CUMMINS GGMA, GGMB, GGMC Operator's Manual

Page 1
Operator Manual
Generator Set
with PowerCommand) Control 1301
GGMA GGMB
GGMC
English 22009 9610117 (Issue 2)
Page 2
Table of Contents
SECTION TITLE PAGE
IMPORTANT SAFETY INSTRUCTIONS iii. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1 INTRODUCTION
General 1-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Generator Set Control 1-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
How to Obtain Service 1-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2 SPECIFICATIONS 2-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3 CONTROL OPERATION (WITHOUT DISPLAY)
General 3-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Prestart Checks 3-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Control Panel 3-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Starting 3-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Stopping 3-4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4 CONTROL OPERATION (WITH DISPLAY)
General 4-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Prestart Checks 4-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Control Panel Power On/Off Modes 4-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Control Panel 4-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
System Messages 4-6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Starting 4-9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Stopping 4-10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Selecting Auto, Manual Run and Off Modes 4-11. . . . . . . . . . . . . . . . . . . . . . . .
Operating Menus 4-14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Service Menus 4-18. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
History/About Menu 4-20. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Screen Adjust Menu 4-22. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Fault History Menu 4-24. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
!!
The engine exhaust from this product
contains chemicals known to the State
of California to cause cancer, birth
defects or other reproductive harm.
Page 3
SECTION TITLE PAGE
5 TROUBLESHOOTING
General 5-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Safety Considerations 5-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Reading Fault Codes 5-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Line Circuit Breaker (Optional) 5-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Control and Diagnostics Via Network or PC (Laptop) 5-2. . . . . . . . . . . . . . . . .
Fault Codes 5-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Control Panel Fuses 5-11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6 MAINTENANCE
General 6-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Maintenance Schedule (Standby Power Gensets) 6-2. . . . . . . . . . . . . . . . . . .
Maintenance Schedule (Prime Power Gensets) 6-3. . . . . . . . . . . . . . . . . . . . . .
Generator Set Inspection 6-4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Generator Set Maintenance (Battery Disconnected) 6-5. . . . . . . . . . . . . . . . . .
Lubrication System 6-6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Cooling System 6-9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Air Filters 6-11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Drive Belt Replacement 6-13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Ignition System 6-14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Batteries 6-15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Out-Of-Service Protection 6-17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7 OPERATING RECOMMENDATIONS
Break-In 7-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
No-Load Operation 7-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Exercise Period 7-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Low Operating Temperature 7-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
High Operating Temperature 7-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ii
Page 4
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS This manual contains important instructions that should be followed during installation and maintenance of the generator and batter­ies.
Before operating the generator set (genset), read the Operator’s Manual and become familiar with it and the equipment. Safe and efficient operation can be
achieved only if the equipment is properly operated and maintained. Many accidents are caused by failure
to follow fundamental rules and precautions.
The following symbols, found throughout this manual, alert you to potentially dangerous conditions to the oper­ator, service personnel, or the equipment.
This symbol warns of immediate hazards which will result in severe personal in­jury or death.
WARNING
This symbol refers to a hazard or un­safe practice which can result in severe person­al injury or death.
CAUTION
This symbol refers to a hazard or un­safe practice which can result in personal injury or product or property damage.
FUEL AND FUMES ARE FLAMMABLE
Fire, explosion, and personal injury or death can result from improper practices.
DO NOT permit any flame, cigarette, pilot light,
spark, arcing equipment, or other ignition source near the generator set or fuel tank.
Fuel lines must be adequately secured and free of
leaks. Fuel connection at the engine should be made with an approved flexible line. Do not use copper piping on flexible lines as copper will be­come brittle if continuously vibrated or repeatedly bent.
Natural gas is lighter than air, and will tend to gather
under hoods. Propane is heavier than air, and will tend to gather in sumps or low areas. NFPA code re-
quires all persons handling propane to be trained and qualified.
Be sure all fuel supplies have a positive shutoff
valve.
Be sure battery area has been well-ventilated prior
to servicing near it. Lead-acid batteries emit a highly explosive hydrogen gas that can be ignited by arc­ing, sparking, smoking, etc.
EXHAUST GASES ARE DEADLY
Provide an adequate exhaust system to properly
expel discharged gases away from enclosed or sheltered areas and areas where individuals are likely to congregate. Visually and audibly inspect the exhaust daily for leaks per the maintenance schedule. Make sure that exhaust manifolds are se­cured and not warped. Do not use exhaust gases to heat a compartment.
Be sure the unit is well ventilated.
Engine exhaust and some of its constituents are
known to the state of California to cause cancer, birth defects, and other reproductive harm.
MOVING PARTS CAN CAUSE SEVERE PERSONAL INJURY OR DEATH
Keep your hands, clothing, and jewelry away from moving parts.
Before starting work on the generator set, discon-
nect battery charger from its AC source, then dis­connect starting batteries, negative (-) cable first. This will prevent accidental starting.
Make sure that fasteners on the generator set are
secure. Tighten supports and clamps, keep guards in position over fans, drive belts, etc.
Do not wear loose clothing or jewelry in the vicinity of
moving parts, or while working on electrical equip­ment. Loose clothing and jewelry can become caught in moving parts. Jewelry can short out elec­trical contacts and cause shock or burning.
If adjustment must be made while the unit is run-
ning, use extreme caution around hot manifolds, moving parts, etc.
MS-5
iii
Page 5
ELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL INJURY OR DEATH
Remove electric power before removing protective shields or touching electrical equipment. Use rub­ber insulative mats placed on dry wood platforms over floors that are metal or concrete when around electrical equipment. Do not wear damp clothing (particularly wet shoes) or allow skin surface to be damp when handling electrical equipment.
Use extreme caution when working on electrical
components. High voltages can cause injury or death. DO NOT tamper with interlocks.
Follow all applicable state and local electrical
codes. Have all electrical installations performed by a qualified licensed electrician. Tag and lock open switches to avoid accidental closure.
DO NOT CONNECT GENERATOR SET DIRECT-
LY TO ANY BUILDING ELECTRICAL SYSTEM. Hazardous voltages can flow from the generator set into the utility line. This creates a potential for elec­trocution or property damage. Connect only through an approved isolation switch or an ap­proved paralleling device.
GENERAL SAFETY PRECAUTIONS
Coolants under pressure have a higher boiling point than water. DO NOT open a radiator or heat ex­changer pressure cap while the engine is running. Allow the generator set to cool and bleed the system pressure first.
Benzene and lead, found in some gasoline, have
been identified by some state and federal agencies as causing cancer or reproductive toxicity. When checking, draining or adding gasoline, take care not to ingest, breathe the fumes, or contact gasoline.
Used engine oils have been identified by some state
or federal agencies as causing cancer or reproduc­tive toxicity. When checking or changing engine oil, take care not to ingest, breathe the fumes, or con­tact used oil.
Keep multi-class ABC fire extinguishers handy.
Class A fires involve ordinary combustible materials such as wood and cloth; Class B fires, combustible and flammable liquid fuels and gaseous fuels; Class C fires, live electrical equipment. (ref. NFPA No. 10).
Make sure that rags are not left on or near the en-
gine.
Make sure generator set is mounted in a manner to
prevent combustible materials from accumulating under the unit.
Remove all unnecessary grease and oil from the
unit. Accumulated grease and oil can cause over­heating and engine damage which present a poten­tial fire hazard.
Keep the generator set and the surrounding area
clean and free from obstructions. Remove any de­bris from the set and keep the floor clean and dry.
Do not work on this equipment when mentally or
physically fatigued, or after consuming any alcohol or drug that makes the operation of equipment un­safe.
Substances in exhaust gases have been identified
by some state or federal agencies as causing can­cer or reproductive toxicity. Take care not to breath or ingest or come into contact with exhaust gases.
Do not store any flammable liquids, such as fuel,
cleaners, oil, etc., near the generator set. A fire or explosion could result.
Wear hearing protection when going near an oper-
ating generator set.
To prevent serious burns, avoid contact with hot
metal parts such as radiator, turbo charger and ex­haust system.
KEEP THIS MANUAL NEAR THE GENSET FOR EASY REFERENCE
iv
Page 6
1. Introduction
GENERAL
Each operator should read this manual before oper­ating the generator set (genset) for the first time. A genset must be operated and maintained properly if you are to expect safe and reliable operation. This manual includes a troubleshooting guide and a maintenance schedule.
WARNING
nance can lead to severe personal injury or loss of life and property by fire, electrocution, me­chanical breakdown or exhaust gas asphyxi­ation. Read Important Safety Instructions pages and carefully observe all instructions and precautions in this manual.
Beginning with spec B, read the warranty statement provided with the genset for US Environmental Protection Agency (EPA) restrictions on servicing specific components.
Improper operation and mainte-
GENERATOR SET CONTROL
There are two versions of the PowerCommand 1301 Control (PCC) that can be configured with this genset. For reference only, they are referred to as PCC 1301 (Without Display) and PCC 1301 (With Display) in this manual (Figure 1-1).
Sections in this manual that are specific to either PCC 1301 control are noted in the section title. All other sections apply to both versions.
PCC 1301
(WITHOUT DISPLAY-STANDARD)
®
PCC 1301
(WITH DISPLAY-OPTIONAL)
FIGURE 1-1. CONTROL PANEL CONFIGURATIONS
1-1
Page 7
HOW TO OBTAIN SERVICE
When the generator set requires servicing, contact your nearest Cummins Power Generation distribu­tor. Factory-trained Parts and Service representa­tives are ready to handle all your service needs.
To contact your local Cummins Power Generation distributor in the United States or Canada, call 1-800-888-6626 (this automated service utilizes touch-tone phones only). By selecting Option 1 (press 1), you will be automatically connected to the distributor nearest you.
If you are unable to contact a distributor using the automated service, consult the Yellow Pages. Typi­cally, our distributors are listed under:
GENERATORS-ELECTRIC or ELECTRICAL PRODUCTS
For outside North America, call Cummins Power Generation, 1-763-574-5000, 7:30 AM to 4:00 PM, Central Standard Time, Monday through Friday. Or, send a fax to Cummins Power Generation using the fax number 1-763-528-7229.
When contacting your distributor, always supply the complete Model, Specification, and Serial Number as shown on the generator set nameplate.
WARNING
INCORRECT SERVICE OR PARTS REPLACEMENT CAN RESULT IN SEVERE PERSONAL IN­JURY, DEATH, AND/OR EQUIPMENT DAMAGE. SERVICE PERSONNEL MUST BE TRAINED AND EXPERIENCED TO PERFORM ELECTRICAL AND/OR MECHANICAL SERVICE.
1-2
Page 8
2. Specifications
MODEL GGMA GGMB GGMC
Engine
GM Gaseous Engine
Generator kW Rating See Genset Nameplate for rating information.
Engine Fuel Connection
Inlet Thread Size
Fuel (Single or Dual)
Standard Optional
Exhaust
Connection Backpressure (Max. Allowed) Exhaust Flow at Rated Load
Propane Natural Gas
2 1/2 inch NPT
14 inch H
O (3.5 kPa)
2
158.0 cfm (4.5 m
172.0 cfm (4.9 m
3
/min)
3
/min)
Exhaust Temperature
Propane Natural Gas
1029° F (554° C) 1004° F (540° C)
Electrical System
Starting Voltage Battery Charging Alternator
Cooling System
Capacity with Radiator
Lubricating System
Oil Capacity with Filters
Tune-up Specifications
Spark Plug Gap
Battery
Ground Required Battery Voltage Group Number CCA (minimum)
Cold Soak @ 0° F (-18° C)
Fuel Supply Pressure
LPG Vapor or Natural Gas
Maximum *Minimum
LPG Liquid (**Maximum)
3.0L, 4 cylinder
3/4 inch NPT Female
LPVapor
Natural Gas or LPLiquid
2 1/2 inch NPT
14 inch H
188.0 cfm (5.3 m
209.0 cfm (6.0 m
O (3.5 kPa)
2
3
/min)
3
/min)
1083° F (584° C) 1056° F (569° C)
12 Volts DC
60 amps (maximum rating)
3 Gal (11.4 L)
4.25 Qts (4 L)
.035
(0.9 mm)
Negative
12 Volts DC
22 NF
420
13.6 inches WC (3.4 kPa) 7 inches WC (1.7 kPa)
312 psi (2,153 kPa)
2 1/2 inch NPT
14 inch H
217 cfm (6.2 m
230 cfm (6.51 m
1128° F (609° C) 1094° F (590° C)
O (3.5 kPa)
2
3
/min)
3
/min)
Fuel Consumption (Standby/Full Load/60Hz)
LPG (Vapor or Liquid) Natural Gas
115.6 cfh (3.3 m3/hr)
334.8 cfh (9.5 m3/hr)
136.7 cfh (3.9 m3/hr)
396.3 cfh (11.2 m3/hr)
* Minimum pressure refers to supply pressure under rated load (maximum gas flow). ** Under any operating condition.
