Page 1
Operator Manual
RV Generator Set
HGJBB (Spec A)
English
Original Instructions
06-2012 A031C171 (Issue 1)
Page 2
Page 3
Table of Contents
1. IMPORTANT SAFETY INSTRUCTIONS ....................................................................................... 1
1.1 Warning, Caution and Note Styles Used In This Manual ....................................................... 1
1.2 General Precautions ............................................................................................................... 1
1.3 Automatic Generator Start Control Hazards ........................................................................... 2
1.4 Generator Voltage is Deadly ................................................................................................... 2
1.5 Engine Exhaust is Deadly ....................................................................................................... 3
1.6 Fuel is Flammable and Explosive ........................................................................................... 4
1.7 Battery Gas is Explosive ......................................................................................................... 4
1.8 Moving Parts Can Cause Severe Personal Injury or Death ................................................... 4
2. INTRODUCTION ............................................................................................................................ 5
2.1 About This Manual .................................................................................................................. 5
2.2 Nameplate ............................................................................................................................... 5
2.3 Typical Genset ........................................................................................................................ 6
2.4 Fuel Recommendations .......................................................................................................... 8
2.4.1 Gasoline Models .......................................................................................................... 8
2.4.2 LPG Models ................................................................................................................. 8
2.5 Engine Oil Recommendations ................................................................................................ 8
2.6 Starting Batteries .................................................................................................................... 9
2.7 Genset Control Panel .............................................................................................................. 9
2.8 Remote Control Panel ........................................................................................................... 10
3. OPERATION ................................................................................................................................ 13
3.1 Conducting the Pre-Start Checks ......................................................................................... 13
3.2 Priming Gasoline Fuel Systems ............................................................................................ 13
3.3 Starting the Genset ............................................................................................................... 14
3.4 Stopping the Genset ............................................................................................................. 14
3.5 Restarting the Genset ........................................................................................................... 14
3.6 Loading the Genset ............................................................................................................... 15
3.7 Resetting Circuit Breakers .................................................................................................... 16
3.8 Connecting Shore Power ...................................................................................................... 17
3.9 Operating in Cold Weather ................................................................................................... 17
3.10 Operating in Hot Weather ................................................................................................... 18
3.11 Operating in Dusty Environments ....................................................................................... 18
3.12 Operating at a High Altitude ................................................................................................ 18
3.13 Breaking in a New Engine .................................................................................................. 18
3.14 Exercising the Genset ......................................................................................................... 18
3.15 Storing the Genset .............................................................................................................. 19
3.15.1 Gasoline Models ...................................................................................................... 19
3.15.2 Liquid Propane Models ............................................................................................ 19
3.15.3 Storing the Genset ................................................................................................... 19
3.15.4 Returning The Genset to Service ............................................................................ 20
A031C171 (Issue 1) i
Page 4
Table of Contents 06-2012
4. PERIODIC MAINTENANCE......................................................................................................... 23
4.1 Conducting General inspections........................................................................................... 23
4.1.1 Oil Level ..................................................................................................................... 23
4.1.2 Exhaust System ......................................................................................................... 23
4.1.3 Fuel System ............................................................................................................... 24
4.1.4 Battery Connections ................................................................................................... 24
4.1.5 Mechanical ................................................................................................................. 24
4.2 Checking Engine Oil Level .................................................................................................... 24
4.3 Changing Engine Oil ............................................................................................................. 25
4.4 Replacing the Air Filter Element ........................................................................................... 26
4.5 Replacing the Spark Plug ..................................................................................................... 26
4.6 Cleaning the Spark Arrestor ................................................................................................. 27
4.7 Replacing the Fuel Filter ....................................................................................................... 28
4.8 Maintaining Battery and Battery Connections ....................................................................... 29
5. TROUBLESHOOTING ................................................................................................................. 31
5.1 Fault Codes ........................................................................................................................... 31
6. SPECIFICATIONS ....................................................................................................................... 37
7. INFORMATION FOR CALIFORNIA GENSET USERS ................................................................ 39
8. HOW TO OBTAIN SERVICE ....................................................................................................... 41
9. MAINTENANCE RECORD ........................................................................................................... 43
ii A031C171 (Issue 1)
Page 5
1 Important Safety Instructions
SAVE THESE INSTRUCTIONS - This manual contains important instructions that should be
followed during installation and maintenance of the generator set and batteries.
Safe and efficient operation can be achieved only if the equipment is properly operated
and maintained. Many accidents are caused by failure to follow fundamental rules and
precautions.
1.1 Warning, Caution and Note Styles Used In This
Manual
The following safety styles and symbols found throughout this manual indicate potentially
hazardous conditions to the operator, service personnel or the equipment.
DANGER: Warns of a hazard that will result in severe personal injury or death .
WARNING: Warns of a hazard that may result in severe personal injury or death .
CAUTION: Warns of a hazard or an unsafe practice that can result in product or property
damage .
NOTE: A short piece of text giving information that augments the current text .
1.2 General Precautions
WARNING: The generator set produces carbon monoxide, has dangerous moving parts
and may be hot at times. Keep children away from the generator set.
WARNING: Evaporative starting fluids are highly explosive and may cause personal
injury or death if ignited. Do not use evaporative starting fluids.
WARNING: Alcohol, drugs and mental or physical fatigue may cause impairment which
may result in personal injury to the affected person or others. Do not operate,
service, or install a generator set after consuming alcohol or drugs, or when
mentally or physically fatigued.
WARNING: Hot, moving, or electrically charged parts can cause severe injury or death.
Only trained and experienced personnel should make adjustments while the
generator set is running.
WARNING: Operating the genset with the access cover off can result in severe personal
injury or equipment damage. Hot components are exposed when the access
cover is removed and genset cooling air does not circulate properly. Do not
operate the genset with the access cover removed.
WARNING: Improper installation may cause product damage, severe injury, or death.
Comply with all applicable local, state and federal codes and regulations to
verify proper generator set installation.
A031C171 (Issue 1) 1
Page 6
1. Important Safety Instructions 06-2012
WARNING: When equipped with an integral or add-on Auto-matic Generator Starting
System (AGS) control, carbon monoxide exhaust inhalation (CO), electric
shock, and moving parts hazards are possible due to unexpected starting.
Turn off AGS whenever performing maintenance or service, when the vehicle
is stored between uses, is awaiting service, or is parked in a garage or other
confined area to avoid these hazards.
WARNING: Electricity, fuel, exhaust, moving parts and batteries present hazards which
can result in severe personal injury or death. Read and adhere to all cautions
and warnings found in this manual to avoid personal injury.
CAUTION: Improper battery cable disconnection may cause accidental or remote starting
which may result in injury to the person servicing the generator set. Disconnect the
negative ( – ) battery cable at the battery to prevent starting while servicing the
generator set.
CAUTION: The generator set requires ample air flow to run without overheating. Keep the
generator set and its compartment clean and free from obstructions at all times.
CAUTION: Restricted air flow may cause a fire. Do not store oil, rags or other gear in the
generator set or generator set compartment to prevent starting a fire.
CAUTION: Operation of the generator set may loosen fasteners. Operating a generator set
with loose fasteners may cause damage to the generator set. Make sure all
fasteners are secured and torqued properly.
1.3 Automatic Generator Start Control Hazards
WARNING: Accidental starting can cause severe personal injury or death. Turn off the
AGS whenever performing maintenance or service, when the vehicle is
stored between uses, is awaiting service, or is parked in a garage or other
confined area.
Unexpected starting may occur if the generator set is equipped with an inverter-charge or other
Automatic Generator Start (AGS) control. This may cause exposure to:
· Unexpected generator starting.
· Moving parts hazards.
· Electric shock.
· Exhaust carbon monoxide (CO).
1.4 Generator Voltage is Deadly
WARNING: Imporperly connected generator electrical output connections can cause
equipment damage, severe personal injury, or death and therefore must be
made by a trained and experienced electrician in accordance with applicable
codes.
WARNING: Imporper installations can cause equipment damage, severe personal injury,
or death and therefore all installations must be conducted by a trained and
experienced person in accordance with the installation instructions and all
applicable codes.
