Save these instructions. This manual contains important instructions that should be followed during
installation and maintenance of the generator set.
Safe and efficient operation can be achieved only if the equipment is properly operated and maintained.
Many accidents are caused by failure to follow fundamental rules and precautions.
1.1Warning, Caution, and Note Styles Used in This
Manual
The following safety styles and symbols found throughout this manual indicate potentially hazardous
conditions to the operator, service personnel, or equipment.
DANGER
Indicates a hazardous situation that, if not avoided, will result in death or serious injury.
WARNING
Indicates a hazardous situation that, if not avoided, could result in death or serious injury.
CAUTION
Indicates a hazardous situation that, if not avoided, could result in minor or moderate injury.
Indicates information considered important, but not hazard-related (e.g., messages relating to
property damage).
1.2General Information
This manual should form part of the documentation package supplied by Cummins Power Generation with
specific generator sets. In the event that this manual has been supplied in isolation please contact your
authorized distributor.
It is in the operator’s interest to read and understand all warnings and cautions contained within
the documentation relevant to the generator set, its operation and daily maintenance.
Hot Pressurized Liquid
Contact with hot liquid can cause severe burns.
Do not open the pressure cap while the engine is running. Let the engine cool down before
removing the cap. Turn the cap slowly and do not open it fully until the pressure has been
relieved.
WARNING
Moving Parts
Moving parts can cause severe personal injury.
Use extreme caution around moving parts. All guards must be properly fastened to prevent
unintended contact.
WARNING
Toxic Hazard
Used engine oils have been identified by some state and federal agencies to cause cancer or
reproductive toxicity.
Do not ingest, breathe the fumes, or contact used oil when checking or changing engine oil.
Wear protective gloves and face guard.
WARNING
Electrical Generating Equipment
Incorrect operation can cause severe personal injury or death.
Do not operate equipment when fatigued, or after consuming any alcohol or drug.
WARNING
Toxic Gases
Substances in exhaust gases have been identified by some state and federal agencies to cause
cancer or reproductive toxicity.
Do not breathe in or come into contact with exhaust gases.
WARNING
Combustible Liquid
Ignition of combustible liquids is a fire or explosion hazard which can cause severe burns or
death.
Do not store fuel, cleaners, oil, etc., near the generator set.
WARNING
High Noise Level
Generator sets in operation emit noise, which can cause hearing damage.
Wear appropriate ear protection at all times.
Hot Surfaces
Contact with hot surfaces can cause severe burns.
Wear appropriate PPE when working on hot equipment and avoid contact with hot surfaces.
WARNING
Electrical Generating Equipment
Incorrect operation and maintenance can result in severe personal injury or death
Make sure that only suitably trained and experienced service personnel perform electrical and/or
mechanical service.
WARNING
Toxic Hazard
Ethylene glycol, used as an engine coolant, is toxic to humans and animals.
Wear appropriate PPE. Clean up coolant spills and dispose of used coolant in accordance with
local environmental regulations.
WARNING
Combustible Liquid
Ignition of combustible liquids is a fire or explosion hazard which can cause severe burns or
death.
Do not use combustible liquids like ether.
WARNING
Automated Machinery
Accidental or remote starting of the generator set can cause severe personal injury or death.
Isolate all auxiliary supplies and use an insulated wrench to disconnect the starting battery
cables (negative [–] first).
WARNING
Fire Hazard
Materials drawn into the generator set are a fire hazard. Fire can cause severe burns or death.
Make sure the generator set is mounted in a manner to prevent combustible materials from
accumulating under the unit.
WARNING
Fire Hazard
Accumulated grease and oil are a fire hazard. Fire can cause severe burns or death.
Keep the generator set and the surrounding area clean and free from obstructions. Repair oil
Fire Hazard
Materials drawn into the generator set are a fire hazard. Fire can cause severe burns or death.
Keep the generator set and the surrounding area clean and free from obstructions.
NOTICE
Keep multi-class ABC fire extinguishers handy. Class A fires involve ordinary combustible
materials such as wood and cloth. Class B fires involve combustible and flammable liquid fuels
and gaseous fuels. Class C fires involve live electrical equipment. (Refer to NFPA No. 10 in
applicable region.)
NOTICE
Before performing maintenance and service procedures on enclosed generator sets, make sure
the service access doors are secured open.
NOTICE
Stepping on the generator set can cause parts to bend or break, leading to electrical shorts, or to
fuel, coolant, or exhaust leaks. Do not step on the generator set when entering or leaving the
generator set room.
1.3Generator Set Safety Code
Before operating the generator set, read the manuals and become familiar with them and the equipment.
Safe and efficient operation can be achieved only if the equipment is properly operated and maintained.
Many accidents are caused by failure to follow fundamental rules and precautions.
WARNING
Electrical Generating Equipment
Incorrect operation and maintenance can result in severe personal injury or death.
Read and follow all Safety Precautions, Warnings, and Cautions throughout this manual and the
documentation supplied with the generator set.
1.3.1Moving Parts Can Cause Severe Personal Injury or Death
• Keep hands, clothing, and jewelry away from moving parts.
• Before starting work on the generator set, disconnect the battery charger from its AC source, then
disconnect the starting batteries using an insulated wrench, negative (–) cable first. This will prevent
accidental starting.
• Make sure that fasteners on the generator set are secure. Tighten supports and clamps; keep
guards in position over fans, drive belts, etc.
• Do not wear loose clothing or jewelry in the vicinity of moving parts or while working on electrical
equipment. Loose clothing and jewelry can become caught in moving parts.
• If any adjustments must be made while the unit is running, use extreme caution around hot
manifolds, moving parts, etc.
The generator set should be placed on level ground with adequate open space around it. The immediate
area around the generator set should be free of any flammable material.
NOTICE
Access or service doors must be closed and locked before repositioning, and they must remain
locked during transportation and siting.
NOTICE
The generator set is capable of operating at inclines of up to +/– 10 degrees, however, for optimal
performance and reliability, any incline should be +/– 5 degrees.
1.3.3Positioning of Generator Set - Open Sets
The area for positioning the set should be adequate and level, and the area immediately around the set
must be free of any flammable material.
1. Important Safety Instructions7-2016
1.4Electrical Shocks and Arc Flashes Can Cause
Severe Personal Injury or Death
WARNING
Electric Shock Hazard
Voltages and currents present an electrical shock hazard that can cause severe burns or death.
Contact with exposed energized circuits with potentials of 50 Volts AC or 75 Volts DC or higher
can cause electrical shock and electrical arc flash. Refer to standard NFPA 70E or equivalent
safety standards in corresponding regions for details of the dangers involved and for the safety
requirements.
Guidelines to follow when working on de-energized electrical systems:
• Use proper PPE. Do not wear jewelry and make sure that any conductive items are removed from
pockets as these items can fall into equipment and the resulting short circuit can cause shock or
burning. Refer to standard NFPA 70E for PPE standards.
• De-energize and lockout/tagout electrical systems prior to working on them. Lockout/Tagout is
intended to prevent injury due to unexpected start-up of equipment or the release of stored energy.
Please refer to the lockout/tagout section for more information.
• De-energize and lockout/tagout all circuits and devices before removing any protective shields or
making any measurements on electrical equipment.
• Follow all applicable regional electrical and safety codes.
Guidelines to follow when working on energized electrical systems:
It is the policy of Cummins Inc. to perform all electrical work in a de-energized state. However,
employees or suppliers may be permitted to occasionally perform work on energized electrical
equipment only when qualified and authorized to do so and when troubleshooting, or if deenergizing the equipment would create a greater risk or make the task impossible and all other
alternatives have been exhausted.
NOTICE
Exposed energized electrical work is only allowed as per the relevant procedures and must be
undertaken by a Cummins authorized person with any appropriate energized work permit for the
work to be performed while using proper PPE, tools and equipment.
In summary:
• Do not tamper with or bypass interlocks unless you are authorized to do so.
• Understand and assess the risks - use proper PPE. Do not wear jewelry and make sure that any
conductive items are removed from pockets as these items can fall into equipment and the resulting
short circuit can cause shock or burning. Refer to standard NFPA 70E for PPE standards.
• Make sure that an accompanying person who can undertake a rescue is nearby.
1.4.1AC Supply and Isolation
NOTICE
Local electrical codes and regulations (for example, BS EN 12601:2010 Reciprocating internal
combustion engine driven generating sets) may require the installation of a disconnect means
for the generator set, either on the generator set or where the generator set conductors enter a
facility.
NOTICE
The AC supply must have the correct over current and earth fault protection according to local
electrical codes and regulations. This equipment must be earthed (grounded).
It is the sole responsibility of the customer to provide AC power conductors for connection to load devices
and the means to isolate the AC input to the terminal box; these must comply with local electrical codes
and regulations. Refer to the wiring diagram supplied with the generator set.
The disconnecting device is not provided as part of the generator set, and Cummins Power Generation
accepts no responsibility for providing the means of isolation.
1.4.2Medium Voltage Equipment (601 V to 15 kV - North
America)
• Medium voltage acts differently than low voltage. Special equipment and training is required to work
on or around medium voltage equipment. Operation and maintenance must be done only by persons
trained and experienced to work on such devices. Improper use or procedures will result in severe
personal injury or death.
• Do not work on energized equipment. Unauthorized personnel must not be permitted near energized
equipment. Due to the nature of medium voltage electrical equipment, induced voltage remains even
after the equipment is disconnected from the power source. Plan the time for maintenance with
authorized personnel so that the equipment can be de-energized and safely grounded.
Fire, explosion, and personal injury or death can result from improper practices.
• Do not fill fuel tanks while the engine is running unless the tanks are outside the engine
compartment. Fuel contact with hot engine or exhaust is a potential fire hazard.
• Do not permit any flame, cigarette, pilot light, spark, arcing equipment, or other ignition source near
the generator set or fuel tank.
• Fuel lines must be adequately secured and free of leaks. Fuel connection at the engine should be
made with an approved flexible line. Do not use copper piping on flexible lines as copper will
become brittle if continuously vibrated or repeatedly bent.
• Make sure all fuel supplies have a positive shutoff valve.
• Make sure the battery area has been well-ventilated prior to servicing near it. Lead-acid batteries
emit a highly explosive hydrogen gas that can be ignited by arcing, sparking, smoking, etc.
1.5.1Gaseous Fuels
Natural gas is lighter than air, and will tend to gather under covered areas. Propane is heavier than air,
and will tend to gather in sumps or low areas. NFPA code requires all persons handling propane to be
trained and qualified.
1. Important Safety Instructions7-2016
1.5.2Spillage
Any spillage that occurs during fueling or during oil top-off or oil change must be cleaned up before
starting the generator set.
1.5.3Fluid Containment
NOTICE
Where spillage containment is not part of a Cummins supply, it is the responsibility of the
installer to provide the necessary containment to prevent contamination of the environment,
especially water courses and sources.
