Before operating the generator set (genset), read the
Operator’s Manual and become familiar with it and the
equipment. Safe and efficient operation can be
achieved only if the equipment is properly operated
and maintained. Many accidents are caused by failure
to follow fundamental rules and precautions.
The following symbols, found throughout this manual,
alert you to potentially dangerous conditions to the operator, service personnel, or the equipment.
This symbol warns of immediate
hazards which will result in severe personal injury or death.
WARNING
This symbol refers to a hazard or unsafe practice which can result in severe personal injury or death.
CAUTION
This symbol refers to a hazard or unsafe practice which can result in personal injury
or product or property damage.
FUEL AND FUMES ARE FLAMMABLE
Fire, explosion, and personal injury or death can result
from improper practices.
• Be sure all fuel supplies have a positive shutoff
valve.
• Be sure battery area has been well-ventilated prior
to servicing near it. Lead-acid batteries emit a highly
explosive hydrogen gas that can be ignited by arcing, sparking, smoking, etc.
EXHAUST GASES ARE DEADLY
Provide an adequate exhaust system to properly
•
expel discharged gases away from enclosed or
sheltered areas and areas where individuals are
likely to congregate. Visually and audibly inspect
the exhaust daily for leaks per the maintenance
schedule. Make sure that exhaust manifolds are secured and not warped. Do not use exhaust gases to
heat a compartment.
• Be sure the unit is well ventilated.
• Engine exhaust and some of its constituents are
known to the state of California to cause cancer,
birth defects, and other reproductive harm.
MOVING PARTS CAN CAUSE SEVERE
PERSONAL INJURY OR DEATH
• DO NOT fill fuel tanks while engine is running, un-
less tanks are outside the engine compartment.
Fuel contact with hot engine or exhaust is a potential
fire hazard.
• DO NOT permit any flame, cigarette, pilot light,
spark, arcing equipment, or other ignition source
near the generator set or fuel tank.
• Fuel lines must be adequately secured and free of
leaks. Fuel connection at the engine should be
made with an approved flexible line. Do not use
copper piping on flexible lines as copper will become brittle if continuously vibrated or repeatedly
bent.
• Natural gas is lighter than air, and will tend to gather
under hoods. Propane is heavier than air, and will
tend to gather in sumps or low areas. NFPA code requires all persons handling propane to be trained
and qualified.
• Keep your hands, clothing, and jewelry away from
moving parts.
• Before starting work on the generator set, discon-
nect battery charger from its AC source, then disconnect starting batteries, negative (-) cable first.
This will prevent accidental starting.
• Make sure that fasteners on the generator set are
secure. Tighten supports and clamps, keep guards
in position over fans, drive belts, etc.
• Do not wear loose clothing or jewelry in the vicinity of
moving parts, or while working on electrical equipment. Loose clothing and jewelry can become
caught in moving parts. Jewelry can short out electrical contacts and cause shock or burning.
• If adjustment must be made while the unit is run-
ning, use extreme caution around hot manifolds,
moving parts, etc.
MS-1
iii
Page 3
ELECTRICAL SHOCK CAN CAUSE
SEVERE PERSONAL INJURY OR DEATH
•
Remove electric power before removing protective
shields or touching electrical equipment. Use rubber insulative mats placed on dry wood platforms
over floors that are metal or concrete when around
electrical equipment. Do not wear damp clothing(particularly wet shoes) or allow skin surface to bedamp when handling electrical equipment.
•Use extreme caution when working on electrical
components. High voltages can cause injury ordeath. DO NOT tamper with interlocks.
•Follow all applicable state and local electrical
codes. Have all electrical installations performed bya qualified licensed electrician. Tag and lock openswitches to avoid accidental closure.
•DO NOT CONNECT GENERATOR SET DI-
RECTLY TO ANY BUILDING ELECTRICAL SYS-TEM. Hazardous voltages can flow from the gen-erator set into the utility line. This creates a potentialfor electrocution or property damage. Connect onlythrough an approved isolation switch or an ap-proved paralleling device.
GENERAL SAFETY PRECAUTIONS
Coolantsunder pressure have a higher boiling point
•
than water. DO NOT open a radiator or heat ex-changer pressure cap while the engine is running.Allowthe generator set to cool and bleed the systempressure first.
•Benzene and lead, found in some gasoline, have
been identified by some state and federal agencies
as causing cancer or reproductive toxicity. When
checking, draining or adding gasoline, take care not
to ingest, breathe the fumes, or contact gasoline.
•Used engine oils have been identified by some state
or federal agencies as causing cancer or reproductive toxicity. When checking or changing engine oil,
take care not to ingest, breathe the fumes, or con-tact used oil.
•Provide appropriate fire extinguishers and install
them in convenient locations. Consult the local firedepartment for the correct type of extinguisher touse. Donot use foam on electrical fires. Use extin-guishers rated ABC by NFPA.
•Make sure that rags are not left on or near the en-
gine.
•Remove all unnecessary grease and oil from the
unit. Accumulated grease and oil can cause over-heating and engine damage which present a poten-tial fire hazard.
•Keep the generator set and the surrounding area
clean and free from obstructions. Remove any de-bris from the set and keep the floor clean and dry.
•Do not work on this equipment when mentally or
physically fatigued, or after consuming any alcoholor drug that makes the operation of equipment un-safe.
•Substances in exhaust gases have been identified
by some state or federal agencies as causing can-cer or reproductive toxicity. Take care not to breathor ingest or come into contact with exhaust gases.
KEEP THIS MANUAL NEAR THE GENSET FOR EASY REFERENCE
Each operator should read this manual before oper-ating the set for the first time. A generator set (gen-set) must be operated and maintained properly ifyou are to expect safe, reliable and quiet operation.The manual includes a troubleshooting guide and amaintenance schedule.
The engine manual is included with the set. Wherethere is conflicting information, this manual takesprecedence over the engine manual.
There are two types of control panels available forthe generator set, the Detector control or the Senti-nel control panel (Figure 1-1). The panels shown in-clude optional features (indicators, meters andswitches) that may or may not be included with thegenset. All standard and optional controls and indi-cators are discussed in Sections 3 and 5 of thismanual.
Detector 12 Control
There are separate Operation and Troubleshootingsections for gensets using the Sentinel control orthe Detector control (Figure 1-1). Refer to the Table ofContents for specific information relating to yourgenset. The remaining sections apply to all versions.
WARNING
nancecan lead to severe personal injury or lossof life and property by fire, electrocution, me-chanical breakdown or exhaust gas asphyxi-ation. Read and follow the safety precautionson page iii and carefully observe all instructionsand precautions in this manual.
Improper operation and mainte-
Sentinel Control
FIGURE 1-1. CONTROL PANEL CONFIGURATIONS
1-1
Page 7
HOW TO OBTAIN SERVICE
When the generator set requires servicing, contact
your nearest Cummins
tor. Factory-trained Parts and Service representatives are ready to handle all your service needs.
®
/Onan® dealer or distribu-
1-800-888-ONAN (this automated service utilizes
touch-tone phones only). By entering your area
code and the first three digits of your local telephone
number, you will receive the name and telephone
number of the distributor nearest you.
If you are unable to locate a dealer or distributor,consult the Yellow Pages. Typically, our distributorsare listed under:
For outside North America, call Onan Corporation,1-612-574-5000,7:30 AM to 4:00 PM, Central Stan-dard Time, Monday through Friday.Or,send a fax toOnan using the fax number 1-612-574-8087.
GENERATORS-ELECTRIC orELECTRICAL PRODUCTS
Whencontacting your distributor,always supply theFor the name of your local Cummins/Onan or Onan-only distributor in the United States or Canada, call
complete Model, Specification, and Serial Number
as shown on the generator set nameplate.
WARNING
INCORRECT SERVICE OR PARTS REPLACEMENT CAN RESULT IN SEVERE PERSONAL IN-JURY,DEATH, AND/OR EQUIPMENT DAMAGE. SERVICE PERSONNEL MUST BE QUALIFIEDTO PERFORM ELECTRICAL AND/OR MECHANICAL SERVICE.
Onan is a registered trademark of Onan Corporation.
Cummins is a registered trademark of Cummins Engine Company, Inc.
1-2
Page 8
2. Specifications
MODELGGHBGGHCGGHD
Engine
Onan Modified Ford V-8
Generator kW Rating
(See Genset Nameplate)
Fuel or a combination of two fuelsPropane
Exhaust
ConnectionBackpressure (Max. Allowed)
Electrical System
Starting VoltageBattery Charging Alternator (Max.