2 A031C171 (Issue 1)
Page 7
06-2012 1. Important Safety Instructions
WARNING: When equipped with an integral or add-on Auto-matic Generator Starting
System (AGS) control, carbon monoxide exhaust inhalation (CO), electric
shock, and moving parts hazards are possible due to unexpected starting.
Turn off AGS whenever performing maintenance o rservice, when the vehicle
is stored between uses, is awaiting service, or is parked in a garage or other
confined area to avoid these hazards.
WARNING: Back feed to shore power can cause electrocution and damage to equipment.
The generator set must not be connected to shore power or to any other
source of electrical power. An approved switching device must be used to
prevent interconnections.
WARNING: Live electrical equipment can cause electricution. Use caution when working
on live electrical equipment. Remove jewelry, make sure clothing and shoes
are dry, stand on a dry wooden platform or rubber insulating mat, and use
tools with insulated handles.
1.5 Engine Exhaust is Deadly
WARNING: When equipped with an integral or add-on Auto-matic Generator Starting
System (AGS) control, carbon monoxide exhaust inhalation (CO), electric
shock, and moving parts hazards are possible due to unexpected starting.
Turn off AGS whenever performing maintenance o rservice, when the vehicle
is stored between uses, is awaiting service, or is parked in a garage or other
confined area to avoid these hazards.
WARNING: Carbon monoxide is a posionus gas. Inhalation of this gas can cause severe
personal injury or death. Adhere to the following bullet points to make sure
carbon monoxide is not being inhaled by occupants of the vehicle as well as
others working on or around the generator set.
· ·
Inspect for exhaust leaks at every startup and after every eight hours of
running.
· ·
Never occupy the vehicle while the generator set is running unless the
vehicle is equipped with a working carbon monoxide detector.
· ·
Never operate the generator set when the vehicle is in a confined space,
such as a garage, basement, or building of any kind.
· ·
Make sure the exhaust system is installed in accordance with the
generator set installation manual.
· ·
Never use engine cooling air for heating a working or living space
compartment.
Carbon monoxide poisioning symptoms include:
· headache
· dizziness
· weakness
· nausea
· vomiting
· chest pain
· confusion
· loss of consciousness
A031C171 (Issue 1) 3
Page 8
1. Important Safety Instructions 06-2012
1.6 Fuel is Flammable and Explosive
WARNING: Fuel and fuel vapor is highly explosive. Adhere to the following bullets to
avoid igniting fuel and fuel vapors.
··
Do not smoke or turn electrical switches on or off where fuel fumes are
present or in areas sharing ventilation with fuel tanks or equipment.
· ·
Keep flame, sparks, pilot lights, arc-producing equipment and all other
sources of ignition well away from fuel lines and sources.
· ·
Fuel lines must be secured, free of leaks and separated or shielded from
electrical wiring.
Leaks can lead to explosive accumulations of gas.
· Natural gas rises when released and can accumulate inside housings and buildings.
· LPG sinks when released and can accumulate inside housings and basements and other
below-grade spaces.
NOTE: Propane (LPG) is identifiable by the rotten egg smell it emits.
1.7 Battery Gas is Explosive
WARNING: Battery gas is highly explosive and may cause personal injury or death if
ignited. Take the proper precautions to avoid personal injury.
· ·
For personal safety, wear appropriate PPE when working on or around
the generator set.
· ·
To make sure battery gas is not ignited, do not smoke around the
generator set.
· ·
To reduce arcing when disconnecting or reconnecting battery cables,
always disconnect the negative ( -) battery cable first and reconnect it
last.
1.8 Moving Parts Can Cause Severe Personal Injury or
Death
WARNING: When equipped with an integral or add-on Auto-matic Generator Starting
System (AGS) control, carbon monoxide exhaust inhalation (CO), electric
shock, and moving parts hazards are possible due to unexpected starting.
Turn off AGS whenever performing maintenance o rservice, when the vehicle
is stored between uses, is awaiting service, or is parked in a garage or other
confined area to avoid these hazards.
WARNING: Moving parts can catch on loose items such as clothing or jewelry. Do not
wear loose clothing or jewelry near moving parts such as PTO (power take-
off) shafts, fans, belts, and pulleys.
WARNING: Moving parts can entangle appendages such as fingers. Keep the protective
guards in place over fans, belts, pulleys, and other moving parts and keep
hands away from all moving parts.
4 A031C171 (Issue 1)
Page 9
2 Introduction
WARNING: Imporperly connected generator electrical output connections can cause
equipment damage, severe personal injury, or death and therefore must be
made by a trained and experienced electrician in accordance with applicable
codes.
WARNING: Imporper installations can cause equipment damage, severe personal injury,
or death and therefore all installations must be conducted by a trained and
experienced person in accordance with the installation instructions and all
applicable codes.
2.1 About This Manual
This manual covers the operation and maintenance of the generator set or sets listed on the
front cover. Each operator should study this manual carefully and adhere to all instructions and
safety precautions therein. Keep this manual readily available for reference.
This manual provides the operator-level instructions necessary for operating the genset and
maintaining it at top performance.
WARNING: This generator set is not a life support system. It can stop without warning.
Children, persons with physical or mental limitations, and pets could suffer
personal injury or death. A personal attendant, redundant power or an alarm
system must be used if genset operation is critical.
2.2 Nameplate
Nameplate information is very useful in identifying a product. Have the model and serial
numbers available when contacting a Cummins/Onan dealer for parts, service or product
information.
A031C171 (Issue 1) 5
Page 10
2. Introduction 06-2012
FIGURE 1. NAMEPLATE LOCATION
2.3 Typical Genset
The control panel and the components requiring attention during periodic maintenance (see
Periodic Maintenance ) are located behind a removable access cover. See Figure 2.
Removing the access cover: Unlock the access cover, using a flat-end tool. Pull the access
cover down and out to remove the access cover.
Securing the access cover: Slide the access cover up and into the opening in the housing.
Hold the base of the cover flush with the housing. Use a flat-end tool to secure the access
cover.
6 A031C171 (Issue 1)
Page 11
06-2012 2. Introduction
WARNING: Operating the genset with the access cover off can result in severe personal
injury or equipment damage. Hot components are exposed when the access
cover is removed and genset cooling air does not circulate properly. Do not
operate the genset with the access cover removed.
The genset itself is usually located behind a door in a compartment somewhere around the
perimeter of the vehicle.
No. Description No. Description
1 Removable Access Cover 5 Control Panel
2 Muffler (inside cover) 6 Fuel Filter (gasoline models only)
3 Air Filter Cover 7 Oil Fill Cap and Dipstick
4 Oil Drain (bottom) 8 Spark Plug Access
FIGURE 2. TYPICAL GENSET
A031C171 (Issue 1) 7
Page 12
2. Introduction 06-2012
2.4 Fuel Recommendations
WARNING: Gasoline and LPG are highly flammable and explosive and can cause severe
personal injury or death. Do not smoke or turn electrical switches ON or OFF
where fuel fumes, tanks or equipment are present or in areas sharing
ventilation. Keep flames, sparks, pilot lights, arc-producing equipment and
switches and all other sources of ignition well away. Keep a type ABC fire
extinguisher in the vehicle.
2.4.1 Gasoline Models
Use clean, fresh unleaded gasoline having a minimum octane rating (Anti-Knock Index) of 87.
CAUTION: Do not use gasoline or gasoline additives containing methanol because methanol
can be corrosive to fuel system components.
Avoid using leaded gasoline because of the extra engine maintenance that will be
required.
2.4.2 LPG Models
Use clean, fresh HD-5 grade liquified petroleum gas (LPG) or equivalent product consisting of at
least 90 percent propane. Commercial liquified petroleum gas fuels may contain more than 2.5
percent butane which can result in poor fuel vaporization and poor engine starting in low
ambient temperatures (below 32 ° F (0 ° C).
Satisfactory performance on low-pressure LPG models requires that the LPG vapor be supplied
at a pressure within the range indicated in Specifications .