If fluid containment is incorporated into the bedframe, it must be inspected at regular intervals. Any liquid
present should be drained out and disposed of in line with local health and safety regulations. Failure to
perform this action may result in spillage of liquids which could contaminate the surrounding area.
Any other fluid containment area must also be checked and emptied, as described above.
1.5.4Do Not Operate in Flammable and Explosive Environments
Flammable vapor can cause an engine to over speed and become difficult to stop, resulting in possible
fire, explosion, severe personal injury, and death. Do not operate a generator set where a flammable
vapor environment can be created, unless the generator set is equipped with an automatic safety device
to block the air intake and stop the engine. The owners and operators of the generator set are solely
responsible for operating the generator set safely. Contact your authorized Cummins Power Generation
distributor for more information.
• Provide an adequate exhaust system to properly expel discharged gases away from enclosed or
sheltered areas, and areas where individuals are likely to congregate. Visually and audibly inspect
the exhaust system daily for leaks per the maintenance schedule. Make sure that exhaust manifolds
are secured and not warped. Do not use exhaust gases to heat a compartment.
• Make sure the unit is well ventilated.
1.6.1Exhaust Precautions
WARNING
Hot Exhaust Gases
Contact with hot exhaust gases can cause severe burns.
Wear personal protective equipment when working on equipment.
WARNING
Hot Surfaces
Contact with hot surfaces can cause severe burns.
Wear appropriate PPE when working on hot equipment and avoid contact with hot surfaces.
WARNING
Toxic Gases
Inhalation of exhaust gases can cause asphyxiation and death.
Pipe exhaust gas outside and away from windows, doors, or other inlets to buildings. Do not
allow exhaust gas to accumulate in habitable areas.
WARNING
Fire Hazard
Contaminated insulation is a fire hazard. Fire can cause severe burns or death.
Remove any contaminated insulation and dispose of it in accordance with local regulations.
The exhaust outlet may be sited at the top or bottom of the generator set. Make sure that the exhaust
outlet is not obstructed. Personnel using this equipment must be made aware of the exhaust position.
Position the exhaust away from flammable materials - in the case of exhaust outlets at the bottom, make
sure that vegetation is removed from the vicinity of the exhaust.
The exhaust pipes may have some insulating covers fitted. If these covers become contaminated they
must be replaced before the generator set is run.
To minimize the risk of fire, make sure the following steps are observed:
• Make sure that the engine is allowed to cool thoroughly before performing maintenance or operation
tasks.
The neutral of the generator set may be required to be bonded to earth ground at the generator set
location, or at a remote location, depending on system design requirements. Consult the engineering
drawings for the facility or a qualified electrical design engineer for proper installation.
NOTICE
The end user is responsible to make sure that the ground connection point surface area is clean
and free of rust before making a connection.
NOTICE
The end user is responsible for making sure that an earthing arrangement that is compliant with
local conditions is established and tested before the equipment is used.
1.8Decommissioning and Disassembly
NOTICE
1. Important Safety Instructions7-2016
Decommissioning and disassembly of the generator set at the end of its working life must
comply with local guidelines and legislation for disposal/recycling of components and
contaminated fluids. This procedure must only be carried out by suitably trained and
experienced service personnel. For more information contact your authorized distributor.
Hazardous Voltage
Contact with high voltages can cause severe electrical shock, burns, or death.
Make sure that only a trained and experienced electrician makes generator set electrical output
connections, in accordance with the installation instructions and all applicable codes.
Electrical Generating Equipment
Faulty electrical generating equipment can cause severe personal injury or death.
Generator sets must be installed, certified, and operated by trained and experienced person in
accordance with the installation instructions and all applicable codes.
2.1About This Manual
The purpose of this manual is to provide the users with sound, general information. It is for guidance and
assistance with recommendations for correct and safe procedures. Cummins Power Generation (CPG)
cannot accept any liability whatsoever for problems arising as a result of following recommendations in
this manual.
WARNING
WARNING
The information contained within the manual is based on information available at the time of going to print.
In line with Cummins Power Generation policy of continuous development and improvement, information
may change at any time without notice. The users should therefore make sure that before commencing
any work, they have the latest information available. The latest version of this manual is available on
QuickServe Online (https://quickserve.cummins.com).
Users are respectfully advised that, in the interests of good practice and safety, it is their responsibility to
employ competent persons to carry out any installation work. Consult your authorized distributor for further
installation information. It is essential that the utmost care is taken with the application, installation, and
operation of any engine due to their potentially hazardous nature. Careful reference should also be made
to other Cummins Power Generation literature. A generator set must be operated and maintained properly
for safe and reliable operation.
For further assistance, contact your authorized distributor.
2.1.1Additional Installation Manual Information
The purpose of this manual is to provide the Installation Engineer with sound, general information for the
installation of the generator set. Refer to the Generator Set Operator Manual for additional information
which must also be read before operating the set.
This manual provides installation instructions for the generator set models listed on the front cover. This
includes the following information:
• Mounting Recommendations - for fastening the generator set to a base and space requirements
for normal operation and service.
• Mechanical and Electrical Connections - covers most aspects of the generator set installation.
• Prestart - checklist of items or procedures needed to prepare the generator set for operation.
• Installation Checklist - reference checks upon completion of the installation.
This manual DOES NOT provide application information for selecting a generator set or designing the
complete installation. If it is necessary to design the various integrated systems (fuel, exhaust, cooling,
etc.), additional information is required. Review standard installation practices. For engineering data
specific to the generator set, refer to the Specification and Data Sheets. For application information, refer
to Application Manual T-030, "Liquid Cooled Generator Sets." To find this manual online:
1. Go to www.powersuite.cummins.com
2. Click on "Application & Technical Manuals" on the Home page.
3. Click on "Liquid Cooled Genset Application Manual"
2.2Schedule of Abbreviations
This list is not exhaustive. For example, it does not identify units of measure or acronyms that appear only
in parameters, event/fault names, or part/accessory names.
AmpSentry, INSITE, and InPower are trademarks of Cummins Inc. PowerCommand is a registered
trademark of Cummins Inc.
ABBR.DESCRIPTIONABBR.DESCRIPTION
ACAlternating CurrentLEDLight-emitting Diode
AMPAMP, Inc., part of Tyco ElectronicsLTSLong Term Storage
ANSIAmerican National Standards
Institute
ASOVAutomatic Shut Off ValveMFMMultifunction Monitor
ASTMAmerican Society for Testing and
Materials (ASTM International)
ATSAutomatic Transfer SwitchMLDMasterless Load Demand
AVRAutomatic Voltage RegulatorNCNormally Closed
AWGAmerican Wire GaugeNCNot Connected
CANControlled Area NetworkNFPANational Fire Protection Agency
CBCircuit BreakerNONormally Open
CEConformité EuropéenneNWFNetwork Failure
CFMCubic Feet per MinuteOEMOriginal Equipment Manufacturer
CGTCummins Generator TechnologiesOOROut of Range
CMMCubic Meters per MinuteOORH / ORHOut of Range High
LCDLiquid Crystal DisplayUPSUninterruptible Power Supply
2.3Related Literature
Before any attempt is made to operate the generator set, the operator should take time to read all of the
manuals supplied with the generator set, and to familiarize themselves with the warnings and operating
procedures.
A generator set must be operated and maintained properly if you are to expect safe and reliable
operation. The Operator manual includes a maintenance schedule and a troubleshooting guide
The relevant manuals appropriate to your generator set are also available:
• Operator Manual for GGHG/GGHH (A034G614)
SW_B+Switched B+
CAUTION
• Installation Manual for GGHG/GGHH (A034G612)
• Specification and Data Sheet (For engineering data specific to the generator set)
Contact your authorized distributor for more information regarding related literature for this product.
2.4After Sales Services
Cummins Power Generation offers a full range of maintenance and warranty services.
2.4.1Maintenance
WARNING
Electrical Generating Equipment
Incorrect operation and maintenance can result in severe personal injury or death
Make sure that only suitably trained and experienced service personnel perform electrical and/or
mechanical service.
For expert generator set service at regular intervals, contact your local distributor. Each local distributor
offers a complete maintenance contract package covering all items subject to routine maintenance,
including a detailed report on the condition of the generator set. In addition, this can be linked to a 24-hour
call-out arrangement, providing year-round assistance if necessary. Specialist engineers are available to
maintain optimum performance levels from generator sets. Maintenance tasks should only be undertaken
by trained and experienced technicians provided by your authorized distributor.
2.4.2Warranty
For details of the warranty coverage for your generator set, refer to the Global Warranty Statement listed
in the Related Literature section.
In the event of a breakdown, prompt assistance can normally be given by factory trained service
technicians with facilities to undertake all minor and many major repairs to equipment on site.
Extended warranty coverage is also available.
For further warranty details, contact your authorized service provider.
Damage caused by failure to follow the manufacturer's recommendations will not be covered by
the warranty. Please contact your authorized service provider.
2.4.2.1Warranty Limitations
NOTICE
For details of the warranty limitations for your generator set, refer to the warranty statement applicable to
the generator set.
FIGURE 2. TYPICAL FORD V-10 6.8L ENGINE GENERATOR SET
3.3Generator Set Rating
For details of the generator set rating, refer to the generator set nameplate. For operation at temperatures
or altitudes above those stated on the nameplate, a derate may be necessary.
Engine-mounted sensors monitor a number of different systems, such as:
• Lube Oil Pressure
• Cooling System Temperature
3.6System Options
The system options available with this installation include:
• Annunciator - see Section 9.11.1 on page 78.
• Battery Charger - see Section 3.6.2.
• Heaters:
◦ Alternator Heater - see Section 9.7.2 on page 74.
◦ Control Cabinet Heater - see Section 3.6.3.3 on page 18.
◦ Oil Pan Heaters - see Section 9.10.
3.6.1Annunciators
The annunciator's lamps and alarm indicate the operating status and fault conditions of an emergency
power system. For more information, see Section 9.11 on page 78.
3.6.2Battery Charger
Battery chargers can be wall, bench, or skid mounted. For more information, see Section 9.8 on page 74.
3.6.3Heaters
3.6.3.1Heater Supply and Isolation
An external power supply is required for the operation of the generator set heaters.
If not already provided, it is the sole responsibility of the customer to provide the power supply
and the means to isolate the AC input to the terminal box. Cummins Power Generation accepts
no responsibility for providing the means of isolation.
3.6.3.2Coolant Heater
Coolant heaters heat the coolant to maintain a minimum engine temperature when the generator set is not
running. For more information on coolant heater components and specifications, see Section 9.6 on page
72.
3.6.3.3Control Cabinet Heaters
A thermostat heater is installed inside the control cabinet. Both 120V and 240V heaters are available.
Seismically certified generator set installations have special requirements, as defined by IAA-VMC
(Independent Approval Agency, the VMC Group).
