CUMMINS HDKBB, HDKBC Installation Manual

Page 1
Installation Manual
Commercial Mobile Generator Set
HDKBB (Spec A−J) HDKBC (Spec DJ)
English Original Instructions 10-2016 981−0650 (Issue 9)
Page 2
Proposition 65 Warning
Diesel engine exhaust and some of its constituents are known to the State of California to cause cancer, birth defects, and other reproductive harm.
Page 3
Table of Contents
TABLE OF CONTENTS II . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SAFETY PRECAUTIONS 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
INTRODUCTION 9 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
About this Manual 9 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Outline Drawings 9 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Installation Codes and Standards for Safety 10 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Noise 10 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electromagnetic compatibility 10 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
MOUNTING, LOCATION AND VENTILATION 11 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Mounting 11 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Location 11 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Ventilation 12 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
EXHAUST CONNECTIONS 13 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Muffler 13 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Tailpipe 14 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
FUEL CONNECTIONS 17 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Biodiesel Fuels B5 B20 18 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ELECTRICAL CONNECTIONS 21 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
AC Power Connections 21 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Remote Control Connections 23 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Battery Connections 23 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
INSTALLATION REVIEW AND STARTUP 27 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Hot Air Recirculation Test 27 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Installation Review 28 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Startup 28 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SPECIFICATIONS 29 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 15. Outline Drawing—Sheet 1 31 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 16. Outline Drawing—Sheet 2 31 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 17. Wiring Diagram—Sheet 1 32 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 18. Wiring Diagram—Sheet 2 33 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Copyright  2016 Cummins Inc.
i
Page 4
This Page Intentionally Left Blank.
ii
Copyright  2016 Cummins Inc.
Page 5
SAFETY PRECAUTIONS
Thoroughly read the OPERAT OR’S MANUAL be­fore operating the genset. Safe operation and top performance can only be obtained when equip­ment is properly operated and maintained.
Only trained and experienced service personnel with knowledge of fuels, electricity , and machin­ery hazards shall remove dismantle and dispose of the generator set. See service manual.
Some generator set installation procedures present hazards that can result in severe person­al injury or death. Only trained and experienced personnel with knowledge of fuels, electricity, and machinery hazards should perform genera­tor set installation procedures.
The following symbols in this manual alert you to po­tential hazards to the operator, service person and equipment.
Used to alert you to a lethal hazard against which you must take steps to prevent se­vere personal injury or death, as when you are in the vicinity of High Voltage equipment.
WARNING
safe practice that can result in severe personal injury or death.
CAUTION
safe practice that can result in personal injury or equipment damage.
Electricity, fuel, exhaust, moving parts and batteries present hazards which can result in severe personal injury or death.
Used to alert you to a hazard or un-
Used to alert you to a hazard or un-
ENGINE EXHAUST IS DEADLY
Inspect for exhaust leaks at every startup and af-
ter every eight hours of running.
Prior to every startup and after every eight hours
of running, all carbon monoxide detectors must be tested and confirmed to be working in accor­dance with the manufacturer’s instructions or owners manual.
Learn the symptoms of carbon monoxide poi-
soning in the genset Operator’s Manual.
Never occupy the vehicle while the genset is
running unless the vehicle is equipped with a working carbon monoxide detector.
Do not operate the genset when the vehicle is
parked in a confined space, such as a garage.
Disable the automatic genset starting feature
(AGS) of an inverter-charger or other automatic starting device before storing the vehicle or parking it in a garage or other confined space.
The exhaust system must be installed in accor-
dance with the genset Installation Manual.
Engine cooling air must not be used for heating
the vehicle.
GENERATOR VOLTAGE IS DEADLY
Disable the automatic genset starting feature
(AGS) of an inverter-charger or other automatic starting device before servicing the genset.
Generator electrical output connections must be
made by a trained and experienced electrician in accordance with applicable codes.
WARNING
and shore power can lead to electrocution of util­ity line workers, equipment damage and fire. Use an approved switching device to prevent inter­connections.
Use caution when working on live electrical
equipment. Remove jewelry, make sure clothing and shoes are dry, stand on a dry wooden plat­form or rubber insulating mat and use tools with insulated handles.
Interconnecting the generator set
DIESEL FUEL IS COMBUSTIBLE
Do not smoke or turn electrical switches ON or
OFF where fuel fumes are present or in areas sharing ventilation with fuel tanks or equipment. Keep flames, sparks, pilot lights, arc-producing equipment and all other sources of ignition well away.
Fuel lines must be secured, free of leaks and
separated or shielded from electrical wiring.
MOVING PARTS CAN CAUSE SEVERE
PERSONAL INJURY OR DEATH
Disable the automatic genset starting feature
(AGS) of an inverter-charger or other automatic starting device before servicing the genset.
Copyright 2016 Cummins Inc.
1
Page 6
Do not wear loose clothing or jewelry near mov-
ing parts such as PTO shafts, fans, belts and pulleys.
Do not work on the genset when mentally or
physically fatigued or after consuming alcohol or drugs.
Keep hands away from moving parts.Keep guards in place over fans, belts, pulleys,
and other moving parts.
BATTERY GAS IS EXPLOSIVE
Wear splashproof safety glasses.Do not smoke or permit flames or sparks to oc-
cur near the battery at any time.
To reduce arcing when disconnecting or recon-
necting battery cables, always disconnect the negative (−) battery cable first and reconnect it last.
FLAMMABLE VAPOR CAN CAUSE A
DIESEL ENGINE TO OVERSPEED
WARNING
genset where a flammable vapor environment can be created by fuel spill, leak, etc.
Flammable vapor can cause a diesel engine to over­speed and become difficult to stop, resulting in pos­sible fire, explosion, severe personal injury and death. The owners and operators of the genset are solely responsible for operating the genset safely.
Do not operate a diesel-powered
GENERAL PRECAUTIONS
Keep children away from the genset.Do not use evaporative starting fluids. They are
highly explosive.
To prevent accidental or remote starting while
working on the genset, disconnect the nega­tive () battery cable at the battery.
Let the engine cool down before removing the
coolant pressure cap or opening the coolant drain. Hot coolant under pressure can spray out and cause severe burns.
Used engine oil has been identified by some
U. S. state and federal agencies as causing can­cer or reproductive toxicity. Do not ingest, in­hale, or contact used oil or its vapors.
Ethylene glycol, used as engine antifreeze, is
toxic to humans and animals. Clean up spills and dispose of used engine coolant in accor­dance with local environmental regulations.
Keep multi-purpose fire extinguishers handy.
Multipurpose fire extinguishers are used for fires that involve ordinary combustible materials such as wood and cloth; combustible and flam­mable liquid fuels and gaseous fuels; live electri­cal equipment. (North America or US: ref. NFPA No. 10)
Genset installation and operation must comply
with all applicable local, state and federal codes and regulations.
Generator sets with a sound shield shall not be
run with the service doors remove/missing.
Engine components can be hot and cause se-
vere burns. Hot coolant under pressure can spray and cause severe burns.
Use personal protective equipment when main-
taining or installing the generator set such as gloves, safety glasses, etc.
THE HAZARDS OF CARBON MONOXIDE
WARNING
duce harmful level of carbon monoxide that can injure or kill you.
Enginedriven generators can pro-
ONLY YOU CAN PROTECT YOURSELF
FROM CO POISONING!