WARNING: High LPG supply pressure can cause gas leaks which can lead to fire and
severe personal injury or death. LPG supply pressure must be adjusted to
Specifications by trained and experienced personnel.
2.5 Engine Oil Recommendations
Use API (American Petroleum Institute) performance Class SJ , SH or SG engine oil, which may
be in combination with performance Class CH-4, CG-4 or CF-4 (for example: SJ/CH-4). Also
look for the SAE (Society of Automotive Engineers) viscosity grade. Referring to Table 1,
choose the viscosity grade appropriate for the ambient temperatures expected until the next
scheduled oil change.
Single-grade SAE 30 oil is preferable when temperatures are consistently above freezing.
Multigrade oils are better when wide temperature variations are expected.
The use of synthetic oils with recommended viscosity grade is acceptable. However, oil change
intervals found in Chapter 4 must still be followed.
TABLE 1. OIL VISCOSITY VS. TEMPERATURE
EXPECTED AMBIENT TEMPERATURES SAE VISCOSITY GRADE
32° F (0° C) and higher 30
10° F to 100° F (-12° C to 38° C) 15W-40 (OnaMaxTM)
0° F to 80° F (-18° C to 27° C) 10W-30 10W-40
8 A031C171 (Issue 1)
Page 13
06-2012 2. Introduction
EXPECTED AMBIENT TEMPERATURES SAE VISCOSITY GRADE
-20° F to 50° F (-28° C to 10° C) 5W-30
2.6 Starting Batteries
The genset has a 12 volt, direct current (DC) engine cranking and control system. See
Specifications regarding minimum battery ratings for reliable genset cranking, especially in cold
weather. Also see Periodic Maintenance Schedule and the battery manufacturer's instructions
regarding battery maintenance. Reliable genset starting and starter service life depend upon
adequate battery system capacity and proper maintenance.
2.7 Genset Control Panel
The genset control panel (Figure 3) is located behind the maintenance access cover on the
genset (Figure 2) and has the following features:
Control Switch - This switch is used to prime the fuel system, start and stop the genset and
display the fault code.
· START position - Hold the switch in this position to crank and start the genset.
· STOP/PRIME position - Press the switch to this position to stop the generator set.
· STOP/PRIME position - Hold the switch in this position to prime the fuel system (gasoline
models only).
Status Indicator Light - This light is an LED (light emitting diode) in the control switch that
blinks rapidly during cranking and stays on continuously when the genset is running. If the
genset shuts down abnormally, the light will blink a numerical code to indicate the cause of the
shutdown. See Troubleshooting about display fault codes.
Line Circuit Breaker - The line circuit breaker protects the AC power leads connected to the
genset from overloads and equipment short circuits.
A031C171 (Issue 1) 9
Page 14
2. Introduction 06-2012
No. Description No. Description
1 Status Indicator Light 3 AC Circuit Breaker
2 Control Switch
FIGURE 3. GENSET CONTROL PANEL
2.8 Remote Control Panel
The vehicle probably has a control panel inside the vehicle for remote control of the genset.
Onan offers three remote control kits as follows:
· Remote switch with status indicator light only (Figure 4).
· Remote switch with status indicator light and hour meter (Figure 5).
· Remote switch with status indicator light and DC voltmeter (Figure 6).
The hour meter records genset operating time in hours. It cannot be reset.
FIGURE 4. REMOTE SWITCH
The DC voltmeter indicates whether voltage across the 12 VDC control system and battery is
normal. If the indicator consistently stays above or below the normal zone, see MAINTAINING
THE BATTERY AND BATTERY CONNECTIONS.
10 A031C171 (Issue 1)
Page 15
06-2012 2. Introduction
FIGURE 5. REMOTE SWITCH / HOUR METER
FIGURE 6. REMOTE SWITCH / DC VOLTMETER
A031C171 (Issue 1) 11
Page 16
2. Introduction 06-2012
This page is intentionally blank.
12 A031C171 (Issue 1)
Page 17
3 Operation
WARNING: EXHAUST GAS IS DEADLY!
Exhaust gases contain carbon monoxide, an odorless, colorless gas. Carbon
monoxide is poisonous and can cause unconsciousness and death.
Symptoms of carbon monoxide poisoning include:
· ·
Dizziness
· ·
Muscular Twitching
· ·
Weakness and Sleepiness
· ·
Throbbing in Temples
· ·
Headache
· ·
Inability to Think Clearly
· ·
Nausea
· ·
Vomiting
IF YOU OR ANYONE ELSE EXPERIENCES ANY OF THESE SYMPTOMS, GET
OUT INTO THE FRESH AIR IMMEDIATELY. If symptoms persist, seek medical
attention. Shut down the genset and do not operate it until it has been
inspected and repaired.
Never occupy the vehicle with the genset running unless the vehicle is
equipped with a working carbon monoxide detector. Primary protection
against inhaling carbon monoxide, however, is proper installation of the
exhaust system, daily (every eight hour) inspection for visible and audible
exhaust system leaks.
3.1 Conducting the Pre-Start Checks
Before the first start of the day and after every eight hours of operation, inspect the genset as
instructed under CONDUCTING GENERAL INSPECTIONS. Keep a log of maintenance and the
hours run and perform any maintenance that may be due. See RETURNING THE GENSET TO
SERVICE if the vehicle has been in storage.
Before each start:
1. Make sure all vehicle CO detectors are working.
2. Check for signs of fuel and exhaust leaks and for damage to the exhaust system.
3. Turn off the air conditioner and other large appliances.
3.2 Priming Gasoline Fuel Systems
STOP/PRIME position - Hold the control switch in this position to prime the fuel system if the
generator set has run out of fuel (gasoline models only).
NOTE: The status indicator light will stay on while the pump is on.
A031C171 (Issue 1) 13
Page 18
3. Operation 06-2012
3.3 Starting the Genset
Park the vehicle so that genset exhaust gases disperse away from the vehicle. Barriers such as
walls, snow banks, high grass, brush and other vehicles can cause exhaust gases to
accumulate in and around the vehicle.
Do not operate power ventilators or exhaust fans while the vehicle is standing with the genset
running. The ventilator or fan can draw exhaust gases into the vehicle.
Check all CO monitors to assure proper operation.
WARNING: EXHAUST GAS IS DEADLY! Do not operate the genset if there is an exhaust
leak or any danger of exhaust gases entering or being drawn into the vehicle.
WARNING: Do not park the vehicle in high grass or brush. Contact with the exhaust
system can cause a fire.
After conducting the visual inspections and after having repaired any components that did not
pass inspeciton:
1. START position - Hold the switch in this position until the generator set starts.
· The status indicator light on the switch flashes while cranking. It will stay on
continuously when the generator set is running.
2. The generator set can be cranked for about 30 seconds. After this period, Fault Code 4
(over crank) will occur.
3. Wait 5 seconds for the control to reset before trying again. After five tries, let the starter
motor cool down for 30 seconds before trying again.
4. See Troubleshooting if the engine shuts down and the status indicator light blinks.
5. For top performance and engine life, especially in colder weather, let the engine warm up
for two minutes before connecting appliances.
6. Always secure the access cover after starting the genset at the genset control panel.
WARNING: Operating the genset with the access cover off can lead to severe burns and
engine damage due to overheating. Always secure the cover after starting the
genset.
3.4 Stopping the Genset
Turn off the air conditioner and other large appliances and let the genset run for two minutes to
cool down before stopping. This reduces backfiring and run-on. Then press the switch to STOP
to stop the genset.
3.5 Restarting the Genset
If the genset shuts down, disconnect or turn off as many appliances as possible and try
restarting the genset. Reconnect only as many appliances as will not overload the genset or
cause the circuit breaker to trip. See Section 3.7 for tripped circuit breaker resetting instrucitons.
14 A031C171 (Issue 1)
Page 19
06-2012 3. Operation
3.6 Loading the Genset
The genset can power AC motors, air conditioners, AC/DC converters and other appliances.
How much appliance load* can be powered depends upon the genset power rating. The genset
will shut down or its circuit breakers will trip if the sum of the loads exceeds genset power.