Rating)
Cooling System
Capacity with Standard Radiator
Lubricating System
Oil Capacity with Filters
Tune-up Specifications
Spark Plug Gap
Battery
Required Battery VoltageGroup Number
LSG-875LSG-875LSG-875
Natural Gas
3 inch NPT
20.4 inch H
12 Volts DC
37 A
7.2 Gal (27.3 L)7.7 Gal (29 L)7.7 Gal (29 L)
9 Qts (8.6 L)10 Qts (9.5 L)10 Qts (9.5 L)
0.035
(0.89 mm)
12 Volts DC
31
Propane
Natural Gas
3 inch NPT
O
2
20.4 inch H
12 Volts DC
37 A
0.035
(0.89 mm)
12 Volts DC
31
O
2
Propane
Natural Gas
3 inch NPT
20.4 inch H
12 Volts DC
37 A
0.035
(0.89 mm)
12 Volts DC
31
O
2
2-1
Page 9
2-2
Page 10
3. Operation (Detector Control)
GENERAL
This section covers prestart checks, starting andstoppingand operating the generator set. Each op-eratorshould read through this entire section beforeattempting tostart the set. It is essential that the op-erator be completely familiar with the set for safeoperation. Refer to Section 9 for operating recom-mendations.
PRESTART CHECKS
Before starting, be sure the following checks havebeen made and the unit is ready for operation. Referto the Maintenance section for the recommendedprocedures.
Lubrication
Check the engine oil level. Keep the oil level asclose as possible to the dipstick high mark withoutoverfilling.
Coolant
Check the engine coolant level. The cold coolantlevel should be about 3/4 inch (18 mm) below the ra-
diator cap lower sealing surface. Do not check while
the engine is hot.
WARNING
severe burns. Do not bleed hot, pressurized coolant
from a closed cooling system.
Contact with hot coolant can result in
Fuel
Open all manual shutoff valves in the fuel supply
system.
Exhaust
Check to make sure entire exhaust system is tight,
that no combustible materials are near system, and
gases are discharged away from building openings.
CONTROL PANEL
The following describes the function and operation
of the Detector Control panel. All instruments and
controlswitches are located on the face of the con-
trol panel as illustrated in Figures 3-1 through 3-3.
The control panel is separated into a DC panel for
monitoringthe engine and an AC panel for monitor-
ing the generator.
3-1
Page 11
OIL PRESSURE
GAUGE
PANEL LAMP
RUN/STOP/REMOTE
SWITCH
COOLANT
TEMPERATURE
GAUGE
DC VOLTMETER
FIGURE 3-1. DC CONTROL PANEL (DETECTOR 12 SHOWN)
DC Panel
Panel Lamp: Illuminates control panel.
RESET/LAMPTEST/ PANEL
LAMP SWITCH
INDICATOR
LAMPS
RUNNING
TIME METER
EMERGENCY STOP
PUSHBUTTON
Run/Stop/Remote Switch: Starts and stops the
set locally, or from a remote location wired to the
control engine monitor board.
Oil Pressure Gauge: Indicates pressure of lubri-cating oil in engine (wired to a sensor located on theengine).Normal oil pressure is 40 to 65 psi (276 to449 kPa) at normal operating temperature.
Coolant Temperature Gauge: Indicates tempera-ture of circulating coolant in engine (wired to a sen-sor located on engine). Engine coolant temperatureis typically between 165
° to 195°F(74° to 91° C).
DC Voltmeter: Indicates the battery charging sys-tem voltage. Normal charging voltage is 12 to 14volts.
Running Time Meter: Registers the total number
of hours the unit has run. Use it to keep a record of
periodic servicing. Time is cumulative; meter can-
not be reset.
Reset/Lamp Test/Panel Lamp Switch: Resets
the fault circuit only when the Run/Stop/Remote
switch is in the Stop (Reset) position. Tests fault
lamps and turns on the control panel lamp.
Emergency Stop Button (Optional): Push-in
switch for emergency shutdown of the engine. To
reset, pull switch out and move Run/Stop/Remote
switch toStop position. Then push test switch to Re-
set/Lamp Test position.
3-2
Page 12
Indicator Lamps: The control panel has twelve indicator lamps which are described as follows:
• RUN (green) lamp comes on when starter cir-
cuit opens after set starting.
•PRE LO OIL PRES (yellow) indicates engine
oil pressure is marginally low.
•PRE HI ENG TEMP (yellow) indicates engine
temperature is marginally high.
•LO OIL PRES (red) indicates engine has shut
down because of critically low oil pressure.
•HI ENG TEMP (red) indicates engine has shut
down because of critically high engine tem-perature.
•OVERSPEED (red) indicates engine has shut
down because of excessive speed.
•OVERCRANK(red) indicates engine has failed
to start during the cranking period.
•FAULT 1 (red) lamp indicates an undedicated
fault.May be field programmed as a shutdownor non-shutdown, and as a timed or non-timedfault. (Normally set for timed shutdown).
•FAULT 2 (red) lamp indicates same features as
Fault 1 (normally set for non-timed shutdown).
•LOW ENG TEMP (yellow) lamp lights if engine
temperature is marginally low for starting. Itmay indicate an inoperative coolant heater.
•LO FUEL (yellow) (optional) indicates fuel sup-
ply pressure is marginally low (5 inches [127mm] WC or less).
•SWITCH OFF (flashing red) indicates genera-
tor set is not in automatic start mode.
FIGURE 3-2. INDICATOR LAMPS
3-3
Page 13
AC VOLTMETER
AC AMMETER
FREQUENCY/
RPM METER
UPPER AND LOWER
SCALE INDICATOR
A−C VOLTS
VOLTAGE
ADJUST
A−C AMPERES
EXCITATION
FIELD BREAKER
RPM
HERTZ
FIGURE 3-3. AC CONTROL PANEL
AC Panel
AC Voltmeter: Dual range instrument indicatingAC voltage. Measurement range in use shown onindicator lamp.
AC Ammeter: Dual range instrument indicates ACgenerator line current.
Frequency/RPM Meter: Indicates generator out-put frequency in hertz and engine speed in revolu-tions-per-minute (RPM).
Voltage Adjusting Rheostat: Provides approxi-matelyplus or minus five percent adjustment of therated output voltage.
PHASE
SELECTOR
SWITCH
Upper and Lower Scale Indicator Lamps: Indi-
cates which scale to use on the AC voltmeter and
ammeter.
Phase Selector Switch: Selects phases of gen-
erator output to be measured by AC voltmeter and
ammeter.
Field Breaker: Provides generator exciter and
regulatorprotection from overheating in the event of
certainfailure modes of generator, exciter and volt-
age regulator.
3-4
Page 14
GENERATOR AC VOLTAGE REGULATOR
The solid-state regulator controls AC output voltage
from the generator at a predetermined level regardless of load. Refer to the GG Series Specification
Sheet for the voltage regulation and random voltage variation specifications.
ENGINE CONTROL MODULE
Electronic and relay components of the enginemonitoring circuit are on a circuit board assembly.Sensor inputs are connected by the wiring harnessto plug connectors on the board. The control mod-ule provides the following functions of unit protec-tion.
•Overcrank - The standard cycle cranking fea-
ture allows three 15-second cranking cycleswith two 15-second rest periods. If engine failsto start, the module lights a fault lamp andopens the cranking circuit.
The overcrank option limits engine cranking to75 seconds. If engine fails to start, the modulelights a fault lamp and opens the cranking cir-cuit.
•Overspeed - Shuts down the engine immedi-
ately if overspeed occurs and lights a faultlamp.
For non-PMG generator sets, the sensorswitch ismounted in the end bell on the genera-tor shaft. It is factory adjusted to shut down 60hertz units at 2100 1850+
PMG generator sets, a frequency detectionmodule, located inside the control box, moni-tors PMG frequency and shuts down 60 hertzunits at 2100
1850+
50 r/min.
50 r/min.
±90 r/min, 50 hertz units at
±90 r/min, 50 hertz units at
• Low Oil Pressure - Shuts down the engine im-
mediately and lights a fault lamp if oil pressure
drops below:
GGHB − 14 psi (97 kPA)
GGHC, GGHD − 25 psi (195 kPA)
The fault is time-delayed about 10 seconds following starter disconnect and inhibited duringcranking. The delay allows oil pressure to riseto normal before the electronic control modulemonitors this system.
A pre-low oil pressure sensor and lamp pro-vides an alarm that oil pressure is marginallylow or less than:GGHB − 20 psi (137 kPA)GGHC, GGHD − 30 psi (207 kPA)The cause should be found and corrected assoon as possible.
•High Engine Temperature - shuts down the en-
gine immediately if coolant temperature risesabove 230°F (110° C) and lights a fault lamp.The fault is time-delayed about 10 seconds fol-lowing starter disconnect and inhibited duringcranking. This delay allows coolant in ahot en-gine time to circulate and return the waterjacket to normal before the electronic controlmodule monitors this system.
