CUMMINS GQMA, GQNA, GQMB, GQNB, GQPB Installation Manual

...
Page 1
Installation Manual
Generator Set
GQMA GQMB
GQNA GQNB
GQPB GQKA
GQNC
GQPC
English 11--2007 983--0604
Page 2
!!
contains chemicals known to the State
of California to cause cancer, birth
defects or other reproductive harm.
Page 3

Table of Contents

IMPORTANT SAFETY INSTRUCTIONS iii........................................
1. INTRODUCTION 1-1..........................................................
About This Manual 1-1....................................................
Installation Overview 1-1..................................................
2. LOCATION AND MOUNTING 2-1...............................................
Location 2-1.............................................................
Access To Set and Lighting 2-1.............................................
Lifting 2-1................................................................
Mounting 2-2.............................................................
Foundation 2-3...........................................................
Checking Elevation of Spring Isolator Locations 2-3...........................
Shimming Isolators 2-5....................................................
Aligning Engine, Gear Box and Generator 2-6................................
3. MECHANICAL CONNECTIONS 3-1.............................................
Fuel System 3-1..........................................................
Exhaust System 3-2......................................................
Ventilation 3-3............................................................
Coolant System 3-3.......................................................
Air Starting (Optional) 3-4..................................................
4. DC AND CONTROL CONNECTIONS 4-1........................................
Generator Control Panel (GCP) 4-1.........................................
Customer Terminals (GCP) 4-1.............................................
Battery Starting Systems 4-3...............................................
5. AUXILIARY EQUIPMENT CONNECTIONS 5-1...................................
Starting Battery Charger 5-1...............................................
Power Supply Unit 5-4....................................................
i
Page 4
6. AC SUPPLY AND POWER CONNECTIONS 6 -1..................................
AC Wiring 6-1............................................................
Insulation Resistance (Megger) & Polarization Index (PI) Testing 6-5............
7. PRESTART PREPARATIONS 7-1...............................................
Prestart Preparations 7-1..................................................
Electrical System 7-1......................................................
Generator Set Installation/ Pre-Commissioning Checklist 7-2...................
Control and Protection Settings 7-5.........................................
TYPICAL GENSET WIRING CONNECTIONS A-1...................................
CUSTOMER WIRING CONNECTIONS A-2.........................................
TYPICAL LOW-PRESSURE GAS TRAIN (7 PSI MAXIMUM) A-3......................
TYPICAL HIGH-PRESSURE GAS TRAIN A-4......................................
TYPICAL GAS TRAIN INSTALLATION A-5.........................................
RECOMMENDED COOLANT SYSTEM SCHEMATIC A-6............................
GENERATOR WIRING DIAGRAM A-7.............................................
ii
Page 5
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS -- This manualcon-
tains important instructions that should be followed during installation and maintenance of the genera­tor and batteries.
Before operating the generator set (genset),
read the Operator’s Manual and become familiar with it and the equipment. Safe and efficient op-
eration can be achieved only if the equipment is properly operated and maintained. Many acci-
dents are caused by failure to follow fundamental rules and precautions.
The following symbols, found throughout this manual, alert you to potentially dangerous condi­tions to the operator, service personnel, or the equipment.
DANGER
hazards which will result in severe personal in­jury or death.
WARNING
unsafe practice which can result in severe per­sonal injury or death.
This symbol warns of immediate
This symbol refers to a hazard or
emit a highly explosive hydrogen gas that can be ignited by arcing, sparking, smoking, etc.
EXHAUST GASES ARE DEADLY
Provide an adequate exhaust system to prop­erly expel discharged gases away from en­closed or sheltered areas and areas where in­dividuals are likely to congregate. Visually and audibly inspect the exhaust daily for leaks per the maintenance schedule. Make sure that ex­haust manifolds are secured and not warped. Do not use exhaust gases to heat a compart­ment. Exhaust height should be tall enough to help clear gases, avoid accumulation of snow or in accordance with local mechanical code.
Be sure the unit is well ventilated.
Engine exhaust and some of its constituents
are k nown to the state of California to cause cancer, birth defects, and other reproductive harm.
MOVING PARTS CAN CAUSE SEVERE PERSONAL INJURY OR DEATH
CAUTION
unsafe practice which can result in personal in­jury or product or property damage.
This symbol refers to a hazard or
FUEL AND FUMES ARE FLAMMABLE
Fire, explosion, and personal injury or death can re­sult from improper practices.
Natural gas is lighter than air, and will tend to gather under hoods. Propane is heavier than air, and will tend to gather in sumps or low areas. NFPA code requires all persons han­dling propane to be trained and qualified.
Be sure all fuel supplies have a positive shutoff valve.
Be sure battery area has been well-ventilated prior to servicing near it. Lead-acid batteries
Keep your hands, clothing, and jewelry away from moving parts. Loose clothing and jewelry can become caught in moving parts.
Before starting work on the generator set, dis­connect battery charger from its AC source, then disconnect starting batteries, negative (-) cable first. This will prevent accidental starting.
To prevent accidental air starting, make sure the air supply line is connected until the genera­tor set is ready to start.
Make sure that fasteners on the generator set are secure. Tighten supports and clamps, keep guards in position over fans, drive belts, etc.
If adjustment must be made while the unit is running, use extreme caution around hot man­ifolds, moving parts, etc.
iii
Page 6
ELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL INJURY OR DEATH
Remove electric power before removing pro­tective shields or touching electrical equip­ment. Use rubber insulative mats placed on dry wood platforms over floors that are metal or concrete when around electrical equipment. Do not wear damp clothing (particularly wet shoes) or allow skin surface to be damp when handling electrical equipment. Do not wear jewelry. Jewelry can short out electrical con­tacts and cause shock or burning.
Use extreme caution when working on electri­cal components. High voltages can cause inju­ry or death. DO NOT tamper with interlocks.
Follow all applicable state and local electrical codes. Have all electrical installations per­formed by a qualified licensed electrician. Tag and lock open switches to avoid accidental clo­sure.
DO NOT CONNECT GENERATOR SET DI­RECTLY TO ANY BUILDING ELECTRICAL SYSTEM. Hazardous voltages can flow from the generator set into the utility line. This creates a potential for electrocution or property damage. Connect only through an approved isolation switch or an approved paralleling de­vice.
MEDIUM VOLTAGE GENERATOR SETS (601V to 15kV)
Medium voltage acts differently than low volt­age. Special equipment and training is required to work on or around medium voltage equip­ment. Operation and maintenance must b e done only by persons trained and qualified to work on such devices. Improper use or proce­dures will result in severe personal injury or death.
GENERAL SAFETY PRECAUTIONS
Coolants under pressure have a higher boiling point than water. DO NOT open a radiator or heat exchanger pressure cap while the engine is running. Allow the generator set to cool and bleed the system pressure first.
Used engine oils have been identified by some state or federal agencies as causing cancer or reproductive toxicity. When checking or chang­ing engine oil, take care not to ingest, breathe the fumes, or contact used oil.
Keep multi-class ABC fire extinguishers handy. Class A fires involve ordinary combustible ma­terials such as wood and cloth; Class B fires, combustible and flammable liquid fuels and gaseous fuels; Class C fires, live electrical equipment. (ref. NFPA No. 10).
Make sure that rags are not left on or near the engine.
Make sure generator set is mounted in a man­ner to prevent combustible materials from ac­cumulating under the unit.
Remove all unnecessary grease and oil from the unit. Accumulated grease and oil can cause overheating and engine damage which present a potential fire hazard.
Keep the generator set and the surrounding area clean and free from obstructions. Remove any debris from the set and keep the floor clean and dry.
Do not work on this equipment when mentally or physically fatigued, or after consuming any alcohol or drug that makes the operation of equipment unsafe.
Substances in exhaust gases have been iden­tified by some state or federal agencies as causing cancer or reproductive toxicity. Take care not to breath or ingest or come into contact with exhaust gases.
Do not work on energized equipment. Unau­thorized personnel must not be permitted near energized equipment. Due to the nature of me­dium voltage electrical equipment, induced voltage remains even after the equipment is disconnected from the power source. Plan the time for maintenance with authorized person­nel so that the equipment can be de-energized and safely grounded.
Do not store any flammable liquids, such as fuel, cleaners, oil, etc., near the generator set. A fire or explosion could result.
Wear hearing protection when going near an operating generator set.
To prevent serious burns, avoid contact with hot metal parts such as radiator, turbo charger and exhaust system.
KEEP THIS MANUAL NEAR THE GENSET FOR EASY REFERENCE
iv
Page 7
1. Introduction
ABOUT THIS MANUAL
This manual provides installation instructions for the generator set models listed on the front cover. This includes the following information:
Mounting Recommendations - for fastening generator set to base and space requirements for normal operation and service.
Mechanical and Electrical Connections ­covers most aspects of the generator set instal­lation.
Installation Checklist -- reference checks upon completion of installation.
Prestart -- checklist of items or procedures needed to prepare generator set for operation.