To avoid overloading the genset and causing shutdowns, compare the sum of the loads of the
appliances that are likely to be used at the same time with the power rating of the genset. Use
Table 2 or the ratings on the appliances themselves (if so marked) to obtain the individual
appliance loads. It may be necessary to run fewer appliances at the same time —the sum
of the loads must not be greater than genset rating.
Note that the genset may shut down due to overload —even though the sum of the loads is less
than genset rating —when a large motor or air conditioner is started last or cycles off and then
on again. The reason for this is that a motor's startup load is much larger than its running load.
It may be necessary to run fewer appliances when large motors and air conditioners are
cycling on and off.
TABLE 2. TYPICAL APPLIANCE LOADS
Appliance Load (watts)
Air Conditioner 1400-2000
Battery Charger Up to 3000
DC Converter 300-700
Refrigerator 600-1000
Microwave Oven 1000-1500
Electric Frying Pan or Wok 1000-1500
Electric Stove Element 350-1000
Electric Water Heater 1000-1500
Electric Iron 500-1200
Electric Hair Dryer 800-1500
Coffee Percolator 550-750
Television 200-600
Radio 50-200
Electric Drill 250-750
Electric Broom 200-500
Electric Blanket 50-200
Note also that air density decreases as altitude increases, causing generator set engine power
to decrease. Power decreases approximately 3.5% of rated power each 1000 feet (305 m) of
increase in elevation. See the following table for typical elevation/generator set power
calculations. It may be necessary to run fewer appliances at higher altitudes.
As ambient temperature increases, rated generator set engine power decreases approximately
1% for every 10 °F (5.5 °C) above 77 °F (25 °C). It may be necessary to run fewer appliances at
higher ambient temperatures.
A031C171 (Issue 1) 15
Page 20
3. Operation 06-2012
TABLE 3. POWER VS. ALTITUDE
Elevation above Mean Sea Level Maximum Genset Power
up to 500 feet (152 m) 2500/2800 watts (rated)
2500 ft (762 m) 2325/2600 watts
5500 ft (1676 m) 2060/2310 watts
2060/2310 watts minus 87.5/98 watts each 1000 ft (305
above 5500 ft (1676 m) m)
1. - This table does not take into account the effect circuit breakers may have in limiting maximum power.
1
* Appliance load and genset power are measured in terms of watts (W) or kilowatts (kW), where
1 kilowatt (kW) = 1000 watts (W).
3.7 Resetting Circuit Breakers
If a circuit breaker in the main power distribution panel of the vehicle or on the genset (Figure 7)
trips, either a circuit shorted or too many appliances were running. Note that the genset may
continue to run after a circuit breaker trips.
If a circuit breaker trips, disconnect or turn off as many loads as possible and reset the circuit
breaker. (Push the circuit breaker to OFF to reset it and then to ON to reconnect the circuit.) If
the circuit breaker trips right away, either the electrical distribution system has a short circuit or
the circuit breaker is faulty. Contact your local Cummins Onan dealer or distributor for generator
service.
If the circuit breaker does not trip, reconnect the appliances, one by one, up to a total load that
does not overload the genset or cause the circuit breaker to trip. If a circuit breaker trips right
away when an appliance is connected, the appliance probably has a short.
Electrical appliances and tools must be used and maintained properly and be properly grounded
to cause the line circuit breakers to trip when short circuits occur.
WARNING: Short circuits in electrical appliances and tools can cause fire and electrical
shock leading to severe personal injury or death. Read and follow the
equipment and tool manufacturer's instructions and warnings regarding use,
maintenance and proper grounding.
16 A031C171 (Issue 1)
Page 21
06-2012 3. Operation
FIGURE 7. AC CIRCUIT BREAKER
3.8 Connecting Shore Power
A vehicle with provisions for connecting utility power must have an approved device to keep the
genset and utility from being interconnected. See the genset Installation Manual for more
information.
WARNING: Backfeed to shore power can cause electric shock resulting in severe
personal injury or death and damage to equipment. The vehicle must have an
approved device to prevent the genset from being interconnected with shore
power.
3.9 Operating in Cold Weather
Pay particular attention to the following items when operating the genset in cold weather:
1. Make sure engine oil viscosity is appropriate for the ambient temperatures. Change oil if
there is a sudden drop in temperature. See ENGINE OIL RECOMMENDATIONS.
2. Perform spark plug maintenance (See REPLACING THE SPARK PLUG).
3. Perform battery maintenance (See MAINTAINING THE BATTERY AND BATTERY
CONNECTIONS).
A031C171 (Issue 1) 17
Page 22
3. Operation 06-2012
3.10 Operating in Hot Weather
Pay particular attention to the following items when operating the genset in hot weather:
1. Make sure nothing blocks airflow to and from the genset.
2. Make sure engine oil viscosity is appropriate for the ambient temperatures. See ENGINE
OIL RECOMMENDATIONS.
3. Keep the genset clean.
4. Perform maintenance due. See PERIODIC MAINTENANCE SCHEDULE.
3.11 Operating in Dusty Environments
Pay particular attention to the following items when operating the genset in dusty environments:
1. Do not let dirt and debris accumulate inside the genset compartment. Keep the genset
clean.
2. Perform air cleaner maintenance more often (See REPLACING THE AIR FILTER
ELEMENT).
3. Keep containers of engine oil that have been opened tightly closed to keep out dust.
3.12 Operating at a High Altitude
When operating a gasoline generator set at altitudes greater than 7500 ft, it is recommended to
install a high altitude kit (A042V579) to avoid performance degradation. Liquid Propane
generator sets are self-compensating and do not require adjustment.
3.13 Breaking in a New Engine
Proper engine break-in on a new genset or on one with a rebuilt engine is essential for top
engine performance and acceptable oil consumption. Run the genset at approximately 1/2 rated
power for the first 2 hours and then at 3/4 rated power for 2 more hours. See LOADING THE
GENSET.
Proper engine oil and oil level are especially critical during break-in because of the higher
engine temperatures that can be expected. Change the oil if not appropriate for the ambient
temperatures during break-in. See ENGINE OIL RECOMMENDATIONS. Check oil level twice a
day or every 4 hours during the first 20 hours of operation and change the oil after the first 20
hours of operation.
The use of synthetic oils with recommended viscosity grade is acceptable. However, oil change
intervals found in Chapter 4 must still be followed.
3.14 Exercising the Genset
Exercise the generator set approximately 45-60 minutes each month if use is infrequent. Run
the genset at approximately 1/2 rated power. See LOADING THE GENSET. A single two hour
exercise period is better than several shorter periods.
18 A031C171 (Issue 1)
Page 23
06-2012 3. Operation
Exercising a genset drives off moisture, re-lubricates the engine, replaces stale fuel in fuel lines
and carburetor and removes oxides from electrical contacts and generator slip rings. The result
is better starting, more reliable operation and longer engine life.
3.15 Storing the Genset
Proper storage is essential for preserving top genset performance and reliability when the
genset cannot be exercised regularly and will be idle for more than 120 days.
3.15.1 Gasoline Models
WARNING: Gasoline preservatives (stabilizers) are toxic. Follow the instructions on the
container label. Avoid skin contact. Wash hands with soap and water after
dispensing the fluid.
1. Fill the fuel tank with fresh fuel and add a fuel preservative (OnaFresh TM ), following the
instructions on the container label.
NOTE: Unless a preservative (stabilizer) is added, the gasoline in the fuel system
will deteriorate causing fuel system corrosion, gum formation and varnish-
like deposits which can lead to hard starting and rough operation.
2. Then run the genset for about 45-60 minutes at approximately 1/2 rated power to fill the
fuel lines with the fresh fuel and preservative.
3.15.2 Liquid Propane Models
Check the local ordinances if the vehicle is to be garaged.
NOTE: Local ordinances typically require that:
· · the LP system be leak-free
· · the LP container not be filled beyond specified limits
· · the container shutoff valve be closed
· · the vehicle not be parked near sources of heat or ignition.