A pre-high engine temperature sensor andlamp provides an alarm that engine tempera-ture is marginally high, 220° F (104° C)cause should be found and corrected as soonas possible.
CAUTION
shutdown system may not operate if thecoolant level is too low. The high enginetemperature sensor monitors coolant tem-perature. Loss of coolant will prevent sen-sor operation and allow the engine to over-heat causing severe damage to the engine.Therefore, maintain adequate coolant levelfor proper operation of the high engine tem-perature shutdown system.
The high engine temperature
. The
•Low Coolant Level Alarm/Shutdown (Optional)
- An electronic switch that provides enginealarm or shutdown if coolant level falls too low.
It also turns on the fault lamp.
3-5
Page 15
STARTING
The following sections cover the three systems
used to start the generator set.
Before starting the generator set, make sure that
exhaust and fuel fittings are tight and properly positioned and that proper maintenance has been per-formed. See Prestart Checks in this section.
Starting at Control Panel
where the minimum ambient temperature is above
40
°F (4°C). NFPA also requires that the engine
coolant be maintained at a minimum of 90
and for most applications, accept the emergency
load in 10 seconds or less. Although most Onan
generator sets will start in temperatures below 40
°C) when equipped with coolant heaters, it might
(4
take some running time to warm the engine up be-
fore a load can be applied when ambient tempera-
tures are below 40
°F (4°C).
°F (32°C)
°F
Movethe Run-Stop-Remote switch on the DC pan-el to the RUN position. This will activate the enginecontrolsystem and the starting system. The starterwill begin cranking and after a few seconds the en-gine should start. The starter will disconnect whenthe engine reaches a speed of 450 to 570 RPM.
If the engine does not start, the starter will disen-gage after a specified period of time and the controlwill indicate an overcrank fault. Generator sets withthe optional overcrank control will crank continu-ously for up to 75 seconds before disengaging thestarter. Generator sets with the standard cyclecranking feature will crank for 15 seconds in eachcycle until 3 cycles have been completed. To clearan overcrank fault, place the Run-Stop-Remoteswitch inthe STOPposition and momentarily pressthe Reset switch. Wait two minutes for the startermotor to cool and then repeat the starting proce-dure. If the engine does not run after a second at-tempt at starting, refer to the Troubleshootingsec-tion.
Starting From Remote Location
Move the Run/Stop/Remote switch on the genera-tor set DC panel to the REMOTE position. This al-lows the generator set to be started from a remoteswitch. Closing the remote switch initiates the start-ing sequence described in the previous section.
Automatic Starting
Place the Run/Stop/Remote switch on the genera-tor set DC panel in the REMOTE position if an auto-matictransfer switch is used. This allows the trans-fer switch to start the generator set if a power outage
occurs and stop it when the power returns.
Cold Starting With Loads
In accordance with NFPA 110, Onan recommends
installing standby generator sets (life safety systems) equipped with coolant heaters in locations
The Low Engine Temperature (LET) lamp on the
Onan Detector 12 control is provided to meet the re-
quirements of NFPA 110. The LET sensor signals
an alarm when the engine coolant temperature falls
below 70
ent temperature falls below 40
may be lit even though the coolant heaters are con-
nected and operable. Under these conditions, al-
though the generator set may start, it may not be
able to accept load within 10 seconds. When this
condition occurs, check the coolant heaters for
proper operation. If the coolant heaters are operat-
ing properly, other precautions might be necessary
to warm the engine before applying a load.
°F (21°C). In applications where the ambi-
°F (4°C), the LET
STOPPING
Before Stopping
Run the generator set at no load for three to five
minutes before stopping. This allows the lubricating
oil and engine coolant to carry heat away from the
combustion chamber and bearings.
To Stop
If the set was started at the set control panel or at a
remote control panel, move the Run/Stop/Remote
switch or remote starting switch to the STOP posi-
tion. If the set was started by an automatic transfer
switch, the transfer switch will send a remote (timed
delay) stop signal after the normal power source re-
turns.
Emergency Stop
An optional emergency stop button is located on the
rightside of control panel (Figure 3-1). Push button
in for emergency stop. To reset, pull switch out and
move Run/Stop/Remote switch to Stop position.
Then push test switch to Reset/Lamp Test position.
Onan automatic transfer switches have as an op-
tion an exerciser that can be preset to provide regu-
lar exercise periods. Typically the exerciser can be
set for time of start, length of run, and day of week.
3-6
Page 16
4. Troubleshooting (Detector Control)
The generator set has sensors that continuously
monitor the engine for abnormal conditions, such as
low oil pressure or high coolant temperature. Ifthese conditions occur, the engine monitor acti-vates a fault lamp, and may also stop the engine(depending onthe condition). If the generator set isstopped for this reason, the operator may be able torestart the set after making adjustments or correc-tions. This section describes the fault condition sys-tem, and suggests troubleshooting procedures.
The control has a single green light to indicate RUN,four amber lights and seven red fault lights. Thecontrol also has a terminal connection for an audi-ble alarm, that sounds when a fault occurs.
SAFETY CONSIDERATIONS
High voltages are present inside the control box andgenerator output box when the set is running. Donot open the control box or generator output boxwhile the set is running.
WARNING
nents can cause electrocution, resulting in se-vere personal injury or death. Keep control andoutputbox covers in place during troubleshoot-ing.
When troubleshooting a set that is shut down, makecertainthe generator set cannot be accidentally re-started. Place the Run/Stop/Remote switch in theSTOP position and remove the negative battery ca-ble from the set starting battery.
CAUTION
charger from its AC source before disconnect-ing the battery cables. Otherwise, disconnect-ing the cables can result in voltage spikes highenough todamage the DC control circuits of theset.
Contacting high voltage compo-
Always disconnect a battery
WARNING
set while working on it can cause severe per-
sonal injury or death. Prevent accidental start-
ing by disconnecting the starting battery cables
(negative [−] first).
Make certain battery area has been well venti-
latedbefore servicing battery, especially if a
battery charger has been connected. Arcing
can ignite explosive hydrogen gas given off by
batteries, causing severe personal injury. Arc-
ing can occur when cable is removed or re-at-
tached, or when negative (−) battery cable is
connectedand a tool used to connect or discon-
nectpositive (+) battery cable touches frame or
other grounded metal part of the set.
When afault lamp turns on during operation, follow
the procedures listed below to locate and correct
the problem. For any symptom not listed, contact an
authorized service center for assistance.
Accidental starting of the generator
Resetting the Control
The external alarm and fault lamp may be deacti-
vated by moving the Run/Stop/Remote switch to
the Stop position and pressing the Reset/Lamp
Test/Panel Lamp switch. Locate the problem and
correct it before restarting the set. While pressing
the Reset/Lamp Test/Panel Lamp switch, make cer-
tain that all lamps light.
Line Circuit Breaker (Optional)
The optional line circuit breaker mounts on the gen-
eratoroutput box. If the load exceeds the generator
current rating, the line circuit breaker will open, pre-
venting the generator from being overloaded. If the
circuit breaker trips, locate the source of the over-
load and correct as necessary. Manually reset the
breaker to reconnect the load to the generator.
4-1
Page 17
TABLE 4-1. TROUBLESHOOTING
Many troubleshooting procedures present hazards which can result in severe personal
injury or death. Only qualified service personnel with knowledge of fuels, electricity, and machinery
hazards should perform service procedures. Review safety precautions on pages iii and iv.
SYMPTOMCORRECTIVE ACTION
1.Green RUN lamp lights following enginestartup.
2.PRE HI ENGINE TEMP lamp lights. En-gine continues to operate.
3.HI ENG TEMP lamp lights. Engine shutsdown.
1.Indicates all engine systems are normal. No correc-tive action required.
2.Indicates engine has begun to overheat and enginetemperaturehas risen to approximately 220C). If generator is powering non-critical and criticalloads and cannot be shut down, use the following:
a.Reduce load if possible by turning offnon-critical
loads.
b.Check air inlets and outlets and remove any ob-
structions to airflow.
If engine can be stopped, follow procedure instep 3.
3.Indicates engine has overheated (engine tempera-ture has risen above 230low (sets with coolant level sensor). Allow engine tocool down completely before proceeding with the fol-lowing checks:
a.Check coolant level and replenish if low. Look for
possible coolant leakage points and repair ifnecessary.
°F/110°C) or coolant level is
°F (104°
4.PRE LO OIL PRES lamp lights. Enginecontinues to operate.
b.Check for obstructions to cooling airflow and
correct as necessary.
c.Check for a slipping fan belt and tighten if loose.
d.Reset control and restart after locating and cor-
recting problem. Contact an authorized servicecenter for service if none of the above.