2-1
148.3 cfh (4.2 m3/hr) 420 cfh (11.9 m3/hr)
Page 9
THIS PAGE LEFT INTENTIONALLY BLANK
2-2
Page 10
3. Control Operation (Without Display)
GENERAL
The following describes the function and operation of the PowerCommand play). The switch/indicator and hour meter are lo­cated on the face of the control panel as illustrated in Figure 3-1.
This section covers prestart checks, starting and stopping and operating the generator set (genset). Each operator should read through this entire sec­tion before they attempt to start the generator set. It is essential that the operator be completely familiar with the generator set and the PCC control. Refer to Section 8 for operating recommendations.
Before starting, be sure the following checks have been made and the unit is ready for operation.
®
1301 Control (without dis-
PRESTART CHECKS
Lubrication
Check the engine oil level. Keep the oil level as near as possible to the dipstick high mark without overfil­ling.
Coolant
Check the engine coolant level. Refer to “Cooling Systems” in the Maintenance section of this manu­als for proper procedure.
Fuel
Open all manual shutoff valves in the fuel supply system.
Ventilation
Make sure the generator set cooling inlet/outlet and exhaust ventilation openings are clear (not blocked) and operational.
Remove all loose debris from surrounding area of generator set. Air flow from the radiator fan can blow loose items around and into ventilation open­ings.
Exhaust
Check to make sure entire exhaust system is tight, that no combustible materials are near system, and gases are discharged away from building openings.
EXHAUST GAS IS DEADLY!
Exhaust gases contain carbon monoxide, an odorless and colorless gas. Carbon monoxide is poisonous and can cause unconsciousness and death. Symptoms of carbon monoxide poisoning can include:
w Dizziness w Nausea w Headache w Weakness and Sleepiness
IF YOU OR ANYONE ELSE EXPERIENCE ANY OF THESE SYMPTOMS, GET OUT INTO THE FRESH AIR IMMEDIATELY. If symptoms persist, seek medical attention. Shut down the unit and do not operate it until it has been inspected and repaired.
Protection against carbon monoxide inhalation includes proper installation and regular, frequent visual and audible inspections of the complete exhaust system.
w Throbbing in Temples w Muscular Twitching w Vomiting w Inability to Think Coherently
3-1
Page 11
THREE POSITION ROCKER SWITCH
HOUR
METER
FIGURE 3-1. FRONT PANEL (WITHOUT DISPLAY)
CONTROL PANEL
Figure 3-1 shows the features of the front panel. It includes one−three position rocker switch to oper- ate the genset and a total hours genset meter.
Start/Off/Remote (Auto) Switch
This rocker switch is used to select the three operat­ing modes of the genset (Start/Off/Remote). This switch also contains a lamp which is used to indi­cate engine genset running and genset fault codes.
OFF Mode: The OFF mode is enabled by moving the control rocker switch to the middle position. The OFF mode will disable the control Auto or Manual modes.
If moved to the OFF position during generator set operation (manual or remote start), the engine will immediately shut down. If possible, hot shutdown under load should be avoided to help prolong the reliability of the generator set.
The OFF mode is also used to acknowledge shut­down messages after the fault has been corrected. Moving the switch to the OFF position clears the switch fault indication and resets the control.
Refer to STOPPING later in this section for a de- tailed description of the Stop mode.
REMOTE (Auto) Mode: The Remote (Auto) mode is enabled by moving the control rocker switch to the bottom position. The Remote mode enables start/stop control of the genset from a remote loca­tion.
Refer to STARTING and STOPPING later this sec- tion for a detailed description of the Remote (auto start and stop) mode.
START Mode: The Start mode is enabled by mov­ing the control rocker switch to the top position. When moved to this position, the control will acti­vate the starting system. Refer to STARTING later this section for a detailed description of the Start mode.
Switch Indicator
Used to indicate the following genset status:
Genset running constant on
Genset fault code flashing (refer to Section 5
to interpret fault code indicator)
Total Hours Meter
Displays the total hours of genset operation.
3-2
Page 12
STARTING
The following headings cover the systems used to start the generator set. Figure 3-2 provides a flow chart for remote start/run/stop sequences.
posed of 15 seconds of cranking and 30 seconds of rest.
The InPower service tool is required to change the cycle number, and the crank and rest times. Contact an authorized service center for assistance.
Before starting the generator set, make sure that exhaust and fuel fittings are tight and properly posi­tioned and that proper maintenance has been per­formed. See Prestart Checks in this section.
Starting at the Control Panel (Start Mode)
Press the control Start switch. This will bypass the Time Delay to Start, activate the engine control sys­tem and the starting system. The starter will begin cranking and, after a few seconds, the engine will start and the starter will disconnect.
If the engine does not start, the starter will disen­gage after a specified period of time and the control will indicate a Fail To Start shutdown.
The generator set can be configured for a number of starting cycles (1 to 7 cycles) with set times for crank and rest periods for all starting modes (manual/re­mote). The default setting is for 3 start cycles, com-
To clear a Fail To Start shutdown, move the control switch to the OFF position. Before attempting to re­start, wait two minutes for the starter motor to cool and then repeat the starting procedure. If the engine does not run after a second attempt, refer to the Troubleshooting section.
Starting from a Remote Location (Remote Mode)
Move the control switch to the Remote position. This allows the generator set to be started from a re­mote switch or device (e.g., transfer switch).
In response to the Remote Start, the control initiates the starting sequence as shown in Figure 3-2.
When the switch is in the Remote position, the con­trol will utilize the Time Delay To Start function.
The InPower service tool is required to enable and change the time delay start/stop settings. Contact an authorized service center for assistance.
3-3
Page 13
STOPPING
Before Stopping
Run the generator set at no load for three to five minutes before stopping. This allows the lubricating oil and engine coolant to carry heat away from the combustion chamber and bearings.
Emergency Stop (Optional)
tion), moving the control switch to the OFF position causes the generator set to stop immediately. If possible, hot shutdown under load should be avoided to help prolong the reliability of the genera­tor set.
Stopping from Remote Location (Remote Mode)
An emergency stop button (local or remote mounted) is connected to the customer input of the PCC control. This switch, when used, will immedi­ately shutdown the generator set.
To reset, open (disable) emergency stop button and move the control switch to the OFF position.
Stopping at Control Panel (Manual/Remote Mode)
If the generator set was started at the control panel (Start position) or started remotely (Remote posi-
REMOTE START
CUST. CONNECT 1
TIME DELAY TO
START (0−300 sec)
RATED SPEED
& VOLTAGE
If the control receives a remote stop signal, the gen­erator set completes its normal shutdown sequence (Figure 3-2). (The remote stop signal is actually the removal of the remote start signal to the control.)
The generator set stops after completing the Time Delay To Stop function (0 to 600 seconds).
The InPower service tool is required to enable and change the time delay start/stop settings. Contact an authorized service center for assistance.
2
NOTES:
1. Input from transfer switch, remote start switch, etc.
2. Timer expires.
FIGURE 3-2. STARTING WITH CONTROL IN AUTO MODE
REMOTE START
REMOVED
TIME DELAY TO
STOP (0−600 sec)
2
STOP
3-4
EMERGENCY
STOP OR
CONTROL OFF
BUTTON
Page 14
4. Control Operation (With Display)
GENERAL
The following describes the function and operation of the PowerCommand play). All indicators, control buttons and graphical display are located on the face of the control panel as illustrated in Figure 4-1.
This section covers prestart checks, starting and stopping and operating the generator set (genset). Each operator should read through this entire sec­tion before they attempt to start the generator set. It is essential that the operator be completely familiar with the generator set and the PCC control. Refer to Section 8 for operating recommendations.
Before starting, be sure the following checks have been made and the unit is ready for operation.
®
1301 Control (with dis-
PRESTART CHECKS
Lubrication
Check the engine oil level. Keep the oil level as near as possible to the dipstick high mark without overfil­ling.
Coolant
Check the engine coolant level. Refer to “Cooling Systems” in the Maintenance section of this manu­als for proper procedure.
Fuel
Open all manual shutoff valves in the fuel supply system.
Ventilation
Make sure the generator set cooling inlet/outlet and exhaust ventilation openings are clear (not blocked) and operational.
Remove all loose debris from surrounding area of generator set. Air flow from the radiator fan can blow loose items around and into ventilation open­ings.
Exhaust
Check to make sure entire exhaust system is tight, that no combustible materials are near system, and gases are discharged away from building openings.
EXHAUST GAS IS DEADLY!
Exhaust gases contain carbon monoxide, an odorless and colorless gas. Carbon monoxide is poisonous and can cause unconsciousness and death. Symptoms of carbon monoxide poisoning can include:
w Dizziness w Nausea w Headache w Weakness and Sleepiness
IF YOU OR ANYONE ELSE EXPERIENCE ANY OF THESE SYMPTOMS, GET OUT INTO THE FRESH AIR IMMEDIATELY. If symptoms persist, seek medical attention. Shut down the unit and do not operate it until it has been inspected and repaired.
Protection against carbon monoxide inhalation includes proper installation and regular, frequent visual and audible inspections of the complete exhaust system.
w Throbbing in Temples w Muscular Twitching w Vomiting w Inability to Think Coherently
4-1
Page 15
CONTROL PANEL POWER ON/OFF
MODES
The power on/off modes of the control panel and op­erating software are Power On and Sleep.
Power On Mode: In this mode, power is continu­ously supplied to the control panel. The control’s operating software and control panel LEDs/graphi­cal display will remain active until the Sleep mode is activated.
Sleep Mode: In the Sleep mode, the control’s oper­ating software is inactive and the LEDs and the graphical display on the control panel are all off. Sleep mode is a feature used to reduce battery power consumption when the control is not being used and is in either the Off or Auto mode.
When all conditions are met (i.e., no unacknowl­edged faults and the control is in the Off/Auto mode) the Sleep mode is activated after five minutes of keypad inactivity.
To activate the control and view the menu display without starting the generator set, press any control button.
A qualified service personnel is required to enable or disable the Sleep mode. When shipped from the factory, Sleep mode is enabled for both modes (Off and Auto mode). Internal adjustment of the control also allows the Sleep mode to be active only during the Off mode or disabled for both modes (Off and Auto mode). When disabled, the operating software will always remain active (Power On mode).
GRAPHICAL
DISPLAY
DISPLAY MENU
SELECTION BUTTONS
FIGURE 4-1. FRONT PANEL (WITH DISPLAY)
PREVIOUS MENU
LEVEL BUTTON
LED
INDICATORS
OFF MODE
BUTTON
4-2
Page 16
CONTROL PANEL
TABLE 4-1. SYMBOLS
Figure 4-1 shows the features of the front panel. It includes six LED indicators, the graphical display, and six buttons used to navigate through the menus and adjust parameters.
Graphical Display
This graphical display is used to view menus of the menu-driven operating system. The bottom of the graphical display indicates the functions that are available by pressing the four selection buttons. Re­fer to the menu trees later in this section.
System messages (communication, event, and fault) are also shown on the graphical display. For more information, see System Messages later this section.
Display Text / Symbolic Versions
This graphical display can be set up to show either text or symbolic versions for fault messages, some Operator menus, and the Mode Change menu. A description of commonly used symbols used are in­cluded in Table 4-1. Combinations of symbols are used to display some fault conditions. Additional specialized symbols are also used for some faults (see Section 5).
A qualified service personnel is required to select text or symbolic display. When shipped from the fac­tory, symbolic display is selected.