Initial Startup -- test complete system to en­sure proper installation, satisfactory perfor­mance, and safe operation. Refer to Operators Manual for troubleshooting information.
This manual DOES NOT provide application infor­mation for selecting a generator set or designing the complete installation. If it is necessary to design the various integrated systems (fuel, exhaust, cooling, etc.), additional information is required. Review standard installation practices. For engineering data specific to the generator set, refer to the Speci- fication and Data Sheets. For application informa­tion, refer to the Application Manual for Liquid Cooled Generator Sets (T030) found in the Cum­mins Power Generation Power Suite Library avail­ableonCD
1
.
INSTALLATION OVERVIEW
These installation recommendations apply to typi ­cal installations with standard model generator sets. Whenever possible, these recommendations
also cover factory designed options or modifica­tions. However, because of the many variables in any installation, it is not possible to provide specific recommendations for every situation. If there are any questions not answered by this manual, contact your nearest Cummins Power Generation distribu­tor for assistance.
A power system must be carefully planned and cor­rectly installed for proper operation. This involves two essential elements: application and installation.
Application
Application (as it applies to generator set installa­tions) refers to the design of the complete power system that usually includes power distribution equipment, transfer switches, ventilation equip­ment, mounting pads, and cooling, exhaust, and fuel systems. Each component must be correctly designed so the complete system will function as in­tended. Application and design is an engineering function generally done by specifying engineers or other trained specialists. Specifying engineers or other trained specialists are responsible for the de ­sign of the complete power system and for selecting the materials and products required.
Installation
Installation refers to the actual set-up and assembly of the power system. The installers set up and con­nect the various components of the system as spe­cified in the system design plan. The complexity of the system normally requires the special skills of qualified electricians, plumbers, sheet metal work­ers, etc. to complete the v arious segments of the installation. This is necessary so all components are assembled using standard methods and prac­tices. Figure 1-1 provides a view of a typical genset.
1. Alternatively, go to the WEB site, http://www.cumminspower.com/library/appengineering/appengineering.jhtml, to view and print the application manual.
1-1
Page 8
Safety Considerations
The generator set has been carefully designed to provide safe and efficient service when properly installed, maintained, and operated. However, the overall safety and reliability of the complete system is dependent on many factors outside the control of the generator set manufacturer. To avoid possible safety hazards, make all mechanical and electrical connections to the generator set exactly as speci­fied in this manual. All systems external to the gen­erator (fuel, exhaust, electrical, etc.) must comply with all applicable codes. Make certain all required inspections and tests have been completed and all
code requirements have been satisfied before certi­fying the installation is complete and ready for ser­vice.
Product Modifications
Agency certified products purchased from Cum­mins Power Generation comply only with those spe­cific requirements and as noted on company prod­uct specification s heets. Subsequent modifications must meet commonly accepted engineering prac­tices and/or local and national codes and stan­dards. Product modifications must be submitted to the local authority having jurisdiction for approval.
FIGURE 1-1. TYPICAL GENSET -- RIGHT HAND VIEW
1-2
Page 9
2. Location and Mounting
Generator set installations must be engineered so the generator set will function properly under the ex­pected load conditions. Use these instructions as a general guide only. Follow the instructions of the consulting engineer when locating or installing any components. The complete installation must com­ply with all local and state building codes, fire ordi­nances, and other applicable regulations.
Requirements to be considered prior to installation:
Level mounting surface
Adequate cooling air
Adequate fresh induction air
Discharge of generator set air
Discharge of exhaust gases
Non-combustible mounting surface
Electrical connections
Accessibility for operation and servicing
Noise levels
Vibration isolation
LOCATION
Generator set location is decided mainly by related systems such as v entilation, wiring, fuel, and ex­haust. The set should be located as near as pos­sible to the main power service entrance. Exhaust must not be able to enter or accumulate around in­habited areas.
Provide a location away from extreme ambient tem­peratures and protect the generator set from ad­verse weather conditions.
ACCESS TO SET AND LIGHTING
Generally, at least 1 meter (3 feet) of clearance should be provided on all sides of the generator set for maintenance and service access.
Lighting should be adequate for operation, mainte­nance and service operations and should be con­nected on the load side of the paralleling switchgear so that it is available at all times.
LIFTING
See the generator set Operators Manual for lifting details.
WARNING
INCORRECT INSTALLATION, SERVICE OR PARTS REPLACEMENT CAN RESULT IN SEVERE PERSONAL INJURY, DEATH, AND/OR EQUIPMENT DAMAGE. SERVICE PERSONNEL MUST BE TRAINED AND EXPERIENCED TO PERFORM ELECTRICAL AND MECHANICAL COM­PONENT INSTALLATION.
IMPORTANT
DEPENDING ON LOCATION AND INTENDED USE, FEDERAL, STATE OR LOCAL LAWS AND REGULATIONS MAY REQUIRE THAT YOU OBTAIN AN AIR QUALITY EMISSIONS PERMIT BE­FORE BEGINNING INSTALLATION OF THE GENSET. MAKE SURE TO CONSULT LOCAL POLLUTION CONTROL AND AIR QUALITY AUTHORITIES BEFORE COMPLETING CONSTRUCTION PLANS.
2-1
Page 10
MOUNTING
in harmful resonances and may void the genset warranty.
The engine-generator assembly is mounted directly to a skid-base. Vibration isolation between the skid­base and the supporting structure is always re­quired. The use of unapproved isolators may result
Locate the vibration isolators (Figure 2-1) as shown on the generator set Outline Drawing referenced in the Data Sheet. Follow the manufacturers instruc­tions for anchoring, assembly and leveling.
FIGURE 2-1. VIBRATION ISOLATORS
2-2
Page 11
FOUNDATION
The foundation to which the genset mounts is equally as important as other parts of the installa­tion. The foundation should provide a level, flat sur­face for the genset. Also, the foundation pad should be isolated from the rest of the concrete flatwork and the joint filled with a flexible caulking.
the foundation weight should be at least 75, 200 pounds. The density of concrete is approximately
0.084 lbs/in
3
. The depth of the foundation is calcu­lated by dividing the weight by the density times the area: 75,200 lbs
÷ (0.084 lbs/in
3
x 288 in. x 79 in) = 39 inches. Therefore, the foundation in this example has a length of 288 inches, a width of 79 inches, and a depth of 39inches.
Foundation size is determined by the dimensions and weight of the equipment to be installed. The length and width should be a minimum of 18 inches longer and wider than the genset’s footprint. Length and width of the genset are provided on the general assembly drawings for each specific model.
The area for the genset’s foundation should be a continuous surface with no significant interruptions such as trenches for piping. Conduit stub--ups are acceptable as long as their position does not inter­fere with the location of the genset mounting points. The locations of the mounting points are shown on the general assembly drawings for each specific model.
The depth of the foundation is determined by the weight of the equipment to be mounted on the foundation. In order to provide sufficient strength and vibration damping ability, the foundation should be deep enough to make the weight of the founda ­tion equal to 1.5 times the weight of installed equip­ment.
For example, a 1750 GQPB Genset with a P80R frame alternator is to be installed. The genset’s out­line drawing gives this model’s dimensions as 270 inches long and 61 inches wide. By adding 18 inch­es to the length and width of the genset, the recom­mended foundation dimensions are 288 inches long by 79 inches wide. The outline drawing also provides a wet weight for the genset of approxi­mately 50,130 pounds. Since the desired weight of the foundation is 1.5 times the weight of the genset,
CHECKING ELEVATION OF SPRING
ISOLATOR LOCATIONS
In addition to proper size, the finish of the founda­tion must allow for proper mounting of the spring isolators. The foundation area should be level and flat within 0.25 inches. The spring isolators used to mount the genset are for vibration isolation and to provide movement of the genset during starting, loading, and unloading. They are not to be used to compensate for unlevel and uneven foundations.
After the foundation is installed but before the gen­set is in place, check the elevations of the spring iso­lator locations. The locations for each genset’s spring isolators are provided by its general assem­bly drawing.
The elevation check is easily done using a transit and sight rod. To check for level along the founda­tion length, the difference between the elevation of the spring isolator locations at the front and rear of the genset are compared. The difference between the two locations should be 0.25 inches or less. To check for level across the width of the foundation, the elevation of the spring isolators at the front are compared to each other, and the elevation of the spring isolators at the back are compared to each other. To check the flatness of the foundation, the elevation of all spring isolator locations are compared, and the difference between all locations should be 0.25 inches or less. Refer to Figure 2-2 for an example of the measurements of spring isolator locations.
2-3
Page 12
DISTANCE FROM
ISOLATOR LOCATION
TO TRANSIT LINE
TRANSIT LEVEL SIGHT LINE
X4
ALTERNATOR
X1 -- 4 SPRING ISOLATOR LOCATIONS
FIGURE 2-2. MEASUREMENT OF SPRING ISOLATOR ELEVATIONS
Figure 2-2 represents typical spring isolator loca­tions for one side of the genset. The measurements at X1 and X4 are compared for level along the length. The measurements at X1 for both sides are compared, and the measurements at X4 for both sides are compared to determine level across the foundation width. The measurements at all loca­tions for both sides are compared to determine flat­ness. The following measurements represent dif­ferent situations.