4.Indicates engine oil pressure has dropped to:GGHB − 20 psi (137 kPA)GGHC, GGHD − 30 psi (207 kPA)If generator is powering critical loads and cannot beshut down, wait until next shutdown period and thenfollow step 5 procedure. If engine can be stopped, fol-low procedures in step 5.
4-2
Page 18
TABLE 4-1. TROUBLESHOOTING (continued)
Many troubleshooting procedures present hazards which can result in severe personal
injury or death. Only qualified service personnel with knowledge of fuels, electricity, and machinery
hazards should perform service procedures. Review safety precautions on pages iii and iv.
SYMPTOMCORRECTIVE ACTION
5.LO OIL PRES lamp lights. Engine shutsdown. NOTE: See also step 6.
6.OVERCRANK lamp lights and enginestops cranking.
or
Engine runs, shuts down, and LO OILPRES lamp lights..
7.OVERSPEED lamp lights and the en-gine shuts down.
5.Indicates engine oil pressure has dropped to:GGHB − 14 psi (97 kPA)GGHC, GGHD − 25 psi (195 kPA)Check oil level, lines and filters. If oil system is OK butoil level is low, replenish. Reset control and restart.Contact anauthorized service center if oil pressure isnot in the range of 40 to 65 psi (276 to 449 kPa).
6.Indicates possible fuel system problem.
a.Open any closed fuel shutoff valve.
b.Check for dirty or plugged air filter and replace if
necessary (see Maintenance section).
c.Gaseous fuel delivery to the set is inadequate.
Contact anauthorized service center for service.
d.Reset the control and restart after correcting the
problem. Contact an authorized service centerfor service if none of the above.
7.Indicates engine has exceeded normal operatingspeed. Contact an authorized service center for serv-ice.
8.SWITCH OFF lamp flashes.8.Indicates Run/Stop/Remote switch is in the Stop po-sition which will prevent automatic starting if an auto-matic transfer switch is used. Move the Run/Stop/Re-mote switch to the Remote position for automaticstarting.
9.LO ENG TEMP lamp lights. Set is in
standby mode but is not operating.
(Lamp lights when engine coolant tem-perature is 70the lamp goes out after the enginewarms up, there should be no cause foralarm even during initial generator setoperation.)
° F (21°C) or lower. Since
9.Indicates engine coolant heater is not operating, notcirculating coolant or ambient temperature too coldfor heater to keep up with demand. Check for the fol-lowing conditions:
a.Coolant heater not connected to power supply.
Check for blown fuse or disconnected heatercord and correct as required.
b.Check for low coolant level and replenish if re-
quired. Look for possible coolant leakage points
and repair as required.
c. Contact an authorized service center for service
if none of the above.
4-3
Page 19
TABLE 4-1. TROUBLESHOOTING (continued)
Many troubleshooting procedures present hazards which can result in severe personal
injury or death. Only qualified service personnel with knowledge of fuels, electricity, and machinery
hazards should perform service procedures. Review safety precautions on pages iii and iv.
SYMPTOM
10.The FAULT 1 or FAULT 2 fault lamplights. Engine shuts down immediately,engine runs for several seconds andthen shuts down, or engine continues torun.
11.The LOW FUEL fault lamp lights. En-gine continues to run or is in standbymode.
12.Fault lamp lights but no fault exists. En-gine gauges show oil pressure, enginetemperature,and frequency (speed) arewithin normal limits.
13.Engine starts from generator controlpanel but will not start automatically orfrom a remote panel. (Note: The Run/Stop/Remote switch must be in the Re-mote position for automatic or remotestarting).
CORRECTIVE ACTION
10.The standard undesignated fault functions are pro-grammed toshut down the set when a fault is sensed.Fault 1 is time delayed while Fault 2 is immediate.The nature of the fault is an optional selection that isdetermined when the set installation is designed.The undesignated fault functions may also be pro-grammed for non-shutdown or non-time delay.
11.Indicates fuel supply pressure is marginally low (5inches [127 mm] WC or less). Check for partiallyclosed shutoff valve, empty propane supply tank. Fornatural gas fueled sets, check with the gas utility.
12.The monitor board or a sensor may be at fault. Con-tact an authorized service center for service.
13.Remotecircuit breaker is tripped. Reset breaker andrestart. Contact an authorized service center ifbreaker trips after resetting.
14.Engine will not crank.
14. Indicates possible fault with control or starting sys-tem. Check for the following conditions:
a.Fault lamp on. Correct fault and reset control.
b.Poor battery cable connections. Clean the bat-
tery cable terminals and tighten all connections.
c.Discharged ordefective battery.Recharge or re-
place the battery.
d.Emergencystop button (if equipped) pushed in.
To reset, pull switch out and move Run/Stop/Re-mote switch to Stop position. Then push testswitch to Reset/ Lamp position.
e.Contact an authorized service center if none of
the above.
4-4
Page 20
TABLE 4-1. TROUBLESHOOTING (continued)
Many troubleshooting procedures present hazards which can result in severe personal
injury or death. Only qualified service personnel with knowledge of fuels, electricity, and machinery
hazards should perform service procedures. Review safety precautions on pages iii and iv.
SYMPTOM
15.No AC output voltage.
16.RUN or fault lamp(s) does not light whenLamp Test switch is engaged.
17.Green RUN lamp does not light follow-ing engine startup.
CORRECTIVE ACTION
15.Field breaker is tripped. Reset breaker. Contact anauthorized service center if voltage buildup causesbreaker to trip.
16.Contact an authorized service center for assistance.
17.Indicates possible Start/Disconnect relay failure.Contact an authorized service center for assistance.
4-5
Page 21
4-6
Page 22
5. Operation (Sentinel Control)
GENERAL
This section covers prestart checks, starting andstoppingand operating the generator set. Each op-eratorshould read through this entire section beforeattempting tostart the set. It is essential that the op-erator be completely familiar with the set for safeoperation. Refer to Section 9 for operating recom-mendations.
PRESTART CHECKS
Before starting, be sure the following checks havebeen made and the unit is ready for operation. Referto the Maintenance section for the recommendedprocedures.
Lubrication
Check the engine oil level. Keep the oil level asclose as possible to the dipstick high mark withoutoverfilling.
Coolant
Check the engine coolant level. The cold coolantlevel should be about 3/4 inch (18 mm) below the ra-
diator cap lower sealing surface. Do not check while
the engine is hot.
WARNING
in severe burns. Do not bleed hot, pressurizedcoolant from a closed cooling system.
Contact with hot coolant can result
Fuel
Check the fuel supply and open all manual shutoffvalves in the fuel supply system.
Exhaust
Check to make sure entire exhaust system is tight,that no combustible materials are near system, andgases are discharged away from building openings.
CONTROL PANEL
The following describes the function and operationof the Sentinel control. All instruments and controlswitches are located on the face of the control panelas illustrated in Figure 5-1.
5-1
Page 23
AC VOLTMETER
AC AMMETER
PHASE
SELECTOR
SWITCH
FREQUENCY/
RPM METER
FIELD BREAKER
(EXCITATION)
VOLTAGE
ADJUST
RUN/STOP/REMOTE
SWITCH
20A CONTROL
FUSE
COMMON FAULT
CIRCUIT BREAKER
RUNNING
TIME METER
AC CONTROLDC CONTROL
FIGURE 5-1. SENTINEL CONTROL PANEL
DC Control
Run/Stop/Remote Switch: Starts and stops theset locally, or from a remote location wired to thecontrol.
Running Time Meter: Registers the total numberof hours the unit has run. Use it to keep a record ofperiodic servicing. Time is cumulative; meter can-not be reset.
20A Control Fuse: Protects control componentsand wiring from current overload.
Common Fault Circuit Breaker: The commonfault circuit breaker shuts down the engine whenany fault shutdown sensor activates. Fault shut-down isindicated when the breaker reset button ex-tends out past normal. Push the button to restore
operation (after the engine has been properly serviced).
The standard fault shutdowns are low oil pressure,
high engine temperature or overcrank. Overspeed
is optional.
AC Control
AC Voltmeter (Optional): Dual range instrumentindicating AC voltage. Measurement range in useshown on indicator lamp.
AC Ammeter (Optional): Dual range instrumentindicates AC generator line current.
Frequency/RPMMeter (Optional): Indicates gen-erator output frequency in hertz and engine speedin revolutions-per-minute (RPM).
Voltage Adjusting Rheostat (Optional): Providesapproximately plus or minus five percent adjust-ment of the rated output voltage.
Phase Selector Switch (Optional): Selectsphases of generator output to be measured by AC
voltmeter and ammeter.