SYMBOL
Hz
DESCRIPTION
Generator Warning Fault
Generator Shutdown Fault
Coolant Temperature
Oil Pressure
Voltage Alternating Current (VAC)
Voltage Direct Current (VDC)
AC Current
Frequency
Battery
Out of Range
High or Pre-High
Low or Pre-Low
Annunciator
4-3
Page 17
Display Menu Selection Buttons
Four momentary soft-key buttons are used to step through the various menus and to adjust parame­ters. These selection buttons are “active” when a word or symbol in the graphical display is shown above the button. Some submenus do not include any active buttons.
The function of the four selection buttons varies with each menu.
When the selection button can be used to switch to Auto mode.
When the tion button can be used to switch to Manual Run mode.
When the up and down triangles ( are displayed, the selection buttons are used to navigate between a series of submenus.
NOTE: When any Operator menu (Figure 4-12
is displayed, a series of Service menus can be viewed by simultaneously pressing the tons for two seconds.
NOTE: When a fault is displayed, it can be
cleared from the front panel by press­ing the
When a button can be used to abort the Auto or Manual Run mode and return to the Operator
symbol is displayed, the
symbol is displayed, the selec-
and )
and selection but-
or button.
symbol is displayed, the selection
menu that was displayed before the Auto or Manual Run mode was selected.
When ADJUST is displayed, the selection button is used to display an adjustable menu. When the ADJUST button is pressed, the first adjustable parameter or value in the sub­menu is highlighted.
When the tion button is used to navigate to an editable field within a menu.
When the + and − symbols are displayed, the selection buttons are used to increase or de­crease a parameter or value shown on the screen.
When changing values, pressing the button be­low the + symbol increase the value and press­ing the button below the symbol decreases the value.
When SAVE is displayed, the selection but- ton is used to save changes made in a sub­menu. If the Previous Menu button is
pressed before pressing SAVE, the changes are not saved.
Some menus include a list of numbered sub­jects. These menus include numbers in pa­renthesis (for example, (1)) displayed above the selection buttons. The selection buttons are then used to display submenus of the subjects included in the list.
When a black box selection button has no function.
symbol is displayed, the selec-
is displayed, the
4-4
Page 18
Previous Main Menu Button
Off Button
Press the button to view the previous main menu.
NOTE: In the Screen Adjust menu, settings are not
button is pressed.
The
saved when the
button is also used to acknowledge warn­ing and shutdown messages after the fault has been corrected. Pressing this button clears the fault from the front panel display and the previous menu is redisplayed.
NOTE: Pressing the
or button also clears the
fault from the front panel display.
Press the button to switch to the Off mode. The Off mode will disable the control Auto or Manual modes.
If the
button is pressed during generator set op­eration (manual or remote start), the engine will im­mediately shut down. If possible, hot shutdown un­der load should be avoided to help prolong the reli­ability of the generator set.
The
button is also used to acknowledge warn­ing and shutdown messages after the fault has been corrected. Pressing this button clears the fault from the front panel and resets the control.
Not in Auto Indicator
This red lamp is lit when the control is not in the Auto mode.
Shutdown Status Indicator
This red lamp is lit when the control detects a Shut­down condition. The generator set cannot be started when this lamp is on. After the condition is corrected, the lamp can be reset by pressing the
(off) button.
OFF
BUTTON
PREVIOUS MAIN
MENU BUTTON
FIGURE 4-2. PREVIOUS MAIN MENU AND OFF
BUTTONS
Warning Indicator
This yellow lamp is lit whenever the control detects a warning condition. This lamp is automatically shut off when the warning condition no longer exists.
Remote Start Indicator
This green lamp indicates the control is receiving a remote run signal.
Auto Indicator
This green lamp indicates the control is in Auto mode. Auto mode can be selected by pressing the
selection button from any of the Operator me-
nus (see Figure 4-12).
Manual Run Indicator
This green lamp indicates the control is in the Manu­al Run mode. Manual Run mode can be selected by pressing the erator menus (see Figure 4-12).
selection button from any of the Op-
4-5
Page 19
SYSTEM MESSAGES
A system pop-up message is displayed when the event it is displaying becomes active. These pop-up messages remain displayed until pre-empted by
another pop-up message or until the
or the
display buttons is pressed. Once the or the button is pressed, the previous screen is redis­played.
Communication Messages
System messages are displayed for initial power-up or when there is a subsequent loss of communica­tions. Note that the Auto and Manual Run modes can be selected when communication messages are displayed.
Upon initial power-up, the message “Establishing communication with control” is displayed (see Fig­ure 4-3). This menu also displays the screen’s soft­ware number and version.
When the display detects that it is no longer com­municating with the control, the Shutdown, Warn­ing, and Remote Start LEDs are turned off.
FIGURE 4-3. ESTABLISHING COMMUNICATION WITH
CONTROL
If communications are lost, the message “Re-es­tablishing communication with control” is displayed until communications have been re-established (see Figure 4-4). The LEDs then return to the state determined by the control.
If either communication message remains displayed (cannot view other menus), contact an authorized service center for service. This indicates that com­munications between the control panel and the con­trol logic is lost.
FIGURE 4-4. RE-ESTABLISHING COMMUNICATION WITH
CONTROL
4-6
Page 20
Event Messages
When pre-set events (time delay to start or stop) are activated, Event messages are displayed showing the time remaining until the event occurs (see Fig­ure 4-5).
Event = TIME DELAY TO START, or STOP
FIGURE 4-5. EVENT MESSAGE
4-7
Page 21
Fault Messages
A Fault message is an indicator of a Warning or Shutdown condition. It includes the fault number, a short description, and when the fault occurred (see Figure 4-6). Symbolic fault messages include the fault code number and symbols, indicating the type of fault (see Figure 4-7). With the symbolic versions of fault messages, the
and symbols flash.
Section 5 provides a list of fault codes, fault types, messages displayed, and descriptions of the faults.
Five of the most recent faults are placed in a fault history file that can be viewed using the Fault Histo­ry Menus (see Figure 4-18).
Fault Acknowledgement
Shutdown faults must be acknowledged after the faults have been corrected. If in Auto or Manual Run mode, the control must be set to “O” (off). Also, faults are acknowledged when in Auto and the re­mote Start command is removed. Faults are cleared from the control panel display by pressing
the
, , or button.
FIGURE 4-6. FAULT MESSAGE
EXAMPLE OF A SYMBOLIC WARNING FAULT
EXAMPLE OF A SYMBOLIC SHUTDOWN FAULT
Fault = WARNING or SHUTDOWN
214
1
Faults are re-announced if they are detected again after being acknowledged.
FIGURE 4-7. FAULT MESSAGES − SYMBOLIC VERSION
4-8
Page 22
STARTING
The following headings cover the systems used to start the generator set. Figure 4-8 provides a flow chart for remote start/run/stop sequences.
In response to the Remote Start, the control lights the Remote Start indicator and initiates the starting sequence as shown in Figure 4-8.
When the switch is in the Auto position, the control will utilize the Time Delay To Start function.
Before starting the generator set, make sure that exhaust and fuel fittings are tight and properly posi­tioned and that proper maintenance has been per­formed. See Prestart Checks in this section.
Starting at the Control Panel (Manual Mode)
Press the button from any of the Operator menus (see Figure 4-12). This will bypass the Time Delay to Start, activate the engine control system and the starting system. The starter will begin cranking and, after a few seconds, the engine will start and the starter will disconnect.
If the engine does not start, the starter will disen­gage after a specified period of time and the control will indicate a Fail To Start shutdown.
The generator can be configured for 1 to 7 starting cycles with set times for crank and rest periods for all starting modes (manual/remote). The default setting is for 3 start cycles, composed of 15 seconds of cranking and 30 seconds of rest.
The InPower service tool or access to the Setup menu is required to change the cycle number, and the crank and rest times. Contact an authorized ser­vice center for assistance.
To clear a Fail To Start shutdown, press the (off) button. Before attempting to restart, wait two min­utes for the starter motor to cool and then repeat the starting procedure. If the engine does not run after a second attempt, refer to the Troubleshooting sec- tion.
Starting from a Remote Location (Auto Mode)
Press the selection button from any of the Op­erator menus (see Figure 4-12) This allows the gen­erator set to be started from a remote switch or de­vice (e.g., transfer switch).
The InPower service tool or access to the Setup menu is required to enable and change the time delay start/stop settings. Contact an authorized ser­vice center for assistance.
Cold Starting with Loads
In accordance with NFPA 110, Cummins Power Generation recommends installing diesel standby generator sets (life safety systems) equipped with engine jacket water coolant heaters in locations where the minimum ambient temperature is above 40
°F (4°C). NFPA also requires that the engine be
heated as necessary to maintain the water jacket temperature determined by the manufacturer for cold start and load acceptance for the type of sys­tem.
Although Cummins Power Generation generator sets may start in temperatures below 40 when equipped with engine jacket water coolant heaters, it might take more than 10 seconds to warm the engine before a load can be applied and may also require other supplemental starting aids. Refer to engine manual for specific engine require­ments.
On generator sets equipped with a graphic display, the Low Coolant Temperature (Code 203) mes- sage, in conjunction with illumination of the Warning LED, is provided to meet the requirements of NFPA
110. The engine cold sensing logic initiates a warn­ing when the engine jacket water coolant tempera­ture falls below 70
the ambient temperature falls below 40 cold engine may be indicated even though the cool­ant heaters are connected and operating correctly. Under these conditions, although the generator set may start, it may not be able to accept load within 10 seconds. When this condition occurs, check the coolant heaters for proper operation. If the coolant heaters are operating properly, other precautions may be necessary to warm the engine before apply­ing a load.
°F (21°C). In applications where
°F (4°C)
°F (4°C), a
4-9
Page 23
STOPPING
Before Stopping
Run the generator set at no load for three to five minutes before stopping. This allows the lubricating oil and engine coolant to carry heat away from the combustion chamber and bearings.
Emergency Stop
An emergency stop button (customer supplied) can be connected to the customer input of the PCC con­trol. This switch, when used, will immediately shut­down the generator set, light the red Shutdown sta­tus indicator and display the emergency stop mes­sage (Code 61).
(Auto indicator is lit), pressing the
(Off) button causes the generator set to stop immediately. If possible, hot shutdown under load should be avoided to help prolong the reliability of the genera­tor set.
Stopping from Remote Location (Auto Mode)
If the control receives a remote stop signal, the gen­erator set completes its normal shutdown sequence (Figure 4-8). (The remote stop signal is actually the removal of the remote start signal to the control.)
To reset, open (disable) emergency stop button and press the
(Off) button.
Stopping at Control Panel (Manual/Auto Mode)
If the generator set was started at the control panel (Manual Run indicator is lit) or started remotely
REMOTE START
CUST. CONNECT 1
TIME DELAY TO
START (0−300 sec)
RATED SPEED
&VOLTAGE
REMOTE START
REMOVED
TIME DELAY TO
STOP (0−600 sec)
The generator set stops after completing the Time Delay To Stop function (0 to 600 seconds).
The InPower service tool or access to the Setup menu is required to enable and change the time delay start/stop settings. Contact an authorized ser­vice center for assistance.
2
EMERGENCY
STOP OR
CONTROL OFF
BUTTON
2
NOTES:
1. Input from transfer switch, remote start switch, etc.
2. Timer expires.
FIGURE 4-8. STARTING WITH CONTROL IN AUTO MODE
STOP
4-10
Page 24
SELECTING AUTO, MANUAL RUN AND
OFF MODES
Auto, Manual Run, and Off modes can be selected:
From any of the Operator menus
When the message “Establishing commu-
nication with control” is displayed
When the message “Re-establishing commu­nication with control” is displayed
Switching to Auto, Manual Run, or Off mode can be restricted to authorized personnel. If a control panel is set up with the mode change access code feature enabled, an access code must first be entered be­fore the mode can be changed.
The InPower service tool or access to the Setup menu is required to enable/disable the mode change access code feature. Contact an authorized service center for assistance.
Entering the Mode Change Access Code
If the mode change access code feature is enabled, an access code must be entered to switch to Auto, Manual Run, or Off mode. The text and symbolic versions of the Mode Change menu are shown in Figure 4-9.