For special installation requirements, refer to the tabulated and written seismic requirements listed in
Section 4.5.1 and Appendix E on page 111. The installation of the seismically certified generator set
should be overseen by the installation project structural engineer of record.
The "Seismic Certificate of Compliance" should be kept with the Warranty and other generator set
documents.
The seismic requirements installation drawing and the Seismic Certificate of Compliance for generator
sets are included in the literature package of each seismically certified generator set.
These installation recommendations apply to typical installations with standard model generator sets.
Whenever possible, these recommendations also cover factory designed options or modifications.
However, because of the many variables in any installation, it is not possible to provide specific
recommendations for every situation. If there are any questions not answered by this manual, contact your
nearest authorized distributor for assistance.
4.1Application and Installation
A power system must be carefully planned and correctly installed for proper operation. This involves two
essential elements.
• Application (as it applies to generator set installations) refers to the design of the complete power
system that usually includes power distribution equipment, transfer switches, ventilation equipment,
mounting pads, cooling, exhaust, and fuel systems. Each component must be correctly designed so
the complete system will function as intended. Application and design is an engineering function
generally done by specifying engineers or other trained specialists. Specifying engineers or other
trained specialists are responsible for the design of the complete power system and for selecting the
materials and products required.
• Installation refers to the actual set-up and assembly of the power system. The installers set up and
connect the various components of the system as specified in the system design plan. The
complexity of the system normally requires the special skills of qualified electricians, plumbers,
sheet-metal workers, etc. to complete the various segments of the installation. This is necessary so
that all components are assembled using standard methods and practices.
4.2Safety Considerations
The generator set has been carefully designed to provide safe and efficient service when properly
installed, maintained, and operated. However, the overall safety and reliability of the complete system is
dependent on many factors outside the control of the generator set manufacturer. To avoid possible safety
hazards, make all mechanical and electrical connections to the generator set exactly as specified in this
manual. All systems external to the generator (fuel, exhaust, electrical, etc.) must comply with all
applicable codes. Make certain all required inspections and tests have been completed and all code
requirements have been satisfied before certifying the installation is complete and ready for service.
4.3Standby Heating Devices
Cummins Power Generation requires installing standby generator sets (life safety systems) with engine
jacket water coolant heaters in order to ensure a 10 second start. Jacket water coolant heaters are also
recommended in prime and continuous applications where time and load acceptance is to be minimized.
The jacket water coolant heater provided by Cummins Power Generation is rated to provide the above
requirements in ambient temperatures as low as 4 °C (40 °F). Although most Cummins Power Generation
generator sets will start in temperatures down to –32 °C (–25 °F) when equipped with engine jacket water
coolant heaters, it might take more than 10 seconds to warm the engine before a load can be applied
when ambient temperatures are below 4 °C (40 °F).
On generator sets equipped with a graphicdisplay, the Low Coolant Temperature message, in
conjunction with illumination of the Warning LED, is provided to meet the current requirements. The
engine cold sensing logic initiates a warning when the engine jacket water coolant temperature falls below
21 °C (70 °F). In applications where the ambient temperature falls below 4 °C (40 °F), or there exists a
high amount of cold airflow, the jacket water coolant heater may not provide the necessary heating. Under
these conditions, although the generator set may start, it may not be able to accept load within 10
seconds. When this condition occurs, check the coolant heaters for proper operation. If the coolant
heaters are operating properly, other precautions may be necessary to warm the engine before applying a
load.
4.4Product Modifications
Agency certified products purchased from Cummins Power Generation comply only with those specific
requirements and as noted on company product specification sheets. Subsequent modifications must
meet commonly accepted engineering practices and/or local and national codes and standards. Product
modifications must be submitted to the local authority having jurisdiction for approval.
4.5Seismic Installations
Seismically certified generator set installations have special requirements, as defined by IAA-VMC
(Independent Approval Agency, the VMC Group).
For special installation requirements, refer to the tabulated and written seismic requirements listed in
Appendix E on page 111.
The installation of the seismically certified generator set should be overseen by the installation project
structural engineer of record.
The "Seismic Certificate of Compliance" should be kept with the Warranty and other generator set
documents.
The seismic requirements installation drawing and the Seismic Certificate of Compliance for generator
sets are included in the literature package of each seismically certified generator set.
4.5.1Seismic Installation Notes
1. The design of post-installed anchors in concrete used for the component anchorage is pre-qualified
for seismic applications in accordance with "ACI 355.2" and documented in a report by a reputable
testing agency. (ex. the evaluation service report issued by the International Code Council)
2. Anchors must be installed to an embedment depth as recommended in the pre-qualification test
report as defined in Note 1. For "IBC 2000" and "IBC 2003" applications, the minimum embedment
must be 8X for the anchor diameter.
3. Anchors must be installed in minimum 4000 PSI compressive strength normal weight concrete.
Concrete aggregate must comply with "ASTM C33". Installation in structural lightweight concrete is
not permitted unless otherwise approved by the structural engineer of record.
4. Anchors must be installed to the torque specification as recommended by the anchor manufacturer
to obtain maximum loading.
5. Anchors must be installed in locations specified in this section.
6. Wide washers must be installed at each anchor location between the anchor head and equipment for
tension load distribution. Wide washers must be Series "W" of American National Standard Type "A"
plain washers (ANSI B18.22.1-1965, R1975) with the nominal washer size selected to match the
specified nominal anchor diameter.
7. Concrete floor slab and concrete housekeeping pads must be designed and rebar reinforced for
seismic applications in accordance with "ACI 318". The design loads shall be taken as those
specified in this section.
8. All housekeeping pad thicknesses must be designed in accordance with the pre-qualification test
report as defined in Note 1 or a minimum of 1.5X the anchor embedment depth, whichever is largest.
9. All housekeeping pads must be dowelled or cast into the building structural floor slab and designed
for seismic application per "ACI 318" and as approved by the structural engineer of record.
10. Wall mounted equipment must be installed to a rebar reinforced structural concrete wall that is
seismically designed and approved by the engineer of record to resist the added seismic loads from
components being anchored to the wall.
11. Floor mounted equipment (with or without a housekeeping pad) must be installed to a rebar
reinforced structural concrete floor that is seismically designed and approved by the engineer of
record to resist the added seismic loads from components being anchored to the floor.
12. When installing to a floor or wall, rebar interference must be considered.
13. Attaching seismic certified equipment to any floor or wall other than those constructed of structural
concrete and designed to accept the seismic loads from said equipment is not permitted by this
specification and beyond the scope of this certification.
14. Attaching seismic certified equipment to any floor constructed of light weight concrete over steel
decking is not permitted by this specification and beyond the scope of this certification.
15. Attaching the seismic certified equipment to any concrete block walls or cinder block walls is not
permitted by this specification and beyond the scope of this certification.
16. Installation upon a rooftop steel dunnage shall be coordinated with the structural engineer of record.
17. Installation upon any rooftop curb shall be coordinated with the curb manufacturer and the structural
engineer of record. Any curb or concrete pad that supports the generator set unit is beyond the
scope of this certification.
18. Connections to the equipment, including but not limited to conduit, wiring from cable trays, other
electrical services, ducting, piping such as exhaust, steam, water, coolant, refrigerant, fuel, or other
connections, are the responsibility of the installing contractor and beyond the scope of this
document. Typical requirements for these connections are stated in the equipment installation
manual. Special considerations for seismic applications are as follows; connections to non-isolated
components or equipment may be installed as typical for that particular application. Connections to
isolated components (ex. breaker box bolted directly to an isolated generator set) or isolated
equipment (ex. an enclosed generator set mounted on external isolators) must be flexibly attached.
The flexible attachment must provide for enough relative displacement to remain connected to the
equipment and functional during and after a seismic event.
Generator set installations must be engineered so that the generator set will function properly under the
expected load conditions. Use these instructions as a general guide only. Follow the instructions of the
consulting engineer when locating or installing any components. The complete installation must comply
with all local and state building codes, fire regulations, and other applicable regulations.
Requirements to be considered prior to installation are:
• Level mounting surface
• Adequate cooling air
• Adequate fresh induction air
• Discharge of generator set air
• Non-combustible mounting surface
• Discharge of exhaust gases
• Electrical connections
• Accessibility for operation and servicing
• Noise levels
• Vibration isolation
NOTICE
Depending on the location and intended use, ensure that international, national or local laws and
regulations regarding Air Quality Emissions have been observed and complied with. Be sure to
consult local pollution control or air quality authorities before completing construction plans.
6.1Location
Electrical Generating Equipment
Incorrect operation and maintenance can result in severe personal injury or death
Make sure that only suitably trained and experienced service personnel perform electrical and/or
mechanical service.
Incorrect installation
Incorrect installation of the generator set, service or parts replacement, can result in severe
personal injury, death, and/or equipment damage.
Service personnel must be trained and experienced to perform electrical and mechanical
Depending on your location and intended use, additional laws and regulations may require for
you to obtain an air quality emissions permit before beginning installation of your generator set.
Be sure to consult local pollution control or air quality authorities before completing your
construction plans.
Generator set location is decided mainly by related systems such as ventilation, wiring, fuel, and exhaust.
The set should be located as near as possible to the main power service entrance. Exhaust gases must
not be able to enter or accumulate around inhabited areas.
Provide a location away from extreme ambient temperatures and protect the generator set from adverse
weather conditions.
Use the following information to locate the generator set for optimal operating conditions:
Surface: Concrete or compacted gravel with the generator set resting on solid, poured concrete blocks, or
timber blocks spaced at reasonable intervals around the perimeter of the generator set.
Leveling: Level the generator set from side-to-side within + 3.5°, and end-to-end within +2.5°.
Placement:
• Generator sets should be a minimum of 5 m (16.4 ft) apart to allow for adequate access.
• Make sure that the air inlets are not obstructed by surrounding trees, buildings, or other obstructions.
• Make sure noise distribution (to prevent echoing) is kept to a minimum.
• Consider exhaust for immediate neighbors.
• The prevailing wind direction should be considered so that the engine combustion air inlet is upwind
and the exhaust discharge is downwind.
• The immediate area around the proposed location of the mounting surface should be evaluated for
proper drainage so that moisture run-off is sufficient to prevent ponding around the unit(s).
6.2Mounting
Generator sets are mounted on a steel skid that provides proper support. The engine-generator assembly
is isolated from the skid frame by rubber mounts that provide adequate vibration isolation for normal
installations. Where required by building codes or special isolation needs, generator sets may be mounted
on rubber pads or mechanical spring isolators.
The use of unapproved isolators may result in harmful resonances and may void the generator
set warranty.
Mount the generator set on a substantial and level base such as a concrete pad. A non-combustible
material must be used for the pad.