Field Breaker (Excitation): Provides generator
exciter and regulator protection from overheating in
the event of certain failure modes of generator, exciter and voltage regulator.
5-2
Page 24
GENERATOR AC VOLTAGE REGULATOR
The solid-state regulator controls AC output voltage
from the generator at a predetermined level regardless of load. Refer to the GG Series Specification
Sheet for the voltage regulation and random voltage variation specifications.
ENGINE MONITORING
Electronic and relay components of the enginemonitoring circuit are mounted inside the controlbox. An optional Dry Contact Module (DCM) canalso beinstalled in the control box to enable remotemonitoring of these components. The componentsprovide the following functions of unit protection.
Note: Refer to the Installation Manual for a functionaldescription of the Dry Contact Module option.
•Overcrank - Limits engine cranking to 60 se-
conds. Ifengine fails to start, the Fault Breakertrips and opens the cranking circuit.
• Low Coolant Level (optional w/DCM) - Shuts
down the engine immediately if coolant level
falls too low. Fault condition cannot be cleared
until sensor detects coolant in radiator.
• Low Fuel Pressure (optional w/DCM) - Indi-
cates fuel supply pressure is marginally low (5inches [127 mm] WC or less). Used only insingle fuel systems. (Remote panel must be at-tached to control to monitor this error.)
CAUTION
down system may not operate if the coolantlevel is too low. The high engine temperaturesensor monitors coolant temperature. Loss ofcoolantwill prevent sensor operation and allowthe engine to overheat causing severe damageto the engine. Therefore, maintain adequatecoolant level for proper operation of the highengine temperature shutdown system.
The high engine temperature shut-
STARTING
•Overspeed(optional) - Shuts down the engine
immediately and trips the common fault circuitbreaker if overspeed occurs. The sensorswitch ismounted in the end bell on the genera-tor shaft for non-PMG sets. PMG sets, a fre-quency detection module, located inside thecontrol box, monitors PMG frequency. The shutdown limits are: 60 hertz units at 2100 min, 50 hertz units at 1850+
50 r/min.
±90 r/
•Low Oil Pressure - Shuts down the engine im-
mediately and trips the common fault circuitbreaker if oil pressure drops below:GGHB − 14 psi (97 kPA)GGHC, GGHD − 25 psi (195 kPA)The fault is time-delayed about 10 seconds fol-lowing starter disconnect and inhibited duringcranking. The delay allows oil pressure to riseto normal before the electronic control modulemonitors this system.
•High Engine Temperature - Shuts down the en-
gine immediately if coolant temperature risesabove 230°F (110° C) and trips the commonfault circuit breaker. Fault condition cannot becleared until sensor detects coolant tempera-
ture of lower than 220° F (104° C)
.
The following sections cover the three systemsused to start the generator set.
Before starting the generator set, make sure thatexhaust and fuel fittings are tight and properly posi-tioned and that proper maintenance has been per-formed. See Prestart Checks in this section.
Starting at Control Panel
Movethe Run-Stop-Remote switch on the DC pan-el to the RUN position. This will activate the enginecontrolsystem and the starting system. The starterwill begin cranking and after a few seconds the en-gine should start. The starter will disconnect whenthe engine reaches a speed of 450 to 570 RPM.
If the engine does not start, the starter will disen-gage after 60 seconds and the control will indicatean overcrank fault. To clear an overcrank fault,place the Run-Stop-Remote switch in the STOPpo-sition and reset the common fault circuit breaker.Wait two minutes for the starter motor to cool andthen repeat the starting procedure. If the enginedoes not run after a second attempt at starting, refer
to the Troubleshooting (Sentinel Control) section.
5-3
Page 25
Starting From Remote Location
Move the Run/Stop/Remote switch on the generator set DC panel to the REMOTE position. This allows the generator set to be started from a remote
switch. Closing the remote switch initiates the starting sequence described in the previous section.
Automatic Starting
Engine coolant heaters are available for easier
starting in cold weather. Make sure the voltage of
the separate power source is correct for the coolant
heater element rating.
CAUTION
heater, make sure the cooling system is full be-fore applying power to the heater.
To avoid damage to the coolant
STOPPING
Place the Run/Stop/Remote switch on the genera-tor set DC panel in the REMOTE position if an auto-matictransfer switch is used. This allows the trans-fer switch to start the generator set if a power outageoccurs and stop it when the power returns.
Cold Starting With Loads
Change the engine oil if it is not of the viscosity rec-ommended for the ambient temperature (Figure7-1).
To prevent engine coolant from freezing, make surethe coolant is a 50/50 mixture of anti-freeze and wa-ter.
Before Stopping
Run the generator set at no load for three to fiveminutes before stopping. This allows the lubricatingoil and engine coolant to carry heat away from thecombustion chamber and bearings.
To Stop
If the set was started at the set control panel or at aremote control panel, move the Run/Stop/Remoteswitch or remote starting switch to the STOP posi-tion. If the set was started by an automatic transferswitch, the transfer switch will send a remote (timeddelay) stop signal after the normal power source re-turns.
5-4
Page 26
6. Troubleshooting (Sentinel Control)
The generator set has sensors that continuously
monitor the engine for abnormal conditions, such as
low oil pressure or high coolant temperature. Ifthese conditions occur, the common fault circuitbreaker trips, and the engine shuts down. After theproblem iscorrected, reset the common fault circuitbreaker torestart the generator set. This section de-scribes the fault condition system, and suggeststroubleshooting procedures.
SAFETY CONSIDERATIONS
High voltages are present inside the control box andgenerator output box when the set is running. Donot open the control box or generator output boxwhile the set is running.
WARNING
nents can cause electrocution, resulting in se-vere personal injury or death. Keep control andoutputbox covers in place during troubleshoot-ing.
When troubleshooting a set that is shut down, makecertainthe generator set cannot be accidentally re-started. Place the Run/Stop/Remote switch in theSTOP position and remove the negative battery ca-ble from the set starting battery.
Contacting high voltage compo-
CAUTION
charger from its AC source before disconnect-ing the battery cables. Otherwise, disconnect-ing the cables can result in voltage spikes highenough todamage the DC control circuits of theset.
WARNING
set while working on it can cause severe per-sonal injury or death. Prevent accidental start-ing by disconnecting the starting battery cables(negative [−] first).
Make certain battery area has been well venti-latedbefore servicing battery, especially if abattery charger has been connected. Arcingcan ignite explosive hydrogen gas given off bybatteries, causing severe personal injury. Arc-ing can occur when cable is removed or re-at-tached, or when negative (−) battery cable isconnectedand a tool used to connect or discon-nectpositive (+) battery cable touches frame orother grounded metal part of the set.
When a fault condition occurs during operation, fol-low the procedures in Table 6-1 to locate and cor-rect the problem. For any symptom not listed, con-tact an authorized service center for assistance.
Always disconnect a battery
Accidental starting of the generator
6-1
Page 27
TABLE 6-1. TROUBLESHOOTING
Many troubleshooting procedures present hazards which can result in severe personal
injury or death. Only qualified service personnel with knowledge of fuels, electricity, and machinery
hazards should perform service procedures. Review safety precautions on pages iii and iv.
SYMPTOMCORRECTIVE ACTION
1.Engine will not crank.1. Indicates possible fault with control or starting system.Check for the following conditions:
a.Correct fault and reset common fault circuit break-
er.
b.Poor battery cable connections. Clean the battery
cable terminals and tighten all connections.
c.Discharged or defective battery. Recharge or re-
place the battery.
d.Replace the control circuit fuse (located inside the
control panel) if it has blown.
2.The engine cranks, but does not start.
3.The engine shuts down due to high en-gine temperature or low coolant level.The Fault Shutdown is being indicatedby the fault circuit breaker reset button(extended out).
2.Indicates possible fuel system problem.
a.Check for empty fuel tank, fuel leaks, or plugged
fuel lines and correct as required.
b.Check for dirty or plugged air filter and replace if
necessary (see Maintenance section).
c.Reset the tripped common fault circuit breaker and
restart after correcting the problem. Contact anauthorized service center for service if none of theabove.
3.Indicates engine has overheated (engine temperaturehas risen above 230down completely before proceeding with the followingchecks:
a.Check coolant level and replenish if low. Look for
possible coolant leakage points and repair if neces-sary.
b.Check for obstructions to cooling airflow and cor-
rect as necessary.
°F/110°C). Allow engine to cool
c.Check for a slipping fan belt and tighten if loose.
d.Reset the tripped common fault circuit breaker.
Contact an authorized service center for service if
none of the above.