To enter the mode change access code,
1. With the first character highlighted, press the button below to the + or symbols until the val­ue reads “1.”
TEXT VERSION
SYMBOLIC VERSION
FIGURE 4-9. MODE CHANGE MENU
2. Press the arrow selection button
to move
to the next numeric character.
3. Press the button below the + or symbols until the value reads “2.”
4. Press the arrow selection button
to move
to the next numeric character.
5. Press the button below the + or symbols until the value reads “1.”
6. After you have completed entering the pass­word, press the arrow selection button
.
NOTE:If an incorrect password is entered, the Op-
erator menu that was displayed before Auto, Manual Run, or Off mode was se­lected is redisplayed.
4-11
Page 25
Selecting Auto Mode
To switch to Auto mode (see Figure 4-10):
1. Press the
button on any of the Operator menus or the “Establishing/Re-establishing communication with control” menus.
2. If the mode change access code feature is en­abled, the Mode Change Access Code menu is displayed. Enter the mode change access code as described above.
3. A menu with alternating arrows is displayed above a second ond
button. The Operator menu that was
symbol. Press the sec-
displayed before Auto mode was selected is re­displayed and the Auto indicator is lit.
4. To disable auto mode, press the
button.
NOTE:Manual Run mode can also be selected
while in Auto mode.
THIS MENU IS DISPLAYED ONLY IF THE MODE CHANGE ACCESS CODE FEATURE IS ENABLED
ALTERNATING ARROWS ARE DISPLAYED
AUTO MODE SELECTED
FIGURE 4-10. SELECTING AUTO MODE
4-12
Page 26
Selecting Manual Run Mode
To switch to Manual Run mode (see Figure 4-11):
1. Press the
button on any of the Operator me­nus or if displayed, the “Establishing/Re-estab­lishing communication with control” menus.
2. If the mode change access code feature is en­abled, the Mode Change Access Code menu is displayed. Enter the mode change access code as described on the previous page.
3. A menu with alternating arrows is displayed above a second
symbol. Press the second
button to start the genset.
The Operator menu that was displayed before Manual Run mode was selected is redisplayed and the Manual Run indicator is lit.
To disable Manual Run mode, press the
button.
NOTE: Auto mode can also be selected while in
Manual Run mode. Switching to Auto mode may result in the generator set shutting down.
THIS MENU IS DISPLAYED ONLY IF THE MODE CHANGE ACCESS CODE FEATURE IS ENABLED
ALTERNATING ARROWS ARE DISPLAYED
Aborting the Transition to Auto or Manual Run Mode
If the Mode Change Access Code menu or the menu showing alternating arrows above the
buttons is displayed, the transition to Auto or
Manual Run mode is aborted when:
Either the
The
, , or button is pressed.
or button is not pressed within
ten seconds.
If the transition to Auto or Manual Run mode is aborted, the Operator menu that was displayed be­fore Auto or Manual Run mode was selected is re­displayed.
or
MANUAL RUN MODE SELECTED
FIGURE 4-11. SELECTING MANUAL RUN MODE
4-13
Page 27
OPERATOR MENUS
Alternator Status Menu
Figures 4-12 and 4-13 show block representations of the following Operator menus.
Engine Status
Alternator Status
Line-to-Line Voltage
Line-to-Neutral Voltage
Alternator Amperage
To navigate between the Operator menus, press the buttons next to the graphical display.
The Operator menus can be used to select Auto or Manual Run modes.
and symbols in the
Engine Status Menu
This menu displays the engine starting battery volt­age, engine coolant temperature, engine oil pres­sure, and hours of engine operation. (Oil pressure ­only available on some models).
This menu displays genset power (in kVA), frequen­cy, and engine speed (RPM). (In applications with­out current transformers, the kVA is not shown.)
Alternator Line-to-Line Voltage Menu
This menu displays L1-L2, L2-L3, and L3-L1 line-to­line voltages for three phase applications only.
Alternator Line-to-Neutral Voltage Menu
This menu displays line-to-neutral voltages for L1, L2, and L3 for three phase wye configurations only. (In delta configurations, this menu is not shown.)
Alternator Single Phase Voltage Menu
This menu displays L1-N, L2-N, and L1-L2 voltages for single phase applications only.
Alternator Amperage Menu
This menu displays L1, L2, and L3 amperage. (In applications without current transformers, this menu is not shown.)
4-14
Page 28
OPERATOR MENUS Text Version
THREE PHASE
ONLY
THREE PHASE
WYE ONLY
CURRENT
SENSE ONLY
SINGLE PHASE ONLY
FIGURE 4-12. OPERATOR MENUS (TEXT VERSION)
4-15
Page 29
OPERATOR MENUS Symbolic Version
THREE PHASE
ONLY
THREE PHASE
WYE ONLY
CURRENT
SENSE ONLY
SINGLE PHASE ONLY
FIGURE 4-13. OPERATOR MENUS (SYMBOLIC VERSION)
4-16
Page 30
THIS PAGE LEFT INTENTIONALLY BLANK
4-17
Page 31
SERVICE MENUS
Figure 4-14 shows a block representation of the menus available from the Service Menus.
The first Service Menu can be viewed from any of the Operator menus by simultaneously pressing the
and selection buttons for two seconds. The first Service Menu provides access to the following menus:
Setup Menus − Used by Service personnel. Adjusting the Setup menus is restricted by a password. To view the Setup menus only, press the VIEW button on the Setup pass­word menu.
History / About − see page 4-20
The third Service Menu can be viewed by pressing the Menu. The third Service Menu provides access to the Network Status menus.
selection button on the second Service
Status Menu
The Status menu is displayed when the (5) button is pressed on the second Service Menu. The Status menu shows the following:
Voltage regulator (drive) level, in percentage of duty cycle
Governor regulator (drive) level, in percent­age of duty cycle. This value is only dis­played if the governor is enabled.
Screen Adjust − see page 4-22
To return to the Operator menu that was displayed prior to viewing the Service Menu, press the
button.
The second Service Menu can be viewed by press­ing the Menu. The second Service Menu provides access to the following menus:
Fault History see page 4-24
Status see below
Lamp Test The six LEDs on the control
panel should light as long as the button (6) is pressed.
selection button on the first Service
Network Status Menus
The Network Status menus are displayed when the (7) button is pressed on the third Service Menu. Two menus are used to display the quantity of the follow­ing devices that are connected to the network.
Auto Mains Failure (AMF) modules
Universal Annunciators
Bar graphs
Battery chargers
Controls
I/O modules
Operator panels (any type)
4-18
Page 32
1ST
SERVICE
MENU
SETUP MENUS
2ND
SERVICE
MENU
HISTORY / ABOUT MENUS
SEE PAGE 4-20
SCREEN ADJUST MENU
SEE PAGE 4-22
3RD
SERVICE
MENU
FAULT HISTORY MENUS
SEE PAGE 4-24
FIGURE 4-14. SERVICE MENUS
4-19
Page 33
HISTORY / ABOUT MENUS
About Genset Submenu
Figure 4-15 shows a block representation of the History / About menu. The first History / About sub­menu is displayed when the (2) button is pressed on the Service Menu.
Press the buttons next to the the graphical display to navigate between the Histo-
ry / About submenus. Press the to the Service Menu.
and symbols in
button to return
History Submenu
This submenu displays the number of engine starts, hours of operation for the engine, and hours of op­eration for the control.
This submenu displays the generator set model number and rating.
About Control Submenu
This submenu displays the control’s part number, serial number (up to 11 characters), software part number, and software version.
About Display Submenu
This submenu displays the optional control panel software part number, software version, screen part number, and screen version of the display.
4-20
Page 34
HISTORY / ABOUT MENUS
FIGURE 4-15. HISTORY / ABOUT MENUS
4-21
Page 35
SCREEN ADJUST MENU
Figure 4-16 shows a block representation of the Screen Adjust menu. The Screen Adjust submenu is displayed when the (3) button is pressed in the first Service Menu.
NOTE: If the Previous Menu button
pressed before pressing the SAVE but­ton, the changes are not saved.
5. Press the Menu.
button to return to the Service
is
Adjusting Values/Parameters
1. Press the ADJUST selection button to select the first parameter or value to be changed.
2. Press the + or selection buttons to adjust val­ues or select parameters.
3. Press the arrow selection button gate to the next or previous adjustable value or parameter.
4. After adjusting values/selecting parameters, press the SAVE button to save your settings.
to navi-
SCREEN ADJUST MENU
Screen Adjust Menu
This menu allows for adjusting the screen’s contrast and brightness and for selecting the units of mea­surement (SAE or SI) to be displayed.
Contrast and Brightness: Press the + or selection buttons to adjust the screen’s con­trast and brightness. Changing the bright­ness setting also affects the brightness of the LEDs on the control panel.
Units: Press the + or − selection buttons to select SAE (_F, PSI) or SI (C, kPa) units of measurement to be displayed.
FIGURE 4-16. SCREEN ADJUST MENU
4-22
Page 36
THIS PAGE LEFT INTENTIONALLY BLANK
4-23
Page 37
FAULT HISTORY MENU
Figure 4-18 shows a block representation of the Fault History menu. The first Fault menu is dis­played when the (4) button is pressed on the sec- ond Service Menu. If there are any active fault sub­menus, an “Active Fault” heading is displayed for the most recent active fault. All other fault subme­nus display a “Fault History” heading. Five of the most recent faults can be viewed. An example of how a fault code is displayed is shown in Figure 4-17.
TIME FAULT OCCURRED
FAULT CODE
FAULT
DESCRIPTION
Press the buttons next to the
and symbols in
the graphical display to navigate between menus.
Press the
button to return to the Service Menu.
Information on faults is found in Section 5.
FIGURE 4-17. FAULT HISTORY MENU EXAMPLE
4-24
Page 38
FAULT HISTORY MENU
Active Fault
Fault 1
OR
Fault 2
Oldest Fault (Maximum of 5)
FIGURE 4-18. FAULT HISTORY MENU
4-25
Page 39
THIS PAGE LEFT INTENTIONALLY BLANK
4-26
Page 40
5. Troubleshooting
GENERAL
The generator set control continuously monitors en­gine sensors for abnormal conditions when genset is operating, such as low oil pressure and high cool­ant temperature. If any of these conditions occur, the control (with graphical display) will light a yellow Warning lamp or a red Shutdown lamp and display a message on the graphical display. A control without the graphical display indicates a shutdown condi­tion by intermittent flashing of the status indicator.
This section lists the warning and shutdown codes/ messages (Table 5-1), and suggests troubleshoot­ing procedures (Table 5-2).
Displayed error codes that are not listed in Table 5-2 will require an authorized service representative to correct the fault. Contact an authorized service cen­ter for assistance.
SAFETY CONSIDERATIONS
WARNING
nents can result in severe personal injury or death. Keep the control box and circuit breaker box covers in place during troubleshooting.
High voltages are present when the generator set is running. Do not open the generator control box or the circuit breaker box while the generator set is running.
WARNING
can cause severe personal injury or death. Arc­ing at battery terminals, light switch or other equipment, flame, pilot lights and sparks can ig­nite battery gas. Do not smoke, or switch trouble light ON or OFF near battery. Discharge static electricity from body before touching bat­teries by first touching a grounded metal sur­face.
Contacting high voltage compo-
Ignition of explosive battery gases
Ventilate battery area before working on or near battery—Wear goggles—Stop generator set and disconnect charger before disconnecting battery cables—Disconnect negative () cable first and reconnect last.
CAUTION
source before disconnecting battery cables. Otherwise, disconnecting cables can result in voltage spikes damaging to DC control circuits of the generator set.
WARNING
set can cause severe personal injury or death. Prevent accidental starting by disconnecting the negative () cable from the battery terminal.
When troubleshooting a generator set that is shut down, make certain the generator set cannot be ac­cidentally restarted as follows:
1. Without Display: Move the Start/Off/Remote switch on the control panel to the OFF position.
With Display: Press the the Off mode.
2. Turn off or remove AC power from the battery charger.
3. Remove the negative () battery cable from the generator set starting battery.
Disconnect battery charger from AC
Accidental starting of the generator
button to switch to
5-1
Page 41
READING FAULT CODES
If the genset contains the graphical display and a fault occurs, the fault code/message can be viewed in the display. If the control does not contain the graphical display, the fault code is read from the control switch indicator.