3.15.3 Storing the Genset
1. Change the engine oil (See ) and attach a tag indicating grade of oil viscosity (See
ENGINE OIL RECOMMENDATIONS).
2. For long term storage only: Remove the air filter and restart the genset. While the genset
is running, spray an engine fogger (OnaGard TM ) into the carburetor, following the
instructions on the container label, and then stop the genset. The fogger leaves a
protective coat of oil on the internal surfaces of the engine.
3. Disconnect the battery cables, negative (-) cable first, from the starting battery and store
the battery according to the battery manufacturer's recommendations (See MAINTAINING
THE BATTERY AND BATTERY CONNECTIONS).
4. Cap the exhaust tail pipe to keep out dirt, moisture, rodents and other foreign materials.
5. Close the fuel supply valve (if so equipped).
6. Turn OFF the AC circuit breaker (See RESETTING CIRCUIT BREAKERS ).
A031C171 (Issue 1) 19
Page 24
3. Operation 06-2012
WARNING: Do not open the carburetor drain when the engine is hot. Close the drain
immediately after draining. Failure to heed this warning can lead to fire
resulting in severe personal injury or death.
7. Draining the carburetor float bowl prevents deposits of gum from clogging the tiny
passages in the carburetor as the gasoline in the bowl evaporates during storage. If the
carburetor has a drain (see the following figure), drain it as follows:
a. Let the engine cool down thoroughly.
b. Place paper towels under the drain to absorb all of the drainage (less than 1/2 cup).
c. Open the drain valve by turning counter-clockwise with a screwdriver.
d. Immediately close the drain valve after draining by turning clockwise with a
screwdriver until just snug.
No. Description
1 Carburator drain valve
FIGURE 8. CARBURETOR DRAIN VALVE
3.15.4 Returning The Genset to Service
1. Check the oil tag on the genset and change the oil if the viscosity indicated is not
appropriate for the temperatures expected. See ENGINE OIL RECOMMENDATIONS.
2. Reconnect the starting battery (negative [-] cable last). See MAINTAINING BATTERY AND
BATTERY CONNECTIONS.
20 A031C171 (Issue 1)
Page 25
06-2012 3. Operation
3. Remove the cap from the exhaust tailpipe.
4. Change the air filter element if it is dirty.
5. Open the fuel supply valve (if so equipped).
6. Inspect the genset. See CONDUCTING GENERAL INSPECTIONS.
7. Gasoline Models - Prime the genset fuel system by holding the control switch at
STOP/PRIME for 30 seconds. (The status indicator light will stay on solid while the pump is
on.)
8. Start the genset. There may be smoke and rough operation for a few minutes until the oil
from the fogger burns off. If the engine does not start, clean or replace the spark plug,
which may have been fouled by the fogger.
9. Turn on the AC circuit breaker ON (See RESETTING CIRCUIT BREAKERS) when the
genset is ready to power appliances.
A031C171 (Issue 1) 21
Page 26
3. Operation 06-2012
This page is intentionally blank.
22 A031C171 (Issue 1)
Page 27
4 Periodic Maintenance
Periodic maintenance is essential for top performance and long genset life. Use Table 4 as a
guide for normal periodic maintenance. In hot and dusty environments some maintenance
procedures should be performed more frequently, as indicated by the footnotes in the table.
Keeping a log of maintenance performed and hours run will help you keep genset maintenance
regular and provide a basis for supporting warranty claims (See MAINTENANCE RECORD).
Maintenance, replacement or repair of emission control devices and systems may be performed
by any engine repair establishment or individual. However, warranty work must be completed by
an authorized Onan dealer.
TABLE 4. PERIODIC MAINTENANCE SCHEDULE
MAINTENANCE FREQUENCY
MAINTENANCE PROCEDURE
General Inspections X
Check Engine Oil Level X
Clean and Check Battery X
Clean Spark Arrestor X
Change Engine Oil X
Replace Air Filter Element X
Clean Engine Cooling Fins X
Replace Spark Plug X
Replace Fuel Filter X
Adjust Valve Lash X
1 - As a part of engine break-in, change the engine oil after the first 20 hours of operation.
2 - Perform more often when operating in dusty environments.
3 - Perform more often when operating in hot weather.
4 - Perform at least once a year.
5 - Perform sooner if engine performance deteriorates.
6 - Must be performed by a qualified mechanic (authorized Onan dealer).
Every Ever
Day or Every Every 50 y 450
Every 8 Month Hours Hour
Hours s
After Every
First 20 150 Page
Hours Hours
3
1
X
2, 3, 4
2
2
5
5
6
-
-
-
4.1 Conducting General inspections
Inspect the genset before the first start of the day and after every eight hours of operation.
4.1.1 Oil Level
Check engine oil level (CHECKING ENGINE OIL LEVEL).
4.1.2 Exhaust System
Look and listen for exhaust system leaks while the genset is running. Shut down the genset if a
leak is found and have it repaired before operating the genset again.
A031C171 (Issue 1) 23
Page 28
4. Periodic Maintenance 06-2012
Replace dented, bent or severely rusted sections of the tailpipe and make sure the tailpipe
extends at least 1 inch (25.4 mm) beyond the perimeter of the vehicle.
Look for openings or holes between the genset compartment and vehicle cab or living space if
the genset engine sounds louder than usual. Have all such openings or holes closed off or
sealed to prevent exhaust gases from entering the vehicle.
4.1.3 Fuel System
Check for leaks at the hose, tube and pipe fittings in the fuel supply system while the genset is
running and while it is stopped. Check flexible fuel hose sections for cuts, cracks, and
abrasions. Make sure the fuel line is not rubbing against other parts. Replace worn or damaged
fuel line parts before leaks occur.
WARNING: Gasoline and LPG are highly flammable and explosive and can cause severe
personal injury or death. Repair leaks right away.
4.1.3.1 Special Considerations for LPG Fuel Systems
· Never use a flame to check for LPG leaks.
· If you smell gas, close the LPG container shutoff valve and have the genset serviced
before using it again.
4.1.4 Battery Connections
Check the battery terminals for clean, tight connections. Loose or corroded connections have
high electrical resistance which makes starting harder. See MAINTAINING THE BATTERY AND
BATTERY CONNECTIONS.
WARNING: Arcing at battery terminals or light switch or other equipment or flames and
sparks can ignite battery gas causing severe personal injury —Ventilate
battery area before working on or near battery —Wear safety glasses —Do not
smoke —Switch trouble light ON / OFF away from battery —Do not disconnect
battery cables while genset is running or vehicle battery charging system is
on —Always disconnect negative (-) cable first and reconnect it last.
4.1.5 Mechanical
Look for mechanical damage and listen for unusual noises and vibrations. Check the genset
mounting bolts.
Check to see that the genset air inlet and outlet openings are not clogged with debris or
blocked.
Clean accumulated dust and dirt from the genset. Do not clean the genset while it is running or
still hot. Protect the generator, air cleaner, control panel, and electrical connections from water,
soap and cleaning solvents.
WARNING: Always wear safety glasses when using compressed air, a pressure washer
or a steam cleaner to avoid severe eye injury.
4.2 Checking Engine Oil Level
Park the vehicle on level ground and stop the genset before checking engine oil level.
24 A031C171 (Issue 1)
Page 29
06-2012 4. Periodic Maintenance
WARNING: Crankcase pressure can blow hot engine oil out the fill opening causing
severe burns. Always stop the genset before removing the oil fill cap.
1. Unscrew the oil fill cap and wipe oil off the dipstick. Reinsert without screwing in
the dipstick. Remove the dipstick again and check the oil level on the dip stick.
2. Add or drain oil as necessary. See ENGINE OIL RECOMMENDATIONS. Keep the oil level
between the FULL and ADD marks.
CAUTION: Too much oil can cause high oil consumption. Too little oil can cause severe
engine damage. Keep the oil level between the FULL and ADD marks.
3. Screw the oil fill cap back on securely.
No. Description No. Description
1 Full 2 Add 300 ml (10 oz)
4.3 Changing Engine Oil
WARNING: State and federal agencies have determined that contact with used engine oil
can cause cancer or reproductive toxicity. Try to avoid skin contact and
breathing of vapors. Use rubber gloves and wash exposed skin.