Watch constantly for people near the exhaust of
the generator set while it is running.
Use personal protective equipment when instal-
ling generator set (gloves, safety glasses, etc).
Keep the genset and its compartment clean. Ex-
cess oil and oily rags can catch fire. Dirt and gear stowed in the compartment can restrict cooling air.
Make sure all fasteners are secure and torqued
properly.
Make sure exhaust cannot enter the living quar-
ters through a window, vent or door.
Make sure all CO detectors and audible alarms
are working properly.
Pay attention to the signs of CO poisoning.Check the exhaust system for corrosion, ob-
struction and leaks each time you start the gen-
2
Copyright 2016 Cummins Inc.
Page 7
erator set and every eight hours if you run it con­tinuously.
SUBSTANCE HAZARDOUS TO HEALTH
Generator sets use substances, and emit and create wastes that can cause health risks. Generator set operators must use appropriate personal protective equipment (such as clothing, gloves, protective glasses/goggles, and respiration equipment) when exposed to fuel, oil, coolant, wet batteries, grease, cleaning agents, or other substances exposed to lungs, eyes, or skin. use appropriate containers for transport, storage, and disposal of waste sub­stances. Follow local regulations for disposal and re­cycling.
ANTIFREEZE (FLEETGUARD − ES
COMPLEAT/EG PREMIX)
This antifreeze is also know as an ethylene glycol based coolant; summer coolant; coolant additive. It is purple coloured, viscous liquid, with a mild chemi­cal odour, is soluble in water and harmful. It contains ethylene glycol, and diethylene glycol. Ethylene gly­col is a potentially hazardous constituent.
The substance has a boiling point of 107 C, and a flash point of 121 C.
It is used as an engine coolant additive, and can be found in engine cooling systems, and head exchang­ers. Installers, operators and maintainers are likely to encounter this substance.
HAZARDOUS REACTIONS
Ethylene glycol is combustible when exposed to heat or flame and can react vigorously with oxidants. Moderate explosive hazard in form of vapour when exposed to heat or flame. Hazardous products re­sulting from combustion or decomposition include carbon monoxide, carbon dioxide and acrid smoke. Selfcontained breathing apparatus must be worn in the event of fume build up.
Avoid strong oxidizing agents incompatible with sulfuric acid, nitric acid, caustics and aliphatic amines.
It may cause neurological signs and symptoms, and kidney damage. It is also a skin and eye irritant.
Very toxic in particulate form upon inhalation. Harm­ful if swallowed, lethal dose for humans reported to be 100ml.
PROTECTIVE MEASURES
Refrain from eating, drinking or smoking when using the product. Adopt a high standard of personal hy­giene. In ca s e o f s k i n c o n t a c t , w a s h i m m edia t e l y w i t h soap and water.
Ensure good ventilation and avoid heat sources. Avoid breathing mist, if there is a risk of vapour, or particulate, use a suitable organic vapour mask.
Eye protection, gloves, overalls, impervious apron should be used. Avoid contamination inside the gloves. If overalls become contaminated, discontin­ue use and clean thoroughly.
STORAGE/TRANSPORT
Store and transport only in correctly marked contain­ers. Keep containers closed when not in use. Keep cool, out of sunlight, away for naked flames and strong acids, do not freeze. Store well away from foodstuffs and drinking water. Take special care to avoid discharge into drains, sewers and water courses.
Contain leak/spill with sand, earth or non−combus- tible, absorbent material to prevent entry of sub­stance into drainage/sewerage system, water courses and land. Eliminate all ignition sources, use plastic shovel to transfer to suitable container and dispose of unwanted or absorbed substance through and authorized contractor to a licensed site.
EMERGENCY ACTION
Fire
Extinguishing media: CO foam, dry powder, or water spray. Fire fighters to use self contained breathing ap­paratus. Keep fire exposed containers cool. Prevent run−off from entering waterways, drains and drinking water supplies.
Ingestion
Toxic by ingestion. If swallowed induce vomiting only
under the advice of a Doctor or poison con­trol centre. Delayed treatment may result in fa­tality.
Inhalation (of vapour)
Remove from further exposure. In case of irrita­tion to lungs or throat, seek medical advice.
Aspiration (inhalation of liquid)
Obtain immediate medical assistance.
alcohol resistant
2,
Copyright 2016 Cummins Inc.
3
Page 8
Eyes
Flush copiously with water or preferably eye wash solution for at least five minutes. Seek medical advice.
Skin
Wash thoroughly with soap and water, and seek medical attention if irritation develops. Change clothing if necessary and wash before re−use.
Spillage
Soakup using an absorbent material and dis­pose of this as directed under Storage/Trans­port (Section 5.1.3)
GAS OIL
This product is also known as Red Diesel, Fuel Oil, and type A1 or A2. It can be pale red or a clear liquid with a characteristic mild odour. It contains catalyti­cally cracked oil, petroleum distillates, quinizarin, and gas oil maker dye red. The catalytically cracked oil and petroleum distillates are potentially hazard­ous constituents.
The substance has an initial boiling point of 180C, a flash point greater than 56C, and a vapour pressure less than 0.7mm Hg at 2 0C and has negligible solu­bility in water.
Gas oil is slightly irritating to the skin and has a de fatting action. Toxicity following single exposure to high level of gas oil is of low order. Prolonged, re­peated skin contact may defat the skin resulting in possible skin irritation and dermatitis. In some cases warty, cancerous growths have occurred.
PROTECTIVE MEASURES
Ensure good ventilation and avoid heat sources. Ob­servance of good housekeeping rules will ensure general safety. Do not smoke. Avoid breathing mist.
When working on, or testing, injection equipment, special care is required to avoid perforation of skin by high pressure fuel. Use eye protection in the event of suspected high pressure leak.
Adopt a high standard of personal hygiene. In the case of skin contact, wash well with soap and water.
Use glove and overalls, and eye protection goggles if there is a risk of splashing. Use oil impervious gloves and avoid contamination inside the gloves. If over­alls become contaminated, discontinue use and clean thoroughly. Contaminated clothing should be removed, soaked with water, and laundered before reuse.
It is used as a fuel for offroad diesel powered ve­hicles and stationary engines, and can be found in fuel tanks, pipes and injection systems. The sub­stance should not be used for any other purpose without contacting the manufacturer or supplier. In­stallers, operators and maintainers are likely to en­counter this substance.
HAZARDOUS REACTIONS
This liquid is flammable. Avoid smoking, heat sources, such as welding and naked flames, sparks and static electricity build−up. Thermal decomposi- tion products are hazardous, containing CO and SOX compounds.
The vapour is explosive. High vapour concentrations can cause respiratory irritation, dizziness, nausea, and loss of consciousness. Excessive and pro­longed exposure to the mist can cause chronic in­flammatory reaction of the lungs and form of pulmo­nary fibrosis.
Avoid strong oxidizing agents, e.g. chlorates which may be use in agriculture.
, NO
X
No special respiratory precautions are necessary in normal use.
DO NOT use as a solvent for removing dirt/grease etc, from skin.
STORAGE/TRANSPORT
Store and transport only in correctly marked contain­ers. Keep containers closed when not in use. Keep cool, out of sunlight and away from naked flames. Electrical continuity is required between the trans­port and storage vessels during product transfer.