A--BANK B--BANK X1 = 48 INCHES
X2 = 48.25 INCHES
X3 = 48.125 INCHES
X4 = 48.25 INCHES
X1 = 48.25 INCHES
X2 = 48 INCHES
X3 = 48 INCHES
X4 = 48.125 INCHES
Based on the preceding measurements, the foundation is level along the length of the A--Bank within 0.25 inches, and the B--Bank is level within
0.125 inches. The foundation is level across the width within 0.25 inches at the engine end and
0.125 at the alternator end. By comparing all mea-
X3
FOUNDATION
X2
ENGINE
XI
surements, the foundation is flat within 0.25 inches. The conditions of this example, where the founda­tion is level and flat within specification, is uncom­mon. The following set of measurements are more typical.
A--BANK B--BANK X1 = 48.5 INCHES
X2 = 48.75 INCHES
X3 = 48.25 INCHES
X4 = 48.25 INCHES
X1 = 48.25 INCHES
X2 = 48.5 INCHES
X3 = 48.625 INCHES
X4 = 48 INCHES
Based on the preceding measurements, the foundation is level along the length and width within specification. However, a comparison of all the measurement locations shows that the foundation is outside the specification for flatness. The mea­surements are graphed in Figure 2-3 to show the profile of the foundation.
2-4
Page 13
DIFFERENCE FROM
HIGH POINt
0
-- 1 / 8
-- 1 / 4
FOUNDATION PROFILE
x1 x2
x3 x4
A--BANK
-- 3 / 8
-- 1 / 2
-- 5 / 8
-- 3 / 4
-- 7 / 8
ISOLATOR LOCATION
FIGURE 2-3. GRAPHICAL REPRESENTATION OF FOUNDATION PROFILE
In Figure 2-3, the values at the top of the graph rep­resent the isolator locations, and the values on the left side of the graph show the differences from the elevation of the highest isolator location on the foundation. By using a transit to measure eleva­tions, the recorded value is the distance to the foundation from a level line above the foundation. When measured in this way, the numerically lowest value represents the highest point on the founda­tion. In this example, X4 located on the B--Bank side of the genset measures 48 inches, which is the low­est numerical elevation measurement and the high­est point of the foundation profile. The difference of all other locations from the highest point shows the distance each point is below it. These values are plotted to create the foundation profile. The graph shows that four of the isolator locations exceed the specification of 0.25 inches for flatness: A--Bank X1 and X2, and B--Bank X2 and X3. This is a situation where isolator locations should be adjusted to be within specification for level and flatness before the genset is installed.
SHIMMING ISOLATORS
Isolator locations can be shimmed to meet the spec­ification for level and flatness for foundations with conditions similar to those in the preceding exam­ple. The simplest approach is to shim an isolator
B--BANK
location before the isolators and genset are in place. The shims are placed under the isolator to raise its elevation to equal the highest point.
Returning to the preceding example and graph, the elevation of shim heights is easily determined. As the highest elevation point, there is no shim re­quired at spring isolator location X4 on the B--bank. All of the other locations are shimmed to equal it. Shim heights at these locations are:
A--BANK B--BANK X1 = 1/2 INCH
X2 = 3/4 INCH
X3 = 1/4 INCH
X4 = 1/4 INCH
X1 = 1/4 INCH
X2 = 1/2 INCH
X3 = 5/8 INCH
X4 = 0 INCH
Some of the isolator locations in the example are within the level and flatness specification, but as long as shimming was necessary at certain loca­tions, it requires minimal extra material and labor to adjust all locations. It is critical when installing shims to ensure that the size of the shim sufficiently covers the footprint of the isolator in order to provide a uni­form surface beneath the isolator to support the weight it carries.
2-5
Page 14
ALIGNING ENGINE, GEAR BOX AND
GENERATOR
Proper alignment of the engine, gear box and gen­erator is necessary to avoid premature wear and im­proper operation of the genset.
Consult an authorized Cummins representative for assistance with alignment of the gearbox generator sets.
2-6
Page 15
3. Mechanical Connections
Generator set mechanical system installation in­cludes connecting fuel, exhaust, ventilation, cooling and starting systems.
FUEL SYSTEM
Pages A-3 and A-4 illustrate typical factory avail­able gas train kits and Page A-5 a typical installa­tion.
WARNING
explosive and can cause severe personal injury or death. Do not smoke if you smell gas or are near fuel tanks or fuel-burning equipment or are in an area sharing ventilation with such equip­ment. Keep flames, sparks, pilot lights, electri­cal arcs and arc-producing equipment and all other sources of ignition well away. Keep a type ABC fire extinguisher handy.
WARNING
cause gas leaks which can lead to fire and se­vere personal injury or death. Gas supply pres­sure must be adjusted to generator set Specifi­cations by trained and experienced persons.
WARNING
quately ventilated space can lead to explosive accumulations of gas. Venting of gas train com­ponents and generator set room ventilation must be in accordance with local codes.
Gaseous-fuel supply system design, materials, components, fabrication, assembly, installation, testing, inspection, operation and maintenance must comply with the applicable codes. See NFPA Standards Nos. 37 and 54.
Cleanliness is of the upmost importance in a fuel system. Make every effort to prevent the entrance of moisture, dirt or contaminants of any kind. Inspect and clean all pipework and fuel system components prior to assembly.
Gaseous fuels are flammable and
High gas supply pressure can
Gaseous fuel leaks into an inade-
genset Data Sheet for fuel consumption. For low­pressure gas supply systems the pressure range is 5to7psi (34to48kPa). For high-pressure gas supply systems the pressure droop from engine not running to full load should not exceed 20 percent.
Note: The engine gas solenoid valve must be pro­tected by a safety device to shut off gas flow in the event of a catastrophic failure of an upstream gas pressure regulator.
The high-pressure gas train (Page A-4) is such a safety device.
The low-pressure gas train (Page A-3) is NOT such a safety device. The installer must install a safety de­vice upstream of the low-pressure gas train.
1. Bolt the flexible gas hose supplied in the gas train kit directly to the engine gas solenoid valve. Make sure the flange has a gasket and that flange bolts are torqued to 37 lb-ft (50 N-m). See Page A-5.
2. Bolt the gas train (Page A-3 or A-4) to the flex­ible hose using a flange gasket. Rigidly support both flanges of the gas train. Up to 15 feet (4.5 meters) of piping built to suit and rigidly sup­ported on both ends may be located between the gas train and flexible hose (Page A-5). Make sure all flanges have gaskets and that flange bolts are torqued to 37 lb-ft (50 N-m).
The flanges between which the flexible hose is bolted must line up and be spaced such that the flexible hose fits without bending or being stretched or compressed. Also, the flange on the supply end must be rigidly supported to pre­vent engine vibration from causing resonance in the gas train.
WARNING
Failure of the flexible gas hose or gas train due to faulty installation can lead to fire or explosion. The installation must be in accordance with these instruc­tions.
The gas supply system must be sized and regulated to supply the generator set at full load. Refer to the
3. Weld the adapter pipe flange in the low-pres­sure gas train kit to the end of the supply piping.
3-1
Page 16
4. The gas solenoid valve on the engine must be vented safely to the outside of the building (Page A-4). A section of flexible gas vent hose must be installed at the solenoid valve to take up engine vibration. See the generator set Out­line Drawing for the location of the vent port and its fitting size. The pressure regulator in the high-pressure gas train kit must also be vented outside.
5. The pressure regulator in the gas train kit has been preadjusted at the factory to maintain 200 millibar at the gas inlet to the engine. Mea­sure the pressure at the engine inlet test port and readjusted as necessary. The regulator manufacturer’s instruction sheet is included in the kit.
EXHAUST SYSTEM
See the Generator Set Data Sheet for exhaust tem­perature, flow and maximum back pressure.
WARNING
haust system must be leak-free and convey all exhaust outside, away from windows, doors and vents. Do not use exhaust gases to heat a building or other enclosed space.
EXHAUST GAS IS DEADLY! The ex-
Flexible exhaust sections must not be used to com­pensate for misaligned piping or to form bends.
Avoid sharp bends by using sweeping, long radius elbows and provide adequate support for mufflers and piping.
Horizontal runs of exhaust piping should slope downwards away from the engine to a drain trap and plug, which should be located where the piping turns to rise vertically.
To prevent overheating that can lead to fire, route exhaust piping at least 12 inches (305 mm) away from combustible construction. Use approved thimbles where exhaust piping passes through combustible walls, ceilings and roofs. Where the minimum clearance cannot be maintained, piping may be shielded or insulated with material rated to withstand at least 1100°F (600°C). The surface of the insulation or shield must not exceed 160°F (71°C). Refer to Section 6-3 of NFPA 37, Stationary Combustion Engines and Gas Turbines for accept­ed design practices.
WARNING
Exhaust piping is very hot and can ignite combustible material. Route, shield or in­sulate exhaust piping to protect adjacent com­bustible materials.