Refer to Table 4 for scheduled engine oil change. Change oil more often in hot or dusty
environments.
1. Run the engine until warm, stop it and remove the oil fill cap.
2. Place a pan underneath the oil drain plug and remove the plug with a 9/16 inch socket. Let
all oil drain from the engine and then secure the drain plug . If you have a torque wrench,
tighten plug to 5-10 ft-lbs.
3. Refill with 0.6L/0.63qt/20 oz of oil. See ENGINE OIL RECOMMENDATIONS. Check the oil
level and add or drain oil as necessary.
A031C171 (Issue 1) 25
Page 30
4. Periodic Maintenance 06-2012
4. Screw the oil fill cap on securely.
5. Dispose of the used oil and oil filter in accordance with local environmental regulations.
FIGURE 9. OIL DRAIN PLUG
4.4 Replacing the Air Filter Element
Refer to Table 4 for scheduled air filter element replacement. Under dusty operating conditions,
inspect and change more often. To change the air filter element, unlatch the filter cover from the
base and slide out the cover and filter together. Install a new filter into the cover and slide the
cover back into position, ensuring that the two tabs at the rear of the cover are inserted into
slots in the base and the latch is engaged.
FIGURE 10. AIR FILTER ELEMENT
No. Description No. Description
1 Filter Cover 2 Air Filter
4.5 Replacing the Spark Plug
Refer to Table 4 for scheduled spark plug replacement. (The genset has one spark plug.) The
spark plug must be in good condition for proper engine starting and performance. A spark plug
that fouls frequently or has heavy soot deposits indicates that the engine needs service. See
Troubleshooting .
· Spark Plug gap: 0.6-0.7mm (0.024-0.028")
26 A031C171 (Issue 1)
Page 31
06-2012 4. Periodic Maintenance
· Spark plug replacement part: NGK BR6HS
Always thread the spark plug in by hand until it seats, to prevent crossthreading, and then
torque to 13 lbs-ft (17 N-m). If you don't have a torque wrench, turn the spark plug an additional
1/4 turn, if being reused, or 3/8 to 1/2 turns if new.
FIGURE 11. SPARK PLUG
4.6 Cleaning the Spark Arrestor
Refer to Table 4 for scheduled cleaning of the spark arrestor muffler (which meets U.S. Forest
Service requirements). Cleaning is required for maximum genset performance.
· Spark plug gap — 0.6-0.7mm (0.024 - 0.028 inches)
· Spark plug replacement part — NGK BR6HS
WARNING: A hot muffler can cause severe burns. Let the muffler cool down before
removing the spark arrestor screen.
The spark arrestor screen is mounted inside the muffler outlet. Clean as follows:
1. Remove the 2 bolts that secure the tailpipe to the muffler (inside the genset housing) and
move the tailpipe aside.
2. Turn the spark arrestor tube flange slightly clockwise and pull to remove from the muffler.
3. Inspect the screen inside for damage and clogging. Replace if damaged.
4. Lightly tap the spark arrestor and remove any remaining deposits with a wire brush. Use a
commercial solvent to loosen hard deposits. (Carefully follow the solvent manufacturer's
instructions and safety precautions.)
5. Reinstall the spark arrestor and tailpipe, making sure that the two gaskets are installed
correctly.
A031C171 (Issue 1) 27
Page 32
4. Periodic Maintenance 06-2012
FIGURE 12. SPARK ARRESTOR
4.7 Replacing the Fuel Filter
Refer to Table 4 for scheduled replacement of the fuel filter (gasoline models only).
Take care to spill as little fuel as possible when disconnecting the filter from the fuel line. Let the
engine cool down before disconnecting the fuel line so that it cannot ignite any fuel that is
spilled. The filter is removable by loosening the hose clamps shown.
WARNING: Gasoline is highly flammable and can cause severe personal injury or death--
Let the engine cool and close any fuel line shutoff valve before
disconnecting the fuel line from the filter--Do not smoke or turn electrical
switches ON or OFF where fuel fumes, tanks or equipment are present or in
areas sharing ventilation. Keep flame, sparks, pilot lights, arc-producing
equipment and switches and all other sources of ignition well away. Keep a
type ABC fire extinguisher in the vehicle.
28 A031C171 (Issue 1)
Page 33
06-2012 4. Periodic Maintenance
No. Description No. Description
1 Fuel filter 2 Clamps
FIGURE 13. FUEL FILTER
4.8 Maintaining Battery and Battery Connections
WARNING: Arcing at battery terminals or light switch or other equipment or flames and
sparks can ignite battery gas causing severe personal injury —Ventilate
battery area before working on or near battery —Wear safety glasses —Do not
smoke —Switch trouble light ON / OFF away from battery —Do not disconnect
battery cables while genset is running or vehicle battery charging system is
on —Always disconnect negative (-) cable first and reconnect it last.
Refer to Table 4 for scheduled battery maintenance, referring to the battery manufacturer's
instructions. Have the battery charging system serviced if DC system voltage is consistently low
or high. Always:
1. Keep the battery case and terminals clean and dry and the terminals tight.
2. Remove battery cables with a battery terminal puller.
3. Make sure which terminal is positive ( + ) and which is negative ( - ) before making battery
connections, always removing the negative ( - ) cable first and reconnecting it last to reduce
arcing.
NOTE: RV house batteries are typically used for starting the genset.
A031C171 (Issue 1) 29
Page 34
4. Periodic Maintenance 06-2012
This page is intentionally blank.
30 A031C171 (Issue 1)
Page 35
5 Troubleshooting
WARNING: Hot engine parts can cause severe burns. Always allow the engine time to
cool before performing any maintenance or service.
Table 5 lists the Fault Codes in numerical order along with step-by-step corrective action. If you
fail to resolve the problem after taking the corrective actions suggested, contact an authorized
Onan dealer. See How to Obtain Service.
First note the following:
· Maintaining engine oil level, keeping battery connections clean and tight, watching the fuel
gauge, not overloading the genset, etc. will prevent most shutdowns.
· When the genset and vehicle engine share a common fuel tank the fuel pickup tubes are
usually arranged so that the genset will run out of fuel first. Marking the genset empty point
on the fuel gauge will make it easier to tell when to stop the genset before running it out of
fuel.
5.1 Fault Codes
The genset controller provides extensive diagnostics by causing the status indicator light on the
Control Switch to blink in a numeric code. Following a fault shutdown, the indicator light will
repeatedly blink 3 blinks or 4 blinks at a time.
· Three blinks indicates a service fault. Press Stop once to cause the two-digit, second-
level fault code to blink. (Pressing Stop again will stop the blinking.) The two-digit code
consists of 1, 2, 3, or 4 blinks, a brief pause, and then 1 to 9 blinks. The first set of blinks
represents the tens digit and the second set of blinks the units digit of the fault code
number. For example, Fault Code No. 36 appears as:
blink-blink-blink — pause —blink-blink-blink-blink-blink-blink — long pause — repeat
· Four blinks indicates that cranking exceeded 15 to 20 seconds without the engine
starting.
· Note: Fault Code Nos. 3 and 4 are first level faults. Avoid interpreting them as
second-level Fault Code Nos. 33 and 44, which have not been assigned as fault
codes.
Restoring Fault Code Blinking - The fault code stops blinking after five minutes. Press Stop
three times within five seconds to restore blinking. Note that the last fault logged will blink,
even after the condition that caused the shutdown has been corrected.
TABLE 5. TROUBLESHOOTING
WARNING: Some genset service procedures present hazards that can result in severe personal
injury or death. Only trained and experienced service personnel with knowledge of
fuels, electricity, and machinery hazards should perform genset service. See Safety
Precautions.
STATUS INDICATOR LIGHT DEAD
(Faulty connections, no battery voltage)
A031C171 (Issue 1) 31
Page 36
5. Troubleshooting 06-2012
WARNING: Some genset service procedures present hazards that can result in severe personal
injury or death. Only trained and experienced service personnel with knowledge of
fuels, electricity, and machinery hazards should perform genset service. See Safety
Precautions.