X
Contain leak/spill with sand, earth or other suitable material, and prevent entry of substance into drain­age/sewerage system, watercourses and land. Dispose of unwanted or absorbed substance through an authorized contractor to a licensed site.
Inform local and fire authorities should the product reach waterways, drains etc.
4
Copyright 2016 Cummins Inc.
Page 9
EMERGENCY ACTION
Fire
Extinguishing media: Large fire − Foam/water fog. Never use water jet. Small fire foam/dry powder, AAAF, CO earth. Avoid making sparks. Fire fighters to use self contained breathing apparatus. Keep fire ex­posed containers cool, using water fog/spray. Prevent runoff from entering waterway, drains and drinking water supplies.
Ingestion
Do not induce vomiting. Wash the mouth out with water, and send to hospital immediately.
Inhalation (of vapour)
Remove from further exposure. Obtain medical assistance immediately.
2
, sand,
It has a boiling point greater than 150C, a flash point Open Cup of 220C (Cleveland), and is insoluble in cold water.
It is used in engine lubricant oil systems, sump pan and filters, makeup tanks and piping systems as a lubrication oil for use in wide range of diesel engines operating under severe conditions. Installers, opera­tors and maintainers are likely to encounter this prod­uct.
HAZARDOUS REACTIONS
This product is stable although slightly reactive with oxidizing agents. Results of decomposition are car­bon oxides (CO, CO
Although harmful if swallowed or aspirated (breathed in), repeated or prolonged exposure is not known to aggravate medical conditions.
) and water.
2
Aspiration (inhalation of liquid)
If, following ingestion of gas oil, vomiting occurs, there is danger of aspiration into the lungs. This would cause intense local irritation and chemi­cal pneumonitis that can be fatal. Obtain imme­diate medical assistance.
Eyes
Irrigate copiously with water or preferably eye wash solution for at least five minutes. If irritation persists seek medical advice.
Skin
Wash thoroughly with soap and water. Change clothing if necessary. If high pressure injection has occurred prompt surgical attention is required.
Spillage
Absorb using sand, earth or other suitable mate­rial. Dispose of unwanted or absorbed flam­mable material as directed under Storage/ Transport (Section 5.7.3).
LUBRICATION OIL − PREMIUM BLUE E
15W40
Used oil may contain harmful combustion by−prod- ucts and unburnt fuel that will cause skin reactions as detailed for fuel. Particular care must be taken if oil form a severely overheated engine is handled use impervious gloves, lab coat and safety glasses.
Do not breathe vapour/spray.
PROTECTIVE MEASURES
Ensure good ventilation and avoid heat sources. Adopt a high standard of personal hygiene. In case of
skin contact, wash thoroughly with soap and water. Use safety glasses, impervious gloves and lab coat.
Avoid contamination inside the gloves. If overalls be­come contaminated, discontinue use and clean thor­oughly.
No special respiratory precautions are necessary n normal use. Do no breathe vapour/spray when han­dling hot materials.
STORAGE/TRANSPORT
Also known as oil, lube oil, sump oil, new oil is dark, viscous liquid with a slight, characteristic odour. T he base oil contains: distillates (petroleum), solvent dewaxed heavy paraffinic. It is not classified as dan­gerous according to Directive 1999/45/EC and its amendments, and is not classified according to the EU regulations.
Copyright 2016 Cummins Inc.
Store and transport only in correctly marked contain­ers. Keep containers tightly sealed when not in use. Keep in a cool, well ventilated area, out of sunlight and away from naked flames. Store well away from foodstuffs and drinking water.
5
Page 10
Wear splash goggles, full suit, boots and gloves. Ab­sorb leak/spill with an inert material and dispose of unwanted or absorbed substance through an autho­rized contractor to a licensed site. Finish cleaning by spreading water on the contaminated surface and al­low to evacuate through the sanitary system.
EMERGENCY ACTION
Fire
Extinguishing media: Large fire Use water spray, fog or foam. Do not use water jet.
Small fire Use dry chemical powder or CO Firefighters to use self contained breathing ap­paratus and full turnout gear. Keep fire exposed containers cool.
Ingestion
Do not induce vomiting, Obtain medical advice immediately.
Inhalation (of vapour)
Remove from further exposure. Obtain medical attention.
2
6
Copyright 2016 Cummins Inc.
Page 11
Generator Set Warning Labels
Warning signs are provided on the generator set at or near the point of risk. To avoid injury, always take the necessary precautions – as indicated on the sample signs shown below:
Caution / Warning. Indicates a risk of personal injury.
Caution / Warning of Temperature Hazard. Indicates a risk of personal injury from high temperature.
Caution / Warning of High Voltage Hazard. Indicates a risk of personal injury from electric shock/electrocution.
Caution / Warning. Indicates a risk of personal injury from equipment that may be subject to automatic starting or remote starting.
Caution / Warning. Indicates to read Operator manual for additional information.
Caution / Warning of Belt and Rotating Part Hazard. Indicates a risk of personal injury from entanglement in moving parts.
Caution / Warning of Pressure Hazard. Indicates a risk of personal injury from pressurized fluids.
Copyright 2016 Cummins Inc.
7
Page 12
THIS PAGE IS INTENDED TO BE BLANK
8
Copyright 2016 Cummins Inc.
Page 13
Introduction
ABOUT THIS MANUAL
WARNING
severe personal injury, death and equipment damage. The installer must be qualified to per­form the installation of electrical and mechanical equipment.
WARNING
tem. It can stop without warning. Children, per­sons with physical or mental limitations, and pets could suffer personal injury or death. A per­sonal attendant, redundant power or an alarm system must be used if genset operation is criti­cal.
WARNING
tected” and shall not be used in a flammable va­por environment.
CAUTION
placement of fuel, exhaust, air intake or speed control system components that affect engine emissions are prohibited by law in the State of California.
This manual is a guide for the installation of the gen­erator sets listed on the front cover. Proper installa­tion is essential for top performance. Read through this manual before starting the installation.
Improper installation can result in
This genset is not a life support sys-
This generator is not “ignition pro-
Unauthorized modifications or re-
This manual addresses the following aspects of the installation:
Location and MountingExhaust ConnectionsFuel ConnectionsElectrical ConnectionsStartup
See the Operator’s Manual for operation and mainte­nance and the Service Manual for service.
Manuals are updated from time to time to reflect changes in the equipment and its specifications. For this reason, only the copy of the installation manual supplied with the genset should be used as a guide for the installation.
OUTLINE DRAWINGS
See the Outline Drawings (Pages 31 and 32) for installation details: mounting bolt hole locations, con­nection points (fuel, battery, exhaust, remote control, AC output), sizes and types of fittings, cooling air openings, weight, and overall dimensions. See your Cummins Onan dealer for a large-scale Outline Drawing and full-size floor cutout template.
Copyright 2016 Cummins Inc.
9
Page 14
INSTALLATION CODES AND STANDARDS
FOR SAFETY
CAUTION
applies only when the genset is installed in a Commercial or Recreational Vehicle.
The genset installer bears sole responsibility for the selection of the appropriate genset, for its proper installation and for obtaining approvals from the au­thorities (if any) having jurisdiction over the installa­tion.
Federal, State and local codes, such as the Califor­nia Administrative Code—Title 25 (RV installation), might also be applicable. Installation codes and rec­ommendations can change from time-to-time and are different in different countries, states and munici­palities. It is recommended that the standards in Table 1 be obtained for reference.