Use 16 mm (5/8inch) or anchored mounting bolts to secure the generator set bedframe to the base. Use a
flat washer and hexagonal nut for each bolt (see Figure 7). The 38 mm x 152 mm (11/2x 6 inch) pipe
inserted over the mounting bolts allows minor adjustment of the bolts to align them to the holes in the
bedframe.
NOTICE
The fixing centers for the mounting bolts can be found on the generator set Outline Drawing.
1Generator Bedframe Flange538 mm x 152 mm Pipe (1½ inch x 6 inch)
2Hexagonal Nut6Mounting Bolt Set in Concrete
3Flat or Bevel Washer7305 mm (12 inch)
4Mounting Base on Concrete
FIGURE 7. BOLT DIAGRAM
6.3Access to Set
Generally, at least 1 meter (3.3 feet) of clearance should be provided on all sides of the generator set for
maintenance and service access. (Increase clearance by width of door if optional housing is used.) A
raised foundation or slab of 152 mm (6 inches) or more above floor level will make servicing easier.
Lighting should be adequate for operation, maintenance and service operations and should be connected
on the load side of the transfer switch so that it is available at all times.
6.4Vibration Isolator Installation and Adjustment
Procedure
1. Place the vibration isolators (see Figure 8) on the generator set support structure. The isolators
should be shimmed or grouted to make sure that all of the isolator bases are within 0.25 inch (6 mm)
elevation of each other. The surface that the isolator bases rest on must also be flat and level.
2. Loosen the side snubber lock nuts so that the top plate of the isolator is free to move vertically and
horizontally. Be sure that the top plate is correctly aligned with the base and springs.
3. Place the generator set onto the isolators while aligning the skid's mounting with the threaded
isolator hole. The top plates will move down and approach the base of the isolator as load is applied.
4. Once the generator set is in position, the isolators may require adjusting so that the set is level. The
isolators are adjusted by inserting the leveling bolt through the skid and into the isolator (the leveling
bolt's locking nut should be threaded up towards the bolt head).
The leveling bolt will adjust the clearance between the top plate and the isolator base. A nominal
clearance of 0.25 inch (6 mm) or greater is desired. This will provide sufficient clearance for the
rocking that occurs during startup and shutdown. If the 0.25 inch (6 mm) clearance is not present,
turn the leveling bolt until the desired clearance is achieved.
5. If the radiator and engine are mounted on separate skids, make sure the radiator skid and
engine/alternator skid are level with each other after adjusting the isolators. If not level, proper fan
belt alignment cannot be achieved.
6. If the generator set is not yet level, adjust the leveling bolts until the set is level and sufficient
clearance still remains. (Clearance on all isolators should be roughly equal).
7. Once all isolators have been set, lock the leveling bolt in place with the lock nut.
8. The snubber nuts must remain loose to provide better isolation between the generator set and the
support structure.
Heavy Load
Incorrect lifting or repositioning can cause severe personal injury or death.
Do not lift the generator set by attaching to the engine or alternator lifting points. Do not stand
under or near the generator set when lifting.
Heavy Load
Incorrect lifting or repositioning can cause severe personal injury or death.
Make sure that only suitably trained and experienced personnel transport and handle generator
sets and associated components.
1. Consult the generator set outline drawing for weight and center-of-gravity information.
2. Attach cables from the lifting lugs to a spreader bar. Never make the spreader bar cable attachment
points wider than the attachment points on the skid or the bars. Make sure cables do not touch any
other part of the generator set other than the skid.
6. Installing the Generator Set7-2016
WARNING
WARNING
NOTICE
Spreader bar cable attach points width "Y" must never be wider than skid cable attach
points "X." Distance "X" is the narrowest width.
NOTICE
Angle B must be slightly greater than angle A. Angle B should be as close to 90 degrees as
possible to provide a stable lift.
3. With pedestal box (not shown), the spreader bars (front and back) should be used to clear the
pedestal box and the attachment cables must be as vertical as possible.
NOTICE
The lifting angle (angle C) must not exceed 20° from vertical.
XThe Narrowest Width (On the Skid)4Center of Gravity
YThis Distance Must be Less than Distance "X"
FIGURE 9. RIGGING
6.6Moving the Generator Set
WARNING
Heavy Load
Incorrect lifting or repositioning can cause severe personal injury or death.
Make sure that only suitably trained and experienced personnel transport and handle generator
sets and associated components.
WARNING
Heavy Load
Incorrect lifting or repositioning can cause severe personal injury or death.
Do not lift the generator set by attaching to the engine or alternator lifting points. Do not stand
Mechanical Hazard
Failed components may be ejected or operate incorrectly which can cause severe personal injury
or death.
Do not climb the generator set; this may damage critical parts.
NOTICE
Make sure that any shipping brackets supplied with the generator set are fitted, before moving
the generator set. Failure to install the shipping brackets before moving may result in damage to
the generator set.
NOTICE
Access or service doors must be closed and locked before repositioning, and they must remain
locked during transportation and siting.
It is essential that there are sufficient trained and experienced personnel in attendance to make sure the
lifting and transportation of the generator set is undertaken in a safe and appropriate manner, and in
accordance to local guidelines and legislation.
Before lifting the generator set, lifting points, angle of slings, mass, access to intended site, and the
distance of movement should all be taken into account when organizing a suitable crane/hoist. Consult the
generator set information supplied with the generator set for details of dimensions and mass.
• Make sure that the crane operating area is able to support the mass of the crane and the generator
set.
• Make sure the equipment used for lifting is adequate to support the weight of the generator set.
• Attach the lifting device to the lifting points only using suitable shackles, chains, and spreader bars.
• Slowly tighten the slings. Inspect the lifting attachments before commencing a full lift to make sure
they are attached correctly.
• Hoist the generator set slowly using the indicated lifting points only.
• Guide the generator set with ropes at a safe distance to prevent uncontrolled rotation when
positioning the generator set.
• Move the generator set to the desired location and place in position, bringing the set down slowly.
• Loosen the slings; unhook and remove the shackles.
6.6.1Positioning a Generator Set Using a Forklift Truck
WARNING
Heavy Load
Incorrect lifting or repositioning can cause severe personal injury or death.
Make sure that only suitably trained and experienced personnel transport and handle generator
sets and associated components.
WARNING
Heavy Load
Incorrect lifting or repositioning can cause severe personal injury or death.
Do not attempt to lift a generator set with an undersized forklift truck.
Access or service doors must be closed and locked before repositioning, and they must remain
locked during transportation and siting.
When using a forklift truck to transport/position the generator set, the dimensions, mass, and route must
be taken into account when selecting an appropriate lifting truck.
It is essential that there are sufficient trained and experienced personnel in attendance to make sure the
lifting and transportation of the generator set is undertaken in a safe and appropriate manner.
1. Insert the arms of the forklift into the forklift pockets. Make sure the generator set completely rests on
the forklift arms.
2. Lift and handle the equipment slowly.
3. Lower the generator set in position.
6.7Transportation
WARNING
Heavy Load
Incorrect lifting or repositioning can cause severe personal injury or death.
Make sure that only suitably trained and experienced personnel transport and handle generator
sets and associated components.
WARNING
Heavy Load
Incorrect lifting or repositioning can cause severe personal injury or death.
Do not lift the generator set by attaching to the engine or alternator lifting points. Do not stand
under or near the generator set when lifting.
NOTICE
Any panels or doors must be locked before re-positioning and must remain locked during
transportation and siting.
• Ensure the generator set is prepared for transport. If necessary drain fluids and ensure that acid or
fumes do not leak from the battery (where applicable).
• If the generator set is transported over long distances, protect it against environmental influences by
sealing it in a plastic cover or similar.
• Ensure the generator set is secured to the vehicle with suitable securing straps. Wooden chocks and
pallets alongside the securing straps can prevent movement during transportation.
• If required, attached impact indicators to the generator set. Upon delivery, check these impact
indicators and contact the transport company immediately if an impact has been detected. Impacts
can cause serious damage to the generator set and its components.
• Ensure that the generator set cannot turn over during transportation.
• Do not overload the transport vehicle. Under no circumstances should the generator set be started
while inside a truck.
• Lifting eyes, where fitted, are to be checked at regular intervals to ensure they are damage free and
tight.
The generator set mechanical system installation includes connecting the fuel, exhaust, ventilation, and
cooling systems. Before starting any type of fuel installation, all pertinent state and local codes must be
complied with and the installation must be inspected before the unit is put in service.
7.1Fuel System
In all fuel system installations, cleanliness is of the utmost importance. Make every effort to prevent
entrance of moisture, dirt, or contaminants of any kind into the fuel system. Clean all fuel system
components before installing. Use only compatible metal fuel lines to avoid electrolysis when fuel lines
must be buried. Buried fuel lines must be protected from corrosion.
7.1.1Gaseous Fuel Supply
Gaseous fueled generator sets (also called "spark-ignited generator sets") may utilize natural gas or Liquid
Petroleum gas (Propane), or both. Dual fuel systems with natural gas as primary fuel and propane as a
backup can be used in seismic risk areas and where there is concern that a natural event could disrupt a
public utility gas system.
Regardless of the fuel used, the primary factors in successful installation and operations of a gas fuel
system are:
• The gas supplied to the generator set must be of acceptable quality. Refer to the Application Manual
T-030, Liquid Cooled Generator Sets for more detailed information about Cummins approved fuel
types and quality.
• The gas supply must have sufficient pressure (defined for each generator set on the respective datasheets). Care must be taken to be sure that the gas supply at the generator set, not just at the
source, is of proper pressure for operation. The specified pressure must be available while the
generator set is running at full load.
• The gas must be supplied to the generator set in sufficient volume to support operation of the
generator set. This is normally a matter of selecting fuel line size to be large enough to transport the
volume of fuel needed. For LP vapor-withdrawal fuel systems the size and temperature of the fuel
tank also affects this requirement.
Failure to meet the minimum requirements of the generator set in these areas will result in the inability of
the generator set to operate, or inability to carry rated load, or poor transient performance. Insufficient flow
can also result in engine damage or catastrophic failure.
7.1.2Gaseous Fuel Quality
Gaseous fuels are actually a mixture of several different hydrocarbon gases such as methane, ethane,
propane and butane; other gaseous elements such as oxygen and nitrogen; vaporized water; and various
contaminants, some of which are potentially damaging to an engine over time. The quality of the fuel is
based on the amount of energy per unit volume in the fuel and the amount of contaminants in the fuel.
One of the most important characteristics of the gaseous fuel used in a generator set is the heat value of
the fuel. The heat value of a fuel describes how much energy is stored in specific volume of the fuel.
Gaseous fuel has a low heat value (LHV) and a high heat value (HHV). The low heat value is the heat
available to do work in an engine after the water in the fuel is vaporized. If the low heat value of a fuel is
too low, even if a sufficient volume of fuel reaches the engine, the engine will not be able to maintain full
output power, because sufficient energy is not available in the engine to convert to mechanical energy. If
the LHV is below 905 BTU/ft3the engine may not produce rated power at standard ambient temperature
conditions.