Corrective Action:
1. Try the genset Start Switch if the remote Start Switch does not work, and vice versa.
2. Clean and tighten the positive ( + ) and negative ( - ) battery cable connections at the battery, vehicle frame and
genset.
3. Recharge or replace the battery. Refer to the battery manufacturer's recommendations.
STARTING BATTERIES RUN DOWN
(Marginal batteries, connections, or charging system or, parasitic loads)
Corrective Action:
1. Clean and tighten the positive ( + ) and negative ( - ) battery cable connections at the battery, vehicle frame and
genset.
2. Recharge or replace the battery. Refer to the battery manufacturer's recommendations.
3. Have a battery charging system installed or serviced in the vehicle.
STARTER ENGAGES-DISENGAGES
(Cranking voltage dips below 6 volts —low battery charge, poor connections, long cables)
Corrective Action:
1. Have the vehicle propulsion engine running while trying to start the genset —the battery charging alternator may
be able to maintain starting voltage high enough to get the genset started.
2. Clean and tighten the positive ( + ) and negative ( - ) battery cable connections at the battery, vehicle frame and
genset.
3. Recharge or replace the battery. Refer to the battery manufacturer's recommendations.
4. Increase battery cable size or run parallel cables.
STATUS INDICATOR LIGHT GOES OUT WHILE CRANKING--NO START
(Internal short circuit caused automatic-reset circuit protective device to trip)
Corrective Action: Try starting again. See an authorized Onan dealer if the status indicator light flashes and then
goes out again without the engine starting.
NO POWER —GENSET RUNNING, STATUS LIGHT ON
(Line circuit breaker OFF, or tripped due to short circuit or overload)
Corrective Action:
1. Turn on or reset the line circuit breaker on the genset.
2. Turn on or reset the line circuit breakers on the main distribution panel in the vehicle.
SERVICE CHECK FAULT —CODE NO. 3
(First-level fault code —Indicates fault with second-level fault code)
Corrective Action: Check the second-level fault code by pressing STOP once. The second-level fault code will have
two-digits. The faults are listed in numerical order in this table.
OVERCRANK FAULT —CODE NO. 4
(First-level fault code —Cranking exceeded 30 seconds without engine starting)
32 A031C171 (Issue 1)
Page 37
06-2012 5. Troubleshooting
WARNING: Some genset service procedures present hazards that can result in severe personal
injury or death. Only trained and experienced service personnel with knowledge of
fuels, electricity, and machinery hazards should perform genset service. See Safety
Precautions.
Corrective Action:
1. Gasoline Models - Check and fill the fuel tank, as necessary. (Note: The genset fuel pickup tube is probably
higher up in the fuel tank than the vehicle engine pickup.)
2. Prime the engine fuel system by holding the control switch at Stop/Prime for 30 seconds.
3. LPG Models - Check and fill the LPG container, as necessary. On cold days the LPG container may have to be
kept at least half full to provide the rate of vaporization necessary to keep up with the genset fuel demand.
4. Open any closed fuel valves.
5. Secure the spark plug lead on the spark plug.
6. Replace the spark plug.
7. Service the air cleaner.
OVERVOLTAGE FAULT —CODE NO. 12
(Controller unable to maintain rated voltage)
Corrective Action: See an authorized Onan dealer.
UNDERVOLTAGE FAULT —CODE NO. 13
(Controller unable to maintain rated voltage)
Corrective Action: Reduce the number of connected appliances, especially when air conditioners and battery
chargers are running.
OVERFREQUENCY FAULT —CODE NO. 14
(Engine governor unable to maintain rated frequency)
Corrective Action: See an authorized Onan dealer.
UNDERFREQUENCY FAULT —CODE NO. 15
(Engine governor unable to maintain rated frequency)
Corrective Action: Reduce the number of connected appliances, especially when air conditioners and battery
chargers are running.
VOLTAGE SENSE FAULT —CODE NO. 27
(Controller unable to sense output voltage)
Corrective Action: See an authorized Onan dealer.
HIGH BATTERY VOLTAGE FAULT —CODE NO. 29
(Voltage across battery system greater than 19 volts)
Corrective Action:
1. Check battery bank connections and reconnect if necessary so that the 12 volt batteries serving the genset are
connected in parallel (12 volt) rather than in series (24 volt).
2. Select a lower battery boost charge rate.
LOW CRANKING SPEED FAULT —CODE NO. 32
(Cranking speed less than 180 rpm for more than 2 seconds)
Corrective Action:
1. Clean and tighten the positive ( + ) and negative ( - ) battery cable connections at the battery and at the genset.
2. Recharge or replace the battery. Refer to the battery manufacturer's recommendations.
3. Replace engine oil with oil of proper viscosity for ambient temperatures. (High oil viscosity can slow down
cranking speed.)
A031C171 (Issue 1) 33
Page 38
5. Troubleshooting 06-2012
WARNING: Some genset service procedures present hazards that can result in severe personal
injury or death. Only trained and experienced service personnel with knowledge of
fuels, electricity, and machinery hazards should perform genset service. See Safety
Precautions.
CONTROL CARD FAILURE FAULT—CODE NO. 35
(Microprocessor EEPROM error during self-test)
Corrective Action: See an authorized Onan dealer.
ENGINE STOPPED FAULT —CODE NO. 36
(Engine stopped without command by controller)
Corrective Action:
1. Gasoline Models - Check and fill the fuel tank, as necessary. (Note: The genset fuel pickup tube is probably
higher up in the fuel tank than the vehicle engine pickup.)
2. LPG Models - Check and fill the LPG container, as necessary. On cold days the LPG container may have to be
kept at least half full to provide the rate of vaporization necessary to keep up with the genset fuel demand.
3. Secure the spark plug lead on the spark plug.
4. Replace the spark plug.
5. Service the air cleaner.
6. Check for mechanical damage.
INVALID GENSET CONFIGURATION FAULT —CODE NO. 37
(Genset configuration is preprogrammed at the factory)
Corrective Action: See an authorized Onan dealer.
OVERCURRENT FAULT —CODE NO. 38
(Low power factor loads)
Corrective Action:
1. Reduce the number of appliances running at the same time, especially those with high motor starting loads such
as air conditioners.
2. Have air conditioners and other appliances checked for proper operation. (A locked compressor rotor can cause
very low power factor.)
GENERATOR ROTOR FAULT —CODE NO. 41
(Controller unable to sense field or output voltage)
Corrective Action: See an authorized Onan dealer.
PROCESSOR FAULT —CODE NO. 42
(Microprocessor ROM error during self-test)
Corrective Action: See an authorized Onan dealer.
PROCESSOR FAULT —CODE NO. 43
(Microprocessor RAM error during self-test)
Corrective Action: See an authorized Onan dealer.
SPEED SENSE FAULT —CODE NO. 45
(Controller unable to sense quadrature frequency)
Corrective Action: See an authorized Onan dealer.
IGNITION FAULT —CODE NO. 47
(Controller unable to sense ignition)
Corrective Action: See an authorized Onan dealer.
GENERATOR FIELD SENSE FAULT—CODE NO. 48
(Controller unable to sense field voltage)
34 A031C171 (Issue 1)
Page 39
06-2012 5. Troubleshooting
WARNING: Some genset service procedures present hazards that can result in severe personal
injury or death. Only trained and experienced service personnel with knowledge of
fuels, electricity, and machinery hazards should perform genset service. See Safety
Precautions.
Corrective Action: See an authorized Onan dealer.
A031C171 (Issue 1) 35
Page 40
5. Troubleshooting 06-2012
This page is intentionally blank.