After the fault is acknowledged and corrected, the recorded fault will be deleted from the control panel memory, but will remain in a data log to maintain a fault code history. The InPower service tool is re­quired to view this data log.
Reading Fault Codes Using Graphical Display:
Refer to Fault History Menu in Section 4, which de- scribes how to view fault codes using the graphical display.
Reading Fault Codes Using Control Switch Indi­cator (PCC without display): The control panel
rocker switch contains a status indicator lamp. This lamp is used to flash genset status and shutdown fault codes. (Only the last shutdown fault code is flashed.) The following describes how to interpret the status indicator light.
Do not move the control switch to the OFF position before interpreting the fault code. Moving the switch to OFF will clear the fault indication.
Constant Fast Flashing = Genset starting.
Constant On = Genset running.
Intermittent Flashing = A genset Shutdown
fault condition exists (Warning conditions are not displayed). All of the Shutdown faults de­scribed in Table 5-1 can be announced with the status indicator lamp.
An example of a single digit fault code Two blinks, followed by a two-second pause indicates a fault code of “2”.
An example of a two digit fault code first digit in the code is flashed, followed by a half-second pause, and then the second digit is flashed, fol­lowed by a two-second pause.
LINE CIRCUIT BREAKER (OPTIONAL)
Optional line circuit breaker/box mounts to the side of the control saddle bracket. If the load exceeds the circuit breaker current rating, the line circuit breaker will open, preventing the generator from being over­loaded. If the circuit breaker trips, locate the source of the overload and correct as necessary. Manually reset the breaker to reconnect the load to the gener­ator.
CONTROL AND DIAGNOSTICS VIA
NETWORK OR PERSONAL COMPUTER
(LAPTOP)
See your authorized Cummins Power Generation dealer regarding software, hardware and network requirements for control and diagnostics via net­work or personal computer.
5-2
Page 42
FAULT CODES
The fault codes have been divided into four catego­ries to help you determine what corrective action to take for safe operation of the generator set. Use Table 5-1 to find the category (CTG) and fault de­scription for all codes. Gaps in the code numbers
are for codes that do not apply to this genset model. Also, some of the codes listed are fea­ture dependent, and will not be displayed by this genset control.
Category A Fault Codes: Pertain to engine or al-
ternator shutdown faults that require immediate re­pair by qualified service personnel (generator set non-operational). Control prevents the generator set from being restarted if shutdown fault is not cor­rected.
TABLE 5-1. FAULT CODES
DISPLAYED MESSAGE/SYMBOLS
CTG
CODE LAMP
C 1
A 2
A 12
A 13
A 14
C 15
A 27
Shutdown
Shutdown
Shutdown
Shutdown
Shutdown
Shutdown
Shutdown
TEXT VERSION
HIGH COOLANT TEMP
LOW OIL PRESSURE
HIGH AC VOLTAGE
LOW AC VOLTAGE
OVER FREQUENCY
UNDER FREQUENCY
EXCITATION FAULT
Category B Fault Codes: Consist of faults that can affect generator set performance or can cause en-
gine, alternator, or connected equipment dam­age. Operate genset only when it is powering criti-
cal loads and cannot be shut down. Requires repair by qualified service personnel.
Category C Fault Codes: Consist of faults that are repairable by site personnel. Service will be re­quired by qualified service personnel if site person­nel cannot resolve the problem after taking the cor­rective actions suggested in Table 5-2.
Category D Fault Codes: Indicates non-critical op­erational status of generator set, external faults, or customer fault inputs. May require repair by quali­fied service personnel.
SYMBOLIC
VERSION
12
13
14Hz
15Hz
27
DESCRIPTION
Indicates that the engine coolant temperature is above normal and has reached the shutdown trip point for the
1
configured time delay.
Indicates the engine oil pressure has dropped below normal and has reached the shutdown trip point for the configured time
2
delay.
Indicates that the one or more measured AC output voltages has exceeded the threshold for longer than a specified time limit. The threshold and time limits are 130% of nominal for 1 second or 110% of nominal for 10 seconds.
Indicates that the measured AC output voltage is below the threshold for longer than a specified time limit. The threshold and time limits are 85% of nominal for 10 seconds.
Indicates that the alternator frequency is 6 hertz above the governor reference.
Indicates that the alternator frequency is 6 hertz under the governor reference.
Indicates that a loss of voltage or frequency sensing from the generator has occurred.
A 31
Shutdown
OVERSPEED
5-3
31
Indicates that the engine has exceeded normal operating speed. The default thresholds are 1725 RPM (50 Hz) or 2075 RPM (60 Hz).
Page 43
TABLE 5-1. FAULT CODES (CONT.)
DISPLAYED MESSAGE/SYMBOLS
CTG DESCRIPTION
CTG DESCRIPTION
A 38
A 45
LAMPCODE
LAMPCODE
Shutdown
Shutdown
TEXT VERSION
FIELD OVERLOAD
SPEED SIGNAL LOST
SYMBOLIC
VERSION
38
45
Indicates that the Field AVR Duty Cycle has been at the maximum continuously for 15 seconds.
Indicates that no magnetic pickup pulses were sensed for a Loss of Speed delay. If a magnetic pickup is not installed, then speed sensing is performed by monitoring AC line frequency.
A 46
C 61
A 71
C 72
C 73
B 74
D 75
D 81-83
Shutdown
Shutdown
Shutdown
Shutdown
Shutdown
Shutdown
Shutdown
Shutdown
HIGH AC CURRENT
EMERGENCY STOP
SPEED HZ MATCH
FAIL TO CRANK
FAIL TO START
FAIL TO STOP
Customer Input 1
Annunciator Fault 1 3
73
75
46
61
72
74
Indicates that alternator output current (one or more phases) has exceeded 150% of the rated output current continuously for more than 10 seconds.
Indicates an Emergency Stop has been activated.
Indicates that measured engine speed and measured alternator AC output frequency do
71
not agree.
The genset has failed to sense rotation for two start attempts. This indicates a possible fault with the control, speed sensing, or the starting system.
The genset has failed to start after a set number of crank attempts. This indicates a possible fuel system or air induction problem (engine cranks but fails to start).
The genset continues to run after receiving a shutdown command from the controller.
The nature of the fault is an optional customer selection.
The nature of the annunciator fault is an optional customer selection.
D 84-91
D 92-95
A 102
A 103
Shutdown
Shutdown
Shutdown
Shutdown
Base I/O Module Input 1 8
Aux I/O Module Input 9 12
VOLTAGE BIAS OOR
SPEED BIAS OOR
81-83
84-91
92-95
102
(None)
5-4
The nature of the Base I/O Module “Fault” is an optional customer selection.
The nature of the Aux I/O Module “Fault” is an optional customer selection.
Indicates the voltage bias circuit output is out of range (OOR), high or low. (I/O Module option.)
Indicates the speed bias circuit output is out of range (OOR), high or low. (I/O Module option.)
Page 44
TABLE 5-1. FAULT CODES (CONT.)
DISPLAYED MESSAGE/SYMBOLS
CTG DESCRIPTION
CTG DESCRIPTION
A 106
LAMPCODE
LAMPCODE
Shutdown
TEXT VERSION
I/O MODULE LOST
SYMBOLIC
VERSION
106
Indicates the data link between the I/O module and the Base board is lost.
D 163
170
D 171
174
C 202
C 203
D 204
D 205
D 205
(None)
(None)
Warning
Warning
Warning
Warning
Warning
Base I/O Module Input 1 8
Aux I/O Module Input 9 12
PRE-HIGH COOLANT TEMP
LOW COOLANT TEMP
Customer Input 1
(spec A) Customer Input 1
(begin spec B) Service Engine
(None)
(None)
204
205
205
202
203
The nature of the Base I/O Module “Event” is an optional customer selection.
The nature of the Aux I/O Module “Event” is an optional customer selection.
Indicates engine is operating near cooling system capacity. Increase in load or higher ambient temperature may cause High Coolant Temp (code 1) shutdown.
Indicates that the engine coolant temperature is below the adjusted setpoint. This may indicate that the coolant heater is not operating or is not circulating coolant.
The nature of the fault is an optional customer selection.
The nature of the fault is an optional customer selection.
Indicates that emissions criteria might not be met due to one of the following:
Engine running in open loop, Lean mixture Rich mixture Failed fuel system component
B 212
C 213
C 214
C 215
B 216
B 217
Warning
Warning
Warning
Warning
Warning
Warning
COOLANT SENSOR OOR
LOW BATTERY
HIGH BATTERY
PRE-LOW OIL PRESSURE
HIGH AC CURRENT
OIL PRESS SENSOR OOR
5-5
212
213
214
215
216
217
Indicates the coolant temperature sensor output is out of range (OOR), high or low.
Indicates battery voltage supply to the control is approaching a low level at which unpredictable operation can occur.
Indicates battery voltage supply to the control is approaching a high level at which damage to the control can occur.
Indicates that the engine oil pressure is approaching an unacceptable level.
Indicates that the alternator output current (one or more phases) has exceeded 130% of nominal, or has exceeded 110% of nominal for 60 seconds.
Indicates the oil pressure sensor output is out of range (OOR), high or low.
Page 45
TABLE 5-1. FAULT CODES (CONT.)
DISPLAYED MESSAGE/SYMBOLS
CTG DESCRIPTION
CTG DESCRIPTION
B 219
C 221
D 222
224
LAMPCODE
LAMPCODE
Warning
Warning
Warning
TEXT VERSION
CHARGER FAILURE
WEAK BATTERY
Annunciator Fault 1 3
SYMBOLIC
VERSION
219
221
Indicates the battery charging alternator has not reached a acceptable voltage range within the selected time period (default = 120 seconds).
Indicates that the genset battery voltage is below battery thresholds during cranking.
The nature of the annunciator fault is an optional customer selection.
222-224
D 225
D 226
233
Warning
Warning
ANNUNCIATOR OUTPUT CON­FIGURATION ERROR
Base I/O Module Input 1 8
Indicates a mismatch in the configuration of one of the annunciator relay outputs.
225
The nature of the Base I/O Module “Fault” is an optional customer selection.
226-233
D 234
237
Warning
Aux I/O Module Input 9 12
The nature of the Aux I/O Module “Fault” is an optional customer selection.
B 252
Warning
I/O MODULE LOST
234-237
252
Indicates an intermittent data link between the I/O module and the Base board.
5-6
Page 46
WARNING
Hazards present in troubleshooting can cause equipment damage, severe personal injury or death. Only trained and experienced service personnel with knowledge of fuels, electric­ity, and machinery hazards should perform service procedures. Read Important Safety Instruc­tions pages and observe all instructions and precautions in this manual.
TABLE 5-2. WARNING AND SHUTDOWN CODES
FAULT CODE CORRECTIVE ACTION
1 HIGH COOLANT TEMP
Lamp: Shutdown
2 LOW OIL PRESSURE
Lamp: Shutdown
15 UNDER FREQUENCY
Lamp: Shutdown
Indicates engine has overheated (coolant temperature has risen above the shut­down trip point). Allow engine to cool down completely before proceeding with the following checks.
1. Check coolant level and replenish if low. Look for coolant leaks and repair if nec­essary.
2. Check for obstructions to cooling airflow and correct as necessary.
3. Check fan belt and repair or tighten if necessary.
4. Check blower fan and circulation pumps on remote radiator installations.
5. Reset control and restart after locating and correcting problem.
Indicates engine oil pressure has dropped below the shutdown trip point. Check oil level. If oil level is low, replenish. Reset control and restart.
Indicates possible fuel system problem or overload condition.
1. Check for dirty or plugged air filter and replace if necessary (see Maintenance sections).
2. Check operation by disconnecting load and restarting generator set.
3. Adjust fuel system (refer to Section 7).
4. Gaseous fuel delivery to the set is inadequate. Contact an authorized service center for service.
61 REMOTE E-STOP
Lamp: Shutdown
72 FAIL TO CRANK
Lamp: Shutdown
5. Reset the control and restart after correcting the problem.
Indicates remote Emergency Stop activation. To reset the remote Emergency Stop button:
1. Deactivate (disable) remote emergency stop button.
2. Move the rocker switch to the OFF position or press the OFF button.
3. Select the desired operating mode (manual or remote).
Indicates possible fault with control, speed sensing or starting system. See fault code 213 for corrective action.