TABLE 1. REFERENCE CODES AND STANDARDS
Code of Federal
Regulations:
Title 49: Chapter III,
Chapter V
National Electrical
NFPA No 70, 1192
ANSI/RVIA-EGS-1
California
Administrative Code:
Title 25, Chapter 3
CAN/CSA-Z240:
Recreational Vehicles
Bulletin 946
IEC 60364-7-708:
Electrical Installations
in Caravan Parks &
Caravans
The Commercial Genset Warranty
Superintendent of Documents
P. O. Box 371954
Pittsburgh, PA 15250-7954
Code:
National Fire Protection Association
470 Atlantic Avenue
Boston, MA 02210
Recreational Vehicle Industry Association
14650 Lee Road
Chantily, VA 22021
State of California Documents Section
P.O. Box 1015
North Highlands, CA 95660
Canadian Standards Association
Housing & Construction Materials
178 Rexdale Blvd.
Rexdale, Ontario, Canada M9W 1R3
International Electrotechnical Commission
3, Rue de Varembé
Geneva, Switzerland
NOISE
Generator sets emit noise. As noise level and time of exposure increase, risk of hearing damage in­creases. The Specifications page n the Operator manual states noise level for this generator set. Se­lect and use personal hearing protection appropriate for your exposure to generator set noise.
Note for use in countries where compliance to the EU Noise directive is required: This generator set has not been evaluated and is not marked for use in open air. Install the generator set in accordance with the Installation manual. Obey local noise restrictions when you operate the generator set.
ELECTROMAGNETIC COMPATIBILITY
Generator sets emit and receive electromagnetic (radio frequency) energy . If the generator set affects operation of nearby devices, or nearby devices affect generator set operation, increase the distance be­tween them.
Note for use in countries where compliance to the EMC directive is required: This generator set has been evaluated for use in residential, commercial, and light industrial environments.
10
Copyright 2016 Cummins Inc.
Page 15
Mounting, Location and Ventilation
MOUNTING
Installation of the generator set requires lift­ing apparatus. Ensure that correctly rated lifting slings with suitable attachments are available prior to commencing work. Lifting and lowering operations should only be car­ried out by properly trained personnel. Do not exceed the rating of any lifting compo­nent. Wear head, eye, hand and foot protec­tion during lifting operations.
The generator set has a 2 point lifting system, which is accessible through an access cover. Refer to out­line drawing (p 24 and p 25) for the location of the ac­cess cover and weight of the generator set. Make provisions accordingly for safe handling.
Support the genset on a structure able to resist the dynamic weight of the genset:
3 g-force vertical and
1 g-force horizontal. See Specifications for the
weight of the genset. Use four Grade 5 screws (3/8-16 UNC) to secure the genset to the floor or frame. The screws must protrude at least 1/2 inch (13 mm) but not more than 1 inch (25 mm) into the base, as measured from the bottom surface of the base. Torque the screws to 35 lb-ft (41 N-m).
WARNING
be designed and installed to support the dynam­ic weight of the genset. Failure to do so can result in the genset dropping onto the roadway causing property damage, severe personal injury and death.
The genset support structure must
LOCATION
Typical genset locations on a vehicle are illustrated in Figure 1.
Provide access to the operator’s console to start and
stop the genset and to check for and add engine oil and coolant.
Provide access for connecting and disconnecting
fuel lines, battery cables, remote control wiring and AC wiring.
Provide access for removing the front and bottom ac-
cess covers to perform periodic maintenance in accordance with the Operator Manual. If the genset compartment has a floor, use the floor cutout template that is available from your Cum­mins Onan dealer. The crosshatched areas on Page 16 indicate the areas that must be open in the floor. These areas must not be obstructed by frame members, exhaust tail pipes or other equipment.
Make sure the genset clears the ground by at least
12 inches (305 mm) to provide adequate ven­tilation and reduce the amount of dust pulled in by the cooling fan.
A genset compartment must be large enough to pro-
vide at least 1/2 inch (12.7 mm) clearance at the top of the genset, 1/4 inch (6.4 mm) at the back and left side, 2 inches (51 mm) at the front for air intake and 4 inches (102 mm) at the right side for air discharge (Figure 2). These minimum clear- ances apply to any thermal or acoustic insula­tion with which the compartment may be lined.
Acoustic/thermal insulation and adhesive must be
Classified as “Self-Extinguishing” at not less than 200 compartment with insulation, which absorbs spilled fuel and oil.
Provide a vapor-tight, fire-resistive barrier between
the genset and the interior of the vehicle. Use approved materials (26 gauge galvanized steel or equivalent). See NFPA 1192 for details.
EXHAUST GAS IS DEADLY. Construct a suit­able vapor barrier of approved materials be­tween the genset and vehicle interior to keep out exhaust gas.
Provide protection from rain and snow when the gen-
set is not mounted in a compartment. The gen­set housing is not water tight. Protection must extend over the entire top of the genset, includ­ing the operator control panel.
F (90C). Do not line the bottom of the
Copyright 2016 Cummins Inc.
11
Page 16
Provide protection from direct road splash if the gen-
set is located behind a road wheel or the front grille of the vehicle.
FIGURE 1. TYPICAL GENSET LOCATIONS
VENTILATION
Unrestricted air flow for cooling, ventilation and com­bustion (Figure 2) is essential for proper genset per­formance and service life. See HOT AIR RECIR­CULATION TEST (Page 27).
The crosshatched areas on Page 16 must be open
for unobstructed air flow into and out of the gen­set for cooling, ventilation and combustion.
When the genset is installed in a compartment that
surrounds the top and sides (Figure 2), provide non-flammable baffles (UL 94 HBF foam or bet­ter) to prevent hot side-discharge air from recir­culating back into the front air inlet grille. The baffles must extend all the way across the top, down the front and half way back below the side air discharge grille. They must close off the gap between the genset and enclosure.
If the air inlet is in the compartment door, it must allow
the air to flow straight into each opening of the inlet air grille without obstruction (Figure 2).
If the air inlet is in the compartment floor in front of the
genset, the opening must be at least 2 inches
(51 mm) wide and extend across the entire front of the genset (crosshatched area, Page 16).
COMPARTMENT WITH BAFFLES
AND AIR OPENINGS ON SIDES OF GENSET
AIR OUTLET IN BOTTOM OF GENSET
FIGURE 2. GENSET COMPARTMENT WITH
BAFFLES TO PREVENT HOT AIR RECIRCULATION
The compartment outlet for side-discharge air must
be at least 4 inches (102 mm) wide and extend across the back half of the floor (Figure 2).
12
Copyright 2016 Cummins Inc.
Page 17
Exhaust Connections
The exhaust system must be gas-tight and designed to limit entry of exhaust gases into the vehicle.
WARNING
EXHAUST GAS IS DEADLY! To keep exhaust gases from entering the vehicle do not terminate the exhaust tailpipe underneath the vehicle or closer than specified to openings into the vehicle (Figure 6) or route it such that it is likely to be damaged (Figure 7). Use approved materials and parts only.
CAUTION
Unauthorized modifications or re­placement of fuel, exhaust, air intake or speed control system components that affect engine emissions are prohibited by law in the State of California.