If the local fuel has a higher energy content than 1000 BTU/ft3, the actual flow requirements in ft3/min will
be lower and the pressure requirements drop slightly. Conversely, if the local fuel has a lower energy
content than 1000 BTU/ft3, the actual flow requirements in ft3/min will be higher and a higher minimum
supply pressure will be needed to meet published performance for any given generator set.
Each engine may have slightly different performance characteristics based on the type of fuel provided,
due to differences in engine compression ratio, and whether the engine is naturally aspirated or
turbocharged.
7.1.2.2Pipeline Natural Gas
The most common fuel for generator sets is called Pipeline Natural Gas. In the US, Dry Pipeline Natural
Gas has specific qualities, based on federal requirements. In other countries, Pipeline Gas may vary in
content, so fuel characteristics should be verified prior to use with a generator set. US Pipeline Gas in a
mixture composed of approximately 98% Methane and Ethane with the other 2% being hydrocarbons such
as Propane and Butane, Nitrogen, Carbon Dioxide and water vapor. "Dry" means that it is free of liquid
hydrocarbons, such as gasoline, but NOT that it is free of water vapor. Dry Pipeline Gas typically has a
LHV of 936 BTU/ft3, and a HHV of 1,038 BTU/ft3.
7.1.2.3Field Gas
The composition of Field Natural Gas varies considerably by region and by continent. Careful analysis is
necessary prior to using Field Natural Gas in an engine. Field Natural Gas can contain heavier
hydrocarbon gases such as Pentane, Hexane and Heptane, which may require derating of the output of
the engine. Other contaminants, such as Sulfur, may also be present in the fuel. A typical Field Gas might
have an LHV of 1203 BTU/ft3, and an HHV of 1,325 BTU/ft3.
7.1.2.4Propane/Liquid Petroleum Gas (LPG)
Propane is available in two grades, either commercial or special duty. Commercial Propane is used where
high volatility is required. Not all spark-ignition engines will operate acceptably with this fuel due to its
volatility. Special duty Propane (also called HD5) is a mixture of 95% Propane and other gases, such as
Butane, that allow better engine performance due to the reduction pre-ignition due to reduced volatility.
Special duty Propane fuel gas that meets the ASTM D 1835 specification for special-duty Propane
(equivalent to HD-5 Propane of Gas Producers Association Standard 2140) is suitable for most engines.
Propane has an LHV of approximately 2,353 BTU/ft3, and an HHV of 2,557 BTU/ft3. The higher heating
value of the fuel necessitates mixing of different volumes of air in the fuel system for Propane vs. Natural
Gas applications, so dual fuel engines essentially have two fuel arrangements for this purpose.
NOTICE
Clarification of abbreviations often seen:
LP - Liquid Petroleum or Propane
LPV - Propane Vapor (gaseous fuel)
LPL - Propane Liquid (liquid fuel)
LPG - Liquid Petroleum Gas
**LPG and LP are the same and are often used interchangeably.**
The most harmful contaminants in gaseous fuels are water vapor and Sulfur.
Water vapor is damaging to an engine because it may cause uncontrolled burning, pre-ignition, or other
effects that can damage an engine. Liquid vapor or droplets must be removed from the fuel prior to entry
into the engine by use of a dry filter that is mounted in the fuel system prior to the primary fuel pressure
regulator. The dew point of fuel gas should be at least 20 °F (11 °C) below the minimum ambient
temperature at the installation site.
Sulfur and Hydrogen sulfides will cause corrosion and serious damage to an engine over a relative short
period of time. Different engines have different levels of tolerance to sulfur contamination, and some
engines simply should not be operated with fuel that contains significant Sulfur content. Contact the
engine manufacturer for approval of specific engines with specific fuels. The effects of Sulfur in the fuel
can be counteracted in part by use of high-ash Natural Gas lubricating oils. In general, engines should not
be operated with fuels in excess of 10 parts per million (ppm).
Certain fuels, such as those derived from land fill applicants, can have useful chemical energy content, but
very high sulfur levels (>24 ppm). These fuels are often termed "sour gas". If this fuel is scrubbed of the
Sulfur content, it can be used as fuel for many engines, provided that it has sufficient BTU content.
7.1.2.6Fuel Analysis
The gaseous fuel supplier can provide a fuel analysis that describes the chemical makeup of the fuel to be
provided. This fuel analysis can be used to make certain that the fuel is suitable for use in the specific
engine proposed for a specific application, and also to verify that the BTU content of the fuel is sufficient to
provide necessary kW output of the machine. Gas suppliers may change the Pipeline Natural Gas
composition without notice, so there is no long-term guarantee of performance, but the process of
evaluation of the fuel can be briefly described as:
7. Mechanical Connections7-2016
1. List the percent of each gas constituent in the fuel.
2. Calculate the percent of the total fuel that is combustible. The combustible portion of the fuel is 100%
less the inert component percentages. Inert components include Oxygen, Carbon Dioxide and water
vapor.
3. Calculate the percent of each combustible component of the fuel.
4. Verify acceptability of the fuel by checking the percent of each combustible element vs. the
recommendations of the engine manufacturer.
See the following tables for a typical listing of Maximum Permissible Combustibles in Cummins Gas
generator sets. Note that in this example, the analysis shows the fuel will be acceptable for a lower
compression ratio engine (typically around 8.5:1) but not for a higher compression engine. A higher
compression engine will have more stringent fuel composition requirements but may operate
satisfactorily with a derating of its output - consult the engine manufacturer.
5. Verify the rating of the generator set based on the use of the proposed fuel.
The total BTU content of the fuel will determine the rating of the generator set when using fuel of a
specific composition. If any component of the fuel has more than the specific value allowed derating will
be required. Consult the engine manufacturer for fuel requirements and derating instructions.
Note that the fuel derating and the altitude/temperature derating 21 are not additive. Only the maximum
value of the fuel derate or the altitude/temperature derate need be applied.
Turbocharged engines have unique fuel composition requirements due to higher cylinder pressures. To
avoid problems with pre-ignition or denotation, power output derating is required if propane and/or ISOButane content exceed the percentages listed in the following tables.
TABLE 4. MAXIMUM ALLOWABLE PERCENTAGES FOR ENGINE FUEL COMBUSTIBLES
8.5:1 Compression Ratio10.5:1 Compression Ratio
Methane (C1)100100
Ethane (C2)100100
Propane (C3)102
ISO-Butane (IC4)70.2
Hydrogen (H2)7trace
Normal Butane (NC4)30.2
ISO-Pentane (IC5)30.2
Normal Pentane (NC5)10.1
Hexane (C6)10.1
Heptane (C7)10.1
TABLE 5. MAXIMUM ALLOWABLE PERCENTAGES OF CONSTITUENT GASES BEFORE DERATING
TURBOCHARGED ENGINES
8.5:1 Compression Ratio10.5:1 Compression Ratio
MethaneN/AN/A
EthaneN/AN/A
Propane5%*
ISO-Butane2%*
*High compression ratio turbocharged engines cannot consume any Propane or ISO-Butane.
The following should be considered when installing a natural gas and/or LPG fuel system:
• Gaseous-fuel supply system design, materials, components, fabrication, assembly, installation,
testing, inspection, operation, and maintenance must comply with all applicable codes (In North
America, NFPA Standards No.30, No.37, No.54 and No. 58 are typical).
• The layout and sizing of gas piping must be adequate for handling the volume of gas required by the
generator set and all other equipment, such as building heating boilers, supplied by the same
source. Full-load gas flow (see the recommended generator set Data Sheet) must be available at not
less than the minimum required supply pressure, typically from 7 to 13.6 inches WC (water column),
depending on model. Final determination of pipe sizes must, however, be based upon the method
approved by the authority having jurisdiction (see NFPA No.54).
• Most installations will require a service gas pressure regulator. Gas supply pressure should not
exceed 14 inches WC, depending on model, at the inlet to the generator set. Refer to the generator
set data sheet for model specific details. Depending on distribution gas pressure, more than one
stage of pressure regulation may be required. High-pressure gas piping is not permitted inside
buildings (5 PSIG for natural gas and 20 PSIG for LPG, unless higher pressures are approved by
the authority having jurisdiction). Gas pressure regulators must be vented to the outdoors according
to code.
• The pressure regulator installed on the supply line at the gas source for generator applications
should never be a "pilot" regulator. A "pilot" style regulator is the type where the regulator requires a
pressure line from the regulator housing to the downstream gas pipe to "sense" when downstream
pressure has dropped. Pilot regulators do not work because the response time is unacceptable
compared to the large instantaneous changes in demand from the generator set.
7. Mechanical Connections7-2016
• Approved fuel hose must be used for connections at the engine to take up generator set movement
and vibration.
• Most codes require both manual and electric (battery-powered) shutoff valves ahead of the flexible
fuel hose(s). The manual valve should be of the indicating type.
• A dryer fuel filter should be installed in each line to protect the sensitive pressure regulating
components and orifices downstream from harmful foreign substances carried along in the gas
stream (rust, scale, etc.)
• An LPG fuel supply system must be dedicated for the emergency power system if it is the required
alternative fuel.
• An LPG vaporizer heated by engine coolant is factory installed on Cummins Power Generation
generator sets equipped for a liquid-withdrawal of LPG. Because high pressure (20 PSIG or greater)
gas piping is not permitted inside buildings, generator sets equipped for liquid withdrawal of LPG
must not be installed inside the building. (Weather-protective housings for outdoor installation are
available for most LPG models.)
• The rate of vaporization in an LPG tank depends upon the outdoor air temperature, unless the tank
is equipped with a heater, and the quality of fuel in the tank. Even on cold days outdoor air heats
and vaporizes LPG (mostly through the wetted tank surface) when air temperature is higher than
LPG temperature. Withdrawing vapor causes tank temperature and pressure to drop. (At -38 °C (-37
°F) LPG has zero vapor pressure.) Unless there is enough fuel and enough heat available from
ambient air, the vaporization rate will drop off, as the generator set runs, to less than that required to
continue running properly.
Refer to Application Manual T-030 Liquid Cooled Generator Sets or Cummins Sales Application
Engineering for more information on Site Fuel System Design.
Use the "Minimum LPG Tank Size (50% Full) Required to Maintain 5 PSIG at Specific Withdrawal Rate
and Minimum Expected Winter Temperature" figure as a quick reference for sizing an LPG tank on the
basis of the lowest ambient temperature expected. For example, on a 40 °F day, withdrawal at 1000 ft3/hr
requires a 2000 gallon tank at least half full. Note: In many instances the amount of total fuel required for
proper vaporization is far greater than that required for the number of hours of operation stipulated by
code.