Exhaust Piping
The exhaust system must meet local codes.
Pipe all exhaust gases outside, away from win­dows, doors and vents. The exhaust system must be gas tight. Exhaust gas must not be used to heat a building or other enclosed space.
The exhaust system must be supported indepen­dently of the engine. Supporting the weight of ex­haust piping on the turbocharger outlet flanges can lead to turbocharger failure. Use the flanged flexible bellows-type stainless steel tubes shipped with the generator set for exhaust connections.
CAUTION
chargers, do not support any part of the exhaust system on the turbocharger outlet flanges. Use the flanged flexible exhaust tubes provided.
Long runs of exhaust pipe (vertical or horizontal) should include sections of flexible, bellows-type stainless steel tube to take up thermal expansion.
To prevent damage to the turbo-
WARNING
Exhaust piping, mufflers and boil­ers are very hot and can cause severe burns. Shield or insulate exhaust piping and equip­ment where there is danger of personal contact.
The entire exhaust system must be accessible for visual inspection and repair.
Use rain caps when exhaust pipes discharge verti­cally.
Exhaust Heat Recovery Boilers
For installations in the U. S. A., a heat recovery boil­er must bear the appropriate ASME mark for fired hot water pressure vessels and be equipped with the appropriate pressure relief valve. The operating system must include an approved high temperature limit control.
WARNING
can cause severe personal injury or death. To reduce the risk of explosion, boiler construc­tion, pressure relief valves and safety controls must meet all local codes and regulations.
A heat recovery boiler explosion
3-2
Page 17
VENTILATION
Generator set room ventilation must remove the heat radiated to the ambient and make up the com­bustion air intake flow. See the Generator Set Data Sheet.
Locate air inlet and outlet openings to minimize the effects of wind and maximize convective air flow in the generator room. Size ventilation fans, louvers, and ducts so they are large enough to handle the re ­quired flow of air.
rates, maximum and minimum static heads and maximum pressure drops (friction). Refer to the Op­erator’s Manual for recommended coolant mix­tures.
Page A-6 illustrates schematically a recommended coolant system configuration designed to provide the following:
Coolant system pressurization and balancing between the HT and LT circuits
Coolant Deaeration
Forced ventilation air flow should be directed paral­lel with the crankshaft and flow from rear (alternator end) to the front of the engine.
The engine crankcase breather has specific routing requirements as follows:
The EcoVent exhaust hose inner diameter must be greater or equal to 2.25 inches (EcoV­ent discharge diameter)
The EcoVent exhaust must be vented to the at­mosphere and never vented to the engine room
The EcoVent exhaust hose or pipe must be monotonically rising
The EcoVent exhaust hose or pipe should dis­charge a minimum of 10 feet from the engine (room) air inlet, and preferably on the down wind side of the inlet.
See Section 4. DC Connections for connections to operate fans, louvers and dampers when the gener­ator set is started and running.
Volume for coolant thermal expansion
Coolant pressure relief if bladder fails in the ex-
pansion tank
Means to warn and shut down on low and high coolant pressures
Connection for draining coolant and filling from the bottom by means of a pump
Valves to isolate engine and heat exchangers during service
Mechanical gauges as backup and quick refer­ence for pressure and temperature on dis ­charge and return loops of LT and HT circuits (On a bladder tank system a single pressure gauge is all that is needed.)
Note 1: A bladder tank is recommended for more consistent system pressurization and balancing. Automatic pressure balancing reduces crossflow between the HT and LT coolant circuits.
Note 2: Static air vents should be placed at all the high points in the system to eliminate air traps.
COOLANT SYSTEM
When designing the high temperature (HT) and low temperature (LT) cooling systems, heat recovery, radiator or other heat dump systems, refer to the Generator Set Data Sheet for engine coolant vol­umes, maximum inlet and outlet temperatures, flow
Note 3: Follow t he pressure relief, initial bladder air pressure, and low and high pressure switch settings on Page A-6.
Note 4: The flexible coolant flange connectors pro­vided with the generator set must be used for con­nection to the coolant piping system. All coolant pip­ing must be Schedule 40 steel pipe.
3-3
Page 18
AIR STARTING (OPTIONAL)
See the Generator Set Data Sheet for air starting system requirements. Figure 3-1 illustrates the air starter connection.
WARNING
Accidental starting of the generator set can cause severe personal injury or death. To prevent accidental starting, do NOT connect the air supply line until the installation has been completed and the set is ready to be started.
1 INCH FLEX HOSE
GENSET START AIR SUPPLY-
CONNECTION POINT (1 INCH BSP)
FIGURE 3-1. AIR STARTER CONNECTION
3-4
Page 19
4. DC And Control Connections
Local regulations often require that wiring connec­tions be made by a licensed electrician, and that the installation be inspected and approved before op­eration. All connections, wire sizes, circuit protec­tion, materials used, etc. must conform to the re­quirements of electrical codes in effect at the instal­lation site.
WARNING
electrical hazard, resulting in severe personal injury or death and/or property and equipment damage.
Improper wiring can cause a fire or
GENERATOR CONTROL PANEL (GCP)
The Generator Control Panel (GCP) is a free stand­ing module that includes the Power Command Su­pervisor (PCS) and Human Machine Interface (HMI) and other customer interface features such as an emergency stop switch, gas valve switch and manual pre-lube push-button switch.
See page A-1 for an illustration of typical generator set connections, including connections to the GCP. There are two wiring harnesses that connect the GCP to the Genset Interface Box (GIB), which is mounted to the genset. The wiring harnesses are supplied by the factory and come in various lengths of 5, 10, 15, 20, 30, and 40 meters to accommodate the customer’s location for the genset. Cable length must be specified when the order for the genset is placed.
CUSTOMER TERMINALS (GCP)
Customer connections to the genset are located in the GCP on customer terminal block C (see Figure 4-1), and include: fault and alarm inputs, inputs and
outputs for genset and ancillary system control, connections for paralleling functions, and additional emergency stop inputs. See page A-2 for a list of customer terminals and their functions. At time of installation, check the current factory drawing for a correct list.
The modbus plus tap for connection of network communication lines is also located in the GCP.
The relay contacts for operating the remote control and annunciating devices connected at the custom­er terminals are rated at 5A @ 250VAC, 30VDC.
B+ fused at 6 amps (5 amps UL) is available at the customer terminals. See connection diagram on page A-2 or equivalent for correct terminal num­bers.
The terminal blocks in the GCP are suitable for a maximum wire size o f 16 AWG (2.5 mm
Refer to Cummins 900-0366 PowerCommand Net- work Installation and Operation manual for the type/ gauge wire to use for network connections.
To accommodate the motion of the generator set on its mounts, use flexible conduit and stranded con­ductors for all wiring that is routed to and terminates in the GIB. See page A-1.
CAUTION
ator set movement and vibration can break sol­id copper wire.
CAUTION
separate conduits from AC power cables to avoid inducing currents that could cause erratic control.
Use stranded copper wiring. Gener-
Always run control circuit wiring in
2
).
4-1
Page 20
HARNESS EA
FROM GEN-
SET
HARNESS EB
FROM GENSET
TERMINALS FOR EXTERNAL
CUSTOMER CONNECTIONS
MODBUS
PLUS TAP
0500--4407
FIGURE 4-1. CUSTOMER CONNECTIONS IN THE GENERATOR CONTROL PANEL (GCP)
4-2
Page 21
BATTERY STARTING SYSTEMS
See the Generator Set Data Sheet for s tarting bat­tery requirements. Figure 4-2 illustrates the starting battery cables and connections at the batteries for 24 volt starter supply.
WARNING
gases causing severe personal injury. Do not smoke when servicing batteries. Always wear safety glasses. To reduce sparking always turn
Sparks can ignite explosive battery
BATTERY CABLE CONNECTIONS AT STARTER
off AC power to the battery charger and discon­nect the negative ( - ) cables first and reconnect them last. Secure insulating boots over the pos­itive (+) terminals at the batteries and starter.
WARNING
Accidental starting of the generator set can cause severe personal injury or death. To prevent accidental starting, do not connect the negative ( - ) cables at the batteries until the installation has been completed and the set is ready to be started.
CONNECTIONS AT BATTERIES FOR
FIGURE 4-2. BATTERY CONNECTIONS
24 VOLTS AT STARTER
4-3
Page 22
Relocation of Starting Batteries
If the batteries are mounted at a distance that is fur­ther from the starter than the standard cables allow, the c ables must be designed accordingly, so that the total resistance (cables plus connections) do not result in an excessive voltage drop between the bat ­tery and the starter motor. Total cranking c ircuit re­sistance, cables plus connections, must not exceed
0.002 ohms for 24 volt systems to meet engine rec­ommendations.
connecting the batteries. There are six cable con­nections. See the following sample calculation.
1. Assume a resistance of 0.0002 ohms for the starter solenoid contact (R
contact
).
2. Assume a resistance of 0.00001 ohms for each of the six cable connections (R
connection
).
3. Based on the formula: Maximum Allowable Cable Resistance = 0.002 -- R R
contact
= 0.002 -- 0.0002 -- (6 x 0.00001) =
connection
--
0.00174 ohms.