6-2
Page 28
TABLE 6-1. TROUBLESHOOTING (continued)
Many troubleshooting procedures present hazards which can result in severe personal
injury or death. Only qualified service personnel with knowledge of fuels, electricity, and machinery
hazards should perform service procedures. Review safety precautions on pages iii and iv.
SYMPTOM
4.Engine shuts down due to low oil pres-sure. The Fault Shutdown is being indi-cated by the fault circuit breaker resetbutton (extended out).
5.The engine shuts down due to over-speed. The Fault Shutdown is being in-dicatedby the fault circuit breaker resetbutton (extended out).
6.The engine shuts down due to low cool-ant level. The Fault Shutdown is beingindicated by the fault circuit breaker re-set button (extended out).
7.The engine shuts down due any of fivefaults but remote monitor device doesnot detect fault.
CORRECTIVE ACTION
4.Indicates engine oil pressure has dropped to:GGHB − 14 psi (97 kPA)GGHC, GGHD − 25 psi (195 kPA)Check oil level, lines and filters. If oil system is OK butoil level is low, replenish. Reset the tripped commonfault circuit breaker. Contact an authorized servicecenter ifoil pressure is not in the range of 40 to 65 psi(276 to 449 kPa).
5.Indicates engine has exceeded normal operatingspeed. Contact an authorized service center for service.
6.Indicates low coolant level. Replenish coolant andlook for possible coolant leakage points and repair asrequired.
7.Indicates possible fault with control or external wiring.
8.Engine starts from generator controlpanel but will not start automatically orfrom a remote panel. (Note: The Run/Stop/Remote switch must be in the Re-mote position for automatic or remotestarting).
8.Remotecircuit breaker is tripped. Reset breaker andrestart. Contact an authorized service center ifbreaker trips after resetting.
6-3
Page 29
6-4
Page 30
7. Maintenance
GENERAL
Establish and adhere to a definite schedule formaintenance and service based on the applicationand severity of the environment. The table belowcovers the recommended service intervals for agenerator set on STANDBY service. If the set willbe subjected to extreme operating conditions, theservice intervals should be reduced accordingly.Some ofthe factors that can affect the maintenanceschedule are the following:
• Use for continuous duty (prime power)
• Extremes in ambient temperature
• Exposure to elements
• Exposure to salt water
• Exposure to windblown dust or sand.
Consult with an authorized Onan Distributor if the
generator set will be subjected to any extreme operating conditions and determine a suitable scheduleof maintenance. Use the running time meter tokeep an accurate log of all service performed forwarranty support. Perform all service at the timeperiod indicated or after the number of operatinghours indicted, whichever comes first. Use Table7-1 to determine the maintenance required andthen refer to the sections that follow for the correctservice procedures.
WARNING
performing maintenance procedures can causeserious personal injury ordeath. Place the Run-Stop-Remote switch in the Stop position,dis-connectbattery charger from its AC source anddisconnect the negative(-) battery cable fromthe battery terminal before beginning mainte-nance procedures.
Accidental starting of the set while
7-1
Page 31
TABLE 7-1. PERIODIC MAINTENANCE SCHEDULE
OPERATIONAL FREQUENCY - HOURS
MAINTENANCE ITEMS10100200Yearly
General Set Inspection.Check engine oil levelCheck radiator coolant levelCheck air cleaner (clean or replace as necessary)Check battery electrolyte levelCheck governor linkageChange engine oil and filter
Check all hardware (fittings, clamps, fasteners, etc.)Drain exhaust condensate trapAdjust drive belt tension
Inspect or replace spark plugsxInspect coolant hoses and clampsInspect coolant heater hoses
Check coolant anti-freeze protectionCheck AC generator and controlsClean cooling system
1
x
1
x
1
x
2
x
3
x
2
x
2
x
4
xx
5
x
6
x
6
xxx
x
x1-As noted or after every run.
2
-Perform more often in extremely dusty conditions
x
3
-Or every two weeks.
x
4
-Or every three months.
x
5
-Adjust to 1/2-inch (12.5 mm) depression between pulleys.
x
6
Replace if hard or brittle.
x
7-2
Page 32
GENERATOR SET INSPECTION
During operation, be alert for mechanical problems
that could create unsafe or hazardous conditions.
The following sections cover several areas that
should be frequently inspected for continued safe
operation.
Exhaust System
WARNING
personal injury or death by fire or explosion. Do
not permit any flame, cigarette, pilot light, arcing switch or equipment, or other ignition
source near the fuel system.
Ignition of fuel can cause severe
AC Electric System
Check the following while the generator set is oper-ating; otherwise measure load lines L1, L2 and L3using the appropriate AC meter.
With the generator set operating, inspect the entireexhaust system visually and audibly, including theexhaust manifold, muffler,and exhaust pipe. Checkfor leaks at all connections, welds, gaskets, andjoints and also make sure that exhaust pipes are notheatingsurrounding areas excessively.Ifany leaksare detected, shut down the generator set and haveleaks corrected immediately.
WARNING
sult inserious personal injury or death. Be suredeadly exhaust gas is piped outside and awayfrom windows, doors or other inlets to building.
Inhalation of exhaust gases can re-
Fuel System
With the generator set operating, inspect the fuelsupply lines, filters, and fittings for leaks. Check anyflexible sections for cuts, cracks and abrasions andmake sure they are not rubbing against anythingthat could cause breakage. If any leaks are de-tected, shut off fuel supply valves, shut down gener-ator set and have them corrected immediately.
Frequency Meter: The generator frequencyshould be stable and the reading should be thesame as the nameplate rating.
AC Voltmeter: Turn the phase selector switch toeach line-to-line phase selection shown onthe voltsscale (L1-L2, L2-L3, and L3-L1). Read the AC volt-meterusing the upper or lower scale as indicated bythe scale indicator light. At no load, the line-to-linevoltage(s)should be the same as the set nameplaterating.
AC Ammeter: Turn the phase selector switch toeach phase selection shown on the amps scale (L1,L2 and L3). Read the ammeter using the upper orlower scale as indicated by the scale indicator light.At no load, the current readings should be zero.With a load applied, each line current should beabout the same.
FaultLamps: Push the Reset/Lamp switch on thecontrol panel. All indicator lamps should light. Con-firm that all of the bulbs are on, then release theswitch. Have any bulbs that are burned out re-placed.
7-3
Page 33
DC Electrical System
Check the terminals on the battery for clean and
tight connections. Loose or corroded connections
create resistance which can hinder starting. Clean
and reconnect the battery cables if loose. Always
disconnect both ends of the negative battery cable.
Reconnect one end of the cable to the negative bat-tery terminal and the other end to ground. Followingthis sequence will help to reduce arcing at the bat-tery.
Make certain battery area has been well ventilated before servicing battery, especially if a
battery charger has been connected. Arcing
can ignite explosive hydrogen gas given off by
batteries, causing severe personal injury. Arcing can occur when cable is removed or re-attached, or when negative (−) battery cable isconnectedand a tool used to connect or discon-nectpositive (+) battery cable touches frame orother grounded metal part of the set.
CAUTION
Always disconnect a batterycharger from its AC source before disconnect-ing the battery cables. Otherwise, disconnect-ing the cables can result in voltage spikes highenough todamage the DC control circuits of theset.
WARNING
Accidental starting of the generatorset while working on it can cause severe per-sonal injury or death. Prevent accidental start-ing by disconnecting the starting battery cables(negative [−] first).
Mechanical
With the generator set stopped, check for loosebelts and fittings, leaking gaskets and hoses, or anysigns of mechanical damage. If any problems arefound, have them corrected immediately. With theset running, listen for any unusual noises that mayindicate mechanical problems and check the oilpressure frequently. Investigate anything that indi-cates possible mechanical problems.
7-4
Page 34
LUBRICATION SYSTEM
MODELS GGHC / GGHD
Before the initial start, check dipstick to be sure
crankcase is filled with oil. See Specifications sec-
tion for lubricating oil capacity.
Generatorsets are shipped with oil and coolant add-ed. Be sure to check these systems to make surethey are at proper operating levels before starting.
Oil Recommendations
Refer toFigure 5-1 for the recommended oil viscos-ity grades at various ambient temperatures. Oilsmust conform to the American Petroleum Institute(API) classification SH or SH/CD. When selectingthe oil viscosity, pick the grade that is right for thelowest temperature expected. Oil that is too thickcan result in a lack of lubrication when the engine isstarted. If the ambient temperature is consistentlybelow -13
°F (-25°C), use a SAE5W synthetic oil.
SAE 40
10W, 5W30
MODEL GGHB
SAE 30, 40
15W30
10W30, 10W40
5W30
FIGURE 5-1. OIL VISCOSITY
7-5
Page 35
Engine Oil Level
Check the engine oil level during engine shutdown
periods at the intervals specified in the Maintenance Table. The dipstick is stamped with FULL
and ADD to indicate the level of oil in the crankcase.