For instance, in an NFPA 110 Class 6 application, there must be enough fuel for the generator set to run
for 6 hours before refilling the tank. LPG yields approximately 36.5 ft3of gas per gallon of liquid. If the
generator set withdrawal rate is 1000 ft3/h:
In this instance the tank must be sized for at least 2000 gallons based on the lowest expected
temperature rather than on the fuel consumed in 6 hours (164 gallons).
Gas Pipe Sizing
Sizing of gas piping for proper fuel delivery, both flow and pressure, can become quite complex. However,
a simplified method, as with other piping for exhaust and coolant, is to convert all fittings, valves, etc. to
equivalent lengths of pipe in the diameter(s) being considered. The total equivalent length can then be
related to flow capacity.
Notes about the following tables:
• Equivalent Lengths of Pipe Fittings and Valves applies to gas as well as liquid piping.
• Show maximum gas capacity for equivalent length for various pipe sizes.
• Show maximum gas capacity for equivalent length for various pipe sizes.
• Reproduced from NFPA 54-2002, National Fuel Gas Code, and are selected considering the general
fuel system operating requirements for generator sets.
• Included for natural gas, propane liquid withdrawal and propane vapor withdrawal under specified
conditions.
• Consult NFPA 54 or other applicable codes for other operating conditions or other fuel system
installation requirements.
A calculation of minimum pipe size is fairly straightforward:
• Make a list of all the fittings and valves in a proposed system and sum their equivalent lengths using
the table.
• Add to this total, all lengths of straight pipe to arrive at a total equivalent length.
• Choose the applicable table based on the fuel system.
• Obtain the maximum fuel requirements for the specific generator set(s) from the manufacturer's
specification sheets. Convert to ft3/hr as needed (Be cognizant of BTU content as discussed earlier
in this section.)
• Locate the equivalent length of pipe (or next larger equivalent length) in the left hand column. Move
across to the columns to where the number is as large or larger than the total equivalent length
calculated above. At the top of that column is the minimum nominal pipe size or tubing size required
for the system as designed.
Gas: Undiluted Propane
Inlet Pressure: 11.0 in. w.c.
Pressure Drop: 0.5 in. w.c.
Specific Gravity: 1.50
Special Use: Pipe sizing between single or second stage (low pressure regulator) and appliance.
Pipe Size (in.)
Nominal
Inside
Actual:0.6220.8241.0491.381.61
Length (ft.)Maximum Capacity in Thousands of BTU per Hour
TABLE 12. PROPANE VAPOR SCHEDULE 40 IRON PIPE SIZING (2-4IN.)
Gas: Undiluted Propane
Inlet Pressure: 11.0 in. w.c.
Pressure Drop: 0.5 in. w.c.
Specific Gravity: 1.50
Special Use: Pipe Sizing between single or second stage (low pressure regulator) and appliance.
Pipe Size (in.)
Nominal
Inside
Actual:2.0673.0683.5484.026
Length (ft.)Maximum Capacity in Thousands of BTU per Hour
*TABLE CAPACITIES ARE BASED ON TYPE K COPPER TUBING INSIDE DIAMETER (SHOWN), WHICH HAS
THE SMALLEST INSIDE DIAMETER OF THE COPPER TUBING PRODUCTS.
Gas: Undilute Propane
Inlet Pressure: 11.0 in. w.c.
Pressure Drop: 0.5 in. w.c.
Specific Gravity: 1.50
Special Use: Sizing between single or second stage (low pressure regulator) and appliance
*TABLE CAPACITIES ARE BASED ON TYPE K COPPER TUBING INSIDE DIAMETER (SHOWN), WHICH HAS
THE SMALLEST INSIDE DIAMETER OF THE COPPER TUBING PRODUCTS.
Gas: Undilute Propane
Inlet Pressure: 11.0 in. w.c.
Pressure Drop: 0.5 in. w.c.
Specific Gravity: 1.50
Special Use: Sizing between single or second stage (low pressure regulator) and appliance
Toxic Gases
Inhalation of exhaust gases can cause asphyxiation and death.
Use extreme care during installation to provide a tight exhaust system. Terminate exhaust pipes
away from enclosed or sheltered areas, windows, doors, and vents. Do not use exhaust heat to
warm a room, compartment, or storage area.
20
(6.1)
9
(2.7)
67
(20)
3
(0.9)
4
(1.2)
WARNING
24
(7.3)
17
(5.2)
78
(23.8)
3
(0.9)
4
(1.2)
26
(7.9)
19
(5.8)
89
(27.1)
3
(0.9)
4
(1.2)
31
(9.4)
22
(6.7)
110
(33.5)
3
(0.9)
4
(1.2)
WARNING
Hot Surface
Hot surfaces can start a fire which can cause severe burns or death.
Use an approved thimble where exhaust pipes pass through wall or partitions.
NOTICE
Weight applied to the engine manifold can result in turbocharger damage. Support the silencer
and exhaust piping so no weight or stress is applied to the engine exhaust elbow.
NOTICE
Gaseous fuels are susceptible to high condensation levels in the exhaust. It is important to have
properly routed/sized exhaust systems to prevent harm to turbochargers and Oxygen sensors
(HEGO).
NOTICE
Liability for injury, death, damage, and warranty expense due to use of unapproved silencers or
modifications to the exhaust system becomes the responsibility of the person installing the
unapproved silencer or performing the modification. Contact your authorized distributor for
approved exhaust system parts.
Pipe exhaust gases to the outside of any enclosure. Locate the exhaust outlets away from any air inlets to
avoid gases re-entering the enclosure. Exhaust installations are subject to various detrimental conditions
such as extreme heat, infrequent operation, and light loads. Regularly inspect the exhaust system both
visually and audibly to see that the entire system remains fume tight and safe for operation.
NOTICE
Enclosed generator sets are not generally designed to be used in a building. If the generator set
is to be used in a building, additional requirements must be applied.
Where an enclosed generator set is used in a building, the exhaust system should be extended to vent the
exhaust gases. Use sealed joint type fittings where possible to provide a tight exhaust system. Use of slip
type fittings (secured with a clamp) may allow leakage of exhaust gases into the building if not fitted
correctly. Check to make sure there are no exhaust leaks.
When a unit is provided with a partially installed or incomplete exhaust system, exhaust piping and
chimneys shall be designed, constructed, and installed in accordance with the Standard for the Installation
and Use of Stationary Combustion Engines and Gas Turbines, NFPA 37, or applicable local standards.
Build according to the code requirements in effect at the installation site.
For indoor installation, the exhaust system should use sealed joint type fittings where possible to provide a
tight exhaust system. Use of slip type fittings (secured with a clamp) may allow leakage of exhaust gases
into the building if not fitted correctly fitted. Check to make sure there are no exhaust leaks.
Use an approved thimble (see Figure 14 on page 57) where exhaust pipes pass through a wall or
partition. Insulated wall/roof thimbles are used where exhaust pipes pass through a combustible roof or
wall. This includes structures, such as wood framing or insulated steel decking, etc. Uninsulated wall/roof
thimbles are used where exhaust pipes pass through a non-combustible wall or roof, such as concrete.
When a unit is provided with a partially installed or incomplete exhaust system, exhaust piping and
chimneys shall be designed, constructed, and installed in accordance with the Standard for the Installation
and Use of Stationary Combustion Engines and Gas Turbines, NFPA 37, or applicable local standards.
Build according to the code requirements in effect at the installation site.
Rain caps are available for the discharge end of vertical exhaust pipes. The rain cap clamps onto the end
of the pipe and opens due to exhaust discharge force from the generator set. When the generator set is
stopped, the rain cap automatically closes, protecting the exhaust system from rain, snow, etc.
Use a section of flexible exhaust pipe between the engine and remainder of exhaust system. Support the
exhaust system to prevent weight from being applied to engine exhaust outlet elbow/turbocharger
connection.
The exhaust system design should meet local code requirements.
Avoid sharp bends by using sweeping, long radius elbows and provide adequate support for the silencer
and tailpipe. Pitch a horizontal run of exhaust pipe downward (away from engine) to allow any moisture
condensation to drain away from the engine. If an exhaust pipe must be turned upward, install a
condensation trap at the point where the rise begins (see Figure 15 on page 57).
Shield or insulate exhaust lines if there is danger of personal contact. Allow at least 305 mm (12 inches) of
clearance if the pipes pass close to a combustible wall or partition. Before installing insulation on exhaust
system components, check the exhaust system for leaks while operating the generator set under full load
and correct all leaks.
Refer to Application Manual T-030, Liquid Cooled Generator Sets for more detailed information about
sizes of exhaust system pipes and fittings.
Toxic Gases
Engine and radiator cooling air may carry carbon monoxide gas, which can cause asphyxiation
and death.
Pipe exhaust gas outside and away from windows, doors, or other inlets to buildings. Do not
allow exhaust gas to accumulate in habitable areas.
Generator sets create considerable heat that must be removed by proper ventilation.
Generator sets in factory-mounted housings for outdoor installation are designed for proper cooling and
ventilation.
Indoor installations require careful design with respect to cooling and ventilation. In an indoor installation,
all radiator cooling air must be discharged to the out-of-doors. Duct adapter kits are available.
Outdoor installations normally rely on natural air circulation but indoor installations need properly sized
and positioned vents for required airflow.
For indoor installations, locate vents so incoming air passes through the immediate area of the installation
before exhausting. Install the air outlet higher than the air inlet to allow for convection air movement.
Size the vents and ducts so they are large enough to allow the required flow rate of air.
The "free area" of ducts must be as large as the exposed area of the radiator. Refer to the
generator set Specification Sheet for the airflow requirements and allowed airflow restriction.
Wind will restrict free airflow if it blows directly into the air outlet vent. Locate the outlet vent so the effects
of wind are eliminated, or if outlet vent cannot be located as mentioned, install a wind barrier, see Figure
17.
7. Mechanical Connections7-2016
NOTICE
No.DescriptionNo.Description
1Prevailing Wind Away from Air Outlet Vent2Prevailing Wind Towards Air Outlet Vent, Wind
Barrier Installed
FIGURE 17. WIND BARRIER
7.5Dampers
Dampers or louvers protect the generator set and equipment room from the outside environment. Their
operation of opening and closing should be controlled by operation of the generator set.
In cold climates, the radiator exhaust air can be recirculated to modulate the ambient air temperature in
the generator set room. This will help the generator set warm up faster, and help to keep fuel
temperatures higher than the cloud point of the fuel. If recirculation dampers are used, they should be
designed to 'fail closed', with the main exhaust dampers open, so that the generator set can continue to
operate when required. Designers should be aware that the generator set room operating temperature will
be very close to the outdoor temperature, and either not route water piping through the generator set
room, or protect it from freezing.
7.6Air Inlet and Outlet Openings
Louvers and screens over air inlet and outlet openings restrict air flow and vary widely in performance.