A Calculation Example
A generator set’s starting system is 24 VDC pow­ered by two 12 volt batteries connected in series. The total cable length is 35 feet, including the cable
#1
#2
2
)(35 MM2)
(50 mm
0.0030
0.0025
0.0020
0.0015
0.0010
Resistance (ohms)
0.0005
(50 mm
#0
4. Refer to figure 4-3 for the American Wire Gauge (AWG) or mm
2
cable resistances, which shows by the dashed lines that the small­est usable cable size is two #00 cables in parallel.
2
)
#00
(70 mm
2
)
#000
(70 mm2)
#0000 or 2 #0
(95 mm2OR 2--50 mm2)
2#00
2#000
(70 MM
2#0000
(95 MM
2
)
2
)
2
)
(70 MM
0.0000 50
(15.2)
(0)
0
10
(3.1)
20
(6.1)
Length of Cable in Feet (Meters)
30
(9.1)
40
(12.2)
FIGURE 4-3. RESISTANCE VS LENGTH FOR VARIOUS AWG (MM2) CABLE SIZES
4-4
Page 23
5. Auxiliary Equipment Connections
Local regulations often require that wiring connec­tions be made by a licensed electrician, and that the installation be inspected and approved before operation. All connections, wire sizes, circuit protection, materials used, etc. must conform to the requirements of electrical codes in effect at the installation site.
WARNING
or electrical hazard, resulting in severe per­sonal injury or death and/or property and equipment damage.
See Page A-1 for an illustration of typical genera­tor set connections, including connections to the generator set mounted Generator Interface Box (GiB).
Auxiliary genset equipment such as engine cool­ant heaters, alternator heaters, oil priming pump, etc., are prewired to the GIB. AC power must be supplied to the GIB.
Two supplies are required for 60 Hz machines. One supply is 480 volts, 3--phase with a capability of 25 continuous amps. The other supply is 120 volts, single phase with a capacity of 25 continu­ous amps. The maximum cable size at termina­tion for both circuits is 6 AWG (16 mm maximum circuit breaker size of 50 amps. See Figure 5-1.
Improper wiring can cause a fire
2
)witha
One supply is required for 50 Hz machines, a single 380--440 volt, 3--phase supply with a ca­pacity of 42 continuous amps. The maximum cable size at termination is 6 AWG (16 mm a maximum circuit breaker size of 50 amps. See figure 5-2.
There is a single-phase supply with circuit break­er available in the GIB for customer use, which is usually used to supply the PSU. See page 5-4 for more information about the PSU.
CAUTION
erator set movement and vibration can break solid copper wire.
Use stranded copper wiring. Gen-
2
)with
STARTING BATTERY CHARGER
In most installations a battery charger will be installed to maintain the charge on the starting bat­teries. Capacity and size are chosen based on site conditions and may be powered by one of the c us­tomer supplies from the GIB or by another supply. The following rule of thumb may be useful to size the charger:
Required Battery Charging Amps =
1.2 X Battery Amp Hours Hours.
÷ Required Charging
5-1
Page 24
SUPPLY FOR
CUSTOMER USE
AUXILIARY SUPPLIES
CUSTOMER EARTH
POINT (EP)
110--120V
1PH/2 WIRE
500--4412
10A SUPPLY FOR CUSTOMER USE
110 -- 120V, 1PH/2 WIRE
(RECOMMENDED FOR PSU)
480V3PH/3
WIRE
AUXILIARY SUPPLY
CONNECTIONS
FIGURE 5-1. CUSTOMER CONNECTIONS IN THE GENSET INTERFACE BOX (GIB) FOR 60 HZ GENSETS
5-2
Page 25
FOR CUSTOMER USE
SUPPLY
AUXILIARY SUPPLY
CUSTOMER EARTH
POINT (EP)
10A SUPPLY FOR CUSTOMER USE
240V 1PH/2--WIRE
(RECOMMENDED FOR PSU)
380--440V 3PH/4--WIRE
AUXILIARY SUPPLY CONNECTION
500--4404
FIGURE 5-2. CUSTOMER CONNECTIONS IN THE GENERATOR INTERFACE BOX (GIB) FOR 50 HZ GENSETS
5-3
Page 26
POWER SUPPLY UNIT
The Power Supply Unit (PSU) is a loose component enclosure that must be mounted as close as practi­cal to the genset. The PSU supplies DC power for the control systems of the genset. The PSU re­quires an AC supply and DC wiring to the genset’s GIB. See figure 5-3.
The AC supply for 60 Hz gensets is single phase, 120V, and for 50 Hz gensets, the AC supply is single phase, 220V. There is a 10 amp supply protected by a circuit breaker that is available from the GIB, and it
is recommended that this supply be used to power the PSU. Maximum wire size is 12 AWG (4 mm
2
DC wire length one way from the PSU to the GIB should not exceed 40 feet (12 meters) and must be 8AWG(10mm
2
). If the cable length one way is less than 25 feet (eight meters), the wire size can be re­duced to 10 AWG (6 mm
CAUTION
GENERATOR SET MOVEMENT AND VIBRATION CAN BREAK SOLID COPPER WIRE.
USE STRANDED COPPER WIRING.
2
).
).
5-4
Page 27
AUXILIARY
SUPPLY
DC CONNECTIONS
FIGURE 5-4. POWER SUPPLY (PSU) CUSTOMER CONNECTIONS
5-5
500--4409
Page 28
THIS PAGE LEFT INTENTIONALLY BLANK
5-6
Page 29
6. AC SUPPLY AND POWER Connections
Local regulations often require that wiring connec­tions be made by a licensed electrician, and that the installation be inspected and approved before op­eration. All connections, wire sizes, materials used, etc. must conform to the requirements of electrical codes in effect at the installation site.
WARNING
electrical hazard, resulting in severe personal injury or death and/or property and equipment damage.
This section provides the procedure that is used to connect the AC electrical system of the genset.
Before making any AC electrical connections, make certain the generator set cannot be accidentally started. Move the RUN/OFF/AUTO switch on the control panel to the OFF position.
If the generator set has the optional air starting sys­tem, close the air supply valve.
If the generator set has a battery starting system, turn off or remove AC power from the battery char­ger and then remove the negative (-- ) battery cable from the set starting battery.
WARNING
can cause severe personal injury or death. Arc­ing at battery terminals, light switch or other equipment, flame, pilot lights and sparks can ig­nite battery gas. Do not smoke, or switch trouble light ON or OFF near battery. Discharge static electricity from body before touching bat­teries by first touching a grounded metal sur­face.
Improper wiring can cause a fire or
Ignition of explosive battery gases
WARNING
set can cause severe personal injury or death. Prevent accidental starting by disconnecting the negative (- ) cable from the battery terminal.
WARNING
this section should be done only by persons trained and experienced in electrical mainte­nance. Improper procedures may result in prop­erty damage, bodily injury or death.
Connecting the genset AC electrical system in­volves:
Load cable connection
Flexible sections of cable and conduit
Generator insulation check
Before starting the genset, check to make sure that all electrical connections are secure, and that all wiring is complete. Replace and secure any access panels that have been removed during installation. Check that the load cables from the genset are properly connected.
WARNING
cause electrocution or property damage. Do not connect to any building electrical system ex­cept through an approved device and after building main switch is opened.
Accidental starting of the generator
Each of the operations described in
Backfeed to utility system can
AC WIRING
Generator Voltage Connections
The generator output voltage and maximum current rating are specified on the generator set nameplate. Line-to-neutral voltage is always the lower voltage shown and line-to-line voltage is the higher rating.
Ventilate battery area before working on or near battery—Wear goggles—Stop genset and dis­connect charger before disconnecting battery cables—Disconnect negative (- ) cable first and reconnect last.
CAUTION
AC source before disconnecting battery cables. Otherwise, disconnecting cables can result in voltage spikes damaging to DC control circuits of the set.
Disconnect battery charger from
The generator is connected at the factory to pro­duce a specified voltage per customer order (they cannot be reconfigured for different voltages in the field). Before shipping, the factory tests the genera­tor set at the specified voltage.
See Page A-1.
Load Connections
Load connections are usually made from the gener­ator output terminals to a free standing circuit break-
6-1
Page 30
er in an enclosure or to paralleling switchgear. These cables are usually protected by conduit or a raceway. There must be flexibility in the cables, con ­duits and/or wireway between the genset and sur­rounding structure. This flexibility is required to ab­sorb the normal vibration movements of the genset. Make sure that the cables and flex conduit are not in a straight line from the genset output box to, for ex­ample, conduit in a concrete floor. Straight runs do not provide three dimensions of flexibility. Always designwithanoffset.
All loads are connected to the generator by lugging the stranded load wires and bolting to the appropri­ate terminals on the generator reconnection termi­nal block. The terminals are stamped U, V, W and N to indicate the line and neutral connections. (Refer­ence: U, V, and W correspond with L1, L2 and L3; and N with L0 respectively).