MUFFLER
The muffler is mounted inside the genset housing and has a flanged outlet opening (Figure 3). It has a
USDA (Forest Service) spark arrestor and meets RVIA EGS-1 construction requirements. The Outline Drawing (Page 16) shows the dimensions of the ex­haust flange and the locations of the tailpipe clear­ance holes.
A genset without a properly installed and maintained spark arresting exhaust system can cause a brush or forest fire, and is illegal on federal lands. Liability for damage, injury and warranty expense due to the modification of the exhaust system or to use of unap­proved parts is the responsibility of the person per­forming the modification or installing the unapproved parts. Contact a Cummins Onan distributor for ap­proved exhaust system parts.
SIDE AND BACK TAILPIPE
EXIT HOLES
MUFFLER OUTLET FLANGE
Copyright 2016 Cummins Inc.
FIGURE 3. EXHAUST CONNECTIONS AT GENSET
13
Page 18
TAILPIPE
The tailpipe of the generator set will be hot dur­ing operation and can cause severe burns. To re­duce the risk of contact, consideration must be taken on where the tailpipe will be located and routed.
Tailpipe adapter kits are separately available. Use a straight adapter for a tailpipe routed through the bot­tom. Use an elbow adapter for a tailpipe routed through the side or back exit holes. When connecting and routing the tailpipe:
Use 1-3/8 inch ID 18-gauge aluminized steel tubing
or equivalent (minimum 35 mm ID with mini­mum 0.012 mm wall thickness). Do not use flex­ible tubing, which is not gas tight or durable.
Secure the tailpipe or adapter flange to the muffler
flange with the gasket and two stainless steel bolts supplied in the kit.
Use U-bolt muffler clamps to connect sections of tail-
pipe. It is recommended that the overlapping pipe be slotted as shown in Figure 4.
3/4 INCH (19 MM)
MAXIMUM SLOT
(BOTH SIDES)
FIGURE 4. EXHAUST TAILPIPE CONNECTIONS
Use flexible automotive-type tailpipe hangers every
2 to 3 feet (0.6 to 0.9 m). Attach the hangers to steel framework, not to wood or other combus­tible material.
Do not terminate the tailpipe underneath the vehicle.
Extend it a minimum of 1 inch (25 mm) beyond the perimeter of the vehicle (Figure 5). Support the end of the tailpipe such that it cannot be pushed inward and up under the skirt of the ve­hicle.
Do not route the tailpipe such that it will interfere with
removing the service access cover and perform­ing periodic maintenance. See the Operator Manual.
Do not route the tailpipe closer than 3 inches
(76 mm) to combustible material (wood, felt, cotton, organic fibers, etc.) unless it is insulated or shielded. The temperature rise (above ambi­ent) on adjacent combustible material must not exceed 117
F (65C).
Do not route the tail pipe near fuel lines or fuel tanks.
1 INCH (25 mm) MINIMUM
LAST TAILPIPE HANGER AS
CLOSE TO END AS
PRACTICAL
FIGURE 5. TERMINATING THE EXHAUST TAILPIPE
NO OPENING INTO THE VEHICLE INTERIOR MAY
BE CLOSER THAN 6 INCHES (153 mm) TO THE
END OF THE TAIL PIPE (WITHIN SHADED AREA)
6 in
153 mm
Do not terminate the tailpipe such that it is closer than
6 inches (153 mm) to any opening into the ve­hicle interior (door, window, vent). See Figure 6.
TAILPIPE
FIGURE 6. MINIMUM DISTANCES TO OPENINGS
Route the tailpipe such that it is not likely to be struck
when the vehicle is moving. Keep it out of the ap-
14
Copyright 2016 Cummins Inc.
Page 19
proach and departure angles of the vehicle and above the axle clearance line (Figure 7).
Excessive back pressure can cause loss of performance and engine damage.
Interconnecting the engine exhaust systems will allow exhaust condensates and soot to migrate into the engine that is idle, causing engine damage.
Do not connect the genset to the vehicle engine ex-
haust system.
DEPARTURE
ANGLE
Exhaust back pressure under full load must not ex-
ceed 2 inches (51 mm) water column (WC) as measured within 6 inches (154 mm) of the muf­fler outlet flange.
APPROACH
ANGLE
AXLE CLEARANCE LINE
FIGURE 7. APPROACH AND DEPARTURE ANGLES AND AXLE CLEARANCE LINE
Copyright 2016 Cummins Inc.
15
Page 20
THIS PAGE IS INTENDED TO BE BLANK
16
Copyright 2016 Cummins Inc.
Page 21
Fuel Connections
WARNING
Diesel fuel is a combustible and can cause severe personal injury or death. Do not smoke or allow any flame, spark, pilot light, arc­producing equipment, electrical switch or other ignition source around fuel or fuel components, or in areas sharing ventilation. Keep a type mul­ticlass fire extinguisher handy.
Do not interconnect genset and vehicle engine fuel lines. Follow the vehicle chassis manufacturer’s in­structions when making connections to the vehicle engine fuel tank.
CAUTION
Either or both engines could starve for fuel if the genset and vehicle engine fuel lines are interconnected. Always use separate fuel lines or a separate fuel tank for the genset.
To prevent the genset from running the vehicle out of fuel, do not extend the genset fuel pickup tube down into the fuel tank as far as the pickup tube for the ve­hicle engine.
Fuel lines (supply and return) must have at least a 1/4 inch (6.4 mm) ID See Figure 8 for connections at the genset.
Run the fuel line at or above the top of the fuel tank to reduce the risk of siphoning fuel out of the tank if the line should break. The maximum fuel pump lift is 36 inches (1 meter).
Route fuel lines away from electrical wiring and hot engine exhaust components. Fuel lines should be accessible for inspection and replacement, pro­tected from damage and secured to prevent kinking, contact with sharp edges and chafing due to vibra­tion.
FUEL SUPPLY
(1/8 INCH NPT)
FUEL RETURN (1/8 INCH NPT)
FIGURE 8. FUEL CONNECTIONS
Copyright 2016 Cummins Inc.
17
Page 22
BIODIESEL FUELS B5 B20
Approved Bio−Diesel Fuel:
Biodiesel meeting either ASTM D6751 or
EN14214.
Place the fuel water separator in a location that is accessible for service by as close the genera­tor set as possible. Locating the separator ahead of the generator set fuel pump is accept­able.
Fuel meeting either ASTM D6751 or EN14214
fuel can be blended with an acceptable diesel fuel meeting ASTM D975 meeting ASTMD975 up to 20 percent volume concentration (B20).
For bio−diesel blends above B5 and up to B20 the following installation requirements must be met:
Supply and Return fuel lines and fittings must be
biodiesel compatible. Not all fuel hoses and fit­tings are bio−diesel compatible. All fuel wetted components must not contain the following ma­terials: copper, brass, bronze, zinc, lead, tin, natural rubber and nitrile rubber compounds. Check with your manufacturer for bio−diesel compatibility.
Fuel tanks must be made from the following ma-
terials: aluminum, steel, flourinated polyethyl­ene, flourinated polypropylene or Teflon (PTFE).
Verify the vehicle propulsion engine is capable
of using B20 when sharing the same fuel tank with the generator set.