For accurate readings, shut off the engine and wait
approximately 10 minutes before checking the en-gine oil level. This allows oil in the upper portion ofthe engine to drain back into the crankcase.
Keep the oil level as near as possible to the FULLmark onthe dipstick. Remove the oil fill cap and addoil of the same quality and brand when necessary.
ENGINE OIL
LEVEL DIPSTICK
CAUTION
Do not operate the engine with the
oil level below the ADD mark or above the FULLmark. Overfilling can cause foaming or aerationof the oil. Operation below the ADD mark cancause loss of oil pressure.
Engine Oil Change
WARNING
termined that contact with used engine oil cancause cancer or reproductive toxicity.Take careto limit skin contact and the breathing of its va-pors. Use rubber gloves and wash exposedskin.
Run engine until thoroughly warm before drainingoil. Stop the set, place a pan under the drain outletand remove the oil drain plug or open the drainvalve. After the oil is completely drained, replacethe drain plug or close the drain valve. Refill with oilof the correct API viscosity grade for the tempera-ture conditions.
WARNING
it is spilled or splashed on skin. Keep fingersand hands clear when removing the oil drainplug and wear protective clothing.
State or federal agencies have de-
Hot crankcase oil can cause burns if
Oil Filter Change
FIGURE 7-2. OIL LEVEL DIPSTICK
FILTER
GASKET
FIGURE 7-3. ENGINE OIL FILTER
Spin offoil filter and discard it in accordance with lo-cal environmental regulations. Thoroughly clean fil-ter mounting surface. Apply a thin film of oil to filtergasket and install new element. Spin element on byhand until gasket just touches mounting pad andthen turn an additional 1/2 to 3/4 turn. Do not over-
tighten (Figure 7-3).
With oil in crankcase, start engine and check for
leaks around filter element. Retighten only as much
as necessary to eliminate leaks but do not overtighten.
7-6
Page 36
COOLING SYSTEM
The cooling system capacity of a standard unit with
set mounted radiator is shown in Specifications
section.
CAUTION
Never pour hot water into a cold engine or cold water into a hot engine. Doing so
can crack a head or cylinder block. Do not operate the generator set without water for even a
few minutes.
Generatorsets are shipped with oil and coolant add-ed. Be sure to check these systems to make surethey are at proper operating levels before starting.
Coolant Requirements
Satisfactoryengine coolant inhibits corrosion and ifnecessary protects against freezing. Use a 50/50coolant solution (50% pure water and 50% anti-freeze). If temperatures below -37
°F (-38°C) are
possible,use a mixture of 65% antifreeze and 35%water. Do not use an antifreeze that contains anti-leak additives.
The water used for engine coolant should be clean,low in mineral content and free of any corrosivechemicals such as chloride, sulfate or acid. Use softwater. Well water often contains lime and other ma-terials which eventually can clog the radiator coreand reduce the cooling efficiency and can alsocause heater element failure.
Filling the Cooling System
Check to make sure that all drain cocks are closedand all hose clamps secure. Remove the radiatorpressurecap and slowly fill the cooling system withthe recommended coolant.
When the engine is first started, remove the pressure cap and monitor the coolant level. As trappedair is expelled from the system, the coolant levelmay drop and additional coolant must be added.Replace the pressure cap when the coolant level isstable.
Coolant Level
Check the coolant level during shutdown periods atthe intervals shown in Table 7-1. Remove the radia-tor cap after allowing the engine to cool and if nec-essary, add coolant until the level is near the top ofthe radiator.
WARNING
in severe burns. Allow cooling system to coolbefore releasing pressure and removing radia-tor cap.
CAUTION
will shut down engine in an overheat conditiononly if coolant is sufficiently high to physicallycontact shutdown switch. Loss of coolant willallow engine to overheat without protection ofshutdown device and cause severe damage tothe engine. It is therefore imperative that ade-quate engine levels be maintained to provideoperational integrity of the cooling system andfor engine coolant overheat shutdown protec-tion.
Contact with hot coolant can result
High Engine Temperature Cutoff
7-7
Page 37
Draining and Flushing
WARNING
Some coolant is toxic. Keep away
from children and animals. Follow local environmental regulations for disposal.
To maintain adequate corrosion protection and remove rust and scale deposits, drain and flush radiator at the recommended interval.
CAUTION
The heater element will burn out ifengine coolant is removed with heater con-nected to power source.
Disconnect engine coolant heater from powersource (if equipped).
Allow the engine to cool and then remove radiatorpressurecap. Open the radiator drain cock and re-move the water drain plugs (one on each side of en-gine). When the coolant is drained, place the end ofa water hose into the radiator filler and turn on watersupply. Regulate the flow of water into the radiatoruntil it is equal to the outflow from drain openings.Continue flushing until outflow from drains is clearof rust sediment.
If engine is equipped with engine coolant heater,drain coolant by removing hose and clamp from bot-tom of heater.
Replace the water drain plugs and close the radia-tor drain cock when flushing is complete. Refill thecooling system with the recommended coolant (re-fer to Filling the Cooling System).
With cooling system properly filled and the enginehas been run, connect heater plug to receptacle.
DRAIN
DRAIN PLUG
(FAR SIDE)
FIGURE 7-4. DRAIN PLUG LOCATIONS
PLUG
7-8
Page 38
AIR FILTER
Remove wing nut in center of filter cover. Remove
cover and filter. Tap filter on a flat surface to remove
dirt. Place a light source inside filter and inspect for
air passage. If necessary, apply a low pressure air
source (30 psi) to the inside of filter to remove as
much dirt as possible. Inspect interior housing. Vac-uum clean if dirty or remove housing and wipeclean.
WING NUT
& PLASTIC
WASHER
COVER
CAUTION
Do not clean filter housing while stillinstalled.Loose dirt entering intake could dam-age carburetor or engine.
Clean air filter every 100 hours of operational time,more often in extremely dusty conditions. Replaceair filter after 500 hours of operational time.
FILTER
ELEMENT
FIGURE 7-5. AIR CLEANER (NATURALLY
ASPIRATED FUEL SYSTEM)
WING NUT& PLASTIC
WASHER
7-9
COVER
FILTER
ELEMENT
FIGURE 7-5. AIR CLEANER (TURBOCHARGED
FUEL SYSTEM)
Page 39
DRIVE BELT
A worn or improperly adjusted drive belt can cause
engine overheating and insufficient battery charging. Before inspecting or adjusting the drive belt,
disconnect the battery (negative [−] cable first) to
prevent accidental starting.
Check the drive belt at the recommended interval.Remove the belt guard and inspect the belt forcracks, fraying, or glazing. Replace when neces-sary.
ALTERNATOR
PULLEY
WATER PUMP
PULLEY
WARNING
Accidental starting can cause se-vere personal injury or death. To prevent acci-dental starting, place the Run/Stop/Remoteswitch in the Stop position and disconnect thenegative (−) battery cable from the battery be-fore working on the generator set.
Arcing can ignite battery gases and cause se-vere personal injury and can cause voltagespikes that can damage generator set controlcircuits. to reduce arcing:
Never disconnect the battery cables while thegenset is cranking or running.
Always disconnect a battery charger from itsAC source before disconnecting the batterycables.
Always disconnect the negative (−) cable firstand reconnect it last. (this prevents arcing if thetool on the positive terminal touches groundedmetal.)
To check belt tension, remove the belt guard andpush the fan belt midway between the two pulleysshown in Figure 7-6. Use a spring balance to mea-sure force (F) and a straight edge and ruler to mea-sure belt deflection (d). Belt deflection should be3/16 inch (4.8 mm) under a force of 5.0 pounds(22.0 N).
To adjust belt tension, loosen the two bolts on thebattery charging alternator and adjust until propertension is obtained. Recheck belt tension after ro-tating the engine so that the belt has travelled atleast once around the pulleys. Retighten the alter-nator bolts after adjustment, reinstall the belt guardand reconnect the battery (negative[−] cable last).
F
CRANKSHAFT
PULLEY
d
FIGURE 7-6. DRIVE BELT ADJUSTMENT
7-10
Page 40
IGNITION SYSTEM
The ignition system consists of the distributor,
ignition coil, high tension wires, spark plugs and
electronic control module. Maintenance consists of
periodic inspections to detect possible problems
and replacement of worn or deteriorated parts. The
ignition system must be completely functional or theset may run poorly or be unable to carry full load.Performthe following inspections at recommendedintervals.
Distributor Cap
Remove the distributor cap and inspect the insidefor cracks, burn marks, deterioration of the carbonbutton or eroded terminals. Replace the cap if anyof these conditions are noted.