36 A031C171 (Issue 1)
Page 41
6 Specifications
GASOLINE MODELS LPG MODELS
2.8HGJBB 2.3HGJBB 2.8HGJBB 2.5HGJBB 2.0HGJBB
GENERATOR: 2-Pole Revolving Field, Self-Excited, Electronically Regulated, 1-Phase, Direct Drive
Power (W) 2800 2300 2800 2500 2000
Frequency
(Hz)
Voltage
(Volts)
Current
(Amps)
Breaker
(Amps)
Speed (RPM) 3600 3000 3600 3600 3000
ENGINE: 1-Cylinder, 4-Cyle, Spark Ignited, OHC, Air-Cooled
Bore mm (in) 67 (2.64)
Stroke mm
(in)
Displacement
mm (in)
Compression
Ratio
Lube Oil Cap
L (qt)
Int Valve
Clearance- 0.12-0.15 (0.0047-0.0059)
Cold mm (in)
Exh Valve
Clearance- 0.12-0.15 (0.0047-0.0059)
Cold mm (in)
Spark Plug
Gap mm (in)
Ignition
Timing
Ignition Coil
Gap mm (in)
Compression
kgf/cm^2 3.9 (55.47) @ 500 rpm
(lbf/in^2)
DC SYSTEM: 12 volts, 360 amps minimum CCA battery
LPG Vapor
Supply 9 to 13 inch (229 to 330 mm) W.C.
Pressure (water column)
(Range)
60* 50 60* 60* 50
120 230 100 120 230
23.3 10 28 20.8 8.7
25 10 30 25 10
60 (2.36)
217 (13.2)
8.5:1
0.6 (0.63)
0.6-0.7 (0.024-0.028)
BTDC 23°
0.3-0.7 (0.012-0.020)
n/a
A031C171 (Issue 1) 37
Page 42
6. Specifications 06-2012
GASOLINE MODELS LPG MODELS
2.8HGJBB 2.3HGJBB 2.8HGJBB 2.5HGJBB 2.0HGJBB
Fuel
Consumption
-No Load L/h
(gal/h)
Fuel
Consumption
-50% Load
L/h (gal/h)
Fuel
Consumption
-Full Load
L/h (gal/h)
Sound Level
(dBA @ 3m 70
half load)
Weight - dry
lb (kg)
Length mm
(in)
Width mm
(in)
Height mm
(in)
* 60 Hz models are listed by CSA and the US Testing Company
0.78 (0.20) 0.69 (0.18) 0.78 (0.20) 0.53 (1.17) 0.43 (0.94)
1.32 (0.35) 1.18 (0.31) 1.32 (0.35) 0.76 (1.66) 0.60 (1.33)
1.75 (0.46) 1.56 (0.41) 1.75 (0.46) 1.02 (2.25) 0.82 (1.80)
57 (125)
560 (22.0)
415 (16.3)
325 (12.8)
38 A031C171 (Issue 1)
Page 43
7 Information for California Genset
Users
This genset meets the requirements of California's Exhaust Emissions Standards as stated on
the nameplate. Figure 1 illustrates where this information appears on the nameplate.
As a California user of this genset, please be aware that unauthorized modifications or
replacement of fuel, exhaust, air intake, or speed control system components that affect engine
emissions are prohibited. Unauthorized modification, removal or replacement of the genset label
is prohibited.
You should carefully review Operator (Owner), Installation and other manuals and information
you receive with your genset. If you are unsure that the installation, use, maintenance or service
of your genset is authorized, you should seek assistance from an approved Onan dealer.
California genset users may use Table 6 as an aid in locating information related to the
California Air Resources Board requirements for emissions control.
WARNING: The engine exhaust from this product contains chemicals known to the state
of California to cause cancer, birth defects or other reproductive harm.
TABLE 6. EMISSIONS CONTROL INFORMATION
Genset Warranty Information same packet of information as this manual when the genset is shipped
Engine Valve Lash See Specifications.
Engine Ignition Timing See Specifications.
Engine Fuel Requirements
Engine Lubricating Oil Requirements See ENGINE OIL RECOMMENDATIONS.
Engine Fuel Mixture Settings
Engine Adjustments None.
Engine Emission Control System
Air Index
To show compliance with California emission regulations, a hangtag has been provided
displayng the Air Index level and durability period of this engine.
The Air Index level defines how clean an engine's exhaust is over a period of time. A bar graph
scaled from "0" (most clean) to "10" (least clean) is used to show an engine's Air Index level. A
lower Air Index level represents cleaner exhuast from an engine.
The California emissions control warranty statement is located in the
from the factory.
Gasoline Models: The engine is certified to operate on unleaded
gasoline. See Fuel Recommendations.
LPG Models: The engine is certified to operate on LPG. See Fuel
Recommendations.
These genset engines have precision-manufactured carburetors which
are not adjustable.
The engine emissions control system consists of inherent engine
design.
The period of time (in hours) that the Air Index level is measured is known as the durability
period. Depending on the size of the engine, a selection of time periods can be used to
measure the Air Index level (see below).
A031C171 (Issue 1) 39
Page 44
7. Information for California Genset Users 06-2012
TABLE 7. AIR INDEX - DESCRIPTIVE TERMS
Descriptive Term Applicable to Emissions Durability Period
Moderate 50 hours (engine from 0-80 cc)
125 hours (engine greater than 80 cc)
Intermediate 125 hours (engine from 0-80 cc)
250 hours (engine greater than 80 cc)
Extended 300 hours (engine from 0-80 cc)
500 hours (engine greater than 80 cc)
1000 hours (225 cc and greater)
This hangtag must remain on this engine or piece of equipment, and only be removed by the ultimate purchaser
before operation.
NOTE: Federal Emissions Component Defect Warranty and California Emissions
Control Warranty are applicable to only those engines/generators compiled
with EPA (Environmental Protection Agency) and CARB (California Air
Resources Board) emission regulations in the U.S.A.
NOTE: To the engines/generators exported to and used in the countries other than
the U.S.A., warranty service shall be performed by the distributor in each
country in accordance with the standard Robin engin/generator warranty
policy as applicable.
40 A031C171 (Issue 1)
Page 45
8 How to Obtain Service
When you need service, parts, or product literature (such as the Service Manual) for your
genset, contact the nearest authorized distributor. Onan has factory-trained representatives to
handle your needs for genset parts and service.
Call 1-800-888-ONAN to contact the nearest Cummins/Onan or Onan-only distributor in the
United States or Canada. (This automated service utilizes touch-tone phones only). Select
OPTION 1 (press 1) to be automatically connected to the distributor nearest to you.
If you are unable to contact a distributor using the automated service, consult the Yellow Pages.
Typically, our distributors are listed under:
GENERATORS - ELECTRIC,
ENGINES - GASOLINE OR DIESEL, or
RECREATIONAL VEHICLES - EQUIPMENT,
PARTS AND SERVICE.
If you are outside North America, call Onan Corporation at 1-763-574-5000 from 7:30 AM to
4:00 PM, Central Standard Time, Monday through Friday, or fax 1-763-528-7229.
Before calling for service, have the following information available:
1. The complete genset model number and serial number. See Model Identification (Page 4).
2. The date of purchase.
3. The nature of the problem. See Troubleshooting.
If you have difficulty in arranging service or resolving a problem, please contact the Service
Manager at the nearest Cummins/Onan distributor for assistance.
WARNING: Improper service or replacement of parts can result in severe personal injury,
death, and/or equipment damage. Service personnel must be trained and
experienced in performing electrical and/or mechanical service.
A031C171 (Issue 1) 41
Page 46
8. How to Obtain Service 06-2012
This page is intentionally blank.
42 A031C171 (Issue 1)
Page 47
9 Maintenance Record
Record all periodic and unscheduled maintenance and service. See Periodic Maintenance.
DATE METER MAINTENANCE OR SERVICE PERFORMED
HOUR
READING
Record the name, address, and phone number of your authorized Onan service center.
A031C171 (Issue 1) 43
Page 48
9. Maintenance Record 06-2012
This page is intentionally blank.
44 A031C171 (Issue 1)
Page 49
Page 50
Cummins Power Generation
1400 73rd Ave. NE
Minneapolis, MN 55432 USA
Phone 1 763 574 5000
Toll-free 1 800 888 6626
Fax 1 763 574 5298
Copyright © 2012 Cummins Power Generation, Inc. All rights reserved.
Cummins, the "C" logo, and "Our energy working for you." are trademarks of
Cummins Inc.