5-7
Page 47
WARNING
Hazards present in troubleshooting can cause equipment damage, severe personal injury or death. Only trained and experienced service personnel with knowledge of fuels, electric­ity, and machinery hazards should perform service procedures. Read Important Safety Instruc­tions pages and observe all instructions and precautions in this manual.
TABLE 5-2. WARNING AND SHUTDOWN CODES (CONT.)
FAULT CODE CORRECTIVE ACTION
73 FAIL TO START
Lamp: Shutdown
75 CUSTOMER INPUT #1
Lamp: Shutdown
8491 BASE I/O MODULE INPUT 18
Lamp: Shutdown
8491 AUX I/O MODULE INPUT 912
Lamp: Shutdown
98 AMBIENT TEMP HIGH
Lamp: Shutdown
163170 BASE I/O MODULE INPUT 18
Lamp: None
Indicates possible fuel system problem. (Engine cranks but fails to start)
1. Open any closed fuel shutoff valve.
2. Check for dirty or plugged air filter and replace if necessary.
3. Gaseous fuel delivery to the set is inadequate. Contact an authorized service center for service.
4. Reset the control and restart after correcting the problem.
The nature of the fault is an optional customer selection. Example inputs: Low Coolant Level, Low Fuel Pressure, Ground Fault, etc.
Each of the fault functions can be programmed (using InPower service tool or ac­cess to Setup menu), as follows:
Warning or Shutdown (Default = Warning) (See fault code 204 for Warning)
Change display name using up to 32 characters.
The nature of the fault is an optional customer selection. Example inputs: Low Fuel Day Tank, Water In Fuel, Ground Fault, etc.
Each of the fault functions can be programmed (using InPower service tool or ac­cess to Setup menu), as follows:
Warning, Shutdown or Event (Default = Warning) (See fault code 226233 for
Warning and code 163170 for Event)
Change display name using up to 32 characters.
The nature of the fault is an optional customer selection. Example inputs: Low Fuel Day Tank, Water In Fuel, Ground Fault, etc.
Each of the fault functions can be programmed (using InPower service tool or ac­cess to Setup menu), as follows:
Warning, Shutdown or Event (Default = Warning) (See fault code 234237 for
Warning and code 171174 for Event)
Change display name using up to 32 characters.
Indicates air temperature in genset room has risen above the shutdown trip point. Check genset room ventilation system (vents/ducts for blockage and dampers/lou­vers for proper operation).
The nature of the event is an optional customer selection.
Each event function can be programmed (using InPower service tool or access to Setup menu), as follows:
Change display name using up to 32 characters.
Select active low or high input.
5-8
Page 48
WARNING
Hazards present in troubleshooting can cause equipment damage, severe personal injury or death. Only trained and experienced service personnel with knowledge of fuels, electric­ity, and machinery hazards should perform service procedures. Read Important Safety Instruc­tions pages and observe all instructions and precautions in this manual.
TABLE 5-2. WARNING AND SHUTDOWN CODES (CONT.)
FAULT CODE CORRECTIVE ACTION
171174 AUX I/O MODULE INPUT 912
Lamp: None
202 PRE-HIGH COOL TMP
Lamp: Warning
203 LOW COOLANT TEMP
Lamp: Warning
Set is not operating. Warning occurs when engine coolant temperature is 70° F (21° C) or lower. NOTE: In applica-
tions where the ambient temperature falls below 405 F (45 C), Low Coolant Temp may be indicated even though the coolant heaters are operating.
204 CUSTOMER INPUT #1
Lamp: Warning
The nature of the event is an optional customer selection.
Each event function can be programmed (using InPower service tool or access to Setup menu), as follows:
Change display name using up to 32 characters.
Select active low or high input.
Indicates engine is operating near cooling system capacity. Increase in load or higher ambient temperature may cause High Coolant Temp (1) shutdown. Review fault code 1 correction list for other possible causes.
Indicates engine coolant heater is not operating or is not circulating coolant. Check for the following conditions:
1. Coolant heater not connected to power supply. Check for blown fuse or discon­nected heater cord and correct as required.
2. Check for low coolant level and replenish if required. Look for possible coolant leaks and repair as required.
The nature of the fault is an optional customer selection. Example inputs: Low Coolant Level, Low Fuel Pressure, Ground Fault, etc.
Each of the fault functions can be programmed (using InPower service tool or ac­cess to Setup menu), as follows:
Warning or Shutdown (Default = Warning) (See fault code 75 for Shutdown)
Change display name using up to 32 characters.
213 LOW BATTERY
Lamp: Warning
214 HIGH BATTERY
Lamp: Warning
Indicates battery voltage supply to the control is approaching a low level at which unpredictable operation will occur.
1. Discharged or defective battery. a. Check the battery charger fuse. b. Recharge or replace the battery.
2. Poor battery cable connections. Clean the battery cable terminals and tighten all connections.
3. Check battery charge voltage float level if applicable (raise float level).
Indicates battery voltage supply to the control is approaching a high level at which damage to the control can occur. Check float level on battery charger if applicable (lower float level).
5-9
Page 49
WARNING
Hazards present in troubleshooting can cause equipment damage, severe personal injury or death. Only trained and experienced service personnel with knowledge of fuels, electric­ity, and machinery hazards should perform service procedures. Read Important Safety Instruc­tions pages and observe all instructions and precautions in this manual.
TABLE 5-2. WARNING AND SHUTDOWN CODES (CONT.)
FAULT CODE CORRECTIVE ACTION
215 PRE-LOW OIL PRES
Lamp: Warning
221 WEAK BATTERY
Lamp: Warning
226233 BASE I/O MODULE INPUT 18
Lamp: Warning
234237 AUX I/O MODULE INPUT 912
Lamp: Warning
226233 BASE I/O MODULE INPUT 18
Lamp: Warning
238 OIL TEMP HIGH
Lamp: Warning
242 AMBIENT TEMP HIGH
Lamp: Warning
Indicates engine oil pressure has dropped to an unacceptable level. If generator is powering critical loads and cannot be shut down, wait until next shutdown period and then follow fault code 2 procedure.
Indicates that during cranking, the battery voltage is at or below the weak battery warning trip point for a time greater than or equal to the weak battery set time. See code 213 for corrective action.
The nature of the fault is an optional customer selection. Example inputs: Low Coolant Level, Low Fuel Pressure, Ground Fault, etc.
Each of the fault functions can be programmed (using InPower service tool or ac­cess to Setup menu), as follows:
Warning, Shutdown or Event (Default = Warning) (See fault code 8491 for Shut-
down and code 163170 for Event)
Change display name using up to 32 characters.
The nature of the fault is an optional customer selection. Example inputs: Low Coolant Level, Low Fuel Pressure, Ground Fault, etc.
Each of the fault functions can be programmed (using InPower service tool or ac­cess to Setup menu), as follows:
Warning, Shutdown or Event (Default = Warning) (See fault code 9295 for Shut-
down and code 171174 for Event)
Change display name using up to 32 characters.
The nature of the fault is an optional customer selection. Example inputs: Low Coolant Level, Low Fuel Pressure, Ground Fault, etc.
Each of the fault functions can be programmed (using InPower service tool or ac­cess to Setup menu), as follows:
Warning or Shutdown (Default = Warning) (See fault code 75 for Shutdown)
Change display name using up to 32 characters.
Indicates engine has begun to overheat (oil temperature has risen to an unaccept­able level). Review fault code 1 correction list for possible causes.
Indicates the ambient temperature has exceeded the warning threshold for genset room temperature. Check genset room ventilation system (vents/ducts for block­age and dampers/louvers for proper operation).
5-10
Page 50
CONTROL PANEL FUSES
After replacing an opened fuse, and the fuse re­opens, contact an authorized service center for ser­vice.
Customer Switched B+
If any external customer connected controls or indi­cators fail to function that are powered by genset
switched B+, replace the Customer Switched B+ (15A) fuse.
Voltage Reference
The generator set will shut down and may display Fault Code 13 or 27 if this fuse opens. This fuse pro­tects the PCC control circuitry from damage due to a generator fault condition.
CUSTOMER
SWITCHED B+ 15A
VOLTAGE
REFERENCE 10A
FIGURE 5-1. CONTROL PANEL FUSES
5-11
Page 51
THIS PAGE LEFT INTENTIONALLY BLANK
5-12
Page 52
6. Maintenance
GENERAL
Establish and adhere to a definite schedule for maintenance and service based on the application and severity of the environment. The recom­mended service intervals for a generator set on STANDBY power service is covered in Table 6-1 and for PRIME power service Table 6-2. If the set will be subjected to extreme operating conditions, the service intervals should be reduced according­ly. Some of the factors that can affect the mainte­nance schedule are the following:
Extremes in ambient temperature
Exposure to weather
Exposure to salt water
Exposure to dust, sand or other airborne con-
taminates.
Consult with your local Cummins Power Generation distributor if the generator set will be subjected to any extreme operating conditions and determine a suitable schedule of maintenance. Use the running time meter to keep an accurate log of all service per­formed for warranty support. Perform all service at the time period indicated or after the number of op­erating hours indicted, whichever comes first. Use Table 6-1 (Standby) or Table 6-2 (Prime) to deter­mine the maintenance required and then refer to the sections that follow for the correct service pro­cedures.
6-1
Page 53
TABLE 6-1. PERIODIC MAINTENANCE SCHEDULE FOR
STANDBY POWER GENSETS
SERVICE TIME
MAINTENANCE ITEMS
Daily
or after
8 Hours
General set inspection X
1
Monthly
or after 100
Hours
6 Months or
after 250
Hours
Yearly
or after 500
Hours
Check engine oil level X
Check coolant level X
Check coolant heater(s) X
Check air cleaner (normal duty filter) X
2,3
Check all hardware (fittings, clamps, fasteners, etc.) X
Check battery electrolyte level X
Check generator air outlet X
Change engine oil and filter X
Check radiator hoses for wear and cracks X
Check drive belt X
2,7
4
5
Check anti-freeze concentration X
Check AC generator and controls X
Replace PCV valve X
Inspect distributor cap and rotor X
Inspect secondary ignition wires X
Clean cooling systems X
Inspect or replace spark plugs X
Inspect or replace oxygen sensor X
6
8,9
X1- Check for oil, fuel, cooling and exhaust system leaks. Check exhaust system audibly and visually with set running and repair
any leaks immediately.
2
- Perform more often in extremely dusty conditions.
X
3
- Replace element after 500 hours.
X
4
X
- Replace if hard or brittle.
5
- Visually check belt for evidence of wear or slippage. Replace if hard or brittle.
X
6
- Replace every 1,000 hours.
X
7
X
- Perform at least once a year.
8
- Must be performed by a qualified mechanic. Contact your authorized service center.
X
9
- Replace every 1,500 hours (recommended).
X
6-2
Page 54
TABLE 6-2. PERIODIC MAINTENANCE SCHEDULE FOR
PRIME POWER GENSETS
SERVICE TIME
MAINTENANCE ITEMS
24 Hours
General set inspection X
1
100
Hours
250
Hours
500
Hours
1000
Hours
Check engine oil level X
Check coolant level X
Check coolant heater(s) X
Check air cleaner (heavy duty filter) X
2,3
Check all hardware (fittings, clamps, fasteners, etc.) X
Check battery electrolyte level X
Check anti-freeze concentration X
Check generator air outlet X
Change engine oil and filter X
2
Replace PVC valve X
Check radiator hoses for wear and cracks X
Check drive belt X
4
5
Check AC generator and controls X
Clean cooling systems X
Inspect distributor cap and rotor X
Inspect secondary ignition wires X
Inspect or replace oxygen sensor X
7,8
Check PCV hoses, tubes, and fittings X
Inspect or replace spark plugs X
6
X1- Check for oil, fuel, cooling and exhaust system leaks. Check exhaust system audibly and visually with set running and repair
any leaks immediately.
2
- Perform more often in extremely dusty conditions.
X
3
- Replace element every 2000 hours.