Load Balancing
When operating in parallel to a utility grid, the gener­ator set will supply balanced load current to the sys­tem. Any unbalance of loads will be taken up by the utility grid.
If the generator set is ever operated in Island Mode, the loads should be balanced as closely as possible across the three phases. When connecting loads to the generator set, balance the loads so the current flow from each line terminal (L1, L2 and L3) is about the same. This is especially important if both single phase and three phase loads are connected. Any combination of single phase and three phase load­ing can be used as long as each line current is about the same, within 10 percent of median value and no line current exceeds the nameplate rating of the generator. Check the current flow from each line af­ter connections by observing the control panel am­meter.
6-2
Page 31
Grounding
Natural gas powered lean burn design generator sets are usually connected through the use of paral­leling switchgear. Some gensets will have a discon­nect circuit breaker on its output in a free standing enclosure. In any case there are many configura­tions and sequences of operation that may affect how the genset neutral and the overall system is grounded. If ground fault sensing equipment is in­cluded in the scheme, another element for consid­eration is added. The grounding decision must be carefully considered by the system designer in con­sideration of system requirements, operational needs, and local codes and standards in force at the site.
Generally in a single genset system, the genset is connected to the system loads using either three-­wire or four--wire systems. In three--wire systems, the neutral of the generator is not used (or not pres­ent in the case of delta systems). A neutral conduc­tor is not installed from the genset to the switchgear and to the loads. The power switching equipment is therefore 3--pole. In this case the generator neutral may be ungrounded, solidly grounded or resistance grounded. See Figure 6-1 for a simplified diagram showing this configuration. In four--wire systems the neutral conductor is run from the generator and the grounding scheme depends on whether the power switching is 3--pole or 4--pole.
If the neutral is solidly connected from the genset to the service entrance and loads, and the neutral is grounded at the service entrance, then the genset neutral is grounded through that system ground. No additional neutral ground should be present at the genset (and is usually not allowed by code). This ground at the service is present whether operating the genset in parallel or in island mode. See the sim­plified diagram in Figure 6-1.
The grounding question becomes considerably more complex in four--wires systems if neutral is switched, which means 4--pole breakers are used. There are no straight forward rules or guidance re­garding the grounding scheme. Multiple issues will affect the grounding decision such as multiple gen­sets operating in parallel, ground fault sensing re­quirements, island vs. utility parallel operation, protection schemes, and of course, safety. In these complex schemes, the grounding decision must be carefully considered and defined physically and op­erationally by the system designer.
WARNING
personal injury or death. Bonding and ground­ing must be done properly. All metallic parts that could become energized under abnormal conditions must be properly grounded.
Typical requirements for bonding and grounding are given in the National Electrical Code, Article
250. All connections, wire sizes, etc. must conform to the requirements of the electrical codes in effect at the installation site.
Electric current can cause severe
Equipment Grounding (Bonding)
All equipment metallic parts must be grounded to earth or to the earth ground system of the facility. This includes the generator set frame, the GCP en­closure, the PSU enclosure, and any other equip­ment associated with the generation system. This bonding is important for safety to avoid the chance of metallic components becoming energized. It is also important in reduction or elimination of stray electrical noise and pulses from static charge or lightning. There is a genset bonding point located and marked as such on the bedframe (skid).
6-3
Page 32
UTILITY
SOURCE
SERVICE
GENSET
PARALLELING CB
GENERATOR
SOURCE
N
G
SIMPLIFIED DRAWING,
ELEMENTS MISSING
FOR CLARITY
UTILITY
SOURCE
N
G
N
G
GENERATOR NEUTRAL MAY BE:
LOADS
SOLIDLY GROUNDED (SHOWN),
OR RESISTANCE GROUNDED
PARALLEL OPERATION, 3-- WIRE, 3--POLE SWITCHING
GENSET
SERVICE
N
G
PARALLELING CB
N
G
UNGROUNDED,
GENERATOR
SOURCE
N
G
SIMPLIFIED DRAWING,
ELEMENTS MISSING
FOR CLARITY
LOADS
GENERATOR NEUTRAL NOT GROUNDED
AT THE GENSET IF THERE IS ANOTHER SYS-
TEM GROUND
PARALLEL OPERATION, 4-- WIRE, 3--POLE SWITCHING
FIGURE 6-1. PARALLEL OPERATIONS FOR 3--WIRE AND 4--WIRE, 3--POLE SWITCHING
6-4
Page 33
INSULATION RESISTANCE (MEGGER) &
POLARIZATION INDEX (PI) TESTING
Megger and PI testing must be performed on all medium voltage (601 through 15,000 volts) genera­tor sets before initial start -up. PI testing for low volt­age (less than 600 volts) generator sets is recom­mended by Cummins Power Generation.
These tests are used to verify that the windings are dry before the generator set is operated and devel­ops a base line for future test comparison.
Before these tests can be performed on medium voltage generator sets, you must first perform the generator grounding procedure.
Generator Set Grounding Procedure
Prior to performing service or inspection proce­dures that may expose personnel to conductors normally energized with voltages greater than 600 volts, the following generator set grounding proce­dure must be followed.
DANGER
unless fully trained in medium voltage ground­ing procedures and have necessary safety equipment. Severe injury or death due to high voltage electrical shock may result.
1. Open, lock-out and tag-out all sources of power to the immediate work area.
2. Disable the starting system of the generator set:
A. Move the Run/Off/Auto switch to the Off
B. Disconnect the battery charger from its AC
C. Remove the negative battery cable from
Do not perform these procedures
position and wait for the controller to power down (approximately 10 minutes).
source.
the battery.
D. Install a lockout device on the battery
cable end. (For engines equipped with an air-powered starting system, close air valve and install valve locking device.)
3. Put on high voltage gloves with leather protec­tors.
4. Using two pre-tested voltage detection devices (of the proper rating), verify de-energized con­dition in the work area. (Retest voltage detec­tion devices immediately after verification of de-energized condition.)
5. Remove the metal cover from the generator output box to gain access to generator load ter­minals.
6. Securely install the Grounding Cluster ground clamp to a verified “grounded” conductor.
WARNING
severe personal injury or death. After DC voltage from the test equipment has been applied to the windings and ground, there will be a definite static charge on the wind­ings. Reconnect Grounding Cluster to re­move static charge from the winding after each generator test.
7. With the Grounding Cluster in place, you are protected from static and/or induced charges that may have been present in the generator stator.
8. Leave grounds connected for at least one min­ute so static charge can dissipate. Remove ground cluster and perform PI and/or any other tests required on the stator winding. Reconnect grounds if additional generator service is nec­essary.
9. When work on the generator set is complete, remove the Grounding Cluster in the reverse order of installation.
10. After getting clearance from all personnel in­volved in the lock-out/tag-out procedure, re­move all lock-out devices in reverse order of installation.
Hazardous voltage. Can cause
6-5
Page 34
Megger and PI Test
DANGER
volts, present special hazards of severe person­al injury or death. Even after genset shutdown, an electrical shock hazard may still exist, caused by induced voltage within the generator or cables. Service personnel must be well­trained/qualified to work with distribution volt­ages. (See Generator Set Grounding Proce­dures, Page 6-3.)
WARNING
(601 through 15,000 volts) generator sets must be dry before the generator is operated. Failure to make sure windings are dry before start-up may result in catastrophic equipment failure, severe personal injury or death.
Megger Test: The megger test consists of applying voltage for up to one minute. The highest resistance values shown in Table 6-1 should be obtained for a new generator with dry windings. For a set that has been in service, the resistance reading should not be less than the lower value shown.
Medium-voltage, 601 to 15,000
The windings of medium-voltage
1. Perform the Generator Set Grounding Proce­dure in this section.
2. Open the control box door and remove connec­tor 10 from the AVR module.
3. Disconnect the AC voltage sense leads from the generator output terminals. The AC voltage sense leads are marked 5, 6, 7 and 8.
4. If the RTD (resistance temperature detector) option is installed, ground all s ix RTD tempera­ture leads. Each RTD has three leads, one red and two white leads. Total of 18 leads must be grounded.
Main Stator:
1. Remove and separate the neutral leads of the generator from the generator load terminal marked “N”.
2. Connect the megger between one phase of the stator and ground while grounding the other two phases and conduct the test. Refer to Table 6-1 for megger voltage selection and required resistance values.
PI Test: The PI test consists of applying a voltage between the winding and ground for ten minutes and recording resistance values at one minute and at ten minutes. The PI is the ratio of a ten minute reading in megohms divided by a one minute read­ing in megohms. A ratio of two or greater is consid­ered good for new and in service sets.
If low readings are obtained, the cause should be in­vestigated and corrected before the generator set is returned to service. If moisture is determined to be the cause of low test readings, a winding drying pro­cess will be required (refer to genset Service manu­al for drying procedure).
3. Repeat this step in turn for the other two phases.
Main Rotor:
1. Disconnect the main rotor and voltage sup­pressor leads from terminals F1+ and F2-- on the rotating rectifier assemblies and isolate them from ground. Tag and mark each lead with its terminal number (F1+ or F2--).
