− MAX FULL LOAD BTU ON NATURAL GAS = 191,000 BTU/HOUR AND ON PROPONE =220,000 BTU/HOUR OR 2.4 GALLON/HOUR − 5−11” WC PRESSURE AT GENERATOR
REQUIRED.
12.UL LISTED PIPE DOPE.
13.BATTERY REQUIREMENT: 12 VOLT, GROUP 26R, 530CCA
0630−3707
CONNECTIONS TO TRANSFER SWITCH
RSS100−6868 OR RSS200−6869
F-5
Page 77
NOTE: THE GENERATOR SET AND TRANSFER SWITCHMUST BE INSTALLED IN ACCORDANCE WITH THEINSTALLATION MANUALS THAT ARE SHIPPED WITHEACH UNIT.
OPTIONAL LOAD MANAGEMENT RELAY CONTROL SIGNAL(B+ OUTPUTS)
MINIMUM MATERIAL REQUIRED: (SEE INSTALLATION MANUAL FOR
COMPLETE MATERIAL LIST AND INSTALLATION INSTRUCTIONS)
1.QTY (7) 18-20 GAUGE WIRES FOR COMMUNICATIONS CONNECTIONS.
CUMMINS RECOMMENDS THE USE OF TWISTED PAIR WIRES
FOR TB1-9 AND TB1-10. 9 WIRES IF OPTIONAL LOAD CONTROL
IS UTILIZED.
2.QTY (4) 8 GAUGE (FOR UP TO 125 FT) 90C WIRE FOR AC CONNECTIONS.
3.QTY (2) 12 GAUGE (FOR UP TO 125 FT) 90C WIRE FOR GFCI AND AC
DISTRIBUTION BLOCK.
4.QTY (7) UL LISTED FORK TERMINALS FOR 18 GAUGE WIRES
(CUMMINS PART NUMBER 0332−2527).
5.AC CONDUIT (FOR LOAD CABLES AND 15 AMP CIRCUIT CABLES).
6.DC CONDUIT (FOR ALL COMMUNICATION AND ETHERNET CABLES).
7.4 WALL ANCHORS AND 4 BLACK SCREWS FOR DISPLAY MOUNTING.
8.CAT 5 ETHERNET CABLE (OPTIONAL).
9.12 VOLT RELAY (OPTIONAL, CUMMINS PART NO. 0307−3172 OR ANY
12 VDC COIL WITH A MINIMUM CONTACT RATING OF 1 AMP AT 24 VAC).
10.CONDUIT SEALING PUTTY.
11.GAS LINE AND STEP DOWN REGULATORS (AS REQUIRED) FOR GAS
CONNECTIONS − MAX FULL LOAD BTU ON NATURAL GAS =
191,000 BTU/HOUR AND ON PROPONE = 220,000 BTU/HOUR OR
2.4 GALLON/HOUR − 5−11” WC PRESSURE AT GENERATOR REQUIRED.
12.UL LISTED PIPE DOPE.
13.BATTERY REQUIREMENT: 12 VOLT, GROUP 26R, 530CCA
0630−3707
CONNECTIONS TOTRANSFER SWITCH RSS100−6634 OR RSS200−6635