A bio−diesel compatible fuel water separator is
required. Cummins Onan strongly recommends using Cummins Filtration filters equipped with StrataPoret media. This filter media removes water more efficiently than standard cellulosic filter media, which will not provide adequate fuel water separation capabilities. However, even StrataPoret fuel filter media is not as effective in removing water from bio−diesel as it is in re- moving water from petro diesel. Therefore, pre­venting water from entering the fuel supply (ve­hicle or storage) remains very important.
Additional information:
Biodiesel blends have higher pour and cloud
points than standard diesel fuels. Generator set locations far from the fuel tank combined with low fuel flow rates can make the generator set fuel system very susceptible to fuel starvation related to gelling in cold weather (below 23
C). In addition to electric or coolant tank
–5
F/
heaters, consideration to routing and possible heating or insulation of the fuel lines to the gen­erator set may be needed.
BioDiesel blends can oxidize more quickly
than standard diesel fuels; more frequent fuel fil­ter service intervals may be required and shorter fuel storage life in tanks is likely.
WARNING
It is highly recommended that specific market applications are avoided or excercised with extra care due to some of the properties of biodiesel fuel blends such as cold weather operation, long term storage, material incompatibilities and other ef­fects on engine operating characteristics. Such ap­plications that should use standard fuels include ap­plications that will experience seasonal usage, storage for periods exceeding 60 days, and extreme temperatures or humidity.
Storage requirements:
If using bio−diesel for seasonal applications
(stored more than 90 days), the generator set must be purged before storage by running the engine on pure diesel fuel meeting ASTM D975 for a minimum of 30 minutes.
18
Copyright 2016 Cummins Inc.
Page 23
TABLE 2. CUMMINS ONAN BIODIESEL RECOMMENDATIONS
APPLICATION
RECOMMENDATION FOR BIODIESEL BLENDS
Emergency Standby
Not Recommended Use petroleum diesel only. Low fuel usage and critical RV Seasonal/Commercial with
low annual hour accumula­tion
Limited Time Prime Approved with
Recommendations
Unlimited Time Prime Approved with
Recommendations
Continuous Approved with
Recommendations
RECOMMENDATIONS COMMENTS
start nature of Emergency Standby make biodiesel impractical.
Use fuel within 6 months of manufacture. Flush fuel system with petroleum die­sel prior to storage.
Use fuel within 6 months of manufacture. Fluh fuel sys­tem with petroleum diesel
Biodiesel is suitable for constant high load opera­tion with proper precau­tions.
Biodiesel is suitable for variable load operation with proper precautions.
prior to storage/transport. Use fuel within 6 months of
manufacture.
Biodiesel is suitable for base load operation with proper precautions.
Copyright 2016 Cummins Inc.
19
Page 24
THIS PAGE IS INTENDED TO BE BLANK
20
Copyright 2016 Cummins Inc.
Page 25
Electrical Connections
AC POWER CONNECTIONS
WARNING
uninsulated live parts inside the generator set and connected equipment can result in severe personal injury or death. For your protection, stand on a dry wooden platform or rubber insu­lating mat, make sure your clothing, and shoes are dry, remove jewelry from your hands and use tools with insulated handles. Secure protective covers when completing installation.
WARNING
electric shock resulting in severe personal injury or death.
WARNING
cause severe personal injury or death. Do not connect the starting battery until so instructed in Installation Review and Startup.
HAZARDOUS VOLTAGE! Touching
IMPROPER WIRING can cause fire or
Accidental starting of the genset can
Wiring Methods
The genset is equipped with a terminal block and conduit connector knockouts for AC power output connections (Figure 9). See the generator connec­tion diagrams on Page 34.
terminals must be re-torqued after a few min­utes because the connection can loosen if the individual strands spread out.
Use vibration-proof switches and controls to prevent
the opening and closing of circuits while the ve­hicle is in motion.
Use rain-tight conduit, conduit connectors and junc-
tion boxes for all exterior wiring.
Provide ground fault circuit interrupters (GFCIs) or
residual current devices (RCDs) for all conve­nience power receptacles.
Seal all conduit openings into the vehicle interior to
keep out exhaust gas. Apply silicone rubber or equivalent sealant inside and outside each con­duit connector. (Flexible conduit is not vapor­tight and will allow exhaust gas to enter along the wires if not sealed.)
Route or protect AC wiring so that it will not be cut or
abraded, exposed to hot surfaces or damaged by road debris. Keep AC wiring away from fuel lines and control wiring (see Remote Control).
AC TERMINAL
ACCESS
AC wiring methods must be in accordance with the National Electrical Code or IEC 60364-7-708, as ap­propriate. Note especially the following:
WARNING
EXHAUST GAS IS DEADLY! Seal all wiring openings into the vehicle interior to keep out exhaust gas.
WARNING
Routing AC wiring with fuel lines can lead to fire and severe personal injury or death. Keep AC wiring away from fuel lines.
Have a trained and experienced electrician super-
vise and inspect the installation of all AC wiring.
Secure only one lead at each AC output terminal.
The terminals are suitable for wire gauges up to No. 6 AWG (16 mm
2
). Torque the terminals to 13 in-lbs (1.5 N-m). When stranded conductors are used, it is recommended that copper fer­rules, available for the various wire gauges, be crimped on the stripped ends of the conductors to facilitate terminal connections. Otherwise, the
CONTROL KNOCKOUTS FOR 3/4 AND 1 INCH CONDUIT
FIGURE 9. ACCESS FOR AC OUTPUT AND
REMOTE CONTROL CONNECTIONS
WIRING
KNOCKOUTS
Copyright 2016 Cummins Inc.
21
Page 26
Grounding
WARNING
electrocution and severe personal injury or death. Grounding must be in accordance with applicable codes.
Faulty grounding can lead to fire or
screw on the red, hexagonal insulator. Cut the jump­er as close to each terminal connector as possible to avoid having to loosen the connections for the other wires at the terminals.
Vehicle Connections to Utility Power
Connect grounding terminal TB1-5 (Page 34) in ac­cordance with applicable codes.
50 Hz Model HDKBB Only If the authority having jurisdiction requires an ungrounded 230 VAC sys­tem, it will be necessary to cut the internal grounding jumper (Figure 10). To do this, remove the side ac­cess cover (four screws) and cut the short jumper be­tween the ground terminal screw and the terminal
WARNING
Interconnecting the genset and the public utility (or any other power source) can lead to electrocution of utility line workers, equipment damage and fire. Use an approved switching device to prevent interconnections.
A vehicle with provisions for connecting utility power must have an approved device to keep the genset and utility from being interconnected.
FOR UNGROUNDED 230 VAC, 50 HZ APPLICATIONS, CUT
THIS JUMPER FROM ITS TERMINAL CONNECTORS
DO NOT LOOSEN THE TERMINAL SCREWS
FIGURE 10. MODEL HDKBB GROUNDING JUMPER
22
Copyright 2016 Cummins Inc.
Page 27
REMOTE CONTROL CONNECTIONS
Leads for connection to a remote control panel are terminated in a 10-pin sealed connector and are stowed inside the AC terminal enclosure when the genset leaves the factory. Details of the connector and its mate are provided on the Outline Drawing (Figure 15). Refer to the Wiring Schematic (Fig­ure 17) for pin connections.
Remote Control Panels
Onan offers harnesses of various lengths with mat­ing receptacles and three remote control kits as fol­lows:
Remote switch / status lamp.Remote switch / status lamp and hour meter.Remote switch / status lamp and DC voltmeter.