2. Connect the megger between one of the rotor leads and ground and conduct the test. Refer to Table 6-1 for megger voltage selection and required resistance values.
6-6
Page 35
FRAME
SIZE
P7
P80
P80
P80
GENERATOR
VO LTAGE
600 VAC or
less
600 VAC or
less
601 thru 5000
VAC
5001 thru
15000 VAC
TABLE 6-1. GENERATOR INSULATION RESISTANCE
MEGGER
VDC
SETTING
500 10 -- 1 10 -- 1 10 -- 1 10 -- 1
1000 10 -- 5
500
2500 100 -- 50
500
5000 300 -- 150
500
MAIN
STATOR
MINIMUM RESISTANCE (MEG)
MAIN ROTOR PMG
200 -- 100
(Combined rotors)
200 -- 100
(Combined rotors)
200 -- 100
(Combined rotors)
5--3 10 -- 5
5--3 10 -- 5
5--3 10 -- 5
EXCITER
STATOR
6-7
Page 36
THIS PAGE LEFT INTENTIONALLY BLANK
6-8
Page 37
7. Prestart Preparations

PRESTART PREPARATIONS

Initial startup and preparation for commissioning may be performed only by a factory trained person who is qualified for commissioning of lean burn nat­ural gas gensets from Cummins Power Generation. This work is normally performed in conjunction with the commissioning of the switchgear as well as oth­er site equipment.
CAUTION
of the control can cause equipment malfunction or damage. Calibration and adjustment must be performed by technically qualified personnel only.
Assuring that the site is prepared for commissioning will reduce time, mitigate issues, and assure effici­ent, effective commissioning efforts.
A generator set installation/prestart--up checklist is included in this chapter and is useful to help assure the site is ready. Qualified site personnel, or those responsible for the design/installation, can use this checklist during design and construction as well as precommissioning to check many aspects of the site.
A list of control and protection settings is also in­cluded in this chapter which provides descriptions and factory settings. If other settings are desired by qualified site personnel, a list of prepared setting prior to commissioning can be prepared to clarify and speed the process of setup of the control sys­tems.
Improper calibration or adjustment
ELECTRICAL SYSTEM
Make sure all electrical connections are secure and all wiring is complete and inspected. Replace and
secure any access panels that may have been re­moved during installation.
Battery Connections
WARNING
set can cause severe personal injury or death. Make sure that the Run/Off/Auto switch on the control panel is set to the Off position before connecting the battery cables.
Starting the unit requires 24 volt battery current (see Specification section). Connect 12 volt batteries in series (negative post of first battery to the positive post of the second battery).
Necessary battery cables are on the unit. Service batteries as necessary. Infrequent use (as in emer­gency standby service), may allow battery to self­discharge to the point where it cannot start the unit. If installing an automatic transfer switch that has no built-in charge circuit, connect a separate trickle charger. Cummins Power Generation automatic transfer switches include such a battery charging circuit.
WARNING
can cause severe personal injury or death. Al­ways connect negative ( - ) battery cable last to prevent arcing.
WARNING
ing on or near battery. Arcing at battery termi­nals, light switch or other equipment, flame, pi ­lot lights and sparks can ignite battery gas. Do not smoke, or switch trouble light ON or OFF near battery. Discharge static electricity from body before touching batteries by first touching a grounded metal surface.
Accidental starting of the generator
Ignition of explosive battery gases
Ventilate battery area before work-
7-1
Page 38
GENERATOR SET INSTALLATION/
PRE--COMMISSIONING CHECKLIST
Room general and safety checks
Ensure starting is inhibited until ready
Lean burn gas generator set
This checklist should be used to validate the completion of a generator set installation prior to commissioning. A checklist should be completed for each generator set of a multiple installation.
Project Details
Project Name:
Customer (End User):
Address of Site:
Telephone No.:
Email:
Start up date:
Generator set details
Generator set model:
Generator set serial number:
Generator set number:
Control type:
Warn personnel of impending equipment start-­up
Generator set clean with all guards in place
No loose materials near generator set
Air ducts clear and clean
Access and egress routes unobstructed and la­belled
Control and maintenance positions unob­structed
Room secure--no unauthorized access
Generator set is level-holding down bolts se­cure
Pipework and cables are secure with trip haz­ards
Overhead obstructions clearly marked and la­belled
All key components are labelled
Pipework and services color coded and la­belled
Electrical bonding complete
Cooling System
Remote mounted radiator systems
Header tank is adequately sized
Control serial number:
System control type (if applicable):
Generator set building and services
Building and installation work complete
Site clean and access clear from obstruction
Building services complete and commissioned (lightning, lighting, electrical auxiliary supplies, water, etc.)
Observations: _______________________________________ _______________________________________ _______________________________________ _______________________________________ _______________________________________ _______________________________________ _______________________________________
Overflow is clear and routed to avoid spillage
Static/friction head is within engine/system ca­pability
Engine vent pipes inclined toward radiator/ header
Header tanks, auxiliary tanks and system filled and cap(s) replaced
Pipework avoids air locks--air bleed valves pro­vided
Pipework isolated from generator set vibration
Pipework complete, cleaned, tested, and painted
Auxiliary supply to fans correctly installed
Electrical bonding completed
Heat exchanger and cooling tower systems
Header tank is adequately sized
7-2
Page 39
Overflow is clear and routed to avoid spillage
Static/friction head is within engine/system ca­pability
Engine vent pipes inclined toward header tank
Pipework avoids air locks--air bleed valves pro­vided
Pipework isolated from generator set vibration
Pipework complete, cleaned, tested and painted
Secondary cooling system is complete
Cooling tower make up supply is complete
Auxiliary supply to fans correctly installed
Electrical bonding completed
Gaseous fuel system
Pipework complete, material and construction correct
Regulator and shut off valves in correct loca­tions
Leak test and certification complete
Test certificates present
Correct pressure regulator and HP/LP safety valves
Flexible connection to engine fitted
HP and LP air/hydraulic pressures checked
Condensate drained
Exhaust system
Installation design prevents exhaust recircula­tion
Flexible connection to engine
Support prevents load on turbocharger/man­ifold
Installation allows for pipework expansion
Pipework/muffler supported at required inter­vals
Joints welded or flanges secure with correct gaskets
Stack/tailpipe prevents rain/snow ingress
Flues are not combined in stack
Condensate drain provided
Exit directed away from buildings/personnel
System is lagged and clad as required
Gas present at shut off valves
Fire alarm/suppression system
Fire alarm/suppression system complete
Sensors protected from radiant heat
Labelling and lock off system complete
Starting system
Battery starting
Starting batteries correct and installed on tray or stand
Battery cables routed correctly and secured
Battery charger installed and wired
Compressed air/hydraulic starting
Compressor set installed and wired
Compressed air pipework correctly rated and installed
Isolating valves correctly positioned and la­belled
Pipework tested, painted, and labelled
Building penetration and weathering complete and sealed
Flammable materials properly protected
Check stack/tailpipe and rain cap are clear
Ventilation and Attenuation
Design prevents hot air recirculation and rain ingress
Design accounts for prevailing wind
Air flow direction is from alternator to engine front
Louver mechanisms complete and wired as re­quired
Check louvers are clear and free to operate
Electrical bonding completed
Bird guard is fitted to intake and outlet
Electrical System
Control system
Field wiring to set mounted control complete
Customer wiring to set mounted control com­plete
7-3
Page 40
Interconnection to remote control complete
Emergency stop controls wired
Select set parameters on set/system control
Check remote control signals to set control
Check set control signals to remote control
Check signals to system control and switch­gear
Check emergency stop c ontrols
Set/Switchgear/Changeover/Transfer
Means of disconnection/isolation provided
Switchgear installation and pretesting com­pleted
Power connections complete and torque-­marked
Cable tests complete and certificates available
Verify cable flexibility at generator set
Energize auxiliary supplies and check function­ality
Enter switchgear protection settings and re­cord
Utility sensing commissioned
Small power and lighting circuits tested and certificated
Alternator insulation test completed
Small power and lighting circuits tested and certificated
Comments on any item that may affect commission­ing: _______________________________________ _______________________________________ _______________________________________ _______________________________________ _______________________________________ _______________________________________ _______________________________________ _______________________________________ _______________________________________ _______________________________________ _______________________________________ _______________________________________ _______________________________________ _______________________________________ _______________________________________ _______________________________________ _______________________________________ _______________________________________ _______________________________________
Electrical general
All electrical boxes clean and covers replaced
Auxiliary electrical supply complete
Grounding system complete and tested
Electrical bonding of services/assemblies complete
Utility supply available as required
Checklist completed by:
Date:
Print name:
Company:
Note: Completion of this checklist does not relieve installer of contract obligations.
7-4
Page 41
CONTROL AND PROTECTION SETTINGS
The following table provides a list of descriptions and factory settings.