A louver assembly with narrow vanes, for example, tends to be more restrictive than one with wide vanes.
The effective open area specified by the louver or screen manufacturer should be used.
Radiator set cooling air is drawn past the control end of the set by a pusher fan that blows air through the
radiator. Locate the air inlet to the rear of the set. Make the inlet vent opening 1.5 times larger than the
radiator area.
Locate the cooling air outlet directly in front of the radiator and as close as possible. The outlet opening
must be at least as large as the radiator area. Length and shape of the air outlet duct should offer
minimum restriction to airflow.
A flexible duct connector must be provided at the radiator to prevent exhaust air recirculation around the
radiator, to take up generator set movement and vibration, and to prevent transmission of noise. Attach
the flexible duct using screws and nuts so that the duct can be removed for maintenance purposes.
Before installing the duct, remove the radiator core guard.
Enclosed generator sets are primarily designed to work in an open environment. When considering
installing an enclosed generator set in an enclosed environment specific application factors must be
considered (air flow, exhaust gas extraction, fuel supply and storage, etc.). For advice, contact the
Application Engineering Group at Cummins Power Generation.
Electric Shock Hazard
Voltages and currents present an electrical shock hazard that can cause severe burns or death.
Avoid contact with the voltage sense and bus sense leads; voltages of up to 600 VAC may still
be present. These voltages could be live even when the generator set is switched off.
Electric Shock Hazard
Voltages and currents present an electrical shock hazard that can cause severe burns or death.
Make sure all power is off before performing control wire installation.
Electric Shock Hazard
Voltages and currents present an electrical shock hazard that can cause severe burns or death.
To prevent accidental electrocution, stand on a clean dry wooden platform or clean rubber
insulating mat, make sure your clothing and shoes are dry, remove all jewelry, and use tools with
insulated handles.
WARNING
WARNING
WARNING
The generator set control box contains connection points for remote control and monitor options.
NOTICE
Always run control circuit wiring in a separate metal conduit from the AC power cables to avoid
inducing currents that could cause problems within the control.
Use cable ties to keep control wiring away from sharp edges and AC power cables within the control
housing.
NOTICE
Stranded copper wire must be used for all customer connections to the control panel. Solid
copper wire may break due to the generator set vibration.
Use flexible conduit for all wiring connections to the generator set.
8.1Guidelines for Customer Connections to the Control
System
Connection points, other than relayed outputs and network are considered digital connections. The
type/gauge wire to use for these connections are:
• Less than 305 m (1000 ft), use 0.5 mm2(20 gauge) stranded copper wire.
• 305 m to 610 m (1000 ft to 2000 ft), use 0.75 mm2(18 gauge) stranded copper wire.
8.3Relay Connections
Due to the wide variety of devices that can be attached to the relay outputs, the electrical contractor must
determine the gauge of the stranded copper wire that is used.
Automated Machinery
Accidental or remote starting of the generator set can cause severe personal injury or death.
Make sure that the generator set can not be started accidentally or remotely before starting work
on the generator.
Remote start terminals should only be used for a remote application. Remote start terminals are
not to be shorted if the remote start function is not intended to be used.
When the control is in Auto/Remote mode, grounding this input initiates the engine cranking and start
sequence. This circuit must be opened to permit resetting a shutdown condition with the Reset input. (The
remote stop is actually the removal of the remote start signal to the control.)
8.4.2Remote Emergency Stop
Opening this input causes an immediate shutdown. Emergency stop must be reset at the remote panel,
then at the front panel.
8. DC Control Wiring7-2016
WARNING
NOTICE
8.4.3Remote Fault Reset
Ground this input to acknowledge faults after they have been corrected. The control must be in Auto
mode.
Faults are re-announced if they are detected again after being acknowledged.
Using the InPower service tool or accessing the Setup submenus is required to modify the
customer outputs. Contact an authorized distributor for assistance.
8.4.4Configurable Inputs
Grounding any one of these inputs activates the corresponding warning or shutdown sequence.
External sensing equipment must be connected to the designated digital input.
The nature of the fault is an optional customer selection. Example inputs: Low Coolant Level, Low Fuel
Level, Ground Fault, etc.
The InPower service tool or access to the Setup submenus is required to modify the customer
fault inputs. Contact your authorized distributor for assistance.
Each output has normally-open contacts. The contacts can be used to control small devices, indicator
lamps, or relays.
The contacts are programmed to energize by entering a code number for the desired event.
NOTICE
Using the InPower service tool or accessing the Setup submenus is required to modify the
customer outputs. Contact an authorized distributor for assistance.
8.4.6Contact Ratings for Configurable Outputs
TABLE 19. CONTACT RATINGS FOR CONFIGURABLE OUTPUTS
DescriptionValue
Maximum voltage30 VDC
Maximum current2 Amps
8.4.7Switched B+
This output is active when the control receives a run command, for example, a remote start signal in Auto
mode or the Start button in Manual mode.
This relay is connected to the corresponding configurable output on the control. If the configurable output
is active, the relay is active. If the configurable output is inactive, the relay is inactive.
This relay allows the configurable output to control larger devices, and it isolates the control from these
devices.
Arc Flash and Shock Hazard
Voltages and currents present an electrical shock hazard that can cause severe burns or death.
Make sure that only service personnel who are trained and experienced perform electrical and
mechanical component installations. The AC sensing harness and other cabling will become
energized when the generator set is in operation.
WARNING
Hazardous Voltage
Contact with high voltages can cause severe electrical shock, burns, or death.
Make sure that only personnel who are trained and qualified to work on this equipment are
allowed to operate the generator set and perform maintenance on it.
WARNING
Automated Machinery
Accidental or remote starting of the generator set can cause severe personal injury or death.
Isolate all auxiliary supplies and use an insulated wrench to disconnect the starting battery
cables (negative [–] first).
WARNING
Combustible Gases
Ignition of battery gases is a fire and explosion hazard which can cause severe personal injury or
death.
Do not smoke, or switch the trouble light ON or OFF near a battery. Touch a grounded metal
surface first before touching batteries to discharge static electricity. Stop the generator set and
disconnect the battery charger before disconnecting battery cables. Using an insulated wrench,
disconnect the negative (–) cable first and reconnect it last.
WARNING
Electric Shock Hazard
Voltages and currents present an electrical shock hazard that can cause severe burns or death.
Avoid contact with the voltage sense and bus sense leads; voltages of up to 600 VAC may still
be present. These voltages could be live even when the generator set is switched off.
This section provides the procedure that is used to connect the AC electrical system of the generator set.
Before making any AC electrical connections, make certain the generator set cannot be accidentally
started. Make sure the Operator Panel is in OFF mode. Turn off or remove AC power from the battery
charger and then remove the negative (–) battery cable from the set starting battery using an insulated
wrench.
If the generator set is being installed in an application where it may parallel with other generators or utility
sources, the generator set control system may be energized from an external source. Lock out tag out any
external source that can provide AC power to the generator set.
Ventilate the battery area before working on or near battery. Wear goggles. Stop the generator
set and disconnect the battery charger before disconnecting battery cables. Disconnect negative
(–) cable first and reconnect last using an insulated wrench.
Connecting the generator set AC electrical system involves:
• Installation of transfer switch
• Installation or verification of paralleling switchboard
• Generator output voltage selection
• Load cable connection
• Standard and optional AC equipment connections (e.g., control box heater, coolant heater, etc.).
For all output connections, including when field connection is made at the alternator terminations,
installation should be completed with conductors of appropriate size, type, and rating specified in local
codes (or UL). For UL compliant installations, use conductor size, X AWG, 75 °C or 90 °C copper wire,
600V. Where X AWG is the conductor size specified by the local electrical code for 75 °C at the rated
output current for the generator set. For non-UL compliant installations, use cable sizes, composition, and
rating per local codes. Strain relief, bending space, raceway, and other installation features should be
completed in compliance with local code.
Local regulations often require that wiring connections be made by a licensed electrician, and that the
installation be inspected and approved before operation. All connections, wire sizes, materials used, etc.
must conform to the requirements of electrical codes in effect at the installation site.
Before starting the generator set, check to make sure that all electrical connections are secure, and that
all wiring is complete. Replace and secure any access panels that have been removed during installation.
Check that the load cables from the generator set are properly connected.
Backfeed to a utility system can cause electrocution or property damage. Do not connect to any
building electrical system except through an approved device and after the building main switch
is opened.
9.1Transfer Switch
A transfer switch must be used for switching the load from the normal power source to the generator set
(see Figure 22). Follow the installation instructions provided with the transfer switch when connecting the
load and control wiring.
2Overcurrent Protective Device4Emergency Power Source
FIGURE 22.TYPICAL LOAD TRANSFER FUNCTION
9.2Alternator Voltage Connections
These alternators can be configured to the nameplate voltages as shown on the Reconnection Diagram
decal, attached to the backside of the control box cover. Many of the voltages listed will require
reconfiguration of the alternator output leads on the connection terminal block. This reconfiguration must
only be done by service personnel that are trained and experienced to perform electrical installation. The
generator set was adjusted to produce a specified voltage during production verification testing prior to
shipment. The installer must always check the stator lead terminal block connections and perform any
necessary reconnect to obtain the voltage required.
Some generator sets are capable of producing a wide range of voltages and connection configurations;
others have specific limited capabilities. Refer to wiring diagram and generator voltages (from the
nameplate) when reviewing the voltage connection information and use the wiring diagram supplied with
your generator set when actually performing load connections.
NOTICE
Reconfiguring generator sets to higher voltages can exceed the voltage capability of the specific
generator windings and damage the generator and also decrease line current, rendering line
circuit breakers too large. Consult with your authorized distributor before performing
reconnection for a different voltage.
NOTICE
Reconfiguring generator sets to lower voltages can reduce generator set ratings, and also
increase line current, rendering line circuit breakers too small. Consult with your authorized
distributor before performing reconnection for a different voltage.
Flexible conduit and stranded conductors must be used for connections to take up movement of
the generator set.
All loads are connected to the alternator by bolting stranded load wires to the appropriate terminals on the
alternator reconnection terminal block or circuit breaker lugs. The terminals are marked U, V, W, and N to
indicate the line and neutral connections. (Reference: U, V, and W correspond with L1, L2 and L3; and N
with L0 respectively). See Appendix C on page 101 for details about the following:
• Load connections
• Conduit
• Cable Size
9.4Load Balancing
When connecting loads to the generator set, balance the loads so that the current flow from each line
terminal (L1, L2, and L3) is about the same. This is especially important if both single phase and three
phase loads are connected. Any combination of single phase and three phase loading can be used as
long as each line current is about the same, within 10 percent of median value and no line current
exceeds the name plate rating of the generator. Check the current flow from each line after connections
by observing the Operator Panel ammeter.
9.5Current Transformers
Current transformers (CTs) reduce high voltage currents (AC) to enable safe monitoring.