X
4
- Replace if hard or brittle.
X X5- Visually check belt for evidence of wear or slippage. Replace if hard or brittle.
6
- Replace every 2,000 hours.
X
7
- Replace every 1,500 hours (recommended).
X
8
X
- Must be performed by a qualified mechanic. Contact your authorized service center.
6-3
Page 55
GENERATOR SET INSPECTION
During operation, be alert for mechanical problems that could create unsafe or hazardous conditions. The following sections cover several areas that should be frequently inspected for continued safe operation.
Exhaust System
With the generator set operating, inspect the entire exhaust system visually and audibly, including the exhaust manifold, muffler, and exhaust pipe. Check for leaks at all connections, welds, gaskets, and joints and also make sure that exhaust pipes are not heating surrounding areas excessively. If any leaks are detected, shut down the generator set and have leaks corrected immediately.
WARNING
Inhalation of exhaust gases can re­sult in severe personal injury or death. Be sure deadly exhaust gas is piped outside and away from any windows, doors, vents or other inlets to building and not allowed to accumulate in in­habitable areas.
Fuel System
With the generator set operating, inspect the fuel supply lines and fittings for leaks. Check any flex­ible sections for cuts, cracks and abrasions and make sure they are not rubbing against anything that could cause breakage. If any leaks are de­tected, shut off fuel supply valves, shut down gener­ator set and have them corrected immediately.
AC Voltmeter (Alternator Menu): At no load, the line-to-line or line-to-neutral voltage(s) should be the same as the genset nameplate rating.
AC Ammeter (Alternator Menu): At no load the current ratings should be zero. With a load applied, each line current should be about the same.
Panel Lamp Test Button: Press and hold this but­ton to test all front panel LEDs. Make sure that all LEDs are OK and then release the button.
DC Electrical System
Check the terminals on the batteries for clean and tight connections. Loose or corroded connections create resistance which can hinder starting. Refer to BATTERIES later in this section for cleaning and safety precautions.
Engine
Monitor fluid levels and oil pressure and coolant temperatures frequently. Most engine problems give an early warning. Look and listen for changes in engine performance, sound, or appearance that can indicate service or repair is needed. Some en­gine changes to look for are as follows:
Misfire
Vibration
WARNING
Ignition of fuel can cause severe personal injury or death by fire or explosion. Do not permit any flame, cigarette, arcing switch or equipment, pilot light, or other igniter near the fuel system or in areas sharing ventilation.
AC Electric System
Check the following while the genset is operating.
Frequency/RPM (Alternator/Engine Menu): The generator frequency should be stable and the read­ing should be the same as the genset nameplate rating (50 or 60 Hz/1500 or 1800 RPM).
Unusual noises
Sudden changes in engine operating tempera-
tures or pressures
Excessive exhaust smoke
Loss of power
An increase in oil consumption
An increase in fuel consumption
Fuel, oil, or coolant leaks.
6-4
Page 56
GENERATOR SET MAINTENANCE
(Battery Disconnected)
WARNING
can cause severe personal injury or death. Arc­ing at battery terminals, light switch or other equipment, flame, pilot lights and sparks can ig­nite battery gas. Do not smoke, or switch trouble light ON or OFF near battery. Discharge static electricity from body before touching bat­teries by first touching a grounded metal sur­face.
Ventilate battery area before working on or near battery—Wear goggles—Stop genset and dis­connect charger before disconnecting battery cables—Disconnect negative () cable first and reconnect last.
Ignition of explosive battery gases
WARNING
Accidental starting of the generator set can cause severe personal injury or death. Prevent accidental starting by disconnecting the negative (−) cable from the battery terminal before beginning maintenance procedures.
When performing the following maintenance proce­dures, make certain the generator set cannot be ac­cidentally restarted as follows:
1. Without Display: Move the Start/Off/Remote switch on the control panel to the OFF position.
With Display: Press the
button to switch to
the Off mode.
2. Turn off or remove AC power from the battery charger.
3. Remove the negative () battery cable from the generator set starting battery.
CAUTION
Disconnect battery charger from AC source before disconnecting battery cables. Otherwise, disconnecting cables can result in voltage spikes damaging to DC control circuits of the set.
Mechanical Inspection
With the generator set stopped, check for loose belts and fittings, leaking gaskets and hoses, or any signs of mechanical damage. If any problems are found, have them corrected immediately.
6-5
Page 57
LUBRICATION SYSTEM
Before the initial start, check dipstick to be sure crankcase is filled with oil. See Specifications sec- tion for lubricating oil capacity.
Gensets are shipped with oil added. Be sure to check oil level before initial start.
Oil Recommendations
Refer to Figure 6-1 for the recommended oil viscos­ity grades at various ambient temperatures. Oils must conform to the American Petroleum Institute (API) classification SJ or SJ/CD. When selecting the oil viscosity, pick the grade that is right for the lowest temperature expected. Oil that is too thick can result in a lack of lubrication when the engine is started.
MODELS GGMA, GGMB, GGMC
10W30
5W30
FIGURE 6-1. OIL VISCOSITY
NORMAL DUTY
AIR FILTER
OIL
CHECK
OIL
FILL
COOLANT
RECOVERY
TANK
OIL
FILTER
RADIATOR
FILL
FIGURE 6-2. ENGINE OIL FILTER
6-6
Page 58
Engine Oil Level
Check the engine oil level during engine shutdown periods at the intervals specified in the Mainte­nance Table. The dipstick is stamped with FULL and ADD to indicate the level of oil in the crankcase. For accurate readings, shut off the engine and wait approximately 10 minutes before checking the en­gine oil level. This allows oil in the upper portion of the engine to drain back into the crankcase.
WARNING
hot oil and cause severe burns. Do NOT check oil while the generator set is operating.
Keep the oil level as near as possible to the FULL mark on the dipstick. Remove the oil fill cap and add oil of the same quality and brand when necessary.
Crankcase pressure can blow out
ENGINE OIL
LEVEL DIPSTICK
CAUTION
Do not operate the engine with the
oil level below the ADD mark or above the FULL mark. Overfilling can cause foaming or aeration of the oil. Operation below the ADD mark can cause loss of oil pressure.
Engine Oil Change
WARNING
termined that contact with used engine oil can cause cancer or reproductive toxicity. Do not contact oil or breath vapors. Use rubber gloves and wash exposed skin.
Used oil and filters must be disposed of proper­ly to avoid environmental damage and clean-up liability. Check all federal, state and local regu­lations for disposal requirements.
Run engine until thoroughly warm before draining oil. Stop the set, place a pan under the drain outlet and remove the oil drain plug (Figure 6-4) or open the drain valve. After the oil is completely drained, replace the drain plug or close the drain valve. Re­place oil filter, then refill with oil of the correct API viscosity grade for the temperature conditions.
State or federal agencies have de-
FIGURE 6-3. OIL LEVEL DIPSTICK
WARNING
Hot crankcase oil can cause burns if
it is spilled or splashed on skin. Keep fingers and hands clear when removing the oil drain plug and wear protective clothing.
6-7
Page 59
Oil Filter Change
Fill the oil filter with clean lubricating oil. To fill, pour the oil into the center hole of the filter.
Spin off oil filter (Figure 6-2) and discard it in accor­dance with local environmental regulations. Thor­oughly clean filter mounting surface.
CAUTION
ing oil before installing it on the engine. Lack of engine lubrication while the filter is being pumped full of oil may be harmful to the engine.
Fill the oil filter with clean lubricat-
Apply a thin film of oil to filter gasket and install new element. Spin element on by hand until gasket just touches mounting pad and then turn an additional 1/2 to 3/4 turn. Do not overtighten (Figure 6-3).
With oil in crankcase, start engine and check for leaks around filter element. Retighten only as much as necessary to eliminate leaks but do not overtigh­ten.
6-8
Page 60
COOLING SYSTEM
Coolant Level
Gensets are shipped with coolant added. Be sure to check coolant level before initial start.
Coolant Requirements
Satisfactory engine coolant inhibits corrosion and if necessary protects against freezing. Use a 50/50 coolant solution (50% pure water and 50% anti­freeze). If temperatures below -37 possible, use a mixture of 65% antifreeze and 35% water. Do not use an antifreeze that contains anti­leak additives.
The water used for engine coolant should be clean, low in mineral content and free of any corrosive chemicals such as chloride, sulfate or acid. Use soft water. Well water often contains lime and other ma­terials which eventually can clog the radiator core and reduce the cooling efficiency and can also cause heater element failure.
CAUTION
The coolant heater must not be op­erated while the cooling system is empty or when the engine is running or damage to the heater will occur.
CAUTION
Do not add cold coolant to a hot en­gine. Engine castings can be damaged. Allow the engine to cool to below 120 ° F (50 ° C) before
adding coolant.
° F (-38° C) are
CAUTION
Loss of coolant can allow engine to overheat without protection of shutdown de­vice and cause severe damage to the engine. Maintain coolant level for proper operation of the high engine temperature shutdown system.
Check the coolant recovery tank level. Note the nor­mal level when the engine is cool. Add coolant to the recovery tank to replace the normal loss of coolant.
Filling the Cooling System
WARNING
gine cool down before removing coolant pres­sure cap. Turn cap slowly, and do not open it ful­ly until the pressure has been relieved.
Check to make sure that all drain cocks are closed and all hose clamps secure. Remove the radiator pressure cap (Figure 6-2) and slowly fill the cooling system with the recommended coolant.
CAUTION
damaged if coolant is filled improperly.
When the engine is first started, remove the pres­sure cap and monitor the coolant level. As trapped air is expelled from the system, the coolant level may drop and additional coolant must be added. Replace the pressure cap when the coolant level is stable.
To prevent severe scalding, let en-
The engine can overheat and be
6-9
Page 61
Draining and Flushing
WARNING
from children and animals. Follow local envi­ronmental regulations for disposal.
Some coolant is toxic. Keep away
Refill the cooling system with the recommended coolant (refer to Filling the Cooling System).
With cooling system properly filled and the engine has been run, connect heater plug to receptacle.
To maintain adequate corrosion protection and re­move rust and scale deposits, drain and flush radia­tor at the recommended interval.
CAUTION
The heater element will burn out if engine coolant is removed with heater con­nected to power source.
Disconnect engine coolant heater from power source (if equipped).
Allow the engine to cool and then remove radiator pressure cap. Open the radiator drain cock and re­move the coolant drain plug.
Do not remove drain plug: If engine is equipped with optional coolant drain extension, open valve to drain coolant, or if engine is equipped with optional engine coolant heater, drain coolant by removing hose and clamp from bottom of heater.
When the coolant is drained, place the end of a wa­ter hose into the radiator filler and turn on water sup­ply. Regulate the flow of water into the radiator until it is equal to the outflow from drain openings. Con­tinue flushing until outflow from drains is clear of rust sediment.
Replace the coolant drain plug (or attach coolant hose to heater/close coolant drain valve) and close the radiator drain cock when flushing is complete.
CAUTION
The heater element will burn out if power is connected before it is filled with cool­ant or if straight antifreeze solution is used for coolant. Before connecting power, fill the en­gine with coolant and run if for a while to circu­late coolant through the heater.
Radiator
Inspect the exterior of the radiator for obstructions. Remove all dirt or foreign material with a soft brush or cloth. Use care to avoid damaging the fins. If available, use low pressure compressed air or stream of water (maximum of 35 psi/242 kPa), in opposite direction of normal air flow to clean radia­tor. If using water, protect the engine and the gener­ator from over spray.
Coolant Heater (Optional)
Check the operation of the coolant heater by verify­ing that hot coolant is being discharged from the outlet hose. Do not touch outlet hose − if heater is operational, radiant heat should be felt with hand held close to outlet hose.
WARNING
gine can result in serious burns. Do not touch cooling system or engine during genset mainte­nance until they are cool.
Contact with cooling system or en-
COOLANT
DRAIN PLUG
OIL DRAIN
PLUG
FIGURE 6-4. DRAIN PLUG LOCATIONS
6-10
Page 62
AIR FILTERS
Heavy Duty Air Filter (Figure 6-5)
Clean filter element every 100 hours of operational time or sooner if the service indicator button pops up indicating air restriction. Replace air filter after 2000 hours of operational time.