If another source is used for the remote panel: The control switch should be a two-pole, momentary-
contact, center-return/center-off type of switch with an indicator light.
nect to the wiring from the remote panel. Use in­sulated 18 AWG ( 1 mm
2
) copper conductors for
the wiring from the remote panel.
Keep control leads away from AC power leads to re-
duce the possibility of erratic operation due to in­duced signals.
Seal the hole where the leads enter the interior of the
vehicle to keep out exhaust gas. Use silicone rubber or an equivalent type of sealant.
BATTERY CONNECTIONS
WARNING
cause severe personal injury or death. Do not connect the starting battery until so instructed in Installation Review and Startup. Make sure an automatic genset starting system is disabled.
Accidental starting of the genset can
Battery Capacity
The genset has a 12 VDC, negative-ground control and starting system. See Specifications for the re- quirements for cranking batteries.
The total load connected to P2-E (Switched B+)
should not exceed 2 amp.
The total load connected to P2-F (Status Light)
should not exceed 2 amp.
Wiring Methods
WARNING
wiring openings into the vehicle interior to keep out exhaust gas.
Remove the AC terminal access cover and remove
one of the control wiring knockouts.
Pull out the remote control connector plug, fit the
bushing around the connector leads into the knockout slot and secure the access cover.
Snap the connector plug and harness receptacle to-
gether.
If the harness does not have a plug for connections
at the control panel, use solder-type butt con­nectors and heat-shrink insulation tubing to con-
EXHAUST GAS IS DEADLY! Seal all
Battery Recharging
The genset is equipped with a 10-amp, regulated­voltage battery charger.
Battery Compartment
Batteries must be mounted in a separate compart­ment from that of the genset and away from spark­producing equipment. An enclosed compartment must have openings of at least 1.7 square inches (11 square centimeters) at the top and bottom for ventilation of battery gasses. Batteries should be mounted such that spills and leaks will not drip acid on fuel lines, wiring and other equipment that could be damaged.
WARNING
drogen gas given off by the battery, causing se­vere personal injury. The battery compartment must be ventilated and must isolate the battery from spark-producing equipment.
Arcing can ignite the explosive hy-
Copyright 2016 Cummins Inc.
23
Page 28
Battery Cables
Battery wiring methods must be in accordance with the National Electrical Code or IEC 60364-7-708, as appropriate.
Size battery cables according to Table 3. The current path between the genset and the negative () battery terminal must also be able to carry full cranking cur­rent without causing excessive voltage drop. It is highly recommended that a full-length cable be used to connect the genset to the negative (−) battery ter- minal (Figure 1 1). Note also that codes may require a bonding conductor between the genset and vehicle frame and between the battery and vehicle frame.
If the vehicle frame is used as the path between the negative () battery terminal and the genset (Fig­ure 12), all frame members in the path of battery cranking currents must have substantial cross sec­tions. The electrical resistance of riveted or bolted frame joints must also be carefully considered, espe­cially if the joints will be exposed to corrosive condi­tions. A cable sized according to Table 3 must be used to connect the frame to the designated negative () terminal on the genset (Figure 12). The genset
mounting bolts are not considered adequate means for bonding the genset to the vehicle frame, either for the purpose of carrying crank­ing currents or for complying with requirements for genset/system grounding.
WARNING
lines can lead to fire and severe personal injury or death. Keep battery cables away from fuel lines.
Routing battery cables with fuel
TABLE 3. BATTERY CABLE SIZES FOR AMBIENT
TEMPERATURES DOWN TO −20 F (−29 C)
TOTAL CABLE LENGTH,
FEET (METERS)
0 to 15 (0 to 4.5) 0* (50)
16 to 20 (4.5 to 6) 000 (95)
* − A total length of up to 25 feet (7.6 meters) may be used in warmer climates or when battery capacity totals at least 1200 CCA (Cold Cranking Amps).
SIZE PER TABLE 3
GENSET
+
VEHICLE FRAME
FIGURE 11. FULL-LENGTH CABLE FROM
BATTERY NEGATIVE (−) TERMINAL
GENSET
+
VEHICLE FRAME
FIGURE 12. VEHICLE FRAME AS PATH FROM
BATTERY NEGATIVE (−) TERMINAL
8 AWG
2
(10mm
MINIMUM
SIZE PER TABLE 3
)
CABLE SIZE,
AWG (mm
+
BAT
+
BAT
2
)
Route battery cables away from fuel lines and hot en­gine exhaust components. Battery cables should be accessible for inspection and replacement, pro­tected from damage and secured to prevent chafing due to vibration.
24
Copyright 2016 Cummins Inc.
Page 29
Genset Bonding Terminal
The negative (−) battery cable terminal shown in Fig- ure 13 is also the bonding terminal for grounding the genset to the vehicle chassis. If the grounding cable is also going to carry starter motor current, it must be sized the same as the battery cables.
Connecting Battery and Bonding Cables
Terminate the battery cables with ring terminals sized for the 5/16 inch genset terminal screws (Fig­ure 13). Permanently mark each end of each cable as to its polarity, positive (+) or negative (). After making sure the battery cables are not connected at the battery and that an automatic genset starting sys­tem is disabled, connect the battery and grounding cables to the genset. Torque the terminals to 7.5 lb-ft (10 Nm).
POSITIVE (+)
NEGATIVE (−)
FIGURE 13. BATTERY CABLE TERMINALS
Copyright 2016 Cummins Inc.
25
Page 30
THIS PAGE IS INTENDED TO BE BLANK
26
Copyright 2016 Cummins Inc.
Page 31
Installation Review and Startup
LOCATION
HOT AIR RECIRCULATION TEST
A representative installation of the genset must be tested to determine that the genset will not overheat due to recirculation of hot air back into the genset.
Test Method
Complete a representative installation. Conduct the test in a well ventilated space in which
carbon monoxide cannot accumulate, but that is protected from cross drafts that could affect tem­perature measurements.
Connect a large, constant load to the genset. If a load
bank is available, connect at least 3/4 full load. If not, connect and run the largest combination of constant loads that can be kept on during the test without tripping the genset circuit breaker. For example, run a combination of air condition­ers and lights. Make sure air conditioners stay on and do not cycle during the test.
Measure temperatures with thermocouples not
heavier than No. 24 AWG (0.21 mm
Measure genset inlet air temperature with one ther-
mocouple tied in the middle of the inlet air grille (Figure 14).
Measure ambient air temperature with a shielded
thermocouple within 4 feet (1.2 meters) of the genset and at approximately the same height. Make sure the thermocouple will not b e a ffected
2
).
by warm air discharged from the genset or by sunlight. Use 2 inch diameter white PVC piping at least 6 inches long as a thermocouple shield.
Close all genset compartment doors and run the
genset for at least 90 minutes. Record tempera­tures at 15 minute intervals. See Table 4 for an example of how the data can be arranged for re­cording and analysis.
TABLE 4. TEMPERATURE DATA
TEMPERATURE C (F)
THERMOCOUPLE
AMBIENT AIR
INLET AIR
Time Of Reading
Test Requirement
The rise in inlet air temperature over ambient air tem­perature must not exceed 15F (8C). A rise in inlet air temperature indicates hot air recirculation. If the rise exceeds the requirement, steps must be taken to reduce recirculation to an acceptable level. Review Mounting, Location and Venting (Page 11).