9.5.1CT Installation Requirements
The CT has a dot on one side. This dot must be facing toward the alternator reconnection terminal block
(conventional current flowing into the dot). A dot is also used to indicate pin 1 of the CT.
Route the load lead through the appropriate CT (refer to the Reconnection Diagram in Appendix D on
page 107.
The CTs have dual secondaries (3 pins). The CT secondary wire marked 1 is connected to pin 1 of the
CT. CT secondary wire marked 2/3 is connected to pin 3 for low voltage generator sets.
9.6Coolant Heater
The coolant heaters are designed to allow the generator set to start and pick up load within 10 seconds in
a 4.4 °C (40 °F) environment. In colder ambient temperature environments the starting time may be
longer.
9.6.1Coolant Heater Connection
NOTICE
The coolant heater must not be operated while the cooling system is empty or damage to the
heater will occur.
A coolant heater keeps the engine coolant warm when the engine is shut down. It heats and circulates the
coolant within the engine. This reduces start-up time and lessens engine wear caused by cold starts. It is
electrically operated and thermostatically controlled.
Refer to Appendix A for electrical connections.
9.6.2Coolant Heater Specifications
The coolant heaters are designed to allow the generator set to start and pick up load within 10 seconds in
a 4.4 °C (40 °F) environment. In colder ambient temperature environments the starting time may be
longer.
An installation may include one of two types of coolant heaters.
• 4990 watt at nominal voltage - This coolant heater is used in an environment where the minimum
temperature is 4.4 °C (40 °F).
• 6420 watt at nominal voltage - This coolant heater is used in an environment where the temperature
is less than 4.4 °C (40 °F).
A coolant heater can be set up for 480 VAC or 240-208 VAC configurations.
9.7Alternator Heaters
9. AC Electrical Connections7-2016
9.7.1Alternator Heater Installation
An alternator heater(s) is used to help keep the alternator free of condensation when the generator set is
not running. During cool and humid conditions, condensation can form within a alternator, creating flashing
and shock hazards.
WARNING
Water or moisture inside an alternator increases the possibility of flashing and electrical shock,
which can cause equipment damage and severe personal injury or death. Do not use an
alternator which is not dry inside and out.
Figure 23 on page 74 shows the installation of a heater element. Connect the heater(s) terminals to a
source of power that will be on during the time the engine is not running. Be sure the supply voltage and
circuit amperage is correct for the heater element rating.
A universal annunciator provides lamps and a horn to annunciate the operating status and fault conditions
of an emergency power system. It is designed for connection to either a 12 VDC or a 24 VDC control
system. It can be configured to be either a positive or negative signal device.
Two versions of the PowerCommand universal annunciator are available.
• Panel Mounted
• Panel with Enclosure
The universal annunciator can communicate using either a PCCNet or a Modbus network.
Refer to the annunciator owner's manual for more information.
Electric Shock Hazard
Voltages and currents present an electrical shock hazard that can cause severe burns or death.
Make sure that only service personnel who are trained and experienced perform electrical and
mechanical component installations. Bonding and grounding must be done properly. All metallic
parts that could become energized under abnormal conditions must be properly grounded.
The following is a brief description of system and equipment grounding of permanently installed AC
generators within a facility wiring system.
It is important to follow the requirements of the local electrical code.
Figure 29, Figure 30 and Figure 31 illustrate typical system grounding for a 2-pole, 3-pole, and 4-pole
Automatic Transfer Switch (ATS). In the 2-pole and 3-pole ATS, note that the generator neutral is
connected to the ATS and is NOT bonded to ground at the generator. In the 4-pole ATS system, a
grounding electrode conductor and a bonding jumper are used to connect the generator neutral to ground.
9. AC Electrical Connections7-2016
WARNING
NOTICE
Make sure the generator set is grounded to earth in one location only. On generator sets without a circuit
breaker, ground to the point indicated on the top of the generator. On generator sets with circuit breakers,
use the ground lug provided in the circuit breaker box.
Electrical Generating Equipment
Incorrect operation and maintenance can result in severe personal injury or death
Make sure that only suitably trained and experienced service personnel perform electrical and/or
mechanical service.
Before an initial start of the generator set, complete the Installation Checklist, see Chapter 11 on page
85.
10.1Electrical System
Verify all electrical connections are secure and all wiring is complete and inspected. Replace and secure
any access panels that may have been removed during installation.
10.2Site-specific Configuration
NOTICE
Site-specific configuration is to be undertaken by suitably trained and qualified service personnel
only.
The generator set is configured at the factory. Before starting the generator set, any site-specific
configuration should be completed by qualified service personnel.
10.3Starting
Refer to the generator set Operator manual for important safety precautions and recommended
procedures for starting the generator set and verifying proper operation. Start the generator set and verify
all engine and generator set menus are displaying the correct values.
Generator set wattage capacity is sufficient to handle maximum anticipated load.
At least 3 feet (914.4 mm) of clearance (or greater for housing door) is provided around the entire generator
set for service and ventilation.
The generator set is located in an area not subject to flooding.
All operating personnel have read and are familiar with the generator set Operator manual, all health and
safety procedures, warnings, cautions, precautions, and the other documentation supplied with the generator
set.
All operators have been thoroughly briefed on preventative maintenance procedures.
All operators have read and understand all important safety instructions.
Generator Set Support
The floor, roof, or earth on which the generator set rests is strong enough and will not allow shifting or
movement. Observe local codes on soil bearing capacity due to freezing and thawing.
The generator set is properly supported and retained to an approved base
The supporting base is large enough and is of non-combustible material, extending 6 inches (152.4 mm) all
around the generator set.
Cooling Air Flow
Generator set air inlet is faced into direction of strongest, prevailing winds.
Air inlet openings are unrestricted and are at least 1 to 11/2times larger than air outlet area.
Cooling air outlet is on downwind side of building (if not, wind barrier is constructed).
Proper ducting material (sheet metal, canvas) is used between radiator and air outlet.
Diesel Fuel System (if applicable)
Fuel tanks meet or exceed all Local, State, or National codes (if applicable).
Fuel lines are properly installed, supported, and protected against damage.
The fuel filters have been installed.
Approved flexible fuel line is installed between the main fuel supply and the generator set’s fuel system near
the generator set, to protect it against damage caused by vibration, expansion, and contraction.
Strainer or fuel screen (100 to 200 mesh) is installed in the fuel supply line to protect the fuel lift pump, day
tank transfer pump, or float valve seat from fuel tank debris (if applicable).
The fuel filter assembly shipped with the generator set is installed and operational (if applicable).
Fuel supply shutoff valves are installed to prevent fuel flow in case of leaks.
No shutoff valves are installed on engine fuel return line (if applicable).
External fuel pumps are connected and operational at all times - generator set started or shut down (if
applicable).
Fuel tanks are filled with the correct grade / type of fuel (if applicable).
Fuel system is properly primed.
No fuel leaks are found in supply line or engine fuel system.
Gaseous Fuel System (if applicable)
Check fuel line and use equations to verify it has proper volume capability.
Check if fuel pressure is between 7-13 inches water column.
Check for any gas leaks.
If necessary, perform initial demand regulator adjustment procedure.
Make sure furl pressure does not drop below 7 inches water column under full load.
Exhaust System
The breather tube routing is set up to blow the fumes away from the generator set (if applicable)
Operators are thoroughly briefed on the dangers of carbon monoxide gas.
If the installation includes a heavy duty air cleaner, it has been installed.
Areas around generator set are well ventilated. No possibility of exhaust fumes entering building doors,
windows, or intake fans.
Exhaust gases are piped safely outside and away from building.
The correct length of approved rigid pipe is connected to the generator set flexible pipe using approved
securing methods with no weight resting on engine exhaust components. There are no bends in flex section.
Condensation drain is provided in lowest section of exhaust piping.
Exhaust piping is insulated to guard against burns to personnel.
Exhaust piping passing through walls or ceilings have approved fire-proof materials and are in compliance
with all codes.
Exhaust piping is large enough in diameter to prevent excessive back pressure on engine.
AC and DC Wiring
For bottom entry circuit breaker installations, the cable chute has been installed (if applicable).
Wire sizes, insulation, conduits and connection methods all meet applicable codes.
AC and DC wires are separated in their own conduit to prevent electrical induction.
All load, line and generator connections are well made and correct.
Flexible conduit is used between the generator and the building or surrounding structure.
Check phase rotation.
Generator Set Pre-Start
Generator set engine is properly serviced with oil and coolant.
Battery charger is installed using the appropriate cable size and is operational.
Battery charger is configured for the proper DC battery voltage, battery type, and float voltage.
Batteries are properly installed, serviced and charged.
Battery temperature sensor is connected and operational (if applicable).
Rua Jati, 310, Cumbica
Guarulhos, SP 07180-900
Brazil
Phone +55 11 2186 4195
Fax +55 11 2186 4729
Cummins Power Generation Limited
Columbus Avenue
Manston Park
Manston, Ramsgate
Kent CT12 5BF
United Kingdom
Phone +44 1843 255000
Fax +44 1843 255902
Cummins Power Generation
2 Rongchang East Street,
Beijing Economic – Technological
Development Area
Beijing 100176, P.R.China
Phone
86 10 59023001
Fax +86 10 5902 3199
Cummins Power Generation Limited
10 Toh Guan Road #07-01
TT International Tradepark
Singapore 608838
Phone +65 6417 2388
Fax +65 6417 2399
Cummins India Ltd,
Power Generation Business Unit,
Plot No B-2, SEZ Industrial Area,
Village-Nandal & Surwadi, Taluka-
Phaltan
Dist- Satara, Maharashtra 415523
India
Phone +91 021 66305514
LATIN AMERICAMEXICO
3350 Southwest 148th Ave.
Suite 205
Miramar, FL 33027
USA
Phone +1 954 431 551
Fax +1 954 433 5797
Eje 122 No. 200 Zona Industrial
San Luis Potosi, S.L.P. 78395
Mexico
Phone +52 444 870 6700
Fax +52 444 824 0082
12.1How to Obtain Service
When a product requires servicing, contact the nearest Cummins Power Generation distributor. To locate
the distributor, refer to power.cummins.com and select Distributor Locator. When contacting the
distributor, always supply the complete model, specification, and serial number as shown on the
nameplate.
To easily locate the nearest certified distributor/dealer for Cummins generator sets in your area, or for
more information, contact us at 1-800-344-0039 or visit power.cummins.com.
If unable to contact a distributor using the automated service, consult the Internet.
If unable to arrange a service or resolve an issue, contact the Service Manager at the nearest Cummins
Power Generation distributor for assistance.
When contacting the distributor, always supply the complete Model, Specification, and Serial Number as
shown on the product nameplate.
The drawings included in this section are representative. For current complete information,
refer to the drawing package that was shipped with the unit.