Inspect all components of the air filtering system in­cluding all ducts and hoses. The vacuator valve dumps collected dust automatically. Verify that all connections and clamps are tight and inspect each component for cracks, dents, or other damage. Re­pair or service as required.
CAUTION
to prevent damage. If the filter does become damaged, install recommended replacement part.
The following procedure should be followed when cleaning or replacing the element.
1. Release the three cover clips and remove the air cleaner cover.
Filters should be handled with care
Gently move the end of the filter up and down and side to side or twist to break the seat.
3. Wipe out the interior of the air cleaner housing and cover with a clean, damp cloth. Make sure that ALL dust is removed from ALL interior sur- faces of the air cleaner housing. Be careful not to damage the sealing area on the outlet tube.
4. CLEAN: Tap filter on a flat surface to remove dirt. Place a light source inside filter and inspect for air passage. If necessary, apply a low pres­sure air source (30 psi) to the inside of filter to remove as much dirt as possible.
NEW: Inspect new air filter for shipping dam­age. Pay attention to the inside of the open end (sealing area). Do not install a damaged filter.
5. Install air filter. The seal area is on the inside of the open end of the filter. The sealing area will stretch slightly and adjust itself over the outlet tube. To complete the seal, apply pressure at the outer rim of the filter, not the flexible center. No cover pressure is required to hold the seal.
2. Slowly remove the air filter to reduce the amount of dust dislodged. There may be some initial resistance when removing the filter.
SERVICE
INDICATOR
6. Install the air cleaner cover (with vacuator valve pointed downward) and secure with the three cover clips.
COVER
COVER
CLIP
VACUATOR
VALVE
AIR
OUTLET
FIGURE 6-5. HEAVY DUTY AIR CLEANER
6-11
Page 63
Normal Duty Air Filter (Figure 6-6)
Clean air filter every 100 hours of operational time, more often in extremely dust conditions. Replace air filter after 500 hours of operational time.
FILTER
The following procedure should be followed when cleaning or replacing the element.
1. Remove wing nut in center of filter cover (Fig­ure 6-6).
2. Remove cover and filter. Tap filter on a flat sur­face to remove dirt.
3. Place a light source inside filter and inspect for air passage. If necessary, apply a low pressure air source (30 psi) to the inside of filter to re­move as much dirt as possible.
4. Install air filter and cover and secure with wing nut.
WING
NUT
COVER
FIGURE 6-6. NORMAL DUTY AIR CLEANER
6-12
Page 64
DRIVE BELT REPLACEMENT
Belt Replacement
Belt Removal
1. Disconnect the negative () cable from the bat­tery to prevent accidental starting.
2. Remove engine alternator side fan guard (be­tween engine and radiator) to gain access to the drive belt and alternator.
3. Loosen the two screws that secure the alterna­tor to the engine to remove belt tension. Re­move drive belt.
1. Install new belt over pulleys.
2. Adjust the alternator for correct belt tension. The belt is generally correctly tensioned when there is an 3/8 inch of depression on the belt between the water pump and the alternator pulley.
3. Install fan guard.
4. Connect the negative () cable to the battery.
5. Start genset and visually check belt for proper alignment with engine running.
3/8 INCH
DEPRESSION
ALTERNATOR
BRACKET
FIGURE 6-7. DRIVE BELT REPLACEMENT
6-13
Page 65
IGNITION SYSTEM
The ignition system consists of a solid state elec­tronic distributor, ignition coil pack, high tension wires and spark plugs. Maintenance consists of pe­riodic inspections to detect possible problems and replacement of worn or deteriorated parts. The igni­tion system must be completely functional or the set may run poorly or be unable to carry full load. Per­form the following inspections at recommended in­tervals.
If the spark plugs show any of the following condi­tions, the engine may require additional service. Contact your authorized service distributor for help.
Carbon Fouled - Overly Rich Mixture
Oil Fouled - High oil consumption
Burned - Excessive engine temperature
Spark Plugs
Remove the spark plugs at the intervals specified in the Maintenance Table and inspect for damaged or cracked insulators, worn electrodes, or excessive carbon deposits. Replace the spark plug if any of these conditions are noted. Clean those plugs that can be reused and regap (Figure 6-8) to the amount specified in the Specifications section.
Before installing the spark plugs:
Clean all dirt and grit away from the spark plug
seats.
Lightly lubricate spark plug threads with high
temp anti-seize compound.
High Tension Wires
Check the spark plug wires for good contact at the ignition coil, distributor and spark plugs. Terminal connections should be tight and fully seated. All spark plug covers and cable end boots should be in good condition and fit tightly. There should be no breaks or cracks in the insulation. Replace the wire if any of these conditions are noted.
Spark Coil/Distributor Cap
Clean the top of the spark coil and distributor cap. Check for cracks, carbon tracks or corrosion in the high tension terminal hole(s). Replace the coil pack or distributor cap if any of these conditions are noted.
FIGURE 6-8. GAPPING SPARK PLUGS
6-14
Page 66
BATTERIES
WARNING
can cause severe personal injury or death. Arc­ing at battery terminals, light switch or other equipment, flame, pilot lights and sparks can ig­nite battery gas. Do not smoke, or switch trouble light ON or OFF near battery. Discharge static electricity from body before touching bat­teries by first touching a grounded metal sur­face.
Ventilate battery area before working on or near battery—Wear goggles—Stop genset and dis­connect charger before disconnecting battery cables—Disconnect negative () cable first and reconnect last.
CAUTION
source before disconnecting battery cables. Otherwise, disconnecting cables can result in voltage spikes damaging to DC control circuits of the set.
Check the condition of the starting batteries at the interval specified in the Maintenance Table. To pre­vent dangerous arcing, always disconnect the neg­ative ground cable from the battery before working on any part of the electrical system or the engine. Disregard the sections On Checking Specific Gravi­ty and Checking Electrolyte Level if using a “mainte­nance-free” battery.
Ignition of explosive battery gases
Disconnect battery charger from AC
Cleaning Batteries
WARNING
that is harmful to the skin and eyes. Do not get the substance in your eyes or contact with skin. Wear goggles and protective, rubber gloves and apron when servicing batteries.
In case of contact, immediately wash skin with soap and water. In case of contact, immediately flood eyes with large amounts of water for a minimum of 15 minutes. IMMEDIATELY CALL A PHYSICIAN.
Electrolyte is a dilute sulfuric acid
Keep the batteries clean by wiping them with a damp cloth whenever dirt appears excessive.
If corrosion is present around the terminal connec­tions, remove battery cables and wash the termi­nals with a solution consisting of 1/4 pound of bak­ing soda added to 1 quart of water. (This solution is also used for washing down spilled electrolyte.)
Be sure the vent plugs are tight to prevent cleaning solution from entering the cells.
After cleaning, flush the outside of the battery and surrounding areas with clean water.
Keep the battery terminals clean and tight. After making connections, coat the terminals with a light application of petroleum jelly or non-conductive grease to retard corrosion.
Checking Specific Gravity
Use a battery hydrometer to check the specific gravity of the electrolyte in each battery cell.
Hold the hydrometer vertical and take the reading. Correct the reading by adding four gravity points (0.004) for every ten degrees the electrolyte tem­perature is above 80
° F (27° C). A fully charged bat-
tery will have a corrected specific gravity of 1.260. Charge the battery if the reading is below 1.215.
Checking Electrolyte Level
CAUTION
unless the engine will run long enough (two to three hours) to assure a thorough mixing of wa­ter and electrolyte.
Check the level of the electrolyte (acid and water solution) in the batteries at least every 200 hours of operation.
If necessary, fill the battery cells to the bottom of the filler neck with distilled water and recharge. If one cell is low, check case for leaks. Keep the battery case clean and dry. An accumulation of moisture will lead to a more rapid discharge and battery fail­ure.
Do not add water in freezing weather
6-15
Page 67
Battery Replacement
Always replace the starting battery with the same number and type (vented, lead acid). Properly dis­pose of battery in accordance with local environ­mental agency requirements.
WARNING
can cause severe personal injury or death. Do not mutilate or burn the battery in a fire for dis­posal.
Damage to case will release electrolyte which is harmful to the skin and eyes and is also toxic. Burning of battery may cause an explosion.
Electrolyte or explosion of battery
NiCad Batteries
NiCad (nickel-cadmium) battery systems are often specified where extreme high or low ambient tem­perature is expected because their performance is less affected by temperature extremes than that of lead-acid batteries.
NiCad batteries require special battery chargers in order to bring them to the full-charge level. These chargers must be provided with filter to reduce “charge ripple” which can disrupt engine and gener­ator control systems.
6-16
Page 68
OUT-OF-SERVICE PROTECTION
When the set will be stored or removed from opera­tion for an extended period of time, take the follow­ing precautions to prevent rust accumulation, corro­sion of bearing surfaces within the engine and gum formation in the fuel system. Perform the following procedures as outlined in this manual.
Preparing Set for Storage
9. Remove the air cleaner and seal off the carbu­retor air inlet opening and PVC hose.
10. Plug the exhaust outlets to prevent entrance of moisture, bugs, dirt, etc.
11. Clean and wipe entire unit. Coat parts suscepti­ble to rust with a light coat of oil. Cover entire set loosely after engine has cooled down.
1. Exercise the set as described in Operation sec­tion until the engine is up to operating tempera­ture.
2. Shut down the engine.
3. Disconnect engine coolant heater from power source (if equipped).
4. Turn off and disconnect battery charger (if equipped).
5. Disconnect battery (negative [] first) and store in a cool, dry place. Connect battery to charger every 30 days to maintain it at full charge.
6. Drain the engine oil while still warm and refill with new oil recommended for set. Attach a tag indicating type of oil used.
7. Remove the spark plugs and pour two ounces of rust preventative oil into each spark plug opening. Crank the set for five seconds to dis­tribute the oil on the cylinder walls and then re­place the spark plugs.
Returning Set to Service
1. Remove protective cover.
2. Remove exhaust plugs, seal from carburetor and PVC hose and replace air cleaner.
3. Check oil dipstick to make sure crankcase is full.
4. Refill cooling system.
5. Reconnect battery (positive [+] cable first) and check specific gravity.
6. Connect the battery charger (if applicable).
7. Connect engine coolant heater to power supply (if applicable).
8 Remove all loads before starting set.
9. Start set and apply load of at least 50% of nameplate rating.
8. Drain the cooling system including the engine block.
10. Check all gauges for normal readings. Set is now ready for service.
6-17
Page 69
THIS PAGE LEFT INTENTIONALLY BLANK
6-18
Page 70
7. Operating Recommendations
NO-LOAD OPERATION
Periods of no load operation should be held to a minimum. If it is necessary to keep the engine run­ning for long periods of time when no electric output is required, best engine performance will be ob­tained by connecting a load bank of at least 30 per­cent of nameplate rating.
EXERCISE PERIOD
Generator sets on continuous standby must be able to go from a cold start to being fully operational in a matter of seconds. This can impose a severe bur­den on engine parts.
Regular exercising keeps engine parts lubricated, prevents oxidation of electrical contacts and in gen­eral helps provide reliable engine starting.
Exercise the generator set at least once a month for a minimum of 30 minutes, under not less than 30 percent of the nameplate rating.
LOW OPERATING TEMPERATURE
Use a coolant heater if a separate source of power is available. The optional heater will help provide re­liable starting under adverse weather conditions. Be sure the voltage of the separate power source is correct for the heater element rating.
CAUTION
the cooling system is full before applying power to the heater.
To avoid damage to heater, be sure
HIGH OPERATING TEMPERATURE
Refer to the genset nameplate for the maximum ambient operating temperature, if applicable.
7-1
Page 71
THIS PAGE LEFT INTENTIONALLY BLANK
7-2
Page 72
Cummins Power Generation
1400 73rd Ave. NE Minneapolis, MN 55432 USA
Phone 1 763 574 5000 Toll-free 1 800 888 6626 Fax 1 763 574 5298 Email ask.powergen@cummins.com www.cumminspower.com
CumminsR, the “C” logo, and “Our energy working for you.” are trademarks of Cummins Inc.
E2009 Cummins Power Generation, Inc. All rights reserved.
Loading...