CAUTION
tures can reduce maximum genset power if the air temperature rise in this test is on the high end of the acceptable range.
High ambient operating tempera-
Copyright 2016 Cummins Inc.
AMBIENT AIR
INLET AIR
FIGURE 14. THERMOCOUPLE LOCATIONS
27
Page 32
INSTALLATION REVIEW
Before starting the genset inspect the installation and check off ( can be answered “YES”. If a question cannot be checked off, review the appropriate section in the manual.
[ ] Is the operator’s console easily accessible for
starting and stopping the genset, resetting cir­cuit breakers and checking and adding engine
coolant? [ ] Is the genset securely bolted in place? [ ] Is there clearance all around the genset? [ ] Are the cooling and combustion air inlet and out-
let openings free of obstructions? [ ] Is there easy access for draining the engine oil? [ ] Is there easy access for draining the engine
coolant? [ ] Is there easy access for changing the air filter,
checking oil level and adding oil? [ ] Is there easy access for cleaning out the spark-
arrest muffler? [ ] Are all tailpipe connections tight and all hangers
and support straps secure? [ ] Does the tailpipe terminate at least 1 inch
(25 mm) beyond the perimeter of the vehicle
and at least 6 inches (153 mm) away from any
opening into the vehicle? [ ] Is the tailpipe routed such that it is not likely to be
struck while the vehicle is moving? [ ] Is the genset located outside the interior space
of the vehicle and separated by approved vapor-
tight and fire-resistive materials? [ ] Are all wiring holes into the vehicle interior (in-
side and outside conduit connectors) sealed to
keep out exhaust gas? [ ] Have the AC output connections been made
properly. [ ] Have properly sized batteries and battery
cables been installed? [ ] Have the battery cables been secured at suffi-
cient intervals to prevent chaffing and contact
with sharp edges, fuel lines and hot exhaust
parts? [ ] Is the genset bonding terminal (negative [−] bat-
tery cable terminal) properly grounded to the ve-
hicle chassis? [ ] Are all fuel connections tight? [ ] Have the fuel lines been secured at sufficient in-
tervals to prevent chaffing and contact with
) each of the following questions if it
sharp edges, electrical wiring and hot exhaust parts?
[ ] Is the genset protected from direct road splash,
rain and snow?
[ ] Does the genset clear the ground by at least
12 inches (305 mm)?
[ ] Has the HOT AIR RECIRCULATION TEST
been conducted? Are the results acceptable?
STARTUP
When all installation requirements have been met, connect the battery cables to the battery, positive (+) cable first.
WARNING
switches or other equipment, and flames or sparks, can ignite battery gas causing severe personal injury. To prevent injury:
fore working on or near
OFF away from battery nect charger before cables
Disconnect negative () cable first and
Read through the Operator Manual and perform the maintenance and pre-start checks instructed. The genset is shipped from the factory with proper levels of engine oil and coolant, which should nevertheless be checked before the genset is started. Start and operate the genset, following all the instructions and precautions in the Operator Manual.
WARNING
operate the genset when the vehicle is indoors unless there is ample fresh air ventilation.
Check for fuel, coolant and exhaust leaks and unusu­al noises while the genset is running under full and intermediate loads. To calculate electrical loads see POWERING EQUIPMENT in the Operator Manual. Do not place the genset in service until all leaks have been fixed and operation is satisfactory.
Arcing at battery terminals or in light
Ventilate battery area be-
battery
Wear safety glasses Do not smoke Switch work light ON or
Stop genset and discon-
disconnecting battery
reconnect it last.
EXHAUST GAS IS DEADLY! Do not
28
Copyright 2016 Cummins Inc.
Page 33
Specifications
HDKBB HDKBC
GENSET CONTROLLER: Integrated Microprocessor Based Engine and Generator Controller GENERATOR: Two-Bearing, Two-Pole Rotating Field, “Poly-Vee” Belt Drive
Power (@1.0 PF) 4800 W 5000 W RPM 3000 3600 Frequency 50 Hz 60 Hz Voltage 230V 1-Ph 120V 1-Ph, 120/240V 1-Ph, or 120/240V 3-Ph Current 21 A 41.7/20.8 A or 12 A (3-Ph) Circuit Breakers 2-pole 25 A (1 pole used) 2-pole 25 A (1-Ph) or 3-pole 15 A (3-Ph)
FUEL CONSUMPTION:
No-load Half-load Full-load
ENGINE: 2-Cylinder In-Line, Water-Cooled, Indirect-Injection, 4-Stroke Cycle Diesel
RPM 2880 2880 Bore 2.64 in (67 mm) 2.64 in (67 mm) Stroke 2.68 in (68 mm) 2.68 in (68 mm) Displacement 29.23 in3 (479 cc) 29.23 in3 (479 cc) Compression Ratio 23 : 1 23 : 1 Injection Order 12 12 Engine Timing 18.25 to 19.75 BTDC 18.25 to 19.75 BTDC Fuel Nozzle Injection
Pressure Valve Lash: Intake & Ex-
haust (cold) Oil Capacity
(with filter) Cooling System
Capacity
0.0057 0.0073 inch (0.145 0.185 mm) 0.0057 0.0073 inch (0.145 0.185 mm)
DC SYSTEM:
Nominal Battery Voltage
Minimum Battery Capacity CCA (Cold Cranking Amps)
Fuse F1 (control, start and glow plug circuits)
650 amps down to 20F (29C)
WEIGHT: 400 lbs (181 kg) SIZE (L x W x H): 34.5 x 22.9 x 20.3 in (876 x 581.2 x 514.4 mm) SOUND LEVEL: 68 dB(A) @ 10 ft (3m) before installation and @ 1/2-load
0.20 gph (0.74 lph)
0.32 gph (1.23 lph)
0.54 gph (2.04 lph)
1991 psi (13.73 mPa) 1991 psi (13.73 mPa)
2 quart (1.9 liter) 2 quart (1.9 liter)
3.0 quart (2.8 liter) 3.0 quart (2.8 liter)
12 volts 12 volts
475 amps down to 0F (17C)
650 amps down to 20F (29C)
30 amp mini-bayonet 30 amp mini-bayonet
0.25 gph (0.95 lph)
0.39 gph (1.47 lph)
0.60 gph (2.27 lph)
475 amps down to 0F (17C)
Copyright 2016 Cummins Inc.
29
Page 34
THIS PAGE IS INTENDED TO BE BLANK
30
Copyright 2016 Cummins Inc.
Page 35
FIGURE 15. OUTLINE DRAWING—SHEET 1
Copyright 2016 Cummins Inc.
31
Page 36
FIGURE 16. OUTLINE DRAWING—SHEET 2
32
Copyright 2016 Cummins Inc.
Page 37
FIGURE 17. WIRING DIAGRAM—SHEET 1
Copyright 2016 Cummins Inc.
33
Page 38
FIGURE 18. WIRING DIAGRAM—SHEET 2
34
Copyright 2016 Cummins Inc.
Page 39
Page 40
power.cummins.com
Copyright E 2016 Cummins Inc. All rights reserved. Cummins, Onan, the “C” logo, and “Performance you rely on.” are trademarks of Cummins Inc. Other company, product, or service names may be trademarks or service marks of others. Specifications are subject to change without notice.
Loading...