Rotor
While the distributor cap is removed, inspect therotor for cracks, excessive burning of the tip,deteriorationof the center spring terminal. Replacethe rotor if any of these conditions are noted.
Spark Plugs
cations section. Clean all dirt and grit away from the
spark plug seats before installing plugs.
If the spark plugs show any of the following conditions, the engine may require additional service.
Contact your authorized service distributor for help.
•Carbon Fouled - Overly Rich Mixture
•Oil Fouled - High oil consumption
•Burned - Excessive engine temperature
High Tension Wires
Check the spark plug wires and coil wire for goodcontact at the coil, distributor cap and spark plugs.Terminal connections should be tight and fullyseated. All spark plug covers and cable end bootsshould be in good condition and fit tightly. Thereshould be nobreaks or cracks in the insulation. Re-place the wire if any of these conditions are noted.
CAUTION
if removed incorrectly from terminals. Graspwire by spark plug boot to prevent damage toconductor.
High tension wires can be damaged
Remove the spark plugs and inspect for damagedor cracked insulators, worn electrodes, damagedgasketsor excessive carbon deposits. Replace thespark plug if any of these conditions are noted.Clean those plugs that can be reused and regap(Figure 7-7) to the amount specified in the Specifi-
Ignition Coil
Clean the top of the ignition coil and check forcracks, carbon tracks or corrosion in the high ten-sion terminal hole. Replace the coil if any of theseconditions are noted.
FIGURE 7-7. GAPPING SPARK PLUGS
7-11
Page 41
BATTERY
Check the battery every month or at least every 100
operating hours. Add distilled water as necessary
and check specific gravity. Recharge the battery if
the specific gravity is less than 1.260. Clean and
tighten the battery terminals and cable connectors
and coat with Vaseline to retard corrosion.
WARNING
can cause severe personal injury. Do notsmoke. Wear goggles and protective, rubbergloves and apron when servicing batteries.
Ignition of explosive battery gases
tribute the oil on the cylinder walls and then replace the spark plugs.
7. Disconnect engine coolant heater from power
source (if equipped).
8. Drain the cooling system including the engine
block.
9.Removethe air cleaner and seal off the carbu-retor air inlet opening and PVC hose.
10.Plug theexhaust outlets to prevent entrance ofmoisture, bugs, dirt, etc.
OUT-OF-SERVICE PROTECTION
When the set will be stored or removed from opera-tion for an extended period of time, take the follow-ing precautions to prevent rust accumulation, corro-sion of bearing surfaces within the engine and gumformation in the fuel system. Perform the followingprocedures as outlined in this manual.
Preparing Set for Storage
1.Exercise the set as described in Operation sec-tion until the engine is up to operating tempera-ture.
2.Shut down the engine.
3.Turn off and disconnect battery charger (ifequipped).
4.Disconnect battery (negative [−] first) and storein a cool, dry place. Connect battery to chargerevery 30 days to maintain it at full charge.
5.Drain the engine oil while still warm and refillwith new oil recommended for set. Attach a tagindicating type of oil used.
6.Remove the spark plugs and pour two ouncesof rust preventative oil into each spark plugopening. Crank the set for five seconds to dis-
11.Clean and wipe entire unit. Coat parts suscepti-ble to rust with a light coat of oil. Cover entireset loosely after engine has cooled down.
Returning Set to Service
1.Remove protective cover.
2.Remove exhaust plugs, seal from carburetorand PVC hose and replace air cleaner.
3.Check oil dipstick to make sure crankcase isfull.
4.Refill cooling system.
5.Reconnect battery (positive [+] cable first) andcheck specific gravity.
6.Connect the battery charger (if applicable).
7.Connect engine coolant heater to power supply(if applicable).
8Remove all loads before starting set.
9.Start set and apply load of at least 50% ofnameplate rating.
10.Check all gauges for normal readings. Set isnow ready for service.
7-12
Page 42
8. Adjustments
OUTPUT VOLTAGE ADJUSTMENT
Output voltage can be adjusted plus or minus fivepercent of nominal voltage by the Voltage Adjustrheostat (optional) on the control panel (Figure3-3).Call your distributor if the required voltage can-not be obtained by this adjustment.
FUEL SYSTEM ADJUSTMENTS
The engine is equipped with a gas mixer to run onnatural gas or propane or both.
WARNING
cause severe personal injury and property dam-age. Do not allow cigarettes, flame, pilot lights,archingswitches or equipment in area or areassharing ventilation.
PRESSURE
SOLENOID
VALVE
Fuel is highly flammable and may
SWITCH
SOLENOID
VALVE
Gaseous and Combination Fuel Systems
An engine equipped for natural gas and propanehas a gas mixer that serves both fuels. Each fuelhas a separate shutoff solenoid valve and a fuelpressure switch for automatic fuel changeover.(While the engine is running, the gas pressureswitch causes the natural gas solenoid valve toclose and the propane solenoid valve to open whennatural gas pressure is lost, without stopping theengine.When natural gas pressure is restored, thenatural gas solenoid valve opens and the propanesolenoid valve closes.)
GAS MIXER
NATURAL GAS
REGULATOR
PROPANE
REGULATOR
FIGURE 8-1. NATURAL GAS AND LPG VAPOR FUEL SYSTEM (NATURALLY ASPIRATED)
8-1
Page 43
Gaseous Fuel Adjustments: Gas mixers have a
power adjust valve and an idle adjustment screw
(Figures 8-2 and 8-3). Engines equipped for natural
gas and propane (dual fuel) also have a propane
flow adjustment valve. If necessary, make the following adjustments.
1.Start the engine and let the set warm up undera partial load (at least 1/4 rated load). If the en-gine is equipped for natural gas and propane,start with natural gas.
GAS MIXER
Step 2 is only required if genset instability ispresent at no−load through 1/4 of rated load.
2.Disconnect all loads, shut down the set, con-nect a tachometer and disconnect the gover-nor linkage at the carburetor. Start the engineand close and hold the throttle by hand so thatthe engine does not overspeed. While holdingthe throttle closed, adjust the throttle idle posi-tionscrew (the one next to the throttle lever) toobtain anengine speed of 800 RPM. Then turnthe idle adjusting screw counterclockwise untilengine speed becomes unstable. Turn thescrew clockwise just enough to regain stabilityand reconnect the governor linkage.
3.Next, connect full rated load and turn the poweradjust valve to full−rich. Slowly turn the adjustvalve towards lean until the engine begins tolose speed and then slowly back towards richuntil the engine carries the full load smoothly.
4.If the set is equipped for natural gas and pro-pane,switch to propane by closing the manualshutoff valve in the natural gas supply line.
5.Reconnect full rated load and turn the propaneflow adjustment valve clockwise until the en-gine begins to lose speed and then slowly turnit back counterclockwise until the engine car-ries full load smoothly.
Drain and replace the crankcase oil after the first 50hours of operation on new generator sets. Refer tothe Maintenance section of this manual for the rec-ommended procedures.
NO-LOAD OPERATION
Periods of no load operation should be held to aminimum. If it is necessary to keep the engine run-ning for long periods of time when no electric outputis required, best engine performance will be ob-tained by connecting a “dummy” electrical load(50% ormore of set rate). Such a load could consistof heater element or load bank.
EXERCISE PERIOD
Generatorsets on continuous standby must be ableto go from a cold start to being fully operational in amatter of seconds. This can impose a severe bur-den on engine parts.
Regular exercising keeps engine parts lubricated,preventsoxidation of electrical contacts and in gen-eralhelps provide reliable engine starting. Exercise
the generator set at least once a week for a minimum of 30 minutes with load (50% or more of set
rate) so the engine reaches normal operating tem-peratures.
LOW OPERATING TEMPERATURES
Use a coolant heater if a separate source of poweris available. The optional heater available fromOnan will help provide reliable starting under ad-verse weather conditions. Be sure the voltage of theseparate power source is correct for the heater ele-ment rating.
CAUTION
the cooling system is full before applying powerto the heater.
To avoid damage to heater, be sure
POWER RATING FACTORS
The generator set power rating applies to sets usedin standby applications. The set will operate at thestatedrating for the duration of normal utility powerinterruptions. The ratings were established for astandard radiator cooled set operating at an altitudeof 300 feet (92 m) with an ambient temperature of81
°F (27°C). For a rating relative to other applica-
tions, altitudes, cooling systems, or ambient tem-peratures, contact your authorized distributor.
9-1
Page 47
9-2
Page 48
Cummins Power Generation
1400 73rd Avenue N.E.
Minneapolis, MN 55432
1-800-888-6626
763-574-5000 International Use
Fax: 763-528-7229
Cummins is a registered trademark of Cummins Inc.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.