TABLE 7-1. CONTROL AND PROTECTION SETTINGS LIST
DESCRIPTION
SET UP
System units Metric
Customer fault 4 Warning Shutdown/warning
Overvoltage 100%
Language English Check with factory
PARALLEL--ISO BUS
Sync time limit 120, warning 10--120 seconds
Permissive window--phase 10 5--20 degrees
Permissive window--time 0.50 0.5--5 seconds
Fail to close 1, shutdown 0.5--5 seconds shutdown/
First start fail 10 5--120
Ramp Unld time 120 5--900 Seconds
Ramp Unld level 5 0--100%
Ramp load time 120 5--900 Seconds
Loss of field time 10, shutdown 2--10 Seconds
Loss of field level 20, shutdown 16--41% kVAR
Reverse power limit (%) 5, shutdown 5--15% KW
Reverse power limit (time) 5, shutdown 1--15 Seconds
PARALLEL-- UTILITY
Base load % 20 2 0--100%
PF level .97 0.8 lag--1.0
Multiple/Single Multiple Multiple/Single
Ramps--same as ISO Bus
AmpSentry
Overcurrent AmpSentry time--overcur-
Overload AmpSentry time--overcur-
High AC volts 110% for 10 seconds, s hut-
Low AC volts 85% for 10 seconds, shut-
Underfrequency 90% for 20 seconds, shut-
ORIGINAL SETTNG RANGE DESIRED NEW SETTING
shutdown/off/warn
off/warn
rent calculation
rent calculation
down, 130% no delay, shutdown
down
down
7-5
Page 42
THIS PAGE LEFT INTENTIONALLY BLANK
7-6
Page 43
(C49 AND C50)
HARNESS EA
HARNESS EB
PROTECT HARNESSES:
RUN IN CONDUIT OR RACEWAY
CUSTOMER CONNECTIONS AT TERMINAL BLOCK C
(0620-- 0268)
24 VDC SUPPLY FUSED AT 6A
AC OUTPUT CONNECTIONS
(REF GENERATOR WD
0630--2861)
(FRAME)
GROUNDING POINT
GENSET EQUIPMENT
FOR REFERENCE)
VIEW B -- ALTERNATOR END (P80 ALTERNATOR SHOWN
50 HZ: 220V, 3 PH
60 HZ: 480V, 3 PH, 4-- WIRE AND 120V, 1 PH, 2-- WIRE
BOX (GIB)
INTERFACE
GENERATOR
HARNESS EB (SEE DETAIL
X FOR CONNECTOR SIZE)
HARNESS EA (SEE DETAIL
Y FOR CONNECTOR SIZE)
CONNECTOR DETAIL Y
OIL PRIMING PUMP, GENERATOR HEATERS, CONTROL POWER, ETC.
CUSTOMER SUPPLIED AC POWER FOR AUXILIARY EQUIPMENT: COOLANT HEATERS,
USE8AWGTO40FT,
10 AWG IF LESS THAN 25 FT
A-1
(2--WIRE)
PSU HEALTHY ALARM
PSU (24 VDC)
50 HZ: 220V 1 PH
60 HZ: 120V 1 PH
FOR SUPPLY TO PSU.
10A RECOMMEDNDED
SHOWN FOR REFERENCE)
VIEW A -- GIB CONTROLLER (P80 ALTERNATOR
CONNECTOR DETAIL X
TYPICAL GENSET WIRING CONNECTIONS
Page 44
620--0268
A-2
STRANDED (MAXIMUM RUN 152 METERS).
2
CUSTOMER SIDE CONNECTION
(16 AWG).
2
CUSTOMER WIRING CONNECTIONS
9
AT 250 VAC, 30 VDC
CONTACTS RATING 5A
MODBUS PLUS TAP
11
CUSTOMER CONNECTION NOTES:
1. OV DC OUTPUT (SWITCHED). OUTPUT GOES HIGH IF AN OVERLOAD OR FREQUENCY CONDITION OCCURS (MAX RATING 2A.)
2. PARALLEL LOAD SHARE LINES (0-- 1MA). USE 4 CONDUCTOR SHIELDED CABLE, 1 MM
3. ANALOGUE 0-- 5V DC INPUTS TO CONTROL GENSET LOAD IN UTILITY PARALLELING MODE.
4. 0V DC OUTPUT (SWITCHED). OUTPUT GOES HIGH WHEN GENSET IS READY TO LOAD, I.E. UP TO SPEED AND VOLTS (MAX RATING 2A).
5. TERMINALS ARE SUITABLE FOR CABLE UP TO A MAXIMUM SIZE OF 2.5 MM
6. TERMINALS MARKED HAVE CODING FINGERS REMOVED FOR EASE OF INSTALLATION.
7. LINK C21/22 TO ENABLE MASTER FIRST START SIMULATOR FUNCTION. ONLY ENABLE ON SINGLE GENSET/PLTE APPLICATIONS.
8. ANALOGUE 0-- 5V DC INPUTS TO CONTROL GENSET KVAR IN UTILITY PARALLELING MODE.
9. BUS SENSING SHOULD BE FUSED WITH 4A FUSE.
10. ADD A 100 OHM RESISTOR IF THERE IS NOT BEARING RTD BETWEEN 217 --218 AND LINK 218 --219.
11. USED 1 PAIR 24 AWG SHIELDED AS PER E108998 OR AWM2919 OR CM1308 (MAXIMUM RUN 450 METERS).
CUSTOMER SIDE CONNECTION
7
8
3
2
1
4
Page 45
TYPICAL LOW-PRESSURE GAS TRAIN (7 PSI MAXIMUM)
A-3
Page 46
A-4
TYPICAL HIGH-PRESSURE GAS TRAIN
Page 47
FLEXIBLE HOSE MUST BE
HORIZONTAL AND VALVE
SUPPORTED FROM FLOOR
OR UPSTREAM PIPEWORK
SUPPLIED PIPING BUIL T TO SUIT
RIGIDLY SUPPORTED CUSTOMER
15 F T (4.5 M) MAXIMUM LENGTH
LOOSE.
CONNECTION HARNESS & 0.5M LENGTH OF
STAINLESS STEEL FLEXIBLE HOSE SUPPLIED
NOTE: DN80 (3”) GAS VALVE, 5” X 3” REDUCER,
GAS VENTS TO OUTSIDE
DIRECTLY TO FLEXIBLE HOSE
RIGIDLY SUPPORT FLANGE IF BOLTED
A-5
TYPICAL GAS TRAIN INSTALLATION
TYPICAL FACTORY AVAILABLE GAS TRAIN
Page 48
L
LW
PS
H
PS
SYMBOLS
FLANGES
VALVE (CLOSED)
PIPE REDUCER
DESIGNATION
VALVE (OPEN)
CROSSING PIPES
FLEXIBLE PIPE
NOT CONNECTED
BLANK FLANGE
QUICK RELEASE
UNIONS COUPLING
ORIFICE
CAP
CONNECTION ITEM
SHUTDOWN SWITCH
THERMOSTATIC
VALVE
LOW PRESSURE
WARNING SWITCH
LOW PRESSUREPSLIMIT SWITCH
HIGH PRESSURE
RELIEF VALVE
PRESSURE
BALANCING VALVE
PUMP
A-6
CPG LIMIT OF
SCOPE OF SUPPLY
GENERATOR
RECOMMENDED COOLANT SYSTEM SCHEMATIC
1/2”
MIN 6 IN LENGTH
OF 3/4 IN PIPE
ASME BLADDER EXPANSION TANK
MOUNTED ON FLOOR ADJACENT TO ENGINE;
CONSULT FACTORY FOR INITIAL MINIMUM FILL PRESSURE
AND MAXIMUM OPERATING PRESSURE FOR SIZING.
AIR SEPARATOR (TYPICAL)
AIR ELIMINATOR (TYPICAL)
S
1/2”
MIN 8 IN LENGTH OF
1INPIPE
1/2”
S
MIN 6 IN LENGTH
OF 3/4 IN PIPE
LT P UMP
60”
MAX
QSV81/91G ENGINE
HT PUMP
AIR PRESSURIZATION
CONNECTION
PRESSURE
GAUGE
LWPS PS H
LPS
3/4”
3/4”
MIN.
1/2”
3/4”
MIN.
SET VALVE TO FLOW 6 GPM
AT OPERATING TEMPERATURE
DRAIN/FILL VALVE
(TYPICAL)
LOWEST POINT DIA1”
FOR FILLING OR
DRAINING THE CIRCUIT
(TYPICAL)
HIGH TEMPERATURE
COOLANT CIRCUIT
LOW TEMPERATURE
TEMPERATURE GAUGES
COOLANT CIRCUIT
HEAT RECOVERY/COOLING SYSTEM
Page 49
630--2861
GENERATOR WIRING DIAGRAM
A-7
Page 50
Cummins Power Generation
1400 73rd Ave. NE Minneapolis, MN 55432 USA
Phone 1 763 574 5000 Toll-free 1 800 888 6626 Fax 1 763 574 5298 Email ask.powergen@cummins.com www.cumminspower.com
CumminsR, the “C” logo, and “Our energy working for you.” are trademarks of Cummins Inc.
E2007 Cummins Power Generation, Inc. All rights reserved.
Loading...